Engineering Data: Air Conditioners

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

AIR CONDITIONERS

TS
T−CLASSE SPLIT SYSTEM UNITS
R−410A − 60 HZ
ENGINEERING DATA Bulletin No. 210524
February 2009
Supersedes January 2009

072−090 Models

180−240 Models

EER up to 11.4
120−150 Models 6 to 20 Tons
Cooling Capacity − 66,000 to 236,000 Btuh

MODEL NUMBER IDENTIFICATION


T S A 120 S 4 S N 1 Y
Brand/Family Voltage
T = T−Class™ Product Line Y = 208/230V-3 phase-60hz
G = 460V-3 phase-60hz
J = 575V-3 phase-60hz
Unit Type
S = Split System Air Conditioner
Minor Design Sequence
Major Design Sequence 1 = 1st Revision
A = 1st Generation 2 = 2nd Revision
B = 2nd Generation 3 = 3rd Revision

Part Load Capability


Nominal Cooling Capacity − Tons N = Single Stage Compressor
072 = 6 Tons
090 = 7.5 Tons Refrigerant Circuits
120 = 10 Tons S = Single Circuit
150 = 12.5 Tons D = Dual Circuits
180 = 15 Tons
240 = 20 Tons Refrigerant Type
4 = R−410A
Cooling Efficiency
S = Standard Efficiency
FEATURES AND BENEFITS

I
F

G 180−240 Models
C
K
H

E
D

120−150 Models

J
072−090 Models

FEATURES AND BENEFITS


CONTENTS Approvals
ARI Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10 All units tested in Lennox’ Research Laboratory
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . Pages 13−15 environmental test room or ETL certified environmental
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . Pages 6−8 testing facility.
Features and Benefits . . . . . . . . . . . . . . . . . Pages 2−4 Certified in accordance with the ULE certification
Guide Specifications . . . . . . . . . . . . . . . . . Page 29 − 32 program, which is based on ARI Standard 340/360−2007.
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . Page 12 Sound tested in Lennox reverberant sound test room in
Model Number Identification . . . . . . . . . . . . . . . Page 1 accordance with test conditions included in ARI Standard
Optional Accessories . . . . . . . . . . . . . . . . . . . . . Page 9 270-95 or 370−2001.
Optional Temperature Control Systems . . . . . Page 5 Units and components within are bonded for grounding to
Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9 meet safety standards for servicing required by UL, ULC,
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . Pages 6−8 NEC and CEC.
Weight Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11 All units are ETL listed.
ISO 9001 Registered Manufacturing Quality System.
EQUIPMENT Warranty
Compressor − limited warranty for five years in
non−residential applications.
All other covered components − one year in
non−residential applications.
Refer to Lennox Equipment Limited Warranty certificate
for specific details.
TS 6 to 20 Ton R−410A Air Conditioners / Page 2
FEATURES AND BENEFITS
Applications G Refrigerant Lines and Service Valves
Air conditioners are available in 6, 7.5, 10 ton (one Suction and liquid lines are located on corner of unit
compressor) and 10, 12.5, 15 and 20 ton (two cabinet and are made with sweat connections. See
compressors) nominal sizes. dimension drawings.
Matching air handlers provide a wide range of cooling Fully serviceable suction and liquid line service valves
capacities and applications. See ARI Ratings tables. provide complete service access to refrigerant system.
See Air Handlers sections for data. Suction valve can be fully shut off, while liquid valve can be
Units shipped completely factory assembled, piped, and front seated to manage refrigerant charge while servicing
wired. Each unit is test operated at the factory insuring system. Accessible outside of unit cabinet.
proper operation.
Installer must set air conditioner, connect refrigerant lines, H Compressors
add refrigerant charge and make electrical connections to TSA072, TSA090 and TSA120S4S models feature a
complete job. single scroll compressor. TSA120S4D, TSA150, TSA180
REFRIGERATION SYSTEM and TSA240 models have two scroll compressors.
Refrigerant Compressor features high efficiency with uniform suction
Units operate with chlorine−free, ozone flow, constant discharge flow and high volumetric
friendly, R−410A (field furnished). efficiency and quiet operation.
B Outdoor Coil Fan(s) Compressor consists of two involute spiral scrolls
matched together to generate a series of crescent shaped
TSA072 and TSA090 units have one outdoor fan. TSA120
and TSA150 units have two outdoor fans. TSA180 and gas pockets between them.
TSA240 units have four outdoor fans. During compression, one scroll remains stationary while
Direct drive fan(s) moves large volumes of air uniformly the other scroll orbits around it.
through entire condenser coil(s) for high refrigerant Gas is drawn into the outer pocket, the pocket is sealed as
cooling capacity. the scroll rotates.
Upward discharge of air reduces operating sound levels As the spiral movement continues, gas pockets are
and prevents damage to lawns, shrubs, and walkways. pushed to the center of the scrolls. Volume between the
Fan motors are totally enclosed, overload protected and pockets is simultaneously reduced.
equipped with a rain shield. When pocket reaches the center, gas is now high pressure
Fan service access is accomplished by removal of fan and is forced out of a port located in the center of the fixed
guard(s) or removal of access panel. scrolls.
During compression, several pockets are compressed
C Copper Tube/Enhanced Fin Coil(s) simultaneously resulting in a smooth continuous
Units are equipped with a wrap−around U" shaped coil compression cycle.
(072−090−120 models) or two L" shaped coils Continuous flank contact, maintained by centrifugal force,
(150−180−240 models). minimizes gas leakage and maximizes efficiency.
Lennox designed and fabricated coils constructed of Scroll compressor is tolerant to the effects of slugging and
precisely spaced ripple-edge aluminum fins machine contaminants. If this occurs, scrolls separate, allowing
fitted to seamless copper tubes. liquid or contaminants to to be worked toward the center and
Lanced fins provide maximum exposure of fin surface to discharged.
air stream resulting in excellent heat transfer. Low gas pulses during compression reduces operational
Fins equipped with collars that grip tubing for maximum sound levels.
contact area. Compressor motor is internally protected from excessive
Flared shoulder tubing connections and machine brazed current and temperature.
silver soldering provide tight, leakproof joints. Compressor is installed in the unit on resilient rubber
Long life copper tubing is corrosion-resistant and easy to mounts for vibration free operation.
field service.
Thoroughly factory tested under high pressure to ensure Crankcase Heater(s) (All Models)
leakproof construction. Crankcase heater(s) prevents migration of liquid
Completely accessible for cleaning. refrigerant into compressor(s) and ensures proper
D High Pressure Switch compressor lubrication.
Shuts off unit if abnormal operating conditions cause
discharge pressure to rise above setting.
Protects the compressor from excessive condensing
pressure.
Manual reset.
E Loss of Charge Switch
Shuts off unit if liquid line pressure falls below setting.
Provides loss of charge and freeze-up protection.
Automatic reset.
F Hi-Capacity Drier(s)
Drier traps moisture or dirt that could contaminate the
refrigerant system.

TS 6 to 20 Ton R−410A Air Conditioners / Page 3


FEATURES AND BENEFITS
Cabinet CONTROLS
I Heavy−gauge, pre−painted steel cabinet provides superior OPTIONS
rust and corrosion protection. Field Installed
Removeable panels allow access for unit servicing.
L Connection® Network
J Heavy duty steel base channels raise the unit off of Complete building automation control system for single or
mounting surface away from damaging moisture.
Unit lifting holes and forklift slots furnished in base rails. multi−zone applications. Options include local interface,
See dimension drawings. software for local or remote communication, and
hardware for networking other control functions. See L
K Control Box Connection Network Engineering Handbook Bulletin for
Control box located in separate compartment in unit
details.
cabinet .
All controls are pre-wired at the factory. Network Thermostat Controller
Control box is large enough for field installed DDC or other Required for use with the L Connection Network. Monitors
field supplied control modules. and controls system operation.
OPTIONS Low Ambient Control
Factory Installed Air conditioning units operate satisfactorily down to 30ºF
Corrosion Protection outdoor air temperature without any additional controls.
Polymeric epoxy coating that is deposited by electrical Low Ambient Control Kit can be field installed, allowing
transport (electrophoresis), using a process known as unit operation down to 0ºF.
electrocoat (e−coat). Available for enhanced coil corrosion Thermostat
protection. Factory installed on the condenser coil. Thermostat is not furnished with unit and must be ordered
Painted base pan is provided with this option. extra.
Field Installed See Page 5, individual Thermostat bulletins and Lennox
Coil Guards Price Book.
Heavy duty sheet metal and metal mesh enclosures
protect coils from damage. Field installed.
Hail Guards
Heavy duty sheet metal and metal mesh enclosures
protect coils from damage. Field installed.

TS 6 to 20 Ton R−410A Air Conditioners / Page 4


OPTIONAL CONVENTIONAL TEMPERATURE CONTROL SYSTEMS − FIElD INSTALLED
COMMERCIAL TOUCHSCREEN THERMOSTAT

Intuitive Touchscreen Interface − Two Stage Heating / Two Stage Cooling Con- C0STAT02AE1L
ventional or Heat Pump − Seven Day Programmable − Four Time Periods/Day −
Economizer Output − Title 24 Compliant − ENERGY STAR® Qualified − Backlit Display −
Automatic Changeover

Sensors For Touchscreen Thermostat


1 Remote non−adjustable wall mount 20k temperature sensor . . . . . . . . . . . . . . . . . . . . C0SNZN01AE1−
1 Remote non−adjustable wall mount 10k averaging temperature sensor . . . . . . . . . . C0SNZN73AE1−
1 Remote non−adjustable duct mount temperature sensor . . . . . . . . . . . . . . . . . . . . . . . C0SNDC00AE1−

Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


C0SNSR03AE1−

Accessories For Touchscreen Thermostat

Locking cover (clear) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0MISC15AE1−


1 Remote sensors for C0STAT02AE1L can be applied in the following combinations:
(1) C0SNZN01AE1−, (2) C0SNZN73AE1−, (2) C0SNZN01AE1− and (1) C0SNZN73AE1−,
(4) C0SNZN01AE1−, (3) C0SNZN01AE1− and (2) C0SNZN73AE1.

DIGITAL NON−PROGRAMMABLE THERMOSTATS

Intuitive Interface − Automatic Changeover − Simple Up and Down Temperature Control

Two−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT10AE1L

Sensor For Digital Non−Programmable Thermostats Above

Remote wall mounted temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0SNZN00AE1−

Intuitive Interface − Automatic Changeover − Backlit Display − Simple Up and Down


Temperature Control

One−stage heating / cooling conventional systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . C0STAT12AE1L

Sensor For Digital Non−Programmable Thermostats Above

Outdoor temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


C0SNSR04AE1−

Accessories For Digital Non−Programmable Thermostats Above

Optional wall mounting plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


C0MISC17AE1−

TS 6 to 20 Ton R−410A Air Conditioners / Page 5


Specifications 6 − 7.5 TON
General Model No. TSA072S4S TSA090S4S
Data
Nominal Size − Tons 6 7.5

Connections Liquid line − in. (o.d) (1) 5/8 (1) 5/8


(sweat)
Suction line − in. (o.d) (1) 1−1/8 (1) 1−1/8

Refrigerant (R−410A) Factory installed holding charge


1 Field provided charge with 25 ft. line set 11 lbs. 0 oz. 16 lbs. 0 oz.

Condenser Net face area − sq. ft. Outer coil 29.3 29.3
Coil
Inner coil −−− 28.4

Tube diameter − in. & no. of rows 3/8 − 1 3/8 − 2

Fins per inch 20 20

Condenser Diameter − in. & no. of blades (1) 24 − 3 (1) 24 − 4


Fan(s)
Motor hp (1) 1/3 (1) 1/2

Total air volume − cfm 5100 5600

Rpm 1075 1075

Watts 430 580


ELECTRICAL DATA
Line voltage data − 60 hz − 3 phase 208/230V 460V 575V 208/230V 460V 575V
2 Maximum Overcurrent Protection (amps) 45 20 15 50 25 20
3 Minimum circuit ampacity 27 14 11 35 17 13

Compressor No. of Compressors 1 1 1 1 1 1

Rated load amps 19 9.7 7.4 25 12.2 9

Locked rotor amps 123 62 50 164 100 78

Condenser No. of motors 1 1 1 1 1 1


FanMotor
(1 phase) Full load amps 2.4 1.3 1 3 1.5 1.2

Locked rotor amps 4.7 2.4 1.9 6 3 2.9


NOTE − Extremes of operating range are plus and minus 10% of line voltage.
1 Refer to the Lennox Refrigerant Piping Manual to determine refrigerant charge required with longer length refrigerant lines.
2 HACR type circuit breaker or fuse.
3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

TS 6 to 20 Ton R−410A Air Conditioners / Page 6


Specifications 10 TON
General Model No. TSA120S4S TSA120S4D
Data
Nominal Size − Tons 10 10

Connections Liquid line − in. (o.d) (1) 5/8 (2) 5/8


(sweat)
Suction line − in. (o.d) (1) 1−3/8 (2) 1−1/8

Refrigerant (R−410A) Factory installed holding charge


1 Field provided charge with 25 ft. line set 17 lbs. 0 oz. 20 lbs. 0 oz.

Condenser Net face area − sq. ft. Outer coil 29.3 29.3
Coil
Inner coil 28.4 28.4

Tube diameter − in. & no. of rows 3/8 − 2 3/8 − 2

Fins per inch 20 20

Condenser Diameter − in. & no. of blades (2) 24 − 3 (2) 24 − 3


Fan(s)
Motor hp (2) 1/3 (2) 1/3

Total air volume − cfm 8300 8300

Rpm 1075 1075

Watts 830 830


ELECTRICAL DATA
Line voltage data − 60 hz − 3 phase 208/230V 460V 575V 208/230V 460V 575V
2 Maximum Overcurrent Protection (amps) 70 40 25 50 25 20
3 Minimum circuit ampacity 43 24 18 41 21 15

Compressor No. of Compressors 1 1 1 2 2 2

Rated load amps (total) 30.1 16.7 12.2 18 (32) 7.8 (15.6) 5.7 (11.4)

Locked rotor amps (total) 225 114 80 110 (220) 52 (104) 38.9 (77.8)

Condenser No. of motors 2 2 2 2 2 2


FanMotor
(1 phase) Full load amps (total) 2.4 (4.8) 1.3 (2.6) 1 (2) 2.4 (4.8) 1.3 (2.6) 1 (2)

Locked rotor amps (total) 4.7 (9.4) 2.4 (4.8) 1.9 (3.8) 4.7 (9.4) 2.4 (4.8) 1.9 (3.8)
NOTE − Extremes of operating range are plus and minus 10% of line voltage.
1 Refer to the Lennox Refrigerant Piping Manual to determine refrigerant charge required with longer length refrigerant lines.
2 HACR type circuit breaker or fuse.
3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

TS 6 to 20 Ton R−410A Air Conditioners / Page 7


Specifications 12.5 − 20 TON
General Model No. TSA150S4D TSA180S4D TSA240S4D
Data
Nominal Size − Tons 12.5 15 20

Connections Liquid line − in. (o.d) (2) 5/8 (2) 5/8 (2) 5/8
(sweat)
Suction line − in. (o.d) (2) 1−1/8 (2) 1−1/8 (2) 1−3/8

Refrigerant (R−410A) Factory installed holding charge


1 Field provided charge with 25 ft. line set 21 lbs. 0 oz. 29 lbs. 0 oz. 35 lbs. 0 oz.

Condenser Net face area − sq. ft. Outer coil 34.2 58.7 58.7
Coil
Inner coil 33.3 57.7 57.7

Tube diameter − in. & no. of rows 3/8 − 2 3/8 − 2 3/8 − 2

Fins per inch 20 20 20

Condenser Diameter − in. & no. of blades (2) 24 − 4 (4) 24 − 3 (4) 24 − 3


Fan(s)
Motor hp (2) 1/2 (4) 1/3 (4) 1/3

Total air volume − cfm 10,300 16,600 16,600

Rpm 1075 1075 1075

Watts 1130 1660 1660


ELECTRICAL DATA
Line voltage data − 60 hz − 3 phase 208/230V 460V 575V 208/230V 460V 575V 208/230V 460V 575V
2 Maximum Overcurrent Protection (amps) 60 30 25 90 40 30 100 50 40
3 Minimum circuit ampacity 49 25 20 66 33 25 78 43 32

Compressor No. of Compressors 2 2 2 2 2 2 2 2 2

Rated load amps 19 9.7 7.4 25 12.2 9 30.1 16.7 12.2


(total) (38) (19.4) (14.8) (50) (24.4) (18) 60.2) (33.4) (24.8)

Locked rotor amps 123 62 50 164 100 78 225 114 80


(total) (246) (124) (100) (328) (200) (156) (450) (228) (160)

Condenser No. of motors 2 2 2 4 4 4 4 4 4


FanMotor
(1 phase) Full load amps 3 1.5 1.2 2.4 1.3 1 2.4 1.3 1
(total) (6) (3) (2.4) (9.6) (5.2) (4) (9.6) (5.2) (4)

Locked rotor amps 6 3 2.9 4.7 2.4 1.9 4.7 2.4 1.9
(total) (12) (6) (5.8) (18.8) (9.6) (7.6) (18.8) (9.6) (7.6)
NOTE − Extremes of operating range are plus and minus 10% of line voltage.
1 Refer to the Lennox Refrigerant Piping Manual to determine refrigerant charge required with longer length refrigerant lines.
2 HACR type circuit breaker or fuse.
3 Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.

