RCA-SERIES
www.addison-hvac.com
Telephone: +1.407.292.4400
40.0
Electric Power (W) 3,380 3,575 3,780
Total Capacity (Btu/h) 46,500 44,500 43,000
45.0
Electric Power (W) 3,400 3,590 3,800
Total Capacity (Btu/h) 50,500 48,500 47,000
50.0
Electric Power (W) 3,420 3,615 3,815
Total Capacity (Btu/h) 54,500 52,500 50,500
55.0
Electric Power (W) 3,440 3,635 3,840
2
UNIT DATA - RCA061
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE Total Capacity (Btu/h) 55,600
DATA
Electric Power (W) 4,244
NET COOLING
Energy Efficiency Ratio (EER) 13.1
40.0
Electric Power (W) 4,355 4,530 4,785
Total Capacity (Btu/h) 55,000 51,000 50,000
45.0
Electric Power (W) 4,380 4,615 4,865
Total Capacity (Btu/h) 57,000 56,000 54,000
50.0
Electric Power (W) 4,435 4,675 4,930
Total Capacity (Btu/h) 62,000 60,000 58,000
55.0
Electric Power (W) 4,530 4,770 5,035
3
UNIT DATA - RCA071
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
40.0
Electric Power (W) 6,415 6,720 7,045
Total Capacity (Btu/h) 71,000 69,000 66,000
45.0
Electric Power (W) 6,600 6,860 7,245
Total Capacity (Btu/h) 77,000 74,000 71,000
50.0
Electric Power (W) 6,695 7,005 7,330
Total Capacity (Btu/h) 82,000 80,000 77,000
55.0
Electric Power (W) 6,840 7,150 7,480
4
UNIT DATA - RCA101
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
Total Capacity (Btu/h) 107,500
DATA
Electric Power (W) 9,430
NET COOLING
Energy Efficiency Ratio (EER) 11.4
40.0
Electric Power (W) 9,130 9,515 10,075
Total Capacity (Btu/h) 105,000 101,000 98,000
45.0
Electric Power (W) 9,300 9,750 10,225
Total Capacity (Btu/h) 113,000 109,000 106,000
50.0
Electric Power (W) 9,465 9,935 10,395
Total Capacity (Btu/h) 122,000 118,000 113,000
55.0
Electric Power (W) 9,660 10,110 10,680
5
UNIT DATA - RCA141
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
40.0
Electric Power (W) 12,150 12,845 13,340
Total Capacity (Btu/h) 133,000 129,000 124,000
45.0
Electric Power (W) 12,535 13,005 13,615
Total Capacity (Btu/h) 143,000 139,000 134,000
50.0
Electric Power (W) 12,710 13,295 13,905
Total Capacity (Btu/h) 153,000 148,000 144,000
55.0
Electric Power (W) 13,070 13,710 14,210
6
UNIT DATA - RCA171
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
Total Capacity (Btu/h) 165,900
DATA
Electric Power (W) 13,598
NET COOLING
Energy Efficiency Ratio (EER) 12.2
40.0
Electric Power (W) 12,400 13,015 13,670
Total Capacity (Btu/h) 170,000 164,000 158,000
45.0
Electric Power (W) 12,560 13,170 13,820
Total Capacity (Btu/h) 183,000 177,000 171,000
50.0
Electric Power (W) 12,775 13,390 14,015
Total Capacity (Btu/h) 198,000 191,000 185,000
55.0
Electric Power (W) 12,980 13,560 14,180
7
UNIT DATA - RCA201
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
40.0
Electric Power (W) 14,740 15,415 16,175
Total Capacity (Btu/h) 197,000 191,000 185,000
45.0
Electric Power (W) 14,955 15,665 16,355
Total Capacity (Btu/h) 213,000 207,000 199,000
50.0
Electric Power (W) 15,170 15,865 16,635
Total Capacity (Btu/h) 230,000 223,000 215,000
55.0
Electric Power (W) 15,390 16,100 16,850
8
UNIT DATA - RCA271
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
Total Capacity (Btu/h) 241,300
DATA
Electric Power (W) 22,343
NET COOLING
Energy Efficiency Ratio (EER) 10.8
40.0
Electric Power (W) 19,590 20,570 21,620
Total Capacity (Btu/h) 252,000 243,000 236,000
45.0
Electric Power (W) 20,020 21,000 21,895
Total Capacity (Btu/h) 273,000 264,000 254,000
50.0
Electric Power (W) 20,360 21,330 22,365
Total Capacity (Btu/h) 294,000 284,000 275,000
55.0
Electric Power (W) 20,720 21,700 22,730
9
UNIT DATA - RCA361
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
40.0
Electric Power (W) 24,090 25,140 26,135
Total Capacity (Btu/h) 283,000 274,000 264,000
45.0
Electric Power (W) 24,410 25,485 26,620
Total Capacity (Btu/h) 306,000 296,000 285,000
50.0
Electric Power (W) 24,890 26,010 27,190
Total Capacity (Btu/h) 332,000 320,000 309,000
55.0
Electric Power (W) 25,085 26,360 27,570
10
UNIT DATA - RCA421
RATED IN ACCORDANCE TO AHRI STANDARD 365-2009.
