Drive Error Codes

This document provides information about reading error codes, operational values, and parameters from a PowerFlex 520 drive using the RS485 (DSI) protocol. Error codes can be read from register address 2101H. Operational values like frequency, current, and voltage can be read from registers 2102H through 210AH. Drive parameters can be accessed using their parameter number as the register address. Additional documentation is available online.

Uploaded by

Antonio Vargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views2 pages

Drive Error Codes

This document provides information about reading error codes, operational values, and parameters from a PowerFlex 520 drive using the RS485 (DSI) protocol. Error codes can be read from register address 2101H. Operational values like frequency, current, and voltage can be read from registers 2102H through 210AH. Drive parameters can be accessed using their parameter number as the register address. Additional documentation is available online.

Uploaded by

Antonio Vargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Appendix C RS485 (DSI) Protocol

Reading (03) Drive Error The PowerFlex 520-series Error Code data can be read through the network by
Codes sending Function Code 03 reads to register address 2101H (Drive Error Codes).
Drive Error Codes
Logic Status
Address (Decimal) Value (Decimal) Description
0 No Fault
2 Auxiliary Input
3 Power Loss
4 Undervoltage
5 Overvoltage
6 Motor Stalled
7 Motor Overload
8 Heatsink Overtemperature
9 Control Module Overtemperature
12 HW Overcurrent (300%)
13 Ground Fault
15 Load Loss
21 Output Phase Loss
29 Analog Input Loss
33 Auto Restart Tries
38 Phase U to Ground Short
39 Phase V to Ground Short
40 Phase W to Ground Short
41 Phase UV Short
42 Phase UW Short
43 Phase VW Short
48 Parameters Defaulted
2101H (8449) 59 Safety Open
63 Software Overcurrent
64 Drive Overload
70 Power Unit Fail
71 DSI Network Loss
72 Option Card Network Loss
73 Embedded EtherNet/IP Adapter Network Loss
80 AutoTune Fail
81 DSI Communication Loss
82 Option Card Communication Loss
83 Embedded EtherNet/IP Adapter Communication Loss
91 Encoder Loss
94 Function Loss
100 Parameter Checksum Error
101 External Storage
105 Control Module Connect Error
106 Incompatible Control-Power Module
107 Unrecognized Control-Power Module
109 Mismatched Control-Power Module
110 Keypad Membrane
111 Safety Hardware
114 Microprocessor Failure
122 I/O Board Fail
125 Flash Update Required
2101H (8449) 126 Non Recoverable Error
127 DSI Flash Update Required

Rockwell Automation Publication 520-UM001K-EN-E - August 2021 209


Appendix C RS485 (DSI) Protocol

Reading (03) Drive The PowerFlex 520-series Drive Operational Values can be read through the
Operational Values network by sending Function Code 03 reads to register addresses
2102H...210AH.
Drive Operational Values
Reference
Address (Decimal) Description
2102H (8450) Frequency Command (xxx.xx Hz)
2103H (8451) Output Frequency (xxx.xx Hz)
2104H (8452) Output Current (xxx.xx A)
2105H (8453) DC-BUS Voltage (xxxV)
2106H (8454) Output Voltage (xxx.xV)

Reading (03) and Writing To access drive parameters, the Modbus register address equals the parameter
(06) Drive Parameters number. For example, a decimal “1” is used to address Parameter b001 [Output
Freq] and decimal “41” is used to address Parameter P041 [Accel Time 1].

Additional Information See https://www.ab.com/drives for additional information.