TS 6 to 20 Ton R−410A Air Conditioners / Page 8


OPTIONs / ACCESSORIES
Item Catalog 072S4S 090S4S 120S4S 120S4D 150S4D 180S4D 240S4D
No.
CABINET
Coil Guards T2GARD20L−1 47W12 x x
T2GARD20M−1 47W13 x x
T2GARD21M−1 47W14 x
T2GARD20N−1− 47W15 x x
Hail Guards T2GARD10L−1 47W16 x x
T2GARD10M−1 47W17 x x
T2GARD11M−1 47W18 x
T2GARD10N−1 47W19 x x
Corrosion Protection Factory f f f f f f f
CONTROLS
L Connection® Building Automation System −−− x x x x x x x
Low Ambient Control (0ºF) T2CWKT01LM1− 44W17 x x x
T2CWKT02M−1− 44W18 x x
T2CWKT03N−1− 44W19 x x
Network Thermostat Controller C0CTRL07AE1L 17M10 x x x x x x x
NOTE − The catalog and model numbers that appear here are for ordering field installed accessories only.
f − Factory Installed with extended lead time.
X − Field Installed

OUTDOOR SOUND DATA


Octave Band Sound Power Levels dBA, re 10−12 Watts 1Sound
1
Unit Rating
Center Frequency − HZ
Model No. Number
63 125 250 500 1000 2000 4000 8000 (dB)
TSA072S4S 60 65 68 73 76 72 68 63 81
TSA090S4S 56 64 69 73 77 74 70 63 81
TSA120S4S 61 70 77 82 81 77 75 71 86
TSA120S4D 65 71 77 80 80 77 72 67 85
TSA150S4D 62 68 77 80 82 78 73 65 86
TSA180S4D 66 73 80 83 83 79 74 66 88
TSA240S4D 66 73 80 85 84 80 78 74 89
NOTE − The octave sound power data does not include tonal correction.
1 Tested according to ARI Standard 270 or 370 test conditions.

TS 6 to 20 Ton R−410A Air Conditioners / Page 9


ARI RATINGS
Gross Net Integrated
Cooling Cooling Part Indoor Coil or Expansion
EER Air Handler Device
Capacity Capacity Load
Btuh Btuh Value
TSA072S4S 6 TON
Air Handlers
68,300 66,000 10.2 −−− 2 CBX32M−060 (Multi−Position) Factory TXV
71,800 69,000 10.2 −−− 3 CBX27UH−060 (Up−Flow / Horizontal) Factory TXV
72,700 71,000 11.2 −−− 3 TAA072S4S (Up−Flow / Horizontal) Factory TXV
Up−Flow Indoor Coils
71,800 69,000 10.5 −−− 2 CX34−62D−6F Factory TXV
75,000 72,000 10.8 −−− (2) CX34−43B/C−6F Factory TXV
Horizontal Indoor Coils
70,100 68,000 10.3 −−− 2 CH33−62D−2F 1 91M02
TSA090S4S 7.5 TON
Air Handlers
91,800 89,000 11.2 −−− 3 TAA090S4S (Up−Flow / Horizontal) Factory TXV
95,000 92,000 11.3 −−− 3 TAA120S4D (Up−Flow / Horizontal) Factory TXV
Up−Flow Indoor Coils
92,200 89,000 10.8 −−− 2 (2) CX34−49C−6F Factory TXV
Down−Flow Indoor Coils
90,800 87,000 10.6 −−− 2 (2) CR33−50/60C−F 1 91M02
Horizontal Indoor Coils
92,800 89,000 10.8 −−− 2 (2) CH33−49C−2F 1 91M02
(2) TSA090S4S (2) 7.5 TON
Air Handlers
178,000 172,000 11.0 12.2 3 TAA180S4D (Up−Flow / Horizontal) Factory TXV
TSA120S4S 10 TON
Air Handlers
117,100 113,000 11.2 −−− 3 TAA120S4D (Up−Flow / Horizontal) Factory TXV
Up−Flow Indoor Coils
115,500 111,000 10.9 −−− 2 (2) CX34−62D−6F Factory TXV
Down−Flow Indoor Coils
111,400 107,000 10.6 −−− 2 (2) CR33−50/60C−2F 1 91M02
Horizontal Indoor Coils
116,000 111,000 10.8 −−− 2 (2) CH33−62D−2F 1 91M02
(2) TSA120S4S (2) 10 TON
Air Handlers
231,800 222,000 11.0 12.0 3 TAA240S4D (Up−Flow / Horizontal)
TSA120S4D (DUAL CIRCUIT) 10 TON
Air Handlers
119,700 115,000 11.2 11.8 3 TAA120S4D (Up−Flow / Horizontal) Factory TXV
Up−Flow Indoor Coils
115,900 111,000 10.8 11.3 (2) CX34−60D−6F Factory TXV
116,900 112,000 10.9 11.4 (2) CX34−62D−6F Factory TXV
Down−Flow Indoor Coils
111,700 107,000 10.7 11.1 2 (2) CR33−50/60C−2F 1 91M02
Horizontal Indoor Coils
116,100 111,000 10.8 11.2 2 (2) CH33−62D−2F 1 91M02
NOTES − Net capacity includes indoor blower motor heat deduction. Gross capacity does not include indoor blower motor heat deduction.
Units with capacity of 65,000 Btuh or greater are certified in accordance with the ULE certification program which is based on ARI Standard 340/360: 95_F outdoor air
temperature, 80_F db/67_F wb entering evaporator air (minimum external duct static pressure) with 25 ft. of connecting refrigerant lines.
1 Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
2 Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation.
3 Blower control must be set for a time−off blower delay.

TS 6 to 20 Ton R−410A Air Conditioners / Page 10


ARI RATINGS
Gross Net Integrated
Cooling Cooling Part Indoor Coil or Expansion
EER Air Handler Device
Capacity Capacity Load
Btuh Btuh Value
TSA150S4D (DUAL CIRCUIT) 12.5 TON
Air Handlers
140,300 136,000 11.0 11.4 3 TAA120S4D (Up−Flow / Horizontal) Factory TXV
140,100 136,000 11.0 11.4 3 TAA150S4D (Up−Flow / Horizontal) Factory TXV
147,700 142,000 11.2 11.6 3 TAA180S4D (Up−Flow / Horizontal) Factory TXV
TSA180S4D (DUAL CIRCUIT) 15 TON
Air Handlers
183,500 178,000 11.0 12.0 3 TAA180S4D (Up−Flow / Horizontal) Factory TXV
195,600 190,000 11.4 12.2 3 (2) TAA090S4S (Up−Flow / Horizontal) Factory TXV
TSA240S4D (DUAL CIRCUIT) 20 TON
Air Handlers
240,900 232,000 11.0 11.8 3 TAA240S4D (Up−Flow / Horizontal) Factory TXV
244,600 236,000 11.3 12.0 3 (2) TAA120S4D (Up−Flow / Horizontal) Factory TXV
NOTES − Net capacity includes indoor blower motor heat deduction. Gross capacity does not include indoor blower motor heat deduction.
Units with capacity of 65,000 Btuh or greater are certified in accordance with the ULE certification program which is based on ARI Standard 340/360: 95_F outdoor air
temperature, 80_F db/67_F wb entering evaporator air (minimum external duct static pressure) with 25 ft. of connecting refrigerant lines.
1 Factory installed RFC or expansion valve on indoor unit MUST be replaced with expansion valve kit (ordered separately).
2 Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (58M81) is recommended for field installation.
3 Blower control must be set for a time−off blower delay.

WEIGHT DATA
Net Shipping
Model No.
lbs. kg lbs. kg
072 305 138 325 147
090 355 161 375 170
120S 465 211 490 222
120D 480 218 505 229
150 535 243 560 254
180 775 352 800 363
240 865 392 890 404
OPTIONs / ACCESSORIES
Net Shipping
lbs. kg lbs. kg
COIL GUARDS
T2GARD20L−1 40 18 45 20
T2GARD20M−1 45 20 50 23
T2GARD21M−1 45 20 50 23
T2GARD20N−1− 90 41 100 45
HAIL GUARDS
T2GARD10L−1 70 32 75 34
T2GARD10M−1 75 34 80 36
T2GARD11M−1 75 34 80 36
T2GARD10N−1 120 54 130 59

TS 6 to 20 Ton R−410A Air Conditioners / Page 11


UNIT CLEARANCES − INCHES (MM)
TSA072 and TSA090

See CONTROL
NOTES BOX ACCESS

NOTES:
Service clearance of 30 in. (762 mm) must be maintained on
one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in.
See See (914 mm).
NOTES NOTES Clearance to one of the remaining two sides may be 12 in.
(305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between
two units.
48 in. (1219 mm) clearance required on top of unit.

See
NOTES

TSA120 and TSA150

See
NOTES

NOTES:
Service clearance of 30 in. (762 mm) must be main-
tained on one of the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. See See
(914 mm). NOTES NOTES
Clearance to one of the remaining two sides may be 12
in. (305 mm) and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained be-
tween two units.
48 in. (1219 mm) clearance required on top of unit.

See CONTROL
NOTES BOX ACCESS

TSA180 and TSA240

See
NOTES

NOTES:
Service clearance of 30 in. (762 mm) must be
maintained on one of the sides adjacent to the
control box.
Clearance to one of the other three sides must be
See See 36 in. (914 mm).
NOTES NOTES Clearance to one of the remaining two sides may
be 12 in. (305 mm) and the final side may be 6 in.
(152 mm).
A clearance of 24 in. (610 mm) must be main-
tained between two units.
48 in. (1219 mm) clearance required on top of unit.

See CONTROL
NOTES BOX ACCESS

TS 6 to 20 Ton R−410A Air Conditioners / Page 12


DIMENSIONS − INCHES (MM) TSA072 AND TSA090
CORNER WEIGHTS CENTER OF GRAVITY
Model No. AA BB CC DD EE FF
lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
TSA072S4S 73 33 67 30 78 35 85 39 33 584 18−1/2 470
TSA090S4S 86 39 93 42 92 42 85 39 25 635 20−1/4 514

OPTIONAL
HAIL GUARD
(Field Installed
All Coil Sides)
(Not used with
9-1/8 Coil Guard)
(232) AA INLET AIR BB

LIQUID
1−1/8 LINE CENTER OF
(29) GRAVITY

INLET AIR
5
(127) 1−1/8 SUCTION EE
(29) LINE FF

3−5/8
(92)
DD INLET AIR CC
REFRIGERANT LINE
ELECTRICAL OUTDOOR
CONNECTIONS DETAIL INLETS (Above FAN GUARD
Refrigerant Lines)

TOP VIEW

37-5/8 OPTIONAL HAIL GUARD 46-1/8 12


(956) (Field Installed All Coil Sides) (1172) (305)
DISCHARGE (Not used with Coil Guard) DISCHARGE
AIR AIR 2(51)

CONTROL
BOX ACCESS
45-1/4
COMPRESSOR COMPRESSOR (1149)

REFRIGERANT 48-3/4
LINE CONNECTIONS (1238)
SEE DETAIL

ELECTRICAL
INLETS (Above
Refrigerant Lines)

LIFTING HOLES FORKLIFT SLOTS


(For Rigging) (Both Sides) 3-1/2
BASE BASE (89)
39-7/8 48-3/8
(1013) (1229) OPTIONAL
COIL GUARD
FRONT VIEW SIDE VIEW (Field Installed All Coil Sides)
(Not used with Hail Guard)

TS 6 to 20 Ton R−410A Air Conditioners / Page 13


DIMENSIONS − INCHES (MM) TSA120 AND TSA150
CORNER WEIGHTS CENTER OF GRAVITY
Model No. AA BB CC DD EE FF
lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
TSA120S4S 136 62 121 55 96 44 108 49 20−1/2 521 33−1/2 851
TSA120S4D 120 54 112 51 124 56 133 60 21 533 28−1/2 724
TSA150S4D 152 69 117 53 117 53 152 69 19 483 30 762

OPTIONAL HAIL GUARD


(Field Installed All Coil Sides)
(Not used with Coil Guard)

AA INLET AIR BB
9−1/8
OUTDOOR FAN
(232)
GUARDS (2)
6−1/2
(165)
CENTER OF
LIQUID GRAVITY
3−3/4 LINES
(95)

INLET AIR
1−1/8 SUCTION
(29) LINES

EE
5 FF
1−1/8
(127) (29)

3−5/8
(92)

CC
SINGLE STAGE STAGE 1 STAGE 2 DD
TSA120S4S TSA120S4D TSA120S4D ELECTRICAL INLET AIR
TSA150S4D TSA150S4D INLETS (Above
Refrigerant Lines)
REFRIGERANT LINE
TOP VIEW
CONNECTIONS DETAIL

57-7/8 41-3/8 12
(1470) OPTIONAL HAIL GUARD (1051) (305)
(Field Installed All Coil Sides)
DISCHARGE (Not used with Coil Guard) DISCHARGE 2(51)
AIR AIR

COMPRESSOR CONTROL
BOX ACCESS 48-3/4
(1238)

REFRIGERANT
LINE CONNECTIONS
SEE DETAIL 45-1/4
(1149)

ELECTRICAL
INLETS (Above
Refrigerant Lines)
3-1/2
FORKLIFT SLOTS LIFTING HOLES (89)
(Both Sides) (For Rigging) OPTIONAL
COIL GUARD
60-1/8 BASE 43-5/8 BASE (Field Installed
(1527) (1108) All Coil Sides)
FRONT VIEW SIDE VIEW (Not used with
Hail Guard)

TS 6 to 20 Ton R−410A Air Conditioners / Page 14


DIMENSIONS − INCHES (MM) TSA180 AND TSA240
CORNER WEIGHTS CENTER OF GRAVITY
Model No. AA BB CC DD EE FF
lbs. kg lbs. kg lbs. kg lbs. kg in. mm in. mm
TSA180S4D 223 101 166 75 178 81 238 108 29 737 38 965
TSA240S4D 265 120 197 89 197 89 265 120 30 762 38 965

OPTIONAL
HAIL GUARD
(Field Installed
All Coil Sides)
(Not used with
Coil Guard)
9−1/8 OUTDOOR FAN
LIQUID INLET
(232) LINE (2) GUARDS (4)
AA AIR BB
6−1/2 SUCTION
(165) LINE (2)

3−3/4
(95)
1−1/8 CENTER OF
(29) GRAVITY

INLET
AIR
5 1−1/8 FF
(127) (29)
EE
3−5/8
(92)

DD CC
STAGE 1 STAGE 2 INLET
ELECTRICAL AIR
REFRIGERANT LINE INLETS (Above
CONNECTIONS DETAIL Refrigerant Lines) TOP VIEW

OPTIONAL
HAIL GUARD
57-7/8 (Field Installed 86-1/2 12
(1470) All Coil Sides) (2197) (305)
DISCHARGE (Not used with DISCHARGE 2(51)
AIR Coil Guard) AIR

COMPRESSOR 48-3/4
REFRIGERANT (1238)
CONTROL LINE CONNECTIONS 45-1/4
BOX ACCESS SEE DETAIL (1149)

ELECTRICAL
INLETS (Above
LIFTING HOLES Refrigerant Lines) FORKLIFT SLOTS
(Both Sides) 3-1/2
(For Rigging)
60-1/8 BASE 88-3/4 BASE (89)
(1527) (2254)
FRONT VIEW SIDE VIEW OPTIONAL
COIL GUARD
(Field Installed All Coil Sides)
(Not used with Hail Guard)

TS 6 to 20 Ton R−410A Air Conditioners / Page 15


RATINGS 6 TON
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

AIR HANDLERS
COOLING CAPACITY − TSA072S4S with [CBX27UH−060]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
1920 905 69.1 20.3 4.83 .68 .83 .98 66.2 19.4 5.37 .70 .86 1.00 62.8 18.4 5.97 .71 .89 1.00 59.1 17.3 6.66 .74 .93 1.00
63_F 2400 1135 72.6 21.3 4.86 .73 .91 1.00 69.5 20.4 5.40 .75 .94 1.00 66.2 19.4 6.00 .77 .97 1.00 62.4 18.3 6.69 .80 1.00 1.00
(17_C)
2880 1360 75.7 22.2 4.87 .78 .97 1.00 72.6 21.3 5.42 .80 1.00 1.00 68.9 20.2 6.01 .84 1.00 1.00 65.3 19.1 6.71 .88 1.00 1.00
1920 905 72.7 21.3 4.86 .55 .66 .79 69.7 20.4 5.39 .55 .67 .81 66.1 19.4 5.99 .56 .69 .84 62.3 18.3 6.69 .57 .71 .88
67_F 2400 1135 76.3 22.4 4.88 .57 .70 .87 72.9 21.4 5.41 .58 .72 .90 69.2 20.3 6.03 .59 .75 .93 65.0 19.0 6.71 .61 .78 .97
(19_C)
2880 1360 79.0 23.2 4.90 .60 .75 .94 75.4 22.1 5.43 .61 .78 .97 71.5 21.0 6.04 .62 .81 1.00 67.2 19.7 6.74 .64 .85 1.00
1920 905 76.3 22.4 4.88 .41 .53 .64 73.0 21.4 5.42 .42 .54 .65 69.5 20.4 6.02 .42 .55 .67 65.4 19.2 6.71 .42 .56 .69
71_F 2400 1135 80.0 23.4 4.90 .42 .56 .68 76.4 22.4 5.44 .43 .57 .70 72.7 21.3 6.05 .44 .58 .72 68.3 20.0 6.74 .44 .60 .75
(22_C)
2880 1360 82.7 24.2 4.91 .44 .59 .73 79.1 23.2 5.46 .44 .60 .75 75.0 22.0 6.07 .45 .61 .78 70.5 20.7 6.77 .46 .63 .82

