67% found this document useful (3 votes)
896 views271 pages

Technical Specification For 11 KV Packaged Substation

Uploaded by

Peter pan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
896 views271 pages

Technical Specification For 11 KV Packaged Substation

Uploaded by

Peter pan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 271

SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Technical Specification for


11 kV Packaged Substation
(With 250 / 400 / 630/ 1000 kVA Distribution Transformer -
Hermetically Sealed Oil Type / Dry Type Transformer)
Specification no – SP-PSSC-38-R7

Prepared by Reviewed by Approved by


Rev Date
Name Sign Name Sign Name Sign
Rohit Amit K
R7 23/04/2020
Patil Tomar Sheshadri

Page 1 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Index
1.0 Scope .................................................................................................................. 7
2.0 Codes & standards.............................................................................................. 7
3.0 Electrical Distribution System Data ..................................................................... 8
4.0 PSS Configuration............................................................................................... 9
5.0 11 kV Ring Main Unit ........................................................................................ 11
6.0 11KV XLPE Cable & termination kit .................................................................. 21
7.0 Oil Type Sealed Distribution Transformer ......................................................... 22
8.0 Dry Type Transformer (1000KVA/ 630KVA/ 400KVA/250 KVA) ....................... 31
9.0 Low Voltage Bus bar system ............................................................................. 39
10.0 Low voltage switchgear, ACB, MCCB & Fuses ................................................. 39
11.0 Automatic Power Factor Correction system ...................................................... 41
12.0 Energy Meter Box ............................................................................................. 43
13.0 Enclosure for packaged substation ................................................................... 44
14.0 Other Provisions: Earthing, Illumination, Hooter & Smoke Detector.................. 46
15.0 Labels & painting............................................................................................... 46
16.0 Approved makes ............................................................................................... 47
17.0 Quality assurance ............................................................................................. 48
18.0 Inspection & testing ........................................................................................... 48
19.0 Shipping, Handling and Site support ................................................................. 51
20.0 Deviations ......................................................................................................... 52
21.0 Drawings Submission ........................................................................................ 52
Annexure A Service Conditions ......................................................................................... 53
Annexure B Technical Specification for transformer oil ..................................................... 54
Annexure C Guaranteed Technical Particulars (Data by Supplier) ..................................... 55
Annexure D CRGO & Testing Points [R7] .......................................................................... 75
Annexure E Recommended spares (Data by supplier) ....................................................... 76
Annexure F BOM for 250 kVA PSS [R7]............................................................................. 77

Page 2 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Record of Revision
Revision Item / clause Approved
Nature of Change/Clause Descriptions
No no. By
R3 4.2.13, 14.24 Added- 02 no’s Smoke detectors for each compartment DS

R3 4.2.15 Fire extinguisher position is added. DS


Anti-theft hinges are changed to Internal anti-theft hinges with
R3 5.2.5 DS
opening angle of 120 deg. minimum.
R3 5.2.6 Added – Operating Handle support DS
Bus bar short time withstand capacity changed to 20kA for 3
R3 5.2.15.2 DS
sec
R3 5.2.18 Routing of control / auxiliary wiring is added DS
Added – Avoid any type of Gaps or holes on the cable
R3 5.2.24.1 DS
termination chamber wall.
R3 5.2.24.2,3 Added – internal arc rating DS

R3 5.3.3 Separate ON/OFF switching for each motor is added DS

R3 5.3.9 LBS short time withstand capacity revised to 20kA for 3 sec DS

R3 5.3.10 LBS fault making capacity revised to 50kA peak DS


Mechanism endurance class M1 and Electrical Endurance
R3 5.3.11 DS
class E3 specified
Minimum no. of operations at rated fault current specified –
R3 5.3.12 DS
Electrical endurance class E3
R3 5.4.2 CB arc interruption medium only in Vacuum bottle DS

R3 5.4.4 Added – Protective flap on Emergency PB DS

R3 5.4.6 20kA short time withstand capacity specified DS


Mechanical – M1 & Electrical-E2 endurance class specified
R3 5.4.7 DS
for circuit breaker module
R3 5.4.8 CB fault making capacity revised to 50kAspecified DS

R3 5.4.9 CB fault breaking capacity revised to 20kA DS


Electrical Endurance – Class E2 specified for CB at fault
R3 5.4.10 DS
current
R3 5.4.12 Protection CT type specified- cast resin ring type DS
No load mechanical endurance class M0 specified for earth
R3 5.5.7 DS
switch
R3 5.5.8 Making capacity endurance class E2 specified DS
Added – Prevent electrical operation if handle is inserted for
R3 5.7.5.1 DS
manual operation
Added – Supply to the motor shall be disconnected after
R3 5.7.5.2 DS
certain time period if LBS fails to operate.

Page 3 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

R3 5.9.0 Sticker type mimic diagram non acceptance specified DS


5.9.2.5,
R3 7.3.1.5, Added – Ref. IS / IEC No. on name plate DS
7.19.1.5, 14.2
6.8, 7.3.8.1, HV side bushings of transformer- Epoxy cast, 630 A, Interface
R3
8.3.4.7 type ‘C’
Delta connection leads for Oil type transformer are defined to
R3 7.2.2.6.5 DS
be with flexible cable connection
7.3.10.4, 5
Accuracy class and VA rating of the LTCT changed to 0.5s
R3 and 8.3.5.3 DS
and 5 VA respectively.
and 4
R3 8.5 Control / Auxiliary cables are changed to FRLS. DS

R3 13.23 Specified – Internal arc classification DS


Name plate materials are defined to be of SS material
R3 15.1.1, 15.2 DS
including BSES insignia and danger plate.
Number of outgoing feeders specified
Type I- 07 No’s
R3 4.6, 9.2.0 DS
Type II- 05 No’s
Type III- 03 No’s

R3 4.2.2, 5.1.1 Requirement of 4 way RMU has been added for PSS type – I DS

R4 2 IS 1180(2014) added KKA

R4 7.2.1 Rating 990KVA changed to 1000KVA as per IS 1180 (2014) KKA

R4 7.2.4 Impedance of 400KVA & 630KVA changed 4.5 % KKA

7.2.5.1 & Total losses at 50% & 100% load updated as per IS
R4 KKA
7.2.5.2 1180(2014)
Flux density at 10% over excitation changed to 12.5% over
R4 7.2.8 KKA
excitation

R4 7.2.10 Tapping range changed to +5% to -10% KKA

R4 7.3.5.2 Core material M4 to M3 KKA

R4 7.3.11.1 Range /Step changed to +5% to -10% in step of 2.5% KKA

8.3.1.2 & Core material grade changed to M4 to M3 & Max Lamination


R4 KKA
8.3.1.3 Thickness changed .27mm to .23mm
8.3.2.1 & Winding material changed Electolytic ALuminum and Max
R4 KKA
8.3.2.2 Current density 1.5A/Sqmm
Total losses at 50% & 100% load changed to Energy
7.2.5.1 &
R5 Efficiency level 1 from Energy Efficiency level 3 as per IS KKA
7.2.5.2
1180(2014)

Page 4 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

10.2.2 &
R6 MCCB Specifications revised AT/VP
10.2.10-13

R6 7.2.5 Max losses revised AT/VP

R6 13 Inspection expenses added AT/VP

R7 4.0 PSS Configuration-added PSS type –IV AT/KS

R7 9.0 Low Voltage Bus bar system-Bus bar rating of PSS-IV added AT/KS

R7 10.0 Low Voltage switchgear, ACB,MCCB & fuses added AT/KS

R7 13 Enclosure for package substation modified AT/KS

R7 16 Approved Makes list added AT/KS

R7 Annexure C GTP added AT/KS

R7 Annexure F BOM for 250 kVA PSS added AT/KS

R7 5.1.0 RMU Configuration clarified AT/KS

RMU panel construction –GI sheet added, sheet thickness


R7 5.2.0 AT/KS
specified from 2 to 2.5 mm.

R7 5.3.0 Load break switch / Isolator (LBS)-elaborated AT/KS

R7 5.4.0 Circuit Breaker-parameters specified AT/KS

R7 5.5.0 Earth switch-three position concept added. AT/KS

R7 5.7.0 RMU operation interlocks- mechanical interlock mentioned AT/KS

R7 5.8.0 Indication and signals modified AT/KS

R7 5.10.0 Quality assurance-added AT/KS

R7 5.11.0 Inspection and testing –specified AT/KS

R7
5.13.0 Special Technical requirement-added AT/KS

Page 5 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

R7 5.14.0 Make List of RMU's Accessories-fixed and added AT/KS

R7 AT/KS
7.2.4 Impedance at 75 deg C for 250 KVA added

R7 AT/KS
7.2.5 Losses at 75 deg C updated and 250 KVA added

R7 AT/KS
7.2.8 Flux density at rated conditions

R7 7.3.5.3 AT/KS
Core Design Features-Type of core added
8.3.1.6
R7 AT/KS
7.3.6.5 Winding Design features-Type of windind added

R7 7.3.10.7 AT/KS
CT ratio for 250 KVA added
8.3.5.6
R7 AT/KS
7.3.11.4 Rated Current for tap Switch for 250 KVA added

R7 8.1.13 AT/KS
8.1.14 E2C2F1 Certification for dry Type DT added
8.1.15
R7 AT/KS
8.2.5 Temperature for losses revised and 250 KVA added

R7 8.2.7 AT/KS
Flux density-maximum value at overfluxing revised
8.3.1.5
R7 AT/KS
8.3.1.4 Design Flux Density at rated conditions at principal tap

R7 AT/KS
18.1 Type test and special test details for transformer added

R7 AT/KS
18.3.2.2 IR value revised

R7 Degree of ingress protection against solids & water for AT/KS


13.14
transformer compartment revised
R7 Approved makes revised AT/KS
16.0

R7 Properties of transformer oil revised AT/KS


Annexure B

R7 CRGO & Testing Points added AT/KS


Annexure D

Page 6 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

1.0 Scope

i. Design, manufacture, testing at manufacturer works before dispatch, packing, and delivery
of Packaged Substation (PSS) as per this specification and supply of commissioning
spares.
ii. Supply of all installation/commissioning accessories for PSS.
iii. Submission of documentation of PSS.
iv. Supervision of testing & commissioning of PSS at site.

2.0 Codes & standards

Materials, equipment and methods used in the manufacture of 11kV Packaged Substation
shall conform to the latest edition of following –
Standard Title
Indian Electricity Rules With latest amendments
Indian electricity act IE act 2003
CBIP manual on transformers
IEC 60076 Power transformers
IEC:60616 Terminal and Tapping Markings for Power Transformers
IEC:60726 Dry-Type Power Transformers
IEC: 60529 Degrees of Protection Provided by Enclosures (IP Code).
IEC:60905 Loading Guide for Dry-Type Power Transformers
IEC 60694 Specification for high voltage switchgear
IEC 60439-1 Low voltage switchgear & control gear assemblies
IEC 60529 Degree of enclosures provided by enclosures
IEC 60664-1 Insulation coordination for low voltage systems
Degree of protection provided by enclosure against mechanical
IEC 62262
shocks
IEC 62271-202 High voltage switchgear & control gear - prefabricated substation
IEC 60044 Instrument transformers - Current & voltage transformers
IEC 60225 Electrical relays
IEC 60625 High voltage switches
IEC 60502 Power cables
IEC 60947-2 Low-voltage switchgear and control gear : Circuit-breakers
Outdoor Type Oil Immersed Distribution Transformers Up to
IS 1180
and Including 2500 kVA, 33kVSpecification [R4]
IS 2026 Power transformers
IS 11171 Dry type transformers

Page 7 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

IS 6600 Loading of power transformers


IS 13947 Low voltage switchgear & control gear
IS 2099 Bushings for voltages above 1000v
IS 3156 Voltage transformers
IS 2705 Current transformers
IS 1554 PVC cables
IS 7098 XLPE cables
IS 2629 Recommended Practice for Hot-Dip Galvanizing of Iron and Steel
IS 4759 Hot-dip zinc coatings on structural steel and other allied products
IS 13585 Shunt capacitors
IS 13340 Shunt capacitors
IS 3043 Code of practice for Earthing
IS 335-2018 Insulating oils
IS 8130 Conductors for insulated cables
IS 5 Ready mixed paints
IS 9920 part 1,3 & 4 High voltage switches above rated voltage 1kv
IS 13118 General requirements of circuit breakers above rated voltage 1kv
IEC 60694 Specification for high voltage switchgear
IEC 60298 AC metal enclosed switchgear
IEC 60694 Specification for high voltage switchgear
IEC 60056 High voltage alternating current circuit breakers
IEC 60265 part 1 High voltage switches

In the event of direct conflict between various order documents, the precedence of authority of
documents shall be as follows -
i. Guaranteed Technical Particulars (GTP)
ii. Specification including applicable codes & standards
iii. Approved Vendor Drawings
iv. Other documents

3.0 Electrical Distribution System Data

3.1.1 HT supply System 3 phase AC, 3 wire


3.1.2 Voltage 11000 volt ±10%
3.1.3 Frequency 50 Hz ± 5%
3.1.4 Fault level 350MVA – 18.5kA
3.1.5 System neutral Earthed at upstream 11kV source

Page 8 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

3.2.1 LT supply system 3 phase AC, 4 wire


3.2.2 Rated voltage 415V +/-10%
3.2.3 Rated frequency 50 Hz ± 5%
3.2.4 Fault level 35MVA – 50kA

4.0 PSS Configuration

4.1 PSS Type On the basis of transformer rating


With 1000kVA oil filled transformer / 1000KVA cast
4.1.1 PSS Type – I
resin transformer
With 630kVA oil filled transformer / 630KVA cast resin
4.1.2 PSS Type – II
transformer
With 400kVA oil filled transformer / 400KVA cast resin
4.1.3 PSS Type – III
transformer
With 250kVA oil filled transformer / 250KVA cast resin
4.1.4 PSS Type – IV
transformer [R7]

4.1.4 Transformer type As per enquiry

4.2 Major Components For all PSS Types


Metallic painted GI enclosure with steel base frame for
4.2.1 Enclosure
overall package
4.2.2 11kV Ring main unit

1. The 3 Way with 02 nos. load break switches (LBS)


+ 01 no. circuit breaker (CB). Or
4.2.2.1 PSS Type – I 2. The 4 Way with 02 nos. Load break switches (LBS)
+ 02 nos. Circuit breaker (CB).[R3]

The 3 Way with 02 nos. load break switches (LBS) +


4.2.2.2 PSS Type – II , III & IV
01 no. circuit breaker (CB).

11kV XLPE Aluminium cable


For CB feeder termination & transformer side
4.2.3 with termination kit along with
termination.
cold applied boots

4.2.4 Low voltage bus bar system Insulated /sleeved with epoxy insulators

Page 9 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Low voltage system 1600A ACB incomer and 07 nos. 400A MCCB
4.2.5
configuration for PSS type-I (utilization category- B) as outgoing.
1600A ACB incomer and 05 nos. 400A MCCB
Low voltage system (utilization category- B) as outgoing. Provisions shall
4.2.6
configuration for PSS type-II also be made in LT panel to increase LT outgoing by
02 no’s by adding MCCB’s in future.
1250A ACB incomer and 03 nos. 400A MCCB
Low voltage system (utilization category- B) as outgoing. Provisions shall
4.2.7
configuration for PSS type-III also be made in LT panel to increase LT outgoing by
02 no’s by adding MCCB’s in future.

Low voltage system 400A ACB incomer and 02 nos. 250A MCCB
4.2.8
configuration for PSS type-IV (utilization category- B) as outgoing. [R7]

300kVAR APFC system with control relay & 630amp


4.2.9 APFC system for PSS type-I
incomer MCCB (utilization category- B)
200kVAR APFC system with control relay & 630amp
4.2.10 APFC system for PSS type-II
incomer MCCB (utilization category- B)
200kVAR APFC system with control relay & 630amp
4.2.11 APFC system for PSS type-III
incomer MCCB (utilization category- B)
APFC system for PSS type-
4.2.12 Not Required [R7]
IV
To be provided on transformer LT side along with
4.2.13 Energy meter box
wiring.
300D x 600W x 900H (mm) space to be provided in
4.2.14 Space for customer FRTU
HV or LV compartment.
Minimum 02 nos. in each LT, HT and Transformer
4.2.15 Smoke detectors compartment. These detectors shall be connected to
local controller / alarm module. [R3].
Hooter with automatic timer
4.2.16 For operator alarm in case of PSS door open position
reset
2Kg CO2 Type shall be placed in HT Compartment
4.2.17 Fire Extinguisher
[R3].
Substation internal cabling, lighting & earthing system
4.2.18 Other requirements along with required hardware, gaskets, gland plates
etc.
3 nos. of fire ball require in each compartment of all
4.2.19 Fire ball
types of PSS [R7]
Cable sealing compound (Roxtec or any other make)
4.2.20 Cable Sealing compound require in LT & HT compartment as per cable size
[R7]

Page 10 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

5.0 11 kV Ring Main Unit

5.1.0 RMU Configuration


5.1.1 RMU Configuration
1. Two Load break switches (LBS) + one transformer
circuit breaker (TCB) or
2. Two Load break switches (LBS) + two transformer
5.1.1.1 PSS Type – I
circuit breaker (TCB). [R3]
Selection between the above configurations shall
depend upon the purchaser’s requirement.
The 3 Way with 02 nos. load break switches (LBS) +
5.1.1.2 PSS Type – II, III & IV {R7}
01 no. circuit breaker (CB).
5.1.2 Extensibility Non extensible type
Load break switch, Circuit
5.1.3 breaker & earth switch in All shall be non draw out type, fixed position
RMU panel
5.1.4 Insulation Medium
5.1.4.1 For panel SF6 gas or Dry air in sealed metallic tank
SF6 gas or Vacuum type (with disconnector & earth
5.1.4.2 For Breakers
switch)
5.1.4.3 For load break switches SF6 gas or Vacuum type (With Earth Switch)

Arc interruption chamber for


Arc interruption chamber of breakers shall be
5.1.5 separate from the main insulated tank. (Desirable
breaker
feature)
Maximum dimensions of 3
3 Way-1250 mm(W) X 800 mm (D) X 2000 mm (H)
Way ( 2LBS+1VCB) RMU
5.1.6 4 Way- dimension of 3 way+ one VCB compartment
and for 4
shall be added
Way(2LBS+2VCB)[R7]
5.2.0 RMU Panel Construction
CRCA/ GI Metal enclosed, framed,
5.2.1 Panel type
Compartmentalized panel construction [R7]
Indoor and outdoor, non air conditioned environment
5.2.2 Service Location
[R7]
5.2.3 Mounting Free Standing

5.2.4 Overall Enclosure Protection IP54X minimum, vermin proof [R7]

Front access with internal anti theft hinge


5.2.5 Doors arrangement with minimum opening angle of 120º
[R3], minimum three hinges (desirable)
Bolted for rear access, with handles. Support for
handle shall be provided at suitable place on RMU
5.2.6 Covers
body. All the accessible bolts / screws shall be vandal
proof stainless steel (except termination bolt, washer

Page 11 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

and reducer which is brass). One set of required


Special tools per RMU (if any) shall be in the scope of
supply. [R7]
CRCA/GI Metal enclosed, framed, Compartmentalized
panel construction. CRCA/GI thickness shall be 2 to
5.2.7 Construction 2.5 mm subject to type test report from CPRI/ERDA.
Sheet thickness below 2 mm in any part of RMU
shall not be accepted [R7]
Base frame shall be made with 75mm ISMC/ISA
channel. Proper Bolted fixing arrangement shall be
provided. Also, base frame shall be painted with 2
coats of anti rust red oxide and 2 coats of bitumen
paint shall be provided. Adjustable HDPE clits as
5.2.8 Base frame
cable supporting clamps for each power cable (to suit
the cable size from 11kV, 3CX150 to 400 sq mm PILC
/ XLPE cable. Exact size shall be provided during
drawing approval stage.), also cleat shall be
adjustable vertically. [R7]
5.2.9 Lifting lugs Four numbers
1. Bottom
2. 3mm metallic, removable type & split type in two
parts, with 1no. 90 mm diameter knocks out
5.2.10 Cable Entry
punch/hole in the centre (For double cable boxes, Un-
drilled gland plate to be supplied. Approval should be
taken for the same during drawing submission)
5.2.11 Cable termination
11kV, 3C X 150 / 240 / 300/ 400 sq mm Aluminium
5.2.11.1 Cable type & size
conductor XLPE/ PILC with armor & PVC outer sheath
With right angled cold applied boots (3M,Raychem or
Terminals for 11kV cable K.D. Joshi make), set of required size of Brass Nut
5.2.11.2
termination bolt – M 16 size, Bimetallic washers and reducer for
different size of cable termination to be provided. [R7]
5.2.11.3 Termination type Suitable for heat shrinkable type
900mm minimum from gland plate to center of
5.2.11.4 Termination height
bushing [R7]
Copper/Tinned copper (Sizing Calculation to be
5.2.12 Bus bar submitted in support of its Guaranteed S.C. rating /
Capability) [R7]
Bus bar continuous rated
5.2.12.1 630amp
current
Bus bar short time withstand
5.2.12.2 20 KA for 3 sec [R3]
capacity
Bus bar support insulator
5.2.12.3 SMC / DMC resin
material
Maximum temperature rise
5.2.12.4 In line with Table 3 of IEC60694
above reference ambient

Page 12 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

5.2.13 Earth bus bar Tinned Copper sized for rated fault duty for 3 sec [R7]
Earth bus internal connection
By 2.5 sq mm copper flexible green PVC wire, Earth
to all
5.2.13.1 connection point maximum 1 meter away from cable
noncurrent carrying metal
test facility
parts
Earth bus external Studs on both sides with holes and with M10 bolt +
5.2.13.2 connection to hardware to readily receive purchaser earth
owners earth connection
5.2.14 Cooling arrangement By natural air without fan
Multi strand flexible color coded PVC insulated Cu
wire 1 sq mm (SCADA) / 2.5 sq mm (for CT’s) 1100
volt grade (R phase - Red, Y phase – Yellow, B phase
5.2.15 Panel internal wiring – Blue, AC- black, DC – grey, Earth – green) with
ferrules at both ends.
All the internal control / auxiliary wiring shall be routed
through proper conduit. [R3]
Hardware (Nut, bolts & Stainless steel (Except termination nut-bolts-washers-
5.2.16
handle) reducer which are Brass / Tinned Copper) [R7]
5.2.17 Gasket Neoprene rubber
1 Sq mm, Nylon 66 material, screw type + 20% spare
5.2.18 Marshalling terminal blocks
in each row of TB.
5.2.19 Panel cover fixing bolts Allen head 6mm with hexagonal slot
5.2.20 Padlock facility Required for all earth switches & all handles

5.2.21 Internal Arc classification


To ensure operator’s safety, design should ensure
that gases / flames generated during flash over / blast
in any of the compartment, must not come out from
the front of RMU as well shall not go to adjacent cable
compartment. Internal arc test report (for Cable
5.2.21.1 Explosion vents
compartment & other compartments) must be
submitted to support above, along with RMU GA
drawing indicating these vents. There shall not be any
type of holes, gaps etc on the walls of cable
termination compartment. [R3]
5.2.21.2 Internal Arc rating 20 kA for 1s [R3]

5.2.21.3 Internal arc classification IAC AFLR [R3]


< 0.1% of total mass. Pressure of SF6 gas shall be
5.2.22 SF6 gas annual Loss above the operating limit throughout the life of the
equipment. [R7]
5.3.0 Load break switch / Isolator (LBS) [R7]
Three poles operated simultaneously by a common
5.3.1 Type
shaft

Page 13 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Arc interruption in
5.3.2 SF6 or Vacuum
dielectric medium
Operating mechanism for
5.3.3 Manual as per enquiry.
close / open
5.3.4 Addition / removal of motor Without overhaul of operating mechanism [R7]
Complete with power & control wiring so that only motor
5.3.5 RMU without motor
can be added at later date
5.3.6 Motor rated voltage NA
5.3.7 Battery type & size a) NA
5.3.8 Continuous rating of LBS 630 Amp at design 40 deg C ambient
5.3.9 Short time withstand capacity 20 KA for 3 sec [R3]
5.3.10 Fault making capacity 50 kA peak [R3]
Minimum number of
Mechanical Endurance – Class M1( 1000 operations)
5.3.11 operations at rated current (as
Electrical Endurance – Class E3 (100 operations) [R3]
per IEC 62271-102)
Minimum number of
operations at rated fault
5.3.12 Class E3 (Min 10 operations) [R3]
current (as per IEC IEC
62271-102 )
Fault passage indicator (FPI) To be provided on incommer side of one LBS for panel
5.3.13 (For both Earth fault and Over type 1CB + 2 LBS. For all other configuration of RMU,
Current Protection) {R7} FPI to be provided on all LBS.
CBCT – Split open type suitable for mounting without
5.3.14 Earth Fault Indicator
disconnection of cable.
Cable connection of FPI with CBCT shall be of pre
5.3.15 Connection of CBCT with FPI moulded type on the CBCT side. Cable shall be 2.5
sq.mm cu PVC insulated cable only. {R7}
Digital type and shall operate as the current exceeds
the set value. Flash indication for identifying faults with
red LED with one flash for every one sec. Test & rest
Fault Passage Indicator
button 1 NO + 1 NC potential free contact for remote
5.3.16 (For both Earth Fault and
indication FPI power supply unit shall use lithium battery
Over Current Protection)
with minimum life of 1000 blinking hours , so that FPI
shall continue to function even after main feeder has
tripped. [R7]
5.3.17 Data by Purchaser [R7]
5.3.17.1 System Fault Level 2kA – 8.75kA
5.3.17.2 Type of Grounding Solidly Grounded
5.3.17.3 Fault clearing time 100ms

Page 14 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

5.3.17.4 Cable Type PILC / XLPE , 11Kv, 3CX150 sq.mm to 400 sq.mm
5.3.18 Earth Fault Indicator
5.3.18.1 Sensing Current 100 to 400A
5.3.18.2 Sensing Time 30 to 100 ms in steps of 10ms.
5.3.18.3 Reset Time 0.5 -1-2-3-4 hr
a) Self rest after reset time
b) Self rest after restoration of voltage
5.3.18.4 Resetting Facility
c) Manual
d) Remote resetting
5.3.18.5 Contact Rating 1A at 230 V
5.3.18.6 Degree of Protection IP 54
5.3.18.7 Mounting Arrangement Surface or Flush Mounting
5.3.18.8 Ambient Temperature -0 to 50 Deg C
5.4.0 Circuit breaker [R7]
Three pole, operated simultaneously by a common
5.4.1 Type
shaft
Transformer circuit breaker -
5.4.2 For controlling transformer, manual operation only
TCB
For controlling cable feeder, manual operation.
5.4.3 Feeder circuit breaker - FCB
Remote trip operation by SCADA possible
Arc interruption in dielectric
5.4.4 Vacuum Bottle
medium
5.4.5 Operating mechanism - TCB Manual spring charged stored energy type
Manual spring charged stored energy type, remote
5.4.6 Operating mechanism - FCB
electrical close / open operation possible.
Emergency trip / open push On panel front with Protective flap to prevent any
5.4.7
button accidental tripping of breaker.
Continuous rating at design
5.4.8 630amp
40 deg C ambient
5.4.9 Short time withstand capacity 20 KA for 3 sec
Minimum number of
Mechanical Endurance – Class M1( 2000 operations)
5.4.10 operations at rated current
Electrical Endurance – Class E2
(as per IEC 62271-100)
5.4.11 Fault making capacity 50 KA peak
5.4.12 Fault breaking capacity a) 20 KA Minimum
Maximum number of
Electrical Endurance – Class E2 . To be guaranteed
5.4.13 operations at rated Fault
by manufacturer with authorized lab test reports
current (as per IEC 62271-

