You are on page 1/ 40

Power Quality

Solution
www.siemens.co.in
Index

Introduction 3

SIECAP™ LV Capaciors 4

Detuned reactors 16

APFC Controllers 24

Capacitor Duty contactors 29

Selection tables 33

4RB LV Capacitors 4KA Detuned Reactors

7UG0 APFC controller 3TS Capacitor Duty Contactor

2
Introduction:
For electricity consumer lagging reactive power generated
from inductive loads is one of the major causes of power Advantages of power factor corrections:
and financial losses i.e. poor power factor (non-unity).
Incorporating power factor correction devices in the network
helps in generating leading reactive power to compensate • Reduction of reactive power in system
lagging reactive power. This techniques help consumer to • Low cost of energy levied at better pf
achieved power factor (cos Ø) close to unity. Fig 1
• Improved voltage quality
The necessary leading power can be produced by LV capacitor
connected in parallel to the supply network close to the • Reduced voltage drops
lagging power source (Like Induction motors, MCC panels etc) • Optimum cable design
The capacitors connect can be fixed type for given fixed • Reduced transmission losses
lagging pf of the system at a point in power system or
variable in steps for a changing connected load. Fig 2

Real Power (P)


Ø2 Ø1

Real Power
= Apparent =
Supply
Power (S) Final Reactive Power
Lagging reactive
power (Q2)

Added Reactive
Power by capacitors
(Qc)
Reactive power added by capacitor banks

Lagging
S = Apparent Power (kVA) Ø1 = actual angle of cos Ø actual Reactive Power
P = Active Power/ Real Power (kW) Ø2 = target angle of cos Ø actual (Q1)
Q = Reactive Power (kVAr) Qc = Q1 – Q2 = P. (tan Ø1- tan Ø2)
Qc = Reactive Power Capacitor (kVAr)

Fig 1

Typical power factor correction circuit diagram

PFC controller

Fuses

Capacitor
contactors

M M
3– 3–

Reactors

Power factor correction


system with filter circuit
reactors for reduction PFC
of harmonics. capacitors

3 Introduction
SIECAP™ LV Capacitors
Capacitor Self-healing properties
SIEMENS SIECAP™ range of capacitor can withstand high
Self-healing
inrush currents caused while individual switching operation
(>100IR) as well while connected in parallel, i.e. as banks
when the inrush current is increased to ≥150 · IR. The high
inrush is because of the charging current comes from the
power line as well as from other capacitors connected in
parallel in the bank.
SIEMENS capacitor range broadly classified in two variants:
1 Dielectric
2 Metalized electrodes
3 Material displacing shock wave
4 Air gap with metal vapor
5,6 Plasma zone
7 Boundary layer between gas phase dielectric and plasma
8 Breakdown channel
9 Gas phase dielectric
10 Zone of displaced metalization and dielectric (isolating region)

Fig 4

In case of electrical overload the dielectric in the breakdown


channel is broken down into highly compressed plasma
that explodes out of the breakdown channel and pushes
SIECAP™ ND SIECAP™ SHD the dielectric layers apart. The discharge continues within
[Normal Duty] [Super Heavy Duty] the spreading plasma via the metal layers so that the
metal surrounding the faulty area is completely burnt out.
SIECAP™ range of capacitor is based MPP technology
This produces perfect isolation of the faulty area within
[Metalized of Zinc Al alloy over Polypropelyne dielectric] of
microseconds. The self-healing process results in negligible
film making with an impregnation of semi-dry biodegradable
capacitance loss less than 100 pF per event. The capacitor
soft resin.
remains fully functional during the entire process, Fig 4
Special film-cutting technique (optimized combination
of wavy and smooth cuts) & heavy edge and produces Overpressure disconnector
a maximum effective surface for the metal spraying or
contacting process, Fig 3. Overpressure disconnector
SIECAP™ capacitors are most compact and light in weight

Wavy cut design


Section A Section A
Metal spray
Metalization

Capacitor Heavy edge


windings
Flame-sprayed
contact area (Zn)
Core
Large effective
contact area
Film and film-
free margin Heavy edge

Metalization Without wavy


cut
Fig 5
Metalization Flame-

Wavy cut
sprayed area At the end of the capacitor’s service life or when a high
Cracks
possible pressure forms inside the can, the overpressure disconnector
Solid contact zone
is activated. The specially designed cover with an expansion
Fig 3 bead moves upwards. Expansion beyond a certain degree will
separate the wires and disconnect the capacitor safely from
the line. The disconnector is separated at its breakpoint (small
notch) and the flow of current to the capacitor windings is
interrupted. Fig 5

Sigut terminals
SIECAP™ range of capacitor comes with SIGUT terminal strip
with electric shock protection (IP2X),
These terminal provides figure touch protection for users
These as well ensures reliable connection

4 SIECAP™ LV Capacitors
Overview Applications

Low Voltage 3 phase Power Capacitors - SIECAP™ ND • Power Factor Correction (PFC)

As per IEC 60831–1/2 Edition 3.0 (2014), IS 13340–1/2 • Automatic capacitor banks

SIECAP™ ND capacitors is a series of MPP Metalized • Fixed PFC applications, e.g. motor compensation
polypropylene) capacitors which have been used for PFC • Detuned PFC systems
applications
• Dynamic PFC systems

Key Features
• Compact design in cylindrical aluminum can with stud
• Stacked winding
• MPP technology
• Voltage range 415 … 480 V
• Output range 0.5 … 30 kvar

Electrical
• Up to 30 kvar per case for three-phase applications
• Long life expectancy of up to 100 000 hours

The power range varies from 0.5 to 30.0 kVar for a three- • High pulse current withstand capability (up to 200 · IR)
phase capacitor design
Mechanical and maintenance
The SIECAP™ ND capacitor is especially intended for power
factor correction in industrial and commercial applications • Reduced mounting costs, easy installation and connection

The capacitors are manufactured using metalized • Low weight and compact volume
polypropylene film as the dielectric and housed in a • Maintenance-free
cylindrical aluminum case
Safety
• Self-healing
• Overpressure disconnector
• Fast On & Shock hazard protected SIGUT- terminals

5 SIECAP™ LV Capacitors
Technical specifications

Standards IEC 60831–1/2 Edition 3.0 (2014), IS 13340–1/2 (2012)

Overvoltage Vmax VR +10% (up to 8 h daily)


VR +15% (up to 30 min. daily)
VR +20% (up to 5 min. daily)
VR +30% (up to 1 min. daily)

Overcurrent I max Up to 1.3 …1.5 • IR (A) (including combined effects of harmonics, overvoltages and
capacitance tolerance) depending on the individual type

Inrush current Is ≤ 200 IR (A)

Losses
• Dielectric 0.2 W/ kVar
• Total 1 0.5 W/ kVar

Rated frequency f 50 / 60 Hz

Capacitance tolerance –5 % / +10 %

Test voltage, terminal / terminal V TT 2.15 * VN VAC / 50 Hz, 2s

Test voltage, terminal / case V TC 3600 VAC / 50 Hz, 2 s

Mean life expectancy TLd(Co) Upto 100 000 hours (temperature class –25/D)

Ambient temperature Class -25/D: Max. short time: + 55°C, max. mean 24h: +45°C; max
mean 1 year: +35°C; lowest temperature: - 25°C

Cooling Natural or Forced air cooling

Humidity Hrel max. 95 %

Altitude max. 4000 m above sea level

Mounting position Upright

Mounting and grounding Threaded M12 (10 Nm) for case size diam. > 53 mm
M8 (4 Nm) for case size diam <= 53 mm

Safety Self-healing technology, overpressure disconnector

Discharge module Discharge module included

Case Extruded aluminium cane

Enclosure IP00 for plastic top – 1 to 5.5 kvar, indoor mounting


IP20 for metal top – 5 to 30 kvar, indoor mounting

Dielectric Polypropylene film

Impregnation Biodegradable soft resin, semi-dry

Terminals SIGUT screw terminals, max current 50 A, max. 16 mm2 cable cross-section or Fast-On
terminals

Number of switching operations 5000 switching’s per year

1) Without discharge resistor

6 SIECAP™ LV Capacitors
Ordering details

50 Hz 60 Hz Weight
Capacity Terminal Dimensions PU MOQ
Output Output Order No per PU Kg
in uF 3 x Type D * H mm Ø Unit (s) Unit (s)
in kVar in kVar approx
Rated Voltage 440 V AC
0.9 1.1 4.9 B 53 x 117 4RB2008-3EE50-8K 1 12 0.44
1 1.2 5.5 B 53 x 117 4RB2010-3EE50-8K 1 12 0.44
1.2 1.4 6.6 B 53 x 117 4RB2012-3EE50-8K 1 12 0.44
1.2 1.4 6.6 B 53 x 117 4RB2012-3EE50-8K 1 12 0.44
2.1 2.5 11.5 B 53 x 117 4RB2021-3EE50-8K 1 12 0.44
2.5 3 13.7 B 63.5 x 129 4RB2025-3EE50-8K 1 12 0.66
3 3.6 16.4 B 63.5 x 129 4RB2030-3EE50-8K 1 12 0.66
4.2 5 23 B 63.5 x 129 4RB2042-3EE50-8K 1 12 0.66
5 6 27.4 B 63.5 x 152 4RB2050-3EE50-8K 1 12 0.66
6 7.2 32.9 A 75x 195 4RB2060-3EE50-8K 1 6 1.32
7 8.4 38.4 A 75 x 195 4RB2070-3EE50-8K 1 6 1.32
7.5 9 41.1 A 75 x 195 4RB2075-3EE50-8K 1 6 1.32
8.3 10 45.5 A 75 x 195 4RB2083-3EE50-8K 1 6 1.32
9 10.8 49.3 A 75 x 195 4RB2090-3EE50-8K 1 6 1.32
10 12 54.8 A 85 x 195 4RB2100-3EE50-8K 1 4 1.65
12.5 15 68.5 A 85 x 270 4RB2125-3EE50-8K 1 4 1.98
15 18 82.2 A 85 x 270 4RB2150-3EE50-8K 1 4 1.98
16.7 20 91.5 A 85 x 348 4RB2167-3EE50-8K 1 4 2.64
20 24 109.6 A 85 x 348 4RB2200-3EE50-8K 1 4 2.64
20.8 25 114 A 85 x 348 4RB2208-3EE50-8K 1 4 2.64
25 30 137 A 90 x 348 4RB2250-3EE50-8K 1 4 2.75
28 – 153.4 A 90 x 348 4RB2280-3EE50-8K 1 4 2.75
30 – 164.4 A 90 x 348 4RB2300-3EE50-8K 1 4 2.75
Rated Voltage 480 V AC
1 1.2 4.6 B 53 x 117 4RB2010-3EJ50-8K 1 12 0.44
1.5 1.8 6.9 B 63.5 x 129 4RB2015-3EJ50-8K 1 12 0.66
2 2.4 9.2 B 63.5 x 129 4RB2020-3EJ50-8K 1 12 0.66
2.5 3 11.5 B 63.5 x 129 4RB2025-3EJ50-8K 1 12 0.66
4.2 5 19.3 B 63.5 x 152 4RB2042-3EJ50-8K 1 12 0.66
5 6 23 A 75 x 195 4RB2050-3EJ50-8K 1 12 1.32
5.5 6.6 25.3 B 63.5 x 188 4RB2055-3EJ50-8K 1 12 0.66
8.3 10 38.2 A 75 x 270 4RB2083-3EJ50-8K 1 6 1.54
10.4 12.5 47.9 A 85 x 270 4RB2104-3EJ50-8K 1 4 1.98
11.1 13.3 51.1 A 85 x 270 4RB2111-3EJ50-8K 1 4 1.98
12.5 15 57.6 A 85 x 348 4RB2125-3EJ50-8K 1 4 2.64
13.8 16.6 63.5 A 85 x 270 4RB2138-3EJ50-8K 1 4 1.98
15 18 69.1 A 85 x 348 4RB2150-3EJ50-8K 1 4 2.64
16.7 20 76.9 A 85 x 348 4RB2167-3EJ50-8K 1 4 2.64
20.8 25 95.8 A 85 x 348 4RB2208-3EJ50-8K 1 4 2.64
25 30 115.1 A 90 x 348 4RB2250-3EJ50-8K 1 4 2.75
27.7 – 127.5 A 90 x 348 4RB2277-3EJ50-8K 1 4 2.75
30 – 138.1 A 90 x 348 4RB2300-3EJ50-8K 1 4 2.75

7 SIECAP™ LV Capacitors
Dimension drawings
Terminal Type A Terminal Type B

Discharge resistor Fast On connection


(6.35 x 8 )
Additionally discharge
resistor to be placed
Sigut
Terminals
4.5 ±0.5

h + 40
FirmLabel
h±3

Marking

h±3
Firm Label
marking

d±1
16 +1

16 +1
M 12
(Pitch 1.75 mm)
Tightening Torque = 10 Nm max.