COOLING CAPACITY − TSA072S4S with [CBX32M−060]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
1920 905 69.2 20.3 4.84 .68 .82 .97 66.0 19.3 5.37 .69 .85 .99 62.5 18.3 5.97 .70 .87 1.00 58.7 17.2 6.65 .72 .91 1.00
63_F 2400 1135 72.5 21.2 4.85 .72 .90 1.00 69.1 20.3 5.40 .74 .93 1.00 65.5 19.2 6.00 .76 .96 1.00 61.5 18.0 6.68 .79 .98 1.00
(17_C)
2880 1360 75.0 22.0 4.87 .77 .96 1.00 71.6 21.0 5.41 .79 .98 1.00 67.8 19.9 6.01 .82 1.00 1.00 63.8 18.7 6.70 .85 1.00 1.00
1920 905 73.0 21.4 4.86 .54 .65 .78 69.7 20.4 5.40 .55 .67 .80 66.0 19.3 6.00 .55 .68 .83 61.9 18.1 6.69 .56 .70 .87
67_F 2400 1135 76.2 22.3 4.88 .56 .69 .86 72.6 21.3 5.41 .57 .71 .88 68.9 20.2 6.02 .58 .73 .92 64.7 19.0 6.70 .60 .76 .95
(19_C)
2880 1360 78.8 23.1 4.90 .59 .74 .93 75.2 22.0 5.43 .60 .76 .95 71.2 20.9 6.04 .61 .79 .98 66.7 19.5 6.73 .62 .82 1.00
1920 905 76.8 22.5 4.88 .41 .52 .63 73.5 21.5 5.42 .42 .53 .64 69.7 20.4 6.03 .42 .54 .66 65.5 19.2 6.71 .42 .55 .68
71_F 2400 1135 80.3 23.5 4.91 .42 .55 .67 76.7 22.5 5.44 .43 .56 .69 72.7 21.3 6.05 .43 .57 .70 68.2 20.0 6.74 .44 .58 .73
(22_C)
2880 1360 82.8 24.3 4.92 .43 .57 .71 78.9 23.1 5.46 .44 .59 .73 74.8 21.9 6.07 .44 .60 .76 70.1 20.5 6.76 .45 .62 .79

COOLING CAPACITY − TSA072S4S with [TAA072S4S]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
1920 905 70.4 20.6 4.84 .68 .83 .99 67.2 19.7 5.38 .69 .86 1.00 63.7 18.7 5.98 .71 .89 1.00 59.7 17.5 6.67 .73 .93 1.00
63_F 2400 1135 74.0 21.7 4.87 .73 .92 1.00 70.5 20.7 5.40 .75 .95 1.00 66.9 19.6 6.01 .77 .98 1.00 62.6 18.3 6.69 .80 1.00 1.00
(17_C)
2880 1360 76.7 22.5 4.88 .78 .99 1.00 72.9 21.4 5.41 .80 1.00 1.00 69.4 20.3 6.02 .84 1.00 1.00 65.7 19.3 6.72 .87 1.00 1.00
1920 905 74.2 21.7 4.86 .54 .66 .79 70.9 20.8 5.41 .55 .67 .81 67.0 19.6 6.01 .56 .69 .84 63.1 18.5 6.70 .57 .71 .88
67_F 2400 1135 77.7 22.8 4.89 .57 .70 .87 74.1 21.7 5.43 .58 .72 .90 70.3 20.6 6.03 .59 .74 .94 65.9 19.3 6.72 .60 .77 .98
(19_C)
2880 1360 80.4 23.6 4.90 .59 .75 .95 76.7 22.5 5.45 .61 .78 .98 72.5 21.2 6.05 .62 .81 1.00 68.0 19.9 6.74 .63 .84 1.00
1920 905 78.4 23.0 4.89 .41 .53 .64 74.9 22.0 5.43 .41 .53 .65 71.1 20.8 6.04 .42 .55 .66 66.6 19.5 6.72 .42 .55 .68
71_F 2400 1135 81.9 24.0 4.92 .42 .56 .68 78.1 22.9 5.45 .43 .56 .70 73.9 21.7 6.06 .43 .58 .72 69.4 20.3 6.75 .44 .59 .74
(22_C)
2880 1360 84.3 24.7 4.93 .43 .58 .73 80.4 23.6 5.47 .44 .59 .75 76.1 22.3 6.08 .45 .61 .78 71.4 20.9 6.77 .45 .62 .81

TS 6 to 20 Ton R−410A Air Conditioners / Page 16


RATINGS 6 TON
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

UP−FLOW INDOOR COIL


COOLING CAPACITY − TSA072S4S with [CX34−62D−6F]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
1920 905 69.7 20.4 4.84 .67 .81 .96 66.6 19.5 5.37 .68 .83 .99 63.1 18.5 5.98 .70 .86 1.00 59.2 17.3 6.65 .72 .90 1.00
63_F 2400 1135 73.4 21.5 4.86 .71 .88 1.00 70.0 20.5 5.40 .73 .91 1.00 66.4 19.5 6.00 .75 .95 1.00 62.2 18.2 6.68 .78 .99 1.00
(17_C)
2880 1360 76.1 22.3 4.87 .76 .95 1.00 72.4 21.2 5.42 .78 .98 1.00 68.6 20.1 6.02 .80 1.00 1.00 64.7 19.0 6.71 .84 1.00 1.00
1920 905 73.4 21.5 4.86 .54 .65 .77 70.3 20.6 5.40 .54 .66 .79 66.6 19.5 6.00 .55 .67 .82 62.7 18.4 6.69 .56 .69 .85
67_F 2400 1135 77.3 22.7 4.88 .56 .68 .84 73.8 21.6 5.42 .57 .70 .87 70.1 20.5 6.03 .57 .72 .90 65.7 19.3 6.71 .59 .75 .94
(19_C)
2880 1360 80.2 23.5 4.90 .58 .73 .91 76.4 22.4 5.44 .59 .75 .94 72.4 21.2 6.05 .60 .77 .98 67.7 19.8 6.73 .62 .81 1.00
1920 905 77.9 22.8 4.89 .41 .52 .63 74.5 21.8 5.43 .42 .53 .64 70.6 20.7 6.04 .42 .54 .65 66.3 19.4 6.72 .42 .55 .67
71_F 2400 1135 81.5 23.9 4.91 .42 .55 .66 77.6 22.7 5.45 .42 .55 .68 73.5 21.5 6.06 .43 .56 .69 69.1 20.3 6.75 .44 .58 .72
(22_C)
2880 1360 83.9 24.6 4.93 .43 .57 .70 80.1 23.5 5.47 .44 .58 .72 76.0 22.3 6.08 .44 .59 .75 71.4 20.9 6.77 .45 .61 .78

COOLING CAPACITY − TSA072S4S with [(2)CX34−43B/C−6F]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
1920 905 72.1 21.1 4.86 .67 .82 .97 68.9 20.2 5.39 .68 .84 1.00 65.3 19.1 5.99 .70 .87 1.00 61.3 18.0 6.68 .72 .91 1.00
63_F 2400 1135 76.0 22.3 4.88 .71 .89 1.00 72.4 21.2 5.42 .73 .92 1.00 68.4 20.0 6.02 .75 .96 1.00 64.1 18.8 6.70 .78 .99 1.00
(17_C)
2880 1360 78.7 23.1 4.90 .76 .97 1.00 75.0 22.0 5.43 .78 .99 1.00 71.1 20.8 6.04 .81 1.00 1.00 67.2 19.7 6.73 .85 1.00 1.00
1920 905 76.1 22.3 4.88 .54 .65 .77 72.4 21.2 5.41 .54 .66 .80 68.9 20.2 6.02 .55 .68 .82 64.8 19.0 6.71 .56 .69 .86
67_F 2400 1135 80.1 23.5 4.90 .56 .69 .85 76.4 22.4 5.44 .57 .70 .88 72.4 21.2 6.05 .58 .73 .91 67.6 19.8 6.73 .59 .75 .95
(19_C)
2880 1360 82.9 24.3 4.92 .58 .73 .92 78.9 23.1 5.46 .59 .75 .95 74.8 21.9 6.07 .60 .78 .99 70.0 20.5 6.75 .62 .81 1.00
1920 905 80.2 23.5 4.90 .41 .52 .63 76.7 22.5 5.44 .41 .53 .64 72.6 21.3 6.04 .41 .53 .65 68.3 20.0 6.74 .42 .55 .67
71_F 2400 1135 83.8 24.6 4.92 .42 .54 .67 79.9 23.4 5.46 .43 .56 .68 75.7 22.2 6.07 .43 .56 .70 71.2 20.9 6.77 .43 .58 .72
(22_C)
2880 1360 86.7 25.4 4.94 .43 .57 .71 82.6 24.2 5.49 .44 .58 .72 78.3 22.9 6.09 .44 .59 .75 73.6 21.6 6.79 .44 .61 .78

HORIZONTAL INDOOR COILS


COOLING CAPACITY − TSA072S4S with [CH33−62D−2F]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
1920 905 69.7 20.4 4.84 .67 .81 .96 66.6 19.5 5.37 .68 .83 .99 63.1 18.5 5.98 .70 .86 1.00 59.2 17.3 6.65 .72 .90 1.00
63_F 2400 1135 73.4 21.5 4.86 .71 .88 1.00 70.0 20.5 5.40 .73 .91 1.00 66.4 19.5 6.00 .75 .95 1.00 62.2 18.2 6.68 .78 .99 1.00
(17_C)
2880 1360 76.1 22.3 4.87 .76 .95 1.00 72.4 21.2 5.42 .78 .98 1.00 68.6 20.1 6.02 .80 1.00 1.00 64.7 19.0 6.71 .84 1.00 1.00
1920 905 73.4 21.5 4.86 .54 .65 .77 70.3 20.6 5.40 .54 .66 .79 66.6 19.5 6.00 .55 .67 .82 62.7 18.4 6.69 .56 .69 .85
67_F 2400 1135 77.3 22.7 4.88 .56 .68 .84 73.8 21.6 5.42 .57 .70 .87 70.1 20.5 6.03 .57 .72 .90 65.7 19.3 6.71 .59 .75 .94
(19_C)
2880 1360 80.2 23.5 4.90 .58 .73 .91 76.4 22.4 5.44 .59 .75 .94 72.4 21.2 6.05 .60 .77 .98 67.7 19.8 6.73 .62 .81 1.00
1920 905 77.9 22.8 4.89 .41 .52 .63 74.5 21.8 5.43 .42 .53 .64 70.6 20.7 6.04 .42 .54 .65 66.3 19.4 6.72 .42 .55 .67
71_F 2400 1135 81.5 23.9 4.91 .42 .55 .66 77.6 22.7 5.45 .42 .55 .68 73.5 21.5 6.06 .43 .56 .69 69.1 20.3 6.75 .44 .58 .72
(22_C)
2880 1360 83.9 24.6 4.93 .43 .57 .70 80.1 23.5 5.47 .44 .58 .72 76.0 22.3 6.08 .44 .59 .75 71.4 20.9 6.77 .45 .61 .78

TS 6 to 20 Ton R−410A Air Conditioners / Page 17


RATINGS 7.5 TON
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

AIR HANDLERS
COOLING CAPACITY − TSA090S4S with [TAA090S4D]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
2400 1135 88.5 25.9 5.78 .68 .82 .97 84.7 24.8 6.40 .69 .84 .99 80.6 23.6 7.13 .71 .87 1.00 76.1 22.3 7.95 .73 .90 1.00
63_F 3000 1415 92.7 27.2 5.86 .73 .90 1.00 88.5 25.9 6.48 .75 .93 1.00 84.0 24.6 7.20 .77 .96 1.00 79.1 23.2 8.02 .79 .99 1.00
(17_C)
3600 1700 95.8 28.1 5.91 .79 .97 1.00 91.3 26.8 6.54 .80 .99 1.00 87.0 25.5 7.26 .83 1.00 1.00 82.5 24.2 8.10 .86 1.00 1.00
2400 1135 93.5 27.4 5.87 .54 .65 .78 89.6 26.3 6.50 .54 .67 .80 85.3 25.0 7.22 .56 .69 .83 80.3 23.5 8.04 .57 .70 .86
67_F 3000 1415 97.5 28.6 5.95 .57 .70 .86 93.4 27.4 6.58 .58 .72 .89 88.6 26.0 7.29 .59 .74 .92 83.3 24.4 8.11 .60 .77 .95
(19_C)
3600 1700 100.7 29.5 6.01 .60 .76 .94 95.8 28.1 6.63 .60 .78 .97 91.1 26.7 7.34 .62 .81 .99 85.8 25.1 8.16 .64 .84 1.00
2400 1135 98.5 28.9 5.97 .41 .52 .63 94.2 27.6 6.59 .42 .53 .65 89.8 26.3 7.32 .42 .54 .66 84.8 24.9 8.15 .42 .56 .68
71_F 3000 1415 102.7 30.1 6.04 .43 .55 .69 98.2 28.8 6.68 .43 .57 .70 93.3 27.3 7.39 .43 .58 .72 87.8 25.7 8.20 .44 .58 .74
(22_C)
3600 1700 105.8 31.0 6.10 .44 .59 .74 100.7 29.5 6.72 .44 .59 .75 95.6 28.0 7.44 .45 .61 .78 90.2 26.4 8.26 .45 .63 .81

COOLING CAPACITY − TSA090S4S with [TAA120S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
2400 1135 89.7 26.3 5.80 .68 .82 .97 85.6 25.1 6.43 .69 .84 .99 81.4 23.9 7.14 .70 .87 1.00 76.8 22.5 7.97 .73 .90 1.00
63_F 3000 1415 93.9 27.5 5.88 .73 .91 1.00 89.5 26.2 6.50 .75 .94 1.00 85.1 24.9 7.22 .77 .97 1.00 80.1 23.5 8.04 .79 1.00 1.00
(17_C)
3600 1700 97.0 28.4 5.94 .78 .98 1.00 92.7 27.2 6.56 .81 1.00 1.00 88.7 26.0 7.30 .83 1.00 1.00 84.1 24.6 8.13 .87 1.00 1.00
2400 1135 94.9 27.8 5.89 .54 .65 .78 90.8 26.6 6.52 .55 .67 .80 86.0 25.2 7.24 .55 .68 .83 81.5 23.9 8.07 .56 .71 .86
67_F 3000 1415 99.3 29.1 5.98 .57 .71 .87 94.8 27.8 6.60 .58 .72 .90 89.8 26.3 7.32 .59 .75 .93 84.4 24.7 8.13 .60 .77 .96
(19_C)
3600 1700 102.1 29.9 6.03 .60 .76 .95 97.3 28.5 6.66 .61 .78 .98 92.3 27.1 7.37 .62 .81 1.00 87.0 25.5 8.19 .63 .85 1.00
2400 1135 100.0 29.3 5.99 .41 .52 .63 95.6 28.0 6.63 .42 .53 .65 90.9 26.6 7.34 .42 .54 .67 85.8 25.1 8.17 .42 .55 .68
71_F 3000 1415 104.9 30.7 6.09 .42 .56 .69 99.8 29.2 6.71 .43 .57 .70 94.8 27.8 7.42 .43 .58 .72 89.1 26.1 8.24 .43 .59 .74
(22_C)
3600 1700 107.6 31.5 6.15 .44 .59 .73 102.3 30.0 6.77 .44 .59 .76 97.4 28.5 7.48 .45 .62 .79 91.5 26.8 8.29 .46 .63 .82

COOLING CAPACITY − (2) TSA090S4S (FIRST STAGE) with [TAA180S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4800 2265 91.2 26.7 4.63 .67 .79 .93 88.1 25.8 5.13 .67 .81 .95 84.6 24.8 5.69 .69 .83 .97 80.8 23.7 6.32 .70 .85 .99
63_F 6000 2830 95.6 28.0 4.70 .71 .86 1.00 92.2 27.0 5.20 .72 .88 1.00 88.4 25.9 5.76 .73 .90 1.00 84.4 24.7 6.39 .75 .93 1.00
(17_C)
7200 3400 98.6 28.9 4.76 .75 .93 1.00 95.1 27.9 5.25 .76 .95 1.00 91.2 26.7 5.81 .78 .97 1.00 87.1 25.5 6.44 .80 .99 1.00
4800 2265 95.9 28.1 4.71 .53 .64 .76 92.7 27.2 5.21 .54 .65 .77 89.1 26.1 5.77 .54 .66 .79 85.2 25.0 6.40 .55 .67 .81
67_F 6000 2830 100.5 29.5 4.79 .56 .68 .83 96.9 28.4 5.29 .56 .69 .85 93.1 27.3 5.84 .57 .71 .87 88.7 26.0 6.47 .58 .72 .89
(19_C)
7200 3400 103.7 30.4 4.85 .58 .72 .89 99.9 29.3 5.34 .59 .74 .91 95.9 28.1 5.90 .60 .76 .94 91.3 26.8 6.52 .61 .78 .96
4800 2265 100.5 29.5 4.79 .42 .52 .62 97.2 28.5 5.29 .42 .52 .63 93.4 27.4 5.85 .42 .53 .64 89.3 26.2 6.48 .42 .54 .65
71_F 6000 2830 105.2 30.8 4.88 .42 .54 .66 101.6 29.8 5.37 .42 .55 .67 97.5 28.6 5.93 .42 .56 .69 93.1 27.3 6.55 .43 .57 .70
(22_C)
7200 3400 108.6 31.8 4.94 .43 .57 .70 104.6 30.7 5.43 .43 .58 .72 100.4 29.4 5.98 .44 .59 .73 95.9 28.1 6.61 .45 .60 .76

