Is 516 (Part-1 Sec-I) - 2021 Compressive, Flexural and Split Tensile Strength

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -

Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

भारतीय मानक IS 516 (Part 1/Sec 1) : 2021


Indian Standard

दृढ़ीकृत कंक्रीट — परीक्षण पद्धतियाँ


भाग 1 दृढ़ीकृत कंक्रीट का सामर्थ्य ज्ञात
करने के लिए परीक्षण
खण्ड 1 सपं ीड़न, फ्लेक्स रल व खंडित तनन सामर्थ्य
(  पहला पनु रीक्षण )

Hardened Concrete —
Methods of Test
Part 1 Testing of Strength of Hardened Concrete

Section 1 Compressive, Flexural and Split Tensile Strength

( First Revision )

ICS 91.100.30

© BIS 2021

भारतीय मानक ब्रयू ो


B U R E A U O F I N D I A N S TA N D A R D S
मानक भवन, 9 बहादरु शाह ज़फर मार्ग, नई िदल्ली – 110002
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI-110002
         www.bis.gov.in  
www.standardsbis.in

March 2021  Price Group 7


Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

Cement and Concrete Sectional Committee, CED 02

FOREWORD
This Indian Standard (Part 1/Sec 1) (First Revision) was adopted by the Bureau of Indian Standards, after the draft
finalized by the Cement and Concrete Sectional Committee had been approved by the Civil Engineering Division
Council.
Testing plays an important role in controlling the quality of cement concrete work. Systematic testing of raw
materials, fresh concrete and hardened concrete, is an inseparable part of any quality control programme for
concrete. This helps achieve a higher efficiency of the materials used and greater assurance of the performance of
the concrete, in regard to workability, strength and durability. The test methods used should be simple, direct and
convenient to apply. This standard was formulated with this objective in view.
This standard was first published in 1959. In this revision, it was decided to review and update the various existing
test methods of concrete also taking into consideration the latest international practices and developments in this
field in the country, and in addition to introduce certain new test methods, wherever required. In the process,
the various existing test methods covered in IS 516 : 1959 ‘Method of tests for strength of concrete’ have been
revised taking into consideration primarily the corresponding ISO standards while also examining the other best
practices world over and in the country. In addition, test methods for determination of additional properties have
been included in areas such as permeability, initial surface absorption, corrosion of reinforcement, carbonation of
concrete (field test) and, creep of concrete. Also, for better understanding and implementation, some of the other test
methods which were spread over in number of other Indian standards have been brought together under the fold of
IS 516 as its various parts, such as the splitting tensile strength, ultrasonic pulse velocity test, rebound hammer
test, bond in reinforced concrete, and determination of water soluble and acid soluble chlorides. This is with a
view to making the standard complete in all respects, and rendering it a comprehensive source of provisions for
testing of concrete and reference in other Indian Standards.
In this revision, IS 516 has been split into 12 parts. The other parts in this series are:
Part 2 Determination of properties of hardened concrete other than strength
Part 3 Making, curing and determining compressive strength of accelerated cured concrete test
     specimens
Part 4 Sampling, preparing and testing of concrete cores
Part 5 Non-destructive testing of hardened concrete
Part 6 Determination of drying shrinkage and moisture movement of concrete samples
Part 7 Determination of creep of concrete cylinders in compression
Part 8 Determination of modulus of elasticity
Part 9 Determination of wear resistance
Part 10 Determination of bond in reinforced concrete
Part 11 Determination of Portland cement content of hardened hydraulic cement concrete
Part 12 Determination of water soluble and acid soluble chlorides in hardened mortar and concrete
This standard (Part 1/Section 1) gives the provisions for determining the compressive, flexural and split tensile
strength of hardened concrete.
These test methods shall be applicable in place of the corresponding provisions given in IS 516 : 1959 ‘Method
of tests for strength of concrete’ and  IS 5816 : 1999 ‘Methods of test for splitting tensile strength of concrete
( first revision )’.  IS 516 : 1959 shall be superseded after the publication of all the parts of the standard.  
IS 5816 : 1999 shall stand withdrawn after the publication of this standard.

(Continued to third cover)


Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Indian Standard
HARDENED CONCRETE — METHODS OF TEST
PART 1 TESTING OF STRENGTH OF HARDENED CONCRETE
Section 1 Compressive, Flexural and Split Tensile Strength

( First Revision )

