Installing and Operating Instructions: Dixel

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

dIXEL Installing and Operating Instructions 1592009550

4. KEYBOARD
WING
XW264K

1. GENERAL WARNING

1.1 PLEASE READ BEFORE USING THIS MANUAL


• This manual is part of the product and should be kept near the instrument for easy and quick reference.
• The instrument shall not be used for purposes different from those described hereunder. It cannot be used
as a safety device.
• Check the application limits before proceeding.

1.2 SAFETY PRECAUTIONS


• Check the supply voltage is correct before connecting the instrument. To display and modify target set point; in programming mode it selects a parameter or confirm an
• Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden operation.
temperature changes with high atmospheric humidity to prevent formation of condensation By holding it pressed for 3s when max or min temperature is displayed it will be erased.
• Warning: disconnect all electrical connections before any kind of maintenance.
• Fit the probe where it is not accessible by the End User. The instrument must not be opened. To see the max. stored temperature; in programming mode it browses the parameter codes or
• In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see increases the displayed value. By holding it pressed for 3s the fast freezing cycle is started.
address) with a detailed description of the fault.
• Consider the maximum current which can be applied to each relay (see Technical Data). To see the min stored temperature; in programming mode it browses the parameter codes or
• Ensure that the wires for probes, loads and the power supply are separated and far enough from each decreases the displayed value.
other, without crossing or intertwining.
• In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful. By holding it pressed for 3s the defrost is started.

2. GENERAL DESCRIPTION
Models XW264K, is microprocessor based controller suitable for applications on medium or low temperature Switch ON and OFF the cold room light.
refrigerating units. They must be connected by means of a two-wire cable (∅ 1mm) at a distance of up to 30
meters to the keyboards T620, 185x38mm format, or V620 64x164mm format. It is provided with six relay Switch ON and OFF the instrument.
outputs to control compressor, two defrosts - which can be either electrical or hot gas - the evaporator fans, the
lights and an ON/OFF output. It is also provided with three NTC probe inputs, one for temperature control, two
to control the defrost end temperature of two evaporators. There are two digital inputs (free contact) for the door KEY COMBINATIONS
switch and configurable by parameter.
The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a ModBUS-
RTU compatible monitoring system and to programme the parameter list with the “Hot Key”.
An output for remote display XW-REP, a 4÷20 mA output to control evaporator or condenser fans and the direct + To lock and unlock the keyboard.

serial output RS485 are available as options.

3. CONTROLLING LOADS + To enter the programming mode.

3.1 THE COMPRESSOR + To exit the programming mode.

The regulation is performed according to the temperature measured by the thermostat probe with a positive
differential from the set point: if the temperature increases and reaches set point plus differential the compressor
is started and then turned off when the temperature reaches the set point value again. USE OF LEDS
In case of fault in the thermostat probe the start and stop of the compressor are timed through parameters
“COn” and “COF”. Each LED function is described in the following table.
LED MODE Function
3.2 FAST FREEZING ON The compressor is running
When defrost is not in progress, it can be activated the keypad by holding the o key pressed for about 3
FLASHING - Programming Phase (flashing with LED )
seconds. The compressor operates in continuous mode for the time set through the “CCt” parameter. The cycle
can be terminated before the end of the set time using the same activation key, o for about 3 seconds. - Anti-short cycle delay enabled
ON The fan is running
3.3 DEFROST
FLASHING
Three defrost modes are available through the “tdF” parameter: defrost with electrical heater, hot gas or Programming Phase (flashing with LED )
thermostatic defrost. The defrost interval is control by means of parameter “EdF”: (EdF=in) the defrost is made ON The defrost is enabled
every “IdF” time, (EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the
compressor is ON and the evaporator temperature is bigger than “SdF” parameter). FLASHING Drip time in progress
At the end of defrost the drip time is controlled through the “Fdt” parameter.
ON The Fast Freezing cycle is enabled
This instrument can menage a defrost on two different evaporators. It waits the defrost end on both evaporators
before starting normal regulation ON - ALARM signal
- In “Pr2” indicates that the parameter is also present in “Pr1”
3.4 CONTROL OF EVAPORATOR FANS
The fan control mode is selected by means of the “FnC” parameter: Function of the LEDs placed on the left top side of buttons:
C-n fans will switch ON and OFF with the compressor and not run during defrost;
C-y fans will switch ON and OFF with the compressor, also during defrost BUTTON MODE FUNCTION
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. SET FLASHING The Set point is displayed and it can be modified
O-n fans will run continuously and not run during defrost; SET SLOW FLASHING The Energy Saving is enabled
O-y fans will run continuously also during defrost DEFROST ON The Manual Defrost is activated
LIGHT ON The Light is ON
An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe, above
which the fans are always OFF. This can be used to make sure circulation of air only if his temperature is lower ON/OFF ON The instrument is OFF
than set in “FSt”.
4.2 HOW TO SEE THE MIN TEMPERATURE
1. Press and release the n key.
3.5 ON/OFF RELAY 2. The “Lo” message will be displayed followed by the minimum temperature recorded.
The ON/OFF relay is switched ON when the instrument is ON and it is OFF when the instrument is switched
3. By pressing the n key or waiting for 5s the normal display will be restored.
OFF. This relay cuts the common of the defrost relays, so that, when the instrument is switched OFF by
keyboard button none of the loads have power supply.
4.3 HOW TO SEE THE MAX TEMPERATURE
1. Press and release the o key.
2. The “Hi” message will be displayed followed by the maximum temperature recorded.
3. By pressing the o key or waiting for 5s the normal display will be restored.