COOLING CAPACITY − (2) TSA090S4S (SECOND STAGE) with [TAA180S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4800 2265 169.3 49.6 11.38 .69 .83 .97 161.7 47.4 12.63 .70 .85 .99 154.1 45.2 14.09 .71 .87 1.00 145.2 42.6 15.75 .73 .90 1.00
63_F 6000 2830 176.9 51.8 11.51 .73 .90 1.00 168.8 49.5 12.77 .75 .93 1.00 160.4 47.0 14.21 .77 .95 1.00 151.1 44.3 15.84 .80 .99 1.00
(17_C)
7200 3400 182.4 53.5 11.62 .78 .97 1.00 174.3 51.1 12.87 .80 .99 1.00 165.3 48.4 14.31 .83 1.00 1.00 157.0 46.0 15.97 .86 1.00 1.00
4800 2265 178.2 52.2 11.54 .54 .66 .79 170.4 49.9 12.81 .55 .67 .81 161.9 47.4 14.23 .56 .69 .83 152.9 44.8 15.90 .57 .71 .87
67_F 6000 2830 186.1 54.5 11.68 .57 .71 .87 177.4 52.0 12.93 .58 .72 .89 168.8 49.5 14.37 .59 .74 .92 158.9 46.6 16.03 .60 .77 .95
(19_C)
7200 3400 191.7 56.2 11.79 .60 .76 .94 182.5 53.5 13.03 .61 .78 .96 173.3 50.8 14.47 .62 .81 .99 163.1 47.8 16.11 .64 .84 1.00
4800 2265 186.7 54.7 11.70 .42 .53 .64 178.7 52.4 12.96 .42 .54 .65 170.0 49.8 14.40 .42 .55 .67 160.6 47.1 16.04 .43 .56 .69
71_F 6000 2830 194.9 57.1 11.86 .42 .56 .69 186.2 54.6 13.11 .43 .57 .70 176.9 51.8 14.55 .44 .58 .72 167.1 49.0 16.19 .44 .59 .75
(22_C)
7200 3400 200.8 58.8 11.97 .44 .59 .73 191.8 56.2 13.22 .45 .60 .76 182.1 53.4 14.64 .45 .61 .78 171.3 50.2 16.27 .45 .63 .82

TS 6 to 20 Ton R−410A Air Conditioners / Page 18


RATINGS 7.5 TON
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

UP−FLOW INDOOR COIL


COOLING CAPACITY − TSA090S4S with [(2) CX34−49C−6F]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
2400 1135 87.5 25.6 5.76 .67 .81 .95 83.8 24.6 6.39 .69 .83 .97 79.7 23.4 7.11 .70 .85 1.00 75.3 22.1 7.94 .72 .88 1.00
63_F 3000 1415 91.7 26.9 5.84 .71 .88 1.00 87.7 25.7 6.46 .73 .90 1.00 83.4 24.4 7.19 .75 .93 1.00 78.7 23.1 8.01 .78 .97 1.00
(17_C)
3600 1700 95.1 27.9 5.90 .76 .95 1.00 90.8 26.6 6.53 .78 .98 1.00 86.3 25.3 7.24 .81 1.00 1.00 81.9 24.0 8.08 .84 1.00 1.00
2400 1135 91.7 26.9 5.83 .54 .65 .77 87.8 25.7 6.47 .55 .66 .79 83.7 24.5 7.19 .55 .68 .81 79.2 23.2 8.02 .56 .69 .84
67_F 3000 1415 96.3 28.2 5.92 .56 .69 .84 92.0 27.0 6.55 .57 .71 .87 87.6 25.7 7.27 .58 .73 .90 82.8 24.3 8.09 .60 .75 .93
(19_C)
3600 1700 99.6 29.2 5.98 .59 .74 .91 95.1 27.9 6.61 .60 .76 .94 90.5 26.5 7.32 .61 .78 .97 85.3 25.0 8.15 .62 .81 1.00
2400 1135 96.4 28.3 5.92 .42 .53 .63 92.1 27.0 6.55 .42 .53 .64 87.9 25.8 7.28 .42 .55 .65 83.0 24.3 8.10 .42 .55 .67
71_F 3000 1415 100.6 29.5 6.01 .43 .55 .67 96.1 28.2 6.63 .43 .56 .69 91.6 26.8 7.35 .44 .57 .70 86.5 25.4 8.18 .44 .59 .73
(22_C)
3600 1700 104.1 30.5 6.08 .44 .58 .71 99.5 29.2 6.71 .44 .59 .73 94.7 27.8 7.42 .45 .60 .76 89.2 26.1 8.23 .45 .62 .79

DOWN−FLOW INDOOR COILS


COOLING CAPACITY − TSA090S4S with [(2) CR33−50/60C−F]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
2400 1135 86.1 25.2 5.73 .68 .81 .96 82.2 24.1 6.36 .69 .83 .98 78.3 22.9 7.08 .70 .86 1.00 73.8 21.6 7.91 .72 .89 1.00
63_F 3000 1415 89.9 26.3 5.80 .72 .88 1.00 85.9 25.2 6.43 .74 .91 1.00 81.6 23.9 7.15 .76 .94 1.00 76.8 22.5 7.97 .78 .97 1.00
(17_C)
3600 1700 92.7 27.2 5.85 .77 .95 1.00 88.5 25.9 6.48 .79 .98 1.00 84.3 24.7 7.20 .81 .99 1.00 80.1 23.5 8.04 .84 1.00 1.00
2400 1135 90.7 26.6 5.82 .54 .66 .78 86.7 25.4 6.45 .55 .67 .80 82.6 24.2 7.17 .56 .68 .82 78.0 22.9 7.99 .57 .70 .85
67_F 3000 1415 94.8 27.8 5.89 .57 .70 .85 90.6 26.6 6.52 .58 .71 .87 86.0 25.2 7.24 .59 .73 .90 81.2 23.8 8.07 .60 .76 .94
(19_C)
3600 1700 97.8 28.7 5.95 .59 .74 .92 93.4 27.4 6.58 .60 .76 .95 88.5 25.9 7.29 .61 .79 .97 83.3 24.4 8.11 .63 .82 1.00
2400 1135 95.2 27.9 5.90 .41 .53 .64 91.1 26.7 6.53 .42 .54 .65 86.8 25.4 7.26 .41 .55 .66 82.1 24.1 8.09 .42 .55 .68
71_F 3000 1415 99.5 29.2 5.98 .42 .56 .68 95.2 27.9 6.61 .43 .57 .69 90.5 26.5 7.33 .43 .58 .71 85.5 25.1 8.16 .44 .59 .73
(22_C)
3600 1700 102.8 30.1 6.05 .44 .58 .72 98.0 28.7 6.67 .44 .59 .74 93.2 27.3 7.39 .45 .61 .76 87.7 25.7 8.19 .45 .62 .79

HORIZONTAL INDOOR COILS


COOLING CAPACITY − TSA090S4S with [(2) CH33−49C−2F]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
2400 1135 87.6 25.7 5.76 .67 .81 .95 83.7 24.5 6.39 .68 .83 .98 79.7 23.4 7.11 .70 .85 1.00 75.1 22.0 7.93 .71 .88 1.00
63_F 3000 1415 91.7 26.9 5.83 .71 .88 1.00 87.6 25.7 6.46 .73 .91 1.00 83.4 24.4 7.19 .75 .93 1.00 78.5 23.0 8.01 .78 .97 1.00
(17_C)
3600 1700 94.9 27.8 5.90 .76 .95 1.00 90.6 26.6 6.52 .78 .98 1.00 85.7 25.1 7.23 .80 1.00 1.00 81.6 23.9 8.07 .84 1.00 1.00
2400 1135 92.4 27.1 5.85 .54 .65 .77 88.4 25.9 6.48 .54 .66 .79 84.1 24.6 7.20 .55 .67 .81 79.6 23.3 8.03 .56 .69 .84
67_F 3000 1415 96.9 28.4 5.93 .56 .69 .84 92.5 27.1 6.56 .57 .71 .87 87.9 25.8 7.28 .58 .73 .90 82.8 24.3 8.10 .59 .75 .93
(19_C)
3600 1700 99.9 29.3 5.99 .59 .74 .92 95.4 28.0 6.62 .60 .76 .94 90.4 26.5 7.33 .60 .78 .97 85.0 24.9 8.14 .62 .81 1.00
2400 1135 97.0 28.4 5.94 .42 .52 .63 92.9 27.2 6.57 .42 .53 .64 88.4 25.9 7.29 .42 .54 .65 83.7 24.5 8.12 .42 .55 .67
71_F 3000 1415 101.7 29.8 6.02 .42 .55 .67 97.2 28.5 6.66 .43 .56 .69 92.5 27.1 7.38 .43 .57 .70 87.2 25.6 8.20 .44 .58 .73
(22_C)
3600 1700 105.0 30.8 6.09 .44 .58 .71 100.3 29.4 6.72 .44 .59 .74 95.2 27.9 7.43 .45 .60 .76 89.6 26.3 8.24 .45 .61 .79

TS 6 to 20 Ton R−410A Air Conditioners / Page 19


RATINGS 10 TON
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

AIR HANDLERS
COOLING CAPACITY − TSA120S4S with [TAA120S4D]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 113.3 33.2 7.09 .71 .86 .99 108.4 31.8 7.90 .73 .88 1.00 103.1 30.2 8.82 .74 .90 1.00 97.4 28.5 9.86 .76 .93 1.00
63_F 4000 1890 118.5 34.7 7.18 .77 .94 1.00 113.2 33.2 7.99 .79 .96 1.00 107.6 31.5 8.90 .81 .99 1.00 101.6 29.8 9.93 .83 1.00 1.00
(17_C)
4800 2265 122.2 35.8 7.25 .82 1.00 1.00 117.2 34.3 8.06 .84 1.00 1.00 112.3 32.9 8.98 .87 1.00 1.00 106.6 31.2 10.03 .90 1.00 1.00
3200 1510 120.0 35.2 7.21 .56 .69 .82 114.8 33.6 8.01 .58 .70 .84 109.3 32.0 8.93 .58 .72 .87 102.9 30.2 9.96 .59 .74 .90
67_F 4000 1890 124.8 36.6 7.30 .60 .75 .91 119.5 35.0 8.10 .60 .76 .93 113.3 33.2 9.00 .62 .78 .96 106.6 31.2 10.03 .63 .81 .99
(19_C)
4800 2265 128.5 37.7 7.37 .63 .80 .98 122.3 35.8 8.16 .64 .82 1.00 116.2 34.1 9.06 .65 .84 1.00 109.3 32.0 10.07 .67 .88 1.00
3200 1510 126.2 37.0 7.33 .43 .55 .67 121.1 35.5 8.13 .43 .56 .68 114.9 33.7 9.03 .43 .57 .70 108.5 31.8 10.06 .44 .58 .71
71_F 4000 1890 131.3 38.5 7.42 .44 .58 .72 125.6 36.8 8.23 .44 .59 .74 119.6 35.1 9.12 .45 .61 .76 112.5 33.0 10.13 .46 .62 .79
(22_C)
4800 2265 135.0 39.6 7.51 .45 .62 .78 128.9 37.8 8.29 .46 .63 .80 122.5 35.9 9.18 .46 .64 .82 115.2 33.8 10.19 .47 .67 .86

COOLING CAPACITY − (2) TSA120S4S (FIRST STAGE) with [TAA240S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
6400 3020 120.0 35.2 5.69 .69 .82 .96 116.1 34.0 6.35 .70 .84 .98 111.7 32.7 7.06 .71 .86 .99 106.7 31.3 7.87 .72 .88 1.00
63_F 8000 3775 125.6 36.8 5.79 .73 .89 1.00 121.0 35.5 6.43 .75 .92 1.00 116.4 34.1 7.14 .77 .94 1.00 110.7 32.4 7.95 .78 .96 1.00
(17_C)
9600 4530 129.1 37.8 5.86 .78 .96 1.00 124.6 36.5 6.50 .80 .98 1.00 120.0 35.2 7.21 .82 1.00 1.00 114.7 33.6 8.01 .84 1.00 1.00
6400 3020 126.8 37.2 5.81 .55 .67 .79 122.5 35.9 6.46 .56 .68 .80 117.8 34.5 7.18 .57 .69 .82 112.7 33.0 7.97 .57 .70 .84
67_F 8000 3775 132.5 38.8 5.91 .58 .71 .86 127.8 37.5 6.55 .58 .73 .88 122.8 36.0 7.26 .60 .74 .90 117.2 34.3 8.06 .60 .76 .93
(19_C)
9600 4530 136.6 40.0 5.99 .60 .77 .93 131.2 38.5 6.62 .61 .78 .95 126.1 37.0 7.33 .63 .80 .97 120.6 35.3 8.12 .64 .82 .99
6400 3020 133.4 39.1 5.93 .43 .54 .64 128.7 37.7 6.57 .43 .54 .65 124.0 36.3 7.28 .43 .55 .67 118.6 34.8 8.09 .43 .55 .68
71_F 8000 3775 139.1 40.8 6.04 .43 .56 .69 134.1 39.3 6.67 .44 .57 .70 129.1 37.8 7.38 .44 .58 .72 123.1 36.1 8.18 .44 .59 .74
(22_C)
9600 4530 143.4 42.0 6.12 .45 .60 .74 137.9 40.4 6.75 .45 .60 .75 132.3 38.8 7.45 .45 .61 .78 126.7 37.1 8.25 .45 .63 .80

COOLING CAPACITY − (2) TSA120S4S (SECOND STAGE) with [TAA240S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Volume Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
Tempera- Motor Motor Motor Motor
ture Capacity Dry Bulb Capacity Dry Bulb Capacity Dry Bulb Capacity Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 185.0 54.2 13.53 .62 .71 .79 178.4 52.3 15.19 .63 .71 .81 170.9 50.1 17.08 .63 .72 .82 162.4 47.6 19.23 .64 .74 .84
63_F 8000 3775 232.7 68.2 14.29 .77 .94 1.00 221.5 64.9 15.89 .78 .96 1.00 211.4 62.0 17.74 .80 .99 1.00 199.4 58.4 19.79 .83 1.00 1.00
(17_C)
4800 2265 208.9 61.2 13.90 .67 .78 .89 200.2 58.7 15.52 .67 .79 .92 190.9 55.9 17.39 .68 .81 .94 181.2 53.1 19.51 .70 .83 .97
3200 1510 196.5 57.6 13.69 .51 .60 .67 189.6 55.6 15.36 .52 .60 .68 181.5 53.2 17.23 .52 .61 .69 172.5 50.6 19.38 .52 .61 .70
67_F 8000 3775 245.7 72.0 14.53 .60 .74 .90 234.4 68.7 16.13 .60 .76 .93 223.4 65.5 17.94 .62 .78 .95 210.5 61.7 20.00 .63 .81 .99
(19_C)
4800 2265 221.0 64.8 14.09 .54 .64 .74 212.3 62.2 15.72 .54 .65 .75 202.2 59.3 17.56 .55 .66 .77 191.7 56.2 19.68 .55 .67 .79
3200 1510 207.7 60.9 13.87 .42 .49 .57 200.5 58.8 15.53 .41 .50 .57 192.1 56.3 17.40 .42 .50 .58 182.3 53.4 19.53 .41 .50 .59
71_F 8000 3775 258.1 75.6 14.76 .44 .58 .72 246.3 72.2 16.35 .44 .59 .74 234.9 68.8 18.17 .45 .61 .76 221.7 65.0 20.22 .46 .62 .78
(22_C)
4800 2265 232.6 68.2 14.30 .42 .52 .62 223.8 65.6 15.93 .42 .53 .62 213.3 62.5 17.76 .42 .53 .64 201.9 59.2 19.84 .43 .54 .65

UP−FLOW INDOOR COIL


COOLING CAPACITY − TSA120S4S with [(2) CX34−62D−6F]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 110.8 32.5 7.05 .70 .84 .97 106.3 31.2 7.86 .71 .85 .99 101.3 29.7 8.79 .73 .88 1.00 95.9 28.1 9.84 .74 .90 1.00
63_F 4000 1890 116.2 34.1 7.15 .74 .90 1.00 111.2 32.6 7.95 .76 .93 1.00 106.0 31.1 8.87 .78 .95 1.00 100.1 29.3 9.91 .80 .99 1.00
(17_C)
4800 2265 120.2 35.2 7.21 .79 .97 1.00 114.9 33.7 8.01 .81 .99 1.00 109.3 32.0 8.93 .83 1.00 1.00 103.9 30.5 9.98 .86 1.00 1.00
3200 1510 116.7 34.2 7.16 .56 .68 .80 111.8 32.8 7.96 .56 .69 .82 106.5 31.2 8.88 .57 .70 .84 100.6 29.5 9.91 .58 .72 .87
67_F 4000 1890 122.0 35.8 7.24 .58 .72 .87 116.8 34.2 8.05 .59 .73 .89 111.2 32.6 8.96 .60 .75 .92 105.1 30.8 10.00 .62 .78 .95
(19_C)
4800 2265 126.0 36.9 7.33 .61 .77 .94 120.5 35.3 8.12 .62 .79 .96 114.6 33.6 9.03 .63 .81 .99 108.0 31.7 10.05 .65 .84 1.00
3200 1510 123.1 36.1 7.27 .43 .54 .66 117.9 34.6 8.07 .43 .55 .67 112.4 32.9 8.99 .44 .56 .68 106.5 31.2 10.03 .44 .57 .70
71_F 4000 1890 128.6 37.7 7.37 .44 .57 .70 123.1 36.1 8.17 .44 .58 .72 117.2 34.3 9.08 .45 .59 .73 110.6 32.4 10.10 .45 .61 .76
(22_C)
4800 2265 132.7 38.9 7.45 .45 .60 .75 126.7 37.1 8.24 .46 .61 .77 120.5 35.3 9.14 .46 .63 .79 113.5 33.3 10.15 .47 .64 .82