1 SCOPE 5). Damaged specimens shall not be tested. Specimens


that are badly honeycombed shall not be regarded as
This standard (Part 1/Section 1) covers procedures for
being representative of the quality of concrete supplied.
testing compressive, flexural and split tensile strength
In general, standard cube and cylinder specimens shall
of hardened concrete.
not be tested if they are badly honeycombed as this is
2 REFERENCES an indication of poor specimen making. When such
specimens are tested, the test report shall include the
The standards listed below contains provisions which fact that the specimen was honeycombed.
through reference in this text, constitutes provisions of
this standard. At the time of publication, the editions 3.2 Apparatus
indicated were valid. All standards are subject to The test shall be carried out using a compression testing
revision and parties to agreements based on this machine conforming to IS 14858. The test machine
standard are encouraged to investigate the possibility shall be in calibration at the time of test.  The calibration
of applying the most recent edition of the standard shall be carried out at least once per year.
indicated below:
3.3 Age at Test
IS No. Title
Tests shall be made at recognized ages of the test
516 (Part 4) : 2018
Hardened concrete  —  Methods specimens, the most usual being 7 and 28 days.  Ages of
of test: Part 4 Sampling, 56 days, 90 days and one year are recommended if tests
preparing and testing of at greater ages are required.  Where it may be necessary
concrete cores (first revision) to obtain the early strengths, tests may be made at the
1199 (Part 5) : Fresh concrete — Methods of ages of 24 h  ± 30 min and 72 h  ± 2 h. The ages shall be
2018 sampling, testing and analysis: calculated from the time of the addition of water to the
Part 5 Making and curing of test dry ingredients.
specimens (first revision)
3.4 Number of Specimens
1500 (Part 1) : Metallic materials — Brinell
2019/ ISO 6506-1 hardness test: Part 1 Test At least three specimens shall be tested at each selected
age.
: 2014 method (fifth revision)
1658 : 2006 Fibre hardboards — 3.5 Procedure
Specification (third revision)
3.5.1 Preparation and Positioning of  Specimens
14858 : 2000 Compression testing machine
used for testing of concrete and For specimens stored in water, excess moisture shall be
mortar — Requirements wiped from the surface of the specimen before placing
them in the testing machine. The dimensions of the
10086 : 1982 Specification for moulds for use specimens to the nearest 0.2 mm and their weight shall
in tests of cement and concrete be noted before testing.
The time between the extraction of the specimen from
3 DETERMINATION OF COMPRESSIVE the curing tank, and the testing, shall be as short as
STRENGTH OF HARDENED CONCRETE possible or not more than 2 h. During the time the
specimen is outside the curing tank, it shall be protected
3.1 Test Specimens from drying, may be by covering with wet cloth.
The test specimen shall be a cube or a cylinder All testing machine bearing surfaces shall be wiped
meeting the requirements of  IS 1199 (Part 5) and  clean and any loose grit or other extraneous material
IS 516 (Part 4) for concrete cores.  Cylindrical removed from the surfaces of the specimen that will be
specimens cast in the lab or cores extracted from the in contact with the platens.
structures, shall be capped as per 6.6 of  IS 1199 (Part

1
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Do not use packing, other than auxiliary platens or than  ± 15 percent of the average. Otherwise repeat test
spacing blocks, between the specimen and the platens shall be made, however if there is no further sample, then
of the testing machine. Cube specimens shall be the average of two closest values may be taken as the
compressed perpendicularly to the direction of casting. average result.
The specimen shall be centered on the lower platen to The actual dimensions of test specimens shall conform
an accuracy of 1 percent of the designated size of cubic, to  IS 10086. If the actual dimensions are within the
or diameter of cylindrical specimens. Where physical tolerance limits as mentioned in  IS 10086, the strength
means of ensuring centering are provided on the may be calculated on the basis of designated size. If the
testing machine and they are in calibration, these shall actual dimensions are outside this tolerance, the strength
be deemed to satisfy the requirements for accuracy of calculation shall be based on the actual dimensions of
centering. If auxiliary platens are used, the top auxiliary the test specimen, however, perpendicularity of the
platen shall be aligned with the top of the specimen. With surface of specimens should be maintained as per
two-column testing machines, cube specimens shall be IS 10086.
placed with the trowelled surface facing a column.
The compressive strength shall be expressed to the
3.5.2 Loading nearest 0.5 MPa.
The load shall be applied without shock and shall 3.7 Test Report
be increased continuously at a constant rate of
14 N/mm2/min until no greater load can be sustained. The following information shall be included in the
The maximum load indicated shall be recorded. report:
a) Details of the concrete like grade, mix details, etc, in
3.5.3 Assessment of  Type of  Failure case of cast specimens; and details of the structure,
For cube specimens, if the failure is satisfactory like structure type, origin member/structure, in case
(see Fig. 1), this fact shall be recorded. If the failure of cored specimen;
pattern is unsatisfactory, this fact shall be recorded and b) Type of specimen: cast (cube/cylinder) or drilled
the type of failure recorded using the pattern number in core;
Fig. 2 closest to that observed.
c) Size of the specimen, and capping details, if
For cylindrical specimens, if the failure is satisfactory applicable;
(see Fig. 3), this fact shall be recorded. If the failure d) Identification mark;
pattern is unsatisfactory, this fact shall be recorded and
the type of failure recorded using the pattern letter in e) Age of specimen;
Fig. 4 closest to that observed. f) Date of test;
g) Curing conditions;
3.6 Test Results
h) Weight of specimen;
The compressive strength is given by the equation:
j) Dimension of specimen;
fc = F/Ac
k) Maximum load;
where
m) Details of the machine used for testing
fc = compressive strength, in MPa; (manual/automated, loading range, date of
F = maximum load, in N; and calibration, etc);
Ac = cross-sectional area, in mm2, of the specimen on n) Compressive strength of specimen (to the nearest
which the compressive force acts. 0.5 MPa); and
Average of three values shall be taken as the representative p) Type of failure (satisfactory or unsatisfactory and,
of the batch provided the individual variation is not more if unsatisfactory, the nearest type).