4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED


To reset the stored temperature, when max or min temperature is displayed :
1. Press SET key until “rST” label starts blinking.

1592009550 XW264K GB r1.0 22.06.2005.doc XW264K 1/4


dIXEL Installing and Operating Instructions 1592009550
de = 0,1°C; in = 1 °C
N.B. After the installation RESET the temperature stored . Lod Local display : select which probe is displayed by the instrument:
P1 = Thermostat probe; P2 = Evaporator probe; P3 = 2nd evaporator probe
HOW TO SEE AND MODIFY THE SET POINT 1r2 = difference between P1 and P2 (P1-P2)
1. Push and immediately release the SET key: the display will show the Set point value; Red Remote display : select which probe is displayed by the remote display (XW-REP)
2. The SET LED start blinking; P1 = Thermostat probe; P2 = Evaporator probe; P3 = 2nd evaporator probe
3. To change the Set value push the o or n arrows within 10s. 1r2 = difference between P1 and P2 (P1-P2)
4. To memorise the new set point value push the SET key again or wait 10s.
DEFROST
TO START A MANUAL DEFROST tdF Defrost type:
rE = electrical heater (Compressor OFF)
1. Push the DEF key for more than 2 seconds and a manual defrost will start. rT = thermostat defrost. During the defrost time “MdF”, the heater switches On and OFF depending on the
evaporator temperature and “dtE” value.
in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode:
TO ENTER IN PARAMETERS LIST “PR1” in = interval mode. The defrost starts when the time “Idf” is expired.
To enter the parameter list “Pr1” (user accessible parameters) operate as follows: Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the compressor
is running (even non consecutively) and only if the evaporator temperature is less than the value in "SdF”
1. Enter the Programming mode by pressing the Set and DOWN key for few (set point for SMARTFROST).
seconds ( and start blinking). SdF Set point for SMARTFROST: (-30÷30 °C/ -22÷86 °F) evaporator temperature which allows the IdF
counting (interval between defrosts) in SMARTFROST mode.
2. The instrument will show the first parameter present in “Pr1”
dtE Defrost termination temperature 1st evaporator: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the
evaporator probe is present) sets the temperature measured by the first evaporator probe which causes
TO ENTER IN PARAMETERS LIST “PR2” the end of defrost.
dtS Defrost termination temperature 2nd evaporator: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the
To access parameters in “Pr2”:
2nd evaporator probe is present) sets the temperature measured by the 2nd evaporator probe which causes
1. Enter the “Pr1” level.
the end of defrost.
2. Select “Pr2” parameter and press the “SET” key.
idF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost
3. The “PAS” flashing message is displayed, shortly followed by “0 - -” with a flashing zero.
cycles.
4. Use o or n to input the security code in the flashing digit; confirm the figure by pressing “SET”. The MdF (Maximum) duration of first defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the
security code is “321“. defrost duration, when P2P = y, defrost end based on temperature, it sets the maximum length for defrost.
5. If the security code is correct the access to “Pr2” is enabled by pressing “SET” on the last digit. MdS (Maximum) duration of second defrost: (0÷255 min) When P3P = n, no 2nd evaporator probe, it sets
the defrost duration, when P3P = y, 2nd defrost end based on temperature, it sets the maximum length for
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys 2nd defrost.
within 30 seconds. dFd Display during defrost:
rt = real temperature; it = temperature reading at the defrost start; Set = set point; dEF = “dEF” label;
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” + n. When a dEG = “dEG” label;
parameter is present in “Pr1” LED is on. dAd Defrost display time out: (0÷255 min) Sets the maximum time between the end of defrost and the
restarting of the real room temperature display.
HOW TO CHANGE THE PARAMETER VALUE dSd Start defrost delay: ( 0÷99min) This is useful when different defrost start times are necessary to avoid
1. Enter the Programming mode. overloading the plant.
2. Select the required parameter with o or n. Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and the
restoring of the control’s normal operation. This time allows the evaporator to eliminate water drops that
3. Press the “SET” key to display its value ( and LED starts blinking).
might have formed due to defrost.
4. Use o or n to change its value. dPO First defrost after start-up:
5. Press “SET” to store the new value and move to the following parameter. y = Immediately; n = after the IdF time
To exit: Press SET + UP or wait 15s without pressing a key. dAF Defrost delay after fast freezing: (0min÷23h 50min) after a Fast Freezing cycle, the first defrost will be
NOTE: the new programming is stored even when the procedure is exited by waiting the time-out. delayed for this time.
FANS
HOW TO LOCK THE KEYBOARD
FnC Fan operating mode:
