Specification Sheet schneider-electric.

com | 1

SmartX Living Space Sensors

Product Description
SmartX sensors are a family of living space sensors for use SmartX living space sensors measure the levels of CO2 (if
with SmartX IP controllers that use the EcoStruxure Building equipped), RH (if equipped), and temperature of air in a living
Operation user interface. These sensors use an RJ-45 sensor space application. The CO2 sensor operates within accuracy
bus that provides communication and power from the SmartX specifications for an interval of two years and can be field
IP controller. For quick installation, up to four SmartX sensors calibrated. The RH and temperature sensors are warranted to
may be connected to each SmartX IP controller through the meet accuracy specifications for a period of two years.
RJ-45 sensor bus using Cat 5/6 cable (22 to 26 AWG). A Blue-
tooth® adapter is available for commissioning and service. It is Features
temporarily connected to installed communicating sensors and • Contemporary, sleek housing
allows for quick setup and configuration. The Bluetooth adapter • 61 mm (2.4”) backlit color touchscreen cover available
communicates to upload devices (smart phone, laptop, table, • LCD (SXWSATXXXSLX only)
etc.) with the Living Space Sensor EcoStruxure Building Opera- • Digital temperature indication (selectable for 0.1 or
tion app installed via USB or Bluetooth communications. 1 degree display resolution of °F or °C).
SmartX living space sensors are modular and are ordered in • Digital humidity indication (selectable for 0.1 or 1% RH
two parts: the sensor base and the cover. Four SmartX commu- display resolution)
nicating sensor base models are available that can be paired • Long-life humidity sensing element with excellent
with any one of six covers. CO2, Relative Humidity, and Tem- resistance to contamination and condensation
perature sensor base options provide an efficient, cost effective • Digital CO2 indication (0-2000 ppm display resolution)
solution for living space air quality and comfort needs. Covers • Field calibratable non-dispersive infrared CO2 sensor
are available with a 61 mm (2.4”) backlit color touchscreen and • Pushbutton override capabilities allow occupants to switch
a three button non-display version for override and setpoint. to timed occupied mode for after hours operation
Blank covers with no user interface are also available. All • Displays selected system values such as setpoints,
modular cover variants are available with and without passive outdoor air temperature, and operating mode
infrared occupancy sensors. • Provides the ability to change operating modes
Two complete sensor/cover combination models are available: • Passive Infrared (PIR) occupancy sensor covers available
• Directly connects to the sensor bus of the MP Series
• SXWSATXXXSLX - Temperature-only with LCD display.
controller with EcoStruxure Building Operation software
Communicating with three button cover. This is a low cost
version 2.0
temperature sensor with a basic display.
• Sensor bus provides power and communication via RJ-45
• SXWSATXXXRXX - A two-wire, resistive-only, non-com- over Cat 5/6 cable (22 to 26 AWG)
municating temperature sensor is offered for a low cost
conformance part. This uses an I/O port on the controller.
Combination models come with a sensor base and cover and
have the same form factor as the modular sensor bases and
covers. Combination units will not work with other covers.

USA: +1 888-444-1311
Europe: +46 10 478 2000
Asia: +65 6484 7877
www.schneider-electric.com

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018
F-28082-2 nk

SmartX Specification Sheet schneider-electric.com | 2

Specifications Dimensions mm (in.)


CO2 Sensor
Non-dispersive infrared (NDIR), diffusion
Sensor type
sampling
Output range 0 to 2000 ppm
Accuracy ±30 ppm ±2% of measured value
Repeatability ±20 ppm ±1% of measured value
115
Response time <60 seconds for 90% step change (4.5)

RH Sensor
HS sensor Thin-film capacitive
Accuracy ±2% from 10 to 80% RH @ 25°C (77 °F)
Hysteresis 1.5% typical
Linearity Included in accuracy specification
85 24
Stability ±1% @ 20°C (68 °F) annually for 2 years (3.3) (0.9)