Page 15 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

100)
Breaker status auxiliary
5.4.14 2NO + 2NC wired to terminal block
contact
b) 75-400 / 1 amp for TCB/ FCB.
c) Considering three core cable terminations,
mounting flexibility shall be provided for CT’s
(in horizontal & vertical direction both).
Additionally, CAUTION marking (by sticker/
5.4.15 Current transformer paint) shall be provided to avoid CT’s
installation above the screen of cable. (I.e.
earth potential point.)
d) Position of CTs inside compartment shall be
adjustable in vertical and horizontal direction

5.4.16 CT accuracy class 5P10 minimum


Self powered, Microprocessor based Numerical relay
(with LCD display), IDMT over current / earth fault
5.4.17 Protection relay protection with high set element, manual reset type
Relay mounting flush to panel front.
Relay shall be communicable for automation purposes
Relay auxiliary contacts for
Potential free contact 1NO + 1NC wired to
5.4.18 remote
terminal block
indication
Shunt trip 230v AC (for WTI
To be wired to terminal blocks (If the functional
trip & door limit switch of Dry
5.4.19 requirement is achieved by the Protection relay, then
type transformer) & for
shunt trip is not required.
remote trip from SCADA.
5.4.20 Breaking Timing 40 to 60 ms
5.5.0 Earth switch [R7]
Three Pole (ON, OFF and Earth), operated
5.5.1 Type simultaneously by a common shaft, for each Circuit
breaker & Load break switch.
Switching in dielectric
5.5.2 Dry Air in sealed medium or SF6 gas
medium
Operating mechanism for
5.5.3 Manual
close & open
5.5.4 Fault making capacity 50 kA (Desirable)
5.5.5 Auxiliary contacts 1NO+1NC wired to terminal block
Disconnect switch (if
Desirable to be located on purchaser cable
5.5.6 provided in series with
connection side of vacuum bottle
vacuum bottle)
Minimum number of
Mechanical Endurance – Class M0( 1000
5.5.7 operations at no load (as per
operations)
IEC 62271-102)

Page 16 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Making capacity endurance


5.5.8 of earth switch (as per IEC Class E2 (Min 5 operations)
62271-102 )
Requirements of sealed
5.6.0
housing live parts
Stainless steel enclosure suitable for IP67. Metal
5.6.1
Enclosure thickness shall be 3mm.
5.6.2 SF6 gas pressure low alarm To be given
To be given (For ‘sealed for life’ design of RMU, this is
5.6.3
Provision for SF6 gas filling not applicable)
Provision for SF6 gas
5.6.4 pressure
indication Digital/Analog Manometer with non return valve
Arc interruption method for
5.6.5 SF6
breaker / Load break switch Puffer type / rotating arc type
Potential free contacts for
5.6.7 SF6 gas
pressure low 1NO +1NC (Desirable)
5.7.0 RMU operation interlocks [R7]

5.7.1 Interlock type Mechanical


Load break switch &
5.7.2
respective earth switch Only one in ‘close’ condition at a time
Circuit breaker & respective
5.7.3
earth switch Only one in ‘close’ condition at a time
Prevent the removal of
respective cable covers if
5.7.4
load break switch or
circuit breaker is ‘ON’ Electrical / Mechanical
Prevent the closure of load
break switch or circuit
5.7.5
breaker if respective cable
cover is open Electrical / Mechanical
Cable test plug for LBS/CB
5.7.6 accessible only if Earth
switch connected to earth Mechanical
5.8.0 Indication & signals [R7] for SCADA / Local
Operation counter on front / To be provided for each LBS & Circuit breaker, with
5.8.1
Inside the RMU LT chamber minimum four digits & non resettable type
Cable charge status Capacitor type voltage indicators with LED on all the
5.8.2
indication for all LBS & CB phases (Shall be clearly visible in day light)
Spring charge status
5.8.3 On front for breaker
indication
Earth switch closed indication
5.8.4 On front
(For Each LBS)

Page 17 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Load break switch ON/OFF


5.8.5 Green for OFF / Red for ON
indication
Circuit breaker On/OFF
5.8.6 Green for OFF / Red for ON
indication
Circuit breaker protection
5.8.7 relay Flag
operated on fault
Fault passage indication on
5.8.8 Flag
LBS
Status signals to SCADA-to
5.8.9 be wired to marshalling 2NO + 2NC
terminal block
5.8.9.1 LBS close / open potential free contacts
LBS & CB Earth Switch close
5.8.9.2 potential free contacts
/open
5.8.9.3 CB close / open potential free contacts

5.8.9.4 Protection relay operated potential free contacts


5.8.9.5 FPI operated potential free contacts

5.8.9.6 SF6 gas pressure low potential free contacts - to be provided.


a) Mimic diagram (Shall not be accepted with
Mimic diagram, labels &
Stickers) [R3]
5.9.0 finish
b) On panel front with description of function &
direction of operation of handles/buttons
Operating instruction chart and Do’s & Don’ts in Hindi
/ local language to be displayed on left / front side of
5.9.1 Operating Instructions
panel enclosure on anodized Al Sheet 16SWG, duly
affixed on panel.
5.9.2 Name plate on panel front Fixing by rivet only
5.9.2.1 Material Anodized aluminum 16SWG / SS
5.9.2.2 Background SATIN SILVER
5.9.2.3 Letters, diagram & border Black

5.9.2.4 Process Etching


Month & year of manufacture, equipment type, input &
5.9.2.5 Name plate details output rating, purchaser name & order number,
guarantee period
Labels for meters & Anodized aluminum with white character on black
5.9.3
indications background OR 3 ply lamicoid
Danger plate on front & rear Anodized aluminum 16 SWG with white letters on red
5.9.4
side background
5.9.5 Painting surface preparation Shot blasting or chemical 7 tank process

Page 18 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Powder coated epoxy polyester base grade A, shade -


5.9.6 Painting external finish
RAL 7032, uniform thickness 60 micron minimum
Powder coated epoxy polyester base grade A, shade -
white, uniform thickness 60 micron minimum
5.9.7 Painting internal finish
Printed copy shall be fixed/mounted inside each and
every compartment.
5.10.0 Quality Assurance [R7]

5.10.1 Vendor quality plan To be submitted for purchaser approval


Inspection points in quality
5.10.2
plan To be mutually identified & agreed
5.10.3 Quality – Process Audits BSES shall carryout vendor process audits.
5.10.4 Field quality plan Bidder to submit field quality plan along with the bid
Bidder to submit detailed spare part list along with the
5.10.5
Spare part list bid
Bidder to submit maintenance manual along with the
5.10.6
Maintenance manual bid
Self Powered O/C & E/F
5.10.7
Relay Ashida ADR241S-761
5.10.8 Boots 3M / Raychem/K.D.Joshi
5.11.0 Inspection and Testing [R7]
1. Equipment of type tested quality only, including
internal arc test (AFLR) shall be accepted as
specified in the specification on various
compartments like cable chamber, SF6 gas tank
etc.(refer IS/IEC mentioned in the clause no 2.)

2. All Type test certificate along with AFLR internal


test report from CPRI/ERDA/Any other reputed
independent international Lab equivalent or better
Type test than CPRI/ERDA to be submitted along with offer
for scrutiny. Type test more than 5 years old will
not be acceptable. In case type test is more than 5
years old, bidder shall conduct type test from
CPRI/ERDA/Any other reputed independent
international Lab equivalent or better than
CPRI/ERDA as per standard without any cost
implication to BRPL. In this regards if BRPL want to
witness the test , all the expenses of BRPL
inspector shall be borne by bidder.
Routine test As per relevant Indian standard (refer IS …)
To be performed in presence of purchaser at
Acceptance test manufacturer works
Physical inspection & BOM, wiring check

Page 19 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Insulation resistance test (Before & after HV test)


HV test for one minute,
Operation & interlock check

Measurement of resistance of main circuit


Voltage Indication check
Functional testing of Fault passage Indicator for Alarm
Primary current injection test for each circuit breaker
feeder with relay
Breaker closing & opening time measurement
PD Test and CRM phase wise
5.12.0 Deviations
a) Deviations from this specification shall be listed separately by bidder clause wise
(format given below) along with optional offer and has to submit the list along with
bid/quotation. BRPL will review the deviations and if BRPL is agreed with the
deviation, seller has to take written confirmation from BRPL on deviation during tender
evaluation.
b) In the absence of any separate list of deviations from the bidders with bid as well as
written confirmation from BRPL on deviations, it will be assumed by the Buyer that the
Seller complies with the Specification fully.
c) Any deviations mentioned in any other submitted bid documents (i.e.in filled GTP,
Catalog, BRPL old approval, buyer’s/seller’s standards etc) by seller without separate
deviation sheets will not consider as a deviation from this tech spec at any stage of
contract.
5.13.0 Special Technical Requirement [R7]

5.13.1 Self Powered Relay Protection setting (min 10%)


5.13.2 NA”.

5.13.3 All the communicable accessories shall have Latch contact


5.13.4 NO/NC contact for manometer shall be provided
5.13.5 Each RMU shall be supplied with 2 sets of Operating Handle
1. Cable termination drawing, cable termination instruction, dia wise bolt tighten torque
range chat shall be fixed by sticker inside the termination compartment of each and
5.13.6 every RMU.
2. Operation instruction manual of RMU shall be given with each and every RMU by
OEM.
In case of Motorized RMU required along with PSS in the place of Manual RMU (If
5.13.7 requirement given by BRPL),bidder may refer technical specification only for
motorized RMU- GN101-03-SP-76-01 or latest version of the same.

Page 20 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

5.14.0 Make List of RMU's Accessories [R7]


Sl. No. Descriptions Make

1 Relay (Self Power+ AUX Ashida 241S-761


DC/AC Supply+
Communicable)
2 CT Narayan Power Tech (NPT)/Gilbert Maxwell, 400/75-
1/1, 5P10, 2.5 VA, Pragati, Nortex
3 FPI (Both for Earth Fault and EMG/C&S/Schneider/SIEMENS
Over Current Protection)
4 CBCT (Both for Earth fault EMG/C&S/Schneider/SIEMENS
and Over current protection)
5 Boot 3M/Raychem/K.D.Joshi
6 Wire Polycab/Havells/Finolex/KEI
7 AC & DC MCB SIEMENS/Havells/C&S/ Schneider
8 Disconnecting type fuses Connectwell/Wago/Phoenix/Elmex

9 TB (disconnecting type) Connectwell/Wago/Phoenix/Elmex


10 Vacuum Interrupter CG/ ABB/Schneider/SIEMENS/other type tested

6.0 11KV XLPE Cable & termination kit

The 11kV XLPE cable connection from RMU to distribution transformer shall be conforming
to IS 7098 and shall have all the following features -

XLPE insulated armoured / un armoured cable 3C x


6.1 Cable type & size
150 sqmm to 400 sqmm Aluminium conductor
6.2 Cable voltage grade 11KV
6.3 XLPE insulation thickness 3.14 mm minimum
Aluminium conductor no of
6.4 As per Table 2 of IS 8130
strands
With semi conducting extrusion, copper tape & water
6.5 Insulation screen
swellable tape
6.6 Type of armour GI flat as per table 4 of 7098 part 2
11KV end termination at
6.7 By 11kv grade end termination kit, heat shrink type
RMU
11KV end termination at By screened separable connector kit suitable for 630 A
6.8
Distribution transformer ‘C’-interface epoxy cast bushings. [R3]
Cable support from RMU to
6.9 GI cable tray 300mm wide
transformer HT side cable

Page 21 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

box

7.0 Oil Type Sealed Distribution Transformer

7.1.0 Major Design criteria


Voltage variation on
7.1.1 + / - 10 %
supply side
Frequency variation on
7.1.2 +/ - 5 %
supply side
Combined variation of
7.1.3 - 20 % or + 10 %
voltage and frequency
7.1.4 Service Condition Refer Annexure B
7.1.5 Insulation level
One minute power
frequency withstand 3KV for 415V system & 28KV for 11KV system
voltage
Lightning impulse
75KV peak for 11KV system
withstand voltage
7.1.6 Short Circuit withstand level
Three phase dead short
circuit at secondary
terminal with rated For 3 sec
voltage maintained on the
other side
7.1.7 Overload capability As per IS 6600
Shall not exceed limits as per NEMA TR-1 with all
accessories running measured as per IEC 551 / NEMA
7.1.8 Noise level
standard running measured as per IEC 551 / NEMA
standard
7.1.9 Radio Influence Voltage Maximum 250 microvolt
Transformer to be designed for suppression of 3rd, 5th,
7.1.10 Harmonic currents
7th harmonic voltages and high frequency disturbances.
Transformer to be free from partial discharge up to 120%
of rated voltage as the voltage is reduced from 150% of
7.1.11 Partial Discharges
rated voltage i.e. there shall be no significant rise above
background level.
Parallel operation with
7.1.12 existing transformer z= Shall be designed to operate in parallel
5%
7.2.0 Major Parameters
7.2.1 Rating [R4] 1000KVA/ 630 KVA/ 400 KVA/250 KVA [R7]
7.2.2 Voltage Ratio 11kv / 433 volts

Page 22 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

7.2.3 Vector Group Dyn11


4.5 % for 250 KVA [R7] 400KVA & 630KVA tolerance as
7.2.4 Impedance at 75 deg C per IS [R4]
5% for 1000KVA tolerance as per IS [R4]
7.2.5 Losses at 75 deg C With ONAN cooling
1000KVA 630KVA 400KVA 250KVA[R7]
Total Loss –Max in KW at
7.2.5.1
50% Load
2.79 [R7] 1.86 [R7] 1.225 [R7] 0.98 [R7]

Total Loss –Max in KW at 1000KVA 630KVA 400KVA KVA[R7]


7.2.5.2
100% Load
7.70 [R7] 5.30 [R7] 3.45 [R7] 2.93 [R7]
Temperature rise top oil –
7.2.6 35 Deg C max over ambient 40 Deg C
without enclosure
Temperature rise winding
7.2.7 40 Deg C max over ambient 40 Deg C
– without enclosure
1.6 Tesla [R7] at 100% rated voltage 1.9 Tesla at
7.2.8 Flux density
112.5% rated voltage [R4]
7.2.9 Current density 3 amp / sqmm for HV & LV winding
7.2.10 Tapping on HV winding Off circuit + 5% to -10% in 2.5% step [R4]
7.2.11 Design Clearances Phase - phase Phase – earth
11kv system 180mm 120mm
415v system 25mm 25mm
7.3.0 Transformer construction
Double Copper wound, three phase, oil immersed, with
7.3.1 Type
ONAN cooling
7.3.2 Tank Type tested design
a) Completely sealed type with corrugated fins and
without conservator
b) Completely oil filled or N2 cushion at top filled with
7.3.2.1 Design
positive pressure. N2 shall be technical grade in
accordance with IS:1747
c) With bolted / welded cover
a) Adequate for meeting mechanical & electrical
withstand requirements, as per applicable standard.
b) The tank and its sealing (gaskets, o-rings, etc.) shall
be of adequate strength to withstand positive and
negative pressures built-up inside the tank while the
Plate / Corrugated fin / transformer is in operation. The maximum pressure
7.3.2.2
tank features generated inside the tank should not exceed 40kPa,
positive or negative.
c) Corrugated fins shall be built up of CRCA sheets of
minimum 1.2mm thick.
d) The corrugated tank wall shall ensure sufficient
cooling of the transformer and compensate for the

Page 23 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

changes in the oil volume during operation.


e) The transformer shall be capable of giving
continuous rated output, without exceeding the
specified temperature rise.
f) Internal clearance of tank shall be such that, it shall
facilitate easy lifting of core with coils from the tank
and HV & LV bushings mounted on Top cover.
g) All joints of tank and fittings shall be oil tight. The
tank design shall be such that the core and windings
can be lifted freely with cover. The tank plate shall
be of such strength that the complete transformers
when filled with oil may be lifted bodily by means of
lifting lugs.
h) Tanks with corrugations & without conservator shall
be tested for leakage at a pressure as per the
applicable standard.
7.3.2.3 Material of Construction Mild steel plate with low carbon
To meet the requirements of pressure and vacuum type
7.3.2.4 Plate Thickness
tests as per CBIP manual
a) All seams and joints shall be double welded
b) All welding shall be stress relieved for sheet
thickness greater than 35 mm
7.3.2.5 Welding features c) All pipes, stiffeners, welded to the tank shall be
welded externally
d) All corrugated fins or expansion bellows provided
shall be double welded.
a) Bottom with stiffeners & adequate space for
collection of sediments
b) No external pocket in which water can lodge
c) Tank bottom with welded skid base
d) Strength to prevent permanent deformation during
7.3.2.6 Tank features
lifting, jacking, transportation with oil filled.
e) Minimum disconnection of pipe work and
accessories for cover lifting
f) Tank to be designed for oil filling under vacuum
g) Tank cover fitted with lifting lug
Inspection cover for
7.3.3 As per manufacturer standard
bushing & Core / Wind
Fittings and accessories
7.3.4 As per clause 7.3.0
on main tank
7.3.5 Core
High grade , non ageing, low loss, high permeability,
7.3.5.1 Material
grain oriented, cold rolled silicon steel lamination
7.3.5.2 Grade Minimum M3 or better [R4]
a) Magnetic circuit designed to avoid short circuit paths
7.3.5.3
Core Design Features within core or to the earthed clamping structures.
b) Magnetic circuit shall not produce flux components

Page 24 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

at right angles to the plane of lamination to avoid


local heating.
c) Least possible air gap and rigid clamping for
minimum core loss and noise generation.
d) Adequately braced to withstand bolted faults on
secondary terminals without mechanical damage
and damage/ displacement during transportation
and positioning.
e) Percentage harmonic potential with the maximum
flux density under any condition limited to avoid
capacitor overloading in the system.
f) All steel sections used for supporting the core shall
be thoroughly sand blasted after cutting, drilling,
welding.
g) Provision of lifting lugs for core coil assembly.
h) Supporting framework designed not to obstruct
complete drainage of oil from transformer
i) Core shall be in the form of step and stack in three
limb format [R7].
Note: No wound core shall be acceptable
7.3.6.0 Winding
7.3.6.1 Material Electrolytic Copper
Maximum Current Density
7.3.6.2 Maximum 3 amp / sqmm
allowed
Winding Insulating Class A, non catalytic, inert to transformer oil, free from
7.3.6.3
material compounds liable to ooze out, shrink or collapse.
7.3.6.4 Winding Insulation Uniform
a) Type of winding [R7]:
LV: Spiral/Helical
HV: Crossover/Disc
Note: No foil winding shall be acceptable
b) Stacks of winding to receive adequate shrinkage
treatment.
c) Connections braced to withstand shock during
transport, switching, short circuit, or other transients.
d) Minimum out of balance force in the winding at all
7.3.6.5 Design features
voltage ratios.
e) Conductor width on edge exceeding six times its
thickness.
f) Transposed at sufficient intervals.
g) Coil assembly shall be suitably supported between
adjacent sections by insulating spacers + barriers.
h) Winding leads rigidly supported, using guide tubes if
practicable.
i) Winding structure & insulation not to obstruct free
flow of oil through ducts.

Page 25 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

j) Delta connection shall be done using Flexible cable.


[R3]
As per Annexure – C, Class 1 new mineral insulating oil,
shall be certified not to contain PCBs. Naphthalene base
7.3.7.0 Transformer Oil
with anti oxidant inhibitor subject to Purchaser’s
specification in Annexure - C
Bushings and
7.3.8.0
Terminations
Epoxy cast bushing, 630 Amp, interface type ‘C’ as per
7.3.8.1 Type of HV side bushing
EN50180 and EN50181. [R3]
Indoor, Epoxy resin cast, 1kv voltage class and
7.3.8.2 Type of LV side bushing
creepage 31mm/KV
Essential provision for LV It shall be complete with copper palm suitable for tinned
7.3.8.2.1
side line bushing copper bus bar of size 100x12 mm

In case of neutral bushing the stem and bus bar palm


Essential provision for LV
7.3.8.2.2 shall be integral without bolted, threaded, brazed joints.
side neutral bushing
Bus bar size shall be 100x12 mm
7.3.8.3 Arcing Horns Not required
Support insulators inside
7.3.8.4 Epoxy resin cast, 12KV rated voltage
HV cable box if provided
Termination on HV side Cable connection by screened separable connector kit.
7.3.8.5
bushing [R3]
Termination of LV side
7.3.8.6 Bus bar connection
bushing
Minimum creepage
7.3.8.7 distance of all bushings 31mm/kv
and support insulators.
Protected creepage
7.3.8.8 At least 50 % of total creepage distance
distance
Minimum 20 % higher than the current corresponding to
7.3.8.9 Continuous Current rating
the minimum tap of the transformer
Rated thermal short time
7.3.8.10 26.3kA for 3 sec
current
Atmospheric protection for
7.3.8.11 clamp and fitting of iron Hot dip galvanizing as per IS 2633
and steel
Bushing terminal lugs in
7.3.8.12 Tinned copper
oil and air
Sealing washers /Gasket
7.3.8.13 Nitrile rubber/ Expanded TEFLON (PTFE) as applicable
ring
7.3.9.0 HV cable box N.A
7.3.9.1 Material of Construction N.A
7.3.9.2 Cable entry As per design
7.3.9.3 Cable size for HV 3C X150sqmm A2XWY 11KV

Page 26 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

7.3.9.4 Connection on LV phase Bus bar 100x12mm copper

Bus bar size for LV


7.3.9.5 Same as phase bus
Neutral
Detachable Gland Plate
7.3.9.6 N.A
material for HV cable box
Gland plate thickness for
7.3.9.7 N.A
HV
7.3.9.8 Cable gland for HV N.A
7.3.9.9 Cable lug for HV Suitable for cable 3CX150 mm2 11KV
Essential parts for HV
7.3.9.10 N.A
cable box
a) Flange type removable front cover with handles min
two no’s
b) Tinned Cu Bus bar
c) Earthing boss for the HV cable box.
d) Earthing link for the gasketed joints at two point for
each joint
e) Earthing provision for cable Armour/ Screen
f) Drain plug
g) Danger / caution plate
Terminal Clearances HV
7.3.9.11 phase – phase & phase - 180mm / 120mm
earth
Termination height
7.3.9.12 required for cable 750mm
termination
7.3.10.0 Current Transformers
7.3.10.1 Requirement All three phases and neutral on LV side
LV side bushings on all three phases and neutral with
7.3.10.2 Mounting the help of fibre glass mounting plate affixed to main
tank by nut bolt arrangement
Maintenance Replacement should be possible by removing fixing nut
7.3.10.3
requirements of mounting plate without disturbing LT bushing
7.3.10.4 Accuracy Class & ISF 0.5s / 10
7.3.10.5 Burden 5 VA
7.3.10.6 Type Resin Cast Ring type suitable for outdoor use
a) 250 KVA-400/5 Amps [R7]
7.3.10.7 CT ratio b) 400/630KVA -1000/5 Amps
c) 1000KVA -1500/5 Amp
7.3.11 Off Circuit tap Switch On HV winding
7.3.11.1 Range /Step + 5 % to -10% in steps of 2.5 % [R4]
7.3.11.2 Type Rotary type, 3 pole gang operated,
7.3.11.3 Operating Voltage 11kV

Page 27 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Rated Current for tap a) 100amp for 1000KVA /630KVA


7.3.11.4
Switch b) 60 amps for 400KVA /250KVA[R7]
External at suitable height to be operated from ground
7.3.11.5 Operating Handle
level.
With direction changing facility, locking arrangement,
7.3.11.6 Tap position indicator
caution plate metallic fixed by rivet.
7.3.12 Pressure Relief Device Required
7.4.0 Hardware
7.4.1 External Stainless Steel
Cadmium plated except special hardware for frame parts
7.4.2 Internal
and core assembly as per manufacturer’s design
7.5.0 Gasket
For Transformer, surfaces
7.5.1 interfacing with oil like Nitrile rubber based / cork
inspection cover etc.
For Cable boxes,
7.5.2 Neoprene rubber
Marshalling box, etc.
7.6.0 Valves
7.6.1 Material of construction Brass / gun metal
Both end flanged gate valve / butterfly valve depending
7.6.2 Type
on application
7.6.3 Size As per manufacturer’s standard
Position indicator, locking rod, padlocking facility, valve
7.6.4 Essential provision
guard, cover plate.
7.7.0 Painting of transformer.
7.7.1 Surface preparation By shot blasting method
Bright Yellow heat resistant and oil resistant paint two
Finish on internal surfaces
7.7.2 coats. Paint shall neither react nor dissolve in hot
of the transformer
transformer insulating oil.
Finish on outer surface of
Battle ship Grey shade 632 Poly urethane paint two
7.7.3 the transformer-frame
coats, minimum dry film thickness 80 microns
parts
7.8.0 Fittings & accessories
7.8.1 Rating and Diagram Plate Required
7.8.1.1 Material Anodized aluminium 16SWG
7.8.1.2 Background SATIN SILVER
7.8.1.3 Letters, diagram & border Black
7.8.1.4 Process Etching
Rating and Diagram Plate
7.8.1.5
details

Page 28 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

a) Following details shall be provided on rating and


diagram plate as a minimum.
b) Type/kind of transformer with winding material.
c) IS/ IEC [R3] standard to which it is manufactured.
d) Manufacturer's name.
e) Transformer serial number.
f) Month and year of manufacture.
g) Rated frequency in HZ.
h) Rated voltages in KV.
i) Number of phases.
j) Rated power in KVA.
k) Type of cooling (ONAN).
l) Rated currents in Amp.
m) Vector group connection symbol.
n) 1.2/50µs wave impulse voltage withstands level in
KV.
o) Power frequency withstands voltage in KV.
p) Impedance voltage at rated current and frequency in
percentage at principal, minimum and maximum tap
q) Load loss at rated current.
r) No-load loss at rated voltage and frequency
s) Continuous ambient temperature at which ratings
apply in deg c
t) Top oil and winding temperature rise at rated load in
deg c;
u) Winding connection diagram with taps and table of
tapping voltage, current and power
v) Transport weight of transformer
w) Weight of core and windings
x) Total weight
y) Volume of oil
z) Weight of oil
aa) Name of the purchaser
bb) PO no and date
cc) Guarantee period
Terminal marking Plate
for Bushing, anodized
aluminium black lettering
on satin silver background
7.8.2 Required
both inside cable boxes
near termination and on
cable box
cover (all fixed by rivet)
Company Monogram
7.8.3 Required
Plate fixed by rivet
Lifting Lug to lift complete
7.8.4 Required
transformer with oil
7.8.5 Lifting lug for top cover Required

Page 29 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

7.8.6 Lashing Lug Required


Jacking Pad with Haulage
hole to raise or lower
7.8.7 Required
complete transformer with
oil
Detachable Bidirectional
7.8.8 Required
flat roller Assembly
Pockets for ordinary
thermometer on tank
7.8.9 cover with metallic Required
identification plate fixed
by rivet.
Drain valve (gate valve)
for the main tank with cork
above ground by 150mm
7.8.10 minimum with padlocking As per manufacturer design
and valve guard with
metallic identification plate
fixed by rivet.
Filter valve (gate valve) at
top with padlocking and
7.8.11 valve guard with metallic As per manufacturer design
identification plate fixed
by rivet.
Air Release Plug on tank
cover with metallic
7.8.12 As per manufacturer design
identification plate fixed
by rivet.
Oil level indicator with low
7.8.13 As per manufacturer design
level switch
Earthing pad on tank for
transformer earthing
complete with non ferrous
7.8.14 nut bolt, washers, spring Required
washers etc. with metallic
identification plate fixed
by rivet
Rain hood for vertical
7.8.15 Desirable
gasket joints
Earthing bridge by copper
strip jumpers on all gasket
7.8.16 joints at at least two Required
points for electrical
continuity
Skid base welded type
7.8.17 Required
with haulage hole
Core , Frame to tank
7.8.18 Required
Earthing

Page 30 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Danger plate made of


Anodized aluminum with
white letters on red
7.8.19 Required
background on
Transformer, cable boxes
(all fixed by rivet)
Caution plate for Off
7.8.20 Circuit tap changer fixed Required
by rivet.
7.8.21 Pressure Relief Device Required
Gas-inlet valve of non- Required (for transformers with nitrogen blanket above
7.8.22
return type oil )
User manual for
Hermetically Sealed
Transformers must be
provided for review as a
part of the technical
proposal. The manual
7.8.23 must be provided with, but Required
not limited to,
maintenance schedule,
frequency & method of oil-
sampling, procedures for
oil-filling & oil-filtration,
etc.

