Installing and Operating Instructions: Dixel
Installing and Operating Instructions: Dixel
Installing and Operating Instructions: Dixel
4. KEYBOARD
WING
XW264K
1. GENERAL WARNING
2. GENERAL DESCRIPTION
Models XW264K, is microprocessor based controller suitable for applications on medium or low temperature Switch ON and OFF the cold room light.
refrigerating units. They must be connected by means of a two-wire cable (∅ 1mm) at a distance of up to 30
meters to the keyboards T620, 185x38mm format, or V620 64x164mm format. It is provided with six relay Switch ON and OFF the instrument.
outputs to control compressor, two defrosts - which can be either electrical or hot gas - the evaporator fans, the
lights and an ON/OFF output. It is also provided with three NTC probe inputs, one for temperature control, two
to control the defrost end temperature of two evaporators. There are two digital inputs (free contact) for the door KEY COMBINATIONS
switch and configurable by parameter.
The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a ModBUS-
RTU compatible monitoring system and to programme the parameter list with the “Hot Key”.
An output for remote display XW-REP, a 4÷20 mA output to control evaporator or condenser fans and the direct + To lock and unlock the keyboard.
The regulation is performed according to the temperature measured by the thermostat probe with a positive
differential from the set point: if the temperature increases and reaches set point plus differential the compressor
is started and then turned off when the temperature reaches the set point value again. USE OF LEDS
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters
“COn” and “COF”. Each LED function is described in the following table.
LED MODE Function
3.2 FAST FREEZING ON The compressor is running
When defrost is not in progress, it can be activated the keypad by holding the o key pressed for about 3
FLASHING - Programming Phase (flashing with LED )
seconds. The compressor operates in continuous mode for the time set through the “CCt” parameter. The cycle
can be terminated before the end of the set time using the same activation key, o for about 3 seconds. - Anti-short cycle delay enabled
ON The fan is running
3.3 DEFROST
FLASHING
Three defrost modes are available through the “tdF” parameter: defrost with electrical heater, hot gas or Programming Phase (flashing with LED )
thermostatic defrost. The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made ON The defrost is enabled
every “IdF” time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the
compressor is ON and the evaporator temperature is bigger than “SdF” parameter). FLASHING Drip time in progress
At the end of defrost the drip time is controlled through the “Fdt” parameter.
ON The Fast Freezing cycle is enabled
This instrument can menage a defrost on two different evaporators. It waits the defrost end on both evaporators
before starting normal regulation ON - ALARM signal
- In “Pr2” indicates that the parameter is also present in “Pr1”
3.4 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the “FnC” parameter: Function of the LEDs placed on the left top side of buttons:
C-n fans will switch ON and OFF with the compressor and not run during defrost;
C-y fans will switch ON and OFF with the compressor, also during defrost BUTTON MODE FUNCTION
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. SET FLASHING The Set point is displayed and it can be modified
O-n fans will run continuously and not run during defrost; SET SLOW FLASHING The Energy Saving is enabled
O-y fans will run continuously also during defrost DEFROST ON The Manual Defrost is activated
LIGHT ON The Light is ON
An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe, above
which the fans are always OFF. This can be used to make sure circulation of air only if his temperature is lower ON/OFF ON The instrument is OFF
than set in “FSt”.
4.2 HOW TO SEE THE MIN TEMPERATURE
1. Press and release the n key.
3.5 ON/OFF RELAY 2. The “Lo” message will be displayed followed by the minimum temperature recorded.
The ON/OFF relay is switched ON when the instrument is ON and it is OFF when the instrument is switched
3. By pressing the n key or waiting for 5s the normal display will be restored.
OFF. This relay cuts the common of the defrost relays, so that, when the instrument is switched OFF by
keyboard button none of the loads have power supply.
4.3 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the o key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3. By pressing the o key or waiting for 5s the normal display will be restored.
72
83,5
odc Compressor and fan status when open door:
no = normal; Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
I1P Door switch input polarity: CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact.
I2P Configurable digital input polarity:
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact
I2F Digital input operating mode: configure the digital input function:
EAL = generic alarm; bAL = serious alarm mode; PAL = Pressure switch; dFr = Start defrost;
AUS = Not used; Es = Energy Saving; onF = remote On/OFF. 40
did Time interval/delay for digital input alarm:(0÷255 min.) Time interval to calculate the number of the
pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines
the time delay between the detection and the successive signalling of the alarm. MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD
OTHER
Adr RS485 serial address (1÷247): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
rEL Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map. 2 CLICK!
Prd Probes display: (read only) display the temperature values of the evaporator probes Pb2 and Pb3.
Pr2 Access to the protected parameter list (read only).
DIGITAL INPUTS 1
The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the 3
second is programmable in seven different configurations by the “I2F” parameter.