PERFORMANCE
Total Capacity (Btu/h) 369,700
DATA
Electric Power (W) 33,609
NET COOLING
Energy Efficiency Ratio (EER) 11.0
40.0
Electric Power (W) 32,350 33,705 35,465
Total Capacity (Btu/h) 359,000 350,000 338,000
45.0
Electric Power (W) 33,355 34,440 35,885
Total Capacity (Btu/h) 391,000 375,000 365,000
50.0
Electric Power (W) 33,900 35,550 36,695
Total Capacity (Btu/h) 421,000 407,000 391,000
55.0
Electric Power (W) 34,815 36,165 37,925
11
TYPICAL WIRING DIAGRAM
Condensing Unit
Condensing L1
Control Panel
Unit L2
Disconnect
R 24VAC, Switched
L3
Y Compressor
G Supply Fan
C 24VAC, Common, Unswitched
NOTES:
1. All electrical wiring and connections, including electrical grounding must comply with:
a. United States: Refer to NFPA 70- latest revision, National Electrical Code, and local ordinances.
b. Canada: Refer to CSA C22.1, Part 1- latest revision, Canadian Electrical Code and local ordinances.
2. Class 1 circuit
3. Condensing unit disconnect is not provided with condensing unit as standard. Disconnect may be obtained from factory as optional equipment or
provided by others.
Disconnect
Disconnect
Outside Air
or Return Air Supply Air
Air Handler
NOTES:
1. Condensing unit disconnect is not provided with condensing unit as standard. Disconnect may be obtained from factory as optional equipment or
provided by others.
2. Air handler, air handler disconnect, interconnecting control wiring, all refrigerant line piping and sleeve/flashing materials are by others.
3. Suction, hot gas bypass, and hot gas reheat lines should be insulated with 5/8” minimum thickness closed cell foam insulation. Liquid line exposed
to high ambient temperatures should be insulated 5/8” minimum thickness closed cell foam insulation.
12
TYPICAL INSTALLATION WITH CONDENSING UNIT ON BOTTOM
Optional Hot
Gas Reheat
NOTES:
1. To prevent oil migration, lines should slope downwards towards the condensing unit and should slope downward away from the air handler.
2. Vertical risers greater than 4' in height should have a “P” trap installed at the base of the air handler.
3. Vertical risers greater than 20' in height require an extra “P” trap for every 20' of riser height in addition to the “P” trap installed at the base of the
air handler. The trap is inverted at the top of the vertical rise.
Suction
Liquid
Optional Hot Gas
Reheat
NOTES:
1. To prevent oil migration, lines should slope downwards towards the condensing unit and should slope downward away from the air handler.
2. Vertical risers greater than 4' in height should have a “P” trap installed at the base of the air handler.
3. Vertical risers greater than 20' in height require an extra “P” trap for every 20' of riser height in addition to the “P” trap installed at the base of the
air handler. The trap is inverted at the top of the vertical rise.