Output range 0 to 100% RH


±0.1% RH/°C above or below 25 °C (77 °F)
Temperature coefficient
typical
Temperature Sensor (Non-communicating Models)
Sensor type 10K Type 3 thermistor
Accuracy ±0.2 °C (±0.4 °F) typical

Resolution 0.1 °C (0.2 °F)


Output range 0 to 50 °C (32 to 122 °F)
Temperature Sensor (Communicating Models)
Accuracy ±0.2 °C (±0.4 °F) typical

Occupancy Sensor
Sensor type Passive infrared (PIR)
Operating Environment
Operating temperature 0 to 50 °C (32 to 122 °F) Software Specifications
Operating humidity Using the eCommission Bluetooth Adapter to Configure
0 to 95% RH, non-condensing
range

Housing material
High impact ABS plastic • Custom field-configurable sensor displays
Flammability rating UL 94 V-0 • Auto-ranging of displayed values
Input power 2 watts, 24 Vdc over sensor bus • Occupant command capabilities
Wiring Terminals • Adjustable minimum/maximum limit setpoint values
Non-communicating • Controller driven, automatically configured, customized
Screw, 2-wire, 18-24 AWG display/command values
models
Communicating models RJ-45 female sensor bus
Communications
Regulatory Information SmartX Sensor Bus
UL 916, European conformance CE:
EN61000-6-3
SmartX sensor bus communications wiring provides power and
EN61000 Series - industrial immunity communication interface to the SmartX MP-X Series control-
Agency approvals standard lers. SmartX sensor bus connects up to four sensor devices per
FCC Part 15 Class B, REACH, RoHS, controller using RJ-45 connectors and Cat 5/6 cable (22 to 26
Green Premium, RCM (Australia), ICES-003 AWG)*. The maximum total length of the SmartX sensor bus is
(Canada), EAC (Russia)
61 m (200 ft.).
*Due to power constraints there are some limitations on the number of sensors
the Sensor Bus can support. For specific sensor combinations supported, see the
Sensor Bus Configuration Calculator on the last page of this document.

USA: +1 888-444-1311
Europe: +46 10 478 2000
Asia: +65 6484 7877
www.schneider-electric.com

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018
F-28082-2 nk

SmartX Specification Sheet schneider-electric.com | 3

Available Products
SmartX Sensor Bases
SmartX Resistive Only
Model Number Temp RH CO2 Cover System Bus (10K T3)
SXWSBTXXXSXX X Not Included X
SXWSBTHXXSXX X X Not Included X
SXWSBTXCXSXX X X Not Included X
SXWSBTHCXSXX X X X Not Included X
SXWSATXXXSLX X Included X
SXWSATXXXRXX X Included X

SmartX Covers
61 mm (2.4”) Occupancy Sensor
Model Number Color Touchscreen Override Setpoint (PIR)
SXWSCDXSELXX X X X
SXWSC3XSELXX X X
SXWSCBXSELXX
SXWSCDPSELXX X X X X
SXWSC3PSELXX X X X
SXWSCBPSELXX X

Sensor and Cover Combination Models


Communicating Temperature Only User Interface with LCD

• Configurable through the eCommission Bluetooth Adapter or EcoStruxure Building Operation


software
Display
Example • LCD displays temperature, heating, cooling status
• Setpoint and override

SXWSATXXXSLX

Non-communicating Temperature Only, No User Interface

• 2-wire resistive output


• 10K Type 3 thermistor
• Uses I/O port on controller

SXWSATXXXRXX

USA: +1 888-444-1311
Europe: +46 10 478 2000
Asia: +65 6484 7877
www.schneider-electric.com

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018
F-28082-2 nk

SmartX Specification Sheet schneider-electric.com | 4

Cover Variants - Communicating Sensors


Blank, No User Interface
• Configurable through the eCommission Bluetooth Adapter or EcoStruxure Building
Operation software
• Occupancy sensor version available