TS 6 to 20 Ton R−410A Air Conditioners / Page 20


RATINGS 10 TON
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

DOWN−FLOW INDOOR COILS


COOLING CAPACITY − TSA120S4S with [(2) CR33−50/60C−2F]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 107.9 31.6 7.00 .71 .84 .98 103.4 30.3 7.81 .72 .86 .99 98.5 28.9 8.74 .73 .89 1.00 93.1 27.3 9.79 .75 .91 1.00
63_F 4000 1890 112.7 33.0 7.08 .75 .91 1.00 107.7 31.6 7.89 .77 .94 1.00 102.4 30.0 8.81 .79 .96 1.00 96.7 28.3 9.85 .81 .98 1.00
(17_C)
4800 2265 115.9 34.0 7.13 .80 .97 1.00 111.0 32.5 7.94 .82 .99 1.00 106.1 31.1 8.87 .84 1.00 1.00 100.7 29.5 9.92 .87 1.00 1.00
3200 1510 114.0 33.4 7.11 .57 .69 .81 109.1 32.0 7.92 .57 .70 .83 103.9 30.5 8.83 .58 .71 .85 98.4 28.8 9.88 .59 .73 .88
67_F 4000 1890 118.8 34.8 7.19 .59 .73 .88 113.7 33.3 7.99 .60 .74 .90 108.1 31.7 8.90 .61 .76 .93 102.1 29.9 9.94 .63 .79 .96
(19_C)
4800 2265 122.4 35.9 7.25 .62 .78 .95 117.0 34.3 8.06 .63 .79 .97 111.0 32.5 8.96 .64 .82 .99 104.7 30.7 9.99 .66 .85 1.00
3200 1510 119.6 35.1 7.20 .43 .55 .67 114.7 33.6 8.01 .43 .56 .68 109.2 32.0 8.93 .44 .57 .69 103.5 30.3 9.97 .44 .58 .71
71_F 4000 1890 124.6 36.5 7.30 .44 .58 .71 119.5 35.0 8.10 .45 .59 .72 113.7 33.3 9.01 .45 .60 .74 107.3 31.4 10.04 .45 .62 .77
(22_C)
4800 2265 128.5 37.7 7.37 .45 .61 .75 122.9 36.0 8.17 .46 .62 .77 116.8 34.2 9.07 .46 .63 .80 110.2 32.3 10.10 .47 .65 .82

HORIZONTAL INDOOR COILS


COOLING CAPACITY − TSA120S4S with [(2) CH33−62D−2F]
Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 109.7 32.1 7.03 .70 .83 .96 105.1 30.8 7.84 .71 .84 .98 100.3 29.4 8.77 .72 .86 1.00 95.0 27.8 9.81 .74 .89 1.00
63_F 4000 1890 114.9 33.7 7.12 .74 .89 1.00 110.1 32.3 7.93 .75 .91 1.00 104.8 30.7 8.85 .77 .94 1.00 99.0 29.0 9.89 .79 .97 1.00
(17_C)
4800 2265 118.8 34.8 7.19 .78 .95 1.00 113.5 33.3 8.00 .79 .98 1.00 108.0 31.7 8.90 .82 1.00 1.00 102.1 29.9 9.94 .84 1.00 1.00
3200 1510 115.2 33.8 7.13 .56 .67 .79 110.5 32.4 7.94 .56 .68 .81 105.3 30.9 8.86 .57 .70 .83 100.0 29.3 9.91 .58 .71 .85
67_F 4000 1890 121.0 35.5 7.23 .58 .71 .85 115.7 33.9 8.03 .59 .73 .87 110.2 32.3 8.94 .60 .74 .90 104.1 30.5 9.98 .61 .77 .94
(19_C)
4800 2265 124.8 36.6 7.30 .60 .75 .92 119.4 35.0 8.11 .61 .77 .94 113.8 33.4 9.01 .63 .79 .97 107.2 31.4 10.03 .64 .82 1.00
3200 1510 121.3 35.5 7.24 .43 .54 .65 116.4 34.1 8.04 .43 .55 .66 111.1 32.6 8.96 .44 .56 .67 105.3 30.9 10.00 .44 .57 .69
71_F 4000 1890 126.9 37.2 7.34 .44 .57 .69 121.8 35.7 8.14 .44 .58 .71 115.9 34.0 9.06 .45 .59 .72 109.5 32.1 10.08 .45 .60 .75
(22_C)
4800 2265 131.2 38.5 7.43 .45 .59 .73 125.5 36.8 8.22 .45 .60 .75 119.4 35.0 9.12 .46 .62 .77 112.5 33.0 10.14 .47 .63 .80

TS 6 to 20 Ton R−410A Air Conditioners / Page 21


RATINGS 10 TON (DUAL CIRCUIT)
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

AIR HANDLERS
COOLING CAPACITY − TSA120S4D (FIRST STAGE) with [TAA120S4D]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 61.7 18.1 2.72 .65 .78 .94 59.4 17.4 3.08 .66 .80 .96 56.8 16.6 3.49 .67 .82 .99 54.2 15.9 3.95 .68 .85 1.00
63_F 4000 1890 64.7 19.0 2.76 .69 .87 1.00 62.1 18.2 3.11 .70 .89 1.00 59.4 17.4 3.52 .72 .92 1.00 56.6 16.6 3.97 .74 .95 1.00
(17_C)
4800 2265 66.9 19.6 2.79 .74 .95 1.00 64.3 18.8 3.14 .76 .97 1.00 61.6 18.1 3.55 .78 .99 1.00 58.7 17.2 4.01 .81 1.00 1.00
3200 1510 65.3 19.1 2.77 .52 .62 .74 62.8 18.4 3.12 .52 .63 .75 60.2 17.6 3.53 .53 .64 .78 57.5 16.9 3.99 .54 .66 .80
67_F 4000 1890 68.5 20.1 2.80 .54 .67 .82 65.7 19.3 3.16 .55 .68 .84 62.8 18.4 3.56 .55 .69 .87 59.9 17.6 4.03 .57 .71 .91
(19_C)
4800 2265 70.6 20.7 2.83 .56 .71 .91 67.8 19.9 3.19 .57 .73 .93 64.8 19.0 3.59 .59 .76 .96 61.6 18.1 4.04 .59 .78 .99
3200 1510 68.9 20.2 2.81 .40 .50 .60 66.3 19.4 3.17 .40 .51 .61 63.5 18.6 3.57 .40 .51 .62 60.7 17.8 4.04 .40 .52 .64
71_F 4000 1890 72.2 21.2 2.84 .41 .53 .65 69.3 20.3 3.21 .41 .54 .66 66.2 19.4 3.61 .41 .54 .67 63.2 18.5 4.07 .41 .56 .69
(22_C)
4800 2265 74.4 21.8 2.87 .41 .55 .69 71.5 21.0 3.24 .42 .56 .71 68.3 20.0 3.64 .42 .58 .73 65.0 19.0 4.10 .43 .59 .75

COOLING CAPACITY − TSA120S4D (SECOND STAGE) with [TAA120S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Volume Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
Tempera- Motor Motor Motor Motor
ture Capacity Dry Bulb Capacity Dry Bulb Capacity Dry Bulb Capacity Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 113.6 33.3 6.99 .67 .82 .99 108.2 31.7 7.91 .68 .85 1.00 102.5 30.0 8.99 .69 .88 1.00 96.4 28.3 10.22 .72 .92 1.00
63_F 4000 1890 118.9 34.8 7.04 .72 .92 1.00 113.1 33.1 7.95 .74 .95 1.00 107.3 31.4 9.03 .77 .98 1.00 100.8 29.5 10.28 .80 1.00 1.00
(17_C)
4800 2265 123.1 36.1 7.10 .78 .99 1.00 117.3 34.4 8.02 .81 1.00 1.00 112.0 32.8 9.11 .84 1.00 1.00 105.6 30.9 10.37 .88 1.00 1.00
3200 1510 120.5 35.3 7.06 .53 .64 .78 114.9 33.7 7.99 .54 .66 .80 108.8 31.9 9.06 .54 .68 .84 102.4 30.0 10.30 .56 .70 .87
67_F 4000 1890 125.6 36.8 7.12 .56 .69 .87 119.7 35.1 8.06 .57 .71 .91 113.3 33.2 9.12 .58 .74 .94 105.9 31.0 10.34 .59 .77 .98
(19_C)
4800 2265 129.6 38.0 7.18 .59 .76 .96 123.2 36.1 8.09 .60 .78 .99 116.3 34.1 9.16 .61 .81 1.00 108.8 31.9 10.38 .63 .85 1.00
3200 1510 127.0 37.2 7.15 .40 .51 .62 121.3 35.5 8.08 .40 .52 .64 114.8 33.6 9.15 .41 .53 .65 108.0 31.7 10.39 .41 .54 .67
71_F 4000 1890 132.4 38.8 7.22 .41 .54 .67 126.5 37.1 8.15 .41 .56 .69 119.4 35.0 9.22 .42 .57 .71 112.1 32.9 10.45 .43 .58 .75
(22_C)
4800 2265 136.5 40.0 7.29 .42 .58 .73 129.9 38.1 8.21 .43 .59 .75 122.7 36.0 9.27 .43 .60 .78 115.1 33.7 10.52 .44 .63 .83

UP−FLOW INDOOR COIL


COOLING CAPACITY − TSA120S4D (FIRST STAGE) with [(2) CX34−60D−6F]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 59.2 17.3 2.70 .64 .77 .91 57.1 16.7 3.06 .65 .78 .93 54.9 16.1 3.47 .66 .80 .96 52.5 15.4 3.93 .67 .82 .99
63_F 4000 1890 62.3 18.3 2.73 .67 .83 .99 60.0 17.6 3.09 .68 .85 1.00 57.5 16.9 3.50 .70 .88 1.00 54.9 16.1 3.96 .72 .91 1.00
(17_C)
4800 2265 64.7 19.0 2.76 .71 .89 1.00 62.2 18.2 3.12 .73 .92 1.00 59.6 17.5 3.52 .75 .95 1.00 56.8 16.6 3.98 .77 .99 1.00
3200 1510 62.7 18.4 2.74 .52 .62 .73 60.5 17.7 3.10 .52 .63 .74 58.1 17.0 3.50 .53 .63 .76 55.5 16.3 3.96 .53 .65 .78
67_F 4000 1890 65.7 19.3 2.77 .53 .65 .79 63.4 18.6 3.13 .54 .66 .81 60.8 17.8 3.53 .55 .67 .84 58.0 17.0 4.00 .56 .69 .86
(19_C)
4800 2265 68.1 20.0 2.80 .55 .69 .85 65.4 19.2 3.16 .56 .69 .88 62.5 18.3 3.56 .57 .72 .91 59.8 17.5 4.02 .58 .74 .95
3200 1510 66.2 19.4 2.78 .40 .50 .59 63.8 18.7 3.14 .40 .50 .60 61.4 18.0 3.55 .40 .51 .61 58.6 17.2 4.01 .41 .52 .62
71_F 4000 1890 69.5 20.4 2.81 .41 .52 .63 67.0 19.6 3.18 .41 .53 .64 64.2 18.8 3.58 .41 .53 .66 61.2 17.9 4.04 .42 .54 .67
(22_C)
4800 2265 71.9 21.1 2.84 .42 .54 .67 69.2 20.3 3.21 .42 .55 .67 66.2 19.4 3.61 .42 .56 .70 63.1 18.5 4.08 .43 .57 .72

COOLING CAPACITY − TSA120S4D (SECOND STAGE) with [(2) CX34−60D−6F]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 109.8 32.2 6.94 .66 .80 .96 104.9 30.7 7.86 .67 .82 .99 99.5 29.2 8.94 .68 .85 1.00 93.8 27.5 10.20 .70 .89 1.00
63_F 4000 1890 115.1 33.7 7.00 .70 .88 1.00 109.8 32.2 7.93 .72 .91 1.00 104.1 30.5 8.99 .74 .94 1.00 98.1 28.8 10.24 .77 .98 1.00
(17_C)
4800 2265 119.2 34.9 7.04 .75 .95 1.00 113.6 33.3 7.97 .77 .99 1.00 107.6 31.5 9.05 .80 1.00 1.00 101.9 29.9 10.30 .84 1.00 1.00
3200 1510 116.1 34.0 7.01 .53 .63 .76 111.0 32.5 7.93 .53 .65 .78 105.5 30.9 9.02 .54 .66 .81 99.3 29.1 10.28 .55 .68 .85
67_F 4000 1890 121.5 35.6 7.06 .55 .67 .84 115.9 34.0 8.01 .56 .69 .86 109.8 32.2 9.08 .57 .71 .90 103.2 30.2 10.33 .58 .74 .94
(19_C)
4800 2265 125.0 36.6 7.13 .57 .72 .91 119.5 35.0 8.05 .58 .75 .95 112.9 33.1 9.12 .59 .77 .98 106.3 31.2 10.35 .61 .81 1.00
3200 1510 122.7 36.0 7.10 .40 .51 .61 117.3 34.4 8.02 .41 .52 .62 111.3 32.6 9.07 .41 .52 .64 105.0 30.8 10.35 .41 .54 .66
71_F 4000 1890 128.4 37.6 7.16 .41 .53 .66 122.3 35.8 8.08 .42 .54 .67 116.1 34.0 9.16 .42 .56 .69 109.1 32.0 10.40 .43 .57 .72
(22_C)
4800 2265 132.4 38.8 7.23 .42 .56 .70 126.2 37.0 8.16 .43 .57 .72 119.5 35.0 9.21 .43 .59 .75 112.1 32.9 10.43 .44 .60 .78

TS 6 to 20 Ton R−410A Air Conditioners / Page 22


RATINGS 10 TON (DUAL CIRCUIT)
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

UP−FLOW INDOOR COIL


COOLING CAPACITY − TSA120S4D (FIRST STAGE) with [(2) CX34−62D−6F]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 59.9 17.6 2.71 .64 .76 .91 57.8 16.9 3.07 .65 .78 .93 55.5 16.3 3.47 .66 .80 .96 53.0 15.5 3.93 .67 .82 .99
63_F 4000 1890 63.0 18.5 2.74 .67 .83 .99 60.8 17.8 3.10 .68 .85 1.00 58.2 17.1 3.51 .70 .88 1.00 55.5 16.3 3.96 .72 .91 1.00
(17_C)
4800 2265 65.5 19.2 2.77 .71 .90 1.00 63.0 18.5 3.13 .73 .92 1.00 60.4 17.7 3.53 .75 .95 1.00 57.5 16.9 3.99 .77 .98 1.00
3200 1510 63.2 18.5 2.74 .52 .62 .72 61.0 17.9 3.10 .52 .63 .74 58.5 17.1 3.50 .53 .63 .76 55.9 16.4 3.97 .53 .65 .78
67_F 4000 1890 66.5 19.5 2.78 .53 .65 .79 63.8 18.7 3.13 .54 .66 .81 61.2 17.9 3.54 .55 .67 .83 58.5 17.1 4.01 .56 .69 .87
(19_C)
4800 2265 68.9 20.2 2.81 .55 .68 .85 66.2 19.4 3.17 .56 .70 .88 63.4 18.6 3.57 .57 .72 .91 60.4 17.7 4.03 .58 .75 .95
3200 1510 66.8 19.6 2.78 .40 .50 .59 64.4 18.9 3.14 .40 .50 .60 61.9 18.1 3.56 .40 .51 .61 59.1 17.3 4.02 .41 .52 .63
71_F 4000 1890 70.2 20.6 2.82 .41 .52 .63 67.6 19.8 3.18 .41 .53 .64 64.8 19.0 3.58 .41 .53 .66 61.7 18.1 4.05 .42 .54 .67
(22_C)
4800 2265 72.7 21.3 2.85 .42 .54 .66 69.9 20.5 3.22 .42 .55 .68 66.9 19.6 3.62 .42 .56 .69 63.7 18.7 4.08 .43 .57 .72

