Edoc-Experiences Battery Capacity Testing
Edoc-Experiences Battery Capacity Testing
Experiences
Introduction
In case of emergencies, it is essential that the battery systems perform as designed, or the
substation may be left unprotected. Although many test methods can be performed to estimate
the condition of the battery, the capacity test at specific time intervals and discharge rates is
presented as the only method that can measure the real capacity of the battery. Nowadays the
capacity test is not performed because of the belief that this type of test is too expensive, and
damages the battery. Most battery users today apply the internal resistance measurements in
order to determine the battery state of health and save time. This approach is not wrong.
However, the real capacity cannot be decided from this test.
Before the test starts, it is important to visually inspect the cell connections are in proper
condition as well as the charger has been disconnected. The load connected to the battery needs
to be adequately backed up, or the current taken by the load needs to be included in the discharge
rate. It is important to emphasize the test preparation and conditions before its start can affect the
test results. Having that in mind, it is important to check the key parameters such as the cell
voltage, float voltage, and cell temperature before the test starts. Once the initial conditions are
met, the load may be connected.
In battery capacity tests, there are some facts that are misunderstood. Mistakes are made as a
result of myths, misunderstandings, and lack of training and experience.
The effect of the performance test on a battery was analyzed on the Powerfit S312/7S battery.
The test was performed with a higher discharge rate and reduced test time. The graph in Figure 1
illustrates the test results collected from the battery with the manufacturer declared five years of
service. After being subjected to five discharge tests, the voltage values and the capacity levels at
the last test were unchanged compared to the results of the first test, even the voltage in the last
test was a bit higher than the voltage in the first test. This confirms that five discharge cycles (as
recommended by standards) will not ruin the battery.
Figure 1 – Measured battery voltage as a function of time in five discharge tests on Powerfit
S312/7S
Myth 3 – Stop the Test When the First Cell Reaches Cell-End
Voltage
During the capacity test, it is not uncommon for a cell or a few of them to fail before the end of
the test. Terminating a test as soon as the first cell fails may result in incomplete or wrong test
results. The total string voltage should be used as terminating criteria as shown in Figure 2.
Figure 2 – Total string voltage on the battery that needs to be replaced
However, a test person should bypass a weak cell except the test has run 90-95% of its course.
Terminating the test when one cell reaches end voltage will not allow us to find other damaged
cells. The detection of the two weak cells is presented in Figure 3.
Test Process
Once the initial conditions are met, the load and other necessary test equipment need to be
connected and setup. The first step is to define the test current, end voltage, and the test duration.
These parameters in our test are found in the manufacturer’s published recommendations. The
battery installation used for testing had 126 cells and the string voltage of 252 V.
The load unit (BLU200A) along with extra load unit (BXL-A) was used to increase loading
capability. The test current is chosen from Table 1.
The terminal voltage was measured during the entire test as a function of time, and the battery
should be discharged until it reaches the minimum terminal voltage, or once the total test time
has been reached.
Figure 4 – String voltage as a function of time
During the discharge test, it is important to monitor cell voltages at least three times during the
test. One measurement should be taken at the beginning of the test and the others at specified
intervals. The sample rate should be more frequent when the voltage starts to decrease faster.
Individual cell voltages can be measured manually or using an automated monitoring system.
Voltages in this particular test were measured using the Battery Voltage Recorder (BVR device)
and the voltage value of each cell is illustrated in Figure 6.
In the time adjusted method, the test current is kept constant as defined in the manufacturer’s
published table as a function of the selected test time duration. The battery capacity is calculated
after the completion of the test by using the published performance data at 20 ̊ C.
C – Capacity at 20 ̊ C.
Ta – Actual time duration of the test.
Tm – Manufacturer’s rated time to reach the string end voltage
Kt – Temperature correction factor (in our case 1.045)
Replacement Criteria
The recommended practice is to replace the battery if its capacity is below 80% of the
manufacturer rating. Following the test, it is necessary to review the battery sizing to conclude if
the remaining capacity is sufficient for the battery to perform the intended function. A capacity
of 80% indicates the battery (cell or string) rate of deterioration is increasing even there is still a
capability to support the load. Additional characteristics such as abnormality of the cell
temperature and the cell voltage are often determinants for complete battery or cell replacements.
The cell voltage is a good indicator for further investigation and cell replacement. In case we use
replacement cells, it is important to ensure they have electrical characteristics compatible with
the existing cells and they should be tested before installation.
To download .pdf format of this article, please log in and visit the following link. Literature and
copyrights are stated in the original document.