Toothed lock washer

M 8 X10 (d = 53),
Heaxagonal Nut
Tightening Torque 4 Nm
M12 X 6 ( d = 63.5 ),
Tightening Torque 10 Nm

d+4
9.8 ±0.3
19.6 ±0.5

d±1

16.7 ±0.5

M4 screws
Tightening Torque 2 Nm

8 SIECAP™ LV Capacitors
Overview Applications

Low Voltage 3 Phase Power Capacitors SIECAP™ SHD • Power Factor Correction (PFC)

IEC 60831–1/2 Edition 3.0 (2014), IS 13340–1/2 (2012) • Automatic capacitor banks

SIECAP™ SHD capacitors is a series of MPP Metalized • Fixed PFC applications, e.g. motor compensation
polypropylene) capacitors which have been used for PFC • Detuned PFC systems
applications
• Dynamic PFC systems
These are designed for commercial, heavy and light industrial
application • Heavy Industries

The power range varies from 1 to 33.0 kvar for a three-phase • Most compact desing in cylindrical aluminum can with
capacitor desing stud

The SIECAP™SHD capacitor is especially intended for power • Stacked winding


factor correction in industrial and commercial applications • MPP technology
Especially designed to meet Heavy duty requirements The • Voltage range 415 … 690 V
capacitors are manufactured using metalized polypropy lene
film as the dielectric and housed in a Cylindrical aluminum • Output range 1 … 33 kvar
case • Super heavy duty

Electrical
• Up to 33 kvar per case for three-phase applications
• Long life expectancy of up to 200 000 hours
• High pulse current withstand capability (up to 500 · IR)

Mechanical and maintenance


• Reduced mounting costs, easy installation and connection
• Low weight and compact volume
• Maintenance-free

Safety
• Self-healing
• Overpressure disconnector
• Shock hazard protected SIGUT- terminal

9 SIECAP™ LV Capacitors
Technical specifications

Standards IEC 60831–1/2 Edition 3.0 (2014), IS 13340–1/2 (2012)

Overvoltage Vmax VR +10% (up to 8 h daily)


VR +15% (up to 30 min. daily)
VR +20% (up to 5 min. daily)
VR +30% (up to 1 min. daily)

Overcurrent I max Up to 1.6 …2.0 • IR (A) (including combined effects of harmonics, overvoltages and
capacitance tolerance) depending on the individual type

Inrush current Is ≤ 500 IR (A)

Losses
• Dielectric 0.2 W/ kVar
• Total 1 0.45 W/ kVar

Rated frequency f 50 / 60 Hz

Capacitance tolerance –5 % / +5 %

Test voltage, terminal / terminal V TT 2.15 * VN VAC / 50 Hz, 2s

Test voltage, terminal / case V TC 3600 VAC / 50 Hz, 2 s upto VN = 525 VAC
6000 VAC / 50 Hz, 2 s above VN = 525 VAC

Mean life expectancy TLd(Co) Upto 200 000 hours (temperature class –40/D)

Ambient temperature Class -40/60: Max. short time: + 60°C, max. mean 24h: +45°C; max mean 1 year: +35°C;
lowest temperature: - 40°C

Cooling Natural or Forced air cooling

Humidity Hrel max. 95 %

Altitude max. 4000 m above sea level

Mounting position Upright / horizontal

Mounting and grounding Threaded M12 (10 Nm) for case size diam. > 53 mm
M8 (4 Nm) for case size diam <= 53 mm

Safety Self-healing technology, overpressure disconnector

Discharge module Discharge module included

Case Extruded aluminium cane

Enclosure IP00 for plastic top – 1 to 4 kvar, indoor mounting


IP20 for metal top – 5 to 30 kvar, indoor mounting

Dielectric Polypropylene film

Impregnation Biodegradable soft resin, semi-dry

Terminals SIGUT screw terminals, max current 80 A, max. 25 mm2 cable cross-section or Fast-On
terminals

Number of switching operations 15000 switching’s per year

1) Without discharge resistor

10 SIECAP™ LV Capacitors
Ordering details
50 Hz 60 Hz Weight
Capacity Terminal Dimensions PU MOQ
Output Output Order No per PU Kg
in uF 3 x Type D * H mm Ø Unit (s) Unit (s)
in kVar in kVar approx
Rated Voltage 415 V AC
5 6 30.8 A 75 x 164 4RB1050-3EB50-8K 1 4 0.95
6.3 7.6 38.8 A 75 x 164 4RB1063-3EB50-8K 1 4 0.95
7.5 9 46.2 A 75 x 200 4RB1075-3EB50-8K 1 4 1.16
10.4 12.5 64.1 A 75 x 200 4RB1104-3EB50-8K 1 4 1.16
12.5 15 77 A 85 x 200 4RB1125-3EB50-8K 1 4 1.48
15 18 92.4 A 85 x 200 4RB1150-3EB50-8K 1 4 1.48
20 24 123.2 B 100 x 207 4RB1200-3EB50-8K 1 4 2.13
25 30 154 B 116 x 192 4RB1250-3EB50-8K 1 4 2.65
28.1 - 173.1 B 116 x 207 4RB1281-3EB50-8K 1 4 2.86
30 - 184.8 B 116 x 207 4RB1300-3EB50-8K 1 4 2.86
33 - 203.3 B 116 x 224 4RB1330-3EB50-8K 1 4 3.09
Rated Voltage 440 V AC
1 1.2 5.5 E 53 x 117 4RB1010-3EE50-8K 1 4 0.44
2 2.4 11 E 53 x 129 4RB1020-3EE50-8K 1 4 0.44
3 3.6 16.4 E 53 x 129 4RB1030-3EE50-8K 1 4 0.44
4 4.8 21.9 E 63.5 x 152 4RB1040-3EE50-8K 1 4 0.66
5 6 27.4 A 75 x 164 4RB1050-3EE50-8K 1 4 0.95
7.5 9 41.1 A 75 x 200 4RB1075-3EE50-8K 1 4 1.16
10 12 54.8 A 75 x 200 4RB1100-3EE50-8K 1 4 1.16
10.4 12.5 57 A 85 x 200 4RB1104-3EE50-8K 1 4 1.48
12.5 15 68.5 A 85 x 200 4RB1125-3EE50-8K 1 4 1.48
15 18 82.2 A 85 x 218 4RB1150-3EE50-8K 1 4 1.62
16.7 20 91.5 B 100 x 207 4RB1167-3EE50-8K 1 4 2.13
20 24 109.6 B 100 x 207 4RB1200-3EE50-8K 1 4 2.13
25 30 137 B 116 x 192 4RB1250-3EE50-8K 1 4 2.65
28.1 - 154 B 116 x 207 4RB1281-3EE50-8K 1 4 2.86
30 - 164.4 B 125 x 192 4RB1300-3EE50-8K 1 4 3.09
33.1 - 181.4 B 116 x 224 4RB1331-3EE50-8K 1 4 3.09
Rated Voltage 480 V AC
5 6 23 A 75 x 164 4RB1050-3EJ50-8K 1 4 0.95
6.3 7.6 29 A 75 x 164 4RB1063-3EJ50-8K 1 4 0.95
8.3 10 38.2 A 75 x 200 4RB1083-3EJ50-8K 1 4 1.16
10.4 12.5 47.9 A 75 x 200 4RB1104-3EJ50-8K 1 4 1.16
11 13.2 50.7 A 85 x 200 4RB1111-3EJ50-8K 1 4 1.48
12.5 15 57.6 A 85 x 200 4RB1125-3EJ50-8K 1 4 1.48
13.8 16.6 63.5 A 85 x 200 4RB1138-3EJ50-8K 1 4 1.48
15 18 69.1 B 100 x 207 4RB1150-3EJ50-8K 1 4 2.13
16.7 20 76.9 B 100 x 207 4RB1167-3EJ50-8K 1 4 2.13
18.7 22.4 86.1 B 100 x 207 4RB1187-3EJ50-8K 1 4 2.13
20 24 92.1 B 100 x 207 4RB1200-3EJ50-8K 1 4 2.13
22 26.4 101.3 B 116 x 207 4RB1220-3EJ50-8K 1 4 2.86
25 30 115.1 B 116 x 192 4RB1250-3EJ50-8K 1 4 2.65
28.1 - 129.4 B 116 x 207 4RB1281-3EJ50-8K 1 4 2.86
30 - 138.1 B 125 x 192 4RB1300-3EJ50-8K 1 4 3.09
31 - 142.7 B 116 x 224 4RB1310-3EJ50-8K 1 4 3.09
33 - 152 B 116 x 224 4RB1330-3EJ50-8K 4 3.09

11 SIECAP™ LV Capacitors
50 Hz 60 Hz Weight
Capacity Terminal Dimensions PU MOQ
Output Output Order No per PU Kg
in uF 3 x Type D * H mm Ø Unit (s) Unit (s)
in kVar in kVar approx
Rated Voltage 525 V AC
5 6 19.2 A 75 x 164 4RB1050-3FC50-8K 1 6 0.95
6.3 7.6 24.2 A 75 x 164 4RB1063-3FC50-8K 1 6 0.95
8.3 10 31.9 A 75 x 200 4RB1083-3FC50-8K 1 6 1.16
10.4 12.5 40 A 85 x 185 4RB1104-3FC50-8K 1 9 1.37
12.5 15 48.1 A 85 x 200 4RB1125-3FC50-8K 1 9 1.48
13.2 15.8 50.8 A 85 x 200 4RB1132-3FC50-8K 1 9 1.48
15 18 57.7 A 85 x 218 4RB1150-3FC50-8K 1 4 1.62
16.7 20 64.3 B 100 x 207 4RB1167-3FC50-8K 1 6 2.13
20 24 77 B 100 x 224 4RB1200-3FC50-8K 1 4 2.3
25 30 96.2 B 116 x 207 4RB1250-3FC50-8K 1 4 2.86
26.5 31.8 102 B 116 x 207 4RB1265-3FC50-8K 1 4 2.86
30 - 115.5 B 125 x 207 4RB1300-3FC50-8K 1 4 3.1
33.1 - 127.4 B 136 x 192 4RB1331-3FC50-8K 1 4 3.65
Rated Voltage 690 V AC
5.3 6.4 11.8 C 75 x 185 4RB1053-3GK50-8K 1 6 1.16
6.9 8.3 15.4 C 75 x 200 4RB1068-3GK50-8K 1 6 1.16
10.4 12.5 23.2 C 75 x 200 4RB1104-3GK50-8K 1 6 1.16
12.5 15 27.9 C 85 x 200 4RB1125-3GK50-8K 1 9 1.48
14.6 17.5 32.5 D 100 x 207 4RB1146-3GK50-8K 1 6 2.13
20 24 44.6 D 100 x 207 4RB1200-3GK50-8K 1 6 2.13
25 30 55.7 D 116 x 192 4RB1250-3GK50-8K 1 4 2.65

12 SIECAP™ LV Capacitors
Dimension drawings
Terminal Type A Terminal Type B

Discharge resistor

Sigut
Terminals

4.5 ±0.5
4.5 ±0.5

h + 40
h + 40
FirmLabel

h±3
FirmLabel Marking
h±3

Marking

16 +1
d±1
d±1
16 +1

M 12
(Pitch 1.75 mm)
Tightening Torque = 10 Nm max.
M 12
(Pitch 1.75 mm)
Tightening Torque = 10 Nm max.