SXWSCBXSELXX SXWSCBPSELXX
with Occupancy
Sensor

3-Button User Interface, Setpoint and Override


• Configurable through the eCommission Bluetooth Adapter or EcoStruxure Building
Operation software
• Setpoint and override buttons
• Halo indicates heating and cooling status
• Occupancy sensor version available

SXWSC3XSELXX SXWSC3PSELXX
with Occupancy
Sensor

Touch Screen User Interface


• Configurable through the eCommission Bluetooth Adapter or EcoStruxure Building
Operation software
• 61 mm (2.4”) color touchscreen
• CO2, RH, temperature, setpont and override displayed
• Heating, cooling, ecomode status
• Occupancy sensor version available

SXWSCDXSELXX SXWSCDPSELXX
with Occupancy
Sensor

Ecomode Heating Cooling Regular State


Example Example Example Example

9:00 AM 9:00 AM 9:00 AM 9:00 AM


74° 65°

69.5 69.5 69.5 69.5


°F °F °F °F

65% 550 65% 550 65% 550 65% 550

USA: +1 888-444-1311
Europe: +46 10 478 2000
Asia: +65 6484 7877
www.schneider-electric.com

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018
F-28082-2 nk

SmartX Specification Sheet schneider-electric.com | 5

Architecture
MP-X Controller and Sensor Bus with Communicating Sensors
MP-X Controller

SmartX Communicating Sensors

Cat 5/6 cable (22 to 26 AWG) terminated via RJ-45.


61 m (200 ft.) total maximum length.
Up to four communicating sensors on sensor bus. For specific combinations of sensors supported by
the Sensor Bus, see the Sensor Bus Configuration Calculator on the last page of this document.

MP-X Controller and Non-communicating Sensors


MP-X Controller
SXWSATXXXRXX Temperature-only Sensors

Each sensor uses an I/O port on the controller.


Maximum number of inputs varies by controller type.

USA: +1 888-444-1311
Europe: +46 10 478 2000
Asia: +65 6484 7877
www.schneider-electric.com

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018
F-28082-2 nk

SmartX Specification Sheet schneider-electric.com | 6

Sensor Bus Configuration Calculator


Calculate Power/mW to Validate Sensor Bus Configuration
Add power/mW for all covers, combination units and bases to
be used on a single sensor bus for total sensor bus wattage.
The sensor bus will support current of up to 2000 mW. Device
combinations totalling more than 2000 mW will not be sup-
ported on the sensor bus.

Sensor Bus Power Table

Description Model Number Power/mW


Sensor Base, Temperature SXWSBTXXXSXX 90
Sensor Base, Temperature, Humidity SXWSBTHXXSXX 90
Sensor Base, Temperature, CO2 SXWSBTXCXSXX 490
Sensor Base, Temperature, Humidity, CO2 SXWSBTHCXSXX 490
Sensor, Temp, LCD, Setpoint, Pushbutton Operation with Cover Plate SXWSATXXXSLX 80
Sensor, Temp, 10K T3, Non-communicating, with Cover Plate SXWSATXXXRXX 0
Cover Plate, Blank Cover SXWSCBXSELXX 0
Cover Plate, User Interface, Basic SXWSCDXSELXX 190
Cover Plate, Override, Setpoint SXWSC3XSELXX 190
Cover Plate, User Interface, Basic, Occupancy SXWSCDPSELXX 210
Cover Plate, Override, Setpoint, Occupancy SXWSC3PSELXX 210
Cover Plate, Blank Cover, Occupancy SXWSCBPSELXX 20
eCommission Bluetooth Adapter SXWBTAECXX10001* 300

*The eCommission Bluetooth Adapter is used temporarily for commissioning and servicing only.

Key Combinations
• Blank covers:
–– Up to four of any combination of sensor base types
• 3-button and touchscreen covers:
–– Up to two sensor bases with CO2
–– Up to four non-CO2 sensor bases
• LCD temperature combination sensors:
–– Up to four are supported

USA: +1 888-444-1311
Europe: +46 10 478 2000
Asia: +65 6484 7877
www.schneider-electric.com

© 2018 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March 2018
F-28082-2 nk