Is 516 (Part-2 Sec-IV) - 2021 Determination of The Carbonation Resistance by Accelerated Carbonation Method

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -

Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

भारतीय मानक IS 516 (Part 2/Sec 4) : 2021


Indian Standard

दृढ़ीकृत कंक्रीट — परीक्षण पद्धतियाँ


भाग 2 बल सामर्थ्य के अतिरिक्त
दृढ़ीकृत कंक्रीट के अन्य गुण
खण्ड 4 त्वरित कार्बनीकरण पद्धति द्वारा
कार्बनीकरण प्रतिरोध ज्ञात करना
(  पहला पनु रीक्षण )

Hardened Concrete —
Methods of Test
Part 2 Properties of Hardened Concrete
other than Strength
Section 4 Determination of the
Carbonation Resistance by Accelerated
Carbonation Method

( First Revision )

ICS 91.100.30

© BIS 2021

भारतीय मानक ब्रयू ो


B U R E A U O F I N D I A N S TA N D A R D S
मानक भवन, 9 बहादरु शाह ज़फर मार्ग, नई िदल्ली – 110002
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI-110002
         www.bis.gov.in  
www.standardsbis.in

March 2021  Price Group 7


Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

Cement and Concrete Sectional Committee, CED 02

FOREWORD
This Indian Standard (Part 2/Section 4) (First Revision) was adopted by the Bureau of Indian Standards, after the
draft finalized by the Cement and Concrete Sectional Committee had been approved by the Civil Engineering
Division Council.
Testing plays an important role in controlling the quality of cement concrete work. Systematic testing of raw
materials, fresh concrete and hardened concrete, is an inseparable part of any quality control programme for
concrete. This helps achieve a higher efficiency of the materials used and greater assurance of the performance of
the concrete, in regard to workability, strength and durability. The test methods used should be simple, direct and
convenient to apply. This standard was formulated with this objective in view.
This standard was first published in 1959. In this revision, it was decided to review and update the various existing
test methods of concrete taking into consideration the latest international practices and developments in this field
in the country, and also to introduce certain new test methods wherever required. In the process, the various
existing test methods covered in IS 516 : 1959 ‘Methods of tests for strength of concrete’ have been revised taking
into consideration primarily the corresponding ISO standards while also examining the other best practices world
over and in the country. In addition, test methods for determination of additional properties have been included in
areas such as permeability, initial surface absorption, corrosion of reinforcement, carbonation of concrete (field
test), accelerated carbonation test, and creep of concrete. Also, for better understanding and implementation, some
of the other test methods which were spread over in number of other Indian standards have been brought together
under the fold of IS 516 as its various parts, such as the splitting tensile strength, ultrasonic pulse velocity test,
rebound hammer test, bond in reinforced concrete, and determination of water soluble and acid soluble chlorides.
This is with a view to making the standard complete in all respects, and rendering it a comprehensive source of
provisions for testing of concrete and reference in other Indian Standards.
In this revision, IS 516 is split into 12 parts. The other parts in the series are:
Part 1 Determination of strength of hardened concrete
Part 3 Making, curing and determining compressive strength of accelerated cured concrete test
specimens
Part 4 Sampling, preparing and testing of concrete cores
Part 5 Non-destructive testing of hardened concrete
Part 6 Determination of drying shrinkage and moisture movement of concrete samples
Part 7 Determination of creep of concrete cylinders in compression
Part 8 Determination of modulus of elasticity
Part 9 Determination of wear resistance
Part 10 Determination of bond in reinforced concrete
Part 11 Determination of Portland cement of hardened hydraulic cement concrete
Part 12 Determination of water soluble and acid soluble chlorides in hardened mortar and concrete

This standard (Part 2/Section 4) covers the procedure for measurement of carbonation depth by accelerated
carbonation test. This is a new test method included in the IS 516 series.
After a period of preconditioning, this test is carried out under controlled exposure conditions using an increased
level of carbon dioxide to which the vertical sides of the specimen are exposed. The test results are designed
to compare the carbonation resistance of similar concretes, which may be used in the same environmental
conditions.

