Siemens 7SL8x V7.80 Line PTT User Manual ENU
Siemens 7SL8x V7.80 Line PTT User Manual ENU
Siemens 7SL8x V7.80 Line PTT User Manual ENU
OMICRON PTL
User Manual
V2.000
Content
1. General ...................................................................................................................................................3
1.1 Supported Relays .................................................................................................................................3
2. Test Universe-Based Testing ...............................................................................................................4
2.1 Software and Hardware Requirements ................................................................................................4
2.2 Hardware ..............................................................................................................................................4
2.3 Functional Range .................................................................................................................................5
2.4 XRIO Converter ....................................................................................................................................6
2.4.1 Diff Topology ..................................................................................................................................6
2.4.2 Additional Information .....................................................................................................................6
2.5 Specific Protection Test ........................................................................................................................7
2.5.1 Line Differential Protection .............................................................................................................7
3. RelaySimTest-Based Testing ...............................................................................................................8
3.1 Software and Hardware Requirements ................................................................................................8
3.2 Test Set Configurations ........................................................................................................................8
3.3 Functional Range .................................................................................................................................9
3.4 Power System Data ........................................................................................................................... 10
3.5 Automatic Reclosing Function ........................................................................................................... 11
3.5.1 General Test Case Settings ........................................................................................................ 11
3.5.2 AR with 1 Cycle ........................................................................................................................... 11
3.5.3 AR with 2 Cycles ......................................................................................................................... 11
3.5.4 AR with Distance Cross-Check ................................................................................................... 11
3.6 Teleprotection with Distance Protection ............................................................................................ 12
1. General
This user manual describes details of testing Siemens 7SL8x relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.
General protection functions are tested with Test Universe (chapter 2). The RelaySimTest
templates provide tests for additional functions (chapter 3).
Any CMC test set can be used with this Protection Test Template. In addition, a CMGPS 588 is
necessary.
2.2 Hardware
There are multiple possibilities of wiring a 7SL8x relay to a CMC test set. The advised connections are
shown in Figure 1. These connections are the default settings in the Hardware Configuration of the PTT.
Please note that in case of 3-pole-tripping application, the binary inputs Trip A, Trip B and Trip C should
be connected parallel.
VC
VN
VA
VB
IN
IC
IA
IB
CB aux C (52b)
CB aux A (52b)
CB aux B (52b)
Manual close
Trip A
Trip B
Start
Trip C
Although the functions listed above are not supported by the Protection Test Template, the
Relay Parameter Section of the XRIO Converter includes most protection parameters of the relay.
A fault outside the protection area located at side 2 followed by a fault outside the protection area located
at side 1 is simulated. Both relays must not send a trip signal during the tests.
Please check and adjust the test points to fit your application. Please make sure, that the same test points
are used in the corresponding test modules for both relays.
3. RelaySimTest-Based Testing
Supported functions:
• Automatic reclosing, 1-/3-pole, with distance zone Z1B or differential protection
o 1 cycle
o 2 cycles
• Teleprotection with distance protection (PUTT, POTT, Blocking)
Important: The Iterative Closed-Loop simulation method of RelaySimTest is used for testing the AR
function. Further information can be found in the RelaySimTest help.
The following parameters have to be entered in the test case view for the teleprotection test cases:
The teleprotection with distance protection function is tested with significant faults at the following
locations:
• Busbar 1
• Busbar 2
• Line, 0%
• Line, 50%
• Line, 100%
The trip signals and the send signal of the relay are measured and assessed according to the expected
relay behavior of the teleprotection mode.
Important: The Iterative Closed-Loop simulation method of RelaySimTest is disabled for testing the
teleprotection function. With Iterative Closed-Loop enabled, please adjust the trip time assessments for
the “Fault on Busbar” test cases according to your application (iterative tripping of relay 1 and relay 2
possible). Further information about Iterative Closed-Loop can be found in the RelaySimTest help.