COOLING CAPACITY − TSA120S4D (SECOND STAGE) with [(2) CX34−62D−6F]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 111.0 32.5 6.94 .66 .80 .96 105.9 31.0 7.87 .67 .82 .99 100.6 29.5 8.95 .68 .85 1.00 94.8 27.8 10.22 .70 .89 1.00
63_F 4000 1890 116.3 34.1 7.02 .70 .88 1.00 111.1 32.6 7.93 .72 .91 1.00 105.4 30.9 9.01 .74 .94 1.00 99.1 29.0 10.28 .77 .98 1.00
(17_C)
4800 2265 120.7 35.4 7.06 .75 .95 1.00 115.0 33.7 7.98 .77 .98 1.00 108.9 31.9 9.07 .80 1.00 1.00 103.0 30.2 10.31 .83 1.00 1.00
3200 1510 116.9 34.3 7.01 .53 .63 .76 111.7 32.7 7.94 .53 .65 .78 106.0 31.1 9.02 .54 .66 .81 99.8 29.2 10.27 .55 .68 .84
67_F 4000 1890 122.4 35.9 7.09 .55 .67 .83 116.9 34.3 8.02 .56 .69 .87 110.9 32.5 9.10 .57 .71 .90 104.3 30.6 10.34 .58 .74 .94
(19_C)
4800 2265 126.8 37.2 7.15 .57 .72 .91 120.8 35.4 8.07 .58 .75 .95 114.5 33.6 9.14 .59 .77 .98 107.4 31.5 10.38 .61 .81 1.00
3200 1510 123.7 36.3 7.12 .40 .51 .61 118.1 34.6 8.04 .41 .52 .63 112.1 32.9 9.11 .41 .52 .64 105.7 31.0 10.35 .41 .53 .66
71_F 4000 1890 129.5 38.0 7.17 .41 .53 .66 123.4 36.2 8.10 .42 .54 .67 117.2 34.3 9.19 .42 .56 .68 110.1 32.3 10.43 .43 .57 .71
(22_C)
4800 2265 133.8 39.2 7.24 .42 .56 .69 127.4 37.3 8.17 .43 .57 .72 120.5 35.3 9.24 .43 .59 .75 113.0 33.1 10.45 .44 .60 .78

DOWN−FLOW INDOOR COILS


COOLING CAPACITY − TSA120S4D (FIRST STAGE) with [(2) CR33−50/60C−2F]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 58.5 17.1 2.70 .65 .77 .92 56.4 16.5 3.06 .66 .79 .95 54.2 15.9 3.46 .66 .81 .97 51.6 15.1 3.91 .68 .83 .99
63_F 4000 1890 61.3 18.0 2.72 .68 .84 .99 59.0 17.3 3.08 .69 .87 1.00 56.5 16.6 3.49 .70 .89 1.00 53.9 15.8 3.95 .72 .92 1.00
(17_C)
4800 2265 63.3 18.6 2.74 .72 .91 1.00 60.9 17.8 3.11 .74 .94 1.00 58.2 17.1 3.50 .75 .96 1.00 55.5 16.3 3.97 .78 .98 1.00
3200 1510 61.8 18.1 2.73 .52 .62 .73 59.5 17.4 3.09 .52 .63 .75 57.2 16.8 3.49 .53 .64 .77 54.6 16.0 3.96 .54 .65 .79
67_F 4000 1890 64.8 19.0 2.76 .54 .66 .80 62.3 18.3 3.12 .55 .67 .82 59.7 17.5 3.52 .56 .68 .85 57.0 16.7 3.98 .56 .70 .88
(19_C)
4800 2265 67.0 19.6 2.79 .56 .69 .87 64.3 18.8 3.14 .57 .71 .90 61.6 18.1 3.55 .58 .73 .92 58.7 17.2 4.01 .59 .75 .96
3200 1510 65.0 19.0 2.76 .40 .50 .60 62.6 18.3 3.12 .40 .51 .61 60.1 17.6 3.52 .40 .52 .62 57.5 16.9 3.99 .40 .52 .63
71_F 4000 1890 68.1 20.0 2.80 .41 .53 .64 65.6 19.2 3.16 .41 .54 .65 62.9 18.4 3.56 .41 .54 .66 59.9 17.6 4.02 .42 .55 .68
(22_C)
4800 2265 70.4 20.6 2.82 .42 .55 .67 67.7 19.8 3.19 .42 .56 .69 64.8 19.0 3.59 .43 .57 .70 61.8 18.1 4.05 .43 .58 .73

COOLING CAPACITY − TSA120S4D (SECOND STAGE) with [(2) CR33−50/60C−2F]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Volume Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
Tempera- Motor Motor Motor Motor
ture Capacity Dry Bulb Capacity Dry Bulb Capacity Dry Bulb Capacity Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 108.3 31.7 6.93 .66 .81 .97 103.2 30.2 7.84 .68 .84 .99 98.0 28.7 8.93 .69 .86 1.00 92.2 27.0 10.17 .71 .90 1.00
63_F 4000 1890 113.1 33.1 6.98 .70 .89 1.00 107.7 31.6 7.90 .72 .92 1.00 102.1 29.9 8.99 .75 .95 1.00 95.9 28.1 10.23 .78 .98 1.00
(17_C)
4800 2265 116.4 34.1 7.01 .76 .96 1.00 111.0 32.5 7.95 .78 .98 1.00 105.6 30.9 9.02 .81 1.00 1.00 99.9 29.3 10.26 .84 1.00 1.00
3200 1510 114.4 33.5 6.99 .53 .64 .77 109.2 32.0 7.92 .54 .65 .79 103.7 30.4 8.97 .55 .67 .82 97.6 28.6 10.25 .56 .69 .86
67_F 4000 1890 119.4 35.0 7.04 .56 .68 .85 113.9 33.4 7.97 .56 .70 .88 108.0 31.7 9.06 .58 .72 .91 101.5 29.7 10.29 .59 .75 .95
(19_C)
4800 2265 123.2 36.1 7.10 .58 .73 .92 117.4 34.4 8.02 .59 .75 .96 111.0 32.5 9.10 .60 .78 .98 104.1 30.5 10.31 .62 .82 1.00
3200 1510 120.2 35.2 7.06 .40 .52 .62 115.0 33.7 7.99 .40 .52 .63 109.2 32.0 9.08 .41 .53 .65 102.8 30.1 10.29 .41 .54 .67
71_F 4000 1890 125.7 36.8 7.13 .41 .54 .66 119.8 35.1 8.04 .42 .55 .68 113.7 33.3 9.13 .42 .56 .69 107.0 31.4 10.36 .43 .58 .72
(22_C)
4800 2265 129.6 38.0 7.19 .43 .57 .70 123.5 36.2 8.11 .43 .58 .73 116.9 34.3 9.17 .43 .59 .75 109.8 32.2 10.42 .44 .61 .79

TS 6 to 20 Ton R−410A Air Conditioners / Page 23


RATINGS 10 TON (DUAL CIRCUIT)
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

HORIZONTAL INDOOR COILS


COOLING CAPACITY − TSA120S4D (FIRST STAGE) with [(2) CH33−62D−2F]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Temperat Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ure Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 59.2 17.3 2.70 .64 .76 .89 57.1 16.7 3.06 .64 .77 .92 54.9 16.1 3.47 .65 .79 .94 52.5 15.4 3.93 .66 .81 .97
63_F 4000 1890 62.4 18.3 2.73 .67 .82 .98 60.0 17.6 3.09 .68 .84 1.00 57.6 16.9 3.49 .69 .86 1.00 55.0 16.1 3.96 .71 .89 1.00
(17_C)
4800 2265 64.8 19.0 2.76 .70 .88 1.00 62.3 18.3 3.12 .72 .90 1.00 59.6 17.5 3.52 .73 .93 1.00 56.8 16.6 3.98 .76 .96 1.00
3200 1510 62.4 18.3 2.73 .51 .61 .72 60.1 17.6 3.09 .52 .62 .73 57.7 16.9 3.49 .52 .63 .75 55.2 16.2 3.95 .53 .64 .77
67_F 4000 1890 65.7 19.3 2.77 .53 .64 .78 63.1 18.5 3.13 .54 .66 .80 60.7 17.8 3.54 .54 .67 .82 57.9 17.0 3.99 .55 .68 .85
(19_C)
4800 2265 68.3 20.0 2.80 .55 .68 .84 65.6 19.2 3.16 .56 .69 .86 62.8 18.4 3.56 .56 .71 .89 59.9 17.6 4.02 .58 .73 .92
3200 1510 65.7 19.3 2.77 .40 .50 .59 63.5 18.6 3.13 .40 .50 .60 61.0 17.9 3.54 .40 .51 .61 58.3 17.1 4.00 .41 .51 .62
71_F 4000 1890 69.3 20.3 2.81 .41 .52 .62 66.7 19.5 3.17 .41 .52 .63 64.0 18.8 3.58 .41 .53 .65 60.9 17.8 4.04 .42 .54 .66
(22_C)
4800 2265 71.8 21.0 2.84 .42 .54 .66 69.1 20.3 3.20 .42 .54 .67 66.1 19.4 3.61 .42 .55 .68 63.0 18.5 4.07 .43 .56 .70

COOLING CAPACITY − TSA120S4D (SECOND STAGE) with [(2) CH33−62D−2F]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Volume Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
Tempera- Motor Motor Motor Motor
ture Capacity Dry Bulb Capacity Dry Bulb Capacity Dry Bulb Capacity Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 109.7 32.1 6.94 .65 .79 .94 104.9 30.7 7.86 .66 .81 .97 99.5 29.2 8.94 .68 .84 1.00 93.8 27.5 10.20 .69 .87 1.00
63_F 4000 1890 115.2 33.8 6.99 .69 .86 1.00 110.0 32.2 7.93 .71 .89 1.00 104.1 30.5 9.01 .73 .92 1.00 97.9 28.7 10.24 .76 .96 1.00
(17_C)
4800 2265 119.1 34.9 7.04 .73 .93 1.00 113.6 33.3 7.96 .76 .96 1.00 107.6 31.5 9.03 .78 .99 1.00 101.2 29.7 10.27 .82 1.00 1.00
3200 1510 115.4 33.8 6.99 .52 .63 .75 110.3 32.3 7.91 .53 .64 .77 104.9 30.7 9.00 .54 .65 .80 98.6 28.9 10.27 .55 .67 .83
67_F 4000 1890 121.4 35.6 7.08 .54 .67 .82 115.8 33.9 8.00 .55 .68 .85 110.0 32.2 9.08 .56 .70 .88 103.3 30.3 10.34 .57 .73 .92
(19_C)
4800 2265 125.6 36.8 7.13 .56 .71 .89 119.7 35.1 8.05 .58 .73 .92 113.4 33.2 9.12 .59 .76 .96 106.5 31.2 10.36 .60 .79 1.00
3200 1510 121.9 35.7 7.08 .40 .51 .61 116.6 34.2 8.00 .41 .51 .62 110.7 32.4 9.09 .41 .52 .63 104.4 30.6 10.34 .41 .53 .65
71_F 4000 1890 127.9 37.5 7.16 .41 .53 .65 121.8 35.7 8.08 .42 .54 .66 115.7 33.9 9.17 .42 .55 .68 108.9 31.9 10.42 .43 .56 .70
(22_C)
4800 2265 132.2 38.7 7.23 .42 .55 .68 126.0 36.9 8.15 .43 .56 .70 119.4 35.0 9.21 .43 .58 .73 112.2 32.9 10.47 .44 .59 .76

TS 6 to 20 Ton R−410A Air Conditioners / Page 24


RATINGS 12.5 TON (DUAL CIRCUIT)
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

AIR HANDLERS
COOLING CAPACITY − TSA150S4D (FIRST STAGE) with [TAA120S4D]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 72.0 21.1 3.62 .65 .76 .89 69.5 20.4 4.04 .65 .77 .91 66.7 19.5 4.49 .66 .79 .93 63.8 18.7 5.01 .67 .81 .95
63_F 4000 1890 76.0 22.3 3.63 .68 .82 .97 73.3 21.5 4.05 .69 .84 .98 70.4 20.6 4.50 .70 .86 1.00 67.1 19.7 5.01 .72 .88 1.00
(17_C)
4800 2265 78.9 23.1 3.65 .72 .89 1.00 76.0 22.3 4.06 .73 .91 1.00 73.1 21.4 4.51 .75 .93 1.00 69.6 20.4 5.02 .77 .96 1.00
3200 1510 76.4 22.4 3.63 .52 .62 .72 73.9 21.7 4.05 .52 .63 .74 71.0 20.8 4.51 .53 .64 .75 67.8 19.9 5.01 .53 .64 .77
67_F 4000 1890 80.5 23.6 3.65 .54 .65 .78 77.8 22.8 4.06 .55 .66 .80 74.6 21.9 4.51 .55 .67 .82 71.4 20.9 5.02 .56 .69 .84
(19_C)
4800 2265 83.5 24.5 3.66 .56 .69 .85 80.8 23.7 4.07 .57 .71 .86 77.7 22.8 4.52 .57 .72 .89 73.9 21.7 5.02 .58 .74 .91
3200 1510 80.6 23.6 3.65 .40 .50 .60 78.1 22.9 4.06 .41 .51 .60 75.3 22.1 4.52 .41 .51 .61 72.0 21.1 5.02 .41 .52 .62
71_F 4000 1890 85.1 24.9 3.67 .42 .52 .63 82.2 24.1 4.07 .41 .53 .64 79.1 23.2 4.53 .42 .54 .65 75.6 22.2 5.03 .42 .54 .66
(22_C)
4800 2265 88.2 25.8 3.68 .42 .54 .67 85.3 25.0 4.08 .42 .55 .68 81.9 24.0 4.53 .42 .56 .70 78.2 22.9 5.04 .43 .57 .71

COOLING CAPACITY − TSA150S4D (SECOND STAGE) with [TAA120S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
3200 1510 133.5 39.1 8.99 .66 .79 .93 127.7 37.4 10.01 .67 .81 .95 120.9 35.4 11.18 .68 .84 .98 113.5 33.3 12.50 .70 .86 1.00
63_F 4000 1890 140.7 41.2 9.01 .70 .86 1.00 134.1 39.3 10.02 .72 .88 1.00 127.3 37.3 11.19 .74 .91 1.00 119.3 35.0 12.53 .77 .95 1.00
(17_C)
4800 2265 146.1 42.8 9.02 .75 .93 1.00 139.2 40.8 10.04 .77 .96 1.00 132.2 38.7 11.19 .80 .98 1.00 124.0 36.3 12.51 .83 1.00 1.00
3200 1510 142.0 41.6 9.01 .53 .64 .75 135.6 39.7 10.02 .53 .64 .77 128.9 37.8 11.17 .54 .66 .79 121.4 35.6 12.52 .55 .68 .82
67_F 4000 1890 149.3 43.8 9.02 .55 .67 .82 142.9 41.9 10.04 .56 .69 .84 135.4 39.7 11.19 .57 .71 .87 127.0 37.2 12.51 .58 .73 .91
(19_C)
4800 2265 155.3 45.5 9.04 .57 .72 .89 147.8 43.3 10.05 .58 .74 .91 140.3 41.1 11.21 .60 .77 .95 131.4 38.5 12.53 .61 .80 .98
3200 1510 150.5 44.1 9.03 .41 .51 .61 144.0 42.2 10.04 .41 .52 .62 136.9 40.1 11.19 .41 .53 .63 128.7 37.7 12.50 .42 .53 .65
71_F 4000 1890 158.2 46.4 9.05 .42 .54 .65 151.2 44.3 10.07 .42 .54 .66 143.6 42.1 11.21 .42 .56 .68 135.0 39.6 12.53 .43 .57 .70
(22_C)
4800 2265 163.8 48.0 9.06 .43 .56 .70 156.3 45.8 10.07 .43 .57 .71 148.5 43.5 11.23 .43 .58 .74 139.8 41.0 12.56 .43 .60 .77

COOLING CAPACITY − TSA150S4D (FIRST STAGE) with [TAA150S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4000 1890 75.2 22.0 3.63 .68 .81 .96 72.8 21.3 4.05 .69 .83 .98 69.9 20.5 4.50 .69 .85 1.00 66.8 19.6 5.01 .71 .87 1.00
63_F 5000 2360 78.9 23.1 3.64 .71 .89 1.00 76.3 22.4 4.06 .73 .91 1.00 73.4 21.5 4.51 .75 .94 1.00 70.2 20.6 5.02 .76 .96 1.00
(17_C)
6000 2830 82.2 24.1 3.65 .77 .96 1.00 79.4 23.3 4.07 .78 .98 1.00 76.4 22.4 4.52 .81 1.00 1.00 73.1 21.4 5.03 .83 1.00 1.00
4000 1890 80.2 23.5 3.65 .54 .65 .77 77.6 22.7 4.06 .54 .66 .79 74.6 21.9 4.51 .55 .67 .81 71.2 20.9 5.02 .56 .68 .83
67_F 5000 2360 83.9 24.6 3.66 .56 .69 .85 81.1 23.8 4.07 .57 .71 .87 78.0 22.9 4.52 .58 .72 .89 74.2 21.7 5.03 .59 .74 .92
(19_C)
6000 2830 86.7 25.4 3.67 .59 .74 .92 83.6 24.5 4.08 .60 .76 .94 80.3 23.5 4.53 .61 .78 .97 76.6 22.4 5.04 .62 .80 .99
4000 1890 85.1 24.9 3.67 .41 .52 .63 82.4 24.1 4.07 .41 .53 .64 79.2 23.2 4.53 .41 .53 .65 75.8 22.2 5.03 .41 .54 .66
71_F 5000 2360 89.0 26.1 3.68 .42 .55 .67 86.0 25.2 4.09 .42 .56 .68 82.8 24.3 4.53 .43 .57 .70 79.0 23.2 5.04 .43 .58 .71
(22_C)
6000 2830 91.9 26.9 3.69 .43 .58 .72 88.9 26.1 4.09 .43 .59 .73 85.2 25.0 4.54 .44 .60 .75 81.4 23.9 5.05 .45 .61 .77