(Continued to third cover)


Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

Indian Standard
HARDENED CONCRETE — METHODS OF TEST
PART 2 PROPERTIES OF HARDENED CONCRETE OTHER THAN STRENGTH
Section 4 Determination of the Carbonation Resistance
by Accelerated Carbonation Method

( First Revision )

1 SCOPE 3 TERMINOLOGY
This standard (Part 2/Sec 4) lays down a procedure For the purpose of this standard, the following terms
for evaluating the carbonation resistance of concrete and definitions apply.
using an accelerated carbonation test. After a period of
preconditioning, the test is carried out under controlled 3.1 Depth of Carbonation — Depth as measured
using a phenolphthalein solution sprayed on a
exposure conditions using an increased level of carbon
freshly-split concrete surface.
dioxide to which, the vertical sides of the specimen are
exposed. 3.2 Single Point Carbonation Depth — Depth of
The test results are designed to compare the carbonation carbonation measured at a single point on a specimen,
resistance of similar concretes, which may be used in dk, point.
the same environmental conditions. 3.3 Specimen Face Carbonation Depth — Mean
depth of carbonation of a single exposed face of a
2 REFERENCES
single specimen, dk, face.
The standards listed below contain provisions, which
through reference in this text, constitute provisions of 3.4 Specimen Carbonation Depth — Mean depth of
this standard. At the time of publication, the editions carbonation of a single specimen, dk, spec.
indicated were valid. All standards are subject to 3.5 Mean Carbonation Depth — Mean depth of
revision and parties to agreements based on this carbonation of two specimens, dk.
standard are encouraged to investigate the possibility
of applying the most recent edition of the standards 4 PRINCIPLE
indicated below:
Two concrete cubes are cast and cured for
28 days in accordance with IS 1199 (Part 5). The two
IS No. Title
concrete cubes are then conditioned in a laboratory
516 Hardened concrete — Methods of air environment for 14 days prior to sealing the top,
test bottom, and two opposite side faces. After sealing of all
  (Part 1/Sec 1) Testing of strength of hardened but two faces, the cubes are placed in a storage chamber
: 2020 concrete, Section 1 Compressive, meeting the conditions specified in 5.4 and having a
flexural and split tensile strength carbon dioxide level of 3.0 ± 0.5 percent for a period of
(first revision) 70 days. After 70 days of exposure, the cubes shall be
split in half, perpendicular to the exposed faces, and the
  (Part 5/Sec 3) Non-destructive testing of depth of carbonation measured in accordance with the
: 2019 hardened concrete, Section 3 procedure given in 7.
Carbonation depth measurement
The test under reference conditions takes therefore a
(first revision)
minimum of 112 days period that comprises a minimum
1199 Fresh concrete — Methods of age of the specimen of 28 days prior to conditioning,
sampling, testing and analysis: a minimum conditioning period of 14 days, and a
  (Part 2) : 2018 Determination of consistency of minimum exposure to increased carbon dioxide levels
fresh concrete (first revision) of 70 days. In case of concretes made with blended
cements or having mineral admixtures, extended curing
  (Part 5) : 2018 Making and curing of test and drying times are allowed and the same should be
specimens (first revision) reported.