Toothed lock washer

Heaxagonal Nut
12 ±0.3

O 120.8 ±0.7

d+4
24 ±0.5
9.8 ±0.3
19.6 ±0.5

16.7 ±0.5
21 ±0.5
M4 screws
Tightening Torque 2 Nm

13 SIECAP™ LV Capacitors
Terminal Type C Terminal Type D

Discharge
resistor

4.5 ±0.5
4.5 ±0.5

h + 40
h +40
FirmLabel

h±3
FirmLabel
h±3

Marking
Marking

+1
116 ±0.5

16
75 ±0.5
16 +1

M 12
(Pitch 1.75 mm)
Tightening Torque = 10 Nm max.
M 12
(Pitch 1.75 mm)
Tightening Torque = 10 Nm max.
12 ±0.3

d + 5.5
d+4

24 ±0.5
19.6 ±0.5
9.8 ±0.3

16.7 ±0.5 21 ±0.5

14 SIECAP™ LV Capacitors
Terminal Type E

Fast On connection
(6.35 x 8 )
Additionally discharge
resistor to be placed

h±3
Firm Label
marking

16 +1

M 8 X10 (d = 53),
Tightening Torque 4 Nm
M12 X 6 ( d = 63.5 ),
Tightening Torque 10 Nm

d±1

15 SIECAP™ LV Capacitors
Detuned reactor
Overview Tuning frequency of LC filtercan be calculated by below
formula:-

fs
ft = p
100
Where
ft = tuning frequency
fs = supply frequency
p = detuning factor in percentage

Impedance

In past few years the use of power electronics equipment’s


like drives, SMPS, UPS etc has increased tremendously.
These devices distort the pure sinusoidal waveform of power
supply. These distortions can be called as harmonics. When
a capacitor is used for power factor correction, it might
create a resonating circuit with the feeding transformer. The
resonance frequency is generally from 250Hz to 500Hz, that
Capacitive ft Inductive Frequency

means 5th to 7th harmonics. This resonance is undesired


condition and it might lead to
• Overloading of capacitors- reduce the life of capacitor This combination of detuned LC filter will act capacitive for
• Overloading of transformer, cables and other switchgear frequency below ft and inductive for frequency above ft. Thus
elements in the circuit- reduces life of all components for base frequency of 50 or 60Hz this detune filter will act as
capacitive and improves the power factor. This LC detuned
• Voltage distortion
filter is selected such that the tuning frequency is much less
• Increased power losses than the dominant harmonic frequency. Thus harmonics
• Nuisance tripping of protection equipment always seeshigher impedance and the condition of resonance
with feeding transformeris avoided.
This resonance can be avoided by putting a detuned reactor
in series with the capacitor. The reactor shall be such that For example if the dominant harmonics is 5th harmonic
the tuning frequency with capacitor shall be less than the and base frequency is 50Hz, a 7% detuned reactor shall be
dominant harmonics. This combination of power factor selected. The tuning frequency of this filter will be
correction capacitor and detuned reactors behaves inductively
to frequencies above tuning frequency. Thus provide high
fs
ft = p
impedance path to harmonics present in the system.
100
Detuning factor
Detuning factor can be defined by following formula:- 50
ft = =>189 Hz
XL 7
100 = p% 100
XC
189Hz, the tuning frequency in this case is lesser then 250Hz,
Where
the harmonic frequency. Hence there will not be a situation
XL = Inductive reactance of resonance between the feeding transformer and capacitor.
XC = Capacitive reactance
p = detuning factor in percentage

16 Detuned reactor
Technical Specifications

7% Cu Reactor
Technical Data
De-tuning factor % 7% 7% 7% 7% 7% 7% 7% 7% 7%
Effective filter output QC kVAr 5 10 12.5 15 20 25 50 75 100
Rated voltage VR V 440
Rated frequency Hz 50
Ambient temperature / 40 °C/H
Insulation class:
Capacitance C delta µF 76.5 172 191 229.5 306 382.5 765 1147 1530
Inductivity L mH 3 X 9.28 3 X 4.64 3 X 3.71 3 X 3.1 3 X 2.32 3 X 1.86 3 X 0.93 3 X 0.62 3 X 0.46
Linear up to A 11.4 22.7 28.4 34 45.4 57 113.5 170.3 227
Effective current Irms A 7.45 14.9 18.61 22.34 29.78 37.2 74.45 111.7 148.9
Temperature protection (NC) yes
Total losses P D W 45 75 80 90 100 120 210 275 350
Total weight kg 7 9 10 15 16 17 26 42 50
Connection
Line 1U1-1V1-1W1
Capacitors 1U2-1V2-1W2
Temperature control: 1-2
Dimension
Length mm 175 175 175 225 225 225 260 300 310
Height mm 158 160 160 230 205 205 240 270 270
Width mm 100 125 125 145 155 155 215 180 205

14%, Cu reactors
Technical Data
De-tuning factor % 14% 14% 14% 14% 14% 14% 14% 14% 14%
Effective filter output QC kVAr 5 10 12.5 15 20 25 50 75 100
Rated voltage VR V 440
Rated frequency Hz 50
Ambient temperature / 40 °C/H
Insulation class:
Capacitance C delta µF 70.7 141.5 176.8 212.2 282.9 356.7 707.4 1061 1061
Inductivity L mH 3X 3X 3 X 8.03 3 X 6.69 3 X 5.02 3 X 4.01 3 X 2.01 3 X 1.34 3X1
20.06 10.03
Linear up to A 9.38 18.76 23.45 28.15 37.53 46.91 93.82 140.7 187.6
Effective current Irms A 7.01 14.03 17.53 21.04 28.05 35.07 70.13 105.2 140.3
Temperature protection (NC) yes
Total losses P D W 80 105 120 150 180 210 270 375 500
Total weight kg 9 15 16 18 26 27 45 75 84
Connection
Line 1U1-1V1-1W1
Capacitors 1U2-1V2-1W2
Temperature control: 1-2
Dimension
Length mm 175 225 225 225 260 260 310 378 378
Height mm 156 205 205 205 232 240 270 300 300
Width mm 125 150 155 155 210 208 204 225 225

17 Detuned reactor
Technical Specifications

5.67%, Cu reactors
Technical Data
De-tuning factor % 14% 14% 14% 14% 14% 14% 14% 14% 14%
Effective filter output QC kVAr 5 10 12.5 15 20 25 50 75 100
Rated voltage VR V 440
Rated frequency Hz 50
Ambient temperature / 40 °C/H
Insulation class:
Capacitance C delta µF 77.6 155.2 191 232.8 310.4 387.9 775.9 1164 1552
Inductivity L mH 3 X 7.41 3 X 3.7 3 X 2.96 3 X 2.47 3 X 1.85 3 X 1.48 3 X 0.74 3 X 0.49 3 X 0.37
Linear up to A 13.65 27.3 34.12 40.94 54.59 68.23 136.5 204.7 272.9
Effective current Irms A 8.37 16.74 20.93 25.11 33.48 41.85 83.71 125.6 167.4
Temperature protection (NC) yes
Total losses P D W 45 75 80 90 100 120 210 275 350
Total weight kg 7 9 10 15 16 17 26 42 50
Connection
Line 1U1-1V1-1W1
Capacitors 1U2-1V2-1W2
Temperature control: 1-2
Dimension
Length mm 175 175 190 225 225 225 260 310 330
Height mm 158 160 160 230 205 205 240 270 270
Width mm 95 124 124 145 155 155 208 180 180

7%, Al reactors
Technical Data
De-tuning factor % 7% 7% 7% 7% 7% 7% 7% 7% 7%
Effective filter output QC kVAr 5 10 12.5 15 20 25 50 75 100
Rated voltage VR V 440
Rated frequency Hz 50
Ambient temperature / 40 °C/H
Insulation class:
Capacitance C delta µF 76.5 172 191 229.5 306 382.5 765 1147 1530
Inductivity L mH 3 X 9.28 3 X 4.64 3 X 3.71 3 X 3.1 3 X 2.32 3 X 1.86 3 X 0.93 3 X 0.62 3 X 0.46
Linear up to A 11.4 22.7 28.4 34 45.4 57 113.5 170.3 227
Effective current Irms A 7.45 14.9 18.61 22.34 29.78 37.2 74.45 111.7 148.9
Temperature protection (NC) yes
Total losses P D W 50 83 85 100 110 130 240 285 380
Total weight kg 7 9 10 15 16 17 26 42 50
Connection
Line 1U1-1V1-1W1
Capacitors 1U2-1V2-1W2
Temperature control: 1-2
Dimension
Length mm 175 175 175 225 225 225 275 310 335
Height mm 158 160 160 230 205 205 238 270 270
Width mm 100 125 125 155 175 175 230 180 185

18 Detuned reactor
Technical Specifications

14%, Al reactors
Technical Data
De-tuning factor % 14% 14% 14% 14% 14% 14% 14%
Effective filter output QC kVAr 5 10 12.5 15 20 25 50
Rated voltage VR V 440
Rated frequency Hz 50
Ambient temperature / 40 °C/H
Insulation class:
Capacitance C delta µF 70.7 176.8 176.8 212.2 282.9 353.7 707.4
Inductivity L mH 3 X 20.06 3 X 10.03 3 X 8.03 3 X 6.69 3 X 5.02 3 X 4.01 3 X 2.01
Linear up to A 9.38 18.76 23.45 28.15 37.53 46.91 93.82
Effective current Irms A 7.01 14.03 17.53 21.04 28.05 35.07 70.13
Temperature protection (NC) yes
Total losses P D W 80 105 120 150 200 210 380
Total weight kg 9 15 16 18 25 28 42
Connection
Line 1U1-1V1-1W1
Capacitors 1U2-1V2-1W2
Temperature control: 1-2
Dimension
Length mm 175 225 225 225 285 285 335
Height mm 156 205 205 205 210 230 270
Width mm 125 150 155 155 188 188 190