Fig. 1 Satisfactory Failure of Cube Specimens


2
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

NOTE: T = TENSILE CRACK


Fig. 2 Unsatisfactory Failure of Cube Specimens

Fig. 3 Satisfactory Failure of Cylindrical Specimens

3
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Fig. 4 Unsatisfactory Failure of Cylindrical Specimens

4 DETERMINATION OF FLEXURAL calculated from the time of the addition of water to the
STRENGTH dry ingredients.

4.1 Test Specimens 4.3 Number of Specimens


The test specimen shall be a prism conforming to At least three specimens shall be tested at each selected
IS 1199 (Part 5). Sawn specimens of nominal width of age.
100 mm or 150 mm with a square cross-section and
4.4 Apparatus
overall length of 500 mm and 700 mm may also be
used. 4.4.1 Testing Machine
4.2 Age at Test The testing machine may be of any reliable type of
sufficient capacity for the tests and capable of applying
Tests shall be made at recognized ages of the test
the load at the rate specified. The permissible errors
specimens, the most usual being 7 and 28 days. Ages
shall be not greater than  ± 1 percent of the applied
of 90 days and 1 year are recommended if tests at
load. The bed of the testing machine shall be provided
greater ages are required. Where it may be necessary
with two steel rollers, 38 mm in diameter, on which
to obtain the early strengths, tests may be made at the
the specimen is to be supported, and these rollers shall
ages of 24 h  ± 30 min and 72 h  ± 2 h. The ages shall be

4
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

be so mounted that the distance from centre to centre longitudinal axis of the specimen at right angles to the
is 600 mm for 150 mm specimens and 400 mm for longitudinal axis of the upper and lower rollers. The
100 mm specimens. The load shall be applied through reference direction of loading shall be perpendicular to
two similar rollers mounted at the third points of the the direction of casting of the specimen.
supporting span, that is, spaced at 200 or 133 mm
respectively centre-to-centre. The load shall be divided 4.5.2 Loading
equally between the two loading rollers, and all rollers The bearing surfaces of the supporting and loading
shall be mounted in such a manner that the load is rollers shall be wiped clean, and any loose sand or other
applied axially and without subjecting the specimen to material removed from the surfaces of the specimen
any torsional stresses or restraints. Each roller, except where they are to make contact with the rollers. The
one of the lower ones shall be capable of rotating specimen shall then be placed in the machine in such a
around its axis and of being inclined in a plane normal manner that the load shall be applied to the uppermost
to the longitudinal axis of the test specimen. surface as cast in the mould.
4.4.2 Force Application The load shall not be applied until all loading and
supporting rollers are resting evenly against the test
The device for applying loads shall consist of two upper specimen. The load shall be applied without shock
rollers and two lower rollers (see  Fig. 5). and shall be increased continuously at a constant rate
The rollers shall be arranged as per 4.4.1. until no greater load can be sustained. The load shall
increase at a rate 0.7 N/mm2/min (rate of loading being
4.5 Procedures 4 kN/min for 150 mm specimens and 1.8 kN/min for
4.5.1 Preparation and Positioning of  Specimens 100 mm specimens).

The specimen shall be examined and any abnormalities The maximum load indicated shall be recorded.
shall be reported. 4.5.3 Assessment of  Type of  Fracture
For specimens stored in water, excess moisture shall be The fractured specimen shall be examined and the
wiped from the surface of the specimen before placing appearance of the concrete and type of fracture shall be
in the testing machine. recorded (see  Fig. 6).
The time between the extraction of the specimen from
the curing tank until the test shall be as short as possible 4.6 Test Results
or not more than 2 h. During the time the specimen is The flexural strength of the specimen shall be expressed
outside the curing tank, it shall be protected from drying, as modulus of rupture, Fb and shall be calculated to the
like by covering with wet cloth. The test specimen shall nearest 0.05 MPa as follows in case of failure Type A
be placed in the machine, correctly centred with the (see  Fig. 6A):

Fig. 5 Test Setup


5
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Fig. 6 Types of Failure Pattern