1
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

If required, additional cube specimens may be cast 5.5 Apparatus for recording the relative humidity and
and used for measurement of the depth of carbonation temperature with a precision of ± 2.0 percent and
at exposure periods other than 70 days. Each cube ± 0.5 °C, respectively.
specimen shall be used for testing at one period of
exposure only. 5.6 Apparatus for recording CO2 concentration with a
precision of  ± 0.1 percent by volume.
When the purpose of the test is to measure the depth
of carbonation on the same specimen at more than one It is recommended that recording apparatus be fitted
exposure period, concrete prisms shall be used. with an audio/visual alarm to alert breaches of CO2
concentration within the storage chamber due to
In this case, two prisms are cast and cured for 28 days possible apparatus malfunction.
in accordance with IS 1199 (Part 5). The prisms are
conditioned in a laboratory air environment for 14 days 5.7 Fans, to facilitate steady circulation of air within
prior to sealing the top, bottom, and two end faces. the storage chamber.
After sealing all but two longitudinal faces, the prisms
are placed in a storage chamber, meeting the conditions 6 PREPARATION OF SPECIMENS
specified in 5.4 and having a carbon dioxide level of
3.0  ± 0.5 percent for the overall test period which 6.1 General
should be 70 days. After each exposure period, a Cubes and/or prisms for the determination of the
50 mm slice is broken from each prism and tested for carbonation resistance shall be made in accordance
carbonation depth. After splitting off a slice, the split with  IS 1199 (Part 5). If the specimens are to be made
end faces of the prisms are sealed and the remainder of by a test laboratory, the test laboratory shall be supplied
the prisms returned to the storage chamber. with a full specification of the concrete mix and the
The specimens, cubes, or prisms shall be positioned mixing procedure. Where the specimens are prepared
with their exposed faces in the vertical position. by the client or their representative, the test laboratory
shall be informed of the day of casting and provided
5 REAGENTS AND APPARATUS with a confirmation that the specimens were stored as
required by this standard.
5.1 Paraffin Wax or Equivalent, for sealing the non- For the determination of the depth of carbonation at any
exposed faces of test specimens. given exposure period, two cube specimens having a
5.2 A solution made of 1 g of phenolphthalein powder cross-section of 100 mm or 150 mm shall be prepared.
dissolved in 100 ml solution composed of 70 ml For the determination of the depth of carbonation
ethanol and 30 ml of de-ionised water. at more than one exposure period on the same test
specimen, two prisms, 500 mm long and having a
5.3 Magnifier and a Gauge, to measure the depth cross-section of 100 × 100 mm, shall be prepared.
of carbonation perpendicular to the exposed concrete The use of mould release agents should be avoided or
surface with a precision of 0.5 mm. minimized, as they might influence the carbonation
depth.
5.4 Storage Chamber with Carbon Dioxide
Concentration at 3.0 ± 0.5 Percent by Volume, 6.2 Making, Curing, and Testing of Prisms and
Temperature at 27 ± 2 °C, and Relative Humidity Cubes
at 65 ± 5 percent. Usually, if saturated surface-dry Cast two prisms/cubes from a single batch of concrete
specimens are placed in the storage chamber shortly for each mix. Before casting, appropriate workability
after removal from water curing, the relative humidity test shall be carried out as per  IS 1199 (Part 2). Cast
could exceed the permitted value. Also, in storage and cure the prisms/cubes as per  IS 1199 (Part 5). The
chambers without active control of carbon dioxide, specimens shall be stored in water or in a chamber
the levels could drop below the permitted tolerance as having a temperature in the range of 27 ± 2 °C and
the carbonation process continues. It is recommended a minimum relative humidity of 95 percent. After
that the storage chamber shall have active control on finishing the prisms/cubes, cover the exposed surface
carbon dioxide, relative humidity, and temperature with polythene or similar impermeable sheeting to
(see Annex A for details of suitable chamber). prevent drying. After 22 ± 2 h, the moulds shall be
Other levels of carbon dioxide concentration, humidity, stripped and the prisms/cubes transferred without delay
and temperature may be used. However, this shall be into a water-filled bath with temperature control set in
recorded and reported. the range of 27  ± 2 °C.
NOTE — Relative humidity levels may be maintained using It is recommended that at least three compressive
any method as per the discretion of the laboratory, for example, strength specimens be made and tested in accordance
active humidification/dehumidification or saturated salt
with IS 516 (Part 1/Sec 1) at 28 days.
solutions.

2
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

After removal from the curing tank, the specimens NOTES


shall be immediately wrapped and sealed in polythene 1 The purpose of sealing the top, bottom, and end faces is to
or similar material that will prevent drying during minimize any corner effect from multi-directional carbonation
and also to prevent longitudinal carbonation through the prism/
transportation. Alternatively, they should be transported cube.
while remaining fully immersed in water, like in a 2 If paraffin wax is used to seal the surfaces, melt it in a
mobile curing tank. On arrival at the test laboratory, temperature controlled crucible and apply to the concrete
the test specimens shall be unwrapped, checked for surface with a paint brush in three equal layers, leaving the
damage, and then stored in a water-filled curing tank wax to set on the concrete between each application.
with temperature in the range of 27 ± 2 °C until they
are 28 days old. 7 CARBONATION DEPTH MEASUREMENTS
At an age of 28 days, the prisms/cubes shall be removed 7.1 Exposure Period and Generation of Colour
from the water bath and transferred for 14 days to a Change
laboratory air drying environment having a temperature
in the range of 27  ± 2 °C and relative humidity in the The carbonation depth of prisms shall be measured
range of 65  ± 5 percent. after the following exposure periods: 56 days, 63 days,
and 70 days or as specified after placing in the storage
Alternative conditioning environments may be used; chamber. The carbonation depth of cubes shall be
however, they shall be recorded and reported. measured at 70 days unless specified otherwise.
After 14 days of conditioning, the top and bottom Ten single point carbonation depths (dk, point) are
longitudinal faces and the two end faces of prisms (or measured after each exposure period on each prism or
top, bottom, and two opposing side faces of cubes) cube and the depth of carbonation dk, is expressed as
shall be sealed using paraffin wax or a similar material the mean of the 20 readings.
that will prevent ingress of carbon dioxide and so as
to allow carbonation to occur only on the two cast A slice approximately 50 mm thick shall be broken
longitudinal surfaces (see  Fig. 1A). off after each exposure period and the split surface on
the remaining prism resealed to prevent longitudinal
Once the prisms/cubes have been sealed, they shall be carbonation [see Fig. 1B]. Where a single determination
placed in the storage chamber complying with 5.4. The of the carbonation depth is made on a cube after 70 days
prisms/cubes shall be positioned in such a way that of storage, the cube shall be split in half. The depths of
their exposed faces are vertical and that permits air carbonation on the freshly broken surface of the split
to circulate freely around the two faces that are to be slice shall be measured.
carbonated (see Annex A).