5.67%, Al reactors
Technical Data
De-tuning factor % 5.67% 5.67% 5.67% 5.67% 5.67% 5.67% 5.67% 5.67% 5.67%
Effective filter output QC kVAr 5 10 12.5 15 20 25 50 75 100
Rated voltage VR V 440
Rated frequency Hz 50
Ambient temperature / 40 °C/H
Insulation class:
Capacitance C delta µF 77.6 155.2 194 232.8 310.4 387.9 775.9 1164 1552
Inductivity L mH 3 X 7.41 3 X 3.7 3 X 2.96 3 X 2.47 3 X 1.85 3 X 1.48 3 X 0.74 3 X 0.49 3 X 0.37
Linear up to A 13.65 27.3 34.12 40.94 54.59 68.23 136.5 204.7 272.9
Effective current Irms A 8.37 16.74 20.93 25.11 33.48 41.85 83.71 125.6 167.4
Temperature protection (NC) yes
Total losses P D W 55 85 88 105 115 135 250 290 390
Total weight kg 8 10 11 16 18 20 27 43 51
Connection
Line 1U1-1V1-1W1
Capacitors 1U2-1V2-1W2
Temperature control: 1-2
Dimension
Length mm 175 190 175 225 225 240 275 310 310
Height mm 158 160 158 230 205 205 238 270 270
Width mm 100 125 125 155 175 175 230 180 210

19 Detuned reactor
Ordering Information

Bank Size Type Detuning Factor Voltage Material


5kVAr 4KA1220-1AA01-0AA0 7% 440V AC Cu
10kVAr 4KA1220-3AA01-0AA0 7% 440V AC Cu
12.5kVAr 4KA1220-4AA01-0AA0 7% 440V AC Cu
15kVAr 4KA1220-5AA01-0AA0 7% 440V AC Cu
20kVAr 4KA1220-6AA01-0AA0 7% 440V AC Cu
25kVAr 4KA1220-7AA01-0AA0 7% 440V AC Cu
50kVAr 4KA1220-2BA01-0AA0 7% 440V AC Cu
75kVAr 4KA1220-3BA03-0AA0 7% 440V AC Cu
100kVAr 4KA1220-4BA03-0AA0 7% 440V AC Cu
5kVAr 4KA1220-1AB01-0AA0 14% 440V AC Cu
10kVAr 4KA1220-3AB01-0AA0 14% 440V AC Cu
12.5kVAr 4KA1220-4AB01-0AA0 14% 440V AC Cu
15kVAr 4KA1220-5AB01-0AA0 14% 440V AC Cu
20kVAr 4KA1220-6AB01-0AA0 14% 440V AC Cu
25kVAr 4KA1220-7AB01-0AA0 14% 440V AC Cu
50kVAr 4KA1220-2BB01-0AA0 14% 440V AC Cu
75kVAr 4KA1220-3BB03-0AA0 14% 440V AC Cu
100kVAr 4KA1220-4BB03-0AA0 14% 440V AC Cu
5kVAr 4KA1220-1AC01-0AA0 5.67% 440V AC Cu
10kVAr 4KA1220-3AC01-0AA0 5.67% 440V AC Cu
12.5kVAr 4KA1220-4AC01-0AA0 5.67% 440V AC Cu
15kVAr 4KA1220-5AC01-0AA0 5.67% 440V AC Cu
20kVAr 4KA1220-6AC01-0AA0 5.67% 440V AC Cu
25kVAr 4KA1220-7AC01-0AA0 5.67% 440V AC Cu
50kVAr 4KA1220-2BC01-0AA0 5.67% 440V AC Cu
75kVAr 4KA1220-3BC03-0AA0 5.67% 440V AC Cu
100kVAr 4KA1220-4BC03-0AA0 5.67% 440V AC Cu
5kVAr 4KA1420-1AA01-0AA0 7% 440V AC Al
10kVAr 4KA1420-3AA01-0AA0 7% 440V AC Al
12.5kVAr 4KA1420-4AA01-0AA0 7% 440V AC Al
15kVAr 4KA1420-5AA01-0AA0 7% 440V AC Al
20kVAr 4KA1420-6AA01-0AA0 7% 440V AC Al
25kVAr 4KA1420-7AA01-0AA0 7% 440V AC Al
50kVAr 4KA1420-2BA01-0AA0 7% 440V AC Al
75kVAr 4KA1420-3BA03-0AA0 7% 440V AC Al
100kVAr 4KA1420-4BA03-0AA0 7% 440V AC Al
5kVAr 4KA1420-1AB01-0AA0 14% 440V AC Al
10kVAr 4KA1420-3AB01-0AA0 14% 440V AC Al
12.5kVAr 4KA1420-4AB01-0AA0 14% 440V AC Al
15kVAr 4KA1420-5AB01-0AA0 14% 440V AC Al
20kVAr 4KA1420-6AB01-0AA0 14% 440V AC Al
25kVAr 4KA1420-7AB01-0AA0 14% 440V AC Al
50kVAr 4KA1420-2BB01-0AA0 14% 440V AC Al
5kVAr 4KA1420-1AC01-0AA0 5.67% 440V AC Al
10kVAr 4KA1420-3AC01-0AA0 5.67% 440V AC Al
12.5kVAr 4KA1420-4AC01-0AA0 5.67% 440V AC Al
15kVAr 4KA1420-5AC01-0AA0 5.67% 440V AC Al
20kVAr 4KA1420-6AC01-0AA0 5.67% 440V AC Al
25kVAr 4KA1420-7AC01-0AA0 5.67% 440V AC Al
50kVAr 4KA1420-2BC01-0AA0 5.67% 440V AC Al
75kVAr 4KA1420-3BC03-0AA0 5.67% 440V AC Al
100kVAr 4KA1420-4BC03-0AA0 5.67% 440V AC Al

20 Detuned reactor
Dimension drawing

7% Cu detuned reactor (all dimensions in mm)


kVAr Type L H W I1 I2 n1 n2 b e d1 d2 A B Ø
5 4KA1220-1AA01-0AA0 175 158 100 150 150 100 62 78 62 10.8 15.5 125 58 6.5
10 4KA1220-3AA01-0AA0 175 160 125 150 150 100 83 98 76 10.8 15.5 125 58 6.5
12.5 4KA1220-4AA01-0AA0 175 160 125 150 150 100 83 98 76 10.8 15.5 125 58 6.5
15 4KA1220-5AA01-0AA0 225 230 145 190 190 150 73 90 97 10.8 15.5 175 71.5 8.5
20 4KA1220-6AA01-0AA0 225 205 155 190 190 150 98 112 100 10.8 15.5 175 95 8.5
25 4KA1220-7AA01-0AA0 225 205 155 190 190 150 98 112 100 10.8 15.5 175 95 8.5
50 4KA1220-2BA01-0AA0 260 240 215 220 220 150 168 185 118 10.8 15.5 175 165 8.5
75 4KA1220-3BA03-0AA0 300 270 180 250 250 150 136.5 150 97 10.8 15.5 175 132 10.5
100 4KA1220-4BA03-0AA0 310 270 205 265 265 150 162.5 178 110 10.8 15.5 175 159 10.5

7% Al detuned reactor (all dimensions in mm)


kVAr Type L H W I1 I2 n1 n2 b e d1 d2 A B Ø
5 4KA1420-1AA01-0AA0 175 158 100 150 150 100 61.5 78 62 10.8 15.5 125 58 6.5
10 4KA1420-3AA01-0AA0 175 160 125 150 150 100 82.5 98 76 10.8 15.5 125 58 6.5
12.5 4KA1420-4AA01-0AA0 175 160 125 150 150 100 82.5 98 76 10.8 15.5 125 78 6.5
15 4KA1420-5AA01-0AA0 225 230 155 190 190 150 73 90 105 10.8 15.5 175 71.5 8.5
20 4KA1420-6AA01-0AA0 225 205 175 190 190 150 97.8 112 115 10.8 15.5 175 95 8.5
25 4KA1420-7AA01-0AA0 225 205 175 190 190 150 97.8 112 115 10.8 15.5 175 95 8.5
50 4KA1420-2BA01-0AA0 275 238 230 235 235 150 168 185 135 10.8 15.5 175 165 8.5
75 4KA1420-3BA03-0AA0 310 270 180 265 265 150 135 150 99 10.8 15.5 175 132 10.5
100 4KA1420-4BA03-0AA0 335 270 185 285 285 150 136.5 150 97 10.8 15.5 175 132 10.5

21 Detuned reactor
14% Cu detuned reactor (all dimensions in mm)
kVAr Type L H W I1 I2 n1 n2 b e d1 d2 A B Ø
5 4KA1220-1AB01-0AA0 175 156 125 150 150 100 84 100 76 10.8 15.5 125 81 6.5
10 4KA1220-3AB01-0AA0 225 205 150 190 190 150 97.5 112 96 10.8 15.5 175 95 6.5
12.5 4KA1220-4AB01-0AA0 225 205 155 190 190 150 98 112 100 10.8 15.5 175 95 8.5
15 4KA1220-5AB01-0AA0 225 205 155 190 190 150 97.5 112 100 10.8 15.5 175 95 8.5
20 4KA1220-6AB01-0AA0 260 232 210 220 220 150 168 185 120 10.8 15.5 175 165 8.5
25 4KA1220-7AB01-0AA0 260 240 208 220 220 150 168 185 116 10.8 15.5 175 165 8.5
50 4KA1220-2BB01-0AA0 310 270 204 265 265 150 135 150 120 10.8 15.5 175 132 8.5
75 4KA1220-3BB03-0AA0 378 300 225 330 330 150 170 190 122 10.5 15.5 175 170 10.5
100 4KA1220-4BB03-0AA0 378 300 225 330 330 150 170 190 122 10.5 15.5 175 170 10.5

14% Al detuned reactor (all dimensions in mm)


kVAr Type L H W I1 I2 n1 n2 b e d1 d2 A B Ø
5 4KA1420-1AB01-0AA0 175 156 125 150 150 100 84 100 76 10.8 15.5 125 81 6.5
10 4KA1420-3AB01-0AA0 225 205 150 190 190 150 97.5 112 96 10.8 15.5 175 95 6.5
12.5 4KA1420-4AB01-0AA0 225 205 155 190 190 150 98 112 100 10.8 15.5 175 95 8.5
15 4KA1420-5AB01-0AA0 225 205 155 190 190 150 97.5 112 100 10.8 15.5 175 95 8.5
20 4KA1420-6AB01-0AA0 285 210 188 235 235 150 168 185 92 10.8 15.5 175 165 8.5
25 4KA1420-7AB01-0AA0 285 230 188 235 235 150 165 185 95 10.8 15.5 175 168 8.5
50 4KA1420-2BB01-0AA0 335 270 190 285 285 150 136 150 99 10.8 15.5 175 132 10.5

22 Detuned reactor
5.67% Cu detuned reactor (all dimensions in mm)
kVAr Type L H W I1 I2 n1 n2 b e d1 d2 A B Ø
5 4KA1220-1AC01-0AA0 175 158 95 150 150 100 56 73 60 10.8 15.5 125 56 6.5
10 4KA1220-3AC01-0AA0 175 160 124 150 150 100 78 95 75 10.8 15.5 125 78 6.5
12.5 4KA1220-4AC01-0AA0 190 160 124 165 165 60 80 98 75 10.8 15.5 85 80 6.5
15 4KA1220-5AC01-0AA0 225 230 145 190 190 150 73 90 97 10.8 15.5 175 71.5 8.5
20 4KA1220-6AC01-0AA0 225 205 155 190 190 150 95 112 100 10.8 15.5 175 95 8.5
25 4KA1220-7AC01-0AA0 225 205 155 190 190 150 95 112 100 10.8 15.5 175 95 8.5
50 4KA1220-2BC01-0AA0 260 240 208 220 220 150 165 185 116 10.8 15.5 175 165 8.5
75 4KA1220-3BC03-0AA0 310 270 180 265 265 150 132 150 97 10.8 15.5 175 132 10.5
100 4KA1220-4BC03-0AA0 330 270 180 285 285 150 132 155 97 10.8 15.5 175 132 10.5