1. Keep the o and n keys pressed together for more than 3 s the o and n keys. C-n = running with the compressor, OFF during the defrost;
2. The “POF” message will be displayed and the keyboard is locked. At this point it is only C-y = running with the compressor, ON during the defrost;
possible the viewing of the set point or the MAX o Min temperature stored and to switch ON O-n = continuous mode, OFF during the defrost;
and OFF the light and the instrument. O-y = continuous mode, ON during the defrost;
Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator fans start.
TO UNLOCK THE KEYBOARD FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe,
above which the fan is always OFF.
Keep the o and n keys pressed together for more than 3s. ALARMS
ALC Temperature alarm configuration
rE = High and Low alarms related to Set Point
ON/OFF FUNCTION Ab = High and low alarms related to the absolute temperature.
By pushing the ON/OFF key, the instrument shows “OFF” for 5 sec. and the ON/OFF LED is ALU High temperature alarm setting: ( ALC= rE, 0 ÷ 50°C or 90°F; ALC= Ab, ALL ÷ 110°C or 230°F)
switched ON. when this temperature is reached and after the ALd delay time the HA alarm is enabled.
During the OFF status, all the relays are switched OFF and the regulations are stopped; if a ALL Low temperature alarm setting: ( ALC = rE , 0 ÷ 50 °C or 90°F; ALC = Ab , - 50°C or -58°F ÷ ALU)
monitoring system is connected, it does not record the instrument data and alarms. when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.
N.B. During the OFF status the Light button is active. AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature
alarm set point and fan regulation set point, always positive.
TO SEE THE PROBE VALUES ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the
1. Enter in “Pr2” level. corresponding alarm signalling.
2. Select “Prd” parameter with o or n. dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of the
temperature alarm condition after the instrument power on and the alarm signalling.
3. Press the “SET” key to display “Pb1” label alternate with Pb1 value. EdA Alarm delay at the end of defrost: (0÷255 min) Time interval between the detection of the temperature
4. Use o and n keys to display the other probe values. alarm condition at the end of defrost and the alarm signalling.
5. Press “SET” to move to the following parameter. dot Delay of temperature alarm after closing the door : (0÷255 min) Time delay to signal the temperature
alarm condition after closing the door.
PARAMETER LIST doA Open door alarm delay:(0÷254min,nu) delay between the detection of the open door condition and its
alarm signalling: the flashing message “dA” is displayed. If doA=nu the door alarm will be not signalled.
REGULATION
nPS Pressure switch number: (0 ÷15) Number of activation of the pressure switch, during the “did” interval,
Hy Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor before signalling the alarm event (I2F= PAL).
Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT is when the temperature reaches the set
ANALOGUE OUTPUT 4÷20 mA (OPTIONAL)
point.
LS Minimum set point limit: (-50,0°C÷SET; -58°F÷SET) Sets the minimum acceptable value for the set AOS Analogue output start point: (-50÷110°C or -58°÷230°F). Sets the temperature at which the analogue
point. output begins.
US Maximum set point limit: (SET÷110°C; SET÷230°F) Set the maximum acceptable value for set point. APB Analogue output band width: (-50÷110°C or -58°÷230°F) sets the width of the regulation band for the
OdS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the analogue output. If APb is positive then it is above the start point and the kind of action is direct
instrument and inhibits any output activation for the period of time set in the parameter. (Light can work) (condenser application). If APb is negative then it is below the start point and the kind of action is inverse
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart. (evaporator application).
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used, CAO Input type for the analogue output: four input types can be selected:
for instance, when the room is filled with new products. P1 = room probe temperature; P2 = evaporator probe temperature; P3 = temperature of the third probe
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case 1r2= temperature difference between the room probe and the evaporator probe
of faulty thermostat probe. With COn=0 compressor is always OFF. PROBE INPUTS
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in case of Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the
faulty thermostat probe. With COF=0 compressor is always active. thermostat probe.
DISPLAY OE 1st Evaporator probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the measurement unit is evaporator probe.
changed the SET point and the values of the regulation parameters have to be modified O3 2nd Evaporator probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the 2nd
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display. evaporator probe.