Fb = (P × L)/B × D2 4.7 Test Report


in which ‘a’ is greater than 200 mm for 150 mm The following information shall be included in the
specimen, or greater than 133 mm for 100 mm report:
specimen, or a) Size of specimen;
in case of failure Type B (see Fig. 6B), modulus of b) Identification mark;
rupture Fb shall be calculated to the nearest 0.05 MPa
c) Age of specimen;
by the following formula:
d) Date of test;
Fb = (3P × a)/B × D2
e) Details of concrete mix such as grade, cement
in which ‘a’ is less than 200 mm but greater than content, curing condition, etc;
170 mm for 150 mm specimen or less than 133 mm but
greater than 110 mm for 100 mm specimen, f) Weight of specimen;
g) Maximum load;
where
h) Type of fracture and flexural strength of specimen
Fb = flexural strength, in MPa; (to the nearest 0.05 MPa);
P = maximum load, in N; j) In case of failure Type B, value of ‘a’.
a = the distance between the line of fracture and
the nearer support, measured on the centre line 5  
DETERMINATION OF SPLITTING
of the tensile side of the specimen, in mm; TENSILE STRENGTH
B, D are the lateral dimensions (breadth and height) of
5.1 Specimens
the specimen, mm; and
The specimen shall be a cube or cylinder meeting the
L = length of span on which the specimen is
requirements of IS 1199 (Part 5). Damaged or badly
supported, expressed in mm.
honeycombed specimens shall not be tested.
If ‘a’ is less than 170 mm for 150 mm or less than
110 mm for a 100 mm specimen, the results of the test 5.2 Apparatus
shall be discarded.
5.2.1 Testing Machine
The flexural strength shall be expressed to the nearest
0.05 MPa. The test shall be carried out using a compression testing
machine conforming to IS 14858.

6
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

The test machine shall be in calibration at the time of of the cube using any suitable procedure and device
test. The calibration shall be carried out at least once that will ensure that they are in the same axial plane
per year. (see Fig. 9).
5.2.2 Jigs 5.5.3 Placing of the Specimen in the Testing Machine
Jig shown in Fig. 7 may be used for splitting cylindrical The bearing surfaces of the testing machine and of the
and cubic specimens. Curved steel loading pieces may loading strips shall be wiped clean.
be used in place of conventional plane platens when
5.5.4 Positioning
tests are carried out on cubical specimen. Alternatively
a jig shown in Fig. 8 may be used for cubic specimen. The test specimen shall be placed in the centering
jig with packing strip and/or loading pieces carefully
5.2.3 Two packing strips of tempered hardboard of positioning along the top and bottom of the plane of
nominal thickness 4 mm conforming to IS 1658 having loading of the specimen. The jig shall then be placed in
following dimensions of the test specimen shall be used the machine so that the specimen is located centrally. In
for each specimen and shall be discarded after each the case of cubic specimens, the load shall be applied
such test: on the moulded faces in such a way that the fracture
a) Width 15 ± 2 mm, plane will cross the trowelled surface. For cylindrical
b) Nominal thickness 4 ± 1 mm, and specimen it shall be ensured that the upper platen is
c) Length greater than the length of the line of parallel with the lower platen.
content of the test specimen. 5.5.5 Rate of Loading
5.2.4 Steel Loading Strips The load shall be applied without shock and increased
A steel loading plate having minimum hardness value, continuously at a nominal rate within the range
when tested in accordance with  IS 1500 (Part 1) shall 1.2 N/mm2/min to 2.4 N/mm2/min. Maintain the rate,
be used between the platen of the machine and the once adjusted, until failure. The maximum load applied
hardboard packing strip. The piece shall not be shorter shall then be recorded. The appearance of concrete and
than the specimen. For cylindrical specimens it shall be any unusual features in the type of failure shall also be
of rectangular cross-section and for cubic specimens, it noted.
shall be a section of a cylinder, with a radius of 75 mm, The rate of increase of load may be calculated from the
so that the load is applied along a line on the surface of
formula:
the specimen.
(1.2 to 2.4) × π/2 × l × d N/min
5.3 Age at Test
Tests shall be made at the recognized ages of the 5.6 Calculation
test specimens, the most usual being 7 and 28 days.
Tests at any other age at which the tensile strength is 5.6.1 The measured splitting tensile strength fc, of the
desired may be made, if so required. The ages shall be specimen shall be calculated to the nearest 0.05 N/mm2
calculated from the time of the addition of water to the using the following formula:
dry ingredients. The age at test shall be reported along a) For cylinders,
with the results.
2P
5.4 Number of Specimens fc =
π ld
At least three specimens shall be tested for each age P
of tests. b) For cubes, fc =
2l 2
5.5 Procedure
where
5.5.1 Specimens when received dry shall be kept in P = maximum load applied to specimen, in N;
water for 48 h before they are taken for testing. Unless
l = length of cylinder/side of the cube, in mm; and
other conditions are required for specific laboratory
investigation specimens shall be tested immediately on d = cross sectional dimension of cylindrical
removal from the water whilst they are still wet. Surface specimen, in mm.
water and grit shall be wiped off the specimens and any 5.7 Examination of Specimen
projecting fins removed from the surfaces which are to
be in contact with the packing strips. The fractured specimen shall be examined and the
appearance of the concrete and type of fracture, if
5.5.2 Marking unusual, shall be recorded. An example of unusual type
Central lines shall be drawn on the two opposite faces of fracture is when the plane of fracture is not vertical.

