Description
The SIPROTEC 7UT82 transformer differential protection
has been designed specifically for the protection of two-
winding transformers. It is the main protection for the
transformer and contains many other protection and mon-
itoring functions. The additional protection functions can
also be used as backup protection for subsequent pro-
tected objects (such as short cables and lines, reactance
coil (shunt reactors)). The modular expandability of the
hardware supports you in this process. With its modular
structure, flexibility, and the high-performance DIGSI 5 en-
gineering tool, SIPROTEC 7UT82 offers future-oriented so-
lutions for protection, control, automation, monitoring,
and Power Quality – Basic.
SIPROTEC 7UT82 Transformer Differential Protec-
Main function 1 differential protection function tion (1/3 device = standard variant W1)
(standard or auto transformer) with ad-
ditional stabilization; up to 2 restricted Functions
ground-fault protection functions
DIGSI 5 permits all functions to be configured and com-
Usable measuring 2 x 3-phase current measuring points, bined as required.
points 2 x 1-phase current measuring points
• Transformer differential protection for two-winding
Inputs and outputs 1 predefined standard variant with
8 current transformers, 7 binary inputs,
transformers with versatile, additional protection
7 binary outputs functions
Hardware The 1/3 base module is available with • Transformer differential protection for phase-angle
flexibility the IO103 module; it is not possible to regulating transformers of the single core type
add 1/6 expansion modules, available
with large and small display • Universal usability of the permissible measuring
points
Housing width 1/3 × 19 inches
• Applicable from average up to extra-high voltage
Applications
• Protection of standard power transformers, auto
• Protection of special transformers (phase shifter, transformers, short lines, cables, shunt reactors and
FACTS and converter transformers, arc furnace trans- motors
formers, HVDC transformers)
• Increased sensitivity with near-neutral-point ground
• Backup protection for motor and generator differen- faults through a separate restricted ground-fault pro-
tial protection applications tection
• For protection of short cables and lines
Compact and efficient
• Flexible adaptation to the transformer vector group • Extensive cybersecurity functionality, such as role-
based access control (RBAC), protocolling security-re-
• Controlling closing and overexcitation processes
lated events, signed firmware or authenticated net-
• Safe behavior in case of current-transformer satura- work access IEEE 802.1X
tion with different degrees of saturation
• Simple, fast and secure access to the device via a
• Adaptive adaptation of the operate curve to the trans- standard Web browser to display all information and
former tap position diagnostic data, vector diagrams, single-line and de-
vice display pages
• Arc protection
• Time synchronization using IEEE 1588
• Graphical logic editor to create powerful automation
functions in the device • High-performance fault recording (buffer for a max.
record time of 80 s at 8 kHz or 320 s at 2 kHz)
• Single line representation in small or large display
• Auxiliary functions for simple tests and commission-
• Integrated electrical Ethernet RJ45 for DIGSI 5 and
ing.
IEC 61850 (reporting and GOOSE)
Benefits
• Up to 2 optional pluggable communication modules,
usable for different and redundant protocols (IEC • Compact and low-cost transformer differential protec-
61850-8-1, IEC 60870-5-103, IEC 60870-5-104, Mod- tion
bus TCP, DNP3 serial and TCP, PROFINET IO) • Safety due to powerful protection functions
• Serial protection data communication via optical fi- • Purposeful and easy handling of devices and software
bers, two wire connections and communication net- thanks to a user-friendly design
works (IEEE C37.94, and others), including automatic
switchover between ring and chain topology • Cybersecurity in accordance with NERC CIP and BDEW
Whitepaper requirements
• PQ-Basic: voltage unbalance; voltage changes: over-
voltage, dip, interruption; TDD, THD and Harmonics • Highest availability even under extreme environmen-
tal conditions by standard coating of the modules
• Reliable data transmission via PRP and HSR redun-
dancy protocols • Full compatibility between IEC 61850 Editions 1. 2.0
and 2.1