COOLING CAPACITY − TSA150S4D (SECOND STAGE) with [TAA150S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4000 1890 139.9 41.0 9.00 .69 .85 1.00 133.5 39.1 10.02 .71 .87 1.00 126.8 37.2 11.18 .73 .90 1.00 119.2 34.9 12.52 .75 .94 1.00
63_F 5000 2360 146.8 43.0 9.03 .75 .94 1.00 140.5 41.2 10.03 .76 .96 1.00 133.1 39.0 11.21 .79 .99 1.00 125.7 36.8 12.54 .83 1.00 1.00
(17_C)
6000 2830 152.8 44.8 9.03 .81 1.00 1.00 146.2 42.8 10.05 .83 1.00 1.00 139.4 40.9 11.21 .86 1.00 1.00 132.2 38.7 12.53 .90 1.00 1.00
4000 1890 149.1 43.7 9.03 .55 .67 .81 142.4 41.7 10.03 .56 .68 .83 135.2 39.6 11.20 .57 .70 .86 127.1 37.2 12.54 .58 .72 .89
67_F 5000 2360 156.0 45.7 9.05 .58 .72 .89 148.5 43.5 10.05 .59 .74 .92 140.9 41.3 11.21 .60 .76 .95 132.2 38.7 12.53 .62 .80 .99
(19_C)
6000 2830 160.6 47.1 9.06 .61 .78 .97 153.3 44.9 10.07 .62 .80 .99 145.0 42.5 11.24 .63 .83 1.00 136.1 39.9 12.55 .65 .87 1.00
4000 1890 158.4 46.4 9.05 .41 .53 .65 151.6 44.4 10.06 .41 .54 .66 144.2 42.3 11.23 .42 .55 .68 135.6 39.7 12.56 .43 .56 .70
71_F 5000 2360 165.5 48.5 9.07 .43 .57 .70 158.0 46.3 10.08 .43 .58 .71 150.2 44.0 11.24 .43 .59 .73 141.0 41.3 12.56 .44 .60 .77
(22_C)
6000 2830 170.3 49.9 9.08 .44 .60 .75 162.7 47.7 10.09 .45 .61 .77 154.4 45.3 11.25 .46 .63 .80 145.2 42.6 12.57 .47 .65 .84

TS 6 to 20 Ton R−410A Air Conditioners / Page 25


RATINGS 12.5 TON (DUAL CIRCUIT)
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

AIR HANDLERS
COOLING CAPACITY − TSA150S4D (FIRST STAGE) with [TAA180S4D]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb CapacityMotor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4000 1890 75.3 22.1 3.63 .68 .81 .96 72.8 21.3 4.05 .69 .83 .98 69.9 20.5 4.50 .70 .85 1.00 66.7 19.5 5.01 .71 .87 1.00
63_F 5000 2360 79.0 23.2 3.64 .72 .89 1.00 76.3 22.4 4.06 .73 .91 1.00 73.1 21.4 4.51 .75 .94 1.00 69.7 20.4 5.01 .77 .96 1.00
(17_C)
6000 2830 81.9 24.0 3.65 .77 .96 1.00 79.2 23.2 4.07 .78 .98 1.00 75.8 22.2 4.52 .81 1.00 1.00 72.6 21.3 5.02 .83 1.00 1.00
4000 1890 79.5 23.3 3.64 .54 .65 .77 76.9 22.5 4.06 .54 .66 .79 73.9 21.7 4.52 .55 .68 .81 70.7 20.7 5.02 .56 .69 .83
67_F 5000 2360 83.5 24.5 3.66 .56 .70 .85 80.7 23.7 4.07 .57 .71 .87 77.5 22.7 4.52 .58 .72 .89 73.8 21.6 5.02 .59 .74 .92
(19_C)
6000 2830 86.4 25.3 3.67 .59 .74 .92 83.3 24.4 4.07 .60 .76 .94 80.0 23.4 4.53 .61 .78 .97 76.1 22.3 5.03 .62 .80 .99
4000 1890 83.8 24.6 3.66 .41 .52 .63 81.0 23.7 4.07 .41 .53 .64 77.9 22.8 4.52 .42 .54 .65 74.5 21.8 5.03 .42 .54 .66
71_F 5000 2360 87.9 25.8 3.68 .42 .55 .67 85.0 24.9 4.08 .43 .56 .69 81.7 23.9 4.54 .43 .57 .70 78.0 22.9 5.03 .43 .58 .72
(22_C)
6000 2830 91.0 26.7 3.69 .43 .58 .72 87.7 25.7 4.09 .43 .59 .73 84.3 24.7 4.54 .44 .60 .75 80.5 23.6 5.05 .45 .61 .77

COOLING CAPACITY − TSA150S4D (SECOND STAGE) with [TAA180S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4000 1890 139.7 40.9 9.00 .70 .85 1.00 133.4 39.1 10.03 .71 .87 1.00 126.3 37.0 11.18 .73 .91 1.00 118.4 34.7 12.49 .75 .94 1.00
63_F 5000 2360 146.3 42.9 9.03 .75 .94 1.00 139.5 40.9 10.03 .77 .96 1.00 132.4 38.8 11.19 .79 .99 1.00 124.5 36.5 12.51 .83 1.00 1.00
(17_C)
6000 2830 151.6 44.4 9.04 .81 1.00 1.00 145.1 42.5 10.04 .83 1.00 1.00 138.2 40.5 11.20 .86 1.00 1.00 130.7 38.3 12.52 .90 1.00 1.00
4000 1890 147.9 43.3 9.03 .55 .68 .81 141.3 41.4 10.03 .56 .69 .83 134.1 39.3 11.20 .56 .70 .86 125.7 36.8 12.51 .58 .72 .90
67_F 5000 2360 155.0 45.4 9.04 .58 .72 .89 147.6 43.3 10.05 .59 .74 .92 140.3 41.1 11.21 .60 .76 .95 131.4 38.5 12.53 .62 .80 .99
(19_C)
6000 2830 160.0 46.9 9.05 .61 .78 .97 152.3 44.6 10.07 .62 .80 .99 144.5 42.3 11.23 .64 .83 1.00 135.3 39.7 12.55 .65 .87 1.00
4000 1890 155.9 45.7 9.04 .42 .54 .65 149.0 43.7 10.05 .42 .54 .66 141.6 41.5 11.22 .43 .55 .68 133.2 39.0 12.53 .43 .57 .70
71_F 5000 2360 163.5 47.9 9.07 .43 .57 .70 156.0 45.7 10.07 .43 .58 .72 147.9 43.3 11.22 .44 .59 .74 139.1 40.8 12.56 .44 .61 .77
(22_C)
6000 2830 168.6 49.4 9.07 .44 .60 .75 161.1 47.2 10.09 .45 .61 .77 152.7 44.8 11.24 .44 .63 .80 143.5 42.1 12.58 .45 .64 .84

TS 6 to 20 Ton R−410A Air Conditioners / Page 26


RATINGS 15 TON (DUAL CIRCUIT)
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

AIR HANDLERS
COOLING CAPACITY − TSA180S4D (FIRST STAGE) with [TAA180S4D]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4800 2265 93.8 27.5 4.63 .70 .82 .94 90.7 26.6 5.14 .71 .83 .95 87.1 25.5 5.70 .72 .85 .97 83.3 24.4 6.33 .73 .87 .99
63_F 6000 2830 98.3 28.8 4.69 .74 .88 1.00 95.0 27.8 5.20 .75 .90 1.00 91.3 26.8 5.76 .76 .91 1.00 87.1 25.5 6.39 .78 .94 1.00
(17_C)
7200 3400 101.7 29.8 4.75 .78 .94 1.00 98.1 28.8 5.25 .79 .95 1.00 94.2 27.6 5.80 .81 .97 1.00 90.0 26.4 6.43 .83 .99 1.00
4800 2265 98.7 28.9 4.70 .56 .68 .79 95.4 28.0 5.21 .57 .69 .80 91.9 26.9 5.77 .57 .70 .82 88.0 25.8 6.40 .58 .71 .83
67_F 6000 2830 103.6 30.4 4.77 .59 .72 .85 99.9 29.3 5.27 .59 .73 .86 96.0 28.1 5.83 .60 .74 .88 91.7 26.9 6.46 .61 .76 .90
(19_C)
7200 3400 106.9 31.3 4.83 .61 .76 .91 103.1 30.2 5.32 .62 .77 .92 99.1 29.0 5.88 .63 .79 .94 94.5 27.7 6.51 .64 .81 .96
4800 2265 103.4 30.3 4.77 .44 .55 .65 100.0 29.3 5.28 .44 .55 .66 96.3 28.2 5.84 .44 .56 .67 92.3 27.1 6.47 .44 .56 .69
71_F 6000 2830 108.5 31.8 4.85 .44 .57 .70 104.8 30.7 5.35 .44 .58 .71 100.7 29.5 5.91 .45 .59 .72 96.3 28.2 6.53 .45 .60 .74
(22_C)
7200 3400 112.0 32.8 4.91 .46 .60 .74 108.2 31.7 5.40 .46 .61 .75 103.8 30.4 5.96 .46 .62 .77 99.3 29.1 6.58 .47 .63 .79

COOLING CAPACITY − TSA180S4D (SECOND STAGE) with [TAA180S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4800 2265 174.3 51.1 11.40 .72 .85 .97 166.7 48.9 12.66 .73 .87 .99 158.8 46.5 14.13 .75 .89 1.00 149.7 43.9 15.81 .77 .91 1.00
63_F 6000 2830 182.6 53.5 11.51 .76 .91 1.00 174.2 51.1 12.79 .78 .94 1.00 165.4 48.5 14.23 .80 .96 1.00 156.3 45.8 15.91 .82 .98 1.00
(17_C)
7200 3400 188.4 55.2 11.60 .81 .97 1.00 179.9 52.7 12.86 .83 .99 1.00 170.7 50.0 14.30 .85 1.00 1.00 162.2 47.5 16.00 .88 1.00 1.00
4800 2265 183.8 53.9 11.53 .57 .70 .82 176.0 51.6 12.80 .58 .71 .83 167.4 49.1 14.25 .59 .72 .86 158.0 46.3 15.94 .60 .74 .88
67_F 6000 2830 191.9 56.2 11.66 .60 .74 .88 183.5 53.8 12.92 .61 .76 .90 174.4 51.1 14.37 .62 .78 .93 164.4 48.2 16.04 .63 .80 .95
(19_C)
7200 3400 198.1 58.1 11.76 .63 .79 .94 189.1 55.4 13.02 .64 .81 .96 179.4 52.6 14.45 .65 .83 .99 168.9 49.5 16.10 .67 .86 1.00
4800 2265 192.7 56.5 11.67 .44 .56 .67 184.5 54.1 12.94 .44 .56 .69 175.7 51.5 14.38 .44 .57 .70 166.2 48.7 16.07 .45 .59 .72
71_F 6000 2830 201.5 59.1 11.81 .45 .59 .72 192.5 56.4 13.06 .45 .60 .74 183.1 53.7 14.51 .46 .61 .75 173.0 50.7 16.17 .47 .62 .78
(22_C)
7200 3400 207.6 60.8 11.92 .46 .62 .77 198.5 58.2 13.17 .47 .63 .79 188.6 55.3 14.61 .48 .64 .81 177.7 52.1 16.25 .47 .66 .84

COOLING CAPACITY − TSA180S4D (FIRST STAGE) with [(2) TAA090S4S]


Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4800 2265 99.4 29.1 4.71 .69 .81 .93 96.1 28.2 5.21 .71 .83 .95 92.4 27.1 5.77 .71 .84 .97 88.3 25.9 6.40 .73 .86 .99
63_F 6000 2830 104.3 30.6 4.79 .74 .88 1.00 100.5 29.5 5.28 .75 .89 1.00 96.6 28.3 5.84 .76 .91 1.00 92.5 27.1 6.48 .78 .93 1.00
(17_C)
7200 3400 108.0 31.7 4.84 .78 .94 1.00 104.3 30.6 5.34 .80 .96 1.00 100.0 29.3 5.89 .81 .97 1.00 95.4 28.0 6.52 .83 .99 1.00
4800 2265 105.0 30.8 4.80 .56 .67 .78 101.5 29.7 5.30 .56 .68 .79 97.7 28.6 5.86 .57 .69 .81 93.5 27.4 6.49 .57 .70 .83
67_F 6000 2830 110.2 32.3 4.88 .58 .72 .85 106.3 31.2 5.38 .59 .73 .87 102.1 29.9 5.93 .60 .74 .88 97.7 28.6 6.56 .61 .76 .90
(19_C)
7200 3400 113.8 33.4 4.93 .60 .76 .91 109.6 32.1 5.42 .62 .77 .93 105.3 30.9 5.98 .63 .79 .95 100.2 29.4 6.60 .64 .80 .97
4800 2265 110.7 32.4 4.88 .43 .54 .65 106.9 31.3 5.39 .43 .55 .66 102.9 30.2 5.94 .44 .55 .66 98.4 28.8 6.57 .44 .56 .68
71_F 6000 2830 115.8 33.9 4.97 .44 .56 .69 111.9 32.8 5.46 .44 .57 .70 107.6 31.5 6.02 .45 .59 .72 102.8 30.1 6.64 .45 .59 .73
(22_C)
7200 3400 119.4 35.0 5.03 .46 .60 .73 115.4 33.8 5.52 .46 .61 .75 110.8 32.5 6.07 .46 .62 .77 105.8 31.0 6.69 .46 .63 .77

COOLING CAPACITY − TSA180S4D (SECOND STAGE) with [(2) TAA090S4S]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
4800 2265 99.4 29.1 4.71 .69 .81 .93 96.1 28.2 5.21 .71 .83 .95 92.4 27.1 5.77 .71 .84 .97 88.3 25.9 6.40 .73 .86 .99
63_F 6000 2830 104.3 30.6 4.79 .74 .88 1.00 100.5 29.5 5.28 .75 .89 1.00 96.6 28.3 5.84 .76 .91 1.00 92.5 27.1 6.48 .78 .93 1.00
(17_C)
7200 3400 108.0 31.7 4.84 .78 .94 1.00 104.3 30.6 5.34 .80 .96 1.00 100.0 29.3 5.89 .81 .97 1.00 95.4 28.0 6.52 .83 .99 1.00
4800 2265 105.0 30.8 4.80 .56 .67 .78 101.5 29.7 5.30 .56 .68 .79 97.7 28.6 5.86 .57 .69 .81 93.5 27.4 6.49 .57 .70 .83
67_F 6000 2830 110.2 32.3 4.88 .58 .72 .85 106.3 31.2 5.38 .59 .73 .87 102.1 29.9 5.93 .60 .74 .88 97.7 28.6 6.56 .61 .76 .90
(19_C)
7200 3400 113.8 33.4 4.93 .60 .76 .91 109.6 32.1 5.42 .62 .77 .93 105.3 30.9 5.98 .63 .79 .95 100.2 29.4 6.60 .64 .80 .97
4800 2265 110.7 32.4 4.88 .43 .54 .65 106.9 31.3 5.39 .43 .55 .66 102.9 30.2 5.94 .44 .55 .66 98.4 28.8 6.57 .44 .56 .68
71_F 6000 2830 115.8 33.9 4.97 .44 .56 .69 111.9 32.8 5.46 .44 .57 .70 107.6 31.5 6.02 .45 .59 .72 102.8 30.1 6.64 .45 .59 .73
(22_C)
7200 3400 119.4 35.0 5.03 .46 .60 .73 115.4 33.8 5.52 .46 .61 .75 110.8 32.5 6.07 .46 .62 .77 105.8 31.0 6.69 .46 .63 .77

TS 6 to 20 Ton R−410A Air Conditioners / Page 27


RATINGS 20 TON (DUAL CIRCUIT)
NOTES: For Temperatures and Capacities not shown in tables, see bulletin − Cooling Unit Rating Table Correction Factor Data in Miscellaneous Engineering Data section.

