Current Driver/Repeater KFD0-CS-Ex2.51P: Function

This document summarizes a 2-channel isolated barrier that transfers DC signals between hazardous and non-hazardous areas. It has a 24V DC loop powered supply, accepts current inputs between 0-40mA, and provides 1% accuracy signal transfer with reverse polarity protection. It is rated for use in Zone 0, 1, 2 hazardous areas and can achieve up to SIL 2 safety integrity for fire alarm and smoke detector signal monitoring applications.

Uploaded by

Mas Agus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
136 views4 pages

Current Driver/Repeater KFD0-CS-Ex2.51P: Function

This document summarizes a 2-channel isolated barrier that transfers DC signals between hazardous and non-hazardous areas. It has a 24V DC loop powered supply, accepts current inputs between 0-40mA, and provides 1% accuracy signal transfer with reverse polarity protection. It is rated for use in Zone 0, 1, 2 hazardous areas and can achieve up to SIL 2 safety integrity for fire alarm and smoke detector signal monitoring applications.

Uploaded by

Mas Agus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Current Driver/Repeater

2
KFD0-CS-Ex2.51P
< 2-channel isolated barrier
< 24 V DC supply (loop powered)
< Current input/output 0 mA ... 40 mA
< I/P or transmitter power supply
< Accuracy 1 %
< Reverse polarity protection
< Up to SIL 2 acc. to IEC 61508

2-channel

Function

This isolated barrier is used for intrinsic safety applications.


The device transfers DC signals of fire alarms and smoke alarms from the hazardous area to the non-hazardous area. The device can also be
used to control I/P converters, valves, indicators, and audible alarms.
A reverse polarity protection prevents damage to the device caused by faulty wiring.
The device is loop powered. From the control side no additional power supply has to be connected.
Use the technical data to verify that proper voltage is available to the field devices.

Connection

KFD0-CS-Ex2.51P

4+ 9+
I

I
mA
P

V
5- 10-
8-

1+ 11+
I

II
mA
P

V
2- 12-
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 294987_eng.pdf

Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2

Technical Data
General specifications
Signal type Analog input/analog output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Rated voltage Ur loop powered
Control circuit
Connection terminals 12-, 11+; 8-, 10-, 9+
Voltage 4 ... 35 V DC
Current 0 ... 40 mA

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 1
Current Driver/Repeater KFD0-CS-Ex2.51P
Technical Data
Power dissipation at 40 mA and Uin < 22 V: 700 mW per channel
at 40 mA and Uin > 22 V: 1.2 W per channel
Field circuit
Connection terminals 1+, 2-; 4+, 5-
Voltage for 4 V < Uin < 24 V: ≥ Uin - (0.37 x current in mA) - 1.0
for Uin > 24 V: ≥ 21 V - (0.36 x current in mA)
Short-circuit current at Uin > 24 V: ≤ 65 mA
Transfer current ≤ 40 mA
Transfer characteristics
Accuracy 1%
Deviation
After calibration ≤ ± 200 µA; incl. calibration, linearity, hysteresis and load fluctuations at the field side
up to a load of 1 kΩ and current ≤ 20 mA at 20 °C (68 °F)
Influence of ambient temperature ≤ ± 2 µA/K at Uin ≤ 20 V; ≤ ± 5 µA/K at Uin > 20 V
Rise time ≤ 5 ms at bounce from 4 ... 20 mA and Uin < 24 V
Galvanic isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Indicators/settings
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2012
EN 61326-3-2:2008
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2012
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate BAS 98 ATEX 7343 X
Marking 1 II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C)
Voltage Uo 25.2 V
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 294987_eng.pdf

Current Io 93 mA
Power Po 585 mW
Control circuit
Maximum safe voltage Um 250 V eff (Attention! The rated voltage can be lower.)
Field circuit
Maximum safe voltage Um 250 V eff (Attention! The rated voltage can be lower.)
Certificate TÜV 99 ATEX 1499 X
Marking 1 II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0437

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 2
Current Driver/Repeater KFD0-CS-Ex2.51P
Technical Data
UL approval
Control drawing 116-0438 (cULus)
IECEx approval
IECEx certificate IECEx BAS 05.0004X
IECEx CML 19.0040X
IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals
where applicable. For information see www.pepperl-fuchs.com.

Assembly

Front view
Removable terminals
blue

1 2 3
4 5 6

KFD0-CS-Ex2.51P

7 8 9
10 11 12
Removable terminals
green
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 294987_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 3
Current Driver/Repeater KFD0-CS-Ex2.51P

Application
The device is used for isolation of power loops for the control of positioner, I/P converters etc. A current source is connected to
the safe area terminals.
The device is used for isolation of a current signal from fire detectors or similar sensors. In this case, a voltage source can be
connected to the safe area terminals. A specific measurement current across a passive sensor can be measured in the safe area
with a series resistor (min. 50 ). When a voltage supply is used, the measuring resistor can also provide current limitations.
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 294987_eng.pdf