7
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Fig. 7 Jig for Splitting Cylinder and Cube

Fig. 8 Alternate Apparatus for Splitting Cubes

8
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Fig. 9 Plane of Loading

5.8 Report c) Age of specimen.


The following information shall be included in the d) Splitting tensile strength to the nearest
report on each specimen: 0.05 N/mm2.
a) Date of test. e) Fracture pattern, in line with Fig. 9.
b) Identification mark, shape and size of the f) Weight of specimen.
specimen, in mm.

9
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

ANNEX A
( Foreword )

COMMITTEE COMPOSITION
Cement and Concrete Sectional Committee, CED 02
Organization Representative(s)
In Personal Capacity (Grace Villa, Shri Jose Kurian (Chairman)
Kadamankulam P.O., Thiruvalla 689583)
ACC Ltd, Mumbai Shri Rajesh J. Modi
Dr Manish V. Karandikar (Alternate)
Ambuja Cements Limited, Ahmedabad Shri Umesh P. Soni
Shri Sukuru Ramarao (Alternate)
Atomic Energy Regulatory Board, Mumbai Shri L. R. Bishnoi
Shri Sourav Acharya (Alternate)
Builders’ Association of India, Mumbai Shri Sushanta Kumar Basu
Shri D. R. Sekor (Alternate)
Building Materials & Technology Promotion Shri C. N. Jha
Council, New Delhi
Cement Manufacturers’ Association, Noida Dr V. Ramachandra
Ms Shashwati Ghosh (Alternate)
Central Public Works Department, New Delhi Shri D. K. Garg
Shri Naveen Kumar Bansal (Alternate)
Central Soil and Materials Research Station, Director
New Delhi Shri U. S. Vidyarthi (Alternate)
Central Water Commission, New Delhi Director (CMDD) (N&W)
Deputy Director (CMDD) (NW&S) (Alternate)
Conmat Technolgies Pvt Ltd, Kolkata Dr A. K. Chatterjee
Dr Subrato Chowdhury (Alternate)
Construction Chemicals Manufacturers’ Shri Samir Surlaker
Association, Mumbai Shri Nilotpol Kar (Alternate)
CSIR ‒ Central Building Research Institute, Shri S. K. Singh
Roorkee Shri Subhash Gurram (Alternate)
CSIR ‒ Central Road Research Institute, Dr Rakesh Kumar
New Delhi Dr V. V. L. Kanta Rao (Alternate)
CSIR ‒ Structural Engineering Research Dr K. Ramanjaneyulu
Centre, Chennai Dr P. Srinivasan (Alternate)
Delhi Development Authority, New Delhi Shri Laxman Singh
Shri Vijay Shankar (Alternate)
Department of Science and Technology, Shri S. S. Kohli
Ministry of Science and Technology,
New Delhi
Engineers India Limited, New Delhi Shri Rajanji Srivastava
Shri Anurag Sinha (Alternate)
Gammon Engineers & Contractors Pvt Ltd, Shri Shriram B. Kulkarni
Mumbai Shri Rahul Biradar (Alternate)
Hindustan Construction Company Limited, Shri Satish Kumar Sharma
Mumbai Shri Mukesh Valecha (Alternate)