13
DIMENSIONS - RCA 051/061/071
COIL
ELECTRICAL
COIL
B
CONTROLS
LIQUID
C Ø E OPTIONAL HOT GAS REHEAT
D
SUCTION OPTIONAL HOT GAS BYPASS
COMPRESSOR
F Q
P
N
M
L
H A K R
A B C D E F G H K L M N P Q R
(in) 3.00 47.38 42.25 52.25 0.75 40.38 39.13 2.00 3.50 5.00 9.00 13.00 20.00 3.25 53.38
14
DIMENSIONS - RCA 101/141
A
TOP VIEW MULTI-DIMENSIONAL VIEW
COIL
COIL
COIL
B
ELECTRICAL
OPTIONAL HOT
GAS BYPASS
LIQUID
C
D ØE SUCTION OPTIONAL HOT GAS REHEAT
COMPRESSOR
P
F
N
G
M
A
L
K
J
A H Q
A B C D E F G H J K L M N P Q
(in) 3.00 68.00 45.50 55.50 0.88 41.38 40.13 49.50 4.00 5.56 8.56 8.38 11.38 14.13 74.00
15
DIMENSIONS - RCA 171/201/271
COIL
LIQUID
J
B H
G
F
E
D A
A B C D E F G H J
(in) 64.25 52.88 51.38 79.00 22.00 25.50 29.00 16.00 21.00
16
DIMENSIONS - RCA 361/421
COIL
OPTIONAL HOT
GAS BYPASS
SUCTION LIQUID
B H
C
G
F
E
D A
A B C D E F G H J
(in) 101.25 53.63 52.13 84.00 22.00 25.50 29.00 16.00 21.00
17
REFERENCE INFORMATION
AMBIENT TEMPERATURE CORRECTION FACTORS
AMBIENT TEMPERATURE (°F) 85 90 95 100 105 110 115
TOTAL CAPACITY (Btu/h) 1.05 1.03 1.00 0.98 0.95 0.91 0.87
SENSIBLE CAPACITY (Btu/h) 1.03 1.02 1.00 0.99 0.97 0.97 0.93
ELECTRIC POWER (W) 0.95 0.98 1.00 1.03 1.05 1.08 1.11
RECOMMENDED REFRIGERANT LINE SIZES- AIR HANDLER BELOW CONDENSING UNIT (IN OD)
0-25 FT. EQUIVALENT LENGTH 26-50 FT. EQUIVALENT LENGTH
NOMINAL CAPACITY (Btu/h) HOT GAS HOT GAS HOT GAS HOT GAS
SUCTION LIQUID SUCTION LIQUID
REHEAT BYPASS REHEAT BYPASS
36,000 5/8, 5/8 3/8 1/2 3/8 3/4, 3/4 1/2 1/2 3/8
48,000 3/4, 3/4 3/8 5/8 3/8 3/4, 3/4 1/2 5/8 3/8
60,000 3/4, 3/4 1/2 5/8 1/2 7/8, 7/8 1/2 5/8 1/2
72,000 7/8, 7/8 1/2 5/8 1/2 7/8, 7/8 1/2 5/8 1/2
84,000 7/8, 7/8 1/2 3/4 1/2 1-1/8, 7/8 1/2 3/4 1/2
96,000 7/8, 7/8 1/2 3/4 1/2 1-1/8, 7/8 1/2 3/4 1/2
120,000 1-1/8, 7/8 1/2 3/4 5/8 1-3/8, 1-1/8 5/8 3/4 5/8
150,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-3/8, 1-1/8 5/8 7/8 5/8
180,000 1-1/8, 1-1/8 5/8 7/8 5/8 1-3/8, 1-3/8 5/8 7/8 5/8
220,000 1-3/8, 1-3/8 5/8 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 3/4
250,000 1-3/8, 1-3/8 5/8 1-1/8 3/4 1-3/8, 1-3/8 3/4 1-1/8 3/4
300,000 1-3/8, 1-3/8 3/4 1-1/8 3/4 1-5/8, 1-3/8 3/4 1-1/8 3/4
360,000 1-3/8, 1-5/8 3/4 1-1/8 7/8 1-5/8, 1-5/8 7/8 1-1/8 7/8
420,000 1-5/8, 1-5/8 3/4 1-3/8 7/8 1-5/8, 1-5/8 7/8 1-3/8 7/8
18
REFERENCE INFORMATION
RECOMMENDED REFRIGERANT LINE SIZES- AIR HANDLER LEVEL WITH OR ABOVE CONDENSING UNIT (IN OD)
0-25 FT. EQUIVALENT LENGTH 26-50 FT. EQUIVALENT LENGTH
NOMINAL CAPACITY (Btu/h) HOT GAS HOT GAS HOT GAS HOT GAS
SUCTION LIQUID SUCTION LIQUID
REHEAT BYPASS REHEAT BYPASS
36,000 5/8 3/8 1/2 3/8 3/4 3/8 1/2 3/8
48,000 3/4 3/8 5/8 3/8 7/8 1/2 5/8 3/8
60,000 3/4 1/2 5/8 1/2 7/8 1/2 5/8 1/2
72,000 7/8 1/2 5/8 1/2 1-1/8 1/2 5/8 1/2