5.67% Al detuned reactor (all dimensions in mm)


kVAr Type L H W I1 I2 n1 n2 b e d1 d2 A B Ø
5 4KA1420-1AC01-0AA0 175 158 100 150 150 100 61.5 78 62 10.8 15.5 125 58 6.5
10 4KA1420-3AC01-0AA0 190 160 125 165 165 60 78 98 76 10.8 15.5 85 76 6.5
12.5 4KA1420-4AC01-0AA0 175 160 125 150 150 100 82.5 98 76 10.8 15.5 125 78 6.5
15 4KA1420-5AC01-0AA0 225 230 155 190 190 150 73 90 105 10.8 15.5 175 71.5 8.5
20 4KA1420-6AC01-0AA0 225 205 175 190 190 150 97.8 112 115 10.8 15.5 175 95 8.5
25 4KA1420-7AC01-0AA0 240 205 175 205 205 150 98 112 115 10.8 15.5 175 95 8.5
50 4KA1420-2BC01-0AA0 275 238 230 235 235 150 168 185 135 10.8 15.5 175 165 8.5
75 4KA1420-3BC03-0AA0 310 270 180 265 265 150 135 150 99 10.8 15.5 175 132 10.5
100 4KA1420-4BC03-0AA0 310 270 210 265 265 150 160 175 110 10.8 15.5 175 160 10.5

23 Detuned reactor
Smart. Easy. Reliable.
Automatic Power Factor Controller Relay 7UG05 for optimized power need.

7UG05 Automatic power factor correction relay


• Controls the required Power factor
• Manage capacitor bank switching
• Monitors power quality
• Communication capable
• Common relay for three CT and Single CT connection

24 APFC Controllers
Overview

7UG0572-1GT21

• Intelligent 12 stage relay controls

• Confirms to IEC 60947‑5‑1, carry and RoHS


Compliant

• 4 digit 7 segment LED display


• Universal control supply – optimizing the no of variants
• Automatic / Linear / rotational switching of banks
• Power factor settable-0.8 lag -- 0.8 Lead
• Selectable 1A /5A current input

7UG0572-1GT20

• Intelligent 12 stage relay controls

• Confirms to IEC 60947‑5‑1, carry and RoHS


Compliant

• Dual colour Backlight LCD display


• Universal control supply – optimizing the no of variants
• Automatic / Linear / rotational switching of banks
• Power factor settable-0.8 lag – 0.8 Lead
• Selectable 1A /5A current input
• Measurement and display of key parameters viz: Voltage, Current, Power factor, THDI etc
• RS485 Communication MODBUS RTU Protocol

7UG0571-1FT20

• Intelligent 08 stage relay controls

• Confirms to IEC 60947‑5‑1, carry and RoHS


Compliant

• Dual colour Backlight LCD display


• Universal control supply – optimizing the no of variants
• Automatic / Linear / rotational switching of banks
• Power factor settable-0.8 lag -- 0.8 Lead
• Selectable 1A /5A current input
• Measurement and display of key parameters viz: Voltage, Current, Power factor, THDI etc
• RS485 Communication MODBUS RTU Protocol

25 APFC Controllers
APFC relay: Technical data

Type 7UG0571-1FT20 (8 step) / 7UG0572-1GT21


7UG0572-1GT20 (12 step)
Display LCD with dual color backlight 3 line 4 digit & 4 digit 7 segment LED
Programable Scrolling (Auto / Manual / Default) to (No display scrolling, only PF is displyed)
show electrical parameters
INPUT
Rated operational voltage [Ue] 415V
Rated Insulation Voltage [Ui] 600V
Rated Impulse Withstand Voltage [Uimp] 6kV
Overvoltage category III
Control supply AC 90 to 250 VAC
Power consumption 15VA
Frequency HZ 50/60Hz
Mains
L-N AC 30 to 250 VAC
L-L AC 50 to 440 VAC
Current AC 5A AC
Frequency HZ 50/60Hz
Digital input Yes NA
Wiring input 3P 4W / 3P 3W / 2P 2W / 1P 2W
Environment condition
Temperature (operating) 0°C to +60°C
Temperature (storage) -20°C to +60°C
Humidity 0 % to 95 %, without moisture condensation
Pollution Degree PCB: 2
Product: 3
IP Protection IP20
Accuracy
Voltage ± 0.5% of full range NA
Current ± 0.5% of full range NA
Power factor ± 0.01
Frequency ± 0.1% of full range NA
Power ( KW, KVA, KVAr) ± 1% of full range NA
Energy ( KWh, KVAh, KVArh) ± 1% of full range NA
Resolution
Energy (kWh) 0.01k, 0.1k, 1k, 0.01M, 0.1M, 1M NA
Power factor For average PF: 0.01 0.001
For phase PF: 0.001
Voltage, current & power Auto NA
Measurement parameters
Power factor √ √
True RMS voltage √ x
Current √ x
Frequency √ x
Power ( KW, KVA, KVAr) √ x
Energy ( KWh, KVArh) √ x
Temperature √ x

26 APFC Controllers
Setting
Power factor (settable) 0.8 lag --- 0.8 Lead
Reconnection time (sec) Reconnection time is same as discharge time
Step switching time (sec) 1 - 999 (Default is 5 sec)
Discharge time (sec) 1 - 9999 (Default is 180 sec)
No voltage release Instantaneous** (Voltage failure)
90 sec (Voltage restoration)
Control sensitivity 55 -- 100%
Switching Automatic / Linear / rotational
Control Automatic / Manual
CT (programable) Pri: 1A / 5A upto 9999A
Sec: 1A/ 5A
CT Burden 20 mohms
PT (programable) Pri: 100 V - 500KV NA
Sec: 100 V - 500V
Alarm Indication
% THDI 20 -100% / OFF NA
Over Voltage AC (L-N) 50 - 277V
(L-L) 85 - 480V
Under Voltage AC (L-N) 50 - 240V
(L-L) 85 - 415V
No Voltage ON / OFF
Over compensate ON / OFF
Under compensate ON / OFF
CT Polarity error ON / OFF
Step error 20 -- 80% or OFF
Over Temperature 0--100°C, ON /OFF NA
Current absent indication NA CURR
Fan setting ON/OFF NA
Test mode Facility YES
Display
% THDI 20 - 100% NA for LED variant
Harmonics Resolutions Upto 31st Harmonics NA for LED variant
Active Power 4 digit NA for LED variant
Reactive Power 4 digit NA for LED variant
Apparent Power 4 digit NA for LED variant
Voltage 100V - 500kV NA for LED variant
Current 1 - 9999A NA for LED variant
Temperature 0 - 100°C NA for LED variant
Frequency 45 - 65 Hz NA for LED variant
Power factor -1.00 to 1.00
Mechanical
Mounting Panel
Dimension(WxHxD) 144 X 144 X 50 MM
Net weight 635gms (Final packing with accessories) 610gms (Final packing with accessories)
Termination for Control supply, Measuring circuit, output relays
Conductor cross section (solid) sq.mm. 1x (0.75 to 2.5) 1 x (0.75 to 2.5)
2x 0.5 to 2x 1.5 2x 0.5 to 2x 1.5
Conductor cross section 1 x (0.5 to 2.5) 1 x (0.5 to 2.5)
(stranded with end sleeve) sq.mm. 2x (0.5 to 1.5) 2x (0.5 to 1.5)
Tightening torque 0.5 Nm 0.5 Nm
Termination for RS485, T1, T2
Conductor cross section (solid / stranded) 1x 0.5 1x 0.5
Tightening torque 0.4 Nm 0.4 Nm
Output
Relay Contacts NO, one common point max fuse 6A
Ie (AC12 @ 250VAC) 5A* @ 250VAC
Ie (AC15 @ 250VAC) 1A @ 250VAC
Password protection YES
Communication RS 485 & Modbus-RTU communication NA
Standards IEC 60947-5-1
Markings CE & RoHS
* 5A rating is for each relay contact. If multiple relays are getting switched simultaneously, relay rating will be derated to 1.2A @ 250V
** Response time is 3-5 sec

27 APFC Controllers
Dimensions and wiring diagram

Wiring Diagram

3 Phase - 4 Wire 1 Phase - 2 Wire

3 Phase - 3 Wire 2 Phase - 2 Wire

Note: • For N/W selection 2P2W voltage (VLL) applied between V1 & V2 and connect CT for I1 (Do not use V3, N, I2 & I3 terminal)
• For N/W selection 1P2W voltage (VLN) applied between V1 & N and connect CT for I1 (Do not use V2, V3, I2 & I3 terminal)
# Only available in 7UG0571-1FT20 & 7UG0572-1GT20 variants * Not applicable for 7UG0571-1FT20

Dimensional Drawing (mm)

Outline Dimension (in mm) Panel Cutout (in mm)


136.5

Side
144

138

Front bezel
view

144 50 138
5

28 APFC Controllers
3TS Capacitor duty contactors
Overview: The amplitude of these current peaks, also known as “inrush
current peaks”, depends on the following factors:
For more than 125 years, Siemens has been developing
and manufacturing industrial control products. We offer a • The network inductances.
wide product range which caters to fulfill the demand of • The transformer power and short-circuit voltage.
our esteemed customers with satisfactory performance • Type of power factor correction: fixed or automatic.
level and improved reliability. The new range of capacitor • Harmonics present in the system.
duty contactor has been launched to provide a reliable and
economical solution for capacitor switching applications. The in-rush current of such high magnitudes is undesirable
and it is likely to weld main contacts of any standard
Capacitor Duty Contactor contactor. Therefore, contactor for capacitor bank switching
must be designed to withstand:
• Permanent current that can reach 1.5 time the nominal
current of capacitor bank.
• Short but high peak current on pole closing.

Hence, capacitor duty switching device requires careful


selection. It is always recommended to use dedicated
capacitor duty switching contactor for switching capacitor
bank, which optimizes the switchgear cost & enhances the
equipment life.
Siemens 3TS capacitor duty contactor works on mechanical
delatching operating principle, which ensures reliable
switching of capacitors as per AC-6b utilization category.