10
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Organization Representative(s)
Housing and Urban Development Representative
Corporation Limited, New Delhi
Indian Association of Structural Engineers, Shri Mahesh Tandon
New Delhi Shri Ganesh Juneja (Alternate)
Indian Concrete Institute, Chennai Shri Vivek Naik
Secretary General (Alternate)
Indian Institute of Technology Delhi, Dr Shashank Bishnoi
New Delhi Dr Dipti Ranjan Sahoo (Alternate)
Indian Institute of Technology Madras, Dr Devdas Menon
Chennai Dr Manu Santhanam (Alternate)
Indian Institute of Technology Roorkee, Dr V. K. Gupta
Roorkee Dr Bhupinder Singh (Alternate)
Indian Roads Congress, New Delhi Shri S. K. Nirmal
Shri R. V. Patil (Alternate)
Military Engineer Services, Engineer-in- Maj Gen S. K. Srivastav
Chief’s Branch, Integrated HQ of MoD Shri Man Singh (Alternate)
(Army), New Delhi
Ministry of Road Transport and Highways, Shri Y. Bala Krishna
New Delhi Shri Sanjeev Kumar (Alternate)
National Council for Cement and Building Shri V. V. Arora
Materials, Ballabgarh Dr S. K. Chaturvedi (Alternate)
National Test House, Kolkata Shri D. V. S. Prasad
Dr Somit Neogi (Alternate)
Nuclear Power Corporation of India Ltd, Shri Arvind Shrivastava
Mumbai Shri Raghupati Roy (Alternate)
Nuvoco Vistas Corporation Limited, Mumbai Shri Pranav Desai
Shri Ravindra Khamparia (Alternate)
Public Works Department, Govt of Tamil Superintending Engineer
Nadu, Chennai Executive Engineer (Alternate)
The India Cements Limited, Chennai Representative
The Indian Hume Pipe Company Limited, Shri P. R. Bhat
Mumbai Shri S. J. Shah (Alternate)
The Institution of Engineers (India), Kolkata Dr H. C. Visvesvaraya
Shri S. H. Jain (Alternate)
The Ramco Cements Limited, Chennai Shri Balaji K. Moorthy
Shri Anil Kumar Pillai (Alternate)
Ultra Tech Cement Ltd, Mumbai Shri Surya Valluri
Dr M. R. Kalgal (Alternate)
Voluntary Organization in Interest of Shri M. A. U. Khan
Consumer Education, New Delhi Shri B. Mukhopadhyay (Alternate)
In personal capacity [B-803, Oberoi Shri A. K. Jain
Exquisite, Oberoi Garden City, Goregaon
(East), Mumbai]
In personal capacity (36, Old Sneh Nagar, Shri L. K. Jain
Wardha Road, Nagpur)

11
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Organization Representative(s)
In personal capacity (EA-92, Maya Enclave, Shri R. C. Wason
Hari Nagar, New Delhi)
BIS Directorate General Shri Sanjay Pant, Scientist ‘F’ and Head (Civil Engineering)
[ Representing Director General ( Ex-officio ) ]

Member Secretaries
Shri S. Arun Kumar
Scientist ‘E’ (Civil Engineering), BIS

Shri Milind Gupta


Scientist ‘C’ (Civil Engineering), BIS
and

Shrimati Divya S.
Scientist ‘C’ (Civil Engineering), BIS

Concrete Subcommittee, CED 2:2


Organization Representative(s)
In Personal Capacity (Grace Villa, Kadamankulam Shri Jose Kurian (Convener)
P.O., Thiruvalla 689583)
ACC Limited, Mumbai Shri Prahlad Majumdar
Shri Anil Kulkarni (Alternate)
Ambuja Cements Limited, Ahmedabad Shri Umesh P. Soni
Shri Sukuru Ramarao (Alternate)
AFCONS Infrastructure Limited, Mumbai Shri Manish Mokal
Association of Consulting Civil Engineers (India), Shri Avinash D. Shirode
Bengaluru Shri K. K. Meghashyam (Alternate)
Atomic Energy Regulatory Board, Mumbai Shri L. R. Bishnoi
Shri Sourav Acharya (Alternate)
Building Materials and Technology Promotion Council, Shri Pankaj Gupta
New Delhi
Bureau of Design for Hydel and Irrigation Project, Shri S. K. Khare
Bhopal Shri Bhagwati Prasad Gupta (Alternate)
Bureau Veritas India Ltd, Mumbai Representative
Central Public Works Department, New Delhi Shri D. K. Garg
Shri Rajesh Khare (Alternate)
Central Soil and Materials Research Station, Shri Rajeev Kumar
New Delhi Shri Raj Kumar (Alternate)
Creative Design Consultants and Engineers Pvt Ltd, Shri Aman Deep Garg
Ghaizabad Shri Manik Chatterjee (Alternate)
CSIR ‒ Central Building Research Institute, Roorkee Dr Rajesh Deolia
Shri H. C. Arora (Alternate)
CSIR ‒ Central Road Research Institute, New Delhi Shri J. B. Sengupta
Shri Satish Pandey (Alternate)
CSIR ‒ Structural Engineering Research Centre Dr B. H. Bharathkumar
Chennai Dr P. Srinivasan (Alternate)