When the digital input is activated, the unit will wait for “did” delay before signalling the “BAL” alarm message. 1
The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.
150
+0.5
-0 Key” and vice-versa.
1. Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert
the “Hot Key” and then turn the Wing ON.
2. Automatically the parameter list of the “Hot Key” is downloaded into the Wing memory, the “DoL”
message is blinking. After 10 seconds the instrument will restart working with the new parameters.
Ø3 x2
3. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages:
V620: CUT OUT
“end “ for right programming. The instrument starts regularly with the new programming.
8(3)A
8(3)A 8(3)A 16(6)A 16(6)A 8(3)A
At the end of the data transfer phase the instrument displays the following messages:
250V~
“end “ for right programming.
“err” for failed programming. In this case push “SET” key if you want to restart the programming again or 1 2 3 4 5 6 7 8 9 10
remove the not programmed “Hot key”. Kbrd
Def.2
Room
Def.1
ALARM SIGNALS
Supply: 230Vac or 120Vac or 24Vac according to the model
Message Cause Outputs
“P1” Thermostat probe failure Alarm output ON; Compressor output according to DEFAULT SETTING VALUES
parameters “COn” and “COF”
“P2” 1 Evaporator probe failure
st Alarm output ON; Other outputs unchanged Label Name Range Default Level
“P3” 2nd Evaporator probe failure Alarm output ON; Other outputs unchanged REGULATION °C/°F
“HA” Max. temperature alarm Alarm output ON; Other outputs unchanged Set Set point LS÷US -5/23 Pr1
“LA” Min. temperature alarm Alarm output ON; Other outputs unchanged Hy Differential 0,1÷25,5 °C; 1÷45°F 2/4 Pr1
“EE” Data or memory failure Alarm output ON; Other outputs unchanged LS Minimum set point -50,0°C÷SET; -58°F÷SET -30/-22 Pr2
“dA” Defrost timeout alarm Alarm output ON; Other outputs unchanged US Maximum set point SET ÷ 110°C, SET ÷ 230°F 20/68 Pr2
“dAL” Door switch alarm Alarm output ON; Other outputs unchanged OdS Outputs activation delay at start up 0÷255 min. 1 Pr2
“EAL” External alarm Alarm output ON; Other outputs unchanged AC Anti-short cycle delay 0÷30 min. 1 Pr1
“BAL” Serious external alarm Alarm output ON; Other outputs OFF CCt Compressor ON time during fast freezing 0 ÷ 23h 50 min. 0 Pr2
“PAL” Pressure switch alarm Alarm output ON; Other outputs OFF COn Compressor ON time with faulty probe 0÷255 min. 15 Pr2
The alarm message is displayed until the alarm condition is recovery. COF Compressor OFF time with faulty probe 0÷255 min. 30 Pr2
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. DISPLAY
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is displayed for CF Temperature measurement unit °C ÷ °F °C/°F Pr2
about 3s. rES Resolution (integer/decimal point) in ÷ de de Pr1
Lod Local display P1 ÷ 1r2 P1 Pr2
SILENCING BUZZER Red Remote display P1 ÷ 1r2 p1 Pr2
Once the alarm signal is detected the buzzer can be silenced by pressing any key. DEFROST
tdF Defrost type rE, rT, in rE Pr1
“EE” ALARM EdF Defrost mode In, Sd In Pr2
The dIXEL instruments are provided with an internal check for the data integrity. Alarm “EE” flashes when a SdF Set point for SMART DEFROST -30 ÷ +30°C; -22÷+86°F 0 Pr2
failure in the memory data occurs. In such cases the alarm output is enabled. dtE Defrost termination temperature (1°Evaporator) -50,0÷110°C; -58÷230°F 8/46 Pr1
dtS Defrost termination temperature (2°Evaporator) -50,0÷110°C; -58÷230°F 8/46 Pr1
ALARM RECOVERY IdF Interval between defrost cycles 1÷120h 6 Pr1
Probe alarms : “P1” (probe1 faulty), “P2” and “P3”; they automatically stop 10s after the probe restarts normal MdF (Maximum) length for 1° defrost 0÷255 min. 30 Pr1
operation. Check connections before replacing the probe. MdS (Maximum) length for 2° defrost 0÷255 min. 30 Pr1
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal
dFd Displaying during defrost rt, it, SEt, dEF, dEG it Pr2
values or when the defrost starts.
dAd MAX display delay after defrost 0÷255 min. 30 Pr2
Door switch alarm “dA” stop as soon as the door is closed.