Delatching operating principle:


The front-mounted block mechanism of the 3TS capacitor
duty contactors ensures:
Range: • early making of the auxiliary contacts “AC” with respect to
• 7kVAr - 50kVAr the main contacts “MC”
• automatic return to the open position of the auxiliary
Features: contacts after the main contacts are closed.
• Delatching operating principle
When the coil is energized, the early making auxiliary
• SIGUT Termination technique contacts connect the capacitor to the network via the set of
• Finger touch proof terminals $ 3 resistors. The damping resistors attenuate the first current
• Compact Dimensions peak and the second inrush current when the main contacts
begin to make. Once the main contacts are in the closed
• DIN / Screw mounting
position, the auxiliary contacts automatically break.
Benefits: When the coil is de-energized, the main contacts break
• Reliable switching of capacitor banks ensuring the breaking of the capacitive current. The contactor
• Ease of wiring (can obviate use of lugs) can then begin a new cycle.
• Operator Safety
• Space saving
• Flexible mounting

Standards:
• IEC 60947-4-1

Approbations:
• CE marking

Operating Principle:
In Low Voltage industrial installations, capacitors are mainly
used for reactive power correction (raising the power factor).
When these capacitors are energized, overcurrents of high
amplitude and high frequencies (3 to 15 kHz) occur during AC = auxiliary contacts MC = main contacts
the transient period (~1 ms).
$ upto 25kVAr

29 Capacitor Duty Contactors


Technical specifications:

Type 3TS11 3TS12 3TS13 3TS14 3TS15 3TS17


Size 1 2 3 3 3 4
Dimensions (H x D x W)
including auxiliary switches HxDxW HxDxW HxDxW HxDxW HxDxW HxDxW
and connecting cables
• Screw-type terminals mm 115 x 125 x 45 115 x 136 x 45 120 x 148 x 55 120 x 148 x 55 120 x 148 x 55 117x177x90
General technical specifications
Conformance to IEC-60947-4-1
Approvals CE
IP20 for Aux IP20 for Aux IP20 for Aux
Degree of protection acc. to IEC 60529 IP IP 20 IP 20 block block block IP 00
IP00 contactor IP00 contactor IP00 contactor
Storage temperature °C -25 to +55
Operating temperature °C -25 to +40
Altitude of site (without technical restrictions) m 2000
Type of mounting DIN / Screw Screw
Main Circuit
Rated insulation voltage Ui V 690
Rated operational voltage Ue V 415 / 440
Rated operational Current Ie
A 9.7 17.4 22.3 27.8 34.8 69.6
(Harmonic & Safety factor excluded)
Impulse withstand voltage Uimp kV 6
Rated frequency Hz 50
Capacitor rating at rated power
(utilization category AC-6b) 415/440 V, kVAr 7 12.5 16 20 25 50
50Hz
Cycles
Max. switching frequency per 180 100
hour
Coil operating range 0.85 to 1.1Us
Auxiliary contacts mounted 1 NO – 2 NO + 2NC
Auxiliary contacts mountable 1NO or 1NC –
Short-circuit protection device for contactors
With Fuse - Operational class gG - A 20 32 50 50 63 125
Type 1 co-ordination (3NA7)
Connecting characteristics
Main conductors Screw terminals

Terminal screw size M3.5 M4 M6


Screw head type Slotted Cheese Head Hex Head
Tightening torque Recom-
N-m 0.8 to 1.4 1 to 1.5 2.5 to 3 4 to 6
mended
Conductor cross-section
Solid mm2 1 x (1 to 2.5) 1 x (2.5 to 6) 1 x (1 to 16)
Finely stranded with end sleeve mm2 1 x (0.75 to 2.5) 1 x (1.5 to 4) 1 x (1.5 to 16)
Finely stranded mm2 - - 1 x (1.5 to 16)
Finely stranded with pin end connector mm2 1 x (0.75 to 2.5) 1 x (1.5 to 4) 1 x (1.5 to 16)
Finely stranded with ring type lug mm2 – 1 x35, 2 x 16
Busbar (max width) mm – 12
Auxiliary conductors
Screw terminals
(built-in auxiliary terminals + coil terminals)
Screw head type Slotted Cheese Head
Tightening torque Recommended N-m 0.8 to 1.4
Conductor cross-section
Solid mm2 2 x (0.5 to 1, 1 to 2.5), 1 x 4
Finely stranded with end sleeve mm2 2 x (0.75 to 2.5)
Finely stranded with pin end connector mm2 2 x (0.75 to 2.5)

30 Capacitor Duty Contactors


Selection and ordering data:
Capacitor duty contactor - 3TS

Capacitor kVAr 415V, Std. pkg.


Built-in aux. contacts Type@ Built-in aux. contacts Type@
3ph, 50Hz (nos.)
7 kVAr 1 NO 3TS1110-0A..5-8K†
12.5 kVAr – 3TS1200-0A..5-8K† 1NO+1NC 3TS1211-0A..5-8K 1
16 kVAr – 3TS1300-0A..5-8K† 1NO+1NC 3TS1311-0A..5-8K 1
20 kVAr – 3TS1400-0A..5-8K† 1NO+1NC 3TS1411-0A..5-8K 1
25 kVAr – 3TS1500-0A..5-8K† 1NO+1NC 3TS1511-0A..5-8K 1
50 kVAr 2 NO + 2 NC 3TS1722-0A..5-8K

3RT26 Capacitor duty contactor Spares for 3TS Contactors

Capacitor Built-in Std. Capacitor Duty


kVAr 415V, Coil voltage aux. Type pkg. Spare coils
3ph, 50Hz contacts (nos.)
24V, 50HZ 3RT2637-1AB03 Contactor Std. pkg.
Description Type*
kVAr (nos.)
75 kVAr 110V, 50HZ 1NO + 1NC 3RT2637-1AF03 1
7 kVAr
230V, 50HZ 3RT2637-1AP03 3TY74030A.. 1
12.5 kVAr
24V, 50HZ 3RT2646-1AB03
16 kVAr
100 kVAr 110V, 50HZ 1NO + 1NC 3RT2646-1AF03 1 AC 50Hz coil
20 kVAr 3TY74430A.. 1
230V, 50HZ 3RT2646-1AP03
25 kVAr
50 kVAr 3TY74630A.. 1

@ AC 50Hz coil code - Please enter coil codes from table * For coil, refer below table
below
For 3TS contactors
For 3TS contactors
Code F0 P0 R0
Code F0 P0 R0
Coil voltage (V) 110 230 415
Coil voltage (V) 110 230 415

† Facility to add one contact block of 1NO / 1NC


Pre-charge resistor + Contact block kit
Auxiliary contact blocks Contactor Std. pkg.
Description Type
kVAr (nos.)
Std.pkg.
For contactor Description Type 12.5 kVAr 3TS9762-0SX15-8K 1
(nos.)
Pre-charge
3TS1110-3TS1500 1NO  3TX4010-2A 10 16 kVAr resistor + 3TS9763-0SX15-8K 1
early making
1NC  3TX4001-2A 10 20 kVAr 3TS9764-0SX15-8K 1
contact block
25 kVAr kit + main 3TS9765-0SX15-8K 1
contacts kit
50 kVAr 3TS9767-0SX15-8K 1

Note: Pre-charge resistor + early making contact block kit +


main contacts should be replaced simultaneously

31 Capacitor Duty Contactors


Mounting details: Terminal drawing:

Frame 1
3TS11 3TS11 3TS12/13/14/15

Frame 2, 3, 4
3TS12 / 13 / 14 / 15 / 17 3TS17

Dimensional drawing:

Dimensional drawing : 7, 12.5, 16, 20, 25 kVAr Dimensional drawing : 50kVAr (3TS1711-0A..5-8K)
(3TS11/12/13/14/1500-0A..5-8K)

Type A B C D F G H J K øE M Term Screw


3TS11 125 74 60 10 115 78 45 60 35 4.8 48 M3.5
3TS12 136 85 70 14.5 115 85 45 75 35 4.8 51 M4
3TS13..15 148 85 63 18 120 103 55 75 45 5 62.5 M4

32 Capacitor Duty Contactors


Selection tables
Standard Values: Selection Tables for Cables, Cable Cross Sections and Fuses
Power Current Section Fuse
kvar A mm2 A
Rated voltage 230 V, 60 Hz
2.5 6.3 1.5 10
5.0 12.6 4.0 25
7.5 18.8 6.0 35
10.0 25.1 10.0 50
12.5 31.4 16.0 50
15.0 37.7 16.0 63
20.0 50.2 25.0 80
25.0 62.8 35.0 100
30.0 75.3 50.0 125
40.0 100.4 70.0 160
50.0 125.5 95.0 200
75.0 188.3 185.0 315
100.0 251.0 2× 120.0 400
125.0 – – –
150.0 – – –
175.0 – – –
200.0 – – –
Rated voltage 400 V, 50 Hz
2.5 3.6 1.5 10
5.0 7.2 2.5 16
7.5 10.8 2.5 16
10.0 14.4 4.0 25
12.5 18.0 6.0 35
15.0 21.6 6.0 35
20.0 28.8 10.0 50
25.0 36.0 16.0 63
30.0 43.2 25.0 80
40.0 57.6 35.0 100
50.0 72.0 50.0 125
75.0 108.3 70.0 160
100.0 144.3 120.0 250
125.0 180.3 185.0 315
150.0 216.5 2× 95.0 350
175.0 252.6 2× 95.0 400
200.0 288.0 2× 120.0 500
Rated voltage 440 V, 60 Hz
2.5 3.3 1.5 10
5.0 6.6 2.5 16
7.5 10.0 2.5 16
10.0 13.2 4.0 25
12.5 16.8 4.0 25
15.0 19.8 6.0 35
20.0 26.4 10.0 50
25.0 33.0 16.0 63
30.0 39.6 25.0 80
40.0 52.8 35.0 100
50.0 66.0 50.0 125
75.0 99.0 70.0 160
100.0 132.0 95.0 200
125.0 165.0 185.0 315
150.0 198.0 2× 95.0 350
175.0 231.0 2× 95.0 400
200.0 264.0 2× 120.0 500
The above mentioned values are guidelines for operation in normal conditions at ambient temperatures up to +35 °C.
Upgrade accordingly if conditions differ, e.g. temperature or hamonics differ. The internal wiring of a capacitor bank is sometimes possible with a
smaller cross section. Various parameters such as temperature inside the cabinet, cable quality, maximum cable insulation temperature, single or multi
core cable, cable length and laying system have to be considered for a proper selection. The local panelbuilder/installer is responsible for a proper
selection of the cable sizes and fuses according to the valid regulations and standards in the specific country where the PFC panels are installed.

33 Selection tables
Standard Values: Selection Tables for Cables, Cable Cross Sections and Fuses
Power Current Section Fuse
kvar A mm2 A
Rated voltage 480 V, 60 Hz
2.5 3.0 1.5 10
5.0 6.0 2.5 16
7.5 9.0 2.5 16
10.0 12.0 4.0 25
12.5 18.0 6.0 35
15.0 21.0 6.0 35
20.0 24.0 10.0 50
25.0 30.0 10.0 50
30.0 36.0 16.0 63
40.0 48.0 25.0 80
50.0 60.0 35.0 100
75.0 90.0 70.0 160
100.0 120.0 95.0 200
125.0 150.0 120.0 250
150.0 180.0 185.0 315
175.0 210.0 2× 95.0 350
200.0 240.0 2× 95.0 400
Rated voltage 525 V, 50 Hz
2.5 2.7 1.5 10
5.0 5.5 1.5 10
7.5 6.9 2.5 16
10.0 11.0 2.5 16
12.5 13.7 4.0 25
15.0 16.5 4.0 25
20.0 22.0 6.0 35
25.0 27.5 10.0 50
30.0 33.0 16.0 63
40.0 44.0 25.0 80
50.0 55.0 35.0 100
75.0 82.5 70.0 160
100.0 110.0 95.0 200
125.0 137.5 95.0 200
150.0 165.0 185.0 300
175.0 193.0 2× 95.0 350
200.0 220.0 2× 95.0 350
Rated voltage 690 V, 50 Hz
2.5 2.1 1.5 10
5.0 4.2 1.5 10
7.5 6.3 1.5 10
10.0 8.4 2.5 16
12.5 10.5 2.5 16
15.0 12.6 4.0 25
20.0 16.7 4.0 25
25.0 20.9 6.0 35
30.0 25.1 10.0 50
40.0 33.5 16.0 63
50.0 41.8 25.0 80
75.0 62.8 50.0 125
100.0 83.7 70.0 160
125.0 105.0 70.0 160
150.0 126.0 95.0 200
175.0 146.0 120.0 250
200.0 167.0 128.5 315
The above mentioned values are guidelines for operation in normal conditions at ambient temperatures up to +35 °C.
Upgrade accordingly if conditions differ, e.g. temperature or hamonics differ. The internal wiring of a capacitor bank is sometimes possible with
a smaller cross section. Various parameters such as temperature inside the cabinet, cable quality, maximum cable insulation temperature, single
or multi core cable, cable length and laying system have to be considered for a proper selection. The local panelbuilder/installer is responsible for
a proper selection of the cable sizes and fuses according to the valid regulations and standards in the specific country where the PFC panels are
installed.