8.0 Dry Type Transformer (1000KVA/ 630KVA/ 400KVA/250 KVA)

8.1.0 Major Design criteria


Voltage variation on
8.1.1 + / - 10 %
supply side
Frequency variation on
8.1.2 +/ - 5 %
supply side
- 20 % or + 10 % combined variation of voltage and
8.1.3 Transient condition
frequency
Refer Annexure B, the transformer enclosure in PSS is to
be designed for outdoor location with service condition as
8.1.4 Service Condition
specified, but its full rating shall be available if located
indoor in poorly ventilated atmosphere
8.1.5 Insulation Level
One minute power
frequency withstand 28KV for 11KV system & 3KV for 415 V system
voltage
Lightning impulse
75KV peak for 11KV system
withstand voltage

Page 31 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Short Circuit withstand


8.1.6 Capacity of the
transformer
Three phase dead short
circuit at secondary
8.1.6.1 terminal with rated For 3 secs.
voltage maintained on the
other side
Single phase short circuit
at secondary terminal with
8.1.6.2 rated voltage maintained For 3 secs.
on other side voltage
maintained on other side
8.1.7 Overload capability As per IEC 60905
Shall not exceed limits as per NEMA TR-1 with all
8.1.8 Noise level accessories running measured as per IEC 551 / NEMA
standard
8.1.9 Radio Influence Voltage Maximum 250 Microvolt
Transformer to be designed for suppression of 3rd, 5th,
8.1.10 Harmonic currents
7th harmonic voltages and high frequency disturbances.
Transformer to be free from partial discharge upto 120 %
of rated voltage as the voltage is reduced from 150 % of
8.1.11 Partial Discharges
rated voltage i.e. there shall be no significant rise above
background level
Shall be designed to operate in parallel with existing
8.1.12 Parallel operation transformer. Details of existing transformers shall be
forwarded to the bidder on request
8.1.13 Fire Protection Class Class F1 shall be required [R7]
8.1.14 Climate Class Class C2 shall be required[R7]
Class E2 shall be required[R7]
8.1.15 Environment Class
Transformer shall be E2C2F1 certified [R7]
8.2.0 Major Parameters
8.2.1 Rating 1000KVA/ 630KVA/ 400KVA/250 KVA[R7]
8.2.2 Voltage Ratio 11kv / 433 volts
8.2.3 Vector Group Dyn11
8.2.4 Impedance 5%, tolerance as per IS
8.2.5 Losses at 130 [R7] deg C
1000 KVA 630 KVA 400 KVA 250 KVA[R7]
8.2.5.1 No load Loss –Max in KW
1.78 1.2 0.9 0.7
1000 KVA 630 KVA 400 KVA 250 KVA[R7]
Load losses at principal
8.2.5.2
tap- Max in KW
7.5 5.4 3.4 2.2

8.2.6 Temperature rise winding Outside PSS without Inside PSS max.

Page 32 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

enclosure

80°C 90°C
Maximum flux density at 10 % over excitation
8.2.7 Flux density
/overfluxing-1.73 Tesla [R7] maximum
Off Circuit taps on HV winding , + / - 5 % in steps of 2.5
8.2.8 Tapping on HV winding
% , change of taps by link
8.2.9 Design Clearances Phase – phase Phase - earth
11KV system 180mm 120mm
415V system 25mm 25mm
415V system 25mm 25mm
8.3 Construction & Design
8.3.1 Core
High grade , non ageing, low loss, high permeability,
8.3.1.1 Material
grain oriented, cold rolled silicon steel lamination
8.3.1.2 Grade Premium grade minimum M3 or better [R4]
8.3.1.3 Lamination thickness 0.23mm (Max) [R4]
Design Flux Density at
8.3.1.4 rated conditions at 1.6 Tesla [R7]
principal tap
Maximum Flux Density at
8.3.1.5 10 % over excitation / over 1.73 Tesla [R7] maximum allowed
fluxing
a. All steel sections used for supporting the core shall
be thoroughly sand blasted after cutting, drilling,
welding.
8.3.1.6 Core Design Features b. Core shall be in the form of step and stack in three
limb format [R7].
Note: No wound core shall be acceptable
c. Provision of lifting lugs for core coil assembly
8.3.2 Winding
8.3.2.1 Material Electrolytic Aluminum [R4]
Maximum Current Density
8.3.2.2 Maximum allowed 1.5 A per sqmm [R4]
allowed
Class F minimum, free from compounds liable to ooze
Winding Insulating out, shrink or collapse. Uniform insulation shall be
8.3.2.3
material applied to the windings and overall winding shall be
epoxy cast resin
Off Circuit taps on HV winding , + / - 5 % in steps of 2.5
8.3.2.4 Tapping
% , change of taps by link
Essential provision for tap Shall be shrouded with cover made from insulating
8.3.2.5
links material. To prevent deposit of dust.

Page 33 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

a) Stacks of winding to receive adequate shrinkage


treatment
b) Connections braced to withstand shock during
transport, switching, short circuit, or other transients.
c) Minimum out of balance force in the transformer
winding at all voltage ratios.
d) Conductor width on edge exceeding six times its
thickness
8.3.2.6 Design features
e) The termination bus-bar coming out from winding
shall be tinned Copper
f) Transposed at sufficient intervals.
g) Threaded connection with locking facility.
h) Winding leads rigidly supported, using guide tubes if
practicable
i) Provision of taps as indicated in the technical
particulars
Phase marking required near termination on both HV and
LV side. Phase colour coding required on insulating
sleeves on both HV and LV side. Phase sequence 1U,
Essential provision of HV 1V, 1W from left to right looking inside from the HV side
8.3.2.7
and LV winding leads door. Phase sequence 2n, 2u, 2v, 2w from right to left
looking inside from LV side door Adequate HV
termination clearance. Provision of check nut in all HV
and LV winding lead connection.
Vibration isolation pads shall be installed between core
8.3.3 Vibration Isolator and coil assembly and enclosure base assembly to
prevent the transmission of structure borne vibrations.
Bushings/Support
8.3.4
Insulator/ terminations
Type of HV and LV
8.3.4.1 Bushings, support Epoxy Resin Cast
insulators
Minimum Creepage of
8.3.4.2 bushings and support 31 mm / kV
Insulators
8.3.4.3 Arcing horns Not required
8.3.4.4 Termination on HV side By cable within main enclosure by separable connector
8.3.4.5 HV side cable size 11 kV (E) grade , A2XCEWY 3C x 150 sqmm
Long barrel medium duty Aluminium lug with knurling on
8.3.4.6 Cable lugs inside surface. and suitable for cable size for 11 kV (E)
grade , A2XCEWY 3C x 150 sqmm
Epoxy cast bushing, 630 Amp, interface type ‘C’ as per
8.3.4.7 HV side bushing
EN50180 and EN50181. [R3]
8.3.4.7 Termination on LV side Suitable bus bar as per PSS spec
8.3.5 Current Transformers

Page 34 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

On LV side terminal busbars on all three phases and


8.3.5.1 Mounting
neutral with the help of fibre glass mounting plate
Replacement should be possible without dismantling LV
8.3.5.2 Maintenance requirements
side support insulators
8.3.5.3 Accuracy Class 0.5s
8.3.5.4 Burden 5VA
8.3.5.5 Type Resin Cast Ring type suitable for outdoor use
a) 250 KVA-400/5 Amps[R7]
8.3.5.6 CT ratio b) 400/630KVA -1000/5 Amps
c) 1000KVA -1500/5 amp
8.3.6 Hardware
8.3.6.1 External Stainless Steel only
Cadmium plated except special hardware for frame parts
8.3.6.2 Internal
and core assembly as per manufacturer’s design
8.4 Gasket Neoprene rubber based gasket across all doors & covers
PVC insulated, extruded PVC inner sheathed, FRLS
[R3], armoured, extruded PVC outer sheathed 1100 V
Control cable specification
8.5 grade control cable as per latest edition of IS 1554 part 1
(to be used by the vendor)
minimum 2.5 sqmm for signals and 4 sqmm for CT with
multistrand copper conductor
Terminal Blocks to be Nylon 66 material, minimum 4 sq mm, screw type for
8.6
used by the vendor control wiring and potential circuit.
Sliding link type disconnecting terminal block screwdriver
Essential provision for CT
8.6.1 operated stud type with facility for CT terminal shorting
terminals
material of housing melamine/ Nylon66
8.7 Painting of WTI box
8.7.1 Surface preparation By 7 tank pre-treatment process or shot blasting method
Finish on internal / Polyurethane based painting, min. Dry film thickness 80
8.7.2
external surfaces microns
Insulating support material Bakelite shall not be used as a base plate for mounting
8.7.3 for base plate for mounting any components, insulating material non hygroscopic
components insulating material like FRP shall be used.
Minimum Protective
8.8
devices on Transformer
Required, Connected on Transformer Primary side on all
8.8.1 Surge Arrestor
three phases
8.8.1.1 Type Metal oxide
8.8.1.2 Housing Polymeric preferable
8.8.1.3 Rating 9 KV.
Continuous operating
8.8.1.4 6.35
voltage , kV rms
Maximum Continuous
8.8.1.5 7.65
operating voltage, kV rms

Page 35 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Nominal Discharge
8.8.1.6 5
Current, kA peak
Energy Absorption
8.8.1.7 Greater than 2.5
Capability, kJ/kV
8.8.1.8 Creepage factor 31 mm /kV
8.8.1.9 Reference std IS 3070 part 3 and IEC 99-4
Winding Temperature
8.8.2 Required
scanner
Five (Three for windings, one for enclosure & one shall
be spare) RTD for enclosure temperature monitoring
8.8.2.1 No of RTD inputs shall be fixed at enclosure Top from inside to give max
enclosure temp reading & shall be wired up to temp.
scanner to indicate the reading
At location of winding where maximum temperature is
8.8.2.1.1 Location of winding RTD
expected.
No of potential free trip
8.8.2.2 Two
contacts
No of potential free Alarm
8.8.2.3 Two
contacts
240 V AC, 1 phase, 50 Hz. Tapped from LV side busbar
8.8.2.4 Auxiliary supply
through a MCB located inside box
Winding Temperature
8.8.2.5 Required
Scanner terminal Box
8.8.2.5.1 Size As per Manufacturer’s Standard
Fixing of instrument within
8.8.2.5.2 On base plate
box
Fixing of terminals within
8.8.2.5.3 On C channel available with the terminals
the box
8.9 Fitting and accessories
8.9.1 Rating & Diagram plate Required
8.9.1.1 Material Anodized aluminum 16SWG
8.9.1.2 Background SATIN SILVER
8.9.1.3 Letters, diagram & border Black
8.9.1.4 Process Etching
Following details shall be provided on rating and diagram
plate as a minimum
a) Type of transformer i.e cast resin or VPI etc. With
winding material
b) IS / IEC [R3] standard to which it is manufactured
8.9.1.5 Name plate details c) Manufacturer's name;
d) Transformer serial number;
e) Month and year of manufacture
f) Rated frequency in HZ
g) Rated voltages in KV
h) Number of phases

Page 36 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

i) Rated power in KVA


j) Type of cooling
k) Rated currents in a
l) Vector group symbol
m) 1.2/50µs wave impulse voltage withstand level in KV
n) Power frequency withstand voltage in KV
o) Impedance voltage at rated current and frequency in
percentage at principal, minimum and maximum tap
at highest temperature
p) Load loss at rated current at highest temperature
q) No-load loss at rated voltage and frequency
r) Auxiliary loss
s) Continuous ambient temperature at which ratings
apply in c
t) Winding connection diagram with taps and table of
tapping voltage, current and power
u) Transport weight of transformer
v) Weight of core and windings
w) Weight of enclosure and fittings
x) Total weight
y) Tapping details
z) Phase ct details
aa) Class of insulation
bb) IP protection rating of the enclosure
cc) Name of the purchaser
dd) Po no and date
ee) Guarantee period
Detachable Bi-directional
8.9.2 Required
flat Roller Assembly
Minimum 900 mm on the side of HV and LV termination
Maximum 800 mm on the other side (perpendicular to
Roller center to center
8.9.2.1 HV, LV termination). and LV termination Maximum 800
distance
mm on the other side (perpendicular to HV, LV
termination).
Roller dia. 150 mm min., roller to be fixed in such a way
so that the lowermost part of the skid is above ground by
8.9.2.2 Essential provision
at least 100 mm when the transformer is installed on
roller.
Earthing pad on enclosure
for transformer earthing
8.9.3 complete with Stainless Required with identification plate on outside of enclosure.
Steel nut, bolt, washers,
spring washers etc.
Core, Frame to tank
8.9.4 Required
Earthing
8.9.5 Off Circuit tapping link Required
8.9.6 Tap link position plate Required inside HV side door

Page 37 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Danger plate made of


Anodized aluminium with
8.9.7 white letters on red Required
background on HV and LV
side
8.9.8 Skid with Haulage lugs Required
Lifting lugs for complete
8.9.9 transformer as well as Required
enclosure
Lifting lugs for core coil assembly shall be provided in
such a way that the weight shall not come on canopy
Essential provision for while lifting Lifting lugs for canopy/ enclosure shall be
8.9.9.1
lifting lugs provided in such a way that the weight shall not come on
canopy while lifting , it shall be borne by supporting
members.
8.9.10 Caution Plate for tap links Required
Ventilation louvers with Required as per Manufacturer’s design, but it is to be
8.9.11 stainless steel wire mesh provided minimum required preventing ingress of
and rain water guard excessive dust.
Surge Arrestor & its
8.9.12 Required
Grounding bushing
Surge arrestor shall be erected vertically in such a way
that the surge arrestor can be removed at site without
removing HV cable lug. Surge arrestor shall not be used
for any kind of support. Surge arrestor grounding strip to
be routed to the surge arrester grounding bushing near
8.9.12.1 Essential provision
bottom of enclosure with proper support. Surge arrestor
grounding bushing shall be identified by identification
plate on outside of enclosure. Surge arrestor grounding
bushing shall be supplied with all hardware to readily
connect purchaser’s ground lead.
LV additional neutral
8.9.13 Required
earthing bushing
Busbar connecting the neutral to additional neutral
bushing shall be properly supported and additional
neutral bushing shall be identified by identification plate
8.9.13.1 Essential provision
on outside of enclosure. Additional neutral bushing shall
be supplied with all hardware to readily connect
purchaser’s ground lead.
Winding temperature
8.9.14 Required
scanner
RTD in Winding and near
8.9.15 Required
top of enclosure.
Thermostatically controlled space heater inside enclosure
Space heater inside
8.9.16 required, supply of space heater from feeder pillar
enclosure
through MCB fixed properly inside enclosure.
By suitable spacers so that heater does not come in
8.9.1 Mounting of space heater
contact with panel wall directly.

Page 38 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

8.9.17 Copper earthing link Across all gasketted joints in the enclosure body.

9.0 Low Voltage Bus bar system

From transformer LV bushing to ACB and from ACB to


9.1 LV bus bar
MCCBs
Type of connection on
9.2 By flexible copper link rated 1600Amp
transformer
a) 100x12 mm tinned copper / Eqvt Size Aluminum.
Bus bar size for phase &
9.3 b) Connection to each MCCB by 40x6 tinned copper
neutral
bar.
9.4 Bus bar support insulators 1 KV voltage class, SMC epoxy
Insulator creepage
9.5 31mm / KV
distance
9.6 Bus bar sleeve insulation Color coded, for 1kv
Type I & II:1600 Amp
9.7 Bus bar rated current Type III:1250 Amp
Type IV : 500 Amp [R7]
Bus bar short circuit
9.8 27.7kA for 1 sec
withstand
9.9 Maximum temperature rise 20º C

10.0 Low voltage switchgear, ACB, MCCB & Fuses

10.1.0 Air Circuit Breaker (ACB) Fixed type 4 pole


ACB - On & OFF Manual as well as electrical by spring charged
10.1.1
operation mechanism
ACB operating
10.1.2 Trip free, anti pumping type
mechanism
10.1.3 Spring charging method Manual as well as electric motor
Spring charging motor
10.1.4 1 ph 240V tapped from LV bus bar
supply
10.1.5 Close & trip coil supply 1 ph 240V tapped from LV bus bar
Fully isolable link sized for 1600 / 1250 / 400 [R7]
10.1.6 ACB Neutral connection
amp
10.1.7 ACB rated voltage 415v +/- 10% at 50Hz
10.1.8 ACB rated current 1600 / 1250 / 400 amp continuous
ACB rated 3 phase short
10.1.9 circuit breaking capacity 50kA minimum at 415v and 50Hz
Ics = Icu

Page 39 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

ACB rated 3 phase short


10.1.10 circuit withstand capacity, 50kA for 1sec
Icw
ACB SC making current
10.1.11 100kA peak
capacity
10.1.12 ACB rated insulation level 1000volt
ACB mechanical &
10.1.13 As per IS 13947 / IEC
electrical endurance
ACB utilization category
10.1.14 B
as per IS
10.1.15 ACB indications ON, OFF & TRIP
10.1.16 ACB operation - manual ON, OFF by push buttons
10.1.17 ACB operation - electrical ON, OFF by TNC switch
By micro processor based releases

ACB overload, short


10.1.18 circuit & earth fault
protection

10.1.19 Operation counter 4 digit minimum , Non reversible [R7]


10.1.20 Multifunction meter Digital CTR & PTR programmable [R7]
Display type LT ACB required with Min. 10 nos
10.1.21 Display & Event log
previous fault event log [R7]
For outgoing feeders – 400A
07 no for Type I PSS,
05+02* no’s for type II PSS&
03+02* no's for Type III PSS
10.2.0 MCCB 02 nos for type IV PSS [R7]
APFC system – 1 no. 630 Amp
*Spare Outgoings - Provisions shall also be made in
LT panel to increase LT outgoing by 02 no’s by
adding MCCB’s in future.
10.2.1 MCCB type 3 pole, one break per pole, Utilization category B
MCCB - On & OFF
10.2.2 Manual by handle
operation
MCCB design ambient
10.2.2(i)[R6] 50deg C
temperature
Thermoplastic material resistant to fire & abnormal
MCCB Housing
10.2.2(ii)[R6] heat , non hygroscopic
Silver coated copper with phase barriers, spreader
10.2.2(iii)[R6] MCCB Terminal
terminals & shrouds
MCCB Spreader size & Minimum-50(W)X50(L)X10(D)mm- Cu suitable for
10.2.2(iv)[R6]
material bimetallic joint i.e. for aluminium bus/cable lug
De-rating at 50Deg
10.2.2(v)[R6] No derarting (0%)
ambient temperature

Page 40 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

MCCB rated 3 phase


10.2.3 short circuit breaking 36kA minimum at 415v and 50Hz
capacity Ics = Icu
MCCB rated 3 phase
10.2.4 short circuit withstand 8kA for 1sec
capacity, Icw
MCCB SC making current
10.2.5 75kA peak
capacity
MCCB rated insulation
10.2.6 1000V
level
MCCB mechanical &
10.2.7 As per IS 13947 / IEC
electrical endurance
10.2.8 MCCB utilization category B as per IS / IEC 947
10.2.9 MCCB indications ON, OFF & TRIP
10.2.10 MCCB protection Microprocessor based release + earth fault
Tripping characteristic
10.2.10(i)[R6]
required
a Overload setting Range 60-100%In (Set on 95%)
b Short Circuit setting Range 200-1200%In (Set on 300%)
c Earth fault setting To be provided
10.2.11[R6] MCCB Clearances in air As per table XIII of IS 13947-1
MCCB temperature rise
10.2.12[R6] As per table 2 & 3 of IS 13947-1
limits

10.2.13[R6] MCCB Ingress Protection IP2X Minimum (pollution degree minimum 2)

Sealing/padlocking of operating knob in OFF


10.2.13(i) position
MCCB additional features
[R6] Sealing/padlocking of operating knob in OFF
position isolation suitable with positive contact
By Cu bar with double PVC insulation
Connection to ACB main
10.2.14 For 400 amp MCCB / fuse – 40x6 mm
bus
For 630 amp MCCB – 50x10 mm
Connection to outgoing By terminals suitable for 2X4CX300sqmm , A2XFY
10.2.15
cables 1100 volt grade cable [R7]

11.0 Automatic Power Factor Correction system

The APFC equipment shall be located in LV compartment of package enclosure either as a


separate panel or integrated along with LV Switchgear and shall have all the following
features –
a) Type I :300 KVAR @ 400 V
11.1 APFC Output
b) Type II and III :200 KVAR @ 400 V

Page 41 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

However APFC should be rated at 440 V.


Manufcatuerer needs to spcify rated output @ 440V.
All components mounted in shelf type arrangement on
11.2 APFC mounting package substation enclosure LV compartment wall or
RMU compartment wall or Part of LT Panel
Mounted on base plate supported on compartment wall
11.3 APFC relay & data logger
by three hinges
APFC system bus bar
By 4CX300sqmm AYFY 1100v grade cable to or Bus
11.4 power connection to
Bars
transformer LT side
50x10mm tinned copper mounted on SMC insulators
11.5 APFC system bus bar size
1100V grade
APFC system CT input From CT on transformer LV side by 7CX2.5sqmm YY
11.6
signal 1100V grade cable
Type I:12x25KVAR three phase compensation
11.7 APFC capacitor modules
Type II & III:8x25KVAR three phase compensation
Capacitor duty contactor
11.8 Utilization category 6b as per IS
for each capacitor module
MCCB for each capacitor
11.9 100amp, Three Pole, Ics=Icu=35kA
module
Connection to each MCCB By 35sqmm copper wire double insulated with tinned
11.10
from APFC system bus copper lugs
11.11 APFC control supply Through 415/240v transformer, 2amp / 6amp SP MCB
Microprocessor based relay for automatic control of
11.12 APFC relay minimum 12 capacitors in sequential or cyclic switching
fashion with settable time delay 0 -180 sec
APFC relay LCD display To show no. of capacitors energized, actual PF &
11.13
with self monitoring feature target PF, voltage & current
Target power factor setting
11.14 0.8 lag to 0.9 lead in steps of 0.1
range
11.15 APFC relay sensing 3 phase CT input 5 amp to sense max load current

11.16 No volt protection in relay To switch OFF all capacitors


Capacitor unit 25KVAR Double layer All Poly Propylene (APP) or Mixed Poly
11.17
type Propylene (MPP)
1.5mm thick sheet metal welded tank or Al cylindrical
11.18 Capacitor unit construction
construction
11.19 Capacitor unit impregnant Dry type filler or non PCB liquid
Capacitor unit conducting
11.20 Al foil or metalized film
layer
11.21 Capacitor sealing Hermetic sealing after vacuum process
Pressure sensitive dis-connector or internal fuse for
11.22 Capacitor unit safety
each element
Between all three phases of capacitor unit, to reduce
11.23 Discharge resistor the voltage across the capacitor to 50V or less in one
minute

Page 42 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

For rated voltage class 1 KV Suitable wires / terminals


11.24 Terminal bushings
brought out from capacitor unit is also acceptable.
Earth connection for
To be done & connected to main earth bus bar of the
11.25 individual capacitor
panel
container
11.26 APFC Operational features
Automatic power factor
11.26.1 To achieve target lagging power factor without hunting
correction
At continuous rated voltage (440 V) & frequency (50
11.26.2 Operation for rated output
Hz)
Operation with over
11.26.3 115% of rated voltage for 12 hours in a day
voltage
Operation with harmonic
11.26.4 THD voltage – 5% & THD current 3%
distortion
Maximum permissible over
11.26.5 1.3 times rated current, continuous
current
11.26.6 Dielectric loss 0.2 watt per KVAR maximum
Temperature Category &
11.26.7 - 5 / 60 deg C Not exceeding 10 deg C over 60 deg C.
Maximum temperature rise
Residual voltage after
11.26.8 50 volts maximum after 60 seconds
disconnection from mains
11.26.9 Design life of capacitor unit Minimum 10 years
11.27.0 Data Logger (approved by requisite authority / Electrical inspector)
Accuracy class 0.5, microprocessor based with LCD
display, with 3 CTs for measurement of cumulative
11.27.1 General
KWH, power factor, voltage & current of transformer
secondary, THD of voltage.
Data logging of KWH value at every 30 minutes to give
cumulative reading of KWH for 45 days minimum, data
11.27.2 Data logging and Software downloadable in ASCII-II or MS Excel format. Software
for downloading the data from data logger to be
provided by data logger vendor.
Display of DATE, TIME, station ID -Display & log power
parameters phase wise & total (load current, kVA, kW
Display and & PF). -Display & log kVAr phase wise & total. -Display
11.27.3
communication TDH V or current. -The logger shall be with built in
communication facility of RS485 / RS232 to down load
all parameters on demand.
12.0 Energy Meter Box

12.1 Energy meter In the scope of purchaser


To be provided mounted on enclosure wall in LV
12.2 Location
compartment.

Page 43 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

12.3 Energy meter box Size 650 mm height x 450 mm width x 275 mm depth.
With antitheft hinge, padlock facility, door fixed by
12.4 Box door design
stainless steel Allen screw M6 size.
On slotted horizontal channel 40 x 12 mm size,
Fixing of energy meter
12.5 channel shall be movable on vertical slotted angle 40
within box
x 40 mm size at two ends.
Front door shall be with acrylic sheet for viewing the
12.6 Meter reading window
energy meter.
02 no’s sealing arrangement shall be provided on
12.7 Sealing arrangement meter box’s door.
Slot shall be provided on door of meter box for fixing 9
12.8 Data downloading port pin DB connector (RS232 serial port).
12.9 Test Terminal Block No Test terminal block shall be provided.
PVC insulated, extruded PVC inner sheathed,
armored, extruded PVC outer sheathed 1100 V grade
12.10 Cables and wires control cable as per latest edition of IS 1554 part 1
minimum 2.5 sq mm for PT and 4 sq mm for CT with
multi strand copper conductor.
Nickel plated brass double compression weatherproof
12.11 Cable Glands
cable gland.
To be fixed on the back of door along with CT spec.
12.12 Wiring diagram
etched on Anodised Aluminium plate fixed by rivet.
All CT and PT’s Secondary wires shall be routed
CT / PT Secondary through metallic conduit. All secondary wires shall be
12.13
wires bunched and kept for termination without any terminal/
TTB in between.