1A Sealing Cube and Prism Prior to Placing in Storage 1B Sealing of Split End Face of Prism After
Environment for the First Time Removing Slice for Testing Carbonation Depth

KEY
1 waxed faces
2 exposed faces
3 concrete slice split and sprayed with phenolphthalein
4 prism split and resealed
Fig. 1 Sealing of Prism Specimen Prior to and During Testing
3
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

NOTE — The sample shall not be sliced using a saw. A paver two specimens (dk) at 70 days shall be reported as the
cutter or paver slicer may be used. carbonation depth of the concrete mix.
Clear the broken surface immediately of dust and loose Where testing is undertaken on prisms at alternative
particles after breaking and then spray with a fine mist exposure periods, these shall be expressed as the
of indicator solution. Avoid the formation of flow arithmetical mean of two specimens (dk) at the reported
channels on the test surface. If only a weak colouration alternative exposure periods.
or none at all appears on the treated surface, spray again
after 30 s. 9 TEST REPORT
The measurements shall be conducted immediately
The test report shall contain the following:
after the colour has stabilized.
a) Details of the concrete mixes/grade of concrete, if
8 DETERMINATION OF THE CARBONATION known;
DEPTH b) Reference of the concrete under test;
8.1 General c) Date of casting of the specimens;
d) Date of the start of test;
The carbonation depth shall be determined by the
colour change in accordance with the method given e) All measured minimum and maximum carbonation
below. depths of at least 20 points at the reference
exposure period of 70 d or the specified exposure
8.2 Measuring the Depth of Carbonation periods;
The carbonation depth shall be measured at five points f) Mean carbonation depth of specimen faces
on each exposed face. To locate these points, the edge (dk, face), each specimen (dk, spec), and the overall
length shall be divided into six equal distances. The five mean (dk);
central points shall be used. With the help of measuring g) If any, the number of values of Δdk, point and
equipment such as vernier caliper, feeler gauge, ruler their magnitude that were not included in the
sliding gauge and a magnifier, the point carbonation calculation of the mean value;
depth (dk, point) shall be determined perpendicular to
h) Any deliberate deviation from the reference
the exposed surface of the prism with a precision of
conditions or non-conformity with the test
0.5 mm per measured point.
conditions, like, any failure to maintain the required
The depth of the carbonation shall be measured on the carbon dioxide for an identified short period or
one broken face on both prisms giving (normally) a changes to the preconditioning environment.
total of at least 20 measurement points. j) The test report may also contain the following:
The corrections for presence of dense aggregate or 1) Details of the concrete mixes;
air voids on the broken face may be applied as per
IS 516 (Part 5/Sec 3). 2) Individual test results and relevant
photographic records;
8.3 Expression of the Results 3) Results of additional testing, example
The mean depth of carbonation for each exposed face compressive strength results at 28 d;
of a specimen (dk, face) shall be calculated and recorded. 4) Any additional comments or observations; and
The mean depth of carbonation for each specimen 5) Any accreditation for undertaking the test
(dk, spec) shall be calculated and recorded. The procedure.
arithmetical mean of the mean carbonation depth of

4
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

ANNEX A
( Clauses 5.4 and 6.2 )
GUIDANCE ON SUITABLE STORAGE CHAMBERS
The features of a typical storage chamber are given It is recommended that spacers should be placed on
in Fig. 2. For the reference conditions, the carbon the sealed faces of the specimens. Prisms should be
dioxide content of the air within the storage chamber placed in the storage chamber in a manner that ensures
is required to be 3.0 ± 0.5 percent by volume. When a gap of at least 50 mm between prisms (see  Fig. 5). A
a large number of specimens are placed in a chamber, similar gap should be provided between the prisms and
the carbon dioxide content might fall rapidly and the walls.
remain below the required levels. For this reason, it Mechanical fans (table fans are suitable) shall be
is recommended that the carbon dioxide content be positioned within the storage chamber to ensure air
controlled and a suitable method is by means of a circulation. It is recommended that the turbulence be
carbon dioxide injector connected to the chamber to monitored during commissioning of the chamber by
replace carbon dioxide consumed by the carbonation means of a smoke generator test or a similar method.
reaction. A suitable apparatus is shown in Fig. 2, 3 and The storage chamber shall be tested with both the
4. Monitoring of the readings from the carbon dioxide minimum and maximum number of prisms to be used
injection equipment shall be carried out on a daily to ensure adequate air circulation during use.
basis. Any deviations from this level shall be reported.
Experience has shown that if non-standard saturated
Prisms should be stored either horizontally or vertically. surface-dry specimens are placed in the storage chamber,
Where prisms are stored horizontally, they should be the relative humidity could exceed the permitted level.
positioned in such a way to permit the free flow of air It is therefore recommended that the storage chamber
to the exposed, unsealed faces of the prism, that is, be provided with active control on relative humidity
using spacers cut from 50 mm diameter plastic piping. 65  ± 5 percent and temperature 27  ± 2 °C.