1592009550 XW264K GB r1.0 22.06.2005.doc XW264K 2/4


dIXEL Installing and Operating Instructions 1592009550
P2P 1st Evaporator probe presence:
n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and time.
P3P 2nd Evaporator probe presence: n= not present; y= present.
HES Temperature increase during the Energy Saving cycle : (-30,0°C ÷ 30,0°C / -22÷86°F) sets the
increasing value of the set point during the Energy Saving cycle. 56
DIGITAL INPUTS

72
83,5
odc Compressor and fan status when open door:
no = normal; Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
I1P Door switch input polarity: CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact.
I2P Configurable digital input polarity:
CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact
I2F Digital input operating mode: configure the digital input function:
EAL = generic alarm; bAL = serious alarm mode; PAL = Pressure switch; dFr = Start defrost;
AUS = Not used; Es = Energy Saving; onF = remote On/OFF. 40
did Time interval/delay for digital input alarm:(0÷255 min.) Time interval to calculate the number of the
pressure switch activation when I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines
the time delay between the detection and the successive signalling of the alarm. MOUNTING WITH KEYBOARD COVER OPENING DOWNWARD
OTHER
Adr RS485 serial address (1÷247): Identifies the instrument address when connected to a ModBUS
compatible monitoring system.
rEL Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map. 2 CLICK!
Prd Probes display: (read only) display the temperature values of the evaporator probes Pb2 and Pb3.
Pr2 Access to the protected parameter list (read only).

DIGITAL INPUTS 1

The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the 3
second is programmable in seven different configurations by the “I2F” parameter.

DOOR SWITCH INPUT


1
It signals the door status and the corresponding relay output status through the “odc” parameter: 2
no = normal (any change); 1 3
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter “dOA”, the alarm output is enabled and the
display shows the message “dA”. The alarm stops as soon as the external digital input is disabled again. During
MOUNTING WITH KEYBOARD COVER OPENING UPWARD
this time and then for the delay “dot” after closing the door, the high and low temperature alarms are disabled.

CONFIGURABLE INPUT - GENERIC ALARM (EAL)


As soon as the digital input is activated the unit will wait for “did” time delay before signalling the “EAL” alarm
message. The outputs status don’t change. The alarm stops just after the digital input is de-activated.
1

CONFIGURABLE INPUT - SERIOUS ALARM MODE (BAL) 3


2

When the digital input is activated, the unit will wait for “did” delay before signalling the “BAL” alarm message. 1
The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.

CONFIGURABLE INPUT - PRESSURE SWITCH (PAL) 2


If during the interval time set by “did” parameter, the pressure switch has reached the number of activation of
the “nPS” parameter, the “PAL” pressure alarm message will be displayed. The compressor and the regulation 3
2 CLICK!
are stopped. When the digital input is ON the compressor is always OFF.
1

CONFIGURABLE INPUT - START DEFROST (DFR)


It executes a defrost if there are the right conditions. After the defrost is finished, the normal regulation will
restart only if the digital input is disabled otherwise the instrument will wait until the “Mdf” safety time is expired.