13.0 Enclosure for packaged substation

13.1 Service conditions For outdoor use


Galvanised Sheet steel 2mm thick with outer finish
13.2 Material for enclosure
painting
Frame supported construction with all doors, covers
13.3 Enclosure construction welded with steel channel ribs at every 1000mm
minimum
Lifting lugs for site handling / Four numbers on top to enable lifting of total
13.4
lifting by crane package unit without any problem
With internal anti theft hinge with minimum opening
Doors for RMU compartment &
13.5 angle of 120º [R3], minimum 3 nos., with lockable
LV compartment
handle & with padlocking facility
Two side covers for
13.6 Bolted with Allen head type bolts to main frame
transformer compartment
Top & other side walls of
13.7 Welded sheet metal to main frame
package substation enclosure

Page 44 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Removable canopy above top


13.8 2mm thick sheet metal with 10º slope
cover
Enclosure integral steel base ‘I’ section of suitable size to support total static and
13.9
frame dynamic load
Base frame bottom support
13.10 pads for fixing by bolt to Minimum six numbers to rest on foundation
foundation
Separate compartments for RMU, transformer & LV
13.11 Enclosure compartments
switchgear/APFC
Separation between RMU &
13.12 By sheet steel 2mm thick
transformer compartment
Separation between
13.13 transformer compartment & LV By sheet steel 2mm thick
compartment
Degree of ingress protection IP53 for RMU compartment
13.14 against solids & water as per IP 34 for transformer compartment [R7]
IS12063 IP54 for LV compartment
Louvers on side covers of
To be provided with steel wire mesh welded from
13.15 transformer compartment &
inside so as to meet IP requirement as above
side walls of LV compartment
Louver area on cover / side
13.16 1500mm height x 1500mm desirable
wall
Louver position from bottom
13.17 Minimum 200mm above bottom
level
Mounted in LV compartment to discharge air in
transformer compartment & Controlled by SPMCB &
13.18 Exhaust Fans
thermostat to operate above 35 deg C, 2x150CFM,
1 ph 230v 50Hz
Gland plate for RMU 3 mm thick MS plate suitable for 3x3c300/400
13.19
compartment sqmm AYFY 11kv cable

Gland plate for LV 3 mm thick MS plate suitable for 10x 4c400sqmm


13.20
compartment cable + 10x7c2.5sqmm cable
13.21 Door Opening Provision Type I, II & III : With 3 side door opening
Class of enclosure as per IEC
13.22 10K
62271-202
13.23 Internal Arc classification IAC AB 20 KA, 1s [R3]
Limiting dimensions of
13.24
package enclosure
Type I (1000KVA Transformer
13.25 a 3400(L) x 2900(W) x 2800(H)
):
Type II & III (400KVA /630KVA
13.25.b 3400(L) x 2600(W) x 2600(H)
Transformer)
13.26 Type IV (250 kVA 2000(L) x 2000(W) x 2000(H) [R7]

Page 45 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Transformer)
14.0 Other Provisions: Earthing, Illumination, Hooter & Smoke Detector

Earth bus connection brought


a) Two earth pads for RMU, transformer & LV
out of package substation
14.1.1 compartment each.
enclosure to earth pad for
b) Two earth pads for transformer neutral
connection to earth pit
14.1.2 Earth bus size 50 x6 GI flat
14.1.3 Earth bus fault current capacity 26.3kA for 1 sec
Earth connection of all covers,
14.1.4 doors & structural parts to GI By metallic jumper connection
bus
Earth connection of RMU, ACB
14.1.5 & transformer body parts to GI By two numbers of 50x6mm GI flat per equipment
bus
14.1.6 Earth bus identification Shown by letter ‘E’
RMU, transformer & LV By 36w CFL fixture controlled through SPMCB &
14.2.1
compartment illumination door limit switch
RMU, transformer & LV
14.2.2 5/15amp 3 pin socket through 15 amp SPMCB
compartment power socket
Minimum 02 no’s Smoke Detectors in each LT,
HT and Transformer compartment with potential
Smoke Detector in each
14.24 free auxiliary contact for tripping the RMU, Alarm
compartment
and SCADA. All detectors shall be wired upto
controller cum alarm unit suitable. [R3]
Required with timer reset for operator alarm on
14.25 Hooter
opening of PSS door

15.0 Labels & painting

15.1 Name plate on package enclosure Fixing by rivet only

Anodized aluminum 16SWG / Stainless Steel


15.1.1 Material
(SS) [R3]
15.1.2 Background SATIN SILVER
15.1.3 Letters, diagram & border Black
15.1.4 Process Etching
Month & year of manufacture, transformer rating,
purchaser name & order number, guarantee
15.2 Name plate details
period, Ref. IS / IES No. Shall be provided inside
enclosure as well as outside enclosure.[R3]

Page 46 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Anodized aluminium with white character on


15.3 Labels for meters & indications
black background OR 3 ply Lamicoid

Danger plate on doors of RMU Etched on 16 swg anodised aluminium / SS plate


15.4
compartment & LV compartment with white letters on red background

a) 02 no’s
b) HV and LV side of PSS enclosure.
c) Shall be etched on anodized aluminium
15.5 BSES Insignia
16SWG / SS plate.
d) Details shall be finalized during drawing
approval.
Enclosure painting surface
15.6 Shot blasting or 7 tank chemical process
preparation
Enclosure painting external finish Hot dip galvanizing – 80 micron thick grade A,
15.7 Powder coated epoxy polyester shade - RAL 7032, uniform thickness 60 micron
base minimum .
Powder coated epoxy polyester base grade A,
15.8 Enclosure painting internal finish shade -white, uniform thickness 80 micron
minimum

16.0 Approved makes

For RMU accessories please refer RMU


16.1.0 RMU
Specification part

Toshiba/Danish/ Schneider// or any other make


16.4.0 Oil type transformer
approved by BRPL.[R7]
ABB/ Raychem / TMC/ or any other make
16.5.0 Dry type transformer
approved by BRPL. [R7]
Transformer core Nippon/JFE/Posco
16.6.0 Pressure relief valve Sukrut / VIAL
16.7.0 Bushings make Baroda bushing / CJI / Jaipur Glass
16.8.0 Winding Temperature Indicator Precimeasure/ Pecon
L&T / Schneider-MG / AREVA / GE / Siemens /
16.9.0 ACB
ABB / C&S [R7]
16.10.0 MCCB GE / Merlin Gerin / ABB / L&T/Siemens [R7]
16.11.0 APFC
16.11.1 Switch ABB / Siemens / L&T (Salzer)
16.5.2 HRC Fuse Links Alstom / Siemens / L&T / GE
L&T / Enercon / AE / DUCATI / Phasetrac M-40 /
16.5.3 Load manager
TAS POWERTECH
16.5.4 APFC relay Beluk / ABB / Fraco / Ducati/ TAS / POWERTECH
16.5.5 AC Contactors ABB / Schneider
16.5.6 Push buttons / Actuator L&T / Teknic / Siemens

Page 47 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

16.5.7 MCB ABB / L&T / Siemens/Schneider –MG


16.5.8 Capacitors FRACO / DUCATI/ABB
16.5.9 Fans EBM Nadi
16.6.0 Terminals Connectwell / Elmex
Euromold (Nexan)/ Elmek/ H.J. International/
16.7.0 Transformer Bushings (HV side)
Pfisterer any other vendor approved by BSES
16.8.0 Termination kits for RMU 3m/ Raychem/ Denson
3M/ Raychem/ Denson / any other make approved
16.9.0 Termination kits for Transformer
by BSES
16.9.1 Cold applied cable boots 3M/ Raychem

17.0 Quality assurance

To be submitted for purchaser approval for all


components listed in clause 4.0 For transformer,
17.1 Vendor quality plan
RMU & APFC panel sub vendor quality plan to be
submitted.
17.2 Inspection points in quality plan To be mutually identified & agreed
17.3 Quality – Process Audits BSES shall carryout vendor process audits.
17.4 Field quality plan Bidder to submit field quality plan along with the bid
Bidder to submit detailed spare part list along with
17.5 Spare part list
the bid
Bidder to submit maintenance manual along with
17.6 Maintenance manual
the bid

18.0 Inspection & testing

a) Only type tested quality equipment(s) shall be


offered.
b) Type test certificates mentioned in this clause shall
be submitted along with offer for scrutiny
c) The test report should not be more than 5years old.
d) Type test and special tests for Transformer (from
CPRI/ERDA) shall include the following [R7]:
i) Impulse withstand test on all three HV limbs of
the transformers for chopped wave as per IS
18.1 Type test as per IS / IEC
2026
ii) Temperature rise test as per IS 2026
iii) Air pressure test for sealed transformers asper
IS 1180
iv) Pressure and Vacuum test on tank
v) Dynamic & Thermal (3 sec) Short Circuit Test
as per IS.
vi) Measure of zero seq. impedance (Cl. 16.10 IS
2026 Part I).

Page 48 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

vii) Measurement of acoustic noise level (Cl. 16.12


of IS 2026 Part I).
viii)Measurement of harmonic level on no load
current.
ix) Partial discharge test
x) High voltage withstand test shall be performed
on the auxiliary equipment and wiring after
complete assembly.
e) If identical rating type test reports for transformers
are not available vendor to carryout Short circuit
withstand test (Dynamic and thermal (for 3 secs)),
Lightning impulse test & temperature rise test
without any additional cost.
18.1.1 Package substation assembly As per IEC 62271-202
11kv RMU, transformer, ACB,
As per relevant IS/ IEC, For RMU type test criteria
18.1.2 MCCB, APFC system and
refer RMU specification part
capacitor units
18.2 Routing tests
18.2.1 Routine tests of PSS As per IEC 62271-202
Routine tests of transformer, As per relevant IS/ IEC , For RMU refer RMU
18.2.2
RMU, LT panel & APFC specification part
a) Purchaser reserves the right to inspect /witness all
tests on the meters at manufacture’s works at any
time, prior to dispatch, to verify compliance with
the specification/ standards.
b) Manufacturer should have all the facilities/
Inspection and acceptance equipments to conduct all the acceptance tests
18.3
testing during inspection. All the testing equipment should
be calibrated.
c) Stage and / or final inspection call intimation shall
be given at least 15 days in advance to the
purchaser.
d) For RMU refer RMU specification part
Stage inspection of Purchaser shall inspect transformers at the core and
18.3.1
transformer coil assembly stage at the manufacturer’s premises.
The sequence of testing shall be as follows
a) Visual and dimension check for completely
assembled transformer.
b) Measurements of voltage ratio.
c) Measurements of winding resistance at principal
tap and two extreme taps.
Final inspection of
18.3.2 d) Vector Group and polarity test.
transformers
e) *Measurements of insulation resistance and
polarization index.
f) Separate sources voltage withstand test.
g) Measurement of iron losses and exciting current at
rated frequency and 90%, 100% and 110% rated
voltage.

Page 49 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

h) Induced voltage withstand test.


i) Load losses measurement.
j) Impedance measurement of principal tap (HV and
LV) of the transformer.
k) Measurement of Iron loss (to be repeated if type
test are conducted).
l) Measurement of capacitance and Tan Delta for
HV and LV bushings and Tan Delta for
transformer oil (for all transformers).
m) Oil leakage test on assembled transformer
n) Magnetic balance test.
o) Power frequency voltage withstand test on all
auxiliary circuits
p) Measure of zero seq. impedance (Cl. 16.10 IS
2026 Part I).
q) Measurement of acoustic noise level (Cl. 16.12 of
IS 2026 Part I).
r) Measurement of harmonic level on no load
current.
*Insulation resistance measurement shall be carried
out at 5kV for HV and 1kV for LV. Value of IR should
not be less than 2000 Mohms[R7]. Polarization Index
(PI = IR10min/IR1min) should not be less than 1.5 (If
one minute IR value is above 5000 Mohms and it is not
be possible to obtain an accurate 10 minutes reading,
in such cases polarization index can be disregarded as
a measure of winding condition.)
As per IEC 62271-202 and relevant IS/ IEC of
equipment.
a) Visual check
b) Dimensional and sheet thickness check
c) Verification of Wiring & BOM
d) Paint thickness inside and outside of PSS
enclosure.
e) Functional test
i. Operation of switchgear and control gear.
ii. Mechanical operation and alignments of PSS
Final Inspection of package
doors.
18.3.3 substation after complete
iii. Fixing of insulating barriers.
assembly
iv. Voltage indication check
v. Checking of temperature and liquid level of the
transformer.
vi. Fitting of earthing devices.
vii. Cable testing
viii. Replacement of LTCT
ix. Operation of transformer tap changer
x. Operation of illumination system
xi. Trip function of HV switchgear.
f) IR test

Page 50 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

g) HV test on power circuit


h) HV test on auxiliary circuits
i) Operational and interlocks check
a) Visual, dimension, wiring & BOM check.
Acceptance Test of LT Panel / b) Operational check.
18.3.4
APFC Panel c) IR Test.
d) HV Test
18.4 Special acceptance tests
Temperature rise test shall be carried out on 01 no
18.4.1 Transformer transformer of each rating randomly selected from the
offered lot.
Temperature rise test of PSS along with transformer
18.4.2 PSS
as per IEC 62271-202.
18.5 Right to waive off tests Reserved by Purchaser

19.0 Shipping, Handling and Site support


Against corrosion, dampness, heavy rains, breakage
19.1 Packing Protection
and vibration
Packing for accessories and Robust wooden non returnable packing case with all
19.2
spares the above protection & identification Label
On each packing case, following details are required:
a) Individual serial number
b) Purchaser's name
c) PO number (along with SAP item code, if any) &
date
d) Equipment Tag no. (if any)
e) Destination
Packing Identification Label f) Manufacturer / Supplier's name
19.3
(Anodized Aluminum Plate)
g) Address of Manufacturer / Supplier / it’s agent
h) Description of PSS.
i) Country of origin
j) Month & year of Manufacturing
k) Case measurements
l) Gross and net weights in kilograms
m) All necessary slinging and stacking instructions
The seller shall be responsible for all transit damage
19.4 Shipping
due to improper packing.
a) Manufacturer instruction shall be followed.
b) Detail handling & storage instruction sheet /
19.5 Handling and Storage
manual to be furnished before commencement of
supply.

Page 51 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

20.0 Deviations
Deviations from this Specification shall be stated in writing with the tender by
reference to the Specification clause/GTP/Drawing and a description of the alternative
20.1
offer. In absence of such a statement, it will be assumed that the bidder complies fully
with this specification.

21.0 Drawings Submission


21.1.0 To be submitted along with bid The seller has to submit following:
21.1.1 GA drawing (Complete assembly, RMU, transformer, LT panel + other items)
21.1.2 BOM of Packaged substation
21.1.3 Calculation for sizing of Transformer
21.1.4 Sizing Calculation of busbar in support of its Guaranteed S.C. rating / Capability
Guaranteed technical particulars (GTP) of Packaged substation in the format as per
21.1.5
annexure ‘C’
21.1.6 Clause wise deviation sheet as per clause no. 20.0
Catalogues & manuals for Package substation + RMU + Transformer + LT switchgear
21.1.7
items + APFC
User manual for Hermetically Sealed Transformers. The manual must be provided
21.1.8 with, but not limited to, maintenance schedule, frequency & method of oil- sampling,
procedures for oil-filling & oil-filtration, etc.
21.1.9 Quality plan for Packaged substation.
21.1.10 Type test reports as per clause 18.1 of this specification.
Recommended spare parts and consumable items for five years of operation and
21.1.11
spare parts catalogue with price list
After award of contract, Seller has to submit following drawings for buyer’s Approval
21.2.0
(A) / Reference (R)
21.3.1 Program for production and testing (A)
21.3.2 GTP of Packaged substation as per annexure ‘C’ of this specification.
21.3.3 Deviation sheet, in case of any deviations finalized in technical bid evaluation.
21.3.4 Design calculations for transformer
Detailed GA drawing(s) (Complete assembly, RMU, transformer, LT panel + meter
21.3.5
box + other items)
Wiring/ schematic drawings (Complete assembly, RMU, transformer, LT panel +
21.3.6
APFC + meter box + other items)
21.3.7 Drawing details of Name plates, danger plates, BSES insignia, instruction sheets etc.
21.3.8 Drawings of cable cleats/ clamps.
21.3.9 Foundation drawing(s).
21.3.10 BOM of Packaged substation
Quality plan Packaged substation, RMU, Transformer, LT panel, APFC (panel and
21.3.11
units etc.
21.3.12 Installation, commissioning manual for all items in Packaged substation. (for

Page 52 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

information)
Operation & maintenance manual for all items in Packaged substation. (for
21.3.13
information)
21.3.14 Transport / Shipping dimensions with weights, wheel base details, un tanking height
21.4 Submittals required prior to dispatch
21.4.1 As built Drawings
21.4.2 Inspection and test reports, carried out in manufacturer’s works
21.4.3 Test certificates of all bought out items
21.4.4 Operation and maintenance Instruction as well as trouble shooting charts/ manuals
21.5 Drawing and document sizes Standard size paper A3, A4
Number of Documents required at 4 hard copies + 2 soft copies in CD
21.6
different stages Format at each stage
Duly signed & stamped copies of the drawings / documentation are required to be
Note :
submitted to BSES for approval.

Annexure A Service Conditions

The package substation shall be designed & tested to operate satisfactorily under following
conditions -
Sr No Description Data by purchaser
1. Location Delhi
2. Reference design ambient temperature 40°C for Delhi
3. Maximum ambient temperature 50°C for Delhi
4. Relative humidity 85% for Delhi
5. Seismic zone Zone IV for Delhi

Page 53 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Annexure B Technical Specification for transformer oil

Transformer oil shall be new and conform to the following requirements:


1.0 Codes & standards
Latest revision of following codes & standards with all amendments –
Standard no Title
1.1 IS 335 New insulating oils
1.2 IS 1783 Drums for oils

1.1 Properties
The insulating oil shall have following features [R7]:
S.No. Item description Specification requirement
2.1 Appearance of oil Clear, free from sediment and suspended matter
Viscosity Max. 15 mm2 /s at 40°C
2.2
1800 mm2 /s at 0°C
2.3 Pour Point, Max -10°C
2.4 Water content, Max 30 mg/Kg
2.5 Breakdown voltage
i) New unfiltered oil. Min. 30 kV
ii) After filtration Min. 70 kV
2.6 Density Max. 0.895 g/ml at 20°C
2.7 Dielectric dissipation factor Max 0.005 at 90 °C,
2.8 Particle Content Value to be provided by the vendor
2.9 Acidity Max 0.01 mg KOH/g
2.10 Interfacial tension at 27°C Min 40 mN/m
2.11 Total sulphur content Value to be provided by the vendor
2.12 Corrosive sulfur Not-corrosive
2.13 Potentially Corrosive sulfur Not-corrosive
2.14 DBDS Not detectable (<5 mg/kg)
2.15 Inhibitor Not detectable (<0.01%)
2.16 Metal Passivator Not detectable (<5 mg/kg)
2.17 Other addivites Type and concentration of additives to

Page 54 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

be provided by the vendor


2.18 2-furfural and related Compounds Not detectable (<0.05 mg/kg) for each
content individual compound
2.19 Oxidation stability
a) Total acidity, Max 1.2 mg KOH/g
b) Sludge Max 0.8%
c) DDF at 90 °C, Max 0.5
2.20 Gassing Tendency Value to be provided by the vendor

2.21 ECT Value to be provided by the vendor


2.22 Flash point Min. 135°C,
2.23 PCA content Max 3%
2.24 PCB content Not detectable (<2 mg/Kg)
2.25 Test As per IS 335-2018

Annexure C Guaranteed Technical Particulars (Data by Supplier)


i. Bidder shall furnish the GTP format with all details against each clause.
ii. Bidder shall not change the format of GTP or clause description.
iii. Bidder to submit duly filled GTP in hard copy format with company seal.
Data to be filled by
Sr. No. Description
Manufacturer
1 Manufacturer Name
2 Manufacturer Address
2.1 Telephone no
3 Manufacturer contact person
Manufacturer brand name (Give catalogue
4
reference)
Conformance to specification Yes/No
If NO for above, Submission of clause wise
Yes/No
deviation sheet
5 11kV RMU
1 11kV RMU, 630A
2 Equipment make
Equipment type / brand name
Conformance to design standards as per
3 Yes/No
specification clause no 2.0 –

Page 55 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Conformance to specification clause no 3.0


4 Yes/No
to 17.0 –
If NO for pt 3 or pt 4 above, Submission of
5 deviation sheet for each specification clause Yes/No
no –
6 Panel overall dimensions in mm
Width (measured from front)
Depth
Height
7 Panel weight in kg
8 Panel extensible on both sides – Yes / No
9 Panel enclosure protection offered
Panel tested for internal arc (Cable & other
10
compartments) –Yes / No
11 Heat generated by the panel in Kw
12 Insulation level for complete panel
12.1 Impulse withstand (Kv peak) -70kvp min
Power frequency withstand (Kv rms) – 28kv
12.2
min
13 Bus bar
13.1 Material & grade
13.2 Bus bar cross section area in sq mm
Bus bar rated current in amp
i) at designed 50 deg.C ambient
13.3
{R9}
at 50 deg.C ambient
Max temperature rise above reference
13.4
ambient of 40 deg C
Short time current withstand capacity for 3
13.5
seconds (in KA)
13.6 Bus bar clearances in mm P-P / P-E
13.7 Bus bar with insulation sleeve / barriers
13.8 Bus bar support insulator type
13.9 Bus bar support insulator voltage class
Bus bar support insulator minimum
13.10
creepage distance / mm
13.11 Earth bus bar material
13.12 Earth bus bar size
14 Circuit breaker type – SF6 or VCB
14.1 Rated voltage & frequency

14.2 Rated current in amp

Page 56 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Rated breaking current – KA rms


14.3
symmetrical
14.4 Short time withstand capacity in KA for 3 sec

14.5 Rated making current - KA peak


Breaker total opening time at rated breaking
14.6
capacity (in milliseconds)
14.7 Number of breaks per pole
14.8 Total length of contact travel in mm
No of circuit breaker operation cycles (close 25% rated current -
& open) guaranteed at rated current, 50% rated current -
14.9 Electrical endurance class
75% rated current -

100% rated current -

No of breaker opening operations


14.10 guaranteed at rated fault current, Electrical
Endurance Class
No of breaker mechanical operation cycles
14.11 (close & open) guaranteed at zero current ,
Mechanical endurance class
14.12 Contact material
14.13 Operating mechanism – trip free
Manual Spring charge type

14.14 Feeder circuit breaker (FCB) –VCB

14.14.3 Closing coil wattage & rated DC voltage


14.14.4 Trip coil wattage & rated DC voltage
14.15 Transformer CT class, ratio & Vk
15 Load break switch type – SF6 or VCB
15.1 Rated voltage & frequency
15.2 Rated current in amp
Load break switch total opening time at
15.3
rated current (in milliseconds)
15.4 Number of breaks per pole

15.5 Total length of contact travel in mm

15.7 No of LBS close & open operation cycles 25% rated current -
guaranteed at 50% rated current -

Page 57 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

75% rated current -

100% rated current -


No of LBS making operations guaranteed at
15.8 rated fault current, Electrical endurance
class
No of LBS close & open operations
15.9 guaranteed at zero current, Mechanical
endurance class
15.10 Contact material

15.11 Operating mechanism type


Minimum permissible SF6 gas pressure (For
15.13
SF6 type RMU only)
Capacitor type cable voltage indication
15.14 Yes / No
provided?
15.15 Operation counter provided Yes/ No
16.1 Disconnect switch continuous rating (Amp)
Disconnect switch Short time withstand
16.2 Yes / No
rating -20kA for 3 sec minimum
One LBS open operation possible in the
16.3 Yes/No
event of loss of SF6 gas
Cable termination –
17.1 Mm
Height of power terminal from gland plate
17.2 Torque required for tightening terminal lug
Mimic diagram, labels & finish as per cl no
18 Yes / No
12
19 Submission of RMU / component catalogue Yes/No
Unit price for Conversion kit offered
separately for converting the RMU from
20 Yes / No
single cable termination design to double
cable termination design
21 Earth Switch
Minimum number of operations at no load-
21.1
Mechanical Endurance class
Making capacity endurance of earth switch –
21.2
Electrical endurance class
As per make list
22 Self Powered Relay – Make / Model (Relay shall be communicable
with SCADA)
22.1 CT Input
Overcurrent-
IDMT Setting Range 4 element – Over
22.2
Current & Earth fault & steps Earth Fault-

Page 58 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Instantaneous O/C-

Instantaneous E/F-
Over Current – Curves
22.3 Operating Time
Instantaneous
22.4 Pick up Current
22.5 Resetting Current
22.6 Relay Burden
22.7 Time Accuracy
22.8 Tripping Coil O/P – type & duration
22.9 Fault Current Display
No of Fault Current Latching with time
22.10
stamping
22.11 Display Facility / Type
22.12 Operational Indicators
22.13 Potential Free Output Contacts
22.14 Thermal Withstand Capacity of Relay
23 Fault Passage Indicator Over Current and Earth Fault
23.1 CBCT
a Type
b Mounting Arrangement
c CT to indicator connection
d ID of sensor
23.2 Earth Fault Indicator
a Sensing Current
b Sensing Time
c Indication
d Reset Time
e Resetting Facility
f Output Contact
g Contact Rating
h Aux Power Supply
i Degree of Protection
j Mounting Arrangement
k Ambient Temperature
24 Current Transformer- Make
24.1 Ratio
24.2 Burden

Page 59 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

24.3 Accuracy Class


25 Voltage Presence Indicator
Make
Rating
Model No
Terminal Blocks, Disconnecting type fuses
26.8
make
6.0.0 11kv cable from RMU to transformer
6.1.0 Cable size 3CX150 sqmm AYFY Yes/No
6.2.0 Cable rated voltage - 11000v Yes/No
6.3.0 Cable short circuit current capacity for 1 sec kA
6.4.0 Type of insulation - XLPE Yes/No
6.5.0 Outer insulation sheath – PVC with armor Yes/No
6.6.0 Cable termination type & make
250 KVA/400KVA /630KVA/1000KVA
7.0.0
hermetically sealed type transformer
7.1.0 Make
7.2.0 Type - Oil immersed, core type, step down Yes/No

HV winding LV winding
Transformer continuous rating when placed
7.3.0
in package substation enclosure
KVA KVA

HV winding LV winding
7.4.0 Rated voltage ( kV )
11 KV 0.433 KV

HV winding LV winding
7.5.0 Rated current
Amps Amps
7.6.0 Transformer vector group – Dyn11 Yes / No
250KVA/400KVA & 630KVA -
Impedance at principal tap rated current and
7.7.0 4.5.0 % & 1000KVA-5% with IS
frequency, ohm @75 °C
tolerance [R4]
7.7.1 Impedance at lowest tap Ω
7.7.2 Impedance at highest tap Ω
HV winding LV winding
7.8.0 Resistance of the winding at 75°C in ohm
Ω Ω
HV winding LV winding
7.9.0 Zero sequence impedance in ohm
Ω Ω
Guaranteed maximum losses at principal tap
7.10.0 full load and 75°C without any positive
tolerance, kW
7.10.1 No load losses (max.) KW

Page 60 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

7.10.2 Load losses (max.) KW


Total losses (max.) at 50% and 100% load
7.10.3 KW
[R4]
No load loss at maximum permissible
7.10.4 KW
voltage and frequency (approx.),
7.11.0 Temperature rise over reference ambient
7.11.1 Top oil by thermometer °C 35 0C
7.11.2 Winding by resistance °C 40 0C
7.12.0 Efficiency at 75°C and unity power factor
7.12.1 at 100% load
7.12.2 at 50% load
7.12.3 at 25% load
7.13.0 Efficiency at 75°C and 0.8 power factor lag
7.13.1 at 100% load
7.13.2 at 50% load
7.13.3 at 25% load
Load and power factor at which Maximum
7.14.0
efficiency occurs
7.15.0 Regulation at full load at 75°C
7.15.1 at unity power factor
7.15.2 at 0.8 power factor lagging
7.16.0 Regulation at 110% load at 75°C
7.16.1 at unity power factor
7.16.2 at 0.8 power factor lagging
7.17.0 Tapping Off circuit
7.17.1 Capacity Full capacity
7.17.2 Range-steps x % variation
7.17.3 Taps provided on HV winding Yes / No
7.17.4 Rated current of rotary switch 100Amp Yes / No
7.18.0 Transformer Tank Corrugated plate tank
7.18.1 Cooling ONAN
Robust mild steel plate without
7.18.2 Tank material
pitting and low carbon content
7.18.3 Thickness of sides mm
7.18.4 Thickness of bottom mm
7.18.5 Thickness of cover mm
Tank designed and tested for Vacuum,
7.18.6 Yes/ No
Pressure ( Ref: CBIP Manual )
7.18.7 Vacuum mm of Hg. / (KN/m2)
Twice the normal head of oil /
7.18.8 Pressure mm of Hg. normal pressure + 35kN/m2
whichever is lower, As per CBIP