Fig. 2 Typical Storage Chamber with Vertical Storage

5
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

Fig. 3 Suitable System for Carbonation Dioxide Injection and Monitoring

Fig. 4 Carbondioxide Monitoring/Injection Apparatus

6
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

KEY
1 50 MM PLASTIC SPACERS
2 EXPOSED FACE OF PRISM
Fig. 5 Horizontal Storage of Specimens

7
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

ANNEX B
( Foreword )

COMMITTEE COMPOSITION
Cement and Concrete Sectional Committee, CED 02
Organization Representative(s)
In Personal Capacity (Grace Villa, Shri Jose Kurian (Chairman)
Kadamankulam P.O., Thiruvalla 689583)
ACC Ltd, Mumbai Shri Rajesh J. Modi
Dr Manish V. Karandikar (Alternate)
Ambuja Cements Limited, Ahmedabad Shri Umesh P. Soni
Shri Sukuru Ramarao (Alternate)
Atomic Energy Regulatory Board, Mumbai Shri L. R. Bishnoi
Shri Sourav Acharya (Alternate)
Builders’ Association of India, Mumbai Shri Sushanta Kumar Basu
Shri D. R. Sekor (Alternate)
Building Materials & Technology Promotion Shri C. N. Jha
Council, New Delhi
Cement Manufacturers’ Association, Noida Dr V. Ramachandra
Ms Shashwati Ghosh (Alternate)
Central Public Works Department, New Delhi Shri D. K. Garg
Shri Naveen Kumar Bansal (Alternate)
Central Soil and Materials Research Station, Director
New Delhi Shri U. S. Vidyarthi (Alternate)
Central Water Commission, New Delhi Director (CMDD) (N&W)
Deputy Director (CMDD) (NW&S) (Alternate)
Conmat Technolgies Pvt Ltd, Kolkata Dr A. K. Chatterjee
Dr Subrato Chowdhury (Alternate)
Construction Chemicals Manufacturers’ Shri Samir Surlaker
Association, Mumbai Shri Nilotpol Kar (Alternate)
CSIR ‒ Central Building Research Institute, Shri S. K. Singh
Roorkee Shri Subhash Gurram (Alternate)
CSIR ‒ Central Road Research Institute, Dr Rakesh Kumar
New Delhi Dr V. V. L. Kanta Rao (Alternate)
CSIR ‒ Structural Engineering Research Dr K. Ramanjaneyulu
Centre, Chennai Dr P. Srinivasan (Alternate)
Delhi Development Authority, New Delhi Shri Laxman Singh
Shri Vijay Shankar (Alternate)
Department of Science and Technology, Shri S. S. Kohli
Ministry of Science and Technology,
New Delhi
Engineers India Limited, New Delhi Shri Rajanji Srivastava
Shri Anurag Sinha (Alternate)
Gammon Engineers & Contractors Pvt Ltd, Shri Shriram B. Kulkarni
Mumbai Shri Rahul Biradar (Alternate)
Hindustan Construction Company Limited, Shri Satish Kumar Sharma
Mumbai Shri Mukesh Valecha (Alternate)

