ABB Utilities GmbH RTU560
Remote Terminal Unit
Connections and Settings
Extension Subrack 23ET23
Application, characteristics and technical data have Subrack address setting
to be taken from the hardware data sheet:
DIP switch register S1 specifies the logical RTU560
23ET23 1 KGT 150 412 rack address. Each subrack must have a different
RTU 560 rack address.
Operation S1-1 S1-2 S1-3
RTU560
rack address
The 23ET23 extension subrack can be mounted in ON OFF OFF 1
hinged frames or open racks. The process signal ac- OFF ON OFF 2
cess is done by DIN-F sub-connectors. They are ON ON OFF 3
clipped into a cut-out in the DIN-F connector body. OFF OFF ON 4
ON OFF ON 5
The extension subrack has 19 slots for process I/O OFF ON ON 6
boards. The power supply is plugged to slot 1 and 5. ON ON ON 7
S1-4 not used
Processing function ON
ON
1 2 3 4
Voltage monitoring and watchdog supervi- OFF
sion
Table 1: RTU560 rack address setting
Fig. 1: shows the voltage monitoring diagram. The
relay k 01 is only switched if: Serial peripheral bus termination
Fig. 6: shows the principle serial peripheral bus
- + 5 V DC and
routing. X1 / X2 allow to expand the RTU560 with
- + 24 V DC are present. additional extension subracks by a daisy chain con-
nection. The serial bus has to be terminated by a 1 k
If one or both of the two voltages is missing relay k 01 resistor at both ends. R1 of the basic subrack is fixed
is released and the contact closed. placed. The other termination should be done during
commissioning.
- Remove all terminator resistors (R 21) on sub-
racks that are not the last one.
X 11 K 01 - Use shielded cables for the serial bus.
RK1 0V
Voltage
+5V
MK1 monitoring Regard grounding conditions, EMC specifications
+ 24 V
RK1 and power distribution in a distributed subrack con-
MK1 figuration for the serial peripheral bus (RS 485 stan-
X 12 dard).
Serial peripheral bus by 23OK22 fibre optic
coupler
Use 23OK22 boards for the serial peripheral bus if a
Fig. 1: Voltage monitoring longer distance must be linked or the grounding situ-
Doc.No.: 1KGT 150 441 V000 1 73
ABB Utilities GmbH
Connections and Settings 23ET23 RTU560
ation is not clear. See Fig. 6: how the principle con- Order number for sub-connector and crimp-
nection is done. clips
Fixing peripheral boards - 1KGN 000758 R1001 (23XS40 R 1001)
Fix each I/O-board or other peripheral RTU560 board 18-pole sub-connector
in the subrack for operation. - 1KGN 000758 R2001 (23XS40 R2001)
Fasten each board by the two fixing screws in the up- Crimp clips (500 pcs)
per and lower fixing rail of the subrack. The front plate
is then connected (grounded) to PE / A.
Tools for 23XS40:
The EMC specification of each board is only valid if - 1KGN 000797 R0001 Crimp tool
the board front plate is grounded. - 1KGN 000798 R0001
Extraction tool for crimp clips
Process I/O connections
- 1 KGN 000799 R0001
The connection of the signal wires is made by the Removal tool for sub- -connectors
means of crimp clips using snap-in fixings. In addition
to the use of premanufactured cables it is also pos-
sible to attach individual wires during commission-
ing.
Use AMP tools for crimp-snap-in spring-contacts.
DIN- -F connector
Sub- -connector looking from cable entry side
Fig. 2: I/O signal sub-connector
74 Doc.No.: 1KGT 150 441 V000 1
ABB Utilities GmbH
RTU560 Connections and Settings 23ET23
RTU 560 board address
NG 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Slot address
1 5 9 13 17 21 25 29 33 37 41 45 49 53 57 61 65 69 73 77 81
Fig. 3: Layout basic subrack
S1
Fig. 4: Layout customer connectors (looking from back side)
Doc.No.: 1KGT 150 441 V000 1 75
ABB Utilities GmbH
Connections and Settings 23ET23 RTU560
UB +
X 14
UB - -
UB +
X 15
UB - -
z 30 / z 32 z 26 z 28
b 30 / b32 b 26 b 28
UE + d 30 / d 32 d 26 d 28
X 16 23NG23
UE - -
UE +
X 17 z8 z 10 z4 z2
UE - - b8 d 10 b4 b2
d8 b 10 d4 d2
0V + 24 V +5V
X 64 X 63
PE
PE 0V
slot 9 A (6.3 Faston) z 20 / b 20 / d 20 z 16 / b18 / d 18 z 18 b 16
slot 13 A z 20 / b 20 / d 20 z 16 / b18 / d 18 z 18 b 16
DIN F connectors
slot 57 A z 20 / b 20 / d 20 z 16 / b18 / d 18 z 18 b 16
slot 61 A z 20 / b 20 / d 20 z 16 / b18 / d 18 z 18 b 16
X 1 socket (A)
subrack X 2 socket (A)
Fig. 5: DC voltage and grounding distribution
76 Doc.No.: 1KGT 150 441 V000 1
ABB Utilities GmbH
RTU560 Connections and Settings 23ET23
BUSABSCHLUSS
+5V
R4
R6 X1 1k
Basic
2 subrack
SPB
R1
3
7
R5 Slot 5...61
socket
Address: 1...15
and slot 65 (communication unit) 2
0V
3
0V 7
(A) socket
X2
R 21 1 k X1 Extension
2 subrack
3 Adr.: 001
SPB
7
BUSABSCHLUSS
Slot 5....81 socket
Address: 1...19 2
3
0V 7
(A) socket
X2
R 21 1 k X1 Extension
2 subrack
3 Adr.: 00n
SPB
7
BUSABSCHLUSS Slot 5...81 socket last subrack
Address: 1...19
2
3
0V 7
(A) socket
X2
Fig. 6: Serial peripheral bus / Bus termination
Doc.No.: 1KGT 150 441 V000 1 77
ABB Utilities GmbH
Connections and Settings 23ET23 RTU560
BUSABSCHLUSS
+5V Slot 5...61
Address: 1...15 R4
R6 and slot 65 (communication unit) X1 1k
Basic
2 subrack
SPB
R1
3
7
R5
23OK22 socket
2
0V Replace T1 and T2
0V
in 23OK22 3
+5V 0V 7
R2 R7 R1 (A) socket
X2
RX TX
fibre optic cable
TX RX
R2 R7 R1
+5V
0V
23OK22 Slot 5....81
R 21 1 k
Address: 1...19 X1 Extension
2 subrack
3 Adr.: 001
SPB
7
BUSABSCHLUSS
socket
Place 23OK22 in slot 9 if not the last subrack 3
Place 23OK22 in slot 81 and solder R21 if last or only subrack 0V 7
(A) socket
X2
R 21 1 k X1 Extension
2 subrack
3 Adr.: 00n
SPB
7
BUSABSCHLUSS Slot 5...81 socket last subrack
Address: 1...19
2
3
0V 7
(A) socket
X2
Fig. 7: Subrack configuration with 23OK22 for serial peripheral bus
78 Doc.No.: 1KGT 150 441 V000 1
ABB Utilities GmbH
RTU560 Connections and Settings 23ET23
Doc.No.: 1KGT 150 441 V000 1 79
ABB Utilities GmbH
Connections and Settings 23ET23 RTU560
ABB Utilities GmbH
68309 Mannheim (Germany)
Telephone +49 (0) 621 381-7592
Telefax +49 (0) 621 381-7622 03/2001 Subject to alteration
80 Doc.No.: 1KGT 150 441 V000 1