Page 61 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

7.18.9 Is the tank lid sloped? Yes / No


7.18.10 Inspection cover provided Yes / No
7.18.11 Location of inspection cover Yes / No
7.19.0 Core
Premium grade minimum M3 or
7.19.1 Core material grade
better [R4]
7.19.2 Core lamination thickness mm
With insulation coating on both
7.19.3 Insulation of lamination
sides
Design flux density at rated condition at
7.19.4
principal tap, Tesla
Maximum flux density at 12.5 %[R4] over
7.19.5 1.9 Tesla
excitation / over fluxing,
7.19.6 Equivalent cross section area mm²
Guaranteed No Load current at 100% rated
7.20.0
voltage.
7.20.1 HV Amps
7.20.2 LV Amps
Guaranteed No Load current At 110% rated
7.21.0
voltage.
7.21.1 HV Amps
7.21.2 LV Amps
7.22.0 Winding
7.22.1 Type of Winding
7.22.1 HV
7.22.2 LV
7.22.2 Conductor material Electrolytic Copper
Maximum allowed 3.0 A per
7.22.3 Current density (HV/LV)
mm2.
7.22.4 Gauge/area of cross section of conductor
HV mm2
LV mm2
7.22.5 Insulating material type & thickness in mm
HV Turn mm
LV Turn mm
LV Core mm
HV - LV mm
Transformer insulation Polarization Index
7.23.0
value (Min 1.5
Transformer insulation IR value for HV
7.24.0
winding (Min 2000Mega Ohm)
7.25.0 Minimum design clearance, mm

Page 62 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

7.25.1 HV to earth in Air


7.25.2 HV to earth in oil
7.25.3 LV to earth in Air
7.25.4 LV to earth in oil
7.25.5 Between HV & LV in Air
7.25.6 Between HV & LV in oil
7.25.7 Top winding and yoke
7.25.8 Bottom winding and yoke
7.26.0 Transformer Insulating oil
7.26.1 Quantity of oil Ltrs
7.26.2 In the Transformer tank
7.26.3 In each radiator
7.26.4 Total quantity
7.26.5 10% excess oil furnished? Yes / No
7.26.6 Type of Oil
7.27.0 Bushing / Support Insulator
7.27.1 Make
7.27.2 Type
7.27.3 HV side
7.27.4 LV side
7.27.5 Reference Standard
7.27.6 Voltage class, kV
HV side Bushing/ Support Insulator 12 kV
LV side line and neutral bushing/ Support
1.1 kV
insulator
Creepage factor for all bushing / Support
7.27.7 31 mm / kV
Insulator mm/KV
7.27.8 Rated thermal short time current
HV bushing KA
LV line and neutral bushing KA
7.27.9 Weight, Kg
HV bushing KG
LV line and neutral bushing KG
7.27.10 Free space required for bushing removal Mm
HV bushing
LV line and neutral bushing
To 3CX150 mm2 AYFY 11KV By
7.28.0 HV Termination arrangement
screened separable connector kit
7.28.1 Phase to phase clearance , mm
7.28.2 Phase to earth , mm
7.29.0 L.V termination arrangement To 100x12 mm for phase &

Page 63 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

neutral
7.29.1 Phase to phase clearance, 25 mm minimum
7.29.2 Phase to earth clearance , 25 mm minimum
7.30.0 Current Transformer on LV phases
7.30.1 Type
7.30.2 Make
7.30.3 Reference Standard
7.30.4 CT Ratio
7.30.5 Burden, VA
7.30.6 Class of Accuracy / ISF
7.30.7 CT terminal box size
7.31.0 Pressure release device on tank - make
Minimum pressure the device is set to
7.31.2
rupture
Fittings Accessories Each Transformer
7.32.0 Yes/No
furnished as per Clause 7.3.0
Painting: as per clause for the transformer,
7.33.0 Yes/No
cable boxes, Marshalling box
7.34.0 Over all transformer dimensions
7.34.1 Length mm
7.34.2 Breadth mm
7.34.2 Height Mm
7.35.0 Weight data
7.35.1 Core KG
7.35.2 Winding KG
7.35.3 Frame KG
7.35.4 Tank KG
7.35.5 Weight of oil in Tank KG
7.35.6 Total Transport weight of the transformer KG
7.36.0 Transformer total oil volume liters
250/400/630/1000KVA Cast Resin
8.0.0
Transformer
8.1.0 Make
8.2.0 Type- Cast Resin Dry Type Yes / No
HV winding LV winding
Transformer continuous rating when placed
8.3.0
in package substation enclosure KVA KVA

HV winding LV winding
8.4.0 Rated voltage ( kV )
11 KV 0.433 KV
8.5.0 Rated current HV winding LV winding

Page 64 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Amps Amps
8.6.0 Transformer vector group – Dyn11 Yes / No
Impedance at principal tap rated current and
8.7.0 5.0 % with IS tolerance
frequency, ohm @130°C
8.7.1 Impedance at lowest tap Ω
8.7.2 Impedance at highest tap Ω

HV winding LV winding
8.8.0 Resistance of the winding at 130°C in ohm
Ω Ω
HV winding LV winding
8.9.0 Zero sequence impedance in ohm
Ω Ω
Guaranteed maximum losses at principal tap
8.10.0 full load and 130°C without any positive
tolerance, kW
8.10.1 No load losses (max.) KW
8.10.2 Load losses (max.) KW
8.10.2 Total losses (max.), KW
No load loss at maximum permissible
8.10.4 KW
voltage and frequency (approx.),
8.10.5 Total stray loses @ 130° C
8.11.0 Temperature rise over reference ambient
Winding by resistance: Outside the
8.11.1 PSS enclosure / inside the PSS 80°C/ 90°C
enclosure 0 C
Maximum hot spot temperature, Deg.
8.11.2 °C
C
8.12.0 Efficiency at 130°C and unity power factor
8.12.1 at 110% load %
8.12.2 at 100% load %
8.12.2 at 80% load %
8.12.3 at 60% load %
8.12.4 at 40% load %
8.12.5 at 20% load
Maximum hot spot temperature, Deg. at 130°C and 0.8 power factor
8.13.0
C lag
8.13.1 Efficiency %
8.13.2 at 110% load %
8.13.3 at 100% load %
8.13.4 at 80% load %

Page 65 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

8.13.5 at 60% load %


8.13.6 at 40% load %
8.14.0 Maximum efficiency at 130°C %
8.14.1 % Load and power factor at which it occurs
8.15.0 Regulation at full load at 130°C
8.15.1 at unity power factor
8.15.2 at 0.8 power factor lagging
8.16.0 Regulation at 110% load at 1300 C
8.16.1 at unity power factor
8.16.2 at 0.8 power factor lagging
8.17.0 Core
Premium grade minimum M3 or
8.17.1 Core material grade
better [R4]
8.17.2 Thickness of lamination mm mm
8.17.3 Insulation of lamination
Design Flux Density at rated condition at
8.17.4
principal tap, Tesla- 1.6 Tesla (Max)
Maximum flux density at 10 % over
8.17.5 excitation /overfluxing, Tesla -1.73Tesla
(Max)
8.17.6 Equivalent cross section area
Guaranteed No Load current At 100% rated
8.18.0
voltage , Amps
8.18.1 HV
8.18.2 LV
Guaranteed No Load current At 110% rated
8.19.0
voltage, Amps
8.19.1 HV
8.19.2 LV
8.20.0 Type of Winding
8.20.1 HV
8.20.2 LV
8.20.3 Conductor material
8.20.4 Current density Amps/sqmm
HV winding
LV winding
Gauge/area of cross section of conductor,
8.20.5
sqmm
HV
LV
8.21.0 Tapping - Off Ckt Yes / No
8.21.1 Capacity Full Capacity

Page 66 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

8.21.2 Range- steps X % variation


8.21.3 Taps provided on HV winding Yes / No
8.21.4 Tap link Current rating , A
8.22.0 Insulating material and thickness Material Thickness
8.22.1 HV Turn mm
8.22.2 LV Turn mm
8.22.3 LV to Core mm
8.22.4 HV to LV mm
8.23.0 Minimum design clearance, mm
8.23.1 HV to earth in Air mm
8.23.2 LV to earth in Air mm
8.23.3 Between HV & LV in Air mm
8.23.4 Top winding and yoke mm
8.23.5 Bottom winding and yoke mm
8.24.0 Bushing / Support Insulator
8.24.1 Make
8.24.2 Type
8.24.3 Reference Standard
8.24.4 Voltage class, kV
8.24.5 HV side Bushing / Support insulator
LV side line and neutral bushing / Support
8.24.6
insulator
8.24.7 Creepage factor for all bushing mm / KV
8.24.8 Weight KG
8.24.9 HV bushing / Support insulator
LV line and neutral bushing / Support
8.24.10
insulator
Free space required for bushing / Support
8.24.11
insulator removal, mm
8.24.12 HV bushing / Support insulator
LV line and neutral bushing / Support
8.24.13
insulator
Suitable for 3CX150 mm2 AYFY
8.25.0 HV Termination arrangement
11KV
8.25.1 Phase to phase clearance mm
8.25.2 Phase to earth clearance mm
8.25.3 HV side bus bar size
8.25.4 HV Termination height Mm
Suitable to 100x12 mm for phase
8.26.0 L.V termination arrangement
& neutral
8.26.1 Phase to phase clearance, 25 mm minimum
8.26.2 Phase to earth clearance , 25 mm minimum

Page 67 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

8.26.3 LV side bus bar size


8.26.4 LV Termination Height Mm
8.27.0 Current Transformer on LV phases
8.27.1 Type
8.27.2 Make
8.27.3 Reference Standard
8.27.4 CT Ratio
8.27.5 Burden, VA
8.27.6 Class of Accuracy
8.28.0 WT scanner terminal box size
Alarm and Trip contact ratings of protective
8.29.0
devices
Rated / making/ breaking currents , Amp @
8.29.1
Voltage for
8.29.2 Winding temperature scanner
Fittings and Accessories as per Cl. 7.19
8.30.0 (YES / NO)
provided
8.31.0 Over all transformer dimensions
8.31.1 Length mm
8.31.2 Width mm
8.31.3 Height mm
8.32.0 Weight data
8.32.1 Core KG
8.32.2 Frame parts, kG KG
8.32.3 Core and frame, kG KG
8.32.4 Total Winding, kG KG
8.32.5 Core , Frame, Winding, kG KG
8.32.6 Enclosure, kG KG
Total Transport weight of the transformer, KG
8.32.7
kG
Total weight of the transformer with all KG
8.32.8
accessories
8.33.0 Shipping Data
8.33.0 Weight of heaviest package, kG KG
Dimensions of the largest package (L x B x
8.33.0 mm
H)
8.34.0 Surge Arrestor requirement
8.34.1 Type
8.34.2 System Voltage , kV rms
8.34.3 Rated Voltage of Arrestor, kV rms
8.34.4 Continuous operating voltage , kV rms
8.34.5 Maximum Continuous operating voltage, kV

Page 68 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

rms
8.34.6 Nominal Discharge Current, kA peak
8.34.7 Energy Absorption Capability, kJ/kV
8.34.8 Creepage factor
8.34.9 Reference std
8.35.0 WTI Scanner Details
8.35.1 Make
8.35.2 Model no.
8.35.3 No of Channel / Input
8.35.4 Manual submitted
To connect transformer LV side
9.0.0 Low voltage bus bar system
to ACB & to MCCB
9.1.0 Bus bar material tinned copper Yes / No
9.2.0 Bus bar size sqmm
9.3.0 Bus bar continuous current rating Amp
9.4.0 Bus bar insulator voltage class kV
9.5.0 Bus bar droppers size from ACB to MCCB
(40x6 tinned copper)
9.6.0 Maximum bus bar temperature rise
10.0.0 ACB, MCCB As per IS 13947
10.1.0 ACB make
10.1.1 ACB rated voltage 415v +/- 10%
10.1.2[R7] ACB 4 pole Yes / No
10.1.3 ACB continuous current capacity at 415v
amp
50Hz, at 50 deg C
10.1.4 ACB short circuit breaking capacity Ics =Icu
kA
= 50kA minimum
10.1.5 ACB SC making current capacity 100kAp kA peak
10.1.6 ACB short time current withstand capacity
kA
for 1 sec (Icw= 50kA)
ACB rated impulse withstand voltage for
10.1.7
main & aux circuit in kv
10.1.8 ACB closing time in ms
10.1.9 ACB opening time in ms
Guaranteed number of close & open
10.1.10
operations at no load
10.1.11 Guaranteed number of close & open
operations at rated load
10.1.12 ACB dimensions
10.1.13 ACB operating mechanism -Trip free, anti
Yes / No
pumping type, manual as well as motor

Page 69 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

10.1.14 Spring charging motor supply volt


10.1.15 Close & trip coil supply volt
10.1.16 ACB utilization category -B as per IS
10.1.17 ACB indications - ON, OFF & TRIP
10.1.18 ACB operation - manual - ON, OFF by push
buttons
10.1.19 ACB operation – electrical - ON, OFF by
TNC switch
10.1.20 ACB overload, short circuit & earth fault
protection - By static or micro processor
based releases
10.1.21 Inbuilt CT burden, ration & class
10.1.22 Overload release setting range
10.1.23 Short circuit release setting range
10.1.24 Earth fault release setting range
10.1.25 [R7] Display Require , Min last 10 nos
Display & Event Log
fault event log req
10.2.0 MCCB make
10.2.1 [R7] MCCB type -3 pole, one break / pole Yes / No
10.2.2 MCCB - On & OFF by Manual handle Yes / No
10.2.3 MCCB Neutral connection - Fully isolable
link sized for rated current
10.2.4 MCCB rated voltage 415v +/- 10% at 50Hz
10.2.5 MCCB rated continuous current at 50deg
C(after derating)(400 amp & 630A MCCB as 400/630 amp
per enquiry)
10.2.5(i){R6] De rating of MCCB(0% at 50 deg C) Yes / No
10.2.6 MCCB 3 ph short circuit breaking capacity
Ics = Icu =36kA
10.2.7 MCCB 3 ph short circuit withstand capacity,
Icw =8kA for 1 sec
10.2.8 MCCB SC making current capacity
10.2.9 MCCB rated insulation level
10.2.10 MCCB mechanical & electrical endurance as
per IS 13947 / IEC
10.2.11 MCCB category of duty - B as per IS / IEC
Yes / No
947
10.2.12 MCCB indications -ON, OFF & TR
10.2.13 MCCB protection – Microprocessor release
+ earth fault
10.2.14[R6] Tripping characteristic required

Page 70 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Overload setting- Range 60-100%In (Set on


a
95%)
Short Circuit setting- Range 200-1200%In
b
(Set on 300%)

c Earth fault setting To be provided


MCCB Housing- Thermoplastic material
resistant to fire & abnormal heat , non
10.2.15R6]
hygroscopic
MCCB Terminal- Silver coated copper with
10.2.16R6] phase barriers, spreader terminals &
shrouds
10.2.16 R6] MCCB Spreader size & material-
Minimum-50(W)X50(L)X10(D)mm- Cu
suitable for bimetallic joint i.e. for aluminium
bus/cable lug
MCCB Clearances in air- As per table XIII of
10.2.17[R6]
IS 13947-1
MCCB temperature rise limits - As per table
10.2.18[R6]
2 & 3 of IS 13947-1
MCCB Ingress Protection- IP2X Minimum
10.2.19[R6]
(pollution degree minimum 2)
Sealing/padlocking of operating
knob in OFF position
10.2.20 [R6] MCCB additional features Sealing/padlocking of operating
knob in OFF position isolation
suitable with positive contact
Connection to ACB main bus by Cu bar with
10.3.0 Yes / No
double PVC insulation
10.3.1 For 400 amp MCCB
10.3.2 For 630 amp MCCB
Connection to outgoing cables by bus bar
10.4.0 terminals suitable for 2x4CX300sqmm AYFY
1100 volt grade cable
MCCB– 7 nos. for Type–I , 5 nos. for Type–
10.4.1 II & 3 for Type-III & 630 Amp three phase + (YES/ NO)
neutral link
Only for Type II & III- Provisions in LT panel
10.4.2 to increase LT outgoing by 02 no’s by (YES/ NO)
adding MCCB’s in future.
11.0.0 APFC system
11.1.0 Rating of APFC system KVAR
11.2.0 Rated voltage & frequency Volts at 50Hz

Page 71 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

11.3.0 Rated line current of APFC system Amp


11.4.0 Rated capacitance micro Farad
11.5.0 Capacitor steps – Type I: 12x25KVAR?
Yes / No
Type II: 8 X 25 KVAR?
11.6.0 Rated current of each 25KVAR unit Yes / No
11.7.0 Rated capacitance – 25KVAR unit micro Farad
11.8.0 Three phase connection – star / delta
11.9.0 Capacitor dielectric type – APP / MPP
11.10.0 No of series group / capacitor unit
11.11.0 No. of parallel elements / series group
11.12.0 Thickness of PP film in micron
11.13.0 Thickness of Al foil in micron
11.14.0 No. of PP film layers
11.15.0 Maximum voltage stress per each PP film
layer
11.16.0 Discharge device material
11.17.0 Capacitor tank steel thickness mm
11.18.0 Capacitor unit dimension (L x D x H)
11.19.0 APFC dimensions in mm (L x D x H)
11.20.0 APFC system weight in kg
11.21.0 Heat generated by APFC in Kw with all
capacitor steps ON
11.22.0 Operation with over voltage 115% of rated
voltage for 12 hours in a day
11.23.0 Operation with harmonic distortion THD 5%
voltage & current
11.24.0 Maximum permissible over current of
11.25.0 1.3 times rated current continuous
11.26.0 Dielectric loss less than 0.2w / KVAR
11.27.0 Guaranteed minimum capacitor switching
operations (ON/OFF) per year
11.28.0 Maximum temperature rise above ambient of
Deg C
45 Deg C
11.29.0 Residual voltage after de-energiszation & at
60 seconds
11.30.0 Design life of capacitor unit
11.31.0 APFC panel insulation level
11.32.0 1 minute power frequency withstand KV
11.33.0 Impulse withstand voltage KVp
11.34.0 Main bus bar material / size (sqmm)
11.35.0 Main bus bar rated current

Page 72 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

11.36.0 Main bus bar short time withstand


11.37.0 CT make & accuracy class
11.38.0 CT ratio & burden (VA)
11.39.0 APFC relay make / type
11.40.0 APFC relay catalogue enclosed? Yes / No
11.41.0 Data logger make / type
11.42.0 Data logger catalogue enclosed? Yes / No
11.43.0 AC contactor make
11.44.0 AC contactor rating Amp
11.45.0 AC contactor utilization category as per IS
11.46.0 100amp MCCB make
11.47.0 100amp MCCB current breaking capacity
Ics=Icu=35kA
11.48.0 Copper wire size from MCCB to contactor &
capacitor – 35sqmm Cu
Energy meter box as per specification
12.0.0 Yes / No
provided?
13.0 Enclosure for package substation
13.1 Service conditions for outdoor use Yes / No
Material for enclosure – Galvanised Sheet
13.2 steel 2.5mm thick CRCA for all side doors, Yes / No
covers with painting
Enclosure construction -Frame supported
construction with all doors, covers welded
13.3 Yes / No
with steel channel ribs at every 1000mm
minimum
Lifting lugs for site handling / lifting by crane
13.4
- qnty
Doors for RMU compartment & LV
compartment with anti theft hinge minimum
13.5 Yes / No
3 nos., with lockable handle & with
padlocking facility
13.6 Two side covers for transformer Yes / No
compartment bolted with Allen head type
bolts to main frame
Top & other side walls of enclosure welded
13.7
sheet metal
Removable canopy above top cover -2.5mm
13.8 Yes / No
thick sheet metal with 10º slope
Enclosure integral steel base frame ‘I’
13.9
section size
Base frame bottom support pads for fixing
13.10 by bolt to foundation - minimum six numbers Yes / No
to rest on foundation

Page 73 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Enclosure compartments -separate


13.11 compartments for RMU, transformer & LV Yes / No
switchgear/APFC
Separation between RMU & transformer
13.12 Yes / No
compartment by sheet steel 2.5mm thick
Separation between transformer
13.13 compartment & LV compartment by sheet Yes / No
steel 2.5mm thick
Degree of ingress protection against solids &
13.14
water as per IS12063
a IP53 for RMU compartment
b IP34 for transformer compartment [R7]
c IP33 for LV compartment
Louvers on side covers of transformer
compartment & side walls of LV
13.15 compartment with steel wire mesh welded Yes / No
from inside so as to meet IP requirement as
above
Louver area on cover / side wall -1500mm
13.16
height x 1500mm minimum
Exhaust fans mounted for APFC system to
discharge air in transformer compartment -
13.17 Controlled by SPMCB & thermostat to
operate above 35 deg C, 2x150CFM, 1 ph
230v 50Hz
Gland plate for RMU compartment - 2.5mm
13.18 thick MS plate suitable for 3x3c300sqmm
AYFY 11kv cable
Gland plate for LV compartment -2.5mm
13.19 thick MS plate suitable for 10x4c400sqmm
cable + 10x7c2.5sqmm cable
Class of enclosure as per IEC 62271-202 =
13.20 Yes / No
10K
Overall dimensions of package substation
13.21 In mm
(LxWxH)
13.22 Overall weight of package substation Kg
14.0 Enclosure earthing & illumination
Two earth bus connection brought out of
package substation enclosure to earth pad
14.1 for connection to earth pit -Two earth pads
for RMU, transformer & LV compartment
each -One earth pads for transformer neutral
14.2 Earth bus size 50X 6 mm GI flat
Earth bus fault current capacity 26.3kA for 1
14.3
sec

Page 74 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

Earth connection of all covers, doors &


14.4 structural parts to GI bus by metallic jumper Yes / No
connection
Earth connection of RMU, ACB &
14.5 transformer body parts to GI bus by two
numbers of 50x6mm GI flat per equipment
14.6 Earth bus identification shown by letter ‘E’ Yes / No
RMU, transformer & LV Compartment
14.7 illumination by 36w CFL fixture controlled
through SPMCB & door limit switch
RMU, transformer & LV compartment power
14.8 socket - 5/15amp 3 pin socket controlled
through 15 amp SPMCB
14.9 Paint shade external for enclosure
14.10 Paint shade internal for enclosure
14.11 Paint material & thickness
Name plate & labels as per specification
14.12 Yes / No
provided?
14.13 Smoke Detector Yes / No
14.13.1 Make
14.13.2 No Of Aux Contacts
14.14 Hooter Yes / No
Type test report submitted with GTP for
15.0 RMU, transformer, ACB, MCCB, APFC Yes / No
system?
GA drawing of package substation submitted
15.1 Yes / No
with GTP?
15.2 Bill of material submitted with GTP? Yes / No
Clause wise deviation to technical
15.3 Yes / No
specification submitted?

Bidder / Vendor seal / signature ---------------------------


Name of the bidder
Address of bidder
Name of contact person
Telephone no & email id

Annexure D - CRGO & Testing Points [R7]

In addition to the BSES specification following points to be verified during


manufacturing/inspection.
1 Transformer core shall be low loss, non-ageing, high permeability PRIME GRADE

Page 75 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

CRGO with M3 Grade or better with max thickness of 0.23mm and with max core loss
of 1 W/Kg, perfectly insulated and clamped to minimize noise and vibrations.
2 Following stage inspections will be carried out by purchaser or by third party engineers
appointed by BSES :
2.1 Verification & inspection of the mother coil at port & putting stamp & seal may be
inspected by BSES.
2.2 Reconciliation of mother coil by checking stamp & seal at factory before slitting. One
sample of CRGO to be sealed for testing at ERDA/CPRI. Following Tests shall be
conducted on the sample:
1) Specific core loss measurement
2) Magnetic polarization
3) Magnetic permeability
4) Specific core loss measurement after accelerated ageing test
5) Surface insulation resistivity
6) Electrical resistivity measurement
7) Stacking factor
8) Ductility(Bend test)
9) Lamination thickness
10) Magnetization characteristics (B-H curve)
2.3 Bidder should have in house core cutting facility for proper monitoring & control on
quality.
In case it is done outside cutting shall be done in presence of BSES.
2.4 Following documents to be submitted during the stage inspection :
2.4.1 Invoice of supplier
2.4.2 Mills test certificates
2.4.3 Packing list
2.4.4 Bill of lading
2.4.5 Bill of entry certificates by customs
2.4.6 Core material shall be directly procured either from the BSES approved manufacturer
or through their authorized service centre/distributor and not through any contractor.
2.5 Bidder should have hydraulic core lifting facility to avoid any jerk at the time of core
building.
2.6 BSES may appoint recognized testing authority like CPRI /ERDA with their
instruments & engineer’s team and measure no load loss, load loss and percentage
impedance of the transformer at supplier’s works at our own cost. Bidder shall agree
and give them full cooperation during their stay & testing at shop floor. The losses &
impedance values so obtained will be considered as final.
2.7 Bidder should have in-house NABL accredited testing facility.

Annexure E Recommended spares (Data by supplier)

List of recommended spares as following


Sr No Description of spare part Unit Quantity
1 No
2 No
3

Page 76 of 77
SP-PSSC-38-R7

Technical Specification For 11 kV Packaged Substation

4
5
6
7

Annexure F: BOM for 250 kVA PSS [R7]

Bill of Material for 11kV, 250 kVA PSS with (2 X 2 X 2 mtr)


A 3 Way RMU (2 LBS + 1 VCB) 1 No.
B 250 kVA Dry/Oil DT 1 No.
C LT Switchgear
Incomer 400 A 4P LT ACB 1 No.
Outgoing 250A 3P MCCB 2 No.
D Outdoor Enclosure

Outdoor type enclosure having modular construction of CRCA sheet


metal in corrugated type wall design for better heat dissipation and
providing robust construction. The enclosure shall have IP54 degree of
protection for HT & LT switchgear compartment & IP34 degree of
protection for Transformer compartment. The enclosure exterior shall be
1 Set
painted with epoxy based powder paint (colour RAL 7032). Each
compartment will be provided with the door and pad locking arrangement.
Doors of transformer compartment are fitted with Arc reflectors from the
inside for providing better safety. The Compartment illumination lamp
with door operated switch shall be provided for each compartment.