12
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Organization Representative(s)
Department of Science and Technology, Ministry of Shri S. S. Kohli
Science and Technology, New Delhi
Elkem South Asia Pvt Ltd, Navi Mumbai Shri Brajesh Malviya
Shri Surendra Sharma (Alternate)
Engineers India Limited, New Delhi Shri Rajanji Srivastava
Shri Anurag Sinha (Alternate)
Gammon Engineers & Contractors Pvt Ltd, Mumbai Shri Sudeesh Rajendran
Hindustan Constrution Company Ltd, Mumbai Shri Satish Kumar Sharma
Shri Khatarbatcha Jimmetain (Alternate)
Indian Concrete Institute, Chennai Shri K. C. Tayade
Secretary General (Alternate)
Indian Institute of Technology Delhi, New Delhi Dr B. Bhattacharjee
Dr Shashank Bishnoi (Alternate)
Indian Institute of Technology Kanpur, Kanpur Dr Sudhir Mishra
Indian Institute of Technology Madras, Chennai Dr Manu Santhanam
Dr Radhakrishna G. Pillai (Alternate)
Indian Institute of Technology Roorkee, Roorkee Representative
Indian Society of Structural Engineers, Mumbai Shri Umesh Joshi
Shri Hemant Vadalkar (Alternate)
Irrigation and Power Research Institute, Amritsar Chief Engineer (Research)
Research Officer (Alternate)
Larsen and Toubro Limited, ECC Division, Chennai Dr B. Sivarama Sarma
Shri S. Manohar (Alternate)
Military Engineer Services, Engineer-in-Chief’s Maj Gen S. K. Srivastav
Branch, Integrated HQ of MoD (Army), New Delhi Shri Man Singh (Alternate)
Ministry of Road Transport & Highways, New Delhi Shri A. P. Pathak
Shri A. K. Pandey (Alternate)
NBCC (India) Limited, New Delhi Shri H. S. Yadav
Shri Arun Kumar Sharma (Alternate)
National Council for Cement and Building Materials, Shri V. V. Arora
Ballabgarh Shri P. N. Ojha (Alternate)
National Institute of Technology Warangal, Warangal Dr C. B. Kameswara Rao
Dr D. Rama Seshu (Alternate)
Nuclear Power Corporation of India Limited, Mumbai Shri Arvind Shrivastava
Shri N. M. Rao (Alternate)
Pidilite Industries Limited, Mumbai Dr Suguna Naik
Ready Mixed Concrete Manufacturers’ Association, Shri Vijaykumar R. Kulkarni
Mumbai Shri Srirang Sondur (Alternate)
Research, Design & Standards Organization Jt Director Stdrs (B&S)/CB-I
(Ministry of Railways), Lucknow Jt Director Stdrs (B&S)/CB-II (Alternate)
RDC Concrete (India) Pvt Ltd, Thane Shri Anil Banchhor
Shri Simranjit Singh (Alternate)
Shapoorji Pallonji and Company Private Limited, Shri Girish Bonde
Mumbai Shri D. N. Vishwanath (Alternate)
Tandon Consultants Pvt Limited, New Delhi Shri Mahesh Tandon
Shri Vinay Gupta (Alternate)

13
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Organization Representative(s)
Tata Consulting Engineers Limited, Mumbai Shri S. N. Diwakar
Shri Manos Kumar De (Alternate)
Ultra Tech Cement Ltd, Mumbai Dr V. Ramachandra
Dr A. K. Singh (Alternate)
Water Resource Department, Govt. of Madhya Shri S. K. Khare
Pradesh, Mumbai Shri B. P. Gupta (Alternate)
In personal capacity (452, Sector 14, Sonipat, Shri R. K. Jain
Haryana)
In personal capacity (36, Old Sneh Nagar, Wardha Shri L. K. Jain
Road, Nagpur)
In personal capacity [B-803, Oberoi Exquisite, Oberoi Shri A. K. Jain
Garden City, Goregaon (East), Mumbai]
In personal capacity (EA-92, Maya Enclave, Hari Shri R. C. Wason
Nagar, New Delhi)
In personal capacity (M1 F1 VGN Minerva Apartments, Dr C. Rajkumar
Guruswamy Road, Nolambur, Chennai)

Panel for Revision of Indian Standards on Test Methods for Concrete, CED 2:2/P7

Organization Representative(s)
In Personal Capacity (EA-92, Maya Enclave, Hari Shri R. C. Wason (Convener)
Nagar, New Delhi 110064)
ACC Limited, Mumbai Shri Avijit Chaubey
Shri Prahalad Majumdar (Alternate)
AIMIL Ltd, New Delhi Dr V. M. Sharma
Bureau Veritas India Limited, Bengaluru Representative
Central Public Works Department, New Delhi Shri Ajay Prakash Mathur
Shri Naveen Kumar Bansal (Alternate)
Central Soil and Materials Research Station, Shri U. S. Vidyarthi
New Delhi
Contruction Diagnostic Centre Pvt Ltd, Pune Shri Ravi Ranade
CSIR ‒ Central Building Research Institute, Roorkee Shri S. K. Singh
Ms M. Surya (Alternate)
CSIR ‒ Central Road Research Institute, New Delhi Representative
CSIR ‒ Structural Engineering Research Centre, Dr S. Bhaskar
Chennai Dr P. Srinivasan (Alternate)
Hindustan Construction Company Ltd, Mumbai Shri Satish Kumar Sharma
Shri Khatarbatcha Jimmetain (Alternate)
Hydraulic & Engineering Instrument, New Delhi Representative
Indian Concrete Institute, New Delhi Shri Ashok Kumar Tiwari
Indian Institute of  Technology Delhi, New Delhi Dr Shashank Bishnoi
Dr Supratic Gupta (Alternate)
Indian Institute of  Technology Madras, Chennai Dr Radhakrishna G. Pillai
Dr Ravindra Gettu (Alternate)
Larsen & Toubro Ltd, ECC Division, Chennai Shri B. Sivarama Sarma
Shri S. Manohar (Alternate)