CONFIGURABLE INPUT - ENERGY SAVING (ES) ELECTRICAL CONNECTIONS


The Energy Saving function allows to change the set point value as the result of the SET+ HES (parameter) The instruments are provided with screw terminal block to connect cables with a cross section up to 2,5 mm2 for
sum. This function is enabled until the digital input is activated. the digital and analogue inputs. Relays and power supply have a Faston connection (6,3mm). Heat-resistant
cables have to be used. Before connecting cables make sure the power supply complies with the instrument’s
CONFIGURABLE INPUT - REMOTE ON/OFF (ONF) requirements. Separate the probe cables from the power supply cables, from the outputs and the power
This function allows to switch ON and OFF the instrument. connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable
external relay.
DIGITAL INPUTS POLARITY N.B. Maximum current allowed for all the loads is 20A.
The digital inputs polarity depends on “I1P” and “I2P” parameters.
CL : the digital input is activated by closing the contact. PROBE CONNECTIONS
OP : the digital input is activated by opening the contact The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is
recommended to place the thermostat probe away from air streams to correctly measure the average room
INSTALLATION AND MOUNTING temperature. Place the defrost termination probes among the evaporators fins in the coldest places, where most
Keyboard T620 shall be mounted on vertical panel, in a 150x31 mm hole, and fixed using two screws ∅ 3 x ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost
2mm. To obtain an IP65 protection grade use the front panel rubber gasket (mod. RG-L). termination.
Keyboard V620 shall be mounted on vertical panel, in a 72x56 mm hole, and fixed using screws ∅ 3 x 2mm. To
obtain an IP65 protection grade use the front panel rubber gasket (mod. RGW-V).
Instrument XW264K shall be mounted in a panel with two or more screws and it must be connected to the TTL SERIAL LINE
keyboard by means of a two-wire cable (∅ 1mm). The temperature range allowed for correct operation is 0 - 60 The TTL connector allows, by means of the external module TTL/RS485, to connect the unit to a network line
°C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same ModBUS-RTU compatible as the dIXEL monitoring system XJ500 (Version 3.0).
recommendations apply to probes. Let the air circulate by the cooling holes. The same TTL connector is used to upload and download the parameter list of the “HOT KEY“. These
instruments can be ordered with direct serial output RS485 (Optional).
T620 CUT OUT
USE OF THE PROGRAMMING “HOT KEY “
The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the “Hot
+1
165 -1

150
+0.5
-0 Key” and vice-versa.

DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)


31 +0.5
-0

1. Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert
the “Hot Key” and then turn the Wing ON.
2. Automatically the parameter list of the “Hot Key” is downloaded into the Wing memory, the “DoL”
message is blinking. After 10 seconds the instrument will restart working with the new parameters.
Ø3 x2
3. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.
At the end of the data transfer phase the instrument displays the following messages:
V620: CUT OUT
“end “ for right programming. The instrument starts regularly with the new programming.

1592009550 XW264K GB r1.0 22.06.2005.doc XW264K 3/4


dIXEL Installing and Operating Instructions 1592009550
“err” for failed programming. In this case turn the unit off and then on if you want to restart the download again CONNECTIONS
or remove the “Hot key” to abort the operation.
XW264K
UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
1. Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then
turn it ON again.
Def 2 Def 1 Light N L Comp Fan
2. When the Wing unit is ON, insert the “Hot key” and push o key; the "uPL" message appears.
3. Push “SET” key to start the UPLOAD; the “uPL” message is blinking.
24 23 22 21 20 19 18 17 16 15 14 13 12 11
4. Turn OFF the instrument remove the “Hot Key”, plug in the TTL serial cable, then turn it ON again.

8(3)A
8(3)A 8(3)A 16(6)A 16(6)A 8(3)A
At the end of the data transfer phase the instrument displays the following messages:
250V~
“end “ for right programming.
“err” for failed programming. In this case push “SET” key if you want to restart the programming again or 1 2 3 4 5 6 7 8 9 10
remove the not programmed “Hot key”. Kbrd