300 mm above
E Height of all equipment (RMU,LT panel & DT) from FGL from FGL
F No foundation requirement , base frame / Pad mounted Req.
G Smoke detector with flag type auxiliary relay Req.
Other material like (MFM, Fire Ball, Cable sealing compound, Space for
H DT meter Installation, etc.) As per Spec

Page 77 of 77
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

1.0 Scope of work


A. 11kV Manual RMU shall be supplied as per the specification. All the manual RMU shall be
compatible for retrofit solution of motorized RMU in future
B. Metering Cubicle (Only with Outdoor RMU, if specified with purchase requisite) [R6]
C. For scope of supply, refer annexure – A

2.0 Codes & standards


Materials, equipment and methods used in the manufacture of switchboards shall conform to the
latest edition of following –
S No. Title
Indian Electricity Rules With latest amendments

Indian electricity act IE act 2003

A.C. Metal Enclosed Switchgear and Control gear for Rated Voltages
IS 3427
Above 1 Kv
IS 9920 part 1,3 & 4 High voltage switches above rated voltage 1kv
IS 13118 General requirements of circuit breakers above rated voltage 1kv
IS 3231 Electric Relays for Power System Protection
IEC 60265 part 1 High voltage switches
IEC 60056 High voltage alternating current circuit breakers
IEC 60059 Preferred current ratings of high voltage switchgear
IEC 60185 Current transformers
IEC 60694 Specification for high voltage switchgear
IEC 60298 AC metal enclosed switchgear
IEC 60129 Ac disconnector and earth switches
IEC 60529 Classification of degrees of protection provided by enclosures
IEC 60255 Electrical relays

In the event of direct conflict between various order documents, the precedence of authority of
documents shall be as follows -
i. Guaranteed Technical Particulars (GTP)
ii. Specification including applicable codes & standards
iii. Approved Vendor Drawings
iv. Other documents
3.0 Electrical Distribution System Data
3.1 Supply 3 phase AC, 3 wire
3.2 Voltage 11000 volt ±10%

Page 6 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

3.3 Frequency 50 Hz ± 5%
3.4 System neutral Earthed at upstream 11kv source

4.0 11kv RMU System layout

As per scheme given in Annexure E & type as per


4.1 RMU Configuration
Purchase requisition

4.2 Extensibility Both side extensible (L.H.S. and R.H.S.) [R7]


Load break switch,
4.3 Circuit breaker & earth All shall be non draw out type, fixed position
switch in RMU panel
Insulation medium for
4.4.1 SF6 gas or Dry air in sealed metallic tank
panel

4.4.2 Breakers SF6 gas or Vacuum type (with disconnector & earth switch)

4.4.3 Load break switches SF6 gas or Vacuum type (With Earth Switch)
i) Separate for each breaker
Arc interruption
4.5 ii) Arc interruption chamber of breakers shall be separate
chamber for breaker
from the main insulated tank. (Desirable feature)
Maximum dimensions
4.6 for a 3 way panel (1 CB
+ 2 LBS)
Width (measured from
4.6.1 1250 mm
front)
4.6.2 Depth 800 mm
4.6.3 height 2000 mm

5.0 RMU panel construction

CRCA/GI Metal enclosed, framed, Compartmentalized


5.1 Panel type
panel construction {R9}
Indoor, non air conditioned environment / Outdoor with
continuous ambient temperature of 50 deg C and shall be
5.2 Service Location
suitable for external climatic condition Resistant to water
ultraviolet radiation (Canopy for outdoor application)
5.3 Mounting Free Standing
Overall Enclosure IP4X minimum, vermin proof
5.4
Protection IP 54 (For outdoor duty)

Page 7 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Front access with anti theft hinge arrangement, Minimum


5.5 Doors three hinges. Hinges arrangement shall ensure that door
cannot be removed.
Bolted for rear access, with handles. Support for handle
shall be provided at suitable place on RMU body. [R5]
5.6 Covers All the accessible bolts / screws shall be vandal proof. One
set of required Special tools per RMU (if any) shall be in the
scope of supply.
CRCA/GI Metal enclosed, framed, Compartmentalized
panel construction. CRCA thickness shall be 2 to 2.5 mm
5.7 Construction subject to type test report from CPRI/ERDA. Sheet
thickness below 2 mm in any part of RMU shall not be
accepted {R9}

Base frame shall be made with 75mm ISMC/ISA channel


for both Indoor and Outdoor type RMU. Proper Bolted fixing
arrangement shall be provided for erection on RCC
foundation. Also, base frame shall be painted with 2 coats
5.8 Base frame of anti rust red oxide and 2 coats of bitumen paint shall be
provided. {R9}Adjustable HDPE clits as cable supporting
clamps for each power cable (to suit the cable size from
150 to 400 sq mm PILC / XLPE cable. Exact size shall be
provided during drawing approval stage.), also cleat shall
be adjustable vertically. {R9}
5.9 Lifting lugs Four numbers
Bottom
3mm metallic, removable type & split type in two parts, with
5.10 Cable Entry 1no. 90 mm diameter knocks out punch/hole in the centre
(For double cable boxes, Un-drilled gland plate to be
supplied. Approval should be taken for the same during
drawing submission)
3c x 150 / 240 / 300/400 sq mm Aluminum conductor
5.12 Cable type & size
XLPE/ PILC with armor & PVC outer sheath {R9}

Terminals for 11kv Suitable for Ring Type Bimetallic lug as per annexure F
5.13
cable termination [R5]

5.13.1 Right angled boots Single piece cold shrink type per bushing

5.13.2 Brass Nut bolt M16 size

5.13.3 Bimetallic washers Required

5.13.4 Termination type suitable for heat shrinkable type

For Indoor / Outdoor : Min. height from gland plate shall be


5.13.5 Termination height
900mm [R5]

Page 8 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Copper with sleeve (Sizing Calculation to be submitted in


5.14 Bus bar
support of its Guaranteed S.C. rating / Capability) {R9}

Bus bar continuous


5.14.1 630amp ( at designed 40 deg.C ambient) {R9}
rated current

Bus bar short time


5.14.2 20 KA for 3 sec (R5)
withstand capacity
Bus bar support
5.14.3 SMC / DMC resin
insulator material
Maximum temperature
5.14.4 rise above reference In line with Table 3 of IEC60694
ambient 40 deg C

5.15 Earth bus bar Tinned Copper flat sized for rated fault duty for 3 sec {R9}
Earth bus internal
connection to all By 2.5 sq mm copper flexible wire, Earth connection point
5.16
non current carrying maximum 1 meter away from cable test facility
metal parts
Earth bus external
Studs on both sides with holes for M10 bolt + hardware to
5.17 connection to
readily receive purchaser earth connection
owners earth

5.18 Cooling arrangement By natural air without fan

Multi strand flexible color coded PVC insulated Cu wire 1 sq


5.19 Panel internal wiring mm (SCADA) / 2.5 sq mm (for CT’s) 1100 volt grade (AC-
black, DC – grey, Earth – green) with ferrules at both ends.

Hardware (Nut, bolts & Stainless steel (Except termination nut-bolts


5.20
handle) which are Brass / Tinned Copper)

5.21 Gasket Neoprene rubber

Marshalling terminal 1 Sq mm, Nylon 66 material, push on type + 20% spare in


5.22
blocks each row of TB. {R9}

5.23 Panel cover fixing bolts Allen head 6mm with hexagonal slot

5.24 Padlock facility Required for all earth switches & all handles

Bushings for future Should be duly insulated & covered with


5.25
extensions of RMU metallic covers in unused condition
To ensure operator’s safety, design should ensure that
gases / flames generated during flash over / blast in any of
5.26 Explosion vents
the compartment, must not come out from the front of RMU
as well shall not go to adjacent cable compartment. Internal

Page 9 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

arc test report (for Cable compartment & other


compartments) must be submitted to support above, along
with RMU GA drawing indicating these vents. There shall
not be any type of holes, gaps etc on the walls of cable
termination compartment. [R5]
< 0.1% of total mass. Pressure of SF6 gas shall be above
5.27 SF6 gas annual Loss
the operating limit throughout the life of the equipment.

6.0 Load break switch (LBS) / Isolator


6.1 Type Three poles operated simultaneously by a common shaft
Arc interruption in
6.2 SF6 or Vacuum
dielectric medium
6.4.2 Clause deleted. [R5]
Continuous rating of
6.6.1 630 Amp at design 40 deg C ambient
LBS
Short time withstand
6.6.2 20 KA for 3 sec [R5]
capacity
6.7 Fault making capacity 50 kA peak [R5]
Minimum number of
operations at rated Mechanical Endurance – Class M1( 1000 operations)
6.8
current (as per IEC Electrical Endurance – Class E3 (100 operations) [R5]
62271-102)
Minimum number of
operations at rated fault
6.9 Class E3 (Min 10 operations) [R5]
current (as per IEC IEC
62271-102 )
Fault passage indicator To be provided on right hand side of one LBS for panel type
(FPI) (For both Earth 1CB + 2 LBS. For all other configuration of RMU, FPI to be
6.10
fault and Over Current provided on all LBS. Wherever, there are two cables per LBS,
Protection) [R8] two FPI needs to be considered for that particular LBS
CBCT – Split open type suitable for mounting without
6.10. 1 Earth Fault Indicator
disconnection of cable.

Cable connection of FPI with CBCT shall be of pre moulded


Connection of CBCT
6.10.2 type on the CBCT side. Cable shall be 2.5 sq.mm cu cable or
with FPI
{R9}

Page 10 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Digital type and shall operate as the current exceeds the set
value. Flash indication for identifying faults with red LED with
Fault Passage Indicator
one flash for every one sec. Test & rest button 1 NO + 1 NC
(For both Earth Fault
6.10.3 potential free contact for remote indication FPI power supply
and Over Current
unit shall use lithium battery with minimum life of 1000 blinking
Protection) [R8]
hours , so that FPI shall continue to function even after main
feeder has tripped.

6.10.4 Data by Purchaser


6.10.4.1 System Fault Level 2kA – 8.75kA
6.10.4.2 Type of Grounding Solidly Grounded
6.10.4.3 Fault clearing time 100ms
6.10.4.4 Cable Type PILC / XLPE , 70 sq.mm to 400 sq.mm {R9}
6.10.4.5 Earth Fault Indicator
6.10.4.5.1 Sensing Current 100 to 400A {R9}
6.10.4.5.2 Sensing Time 30 to 100 ms in steps of 10ms.
6.10.4.5.3 Reset Time 0.5 -1-2-3-4 hr
a) Self rest after reset time
b) Self rest after restoration of voltage
6.10.4.5.4 Resetting Facility
c) Manual
d) Remote resetting
6.10.4.5.5 Contact Rating 1A at 230 V
6.10.4.5.6 Degree of Protection IP 54
6.10.4.5.7 Mounting Arrangement Surface or Flush Mounting
6.10.4.5.8 Ambient Temperature -20 to 50 Deg C {R9}

7.0 Circuit breaker (TCB / FCB)

7.1.1 Type Three pole, operated simultaneously by a common shaft


Transformer circuit
7.1.2 For controlling transformer, manual operation only
breaker -TCB
Feeder circuit breaker - For controlling cable feeder, manual operation. Remote trip
7.1.3
FCB operation by SCADA
Arc interruption in
7.2 Vacuum Bottle (R5)
dielectric medium
Operating mechanism -
7.3.1 Manual spring charged stored energy type
TCB
Operating mechanism - Manual spring charged stored energy type, remote electrical
7.3.2
FCB close / open operation possible.
Emergency trip / open On panel front with Protective flap to prevent any accidental
7.4
push button tripping of breaker. [R5]
Continuous rating at
7.5.1 630amp
design 40 deg C

Page 11 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

ambient {R9}
Short time withstand
7.5.2 20 KA for 3 sec (R5)
capacity
Minimum number of
operations at rated Mechanical Endurance – Class M1( 2000 operations)
7.6
current (as per IEC Electrical Endurance – Class E2 ( R5)
62271-100)
7.7 Fault making capacity 50 KA peak (R5)
7.8 Fault breaking capacity 20 KA Minimum (R5)
Maximum number of
operations at rated Electrical Endurance – Class E2 . To be guaranteed by
7.9
Fault current (as per manufacturer with authorized lab test reports (R5)
IEC 62271-100)
Breaker status auxiliary
7.10 2NO + 2NC wired to terminal block
contact
1. 75-400 / 1 amp for TCB/ FCB. {R9}
2. Considering three core cable terminations, mounting
flexibility shall be provided for CT’s (in horizontal &
vertical direction both). Additionally, CAUTION
marking (by sticker/ paint) shall be provided to avoid
7.11 Current transformer
CT’s installation above the screen of cable. (I.e.
earth potential point.)
3. Position of CTs inside compartment shall be
adjustable in vertical and horizontal direction {R9}

7.12 CT accuracy class 5P10 minimum {R9}


Self powered, Microprocessor based Numerical relay (with
LCD display), IDMT over current / earth fault protection with
7.13 Protection relay high set element, manual reset type Relay mounting flush to
panel front.
Relay shall be communicable for automation purposes
Relay auxiliary contacts
Potential free contact 1NO + 1NC wired to
7.14 for remote
terminal block
indication
Shunt trip 230v AC (for
WTI trip & door limit
To be wired to terminal blocks (If the functional requirement
switch of Dry type
7.15 is achieved by the Protection relay, then shunt trip is not
transformer) & for
required.
remote trip from
SCADA.

7.16 Breaking Timing 40 to 60 ms {R9}

8.0 Earth switch (ES)

Page 12 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Three Pole (ON, OFF and Earth), operated simultaneously


8.1 Type by a common shaft, for each Circuit breaker & Load break
switch.
Switching in dielectric
8.2 Dry Air in sealed medium or SF6 gas
medium
Operating mechanism
8.3 Manual
for close & open
8.4 Fault making capacity 50 kA (Desirable)
8.5 Auxiliary contacts 1NO+1NC wired to terminal block
Disconnect switch (if
Desirable to be located on purchaser cable connection side
8.6 provided in series with
of vacuum bottle
vacuum bottle)
Minimum number of
Mechanical Endurance – Class M0( 1000
8.7 operations at no load
operations) [R5]
(as per IEC 62271-102)
Making capacity
endurance of earth
8.8 Class E2 (Min 5 operations) [R5] {R9}
switch (as per IEC
62271-102 )

9.0 Requirements of sealed housing live parts


Stainless steel enclosure suitable for IP67. Metal thickness
9.1 Enclosure shall be 3mm. {R9}
SF6 gas pressure low
9.2 alarm To be given
Provision for SF6 gas To be given (For ‘sealed for life’ design of RMU, this is not
9.3 filling applicable)
Provision for SF6 gas
pressure
9.4 indication Digital Manometer with non return valve
Arc interruption method
for SF6
breaker / Load break
9.5 switch Puffer type / rotating arc type
Potential free contacts
for SF6 gas
9.6 pressure low 1NO +1NC (Desirable)

10.0 Operational interlocks

10.1.1 Interlock type Mechanical


Load break switch &
10.1.2 respective earth switch Only one in ‘close’ condition at a time
Circuit breaker &
10.1.3 respective earth switch Only one in ‘close’ condition at a time

Page 13 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Prevent the removal of


respective cable covers
if load break switch or
10.2 circuit breaker is ‘ON’ Electrical / Mechanical
Prevent the closure of
load break switch or
circuit breaker if
respective cable cover
10.3 is open Electrical / Mechanical
10.4 ® clause deleted
Cable test plug for
LBS/CB accessible
only if Earth switch
10.5 connected to earth Mechanical

11.0 Indication & signals (for Local)


Operation counter on
To be provided for each LBS & Circuit breaker, with minimum
11.1 front / Inside the RMU
four digits & non resettable type
LT chamber
Cable charge status
Capacitor type voltage indicators with LED on all the phases
11.2 indication for all LBS &
(Shall be clearly visible in day light)
CB
Spring charge status
11.3 On front for breaker
indication
Earth switch closed
11.4 indication (For Each On front
LBS)
Load break switch
11.5 Green for OFF / Red for ON
ON/OFF indication
Circuit breaker On/OFF
11.6 Green for OFF / Red for ON
indication
Circuit breaker
11.7 protection relay Flag
operated on fault
Fault passage
11.8 Flag
indication on LBS
Status signals to
SCADA-to be wired to
11.9 2NO + 2NC
marshalling terminal
block
11.9.1 LBS close / open potential free contacts
LBS & CB Earth Switch
11.9.2 potential free contacts
close /open
11.9.4 CB close / open potential free contacts
Protection relay
11.9.5 potential free contacts
operated

Page 14 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

11.9.6 FPI operated potential free contacts


11.9.7 SF6 gas pressure low potential free contacts (Desirable)
11.10.1 Commands from LBS close / open
11.10.2 SCADA- to be wired FCB close / open
to marshalling terminal
11.10.3 block FPI Reset

12.0 Mimic diagram, labels & finish

1. Mimic diagram (Shall not be accepted with Stickers)


[R5]
Mimic
2. On panel front with description of function & direction
12.1 of operation of handles/buttons
Operating instruction chart and Do’s & Don’ts in Hindi / local
language to be displayed on left / front side of panel
Operating Instructions
enclosure on anodized Al Sheet 16SWG, duly affixed on
panel.
Name plate on panel
12.2 Fixing by rivet only
front
12.2..1 Material Anodized aluminum 16SWG / SS
12.2.2 Background SATIN SILVER
Letters, diagram &
12.2.3 Black
border
12.2.4 Process Etching
Month & year of manufacture, equipment type, input &
12.2.5 Name plate details output rating, purchaser name & order number, guarantee
period
The label shall be riveted and not pasted on the panel
Labels for meters &
12.3 compartment door. Preferable the labels shall be engraved
indications
on the plate.
Danger plate on front & Anodized aluminum 16 SWG with white letters on red
12.4
rear side background
Painting surface
12.5 Shot blasting or chemical 7 tank process
preparation
Powder coated epoxy polyester base grade A, shade -RAL
12.6 Painting external finish
7032, uniform thickness 60 micron minimum
Powder coated epoxy polyester base grade A, shade -white,
12.7 Painting internal finish
uniform thickness 60 micron minimum
Termination Drawing Printed copy shall be fixed/mounted inside each and every
12.8
and Wiring Drawing compartment. {R9}

13.0 Quality assurance

Page 15 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

13.1 Vendor quality plan To be submitted for purchaser approval


Inspection points in
13.2 quality plan To be mutually identified & agreed
Quality – Process
13.3 Audits BSES shall carryout vendor process audits.
13.4 Field quality plan Bidder to submit field quality plan along with the bid
13.5 Spare part list Bidder to submit detailed spare part list along with the bid
13.6 Maintenance manual Bidder to submit maintenance manual along with the bid
Approved sub vendor
13.7 List [R5]
Fault Passage
13.7.2 Indicator pls refer make list
Self Powered O/C &
13.7.4 E/F Relay Ashida ADR241S-761 {R9}
13.7.5 Boots 3M / Raychem/K.D.Joshi

14.0 Inspection & testing

1. Equipment of type tested quality only, including


internal arc test on various compartments like cable
chamber, SF6 gas tank etc.
14.1 Type test
2. Type test certificate to be submitted along with offer
for scrutiny. Type test more than 5 years old will not
be acceptable.
3. a) temperature rise test
b) voltage regulation test
14.2 Routine test As per relevant Indian standard
To be performed in presence of purchaser at manufacturer
works
1. Physical inspection & BOM, wiring check
2. Insulation resistance test (Before & after HV test)
3. HV test for one minute,
4. Operation & interlock check
14.3 Acceptance test
5. Measurement of resistance of main circuit
6. Voltage Indication check
7. Functional testing of Fault passage Indicator for
Alarm
8. Primary current injection test for each circuit breaker
feeder with relay
9. Breaker closing & opening time measurement

15.0 Shipping, Handling and Site support

Page 16 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Against corrosion, dampness, heavy rains, breakage and


15.1 Packing Protection
vibration
Packing for
Robust wooden non returnable packing case with all the
15.2 accessories and
above protection & identification Label
spares
On each packing case, following details are required:
i. Individual serial number
ii. Purchaser's name
iii. PO number (along with SAP item code, if any) & date
iv. Equipment Tag no. (if any)
v. Destination
vi. Manufacturer / Supplier's name
Packing Identification
15.3 Label (Anodized vii. Address of Manufacturer / Supplier / it’s agent
Aluminum Plate) viii. Description (Configuration of RMU; e.g. 1CB + 2
ISO, Manual, Extensible and Quantity must be
prominently displayed at least 3 sides of packing box
& on top.
ix. Country of origin
x. Month & year of Manufacturing
xi. Case measurements
xii. Gross and net weights in kilograms
xiii. All necessary slinging and stacking instructions
The seller shall be responsible for all transit damage due to
15.4 Shipping
improper packing.
1. Manufacturer instruction shall be followed.
15.5 Handling and Storage 2. Detail handling & storage instruction sheet / manual
to be furnished before commencement of supply.

16.0 Deviations
a) Deviations from this specification shall be listed separately by bidder clause wise
(format given below) along with optional offer and has to submit the list along with
bid/quotation. BRPL will review the deviations and if BRPL is agreed with the
deviation, seller has to take written confirmation from BRPL on deviation during tender
evaluation.
b) In the absence of any separate list of deviations from the bidders with bid as well as
16.1
written confirmation from BRPL on deviations, it will be assumed by the Buyer that the
Seller complies with the Specification fully.
c) Any deviations mentioned in any other submitted bid documents (i.e.in filled GTP,
Catalog, BRPL old approval, buyer’s/seller’s standards etc) by seller without separate
deviation sheets will not consider as a deviation from this tech spec at any stage of
contract.

Page 17 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Deviation sheet format.


Sl. No. Document Name Clause No. Deviation Reason Merit to BRPL

17.0 Drawings Submission

17.1 To be submitted along with bid The seller has to submit following:
17.1.1 GA / cross sectional drawing of product showing all the views / sections
Detailed reference list of customers using the offered product during the last 5 years
17.1.2 with similar design and rating
17.1.3 Completely filled GTP
17.1.4 Manufacturer's quality assurance plan and certification for quality standards
17.1.5 Type test reports for the type, size & rating of product / equipment offered
17.1.6 Complete product catalogue and Manual.
Recommended spare parts and consumable items for five years of operation and
17.1 spare parts catalogue with price list
17.2 All documents as per clause 13 of this specification
After award of contract, Seller has to submit following drawings for buyer’s Approval
17.3 (A) / Reference (R)
17.3.1 Program for production and testing (A)
17.3.2 Guaranteed Technical Particulars (A)
17.3.3 GA drawing
17.3.4 Schematic and wiring drawings for all components
17.3.5 Terminal arrangement & cable box details including gland plate arrangement etc
17.3.6 Bill of material
17.3.7 Detailed loading drawing to enable the buyer to design and construct foundations
17.3.8 Transport / Shipping dimensions with weights, wheel base details, un tanking height
17.3.9 detailed installation and commissioning instructions
17.3.10 quality plan
17.4 Submittals required prior to dispatch
-Inspection and test reports, carried out in manufacturer’s works
-Test certificates of all bought out items
-Operation and maintenance Instruction as well as trouble shooting charts/ manuals

Page 18 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

17.5 Drawing and document sizes Standard size paper A3, A4


17.6 Number of Documents required at different stages shall be per Annexure-A
Duly signed & stamped copies of the drawings / documentation are required to be
Note : submitted to BRPL for approval.

18.0 Equipment ID [R7]

I. Equipment ID shall be painted on any appropriate face of the equipment at a clearly


readable height from the base level of the equipment.
II. Font: Recommended type face for the signage is True type or Post script
III. Font Size: All painting should be in UPPERCASE. Recommended height of 50 mm
with spacing between alphabets of 3 mm.
IV. Total No’s of Character: 18
V. Height of Font: 50 mm
VI. Height of Base: 100 mm
VII. Spacing between alphabets: : 3 mm
VIII. Paint: Base coat – Dense Yellow. Letters – Black Quick Drying paint 2 coats.
IX. Equipment ID shall be separately provided by BRPL  

Annexure A Scope of supply


1.0 The scope of supply shall include following
1.1 Design, manufacture, testing at manufacturer works before dispatch, packing,
delivery and submission of all documentation the 11kv Ring Main Unit (RMU). All the
manual RMU shall be compatible for retrofit solution of motorized RMU in future 11kV
RMU shall be as per scheme enclosed as Annexure E.
1.2 Configuration of 11kV RMU shall be as per Purchase Requisition.
1.3 Control Center has to be carried out at all sites by vendor engineer. [R5]
1.4 Guarantee Period for RMU shall be 66 months from the date of supply or 60months
from date of commissioning, whichever is earlier. [R5]
1.5 Service Performance Requirements During Guarantee Period: [R5].
1.6 Each RMU shall be supplied with 2 sets of Operating Handle. [R5]
1.7 Supplier scope includes training of BRPL team – Minimum 4 batches (each batch
with 4-5 engineers) for minimum 3 days at factory for erection, commissioning,

Page 19 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

maintenance trouble shooting of mechanism, FPI and all other components. This
shall be carried out within 1 week from date of 1st shipment/ dispatch. Supplier shall
also provide training for Self Powered relay at respective manufacturer’ factory for 12
engineers/ technicians in 2 batches. [R5].All the trainings shall be applicable for each
P.O.
1.8 Unit price for Conversion kit should be offered separately for converting the RMU
from single cable termination design to double cable termination design, at site.
1.9 BOQ as following –

Purchaser Equipment Tag No / RMU standard configuration


Sr No Unit Quantity
SAP code Type
1 Example – Type A2 No e.g. 1
2 Example – Type R5
3
4

2.0 Submission of documents

For Approval after award of


Along with offer Final after approval
contract
Documents as
6 copies + 1 soft copy
given in clause 3 copies + 1 soft 4 copies + 1soft
on CD for all type of
no 17 of copy on CD copy on CD
documents
specification

3.0 Delivery schedule

3.1 Delivery period start date - from date of purchase order


3.2 Delivery period end date - as agreed with supplier
3.3 Material dispatch clearance - after inspection by purchaser

Annexure B Technical particulars (Data by purchaser)

Sr No Description Data by purchaser


1. Reference design ambient temperature 40 deg C
2. Maximum ambient temperature 50 deg c for Delhi
3. Relative humidity e.g. 85% for Delhi
4. Seismic zone e.g. 4 for Delhi
Extensibility of RMU on one side is
5. required - Yes / No

Page 20 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Annexure C Guaranteed Technical Particulars (Data by Supplier)


Bidder shall furnish the GTP format with all details against each clause.
Bidder shall not change the format of GTP or clause description.
Bidder to submit duly filled GTP in hard copy format with company seal.