8
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

Organization Representative(s)
Housing and Urban Development Representative
Corporation Limited, New Delhi
Indian Association of Structural Engineers, Shri Mahesh Tandon
New Delhi Shri Ganesh Juneja (Alternate)
Indian Concrete Institute, Chennai Shri Vivek Naik
Secretary General (Alternate)
Indian Institute of Technology Delhi, Dr Shashank Bishnoi
New Delhi Dr Dipti Ranjan Sahoo (Alternate)
Indian Institute of Technology Madras, Dr Devdas Menon
Chennai Dr Manu Santhanam (Alternate)
Indian Institute of  Technology Roorkee, Dr V. K. Gupta
Roorkee Dr Bhupinder Singh (Alternate)
Indian Roads Congress, New Delhi Shri S. K. Nirmal
Shri R. V. Patil (Alternate)
Military Engineer Services, Engineer-in- Maj Gen S. K. Srivastav
Chief’s Branch, Integrated HQ of MoD Shri Man Singh (Alternate)
(Army), New Delhi
Ministry of Road Transport and Highways, Shri Y. Bala Krishna
New Delhi Shri Sanjeev Kumar (Alternate)
National Council for Cement and Building Shri V. V. Arora
Materials, Ballabgarh Dr S. K. Chaturvedi (Alternate)
National Test House, Kolkata Shri D. V. S. Prasad
Dr Somit Neogi (Alternate)
Nuclear Power Corporation of India Ltd, Shri Arvind Shrivastava
Mumbai Shri Raghupati Roy (Alternate)
Nuvoco Vistas Corporation Limited, Mumbai Shri Pranav Desai
Shri Ravindra Khamparia (Alternate)
Public Works Department, Govt of Tamil Superintending Engineer
Nadu, Chennai Executive Engineer (Alternate)
The India Cements Limited, Chennai Representative
The Indian Hume Pipe Company Limited, Shri P. R. Bhat
Mumbai Shri S. J. Shah (Alternate)
The Institution of Engineers (India), Kolkata Dr H. C. Visvesvaraya
Shri S. H. Jain (Alternate)
The Ramco Cements Limited, Chennai Shri Balaji K. Moorthy
Shri Anil Kumar Pillai (Alternate)
Ultra Tech Cement Ltd, Mumbai Shri Surya Valluri
Dr M. R. Kalgal (Alternate)
Voluntary Organization in Interest of Shri M. A. U. Khan
Consumer Education, New Delhi Shri B. Mukhopadhyay (Alternate)
In personal capacity [B-803, Oberoi Shri A. K. Jain
Exquisite, Oberoi Garden City, Goregaon
(East), Mumbai]
In personal capacity (36, Old Sneh Nagar, Shri L. K. Jain
Wardha Road, Nagpur)

9
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

Organization Representative(s)
In personal capacity (EA-92, Maya Enclave, Shri R. C. Wason
Hari Nagar, New Delhi)
BIS Directorate General Shri Sanjay Pant, Scientist ‘F’ and Head (Civil Engineering)
[ Representing Director General ( Ex-officio ) ]

Member Secretaries
Shri S. Arun Kumar
Scientist ‘E’ (Civil Engineering), BIS
Shri Milind Gupta
Scientist ‘C’ (Civil Engineering), BIS
and
Shrimati Divya S.
Scientist ‘C’ (Civil Engineering), BIS

Concrete Subcommittee, CED 2:2


Organization Representative(s)
In Personal Capacity (Grace Villa, Kadamankulam Shri Jose Kurian (Convener)
P.O., Thiruvalla 689583)
ACC Limited, Mumbai Shri Prahlad Majumdar
Shri Anil Kulkarni (Alternate)
Ambuja Cements Limited, Ahmedabad Shri Umesh P. Soni
Shri Sukuru Ramarao (Alternate)
AFCONS Infrastructure Limited, Mumbai Shri Manish Mokal
Association of Consulting Civil Engineers (India), Shri Avinash D. Shirode
Bengaluru Shri K. K. Meghashyam (Alternate)
Atomic Energy Regulatory Board, Mumbai Shri L. R. Bishnoi
Shri Sourav Acharya (Alternate)
Building Materials and Technology Promotion Shri Pankaj Gupta
Council, New Delhi
Bureau of Design for Hydel and Irrigation Project, Shri S. K. Khare
Bhopal Shri Bhagwati Prasad Gupta (Alternate)
Bureau Veritas India Ltd, Mumbai Representative
Central Public Works Department, New Delhi Shri D. K. Garg
Shri Rajesh Khare (Alternate)
Central Soil and Materials Research Station, New Shri Rajeev Kumar
Delhi Shri Raj Kumar (Alternate)
Creative Design Consultants and Engineers Pvt Ltd, Shri Aman Deep Garg
Ghaizabad Shri Manik Chatterjee (Alternate)
CSIR ‒ Central Building Research Institute, Roorkee Dr Rajesh Deolia
Shri H. C. Arora (Alternate)
CSIR ‒ Central Road Research Institute, New Delhi Shri J. B. Sengupta
Shri Satish Pandey (Alternate)
CSIR ‒ Structural Engineering Research Centre, Dr B. H. Bharathkumar
Chennai Dr P. Srinivasan (Alternate)
Department of Science and Technology, Ministry of Shri S. S. Kohli
Science and Technology, New Delhi

