Sample Calibration Certificate

The calibration report summarizes the calibration of a temperature transmitter. Key details include: - The temperature transmitter with serial number 09091789 passed calibration on May 8, 2011. - It was calibrated against standards with serial numbers 1039C11 and Example that are both due for recalibration in 2012. - The transmitter's output was tested at six temperature points between 0 and 150 degrees C and found to be within 0.18% of the allowed error at each point.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
630 views1 page

Sample Calibration Certificate

The calibration report summarizes the calibration of a temperature transmitter. Key details include: - The temperature transmitter with serial number 09091789 passed calibration on May 8, 2011. - It was calibrated against standards with serial numbers 1039C11 and Example that are both due for recalibration in 2012. - The transmitter's output was tested at six temperature points between 0 and 150 degrees C and found to be within 0.18% of the allowed error at each point.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Page 1 of 1

CALIBRATION REPORT
Issued By: Laboratory

Certificate Number: 10060

Device Information Procedure Information Calibration Information


Device TAG / ID: TMP_TX Procedure:TMP-TX Calibration Date : 08 May 2011
Type: Temperature Transmitter Input Range:0.00 to 150.00°C Due Date: 06 May 2012 (52wks)
Model: Example 0-150°C 4-20mA Output Range:4.00 to 20.00mA Temperature: 22.0°C
Serial Number: 09091789 Reject Error >:0.50% of Range Relative Humidity: 50%
Location:AREA 996

Comments:

Calibrator Information
Description Serial No. Cert No. Cal Date Cal Due
5051+ (DMM mode) 1039C11 0313989 12 Apr 2011 10 Apr 2012
Temperature Standard Example Example 12 Apr 2011 09 Apr 2013

Results:

Input Nominal Actual Allowed % of Range


Test Point Temperature Output Output Error Pass/Fail
0% 0.00°C 4.00mA 4.03mA ±0.1mA 0.1725% Pass
20% 30.00°C 7.20mA 7.22mA ±0.1mA 0.1035% Pass
40% 60.00°C 10.40mA 10.44mA ±0.1mA 0.1800% Pass
60% 90.00°C 13.60mA 13.62mA ±0.1mA 0.1242% Pass
80% 120.00°C 16.80mA 16.82mA ±0.1mA 0.1031% Pass
100% 150.00°C 20.00mA 20.02mA ±0.1mA 0.1205% Pass

End Of Results

Comments:

Calibrated by: Op 1 Aprroved By:Sig 3 Signed:

Aprroved Date:16-May-2011