Sr. No. Description Data to be filled by Manufacturer


11kv RMU ( as per scope of supply Separate GTP to be filled for each type of
1
annexure A) RMU
2 Equipment make
Equipment type / brand name
Conformance to design standards as per
3 Yes/No
specification clause no 2.0 –
Conformance to specification clause no
4 Yes/No
3.0 to 17.0 –
If NO for pt 3 or pt 4 above, Submission
5 of deviation sheet for each specification Yes/No
clause no –
6 Panel overall dimensions in mm
Width (measured from front)
Depth
height
7 Panel weight in kg
Panel extensible on both sides – Yes /
8
No
9 Panel enclosure protection offered
Panel tested for internal arc (Cable &
10
other compartments) –Yes / No
11 Heat generated by the panel in Kw
12 Insulation level for complete panel
12.1 Impulse withstand (Kv peak) -70kvp min
12.2 Power frequency withstand (Kv rms) –

Page 21 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

28kv min
13 Bus bar
13.1 Material & grade
13.2 Bus bar cross section area in sq mm
Bus bar rated current in amp
i) at designed 50 deg.C ambient
13.3
{R9}
ii) at 50 deg.C ambient
Max temperature rise above reference
13.4
ambient of 40 deg C
Short time current withstand capacity for
13.5
3 seconds (in KA)
13.6 Bus bar clearances in mm P-P / P-E
13.7 Bus bar with insulation sleeve / barriers
13.8 Bus bar support insulator type
13.9 Bus bar support insulator voltage class
Bus bar support insulator minimum
13.10
creepage distance / mm
13.11 Earth bus bar material
13.12 Earth bus bar size
14 Circuit breaker type – SF6 or VCB
14.1 Rated voltage & frequency
14.2 Rated current in amp
Rated breaking current – KA rms
14.3
symmetrical
Short time withstand capacity in KA for 3
14.4
sec
14.5 Rated making current - KA peak
Breaker total opening time at rated
14.6
breaking capacity (in milliseconds)
14.7 Number of breaks per pole

Page 22 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

14.8 Total length of contact travel in mm


No of circuit breaker operation cycles 25% rated current -
(close & open) guaranteed at rated 50% rated current -
14.9 current, Electrical endurance class 75% rated current -

100% rated current -

No of breaker opening operations


14.10 guaranteed at rated fault current,
Electrical Endurance Class
No of breaker mechanical operation
14.11 cycles (close & open) guaranteed at zero
current , Mechanical endurance class
14.12 Contact material
14.13 Operating mechanism – trip free
Manual Spring charge type
14.14 Feeder circuit breaker (FCB) –VCB
14.14.3 Closing coil wattage & rated DC voltage
14.14.4 Trip coil wattage & rated DC voltage
14.15 Transformer CT class, ratio & Vk
15 Load break switch type – SF6 or VCB
15.1 Rated voltage & frequency
15.2 Rated current in amp
Load break switch total opening time at
15.3
rated current (in milliseconds)
15.4 Number of breaks per pole
15.5 Total length of contact travel in mm
25% rated current -
No of LBS close & open operation cycles 50% rated current -
15.7
guaranteed at 75% rated current -
100% rated current -
15.8 No of LBS making operations guaranteed

Page 23 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

at rated fault current, Electrical


endurance class
No of LBS close & open operations
15.9 guaranteed at zero current, Mechanical
endurance class
15.10 Contact material
15.11 Operating mechanism type
Minimum permissible SF6 gas pressure
15.13
(For SF6 type RMU only)
Capacitor type cable voltage indication
15.14 Yes / No
provided?
15.15 Operation counter provided Yes/ No
Disconnect switch continuous rating
16.1
(Amp)
Disconnect switch Short time withstand
16.2 Yes / No
rating -20kA for 3 sec minimum
One LBS open operation possible in the
16.3 Yes/No
event of loss of SF6 gas
Cable termination –
17.1 mm
Height of power terminal from gland plate
Torque required for tightening terminal
17.2
lug
Mimic diagram, labels & finish as per cl
18 Yes / No
no 12
Submission of RMU / component
19 Yes/No
catalogue
Unit price for Conversion kit offered
separately for converting the RMU from
20 Yes / No
single cable termination design to double
cable termination design
21 Earth Switch
Minimum number of operations at no
21.1
load- Mechanical Endurance class

Page 24 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Making capacity endurance of earth


21.2
switch – Electrical endurance class
As per make list (refer annexure I
22 Self Powered Relay – Make / Model (Relay shall be communicable with
SCADA)

22.1 CT Input

Overcurrent-
Earth Fault-
IDMT Setting Range 4 element – Over
22.2 Instantaneous O/C-
Current & Earth fault & steps

Instantaneous E/F-
Over Current – Curves
22.3 Operating Time
Instantaneous
22.4 Pick up Current
22.5 Resetting Current
22.6 Relay Burden
22.7 Time Accuracy
22.8 Tripping Coil O/P – type & duration
22.9 Fault Current Display
No of Fault Current Latching with time
22.10
stamping
22.11 Display Facility / Type
22.12 Operational Indicators
22.13 Potential Free Output Contacts
22.14 Thermal Withstand Capacity of Relay
23 Fault Passage Indicator Over Current and Earth Fault
23.1 CBCT
a Type
b Mounting Arrangement
c CT to indicator connection

Page 25 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

d ID of sensor
23.2 Earth Fault Indicator Make / Model as per Annexure-I
a Sensing Current
b Sensing Time
c Indication
d Reset Time
e Resetting Facility
f Output Contact
g Contact Rating
h Aux Power Supply
i Degree of Protection
j Mounting Arrangement
k Ambient Temperature
24 Current Transformer- Make As per Annexure-I
24.1 Ratio
24.2 Burden
24.3 Accuracy Class
25 Voltage Presence Indicator
Make As per Annexure-I
Rating
Model No
Terminal Blocks, Disconnecting type
26.8
fuses make

Bidder / Vendor seal / signature ---------------------------

Name of the bidder


Address of bidder
Name of contact person
Telephone no & email id

Page 26 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Annexure D Recommended spares (Data by supplier)


List of recommended spares as following

Sr No Description of spare part Unit Quantity


1 No
2 No
3
4
5
6

Annexure E Typical scheme of RMU

a) 11kv RMU shall have Transformer circuit breakers (TCB) with Load break switches (LBS) or Feeder

circuit breakers (FCB) as per configuration defined in Purchase Requisition.c) TCB shall be operated

manually only with facility for remote shunt trip.

Page 27 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

d) 11kv RMU shall be suitable for extension on sides for addition of LBS, TCB or FCB.

e) Fault passage indicator (For Both Earth Fault and Over Current Protection) including associated CT &

connecting cable is shown by letter ‘F’.

f) RMU Configuration-

S.no. Item description Type Combination

1 3 Way Indoor 2LBS+1VCB

2 4 Way Indoor 2LBS+2VCB

3 3 Way Outdoor 2LBS+1VCB

4 4 Way Outdoor 2LBS+2VCB

5. 1 way Outdoor 1VCB

Annexure F Drawing of Bimetallic Ring Type Lug

Page 28 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Annexure G(1) [R7] SERVICING AND WARRANTY REQUIREMENT-


EQUIPMENT SUPPLY (11KV RING MAIN UNIT)

                                                                         
                                                                            INDEX 
1.0   Purpose  …………………………………………………………………………………………..3 
 
2.0   Applicability ……………………………………………………………………………………..3 
 
3.0   Priority ……………………………………………………………………………………………..3 
 
4.0   Liability …………………………………………………………………………………………....3 
 
 
5.0   Warranty Requirements …………………………………………………………………..3 
 
6.0   Process Requirements ………………………………………………………………………4 
 
7.0   Documents/records/report submission …………………………………………….7 
 
8.0   Qualification requirement for service engineers ……………………………….8 
 
9.0   Safety ……………………………………………………………………………………………....8 
 
10.0 Communication …………………………………………………………………………………8 
 
11.0 Changes/revision management ………………………………………………………...8 
 
 

Page 29 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

1. Purpose 
This  document  is  prepared  to  specify  the  servicing  requirement  and  Warranty  / 
Guarantee handling procedure in case of difficulty that arises in the supplied equipment 
within the useful service life of the equipment being procured by BSES Rajdhani Power 
Limited. 
 
2. Applicability 
It is applicable to any equipment supplied directly or indirectly for installation / use in 
BSES Rajdhani Power Limited. 
 
3. Priority  

This  document  which  include    service,  warranty  /  guarantees  management  /  handling 


procedures  shall  be  considered  a  final  in  case  of  any  contradiction    with  other 
contractual document. 
 
4. Liability  

i) Supplier shall be liable to arrange OEM qualified service engineers as and when 
required by BSES Rajdhani Power Limited to attend defects, trouble shooting to 
restore equipment health to ensure 100 % capacity availability.  

ii) OEM  shall  be  liable  to  provide  essential  spares  at  reasonable  price  for  entire 
lifespan of the equipment. 

iii) Service call shall be attended within reasonable time frame as mentioned in this 
document.   

iv) Service  cannot  be  denied  by  supplier/OEM  till  completion  of  useful  life  of  the 
equipment.  

v) The commercial liability shall be restricted to supply/service contract provision.  

It will be liability of manufacturer /vendor tie up with accessories / component 
manufacturer to full fill requirement stipulated this document. 
 

        5. Warranty Requirements 

Page 30 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

i) The equipment failed / malfunctioned within stipulated warranty period shall 
be  attended  free  of  cost  for  the  reasons  not  attributed  to  BSES  Rajdhani 
Power Limited. 

ii) The  cost  incurred  for  service,  spares,  transportation,  consumable  and 
manpower / labour shall be borne by supplier. 

iii) OEM is bound to send service engineer to site on request for troubleshooting 
promptly. 

iv) There is no cap on number of visit or spare replacement required to repair / 
trouble soot the problem in the equipment during warranty period. 

v) Each  break  down  /  problem  reported  shall  be  analysed  scientifically  to 
establish the root cause of breakdown. 

vi) In case  it is established that  any component or accessories is not performing 
satisfactorily  or  causing  repeated  failure  due  to  poor  performance, 
manufacturing mistakes, design mistakes or not suitable to our environment 
condition  applicable  to  NCR  region,  the  OEM  shall  be  liable  to  rectify  or 
replace the same in all equipment supplied to BRPL irrespective of warranty 
period.   

vii) In  case  if  RMU  supplier  is  not  OEM  of  the  equipment  /  accessories,  the 
supplier will be liable to tie up with OEM to provide service / spares to meet 
warranty / servicing requirement stipulated in this documents.   

viii) Irrespective of onsite or workshop repairing, it will be responsibility of OEM 
to  maintain  work  quality  to  ensure  no  compromise  on  performance  and 
useful life of the equipment.  

6. Process requirements 
6.1 Complain Registration. 

i) Supplier to provide communication details for complaint registration in O&M 
Manual, on website as well as shall be printed on the equipment.  In case of 
changes, same shall be communicated to BRPL. 

ii) BRPL  will  register  complain  through  a  e‐mail  /  telephonic  call  to  the  call 
centre / service centre 

Page 31 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

6.2 Confirmation and Service time Schedule. 

 
i) All  timing  will  be  counted  from  date  of  call  registration  by  BRPL  till 
restoration  of  equipment  health  at  respective  site  in  operation  condition 
satisfactory of BRPL engineer. 

ii) Service call confirmation & service engineer visit schedule shall be provided 
within  two  hour  for  working  hour  call  (09:00AM  to  06:00PM,  Monday  to 
Saturday) and before 10 AM next working day for off working hour calls.   

iii) Emergency  trouble  shooting  calls  ‐  within  12  Hrs  including  spare 
arrangements. 

iv) Normal trouble shooting call ‐ within 48 Hrs. 

v) On site repairing / component replacement ‐ within 7 days. 

vi) OEM workshop repairing ‐ within 30 days including returning to BRPL stores.  

vii) Replacement of complete RMU ‐ within 45 days. 

viii) The  service  engineer  shall  intimate  necessary  requirement  to  attend  call 
along with confirmations 

6.3 Site visit & Investigation. 

i) The OEM shall depute qualified and experienced engineer to carryout trouble 
shoot  as  well  as  testing  and  collecting  necessary  data  /  details  essential  for 
root cause analysis. 

ii) The  service  engineer  shall  collect  preliminary  details  to  understand  and 
estimate  the  spare  requirement,  shutdown  time  requirement  from  our 
respective  area  engineer  whose  details  will  be  provided  along  with  service 
call.   

iii) The necessary tools shall be carried by service engineer attending calls. 

iv) Service engineer to get call attendance certificate from respective area BRPL 
engineers. 

Page 32 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

v) Service  engineer  to  intimate  necessary  precaution  required  to  prevent 


repetition of problem to respective area BRPL engineer as well as CES Team.  

vi) Detailed technical report (root cause analysis) to be submitted to CES Team 
for records and analysis against each call. 

6.4 Recommendation.  

i) Shall be based on scientific study / test results only. 

ii) Shall cover root cause analysis for failure. 

iii) Shall cover spares / component list for repairing. 

iv) Shall cover time requirement. 

v) Shall cover site preparation / condition requirement. 

vi) Other critical measures essential for quality work. 

6.5 On Site Repairing. 

i) All site repairing shall be under supervision of OEM engineer and shall meet 
all OEM recommendation to ensure quality of work. 

ii) All  spares  arrangement  shall  be  carried  out  well  in  advance  to  minimize 
outage time. The list must be shared with CES team 

iii)  Necessary repairing process to be intimated to CES team in advance. It shall 
include in process & final quality and performance checks / test.  

iv) The repairing process shall be certified by OEM design / quality expert.   

v) Detailed time schedule and spares arrangement details shall be submitted to 
CES team for necessary planning. 

vi) The repairing work shall be witness by BRPL CES engineer, who may insist in 
process / performance checks / test in addition to above if felt essential. 

vii) If BRPL engineer observed any quality problem / skill problem, may insist for 
repairing at OEM facility. 

6.6 Repairing at OEM facility. 
Following requirement shall be fulfilled during OEM workshop repairing work: ‐ 

Page 33 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

i) During site inspection, if service engineer felt necessary to send equipment to 
OEM facility, the same shall be organized by OEM. 

ii) In case if BRPL felt that site repairing is not up to the required quality or felt 
necessary to analyze cause of failure, the same shall be organized by OEM.  

iii) Equipment  unpacking,  testing  and  opening  for  analysis  inspection  shall  be 
carried out in presence of BRPL engineer. It shall be intimated to BRPL at least 
3 days in advance for necessary travel arrangement. 

iv) If cause of failure observed due to design mistake / manufacturing mistakes, 
the same shall be rectified in all other similar design equipments without any 
cost to BRPL. 

v) OEM to intimate the final testing for inspection. BRPL may depute engineer 
or third party representative to carryout inspection / testing before dispatch. 

vi) Dispatch shall be carried out only after BRPL clearance. 

vii) Necessary lifting, shifting, loading / unloading & transportation arrangement 
shall be in the scope of OEM / supplier. 

viii) A  document  required  essential  for  lifting  and  shifting  of  equipment  will  be 
intimated at least two days in advance. 

6.6 Witness / Inspection stages. 

Even though OEM is liable for overall quality of work, BRPL may witness / Inspection 
following activity:‐ 

i) On site inspection, repairing/replacement work. 

ii) Testing / inspection equipments / any accessories / component to establish the 
cause of failure. 

iii) Opening of equipment for internal part inspection. 

iv) Final testing/inspection before despatch. 

v) Testing / checking of the evidence causing failure / problem. 

Page 34 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Note:  It  will  be  responsibility  of  OEM  /  Supplier  to  establish  with  facts,  figure, 
photographs, and evidence to prove that cause of failure not attributed to design. 
  
7 .0 Documents / records / report submission 

The following be recorded and provided to BRPL by OEM against each call / repairing / 
rectification works for BRPL clearance and future reference:‐ 
i) Root cause analysis report. 

ii) All test report. 

iii) Minutes of meeting. 

iv) Spares / accessories test report / calibration certificates. 

v) Proof of expenditure for cost incurred to BRPL. 

vi) Copy of transportation documents. 

vii) All technical details of parts / accessories being replaced. 

8.0  Qualification requirements for service engineers 

i) All work must be carried out by only qualified, experience engineer certified by OEM. 
BRPL may request qualification and experience details if felt necessary. 
 
 
9.0 Safety. 

i) All  necessary  personal  protective  equipments  requirement  for  the  personal  and 
labour will be in the scope of OEM / supplier.  

ii) It will be liability of OEM / Supplier to meet the necessary safety norms , standards, 
rules & regulation . 

iii) BRPL may audit the same during on site work.  

10.0  Communications. 

For  better  coordination,  single  channel  communication  must  be  followed.  BRPL  and 
OEM / Supplied  to communicate to each other their team for communication time to 
time in case of any changes. 

     At present, all warranty related communication is to be done with CES team. 
 

Page 35 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

11.0  Changes / revision management. 

Necessary approval of O&M analytic cell is essential for changes in this document.  
In case if any stack holders do not agree or wish to amend its content may send request 
to BRPL O&M analytic cell for approval.  
The request will be in effect only on consideration and authorized release of revision in 
document by O&M analytic cell. 

Annexure ‘H’ 11 Kv Metering Cubicle


1.0 General Requirement
Outdoor, Metal enclosed, framed,
1 Panel Type
Compartmentalized panel construction

2 Service Location Outdoor

3 Mounting Free Standing

IP 54 Minimum
Overall Enclosure
4 (Complete unit i.e. RMU coupled to Metering unit shall be
Protection
IP54)

The metering cubicle shall be fabricated with 2.0mm CRC


sheet. Load bearing members and high voltage compartments
shall be 3.0 mm.

The panel shall be vermin proof and totally enclosed.


5 Panel Fabrication CT/PT compartment shall be fabricated after bending the M.S.
Sheets on three sides and fourth side shall be welded to make
the complete assembly tamper proof. Pressure release
device/ explosion vent should be provided on the CT PT
compartment at the rear side.

The panel shall have four separate compartments. All the


compartments shall be completely segregated from each
other.

Compartmentalized 1. Meter Compartment


6
panel construction
2. CT- PT compartment
3. Incoming
4. Outgoing

Page 36 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

The Upper compartment i.e. the “meter compartment” shall be


7 Meter Compartment suitable for housing 3 phase 4 wire Energy Meter (energy
meter not in bidder’s scope of supply) and associated wiring.

1. Double door arrangement as front and back door to meet


IP54 requirement. Both the doors should have 02 no’s
7.1 Double door concealed type (Anti Theft) hinges.

2. Front door should have at least 01 no's padlocking and 02


no's sealing arrangements.

Provided on front and back door to enable the meter reader to


perform inspection of meter compartment and note down the
reading of meter.

1. Front Door: window of size 350 (W) X 300 (H) mm


7.2 Meter reading Window
approximately with colour-less transparent acrylic sheet
and wire mesh welded from inside.

2. Back door: window of size 350 (W) X 300 (H) mm


approximately with colour-less transparent acrylic sheet.

Slot to facilitate installation of data downloading cable with


DB9 serial connector.

1. Front door: Slot of size 25mm X10 mm (+/- 2 mm) should


7.3 Data Downloading slot
be provided on front door with sealable cover.

2. Back door: Slot of size 30 mm X 50 mm shall be provided


to facilitate installation of data downloading cable.

The meter compartment shall contain hanger arrangement of


Meter hanging slotted angle for mounting meter so that meter can be
7.4
arrangement adjusted vertically and horizontally. Two horizontal and two
vertical slotted channels should be provided for the same.

The CT/PT compartment shall be completed welded type and


8 CT PT Compartment house the 11 KV dry type current transformers (3 no’s) and 3
phase dry type potential transformer.

The metering current transformers shall be suitable for 11 KV;


50Hz effectively earthed neutral system. The CT shall be
single core, epoxy resin cast, copper wound primary type with
rated burden 5VA and accuracy class 0.5s or better
8.1 Current Transformers conforming to IS:2705 (Part-I&II). Instrument security factor
shall be less than or equal to 10. CTs should have solid
copper bus bar type primary terminals for connection with
main busbar/bushing terminal. Secondary terminals of CTs
should be made of copper or brass.

Page 37 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

SL CT ratio Short time rating Size of main Bus bar

1 15 / 5 A 6 KA for 1 sec. 30 x 4 sqmm

2 30 / 5 A 6 KA for 1 sec. 30 x 4 sqmm

8.2 STC of CT 3 60 / 5 A 18KA for 1 seconds 30 x 4 sqmm

4 100 / 5A 18KA for 1 seconds 30 x 4 sqmm

5 150 / 5 A 18KA for 1 seconds 30 x 4 sqmm

6 300 / 5 A 18KA for 1 seconds 40 x 6 sqmm

The Potential Transformer shall be dry type Epoxy resin cast,


Copper wound suitable for 3 phase 11KV, 50Hz effectively
earthed neutral system. The PT shall be connected in star to
have ratio 11KV/√3 / 110/√3 V with rated burden of 10VA per
8.3 Potential Transformer
phase and accuracy class 0.5 or better conforming to IS:3156
(Part I & II). Primary terminal of PT should be of copper.
Secondary terminals of PT should be made of copper or
brass.

Pressure release device/ explosion vent should be provided


8.4 Pressure release device
on the CT PT compartment at the rear side.

1. Coupled to the breaker module of RMU.


9 Incoming
2. Coupling arrangement should meet the IP54 requirement.
10 Outgoing Cable compartment with cover/ door.

3C x 300 to 400 sq mm Aluminum conductor XLPE with armor


10.1 Cable type & size
& PVC outer sheath {R9}

1. Bottom
2. Gland plate - 3mm metallic, removable & split type in two
10.1 Cable Entry
parts, with 1no. 90 mm diameter knocks out punch/hole in
the centre. Approval should be taken for the same during
drawing submission

10.2 Cable support ‘HDPE’ cleat(s) shall be provided.

10.3 Termination Type Suitable for heat shrinkable type

1. Suitable for Ring Type Bimetallic lug.


Terminals for 11kV
10.4
cable termination
2. Material of Nut, bolts and spring washer- Brass
3. Size of Nut bolt- M16

Page 38 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

10.5 Termination height From gland plate 900 mm minimum

Single piece cold shrink type ( make – 3M/K.D.Joshi


10.6 Right angled boots
Raychem) {R9}

1. Secondary wiring of CTs and PTs shall be done with 2.5 sq.
mm PVC insulated cables with stranded copper conductor.

2. CT and PT wiring should run in independent rigid steel


conduit pipes of appropriate size from CT/PT compartment
to meter compartment.

3. Conduit pipes shall be clamped with the inner wall of the


11 Panel Wiring panel and shall be so laid that none of the wires can be
tampered from outside.

4. Current transformer and Potential transformer secondary


wiring shall be colour coded as per IS and shall be suitably
ferruled for identification.

5. No link or test terminals shall be provided in wire from


CT/PT to meter terminals.

1. The assembly comprising of the chassis, framework and


the fixed parts of the metal casing shall be provided with
two separate earthing terminals of M10 or above.

2. These terminals shall be provided over and above all other


means provided for securing and earthing metallic
enclosures (armour or other metallic coverage) or current-
carrying cables.

3. The earthing terminals shall be readily accessible and so


placed that the earth connection of the CT/ PT chamber is
maintained when the cover or any other movable part is
removed.
12 Earthing
4. The earthing terminals shall be protected against corrosion
and shall be metallically clean.

5. Earth continuitity shall be provided to all Gesketted joints by


copper braid suitable for rated fault current.

6. Under no circumstances shall a movable metal part of the


enclosure be insulated from the part carrying the earthing
terminals when the movable part is in place.

7. The earthing terminals shall be identified by means of the


symbol marked in a legible and indelible manner on or
adjacent to the terminals.

Page 39 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Bushing should be made of homogeneous epoxy / polymeric


material free from laminations, cavities and other flaws or
imperfections that might affect the mechanical or dielectric
quality. Bushings shall be designed to have ample insulation
level, mechanical strength and rigidity for the conditions under
which they will be used. The hollow porcelain bushings shall
conform to IS-5621.
13 Bushing Bushing clamping accessories, bolts, studs etc shall be hot
dip galvanized. All the nuts and washer shall be SS-304. All
iron parts shall be hot tin galvanized and all points shall be
airtight. All current carrying contact surfaces shall be silver
plated. The creepage distance of the bushing shall not be less
than 31 mm/KV. Bushing shall be tested in accordance with
IS-2099. Routine as well as type tests reports in conformity
with IS-2099 shall be furnished to the purchaser.

1. No joint in the primary winding of CT shall be acceptable.


2. Connection between CT terminal and bushing terminals
shall be done with solid copper busbar of adequate size.

3. Flexible copper strip / rope are not acceptable for primary


connection.
14 Connections
4. PT should be connected to primary busbar through bus bar
of appropriate size (connections using flexible conductor
are not acceptable).

5. All bus bars/ connections in the CT/PT compartment shall


be encapsulated in epoxy.

1. 04 No’s lifting lugs shall be provided at the top of the


15 Lifting Lug metering cubicle for transportation.

2. All nuts, bolts, flat and spring washers shall be SS only.


The total height including base channel shall not be more than
16 Height of the Base frame 2000 mm. Width and depth should be minimum possible and
may be increased suitably to accommodate CT’s/PT’s.

Welded Stud with nut must be provided for the purpose of


sealing on the following compartments/ locations.

17 Provision for Sealing 1. Meter compartment


2. Coupling arrangement of RMU and metering cubicle.
3. Outgoing cable compartment
2.0 Labels & painting

Page 40 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

The metering cubicles shall be provided with a non detachable


type nameplate with legible and indelible marking fixed on the
1 Name plate enclosure sheet with welded arrangement so that in case
name plate is removed no passage holes are left. (separate
name plate should be provided for RMU & metering cubicle)

Name plate having complete data shall be provided outside as


2.1 Location well as inside the metering cubicle at a suitable place where it
can be easily read.

2.2 Material Anodized aluminum 16SWG / SS

2.3 Background SATIN SILVER

Letters, diagram &


2.4 Black
border

2.5 Process Etching

1. BRPL Property
2. Supplier’s name
3. P.O. No. & Year of manufacturing
4. Sr. No. of metering cubicle
5. Particulars of CT’s such as ratio, VA burden, accuracy
class, SC rating, BIL.
2.6 Name plate details
6. Particulars of PT’s such as ratio, accuracy class, VA
burden, BIL.

7. Standard connection diagram


8. Consumer account no
9. Sanctioned load.
10. Date of release of connection.
On CT PT compartment by anodized aluminum with white
2.7 Labels for CT Ratio
character on black background OR 3 ply lamicoid

1. On CT PT compartment and each cable compartment


2.8 Danger plates
2. Anodized aluminum 16 SWG with white letters on red
background

a) 01 no’s
2.9 BSES Insignia
b) Shall be etched on anodized aluminium 16SWG / SS

Page 41 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

plate.

c) Details shall be finalized during drawing approval.


Enclosure painting
2.10 7 tank chemical process
surface preparation

Enclosure painting
internal/ external finish Hot dip galvanizing – 80 micron thick grade A, shade - RAL
2.11
Powder coated epoxy 7032, uniform thickness 60 micron minimum.
polyester base

3.0 Technical requirement of CT and PT


SL Description Requirement for CT Requirement for PT

Nominal System Voltage


1 11KV 11KV
(KV rms)

Highest System Voltage


2 12KV 12KV
(KV rms)

3 Type Single phase Indoor CT’s Three phase Star/Star PT.

4 Accuracy Class 0.5s 0.5

5 Rated frequency 50Hz 50Hz

Rated Secondary Current


6 5 Amp N/A
Amp.

Rated continuous thermal 1.2 times of rated primary


7 NA
current current,

8 Max Ratio error As per IS 2705 As per IS 3156

9 Max Phase angle error As per IS 2705 As per IS 3156

10 Rated burden 5VA at 0.8 pf (Lag) 10VA/ phase at 0.8 pf (Lag)

1.2 times continuous and 1.5


11 Rated voltage factor N/A
times for 30 seconds

12 Short time current rating

12.1 Thermal rating As provided in section 3.2 N/A

2.55 times of short time


12.2 Dynamic rating N/A
thermal current rating

Page 42 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

One minute high voltage


13 power frequency withstand
voltage

On primary winding KV rms 28KV (rms) for 1 minute 28KV (rms) for 1 minute for 11
13.1 On secondary winding KV for 11 KV class 3KV (rms) KV class 3KV (rms) for 1
rms for 1 minute minute

1.2 / 50 impulse withstand 75 KV (peak) for 11 KV


13.2 75 KV (peak) for 11 KV class
voltage class

14 Winding materials Copper Copper

15 Insulation security factor < 10 N/A

4.0 Inspection & testing


1. Metering cubicle shall be type tested as per IS 3427
2. CT and PTs shall be type tested as per IS2705 and
IS3156 respectively.
1 Type test
3. Bushings shall be type tested in accordance with
IS2099.

4. Type tests should not pertain to period earlier than five


Years.

1. Metering cubicle shall be tested as per IS 3427


2. CT and PTs will be tested in accordance with IS2705
and IS3156 respectively.
2 Routine test
3. Temperature rise test will have to be carried out during
Inspection.

4. During inspection, all routine and acceptance tests shall


be carried out in presence of purchaser’s representative.

1. Checks of all mounting plates / fasteners.


2. Checking of components as per drawing.
3. Electrical circuit’s fasteners tightness / surface area
3 Physical Inspection contacts.