34 Selection tables
Calculation Table for Reactive Power Demand (Qc)
TARGET
cos ϕ = 0.96
cos ϕ ≤ 1
Current
Achievable (TARGET) cos ϕ Qc = Pmot · F (0.96) = … [kvar]
(ACTUAL) cos ϕ Qc
100 · 1.01 = 101.0 kvar
tan ϕ
0.80 0.82 0.85 0.88 0.90 0.92 0.94 0.96 0.98 1.00
Faktor F
3.18 0.30 2.43 2.48 2.56 2.64 2.70 2.75 2.82 2.89 2.98 3.18
2.96 0.32 2.21 2.26 2.34 2.42 2.48 2.53 2.60 2.67 2.76 2.96
2.77 0.34 2.02 2.07 2.15 2.23 2.28 2.34 2.41 2.48 2.56 2.77
2.59 0.36 1.84 1.89 1.97 2.05 2.10 2.17 2.23 2.30 2.39 2.59
2.43 0.38 1.68 1.73 1.81 1.89 1.95 2.01 2.07 2.14 2.23 2.43
2.29 0.40 1.54 1.59 1.67 1.75 1.81 1.87 1.93 2.00 2.09 2.29
2.16 0.42 1.41 1.46 1.54 1.62 1.68 1.73 1.80 1.87 1.96 2.16
2.04 0.44 1.29 1.34 1.42 1.50 1.56 1.61 1.68 1.75 1.84 2.04
1.93 0.46 1.18 1.23 1.31 1.39 1.45 1.50 1.57 1.64 1.73 1.93
1.83 0.48 1.08 1.13 1.21 1.29 1.34 1.40 1.47 1.54 1.62 1.83
1.73 0.50 0.98 1.03 1.11 1.19 1.25 1.31 1.37 1.45 1.63 1.73
1.64 0.52 0.89 0.94 1.02 1.10 1.16 1.22 1.28 1.35 1.44 1.64
1.56 0.54 0.81 0.86 0.94 1.02 1.07 1.13 1.20 1.27 1.36 1.56
1.48 0.56 0.73 0.78 0.86 0.94 1.00 1.05 1.12 1.19 1.28 1.48
1.40 0.58 0.65 0.70 0.78 0.86 0.92 0.98 1.04 1.11 1.20 1.40
1.33 0.60 0.58 0.63 0.71 0.79 0.85 0.91 0.97 1.04 1.13 1.33
1.30 0.61 0.55 0.60 0.68 0.76 0.81 0.87 0.94 1.01 1.10 1.30
1.27 0.62 0.52 0.57 0.65 0.73 0.78 0.84 0.91 0.99 1.06 1.27
1.23 0.63 0.48 0.53 0.61 0.69 0.75 0.81 0.87 0.94 1.03 1.23
1.20 0.64 0.45 0.50 0.58 0.66 0.72 0.77 0.84 0.91 1.00 1.20
1.17 0.65 0.42 0.47 0.55 0.63 0.68 0.74 0.81 0.88 0.97 1.17
1.14 0.66 0.39 0.44 0.52 0.60 0.65 0.71 0.78 0.85 0.94 1.14
1.11 0.67 0.36 0.41 0.49 0.57 0.63 0.68 0.75 0.82 0.90 1.11
1.08 0.68 0.33 0.38 0.46 0.54 0.59 0.65 0.72 0.79 0.88 1.08
1.05 0.69 0.30 0.35 0.43 0.51 0.56 0.62 0.69 0.76 0.85 1.05
1.02 0.70 0.27 0.32 0.40 0.48 0.54 0.59 0.66 0.73 0.82 1.02
0.99 0.71 0.24 0.29 0.37 0.45 0.51 0.57 0.63 0.70 0.79 0.99
0.96 0.72 0.21 0.26 0.34 0.42 0.48 0.54 0.60 0.67 0.76 0.96
0.94 0.73 0.19 0.24 0.32 0.40 0.45 0.51 0.58 0.65 0.73 0.94
0.91 0.74 0.16 0.21 0.29 0.37 0.42 0.48 0.55 0.62 0.71 0.91
0.88 0.75 0.13 0.18 0.26 0.34 0.40 0.46 0.52 0.59 0.68 0.88
0.86 0.76 0.11 0.16 0.24 0.32 0.37 0.43 0.50 0.57 0.65 0.86
0.83 0.77 0.08 0.13 0.21 0.29 0.34 0.40 0.47 0.54 0.63 0.83
0.80 0.78 0.05 0.10 0.18 0.26 0.32 0.38 0.44 0.51 0.60 0.80
0.78 0.79 0.03 0.08 0.16 0.24 0.29 0.35 0.42 0.49 0.57 0.78
0.75 0.80 0.05 0.13 0.21 0.27 0.32 0.39 0.46 0.55 0.75
0.72 0.81 0.10 0.18 0.24 0.30 0.36 0.43 0.52 0.72
0.70 0.82 0.08 0.16 0.21 0.27 0.34 0.41 0.49 0.70
0.67 0.83 0.05 0.13 0.19 0.25 0.31 0.38 0.47 0.67
0.65 0.84 0.03 0.11 0.16 0.22 0.29 0.36 0.44 0.65
0.62 0.85 0.08 0.14 0.19 0.26 0.33 0.42 0.62
0.59 0.86 0.05 0.11 0.17 0.23 0.30 0.39 0.59
0.57 0.87 0.08 0.14 0.21 0.28 0.36 0.57
0.54 0.88 0.06 0.11 0.18 0.25 0.34 0.54
0.51 0.89 0.03 0.09 0.15 0.22 0.31 0.51
0.48 0.90 0.06 0.12 0.19 0.28 0.48
0.46 0.91 0.03 0.10 0.17 0.25 0.46
0.43 0.92 0.07 0.14 0.22 0.43
0.40 0.93 0.04 0.11 0.19 0.40
0.36 0.94 0.07 0.16 0.36
0.33 0.95 0.13 0.33

QC = PA · (tan ϕ1– tan ϕ2) Example:


QC [kvar] = PA · F = active power [kW] · factor “F” Actual motor power P = 100 kW
PA = S · cos ϕ = apparent power · cos ϕ ACTUAL cos ϕ 0.61
tan ϕ1 + ϕ2 according to cos ϕ values ref. table TARGET cos ϕ 0.96
Factor F from table 1.01
Capacitor reactive power QC
QC = 100 · 1.01 = 101.0 kvar

35 Selection tables
Individual PFC for Motors

Approximate values (specified by the German Electricity Association VDEW) for fixed PFC of motors
Capacitor power rating Capacitor power rating Capacitor power rating
Motor nominal rating
(1500 r.p.m.*) (1000 r.p.m.*) (750 r.p.m.*)

kW kvar kvar kvar

1 … 1.9 0.5 0.5 0.6

2 … 2.9 1 1.1 1.2

3 … 3.9 1.5 1.6 1.7

4 … 4.9 2 2.1 2.3

5 … 5.9 2.5 2.6 2.9

6 … 7.9 3 3.2 3.5

8 … 10.9 4 4.2 4.6

11 … 13.9 5 5.3 5.8

14 … 17.9 6 6.3 6.9

18 … 21.9 7.5 8.0 8.6

22 … 29.9 10 10.5 11.5

30 … 39.9 approx. 40% of the motor power

40 and above approx. 35% of the motor power

*r.p.m.: revolutions per minute

The capacitor output should be approx. 90% of the apparent oscillating weight and still continues to rotate after switching
power of the motor when idle. off.
This means a power factor of 0.9% at full load and 0.95 to The capacitor placed in parallel may act as generator for
0.98 during idling. Important: The capacitor output must the motor which will cause serious overvoltages. The
not be rated too high for individual compensated machines consequence could be heavy damage to the capacitor as well
where the capacitor is directly connected with the motor as to the motor.
clamp. This especially applies when the machine has a big

36 Selection tables
Individual PFC for Transformers

Standard values for transformer power factor correction


Rated apparent power Rated capacitor power Rated capacitor power
of transformer for oil immersed transformers for cast resin transformers

kVA kvar kvar

10 1.0 1.5

20 2.0 1.7

50 4.0 2.0

75 5.0 2.5

100 5.0 2.5

160 7.0 4.0

200 7.5 5.0

250 8.0 7.5

315 10.0 8.0

400 12.5 8.5

500 15.0 10.0

630 17.5 12.5

800 20.0 15.0

1000 25.0 16.7

1250 30.0 20.0

1600 35.0 22.0

2000 40.0 25.0

2500 50.0 35.0

3150 60.0 50.0

For an exact calculation of the right capacitor value, following There are regional differences in the guidelines of power
formula can be used: suppliers concerning the admissible size of capacitors directly
connected with a transformer. Therefore a consultation

AN with the respective power supplier is recommended before
QC = I0% ·
100 installation of a compensation bank. Modern transformers

have laminations which only need low capacity to reverse the
Qc = needed capacitor (kvar) magnetism. In case the capacitor output is too high, stress
I0% = magnetising current of the transformer (AS%) increase may occur during idling.
AN = apparent rated power of the transformer in kVA

37 Selection tables
Notes

38
Notes

39
Your partners
Sales offices:
Ahmedabad Chennai Jaipur Mumbai
3rd Floor, Prerna Arbour 4th Floor, ETA Mount Central International Business Center, K14 First Floor Business Centre-1
Girish Coldrinks Cross Roads, Navrangpura Seethakathi Business Centre, Mount Road Ashok Marg, Ashok Nagar, C Scheme Thane Belapur Road, Thane - 400 601
Ahmedabad - 380 009 Chennai - 600006 Jaipur - 302001 ( : +91 22 39663000
( : +91 79 30927600 ( : +91 44 30474000 ( : +91 141 5152108 Fax: +91 22 39663721
Fax: +91 79 30927699 Fax: +91 44 30474080 Fax: +91 141 2370482
Nagpur
Baroda Coimbatore Jamshedpur 4th Floor, Land Mark Building
Ground Floor, Urja Bhavan 1st Floor, “Senthil Towers”, 1078, Avinashi Road “Roshan Tower”, Main Road, Bistupur (2nd Floor) Wardha Road, Ramdas Peth
Opp.Makarpura Railway Station, Maneja Coimbatore - 641018 Jamshedpur - 831001 Nagpur - 440 010
Vadodara - 390 013 ( : +91 422 3076300 ( : +91 657 6682201 ( : +91 712 3093000
( : +91 265 3957701 Fax: +91 422 3076310 Fax: +91 712 3093111
Kolkata
Fax: +91 265 3039190
Gurgaon 3rd Floor, 43, Shanti Palli Pune
Bengaluru Plot No. - 78, Tower - B Rashbihari Bypass Connector Tower B/701-705, ICC Trade Tower
1st Floor, Jyoti Mahal, No. 49, St. Marks Rd. Jagatjit Industries Building (JIL) Kolkata - 700042, India 403A, Senapati Bapat Road
Bengaluru - 560 001 Opposite SBI Academy, Sector-18 ( : +91 33 30939000 Pune - 411016
( : +91 80 33422000 Gurgaon - 122015 Fax: +91 33 30939010 ( : +91 20 30466000
Fax: +91 80 33424131 ( : +91 124 2842000, 3810200 Fax: +91 20 30466060
Lucknow
Bhubaneswar Hyderabad 510-511, 5th Floor, Shalimar Titanium Vishakhapatnam
Unit: 1102 & 1103, DLF Cyber City 5-9-19, 4th & 5th Floor, Laxmi Narasinh Estate Plot No. TC.G-1/1, Vibhuti Khand 2nd Floor, 30-8-47, Lakshmi Narasimha Towers
Chandaka Industrial Estate, Patia, Bhubaneswar Opp. Secretariat Road, Saifabad Gomti Nagar, Lucknow Banu Street, Daba Gardens
Odisha - 751024 Hyderabad - 500 004 Uttar Pradesh 226010 Visakhapatnam - 530 020
( : +91 40 30922500 ( : +91 522 4031039 Andhra Pradesh
Chandigarh
Fax: +91 40 30923145 ( : +91 891 3050200
SCO 188/191, 3rd Floor, Sector-17 C
Fax: +91 891 3050222
Chandigarh - 160 017
( : +91 172 4690300
Fax: +91 172 4690399