84,000 7/8 1/2 3/4 1/2 1-1/8 5/8 3/4 1/2
96,000 7/8 1/2 3/4 1/2 1-1/8 5/8 3/4 1/2
120,000 1-1/8 5/8 3/4 5/8 1-1/8 5/8 3/4 5/8
150,000 1-1/8 5/8 7/8 5/8 1-3/8 3/4 7/8 5/8
180,000 1-1/8 3/4 7/8 5/8 1-3/8 3/4 7/8 5/8
220,000 1-3/8 3/4 1-1/8 3/4 1-3/8 7/8 1-1/8 3/4
250,000 1-3/8 3/4 1-1/8 3/4 1-3/8 7/8 1-1/8 3/4
300,000 1-3/8 7/8 1-1/8 3/4 1-5/8 7/8 1-1/8 3/4
360,000 1-3/8 7/8 1-1/8 7/8 1-5/8 7/8 1-1/8 7/8
420,000 1-5/8 1-1/8 1-3/8 7/8 1-5/8 1-1/8 1-3/8 7/8
NOTES:
1. Line sizes are calculated assuming single scroll compressors in Models 051-201 and tandem scroll compressors in Models 271-421. Contact the factory for
any other compressor configuration.
2. All piping must comply with standard refrigeration piping techniques. Consult the American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE) Handbook-Refrigeration.
3. Suction, hot gas bypass and hot gas reheat lines should be insulated with a 5/8” minimum thickness closed cell foam insulation. Liquid line exposed to
high ambient temperatures should be insulated with a 5/8” minimum thickness closed cell foam insulation.
4. Maximum suction line vertical lift is 60’. Loop piping to the top of the coil.
5. Maximum liquid line vertical lift is 60’.
6. If ordered, hot gas reheat and hot gas bypass require only one line.
7. Standard hot gas bypass is not recommended for use with greater than 75’ of equivalent line length. Internal hot gas bypass should be used as an
alternative.
8. Contact factory for applications with digital scroll compressors.
9. Contact factory for layouts requiring more than 75’ of actual line length.
19
THANK YOU FOR YOUR BUSINESS
Installation Code and Quarterly Inspections: All installation and service of ADDISON® equipment must be performed by a contractor qualified in the
installation and service of equipment sold and supplied by Addison and conform to all requirements set forth in the ADDISON® manuals and all applicable
governmental authorities pertaining to the installation, service, operation and labeling of the equipment. To help facilitate optimum performance and safety,
Addison recommends that a qualified contractor conduct, at a minimum, quarterly inspections of your ADDISON® equipment and perform service where
necessary, using only replacement parts sold and supplied by Addison.
Further Information: Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through
ADDISON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.
These products (with the exception of the CGTH and UHA[X][S] 30 - 75) are not for residential use.
This document is intended to assist licensed professionals in the exercise of their professional judgment.
Specifications are subject to change without notice.