Technical Guide: ORBIT System Wiring Guide
Technical Guide: ORBIT System Wiring Guide
Technical Guide: ORBIT System Wiring Guide
2017/08/07
0 Summary of All Wiring Precautions
1. Power filter (PL-NF10A or other power filter) is required to block external noise on AC or DC power line. (3-2)
2. The two wires of DC (or AC) should be closed to each other. PVC insulated cable is recommended. (3-1)
3. Any electrical device (other than ORBIT device) is prohibited to connect to ORBIT.AC or ORBIT.DC line.(3-1)
4. ORBIT.AC line can be up to 200M. To extend ORBIT.AC to more than 200M, please add an ORBIT.AC repeater
(PL-RPT01). (4-2)
5. ORBIT.AC line can carry up to 32 ORBIT.AC devices. To extend more than 32 ORBIT.AC devices on the same line,
6. In large-scale installation, only signal isolators can be installed on the main line (backbone). All other devices
7. If central monitoring requires fast feedback from all ORBIT devices, we recommend that one Ethernet interface
2017/08/07
1 ORBIT Systems
ORBIT applies power line communication technology. ORBIT signal can be carried on DC 24V or AC 100-240V.
“ORBIT.AC” means the signal and AC power (100-240V) carried on an AC power line.
“ORBIT.DC” means that the signal and DC power (24V) on a DC power line.
ORBIT.AC and ORBIT.DC share the same format of commands. ORBIT.AC and ORBIT.DC can communicate to each
ORBIT system was called PLNET system or PLC system. Some products might still got “PLNET” or “PLC” on the
2. Easy wiring:
Both ORBIT.AC and ORBIT.DC cable are non-polarities. Therefore, the wiring is almost impossible to get wrong.
3. Bi-Directional Transmission
Able to get feedback and retrieve data from modules through ORBIT systems.
4. Desktop/Handheld GUI
Both desktop GUI and handheld GUI (iOS/Android) are available on ORBIT systems.
ORBIT.AC LED drivers feature advanced 16,384 steps dimming steps and remains non-flicker at 1% output.
2017/08/07
2 ORBIT Modules
PL-DPE100
PL-DPE200
PL-DPE200 shares the same function as PL-DPE100. There is no LCD display and buttons on PL-DPE200.
2017/08/07
PL-MXE101
ORBIT Commander is a GUI to configure ORBIT modules. The GUI requires an Ethernet to ORBIT interface to
ORBIT Commander
2017/08/07
2-2 ORBIT LED Drivers
Constant current , constant voltage, and different wattage models are available in ORBIT LED drivers.
2017/08/07
2-3 ORBIT Switch Packs/Relay Modules/Dimmers
2017/08/07
2-4 ORBIT Control Plates
ORBIT control plate is able to recall scenes or control channel levels on ORBIT system.
PL-CP110T
PL-CP310
2017/08/07
2-5 ORBIT Interfaces
In large scale system, ORBIT signal isolator is required to make the communication stable.
2017/08/07
PL-DP102II – DMX-512 to ORBIT.AC Interface
2017/08/07
2-6 ORBIT System Diagram
2017/08/07
2-6-2DMX-512 to ORBIT.AC
Through DMX-512 to ORBIT converting interface (PL-DP102II), you can control ORBIT.AC LED drivers by using any
DMX-512 controller.
2017/08/07
3 ORBIT Wiring Instruction
3-1-1 ORBIT.DC
1. ORBIT.DC is based on DC 24V. We recommend using PVC insulated cable (RVV cable) with at least 1.0mm core.
2. Please also consider the voltage drop in the application. The voltage of ORBIT.DC is 24V. The modules require at
3. The two wires (cores) should be closed to each other. Otherwise, the signal cannot be transmitted correctly.
3-1-2 ORBIT.AC
1. ORBIT.AC is based on AC 100-240V. We recommend using PVC insulated cable (RVV cable) power cable.
2. The two wires (cores) should be closed to each other. Otherwise, the signal cannot be transmitted.
4. Any other non-ORBIT.AC device is prohibited to connect to ORBIT.AC line. These devices could cause severe
2017/08/07
2017/08/07
3-2 Power Filter
ORBIT carries signal on AC/DC power line. Therefore, a power filter is required to isolate/filter external noises
Please note:
If ANY device other than ORBIT.AC devices connecting to ORBIT.AC line, it will cause signal interference and
2017/08/07
3-2-1 ORBIT.DC with Power Filter
Some ORBIT power supplier (PL-PW20-24) got built-in filter. You don’t need power filter with ORBIT power
supplier.
2017/08/07
3-2-3 Coupling ORBIT.AC and ORBIT.DC Signal
By using signal coupling connector, ORBIT.AC and ORBIT.DC signal can be communicate to each other.
2017/08/07
3-2-4 Coupling Different ORBIT.AC Lines
2017/08/07
4 ORBIT.AC Wiring Consideration
Please note:
If ANY device other than ORBIT.AC devices connecting to ORBIT.AC line, it will cause signal interference and
As mentioned before, a power filter (PL-NF10A) is required to filter the noise from AC power source.
PL-NF10A is able to afford 10A power consumption. If the power consumption is more than the power filter can
A power filter can connect up to 32 ORBIT.AC devices. If more than 32 ORBIT.AC devices (LED drivers) are
An ORBIT.AC line can be up to 200M. To extend more than 200M, please add an ORBIT.AC repeater (PL-RPT01).
2017/08/07
5 ORBIT.DC Wiring Consideration
As mentioned before, power filter (PL-NF10A) is required to filter the noise from DC power source. PL-NF10A is
able to afford 10A power consumption. If the power consumption is more than the power filter can afford, please
2017/08/07
6 Large Scale Installation
However, there are still some principle and limitations need to understand before the installation, especially in
1. An Ethernet to ORBIT interface can connect up to 256 ORBIT devices. Different Ethernet to ORBIT interfaces
If monitoring required fast feedback, we recommend an Ethernet to ORBIT interface should not connect more
3. The total distance of ORBIT.DC is up to 2000M. By adding a signal isolator (PL-ISO2/PL-ISO2II), the main line
extend another 2000M. The main line can extend to 10,000M. (Check the Main Line section in the diagram)
4. The main ORBIT line should only connect signal isolators. All control modules should connect behind the signal
5. The total distance of sub line is 100M. If 100M is not enough, please add an isolator on sub line. (Check the Sub
6. Please consider the voltage drop. ORBIT.DC is DC 24V and can be operated as long as the voltage is over 18V.
2017/08/07
6-1 Large-Scale ORBIT System Diagram
2017/08/07
6-2 Central Monitoring and Feedback
If central monitoring for all devices is required, we recommend connecting no more than 32 devices on each
Each device should set “response time” with 0.5 second incrementally. This is to avoid signal collision when
2017/08/07