Def.2

Room
Def.1
ALARM SIGNALS
Supply: 230Vac or 120Vac or 24Vac according to the model
Message Cause Outputs
“P1” Thermostat probe failure Alarm output ON; Compressor output according to DEFAULT SETTING VALUES
parameters “COn” and “COF”
“P2” 1 Evaporator probe failure
st Alarm output ON; Other outputs unchanged Label Name Range Default Level
“P3” 2nd Evaporator probe failure Alarm output ON; Other outputs unchanged REGULATION °C/°F
“HA” Max. temperature alarm Alarm output ON; Other outputs unchanged Set Set point LS÷US -5/23 Pr1
“LA” Min. temperature alarm Alarm output ON; Other outputs unchanged Hy Differential 0,1÷25,5 °C; 1÷45°F 2/4 Pr1
“EE” Data or memory failure Alarm output ON; Other outputs unchanged LS Minimum set point -50,0°C÷SET; -58°F÷SET -30/-22 Pr2
“dA” Defrost timeout alarm Alarm output ON; Other outputs unchanged US Maximum set point SET ÷ 110°C, SET ÷ 230°F 20/68 Pr2
“dAL” Door switch alarm Alarm output ON; Other outputs unchanged OdS Outputs activation delay at start up 0÷255 min. 1 Pr2
“EAL” External alarm Alarm output ON; Other outputs unchanged AC Anti-short cycle delay 0÷30 min. 1 Pr1
“BAL” Serious external alarm Alarm output ON; Other outputs OFF CCt Compressor ON time during fast freezing 0 ÷ 23h 50 min. 0 Pr2
“PAL” Pressure switch alarm Alarm output ON; Other outputs OFF COn Compressor ON time with faulty probe 0÷255 min. 15 Pr2
The alarm message is displayed until the alarm condition is recovery. COF Compressor OFF time with faulty probe 0÷255 min. 30 Pr2
All the alarm messages are showed alternating with the room temperature except for the “P1” which is flashing. DISPLAY
To reset the “EE” alarm and restart the normal functioning press any key, the “rSt” message is displayed for CF Temperature measurement unit °C ÷ °F °C/°F Pr2
about 3s. rES Resolution (integer/decimal point) in ÷ de de Pr1
Lod Local display P1 ÷ 1r2 P1 Pr2
SILENCING BUZZER Red Remote display P1 ÷ 1r2 p1 Pr2
Once the alarm signal is detected the buzzer can be silenced by pressing any key. DEFROST
tdF Defrost type rE, rT, in rE Pr1
“EE” ALARM EdF Defrost mode In, Sd In Pr2
The dIXEL instruments are provided with an internal check for the data integrity. Alarm “EE” flashes when a SdF Set point for SMART DEFROST -30 ÷ +30°C; -22÷+86°F 0 Pr2
failure in the memory data occurs. In such cases the alarm output is enabled. dtE Defrost termination temperature (1°Evaporator) -50,0÷110°C; -58÷230°F 8/46 Pr1
dtS Defrost termination temperature (2°Evaporator) -50,0÷110°C; -58÷230°F 8/46 Pr1
ALARM RECOVERY IdF Interval between defrost cycles 1÷120h 6 Pr1
Probe alarms : “P1” (probe1 faulty), “P2” and “P3”; they automatically stop 10s after the probe restarts normal MdF (Maximum) length for 1° defrost 0÷255 min. 30 Pr1
operation. Check connections before replacing the probe. MdS (Maximum) length for 2° defrost 0÷255 min. 30 Pr1
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal
dFd Displaying during defrost rt, it, SEt, dEF, dEG it Pr2
values or when the defrost starts.
dAd MAX display delay after defrost 0÷255 min. 30 Pr2
Door switch alarm “dA” stop as soon as the door is closed.
External alarms “EAL”, “BAL” stop as soon as the external digital input is disabled “PAL” alarm is recovered by dSd Defrost delay 0÷99min 0 Pr2
switching OFF the instrument. Fdt Draining time 0÷60 min. 0 Pr2
dPO First defrost after start up n÷y n Pr2
TECHNICAL DATA dAF Defrost delay after fast freezing 0 ÷ 23h 50 min. 2 Pr2
T820 keyboard FANS
Housing: self extinguishing ABS. FnC Fans operating mode C-n, C-y, O-n, O-y O-n Pr2
Case: T620 facia 38x185 mm; depth 23mm; V620 facia 64x164 mm; depth 23mm Fnd Fans delay after defrost 0÷255 min. 10 Pr2