Territory managers:
Agra Haridwar Maraimalainagar Renukoot
F7B, ACR Desire Appartment Flat No. 204, Shiv Asthaly Appartment No.11, Ambedkar Street, SRS Buildings, Upstairs Raga Vijay Gupta Bhawan, Swami Vivekanand Colony
Near Kargil Petrol Pump, Sikandra Purshotyam Vihar, Kankhal, Haridwar - 249408 Dental Clinic, Potheri, Chennai - 603203 Murdhawa, Renukoot - 231217, U.P.
Agra - 282007, U.P. Mobile: +91 9889384222 Mobile: +91 9840392926 Mobile: +91 9984500021
Mobile: +91 7665590333 E-mail: [email protected] E-mail: [email protected] E-mail: [email protected]
E-mail: [email protected]
Hospet Meerut Rourkela
Aurangabad #727, Lakshmi Narasimha Nilaya D-205, Ansal Courtyard, Roorkee Bypass D/7, Gafoor Colony, Ground Floor
Mobile: +91 9673333024 Near Surbhi Kalyana Mantapa, Amaravathi Modipuram, Meerut - 250110, UP Near LIC Office, Udit Nagar
E-mail: [email protected] Hospet - 583203 Mobile: +91 7619047999 Rourkela - 769012, Odisha
Mobile: +91 9741114877 E-mail: [email protected] Mobile: +91 9776967773
Belgavi
E-mail: [email protected] E-mail: [email protected]
Flat no-201, 2nd Floor, Harimanor Apartment Mehsana
1st Cross- Bhagya Nagar, Angol Extension, Belgavi Hosur Mr. Prabhakaran Mudaliar Rudrapur
Karnataka 590006 Plot No. 12 Vishnu Anandam Galaxy Mobile: +91 9724753579 Shanti Vihar Colony, Chatarpur Road
Tel.: +91 0831 2495156 Chittanapalli Nallur Village, Hosur - 635109 E-mail: [email protected] Oppsoite – Dr. Pandey Hospital
Mobile: +91 9740277991 Mobile: +91 8971200266 Rudrapur - 263153, Uttarakhand
Mysore
E-mail: [email protected] E-mail: [email protected] Mobile: +91 9839174578
No. 980, 4th Cross, 6th Main
Mobile: +91 8105254395 E-mail: [email protected]
Hubli Bannimantap B layout, SS Nagar
E-mail: [email protected]
Plot No. 8, Abhi Nilay, Manjunath Nagar Mysore - 570015 Salem
Bharuch Gokul Road, Hubli - 30, Karnataka Mobile: +91 9611311645 Rajagiragham, Lumbini Illam, No. 20
Gold B, 804, Samruddhi Residency Mobile: +91 9945961052 E-mail: [email protected] Palaniappa Nagar Hasthampatti, Salem - 636007
Opp. Zadeshwar Bus Stop, Zadeshwar Road E-mail: [email protected] Mobile: +91 8754922245
Naidupeta
Bharuch - 392011 E-mail: [email protected]
Jalandhar Door No. 3-3-140, Raghavaiahpeta
Mobile: +91 9429037805
H.No. 140, Ground Floor, Defence Colony Sriharikota Road, Opp to Race School Siliguri
E-mail: [email protected]
Jalandhar, Punjab - 144001 Sullurpeta Town & Mandal, SPSR Nellore District C/o Ratan Saha
Bhilai Mobile: +91 8427979870 AP - 524123 Ground Floor, Raja Rammohan Roy Road
C/o. Mr. Anil Dhusia E-mail: [email protected] Mobile: +91 9840255185 Beside Babubhai Atta Mill, Hakimpara
Qtr No. 4A, Street 33, Sector - 4 E-mail: [email protected] Siliguri - 734001, West Bengal
Jodhpur
Bhilai - 490001 Mobile: +91 9932276294
A-240, Shastri Nagar, Jodhpur - 342003 Nashik
Mobile: +91 7869922211 E-mail: [email protected]
Mobile: +91 9929110493 Flat No 402, ”D” Wing, Hari Shrushti
E-mail: [email protected]
E-mail: [email protected] Near Jogging Track, Opposite WNS, Indira Nagar Sonepat
Bhopal Nashik - 422009 H.No. 1103, 1st Floor, Sector - 14
Kanpur
Flat-102, Tower – Jasmine Nikhil Nestles Mobile: +91 9822193204 Sonepat, Haryana - 131001
Flat No. 702, Pushpi Apartments
Jatkheri Hoshangabad Road E-mail: [email protected] Mobile: +91 9855526122
Sharda Nagar, Kanpur - 208025, Uttar Pradesh
Bhopal, MP - 462026 E-mail: [email protected]
Mobile: +91 8802011478 Neemrana
Mobile: +91 9711007466
E-mail: [email protected] Flat No. F111, Anantraj Aashray Apartment Sriperumbudur
E-mail: [email protected]
Plot No. 236, Japanese Zone Villa No. 97, Casa Grande Futura, Chengalpet Road
Khopoli
Boisar Neemrana - 301705, Dist.- Alwar Sriperumbudur, Kanchipuram Dist - 602105
Samarthanagar Co-op Hsg. Soc.
Flat No. A-21, Sai Sagar CHS, MAHADA Colony Mobile: +91 9650481919 Mobile: +91 9791045280
Mogalwadi Road, Khopoli
Chitrayalaya Road, Boisar - 401506 E-mail: [email protected] E-mail: [email protected]
Taluka - Khalapur, Dist. Raigad - 410 203
Mobile: +91 9819231892
Mobile: +91 9867748975 Patna Surat
E-mail: [email protected]
E-mail: [email protected] A-53, 5th Floor, Krishna Apartment, Boring Road A 604, Stuti Universal, Green City Road
Cochin Patna - 800001 Pal-Adajan, Surat - 395009, Gujarat
Kolhapur
Jomer Symphony, 33/2317, 5th Floor Mobile: +91 9641574289 Mobile: +91 9712445504
RS No. 84-1, Pinac Prasad, Flat No. A-35
Chalikkavattom, Ponnurunni North, Vytilla E-mail: [email protected] E-mail: [email protected]
New Palace Road, Kolhapur - 416006
Kochi - 682019
Mobile: +91 9850836839 Pondicherry Trichy
Tel.: +91 4028611/22
E-mail: [email protected] R.A.M. Paradise, II Floor, No.4, 2nd Cross Flat No.102, `B’ Block, 2nd Floor, Vignesh Empire
Mobile: +91 9656690111
Kamban Nagar, Reddiarpalayam Apartments, Salai Road, Woraiyur, Trichy - 620003
E-mail: [email protected] Kota
Puducherry - 605010 Mobile: +91 8056025127
406, Manglayatan Appartment
Durgapur Mobile: +91 9176609374 E-mail: [email protected]
Near Jain Temple, Bhimganj Mandi
6/15, Bengal Ambuja E-mail: [email protected]
Kota - 324002 Trissur
(Near Durgapur Cinema Hall), Citi Centre
Mobile: +91 9828419111 Raipur Plot No. 12, Cherakekaran House, Unity Nagar
Durgapur - 713216
E-mail: [email protected] 103 Risabh Regency, Near Shri Medishine Hospital Kuriachira P.O, Thrissur, Kerala - 680006
Mobile: +91 9051020207
New Rajendra Nagar, Raipur (CG) - 492001 Mobile: +91 9947957839
E-mail: [email protected] Ludhiana
Mobile: +91 9425601849 E-mail: [email protected]
H.No. 1858, First Floor, Sector - 32 A
Gandhidham E-mail: [email protected]
Ludhiana - 141008, Punjab Udaipur
Plot No. 299, Ward 3A, Adipur
Mobile: +91 9876047929 Rajkot A-39, New Ahinsapuri, Fatehpura
Gandhidham - 370205, Gujarat
E-mail: [email protected] 301, Snowhill Apartment Udaipur - 313004
Mobile: +91 9099010323
Near Golden Supermarket, Amin Marg Mobile: +91 8696222212
E-mail: [email protected] Ludhiana
Rajkot - 360007, Gujarat E-mail: [email protected]
R-115, Near DAV School
Gorakhpur Mobile: +91 9909904993
Sarabha Nagar Ext Ph-2, Pakhowal Road Vapi
Flat No. 3B, 3rd Floor, Plot No. 298 E-mail: [email protected]
Ludhiana, Punjab - 142022 Flat No. 302, 3rd Floor, Samrajya-IV
Near Sawatri Hosiptal, Purdilpur, Vijay Chowk
Mobile: +91 9888484066 Ranchi Royal Residency, Gokul Vihar Township
Gorakhpur - 273001, UP
E-mail: [email protected] Flat No. A-101, 1st Floor, Sundaram Apartment Charwada Road, Taluka - Pardi, Dist. Valsad
Mobile: +91 917800960310
Kilburn Colony, Hinoo, Ranchi Vapi - 396195
E-mail: [email protected] Madurai
Jharkhand - 834002 Mobile: +91 9825147957
Anirudh block, F-Top 3, Vasudhara Apartment
Guwahati Mobile: +91 8294052647 E-mail: [email protected]
84, TPK Main Road, Andalpuram
Shivalaya Housing Society, Flat No. B3A E-mail: [email protected]
Madurai - 625 003, Tamil Nadu Vijayawada
Bylane 4, Joymati Nagar, Adabari, Pandu
Mobile: +91 9894617776 Mobile: +91 9948664228
Guwahati - 781012
E-mail: [email protected] E-mail: [email protected]
Mobile: +91-9864110684
E-mail: [email protected]

Siemens Ltd. Order No.: 109556591


Digital Factory PQS _CC96112018
Control Products
R&D Technology Centre
Kalwa Works, Thane Belapur Road, Thane - 400 601
Fax: +91 22 33265627
Product upgradation is a continuous
For more information contact toll free 1800 209 1800 process. Hence, data in this catalog is
E-mail: [email protected] Customer Care Toll free no. subject to change without prior notice. For
1800 209 0987 the latest information, please get in touch
www.siemens.co.in Email: [email protected] with our Sales Offices.

You might also like