10
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

Organization Representative(s)
Elkem South Asia Pvt Ltd, Navi Mumbai Shri Brajesh Malviya
Shri Surendra Sharma (Alternate)
Engineers India Limited, New Delhi Shri Rajanji Srivastava
Shri Anurag Sinha (Alternate)
Gammon Engineers & Contractors Pvt Ltd, Mumbai Shri Sudeesh Rajendran
Hindustan Constrution Company Ltd, Mumbai Shri Satish Kumar Sharma
Shri Khatarbatcha Jimmetain (Alternate)
Indian Concrete Institute, Chennai Shri K. C. Tayade
Secretary General (Alternate)
Indian Institute of Technology Delhi, New Delhi Dr B. Bhattacharjee
Dr Shashank Bishnoi (Alternate)
Indian Institute of Technology Kanpur, Kanpur Dr Sudhir Mishra
Indian Institute of Technology Madras, Chennai Dr Manu Santhanam
Dr Radhakrishna G. Pillai (Alternate)
Indian Institute of Technology Roorkee, Roorkee Representative
Indian Society of Structural Engineers, Mumbai Shri Umesh Joshi
Shri Hemant Vadalkar (Alternate)
Irrigation and Power Research Institute, Amritsar Chief Engineer (Research)
Research Officer (Alternate)
Larsen and Toubro Limited, ECC Division, Chennai Dr B. Sivarama Sarma
Shri S. Manohar (Alternate)
Military Engineer Services, Engineer-in-Chief’s Maj Gen S. K. Srivastav
Branch, Integrated HQ of MoD (Army), New Shri Man Singh (Alternate)
Delhi
Ministry of Road Transport & Highways, New Delhi Shri A. P. Pathak
Shri A. K. Pandey (Alternate)
NBCC (India) Limited, New Delhi Shri H. S. Yadav
Shri Arun Kumar Sharma (Alternate)
National Council for Cement and Building Materials, Shri V. V. Arora
Ballabgarh Shri P. N. Ojha (Alternate)
National Institute of Technology Warangal, Warangal Dr C. B. Kameswara Rao
Dr D. Rama Seshu (Alternate)
Nuclear Power Corporation of India Limited, Mumbai Shri Arvind Shrivastava
Shri N. M. Rao (Alternate)
Pidilite Industries Limited, Mumbai Dr Suguna Naik
Ready Mixed Concrete Manufacturers’ Association, Shri Vijaykumar R. Kulkarni
Mumbai Shri Srirang Sondur (Alternate)
Research, Design & Standards Organization Jt Director Stdrs (B&S)/CB-I
(Ministry of Railways), Lucknow Jt Director Stdrs (B&S)/CB-II (Alternate)
RDC Concrete (India) Pvt Ltd, Thane Shri Anil Banchhor
Shri Simranjit Singh (Alternate)
Shapoorji Pallonji and Company Private Limited, Shri Girish Bonde
Mumbai Shri D. N. Vishwanath (Alternate)
Tandon Consultants Pvt Limited, New Delhi Shri Mahesh Tandon
Shri Vinay Gupta (Alternate)
Tata Consulting Engineers Limited, Mumbai Shri S. N. Diwakar
Shri Manos Kumar De (Alternate)

11
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

Organization Representative(s)
Ultra Tech Cement Ltd, Mumbai Dr V. Ramachandra
Dr A. K. Singh (Alternate)
Water Resource Department, Govt. of Madhya Shri S. K. Khare
Pradesh, Mumbai Shri B. P. Gupta (Alternate)
In personal capacity (452, Sector 14, Sonipat, Shri R. K. Jain
Haryana)
In personal capacity (36, Old Sneh Nagar, Wardha Shri L. K. Jain
Road, Nagpur)
In personal capacity [B-803, Oberoi Exquisite, Oberoi Shri A. K. Jain
Garden City, Goregaon (East), Mumbai]
In personal capacity (EA-92, Maya Enclave, Hari Shri R. C. Wason
Nagar, New Delhi)
In personal capacity (M1 F1 VGN Minerva Dr C. Rajkumar
Apartments, Guruswamy Road, Nolambur,
Chennai)

Panel for Revision of Indian Standards on Test Methods for Concrete, CED 2:2/P7

Organization Representative(s)
In Personal Capacity (EA-92, Maya Enclave, Hari Shri R. C. Wason (Convener)
Nagar, New Delhi 110064)
ACC Limited, Mumbai Shri Avijit Chaubey
Shri Prahalad Majumdar (Alternate)
AIMIL Ltd, New Delhi Dr V. M. Sharma
Bureau Veritas India Limited, Bengaluru Representative
Central Public Works Department, New Delhi Shri Ajay Prakash Mathur
Shri Naveen Kumar Bansal (Alternate)
Central Soil and Materials Research Station, Shri U. S. Vidyarthi
New Delhi
Contruction Diagnostic Centre Pvt Ltd, Pune Shri Ravi Ranade
CSIR ‒ Central Building Research Institute, Roorkee Shri S. K. Singh
Ms M. Surya (Alternate)
CSIR ‒ Central Road Research Institute, New Delhi Representative
CSIR ‒ Structural Engineering Research Centre, Dr S. Bhaskar
Chennai Dr P. Srinivasan (Alternate)
Hindustan Construction Company Ltd, Mumbai Shri Satish Kumar Sharma
Shri Khatarbatcha Jimmetain (Alternate)
Hydraulic & Engineering Instrument, New Delhi Representative
Indian Concrete Institute, New Delhi Shri Ashok Kumar Tiwari
Indian Institute of  Technology Delhi, New Delhi Dr Shashank Bishnoi
Dr Supratic Gupta (Alternate)
Indian Institute of  Technology Madras, Chennai Dr Radhakrishna G. Pillai
Dr Ravindra Gettu (Alternate)
Larsen & Toubro Ltd, ECC Division, Chennai Shri B. Sivarama Sarma
Shri S. Manohar (Alternate)