AIR HANDLERS
COOLING CAPACITY − TSA240S4D (FIRST STAGE) with [TAA240S4D]
Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
6400 3020 124.8 36.6 5.92 .72 .84 .95 120.3 35.3 6.61 .73 .85 .97 115.7 33.9 7.37 .74 .87 .98 110.8 32.5 8.25 .75 .89 1.00
63_F 8000 3775 130.7 38.3 6.02 .76 .90 1.00 125.9 36.9 6.70 .77 .92 1.00 121.0 35.5 7.46 .79 .93 1.00 115.6 33.9 8.33 .80 .96 1.00
(17_C)
9600 4530 135.1 39.6 6.09 .81 .96 1.00 129.9 38.1 6.75 .82 .97 1.00 124.9 36.6 7.52 .84 .99 1.00 119.4 35.0 8.39 .86 1.00 1.00
6400 3020 132.3 38.8 6.03 .57 .70 .81 127.4 37.3 6.72 .58 .70 .82 122.6 35.9 7.48 .59 .72 .84 117.3 34.4 8.36 .59 .73 .85
67_F 8000 3775 138.2 40.5 6.14 .60 .74 .87 133.1 39.0 6.81 .61 .75 .88 128.1 37.5 7.58 .61 .77 .90 122.4 35.9 8.44 .62 .79 .93
(19_C)
9600 4530 142.9 41.9 6.22 .63 .79 .93 137.6 40.3 6.89 .63 .80 .95 132.0 38.7 7.64 .65 .82 .96 125.9 36.9 8.50 .66 .84 .98
6400 3020 139.3 40.8 6.16 .44 .56 .67 134.2 39.3 6.83 .45 .56 .68 129.0 37.8 7.59 .45 .57 .69 123.4 36.2 8.46 .45 .58 .70
71_F 8000 3775 145.4 42.6 6.26 .45 .58 .72 140.2 41.1 6.93 .46 .59 .73 134.7 39.5 7.69 .46 .60 .74 129.0 37.8 8.56 .46 .62 .76
(22_C)
9600 4530 150.2 44.0 6.34 .46 .61 .76 144.5 42.3 7.01 .46 .62 .78 138.6 40.6 7.75 .46 .63 .80 132.4 38.8 8.62 .47 .65 .81

COOLING CAPACITY − TSA240S4D (SECOND STAGE) with [TAA240S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
6400 3020 231.4 67.8 14.74 .74 .87 .98 221.6 64.9 16.50 .75 .89 1.00 210.8 61.8 18.52 .77 .91 1.00 199.1 58.4 20.85 .79 .93 1.00
63_F 8000 3775 242.0 70.9 14.91 .79 .93 1.00 231.2 67.8 16.66 .80 .96 1.00 219.2 64.2 18.66 .83 .98 1.00 207.4 60.8 20.98 .85 1.00 1.00
(17_C)
9600 4530 249.8 73.2 15.05 .84 .99 1.00 238.9 70.0 16.79 .86 1.00 1.00 227.5 66.7 18.81 .88 1.00 1.00 215.8 63.2 21.09 .90 1.00 1.00
6400 3020 245.2 71.9 14.95 .59 .72 .84 234.6 68.8 16.71 .59 .73 .85 223.2 65.4 18.72 .60 .74 .87 211.1 61.9 21.04 .62 .76 .90
67_F 8000 3775 256.1 75.1 15.16 .61 .77 .90 244.8 71.7 16.87 .62 .79 .93 232.1 68.0 18.86 .64 .80 .95 219.1 64.2 21.14 .65 .83 .98
(19_C)
9600 4530 263.9 77.3 15.29 .65 .82 .96 251.7 73.8 16.99 .66 .84 .98 238.8 70.0 18.97 .67 .86 1.00 224.0 65.6 21.22 .69 .88 1.00
6400 3020 257.9 75.6 15.18 .45 .57 .69 246.9 72.4 16.92 .45 .58 .70 235.2 68.9 18.91 .45 .59 .72 222.3 65.1 21.22 .46 .60 .74
71_F 8000 3775 269.4 79.0 15.38 .46 .60 .74 258.0 75.6 17.12 .46 .62 .76 244.8 71.7 19.10 .46 .63 .78 231.0 67.7 21.37 .47 .65 .80
(22_C)
9600 4530 277.1 81.2 15.51 .46 .63 .80 264.8 77.6 17.23 .47 .65 .81 251.1 73.6 19.20 .47 .66 .84 236.8 69.4 21.47 .48 .68 .86

COOLING CAPACITY − TSA240S4D (FIRST STAGE) with [(2) TAA120S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 65_F (18_C) 75_F (24_C) 85_F (29_C) 95_F (35_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
6400 3020 127.0 37.2 5.95 .72 .84 .96 122.5 35.9 6.64 .73 .86 .97 117.7 34.5 7.42 .74 .87 .99 112.5 33.0 8.29 .76 .89 1.00
63_F 8000 3775 133.4 39.1 6.06 .77 .90 1.00 128.4 37.6 6.73 .78 .92 1.00 123.4 36.2 7.50 .79 .94 1.00 117.9 34.6 8.37 .81 .96 1.00
(17_C)
9600 4530 138.4 40.6 6.14 .81 .96 1.00 133.1 39.0 6.81 .83 .98 1.00 127.6 37.4 7.57 .84 .99 1.00 121.7 35.7 8.43 .86 1.00 1.00
6400 3020 134.6 39.4 6.08 .58 .69 .81 129.8 38.0 6.76 .58 .71 .82 124.6 36.5 7.52 .59 .71 .84 119.4 35.0 8.38 .59 .73 .86
67_F 8000 3775 141.3 41.4 6.19 .60 .75 .87 135.9 39.8 6.86 .61 .76 .89 130.2 38.2 7.61 .61 .77 .91 124.5 36.5 8.47 .63 .79 .93
(19_C)
9600 4530 145.8 42.7 6.26 .63 .79 .93 140.2 41.1 6.93 .64 .81 .95 134.1 39.3 7.68 .65 .82 .97 128.0 37.5 8.53 .66 .84 .99
6400 3020 142.7 41.8 6.22 .44 .56 .67 137.4 40.3 6.89 .44 .57 .68 131.9 38.7 7.64 .44 .57 .69 126.2 37.0 8.51 .45 .58 .71
71_F 8000 3775 148.7 43.6 6.31 .45 .58 .72 143.6 42.1 7.00 .46 .60 .73 137.5 40.3 7.74 .46 .61 .74 131.2 38.5 8.60 .46 .61 .76
(22_C)
9600 4530 153.4 45.0 6.40 .46 .61 .76 147.6 43.3 7.07 .46 .63 .78 141.5 41.5 7.81 .47 .64 .80 134.9 39.5 8.66 .47 .65 .82

COOLING CAPACITY − TSA240S4D (SECOND STAGE) with [(2) TAA120S4D]


Outdoor Air Temperature Entering Outdoor Coil
Total 85_F (29_C) 95_F (35_C) 105_F (41_C) 115_F (46_C)
Entering Air
Wet Bulb Volume Total Sensible To Total Total Sensible To Total Total Sensible To Total Total Sensible To Total
Tempera- Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T) Cooling Comp Ratio (S/T)
ture Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb Capacity Motor Dry Bulb
kW kW kW kW
cfm L/s kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input
75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
kBtuh kW Input 75_F 80_F 85_F
24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C 24_C 27_C 29_C
6400 3020 235.4 69.0 14.83 .74 .87 .99 225.0 65.9 16.58 .76 .89 1.00 214.1 62.7 18.55 .77 .91 1.00 202.4 59.3 20.87 .79 .94 1.00
63_F 8000 3775 246.8 72.3 15.00 .79 .94 1.00 235.8 69.1 16.73 .81 .96 1.00 224.1 65.7 18.76 .83 .98 1.00 210.9 61.8 21.01 .85 1.00 1.00
(17_C)
9600 4530 255.3 74.8 15.14 .84 .99 1.00 243.5 71.4 16.86 .86 1.00 1.00 233.4 68.4 18.89 .88 1.00 1.00 220.9 64.7 21.21 .91 1.00 1.00
6400 3020 249.1 73.0 15.04 .59 .71 .84 238.9 70.0 16.77 .59 .73 .86 227.4 66.6 18.80 .61 .75 .88 214.2 62.8 21.06 .62 .77 .90
67_F 8000 3775 260.4 76.3 15.21 .61 .77 .91 249.0 73.0 16.95 .63 .79 .93 236.1 69.2 18.92 .64 .81 .95 221.7 65.0 21.17 .65 .83 .98
(19_C)
9600 4530 268.2 78.6 15.35 .65 .82 .97 256.1 75.1 17.06 .66 .84 .99 243.2 71.3 19.05 .67 .86 1.00 228.2 66.9 21.28 .69 .89 1.00
6400 3020 263.8 77.3 15.28 .44 .57 .69 252.4 74.0 17.01 .45 .58 .71 240.3 70.4 18.99 .46 .59 .72 226.7 66.4 21.28 .46 .60 .74
71_F 8000 3775 275.0 80.6 15.48 .46 .61 .74 262.4 76.9 17.20 .46 .61 .76 249.6 73.2 19.16 .47 .63 .79 235.0 68.9 21.44 .47 .65 .81
(22_C)
9600 4530 283.0 82.9 15.62 .47 .64 .80 269.7 79.0 17.32 .47 .65 .82 255.7 74.9 19.31 .49 .67 .84 240.2 70.4 21.55 .48 .68 .87

TS 6 to 20 Ton R−410A Air Conditioners / Page 28


GUIDE SPECIFICATIONS

This Specification is for Lennox Industries T−Classt, 6 to 20 Ton, outdoor air conditioner split system
(TS series) units. Revise specification section number and title below to suit project requirements,
specification practices and section content. Refer to CSI MasterFormat for other section numbers and
titles.
Optional text or text requiring a decision is indicated by bold brackets [ ]; delete text not required in final
copy of specification. Specifier Notes typically precede specification text; delete notes in final copy of
specification. Trade/brand names with appropriate symbols typically are used in Specifier Notes; symbols
are not used in specification text. Metric conversion, where used, is soft metric conversion.

SECTION 23 63 00
REFRIGERANT CONDENSERS
PART 1 GENERAL
1.01 SUMMARY
A. Section Includes: Split System Condensing Units.
Specifier Note: Revise paragraph below to suit project requirements. Add section numbers and titles per CSI
MasterFormat and specifier’s practice.

B. Related Sections
Specifier Note: Article below may be omitted when specifying manufacturer’s proprietary products and
recommended installation. Retain Reference Article when specifying products and installation by an industry
reference standard. If retained, list standard(s) referenced in this section. Indicate issuing authority name,
acronym, standard designation and title. Establish policy for indicating edition date of standard referenced.
Conditions of the Contract or Division 1 References Section may establish the edition date of standards. This
article does not require compliance with standard, but is merely a listing of references used. Article below
should list only those industry standards referenced in this section. Retain only those reference standards to
be used within the text of this Section. Add and delete as required for specific project.

1.02 REFERENCES
A. Air−Conditioning and Refrigeration Institute (ARI):
1. ARI 270−95 Sound Rating of Outdoor Unitary Equipment.
2. ARI 340/360 Commercial and Industrial Unitary Air−Conditioning and Heat Pump Equipment (ANSI
approved)
B. Servicing Standards:
1. National Electric Code (NEC).
2. Underwriters Laboratories (UL).
3. Canadian Electric Code (CEC).
C. Units to be Department of Energy (DOE) rated
D. ISO 9001, units manufactured to quality standard
E. Meet Minimum EPACT 2005, and addendums, efficiency levels

Specifier Note: Article below should be restricted to statements describing design or performance requirements
and functional (not dimensional) tolerances of a complete system. Limit descriptions to composite and
operational properties required to link components of a system together and to interface with other systems.

1.03 SYSTEM DESCRIPTION


A. Performance Requirements:
1. Condensing Unit: [6, 7.5, 10, 12.5, 15 and 20 ton capacity].
2. Electrical Characteristics:
a.60 Hz.
b.3 phase.
c. Voltage: [208/230 V] [460 V] [575 V].

Specifier Note: Article below includes submittal of relevant data to be furnished by Contractor before, during or
after construction. Coordinate this article with Architect’s and Contractor’s duties and responsibilities in
Conditions of the Contract and Division 1 Submittal Procedures Section.

1.04 SUBMITTALS
A. General: Submit listed submittals in accordance with Conditions of the Contract and Division 1 Submittal
Procedures.
TS 6 to 12.5 Ton R−410A Air Conditioners / Page 29
GUIDE SPECIFICATIONS

B. Product Data: Submit product data for specified products.


C. Shop Drawings:
1. Submit shop drawings in accordance with Section [01330 − Submittal Procedures].
2. Indicate:
a.Equipment, piping and connections, together with valves, strainers, control assemblies,
thermostatic controls, auxiliaries and hardware and recommended ancillaries which are
mounted, wired and piped ready for final connection to building system, its size and
recommended bypass connections.
b.Piping, valves and fittings shipped loose showing final location in assembly.
c. Control equipment shipped loose, showing final location in assembly.
d.Field wiring diagrams.
e.Dimensions, internal and external construction details, installation clearances, recommended
method of installation, sizes and location of mounting bolt holes.
f. Detailed composite wiring diagrams for control systems showing factory installed wiring and
equipment on packaged equipment or required for controlling devices or ancillaries,
accessories, controllers.
D. Quality Assurance:
1. All units to be factory tested before shipping.
2. Manufacturer’s Instructions: Manufacturer’s installation instructions.
Specifier Note: Coordinate paragraph below with Part 3 Field Quality Requirements Article herein. Retain or
delete as applicable.

E. Closeout Submittals: Submit the following:


1. Warranty: Warranty documents specified herein.
2. Operation and Maintenance Data: Operation and maintenance data for installed products in
accordance with Division 1 Closeout Submittals (Maintenance Data and Operation Data) Section.
Include methods for maintaining installed products and precautions against cleaning materials and
methods detrimental to finishes and performance. Include names and addresses of spare part
suppliers.
3. Provide brief description of unit, with details of function, operation, control and component service.
4. Commissioning Report: Submit commissioning reports, report forms and schematics in accordance
with Section 01810 − Commissioning.
1.05 QUALITY ASSURANCE
A. Qualifications:
1. Installer experienced in performing work of this section who has specialized in installation of work
similar to that required for this project.
2. Manufacturer Qualifications: Manufacturer capable of providing field service representation during
construction and approving application method.
B. Preinstallation Meetings: Conduct pre−installation meeting to verify project requirements, manufacturer’s
installation instructions and manufacturer’s warranty requirements. Comply with Division 1 Project
Management and Coordination (Project Meetings).
1.06 DELIVERY, STORAGE & HANDLING
A. General: Comply with Division 1 Product Requirements.
B. Ordering: Comply with manufacturer’s ordering instructions and lead time requirements to avoid construction
delays.
C. Packing, Shipping, Handling and Delivery:
1. Deliver materials in manufacturer’s original, unopened, undamaged containers with identification
labels intact.
2. Ship, handle and unload units according to manufacturer’s instructions.
D. Storage and Protection:
1. Store materials protected from exposure to harmful weather conditions.
2. Factory shipping covers to remain in place until installation.
Specifier Note: Coordinate article below with Conditions of the Contract and with Division 1 Closeout
Submittals (Warranty).
1.07 WARRANTY
A. Project Warranty: Refer to Conditions of the Contract for project warranty provisions.
B. Manufacturer’s Warranty: Submit, for Owner’s acceptance, manufacturer’s standard warranty document
executed by authorized company official. Manufacturer’s warranty is in addition to, and not a limitation of,
other rights Owner may have under Contract Documents.
TS 6 to 12.5 Ton R−410A Air Conditioners / Page 30
GUIDE SPECIFICATIONS

Specifier Note: Coordinate paragraph below with manufacturer’s warranty requirements.

C. Warranty: Commencing on Date of Installation.


1. Compressor: 5 year limited (nonresidential applications).
2. Other Covered Components: 1 year limited (nonresidential applications).

PART 2 PRODUCTS

Specifier Note: Retain article below for proprietary method specification. Add product attributes, performance
characteristics, material standards and descriptions as applicable. Use of such phrases as or equal" or or
approved equal" or similar phrases may cause ambiguity in specifications. Such phrases require verification
(procedural, legal and regulatory) and assignment of responsibility for determining or equal" products.

2.01 OUTDOOR CONDENSING UNITS


A. Manufacturer: Lennox Industries.
1. Contact: 2100 Lake Park Blvd., Richardson, TX 75080; Telephone: (800) 453−6669; Web site:
www.lennox.com.
B. Proprietary Products/Systems: TS Series, including the following equipment:
1. Cabinet:
a.Galvanized steel
b.Pre−painted finish
c. Refrigerant line connections to be located outside the unit
d.Control access.
e.All controls factory wired
2. Compressor:
a.Scroll Type
b.Resiliently mounted on rubber mounts for vibration isolation
c. Overload protected
d.Internal excessive current and temperature protection.
e.Crankcase heater
f. 1 or 2 single speed compressor(s) per unit.
3. Refrigerant System
a.General
1. Refrigerant: R410−A
2. Fully serviceable liquid and suction line service valves.
3. Gauge ports.
b.Refrigerant System (large):
1. High pressure switch
2. Loss of charge (low pressure) switch
3. Hi−capacity driers
4. Outdoor Coil(s):
a.Aluminum rippled and lanced fins.
b.Copper tube construction.
c. Aluminum fins to be mechanically bonded to copper tubes.
d.All coils to be high pressure leak tested at factory.
5. Outdoor Coil Fans/Air Mover:
a.Direct drive, propeller type fan(s).
b.Totally enclosed fan motors.
c. Steel fan guards or fan guard.
d.Fan service by removal of fan guard.
6. Controls: Low Ambient Operation, down to 30 °F
7. [Field Installed Options/Accessories]:
a.Outdoor Coils:
1. [Hail Guards: heavy duty metal mesh enclosures]
2. [Coil Guards: heavy duty metal mesh]
b.Controls
1. [L−Connection® Network]
2. [Low Ambient Control, down to 0 °F]
3. [Thermostat]

TS 6 to 12.5 Ton R−410A Air Conditioners / Page 31


GUIDE SPECIFICATIONS

2.02 PRODUCT SUBSTITUTIONS


A. Substitutions: No substitutions permitted.

PART 3 EXECUTION
3.01 MANUFACTURER’S INSTRUCTIONS
Specifier Note: Revise article below to suit project requirements and specifier’s practice.

A. Compliance: Comply with manufacturer’s written data, including product technical bulletins, product catalog
installation instructions and product carton installation instructions.
3.02 EXAMINATION
A. Site Verification of Conditions: Verify substrate conditions, which have been previously installed under other
sections, are acceptable for product installation in accordance with manufacturer’s instructions.
3.03 INSTALLATION
A. Install Condensing Units in accordance with manufacturers instructions and regulations of authorities having
jurisdiction.
END OF SECTION

TS 6 to 12.5 Ton R−410A Air Conditioners / Page 32


REVISIONS
Sections Description of Change
Document Added Specifications, ratings and dimensions for TSA180 and TSA240 models.

Visit us at www.lennox.com
For the latest technical information,
www.lennoxcommercial.com
Contact us at 1−800−4−LENNOX

NOTE − Due to Lennox’ ongoing committment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency. ©2009 Lennox Industries Inc.

You might also like