14
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

IS 516 (Part 1/Sec 1) : 2021

Organization Representative(s)
National Council for Cement and Building Materials, Shri V. V. Arora
Ballabgarh Shri Puneet Kaura (Alternate)
Nuclear Power Corporation of India Ltd, Mumbai Shri Arvind Shrivastava
Shri A. K. Laharia (Alternate)
RDC Concrete (India) Pvt Ltd, Mumbai Shri Anil Banchhor
Shri Navneet Nair (Alternate)
Ready Mixed Concrete Manufacturers’ Association, Shri Vijaykumar R. Kulkarni
Mumbai Shri N. G. Muralidharan (Alternate)
Stedrant Technoclinic Pvt Ltd, Bengaluru Dr R. Nagendra
Shri Sunil V. Sonnad (Alternate)
Unique Engineering Testing and Advisory Services, Shri Hitesh Desai
Surat Shri Nehal H. Desai (Alternate)
In personal capacity (50, Mangla Apartments Kalkaji, Dr S. C. Maiti
New Delhi)

In personal capacity (Type IV/17, President’s Estate, Shri K. H. Babu


New Delhi)
In personal capacity (Grace Villa, Kadamankulam P.O., Shri Jose Kurian
Thiruvalla)
In personal capacity (624, Ranisatinagar, Lane 6, Lodhi Dr P. S. Gahlot
Marg, Ajmer Road, Jaipur)

15
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

(Continued from second cover)

This revision has been taken up to incorporate the modifications found necessary in the light of experience gained
in its use and also to bring it in line with the latest development on the subject nationally as well as internationally.
Significant modifications in this revision include,
a) all the provisions relating to compression testing of cubical and cylindrical specimens have been brought
under this standard. The capping details of cylindrical specimens have been elaborated.
b) arrangement of loading of flexural test specimens has been simplified. A new figure has been included
indicating the failure types clearly.
c) the formula for split tensile strength for cubical specimens has been included.
The composition of the Committee responsible for the formulation of this standard is given in Annex A.
In reporting the result of a test or analysis made in accordance with this standard, if the final value observed or
calculated, is to be rounded off, it shall be done in accordance with IS 2 : 1960 ‘Rules for rounding off numerical
values ( revised )’. The number of significant places retained in the rounded off value should be the same as that
specified value in this standard.
Free Standard provided by BIS via BSB Edge Private Limited to Rameshwar Dayal -
Alwar([email protected]) 157.41.150.245 [for non-commercial use only].

Bureau of Indian Standards

BIS is a statutory institution established under the Bureau of Indian Standards Act, 2016 to promote harmonious
development of the activities of standardization, marking and quality certification of goods and attending to
connected matters in the country.

Copyright

BIS has the copyright of all its publications. No part of these publications may be reproduced in any form without
the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing the
standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating to
copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards: Monthly Additions’.
This Indian Standard has been developed from Doc No.: CED 02 (13828).

Amendments Issued Since Publication


Amend No. Date of Issue Text Affected

BUREAU OF INDIAN STANDARDS


Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002
Telephones: 2323 0131, 2323 3375, 2323 9402 Website: www.bis.gov.in
Regional Offices: Telephones
Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg
NEW DELHI 110002 { 2323 7617
2323 3841
Eastern : 1/14 C.I.T. Scheme VII M, V.I.P. Road, Kankurgachi
KOLKATA 700054 { 2337 8499, 2337 8561
2337 8626, 2337 9120
Northern : Plot No. 4-A, Sector 27-B, Madhya Marg
CHANDIGARH 160019 { 265 0206
265 0290
Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113
{ 2254 1216, 2254 1442
2254 2519, 2254 2315
Western : Manakalaya, E9 MIDC, Marol, Andheri (East)
MUMBAI 400093 { 2832 9295, 2832 7858
2832 7891, 2832 7892
Branches : AHMEDABAD. BENGALURU. BHOPAL. BHUBANESHWAR. COIMBATORE.
DEHRADUN. DURGAPUR. FARIDABAD. GHAZIABAD. GUWAHATI.
HYDERABAD. JAIPUR. JAMMU. JAMSHEDPUR. KOCHI. LUCKNOW.
NAGPUR. PARWANOO. PATNA. PUNE. RAIPUR. RAJKOT. VISAKHAPATNAM.
Published by BIS, New Delhi

You might also like