Mounting : T620 panel mounting in a 150x31 mm panel cut-out with two screws. ∅ 3 x 2mm. FSt Fans stop temperature -50,0÷110°C; -58÷230°F 2/35 Pr2
Distance between the holes 165mm ALARMS
V620: panel mounting in a 56x72 mm panel cut-out with two screws. ∅ 3x2mm. Distance between the ALC Temperature alarms configuration rE÷Ab rE Pr2
holes 40mm ALU MAXIMUM temperature alarm -50,0÷110°C; -58÷230°F 10/20 Pr1
Protection: IP20; Frontal protection: IP65 with frontal gasket mod RG-L. (optional) ALL minimum temperature alarm -50,0÷110°C; -58÷230°F 10/20 Pr1
Connections: Screw terminal block ≤ 2,5 mm2 heat-resistant wiring and 6,3mm
AFH Temperature alarm and fan differential 0,1÷25,5 °C; 1÷45°F 2/4
Power supply: from XW230K power module
ALd Temperature alarm delay 0÷255 min. 15 Pr2
Display: 3 digits, red LED, 14,2 mm high; Optional output: buzzer
dAO Delay of temperature alarm at start up 0 ÷ 23h 50 min. 1,3 Pr2
Power module XW264K EdA Alarm delay at the end of defrost 0÷255 min. 30 Pr2
Housing: self extinguishing ABS; Case: facia 38x185 mm; depth 76mm dot Delay of temperature alarm after closing the door 0÷255 min. 15 Pr2
Mounting: panel mounting in a 150x31 mm panel cut-out with two screws. ∅ 3 x 2mm. dOA Open door alarm delay 0÷254 min.,nu 15 Pr2
Distance between the holes 165mm nPS Pressure switch activation number 0÷15 0 Pr2
Protection: IP20. ANALOGUE INPUTS
Frontal protection: IP65 with frontal gasket mod RG-L. (optional) Ot Thermostat probe calibration -12,0÷12,0°C; -21÷21°F 0 Pr1
Connections: Screw terminal block ≤ 2,5 mm2 heat-resistant wiring and 6,3mm Faston; Optional OE 1st evaporator probe calibration -12,0÷12,0°C; -21÷21°F 0 Pr2
disconnectable terminal blocks (max.12A)
O3 2nd evaporator probe calibration -12,0÷12,0°C; -21÷21°F 0 Pr2
Power supply: 230Vac or. 110Vac ± 10%; Power absorption: 7VA max.
Display: 3 digits, red LED, 14,2 mm high; Inputs: 3 NTC probes P2P 1st evaporator probe presence n÷y y Pr2
Digital inputs: 2 free voltage P3P 2nd evaporator probe presence n÷y n Pr2
Relay outputs: Total current on loads MAX. 20A HES Temperature increase during the En. Saving cycle -30÷30°C; -22÷86°F 0 Pr2
compressor: relay SPST 8(3) A, 250Vac DIGITAL INPUTS
light: relay SPST 16(3) A, 250Vac (or optional relay SPST 16(3) A, special for fluorescent lights) Odc Open door control no, Fan, CPr, F_C Fan Pr2
fans: relay SPST 8(3) A, 250Vac I1P Door switch polarity CL÷OP CL Pr2
1st defrost: relay SPDT 8(3) A, 250Vac I2P Configurable digital input polarity CL÷OP CL Pr2
2nd defrost : relay SPDT 8(3) A, 250Vac i2F Digital input configuration EAL, bAL, PAL, EAL Pr2
ON/OFF: SPST relay 16(3) A, 250Vac dFr, AUS, ES, OnF
Other output: Alarm buzzer (Standard)
dId Digital input alarm delay 0÷255 min. 5 Pr2
Direct RS485 (optional)
OTHER
Serial output : TTL standard; Communication protocol: Modbus - RTU
Data storing: on the non-volatile memory (EEPROM). Adr Serial address 0÷247 1 Pr1
Kind of action: 1B; Pollution grade: normal; Software class: A. rEL Software release --- 1.0 Pr2
Operating temperature: 0÷60 °C; Storage temperature: -25÷60 °C. Ptb Map code --- --- Pr2
Relative humidity: 20÷85% (no condensing) Prd Probes display Pb1÷Pb3 --- Pr2
Measuring and regulation range: NTC probe: -40÷110°C (-58÷230°F) Pr2 Access parameter list --- --- Pr2
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,5 °C ±1 digit Dixell S.p.A. Via dell’Industria, 27 - 32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 - 0437 - 98 33 - fax +39 - 0437 - 98 93 13
E-mail:[email protected] - http://www.dixell.com

1592009550 XW264K GB r1.0 22.06.2005.doc XW264K 4/4

You might also like