12
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 2/Sec 4) : 2021

Organization Representative(s)
National Council for Cement and Building Materials, Shri V. V. Arora
Ballabgarh Shri Puneet Kaura (Alternate)
Nuclear Power Corporation of India Ltd, Mumbai Shri Arvind Shrivastava
Shri A. K. Laharia (Alternate)
RDC Concrete (India) Pvt Ltd, Mumbai Shri Anil Banchhor
Shri Navneet Nair (Alternate)
Ready Mixed Concrete Manufacturers’ Association, Shri Vijaykumar R. Kulkarni
Mumbai Shri N. G. Muralidharan (Alternate)
Stedrant Technoclinic Pvt Ltd, Bengaluru Dr R. Nagendra
Shri Sunil V. Sonnad (Alternate)
Unique Engineering Testing & Advisory Services, Shri Hitesh Desai
Surat Shri Nehal H. Desai (Alternate)
In personal capacity (50, Mangla Apartments Kalkaji, Dr S. C. Maiti
New Delhi)
In personal capacity (Type IV/17, President’s Estate, Shri K. H. Babu
New Delhi)
In personal capacity (Grace Villa, Kadamankulam Shri Jose Kurian
P.O., Thiruvalla)
In personal capacity (624, Ranisatinagar, Lane 6, Dr P. S. Gahlot
Lodhi Marg, Ajmer Road, Jaipur)

13
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

(Continued from second cover)

The test under reference conditions takes therefore a minimum of 112 days period that comprises a minimum age
of the specimen of 28 days prior to conditioning, a minimum conditioning period of 14 days, and a minimum
exposure to increased carbon dioxide levels of 70 days. In case of concretes made with blended cements or
having mineral admixtures, extended curing and drying times are allowed. Details on suitable storage chamber for
carrying out this test have also been mentioned.
In the formulation of this standard, assistance was derived from ISO 1920-12 : 2015 Testing of concrete —
Part 12 : Determination of the carbonation resistance of concrete — Accelerated carbonation method.
The composition of the Committee responsible for the formulation of this standard is given in Annex B.
In reporting the result of a test or analysis made in accordance with this standard, is to be rounded off, it shall
be done in accordance with IS 2 : 1960 ‘Rules for rounding off numerical values ( revised )’. The number of
significant places retained in the rounded off value should be the same as that specified value in this standard.
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

Bureau of Indian Standards

BIS is a statutory institution established under the Bureau of Indian Standards Act, 2016 to promote harmonious
development of the activities of standardization, marking and quality certification of goods and attending to
connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any form without
the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the
standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to
copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards: Monthly Additions’.
This Indian Standard has been developed from Doc No.: CED 02 (13829).

Amendments Issued Since Publication


Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS


Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002
Telephones: 2323 0131, 2323 3375, 2323 9402 Website: www.bis.gov.in
Regional Offices: Telephones
Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg
NEW DELHI 110002 { 2323 7617
2323 3841
Eastern : 1/14 C.I.T. Scheme VII M, V.I.P. Road, Kankurgachi
KOLKATA 700054 { 2337 8499, 2337 8561
2337 8626, 2337 9120
Northern : Plot No. 4-A, Sector 27-B, Madhya Marg
CHANDIGARH 160019 { 265 0206
265 0290
Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113
{ 2254 1216, 2254 1442
2254 2519, 2254 2315
Western : Manakalaya, E9 MIDC, Marol, Andheri (East)
MUMBAI 400093 { 2832 9295, 2832 7858
2832 7891, 2832 7892
Branches : AHMEDABAD. BENGALURU. BHOPAL. BHUBANESHWAR. COIMBATORE.
DEHRADUN. DURGAPUR. FARIDABAD. GHAZIABAD. GUWAHATI.
HYDERABAD. JAIPUR. JAMMU. JAMSHEDPUR. KOCHI. LUCKNOW.
NAGPUR. PARWANOO. PATNA. PUNE. RAIPUR. RAJKOT. VISAKHAPATNAM.
Published by BIS, New Delhi

You might also like