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled “PAL” alarm is recovered by dSd Defrost delay 0÷99min 0 Pr2
switching OFF the instrument. Fdt Draining time 0÷60 min. 0 Pr2
dPO First defrost after start up n÷y n Pr2
TECHNICAL DATA dAF Defrost delay after fast freezing 0 ÷ 23h 50 min. 2 Pr2
T820 keyboard FANS
Housing: self extinguishing ABS. FnC Fans operating mode C-n, C-y, O-n, O-y O-n Pr2
Case: T620 facia 38x185 mm; depth 23mm; V620 facia 64x164 mm; depth 23mm Fnd Fans delay after defrost 0÷255 min. 10 Pr2
Mounting : T620 panel mounting in a 150x31 mm panel cut-out with two screws. ∅ 3 x 2mm. FSt Fans stop temperature -50,0÷110°C; -58÷230°F 2/35 Pr2
Distance between the holes 165mm ALARMS
V620: panel mounting in a 56x72 mm panel cut-out with two screws. ∅ 3x2mm. Distance between the ALC Temperature alarms configuration rE÷Ab rE Pr2
holes 40mm ALU MAXIMUM temperature alarm -50,0÷110°C; -58÷230°F 10/20 Pr1
Protection: IP20; Frontal protection: IP65 with frontal gasket mod RG-L. (optional) ALL minimum temperature alarm -50,0÷110°C; -58÷230°F 10/20 Pr1
Connections: Screw terminal block ≤ 2,5 mm2 heat-resistant wiring and 6,3mm
AFH Temperature alarm and fan differential 0,1÷25,5 °C; 1÷45°F 2/4
Power supply: from XW230K power module
ALd Temperature alarm delay 0÷255 min. 15 Pr2
Display: 3 digits, red LED, 14,2 mm high; Optional output: buzzer
dAO Delay of temperature alarm at start up 0 ÷ 23h 50 min. 1,3 Pr2
Power module XW264K EdA Alarm delay at the end of defrost 0÷255 min. 30 Pr2
Housing: self extinguishing ABS; Case: facia 38x185 mm; depth 76mm dot Delay of temperature alarm after closing the door 0÷255 min. 15 Pr2
Mounting: panel mounting in a 150x31 mm panel cut-out with two screws. ∅ 3 x 2mm. dOA Open door alarm delay 0÷254 min.,nu 15 Pr2
Distance between the holes 165mm nPS Pressure switch activation number 0÷15 0 Pr2
Protection: IP20. ANALOGUE INPUTS
Frontal protection: IP65 with frontal gasket mod RG-L. (optional) Ot Thermostat probe calibration -12,0÷12,0°C; -21÷21°F 0 Pr1
Connections: Screw terminal block ≤ 2,5 mm2 heat-resistant wiring and 6,3mm Faston; Optional OE 1st evaporator probe calibration -12,0÷12,0°C; -21÷21°F 0 Pr2
disconnectable terminal blocks (max.12A)
O3 2nd evaporator probe calibration -12,0÷12,0°C; -21÷21°F 0 Pr2
Power supply: 230Vac or. 110Vac ± 10%; Power absorption: 7VA max.
Display: 3 digits, red LED, 14,2 mm high; Inputs: 3 NTC probes P2P 1st evaporator probe presence n÷y y Pr2
Digital inputs: 2 free voltage P3P 2nd evaporator probe presence n÷y n Pr2
Relay outputs: Total current on loads MAX. 20A HES Temperature increase during the En. Saving cycle -30÷30°C; -22÷86°F 0 Pr2
compressor: relay SPST 8(3) A, 250Vac DIGITAL INPUTS
light: relay SPST 16(3) A, 250Vac (or optional relay SPST 16(3) A, special for fluorescent lights) Odc Open door control no, Fan, CPr, F_C Fan Pr2
fans: relay SPST 8(3) A, 250Vac I1P Door switch polarity CL÷OP CL Pr2
1st defrost: relay SPDT 8(3) A, 250Vac I2P Configurable digital input polarity CL÷OP CL Pr2
2nd defrost : relay SPDT 8(3) A, 250Vac i2F Digital input configuration EAL, bAL, PAL, EAL Pr2
ON/OFF: SPST relay 16(3) A, 250Vac dFr, AUS, ES, OnF
Other output: Alarm buzzer (Standard)
dId Digital input alarm delay 0÷255 min. 5 Pr2
Direct RS485 (optional)
OTHER
Serial output : TTL standard; Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM). Adr Serial address 0÷247 1 Pr1
Kind of action: 1B; Pollution grade: normal; Software class: A. rEL Software release --- 1.0 Pr2
Operating temperature: 0÷60 °C; Storage temperature: -25÷60 °C. Ptb Map code --- --- Pr2
Relative humidity: 20÷85% (no condensing) Prd Probes display Pb1÷Pb3 --- Pr2
Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F) Pr2 Access parameter list --- --- Pr2
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit Dixell S.p.A. Via dell’Industria, 27 - 32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail:[email protected] - http://www.dixell.com