Introduction
This installation guide is intended for technicians involved in the installation of the HCU option
board in Enraf series 854 ATG / XTG servo gauges, 873 SmartRadar and 877 Field Display &
Interface. The technician must have basic technical skills and knowledge of safety regulations and
explosion proof equipment in hazardous areas.
Note:
Read carefully the chapter safety in the installation guide of the specific instrument before
continuing installation of the HCU optional board.
When the HCU option board is used to replace one of the above mentioned option boards, please
note that an XPU-2 board is required in the servo gauges 854 ATG and 854 XTG.
Notes:
1 When the HCU board is used to replace an option board with average temperature
measurement, please note the following.
The 863 MRT with 862 MIR or the 864 MTT with 864 MIT temperature connection cannot
be maintained:
The 864 MTT can be connected to the 762 VITO MTT Interface which interfaces to the
HCU option board;
The 863 MRT can be connected to the 762 VITO MRT Interface which interface to the
HCU option board.
2 The optional data transmission channel on the XPU-2 board (i.s. channel for 977 TSI or
RS-232C/RS-485 channel) can only function when Backplane-2 is installed in the gauge.
Backplane-2 is standard installed in instruments:
854 ATG with series number: 854-20-400 and higher;
854 XTG with series number: 894-02-001 and higher;
873 SmartRadar; all gauges including XPU-2 board;
877 FDI with series number: 877-17-001 and higher.
The HCU option board can be used to replace an existing option board in the 877 FDI.
Please take care about the notes 1 and 2 above and be informed that when the water bottom
measurement function is added, an XPU-2 board is required.
Page 2
Installation
Installation - common
Warning
Make sure that all power to the instrument is switched off before opening the cover(s).
Failure to do so may cause danger to persons or damage the equipment.
The cover(s) must be closed before switching on the power.
Caution
Do not damage the thread of the cover(s) and instrument and keep the threads free of dirt.
After opening, grease them lightly with anti seize grease.
When closing, turn the cover(s) counter-clockwise until the thread clicks in place, then turn
clockwise until the cover(s) is (are) fully closed.
Caution
Make sure that no dangerous quantities of combustible products are present in the working area.
HCU option 854 ATG 854 XTG 873 SmartRadar 877 FDI
board p/n Appendix B Appendix C Appendix D Appendix E
Note:
When replacing a previous model option board in the 854 ATG by one of the HCU boards with
part no’s: S0854933 or S0854934, it is also required to change the i.s. wire plug for part no.
S2695241 with 8 blue wires.
For part number S0854933 with functions spot temperature Pt100 and HART device(s), the 4
blue wires in the 854 ATG and 854 XTG can be connected as per Fig. 7 and Fig. 13. Please
note the difference of the Ex-i parameters for the HART 1 channel.
Caution
Use only intrinsically safe Ex-approved blue terminals.