Current Driver/Repeater KFD0-CS-Ex2.51P: Function
Current Driver/Repeater KFD0-CS-Ex2.51P: Function
2
KFD0-CS-Ex2.51P
< 2-channel isolated barrier
< 24 V DC supply (loop powered)
< Current input/output 0 mA ... 40 mA
< I/P or transmitter power supply
< Accuracy 1 %
< Reverse polarity protection
< Up to SIL 2 acc. to IEC 61508
2-channel
Function
Connection
KFD0-CS-Ex2.51P
4+ 9+
I
I
mA
P
V
5- 10-
8-
1+ 11+
I
II
mA
P
V
2- 12-
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 294987_eng.pdf
Zone 0, 1, 2 Zone 2
Div. 1, 2 Div. 2
Technical Data
General specifications
Signal type Analog input/analog output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Rated voltage Ur loop powered
Control circuit
Connection terminals 12-, 11+; 8-, 10-, 9+
Voltage 4 ... 35 V DC
Current 0 ... 40 mA
Current Io 93 mA
Power Po 585 mW
Control circuit
Maximum safe voltage Um 250 V eff (Attention! The rated voltage can be lower.)
Field circuit
Maximum safe voltage Um 250 V eff (Attention! The rated voltage can be lower.)
Certificate TÜV 99 ATEX 1499 X
Marking 1 II 3G Ex nA II T4 [device in zone 2]
Galvanic isolation
Field circuit/control circuit safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0437
Assembly
Front view
Removable terminals
blue
1 2 3
4 5 6
KFD0-CS-Ex2.51P
7 8 9
10 11 12
Removable terminals
green
Release date: 2020-09-23 Date of issue: 2020-09-23 Filename: 294987_eng.pdf
Application
The device is used for isolation of power loops for the control of positioner, I/P converters etc. A current source is connected to
the safe area terminals.
The device is used for isolation of a current signal from fire detectors or similar sensors. In this case, a voltage source can be
connected to the safe area terminals. A specific measurement current across a passive sensor can be measured in the safe area
with a series resistor (min. 50 ). When a voltage supply is used, the measuring resistor can also provide current limitations.