4. Labels / identification / nameplates.


5. All doors checks – safety and accessibility.
6. Panel surface finish / smoothness.

Page 43 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

4 Right to waive off tests Reserved by Purchaser

5.0 Guaranteed Technical Particulars (Data by Supplier)


SL Description Requirement Data By Supplier

1 Name of Manufacturer

Outdoor type with resin cast


2 Type and Designation
CT and PT

3 Normal system voltage 11KV

4 Highest system voltage 12KV

5 Frequency 50Hz

6 Insulation Class

Impulse Withstand Voltage


7 75 KV peak
(On assembled CT-PT set)

One minute power


frequency dry withstand
7.1 28KV rms
voltage (On assembled CT-
PT set Primary)

7.2 Secondary 3KV rms

(3 nos. total, 01 no. per


8 Current Transformers:
phase)

8.1 Type Resin cast wound type

Transformation ratio (CT


8.2 As per requirement
Ratio)

8.3 Rated Output (VA Burden) 5VA

8.4 Class of accuracy 0.5s

Rated continuous thermal 1.2 times of rated primary


8.5
current current

Short time thermal current As per CT ratio and


8.6
rating for one second specification

2.55 times of short time


8.7 Rated Dynamic current
thermal current rating

8.8 Security factor Less than 10

Page 44 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

SL Description Requirement Data By Supplier

8.9 Insulation level 28KV for 1 min

8.10 No. of cores One

8.11 Max Ratio error As per IS:2705/1992

8.12 Max phase angle error As per IS:2705/1992

Max. temp rise over max


ambient temp of 50 deg C
8.13 at rated continuous thermal As per IS:2705/1992
current at rated frequency &
withstand burden

Make and Grade of epoxy


8.14 Cycloaliphatic {R9}
resin

9 Potential Transformers (3 Phase 4 wire unit)

9.1 Burden in VA/Phase 10 VA/phase

9.2 Transformation ratio 11KV/110V (L-L)

9.3 Class of accuracy 0.5

9.4 Winding connection Star/Star

9.5 Insulation level 28KV for 1 min

Rated voltage factor and 1.2 continuous and 1.5 for


9.6
time 30 seconds

Temp rise over max Within limits of IS-


9.7
ambient temp 3156/1992

Within limits of IS-


9.8 Max phase angle error
3156/1992

Within limits of IS-


9.9 Max Ratio error
3156/1992

Make and Grade of epoxy


9.10 Cycloaliphatic {R9}
resin

10 Size of main bus bar

For CT ratio less than and


10.1 30 x 4mm (minimum)
equal to 150/5

10.2 For CT ratio of 400/5 {R9} 40 x 6mm (minimum)

Page 45 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

SL Description Requirement Data By Supplier

11 Core material CRGO (Virgin grade)

Minimum creepage for HT


12 341mm
Bushing

Clearances a. Phase to
13 phase clearance b. Phase
to earth clearance

No. of Paint coats a. Primer


14 2 coats 2 coats
b. Enameled RAL 7032

15 Weight of complete unit

Gauge of a. Meter box b.


16 2mm (min) 3 mm (min)
HT compartments

Dimensions of complete
Metering cubicle a. Height
17
(mm) b. Breadth (mm) c.
Length (mm)

18 Meter compartment

Dimensions of meter
compartment with double
door (minimum sheet
18.1
thickness 2mm) a. Height
(mm) b. Breadth (mm) c.
Length (mm)

18.2 Protection class IP 5X

18.3 Provision of Acrylic window

Provision of slotted channel


18.4 (40*12mm) suitable for Required
6mm bolts (4 Nos)

Provision of Pad locking &


18.5
sealing arrangement of door

Provision of mounting
18.6 metering reading port on
door.

19 Metering cubicle mounting Floor mounting

Page 46 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

 
Annexure ‘I’ Make list

Make List of RMU's Accessories {R9}

Sl. No. Descriptions Make


1 Relay (Self Power+ AUX DC/ACSupply+ Ashida 241S-761
Communicable)
2 CT Narayan Power Tech
(NPT)/Gilbert Maxwell, 400/75-
1/1, 5P10, 2.5 VA, Pragati, Nortex
3 FPI (Both for Earth Fault and Over Current EMG/C&S/Schneider/SIEMENS
Protection)
4 CBCT (Both for Earth fault and Over current EMG/C&S/Schneider/SIEMENS
protection)
5 Boot 3M/Raychem/K.D.Joshi
6 Wire Polycab/Havells/Finolex/KEI

7 AC & DC MCB SIEMENS/Havells/C&S/


Schneider
8 Disconnecting type fuses Connectwell/Wago/Phoenix/Elmex

9 TB (disconnecting type) Connectwell/Wago/Phoenix/Elmex

10 Vacuum Interrupter CG/ ABB/Schneider/SIEMENS/other


type tested

Annexure ‘J’ Type test


The entire product shall be type tested from CPRI / ERDA. In case of new offer or type test
report is older than 5 years, bidders shall carry out type tests from CPRI / ERDA without any
cost implication to BRPL

Annexure-K -Special Technical Requirement: {R9}

Sl. No Descriptions

1 Animated video for ETC guide of RMU shall be submitted to BRPL before
delivery of first lot
2 Relay Protection setting (min 10%)
3 All the communicable accessories shall have Latch contact
4 NO/NC contact for manometer shall be provided

Page 47 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Sl. No Descriptions
--Bidders shall have additional RMU readily available of each type to replace
under warranty faulty RMU in case it is repairable at OEM factory
--In case of under warranty failure and if the faulty RMU is repairable only at
OEM factory, bidder has to replace the faulty RMU during lifting with new/
operatable same type of RMU within the time period mentioned in the tech spec
5
warranty clauses.
--BRPL shall not issue any RMU from their assets for replacement activity. In
case of delay, penalty shall be imposed as per this corrigendum sl no 9
--After Warranty period completion (5 years), these clause shall not be
applicable to OEM
6 Sample RMU

1 sample RMU of each type shall be manufactured as per BRPL specification


6.1 after award of PO. BRPL will do the routine testing and inspection of the sample
RMU and if found satisfactory as per BRPL specification, BRPL will give
clearance/ approval for bulk manufacturing
During inspection of the sample RMU, BRPL may ask the vendor to modify/
change the design as per BRPL requirement including the make of accessories
6.2 mentioned in the specification. OEM is liable to modify the design irrespective of
the offer submitted during tender stage. However, BRPL will not ask for the
requirement beyond the technical specification.
6.3 The lead time required to arrange the accessories/ to modify the design
required as per BRPL requirement shall be in the account of bidder.
6.4 BRPL is not liable to bear any extra cost, out of the PO for the approval of
sample RMU and the bulk quantity afterwards.
The sample may be used in BRPL network based on fulfilment of technical
6.5 requirement and BRPL approval. Else fesh RMUs as per the approved sample
shall be supplied in line with PO quantity.
During bulk manufacturing and PO execution, BRPL may ask necessary
changes to be done (if required). Bidder is liable to provide the required
6.6 changes as per the BRPL requirement irrespective of the offer / design given
during tendering stage without any cost implication to BRPL. However, BRPL
will not ask any changes out of BRPL Technical specification
Warranty clause’s terms & conditions mentioned in the technical specification
7 Annexure- G(1), Clause no-6.2 shall be strictly followed by the OEM, in the
event of violation of warranty clauses, BRPL is liable to impose penalty with1%
of RMU unit rate per day basis (Unit rate shall be considered as per the PO)
Submission of Type test report (not more than 5 years from the date of tender
8 opening) of internal arc for 1 sec (AFLR 20kA for 1 sec) from CPRI/ERDA is
mandatory with minimum 3 way RMU configurations.
9 Complete Civil foundation Drawing along with sectional view (RCC casting shall
be followed) and Bar Bending Scheduled (BBS) shall be submitted by bidders

Page 48 of 49
SP-ERMUX-15-R9

Technical Specification For 11 kV Ring Main Unit

Sl. No Descriptions
along with drawing

Submission of 3nos as built drawing to BRPL before dispatch of first lot of


material is mandatory. Also one set of as built drawing shall send with each unit
10
of supplied RMU. Proper holding arrangement to be provided to place as built
drawing inside the RMU.
Test bushing feature-The bushing of RMU must have the feature of “Test
11
Bushing”.
12 Broken conductor feature in relay-The relay must have the feature of detecting
change in impedance (negative phase sequence over current)
BRPL may conduct stage wise inspection of RMU manufacturing at vendor
13 works. OEM is liable to intimate the manufacturing scheduled along with related
dates before commencement of manufacturing.

Page 49 of 49
GN101-03-SP-06-03

Index

General Specification .................................................................................................3


1.0.0 Codes & standards ............................................................................................3
2.0.0 Design Guidelines & Parameters for Cable laying.............................................3
3.0.0 General Guidelines for Laying Cables...............................................................7
4.0.0 Testing ..........................................................................................................................14
5.0.0 Progress Reporting .........................................................................................15
6.0.0 Drawing, Data & manuals.............................................................................................15
7.0.0 Deviations........................................................................................................16

Annexure # 1 – DEVIATION REPORT FORMAT......................................................16


Annexure # 2 – DC HIGH VOLTAGE TEST .............................................................16
Annexure # 3 – CABLE TRENCH DETAILS .............................................................17
Annexure # 4 – STANDARD ROAD PROFILE .........................................................18
Annexure # 5 – ROAD RESTORATION SECTIONAL DRAWINGS..........................20
Annexure # 6 – DRAWINGS (CABLE TRENCH AND RCC CABLE COVER)..........23
Annexure # 7 – BARRICADING AND SAFETY…………………….………………….38
Annexure # 8 – ROUTE MARKER AND BARRICADING DRAWING……………….38
Annexure # 9- NOTE FOR HDPE PIPE DIAMETER IN CABLE LAYING................43

Page 2 of 44
                                                                                             GN101-03-SP-06-R

General Specification 

1.0 Codes & standards  
Materials,  equipment  and  methods  used  in  the  Laying  of  11/33/66KV  Cable  shall  conform  to  the 
latest edition of following –  
 

S.  Reference No.  Name of Standard 


No. 
1    Indian Electricity Rules, 1956 
2    Indian Electricity Act, 1910 
3    Indian Electricity Supply Act, 1948 
4    Electricity Laws Act, 1991 
5    National Electrical Code ( Indian standards Institution) 
6  IS 1255   Code of practice for installation and maintenance of Power Cable upto 
and Including 33KV rating. 
7  IS 1554  PVC Insulated Electrical Cables upto 11KV 
8  IS 2274  Code of Practice for electrical wiring installation – system voltage 
exceeding 650V 
9  IS 7098 Part II  Crosslinked Polyethylene Insulated PVC sheathed cables for working 
voltages from 3.3KV upto and including 33KV 
10  IS 7098 Part III  Crosslinked Polyethylene Insulated PVC sheathed cables for working 
voltages from 66KV upto and including 220KV 
11  IS 5820  Specification of precast concrete Cable cover. 
 

2.0 Design guidelines and Parameter for cable laying‐ 

S.  Parameter  Details 


No. 
2.1  Selection of  The cable route selection shall be done by the concerned supervising 
Cable Route  engineer by first conducting route survey and  selecting a route along 
with contractor keeping followings in mind: 
‐The side of road which presents the least obstacles and the fewest 
roadways crossings.  
‐The future consumers and existing cables in the route may influence the 
cable route.  
‐Railway, road crossings, MCD and other government agencies may also 
influence in selection of cable route.  
‐Plans for future building projects should be considered.  
‐The route shall be as far as possible away from parallel running gas, 
water pipes and telephone/telecommunication cables. 
2.2  Site Preparation  a) Barricading: 
• The identified cable route shall be barricaded continually 
before excavation. 
• Barricading shall be as drawing  laid  
• Open Trench method shall be adopted as far as possible for 
trench preparation.  
b) Excavated Earth: 

Page 3 of 44
                                                                                             GN101-03-SP-06-R3 

• The excavated earth shall be so stored at site, that it shall 
not cause trouble to running traffic 
• All excavated earth shall be stored within the barricaded 
area. 
•     
c) Full height fence, barriers, barricades etc. shall be erected 
around the site in order to prevent the working area from the 
risk of accidents due to speedy vehicular movement. Same the 
way barricades protect the road users from the danger due to 
construction equipment and temporary structures. 
d) The structure dimensions of the barricades , material and 
composition, its colour scheme, BSES logo and details shall be in 
accordance with specification and drawing laid down in the 
tender documents. 
e) All the barricades shall be erected as per the design 
requirements of employer, numbered painted and maintained in 
good condition and also barricade in charge maintain a barricade 
register at site. 
f) All barricades shall be conspicuously seen in the dark/night time 
by the road users so that no vehicle hits the barricades. 
Conspicuity shall be ensured by affixing retro reflective strips of 
required size and shape at appropriate angle at bottom and 
middle portion of the barricades at a minimum gap of 1000 mm. 
In addition minimum one red light /red blinker and red beacon 
light should be placed at the top of each barricade. 
g) PPP to be provided by vendor to all workers and engineers. 
h) Also refer Annexure‐ 7: Barricading and Safety 
 
2.3  Clearance  The desired minimum clearances are as follows – 
‐ Power cable to power cable – A minimum clearance equal to diameter 
shall be maintained. Trench drawings shall be referred to for guidance. 
‐ Power Cable to control cables – 0.2 M 
‐ Power cable to communication cable – 0.3M 
‐ Power cable to gas/water main – 0.3 M 
2.4  Depth of Cable  The desired minimum depth of laying from ground surface to the top of 
Laying  cable shall be: 
650 / 1100V grade XLPE Cables – 75 cm 
6.35 / 11KV grade XLPE Cables – 90 cm 
Low voltage and Control cable ‐ 75 cm 
19 / 33KV grade XLPE Cables ‐ 1.2 M 
38 / 66KV grade XLPE Cables ‐ 1.5 M 
Cables at Road crossing ‐ 1.0 M (min.) 
Cables at railways level crossings (measured from bottom of sleepers to 
the top of Pipe) ‐ 1.0 M (min.) 
Whenever there is any obstacle at the laying depth, the cable should be 
lowered/ raised to cross the obstacle. However variation in the depth is 
to be approved by BSES. The Contractor shall provide the same in 
deviation report. 
2.5  Width of Cable  The width and depth of Cable Trenches shall depend upon number of 

Page 4 of 44
                                                                                             GN101-03-SP-06-R3

trenches  circuits and Voltage Grade. Annexure # 3 and drawings of this 
specification shall be followed. 
2.6  Bending Radius  While pulling of the Cable from the drum or during laying 
of Cables  following minimum bending radius shall be maintained so that 
the cable, in particular the insulation does not get damaged – 
A) Single Core Cables ( PVC & XLPE) 
Upto 1.1KV grade – 15 X D 
Above 11KV grade ‐ 20 X D 
B) Multi Core Cables ( PVC & XLPE) 
Upto 1.1KV grade ‐ 12 X D 
Above 1.1KV grade – 15 X D 
Where ‘D’ is overall diameter of the cable. 
2.7  Maximum  For cables pulled with Stocking 
permissible  PVC and XLPE SWA Armoured cables P = 30 X D 
Tensile  PVC and XLPE AWA Armoured cables P = 20 X D 
Strength for  Where P= pulling force in Kgrm, D= Diameter of Cable in mm 
Cables   
For Cables pulled by Cable eyes 
Aluminium conductor – 30 N/mm2 = 3 Kg/sq. mm 
Copper conductors ‐ 50N/mm2 = 5 Kg/sq. mm 
 
Permissible force is calculated by multiplying the above values by cross 
sectional area (CSA) of conductor of each core and then number of cores. 
2.8  Methods of  a) Cables shall be laid in direct in ground, in trenches excavated 
Laying  therein and shall be protected with covers as given in the 
drawing. Cables shall also be drawn into pipes of ducts or laid in 
the formed trenches or troughs or on racks or supported in trays 
or cleats as required by the site exigencies. Where the cables are 
laid in the formed trenches, the installation shall include removal 
and replacement of the trench covers and the provision of 
temporary protective covers on the trenches where they cross 
the access ways. 
 
b) HDPE (PN6,PE80) or RCC ducts shall be used where cable cross 
roads and railways tracks. Spare ducts for future extensions 
should be provided. Spare duct should be sealed off. Buried 
ducts or ducting blocks shall project into footpath or upto the 
edge of road, where there is no footpath, to permit smooth entry 
of cable without undue bending. The diameter of the cable 
conduit or pipe or duct should be at least 1.5 times the outer 
diameter of the cable. Angular alignment of the duct across road 
crossings shall be predetermined to maintain safe bending radius 
when direction of cable trench changes before or after the road. 
 
c) The contractor shall lay cable by Horizontal direct drilling (HDD) 
in main roads and highway with heavy traffic, passage to public 
property where excavation is not possible. Contractor shall take 
approval for laying of cable by means of HDD wherever required 
from the supervising engineer. The cable laid by HDD shall be 

Page 5 of 44
                                                                                             GN101-03-SP-06-R3 

minimized so that it doesn’t exceed by 12% of total route length. 
This is to avoid De‐rating of Cables. 
 
d) Unless approved by BSES, the contractor shall lay the cables, 
direct in ground, in single layer. The cables shall be laid with the 
pre‐determined and approved cable route. 
 
e) Spacing shall be maintained uniformly between the cables all 
along the length including the bends, as approved by BSES. To 
maintain the spacing, suitable non‐metallic formers shall be 
placed uniformly with spacing not exceeding 5 meters. Every 
bend shall have at least one spacer. 
 
f) 75 mm of the sand bed shall be placed at the bottom of cable 
trench. 
 
g) After the cables have been laid the trench shall be filled with the 
sand and shall be well rammed to a level not less than 75 mm 
above the top of the cables all throughout the route. 
 
h) To protect the cables against external mechanical damage, which 
may be caused by other agencies, the cable shall be protected by 
suitable cover. (for drawing of RCC cable cover refer annexure 
VI).  
 
i) The type of the covers shall be as under 
‐ 1.1KV Cables – Single layer of brick thickness not less than 
75 mm ( 3 inch) 
‐ 11KV Cables – sand stone of thickness not less than 75mm ( 
3 inch). 
‐ 33KV Cables shall be protected by reinforced concrete cover of 
width 300 mm as per attached drawing with thickness not less 
than 50mm. 
‐ 66KV Cables shall be protected by reinforced concrete cover as 
per attached drawing with thickness not less than 50mm. 
 
The RCC cable cover shall be embossed as “BSES EHV 
CABLE”. 
 
j) Back fill to be filled up to 75mm and the warning tape shall be 
installed continuously. The tape shall be yellow in colour with 
Black / Red lettering of minimum 20mm height. The approved 
warning message shall be written in English and Hindi/ local 
language. The minimum thickness and width of the tape should 
be 300 microns and 150 mm respectively. 
 
k) The trench shall be filled‐up by loose soft soil (300mm) and 
Excavated soil as indicated in drawings. 
2.9  Cable over  On Bridges the cables are generally supported on wooden cleats and 

Page 6 of 44
                                                                                             GN101-03-SP-06-R3 

Bridges  clamped on steel supports at regular intervals. The cables laid on bridges 
shall be provided with Sun shield.  
Approval from appropriate authorities (PWD/railways) as applicable shall 
be taken by contractor. 
2.10  Laying of Single  a) The single core cables shall be laid in trefoil formation. Single 
Core Cables  core cables can be laid individually in HDPE pipe in case 
of HDD only. (Details of HDPE Pipe as per Annexure-9)
 
b) For single core cables laid in trefoil formation, plastic cable ties 
shall be used at interval of 1.0 (one) meter throughout the cable 
length to maintain the trefoil arrangement. 
 
c) To balance the inductance, the phase sequence  in trefoil format 
shall be maintained by vendor ( for double circuit) 
 
d) To prevent magnetic losses (eddy current and hysteresis losses), 
the base plate of the panels or the terminal box of the 
equipments, shall have aluminium plate. In case the entry into 
the building is through GI pipe, a “slit” in the GI pipe shall be 
necessary. Alternatively GI pipes may altogether be avoided and 
non‐metallic pipes such as PVC or HDPE pipe shall be used. 
Concrete pipes having steel reinforcement (RCC pipe) are not to 
be used. 
2.11  Earthing of  a) Single point bonded earthing shall be employed to prevent flow 
Single Core  of induced circulating current in the armour and screen and 
Cables  consequential de‐rating of cables for feeder less than 2.0 KM. 
 
b) For feeder length more than 2 KM, mid point earthing shall be 
provided. 
2.12  Violation of  On violation of barricading guideline and safety norms, a fine of Rs.5000 
barricading  /day shall be imposed.  
guideline  and  BRPL inspector/engineer in‐charge shall be empowered to impose the 
safety norms  above penalty. 
 

3.0 General guidelines for Laying Cables  

S.  Parameter  Details 


No. 
3.1  General  a) Laying of the cables and handling of the same shall be 
undertaken, at all times, by adequate staff suitably trained and 
supplied with all the necessary plant, equipment and tools. 
b) The contractor shall be responsible for all the route survey, 
establishment of the position of the joints as per the site 
exigencies and the drum lengths of cables to be laid. While 
carrying out the route survey the contractor shall take into 
account the obstacles on the route whether above or below 
ground. The cable shall be planned to be laid in an orderly 
formation, free from unnecessary bends and crossings 
c) The contractor shall submit a drawing for the complete scheme 

Page 7 of 44
                                                                                             GN101-03-SP-06-R3 

showing the entire route, road crossings, location of joints and 
also the arrangement of cables to be laid. In case due to site 
exigencies, cables have to cross over within the trench, the same 
shall be shown in the drawing. For each and every job, these 
drawings shall be approved by BSES, prior to commencement of 
work. 
d) BSES shall arrange for all the material and manpower required 
for jointing and end termination. The Contractor shall provide 
pit, carry out excavation for creation of working space required 
for jointing by the jointer. All civil works, structural work, 
clamping and earthing shall be carried out by the contractor, so 
that the cables and accessories perform satisfactorily during the 
entire life time. 
e) The entry and exit of the cables into the building shall be through 
RCC or GI pipe except for single core cables, which shall be 
properly sealed and shall be duly supported as per the method 
and technique approved by BSES, so that the outer sheath of the 
cable does not get damaged at the entry and exit points. The 
sealing should be of adequate length so that it minimizes the risk 
of spreading of fire or ingress of water. 
3.2  Handling and  a) The cable drums shall be transported upright, so that the weight 
Storage of  is distributed on both the flanges. Under no circumstances the 
Cable drums (All  cable drum may be laid on its side. During transportation the 
empty drums are  drums must be properly secured. The cable drums should never 
returnable)  be dropped from Lorry or a trailer, so as to prevent damage to 
the cable drum and also to the cable. Ramp may be used for 
unloading. The drums may be rolled over short distance, 
provided the correct direction of rolling as provided on the drum 
is observed. Alternatively, a mobile crane should be used for 
lifting and lowering the drum. A chain‐pulley arrangement may 
also be used to lift the drums and deposit the same on ground if 
required. 
b) In case the drums are to be stored prior to cable laying, they 
should be arranged in such a way to leave some space between 
them for air circulation. It is desirable that the drums stand on 
battens placed directly under the flanges. Overhead covering is 
not essential except in heavy rainfall areas or during monsoon. 
Cable should however be protected from direct rays of sun by 
leaving the battens on or by providing some form of sunshade. In 
no case the drums shall be stored in a flat position with flanges 
horizontal. 
c) For transportation of the cable drums from storage site to work 
site, the drum should be mounted on a trailer or an open lorry 
and unloaded by mobile cranes. 
d) After cable laying, empty cable drums shall be taken return back 
by vendor from site at their own risk and cost. Cost of empty 
drums shall be deducted from vendor account during final 
settlement. 
3.3  Cable Laying  a)  The ground over which the drum is positioned at site should be 

Page 8 of 44
                                                                                             GN101-03-SP-06-R3 

properly consolidated and jacks placed on both sizes of the drum 
to make the pay‐off arrangement stable. Suitable arrangement 
be made to stop the drum rotation, during cable laying 
preferably by square wooden poles kept temporarily pivoted 
over cable roller under the flanges which when required can be 
applied on the flange as a brake by personnel manning the drum.
b) The cable should always be paved off from the top of the drum. 
The drum must be positioned in such a way that the arrow on 
the drum points opposite to the direction of rotation marked on 
the drum. 
c) It must be ensured that the cable is not dragged over sharp 
object or on the road surface, so as to avoid damage to the outer 
sheath of the cable. 
d) The pulling method to be used shall be approved by BSES. Cable 
supplier’s recommended maximum pulling tension shall not be 
exceeded. 
e) Rollers shall be placed at intervals and the cable shall be pulled 
over the rollers. The rollers shall be kept lubricated so that they 
rotate freely, minimize friction to the cable in motion. Rollers 
shall be positioned at the bends to minimize side wall friction. 
The contractor shall ensure that PVC/HDPE sheath of cable is 
free from damage due to abrasion. 
f) The cable should not be pulled out from the drum by lifting of 
the coil while the drum is lying flat on the flange. This leads to 
twisting of the armour and cores resulting in permanent damage 
to the cable. 
g) To avoid ingress of moisture, it must be observed that the end 
capping of the cables is not damaged. Cut pieces of the cables 
must be capped immediately, before laying of the same is taken‐
up. 
3.4  Excavation of  a) The excavation of the trenches shall be commenced, with proper 
the Trenches  co‐ordination with BSES, so that all the necessary clearances for 
the route are already obtained from the competent authorities, 
well in time. 
b) Before opening of the section of the trench, the contractor shall 
satisfy himself that the line of the trench is clear of underground 
obstructions, by taking out trial pits on the line of the trench. 
c) The exact location of each trench shall be approved on site by 
BSES. The trenches shall be kept as straight as possible and each 
trench shall be excavated to approved formation and 
dimensions. If necessary, the trenches shall be adequate shored 
by wooden planks and bracing to avoid trench cave‐ins which 
would cause injury to the persons and also damage the cables 
laid. 
d) The bottom of each trench shall be firm and of smooth contour. 
The contractor shall take reasonable precautions to prevent 
damage to the highway or ground surface from a slip or breaking 
away of the sides of the trench. 
e) The trench excavation and filling in shall be so executed that all 

Page 9 of 44
                                                                                             GN101-03-SP-06-R3 

walls, roads, sewers, drains, pipes, cables, structures, places and 
things shall be reasonably secured against risk of subsidence or 
injury and shall be carried out to the satisfaction of the 
authorities concerned. Should, however, a damage to an existing 
or other services be made, the Contractor will arrange and pay 
for any necessary repair, to make good the damages. 
f) Where trenches pass from a footway to a roadway or at other 
positions where a change of level is necessary, the bottom of the 
trench shall rise or fall gradually. The rate of rise or fall shall be 
approved by BSES. 
g) Contractor shall ensure that during excavation and until 
restoration has been completed, for reasonable access of 
persons and vehicles to property or places adjacent to the route. 
h) When the excavation of the trenches has been accurately 
executed, the contractor shall inform BSES for approval. Laying 
of cables or building of structure shall not be started until the 
contractor has been advised by BSES to proceed with the work. 
3.5  Excavated  a) The materials excavated from each trench shall be placed so as 
material  to prevent nuisance or damage to adjacent ditches, drains 
fences, gateways and other property or things. Excavated 
material shall be stacked so as to avoid undue interference with 
traffic. 
b) Where, owing to traffic or for reasons of safety or other 
considerations, this is not permissible, the excavated material 
shall be removed from the site and returned for refilling the 
trench on completion of laying; surplus material shall be 
disposed off by the contractor at his own cost. 
3.6  Pipes and  a) Care shall be taken to make the bend of the pipes or duct lines as 
Ducts  easy as practicable and in no case of radius less than 3 meters. 
Where approved, split pipes may be used on bends, the pipes 
being fitted round the cable after laying. 
b) All road crossings shall be ducted. This applies to present and 
future roads as indicated on the route plans. The pipes and the 
ducts shall be laid in an approved manner and shall be 
surrounded by 150 mm of PCC (1:2:4) 
c) Ducts under the road shall be provided by the contractor, by 
non‐disruptive method, if road cutting is not permitted by the 
concerned authorities Cable laying shall be done by Horizontal 
Direct drilling method (HDD). 
d) The cables shall be suitably protected at entry and exit from the 
pipes, so that the outer sheath does not come in contact with 
the edges of the pipes / ducts. The pipes and ducts shall have 
slope so that the seepage water can drain through the small 
opening provided on the lower side of the pipe sealing. 
e) The pipes and ducts shall be secured to the base at both ends 
and at regular interval, throughout the length, so that at no point 
the ducts or pipes get suspended over the threaded cable, and 
damage the same, thus defeating the very purpose of providing 
the pipe / duct. 

Page 10 of 44
                                                                                             GN101-03-SP-06-R3 

f) At all road crossings at least one spare duct / pipe shall be 
provided for future use. The pipe shall be thoroughly cleaned of 
obstructions. A draw wire or rope shall be left in each pipe to 
facilitate the drawing in of the cables. The duct end shall be 
sealed temporarily to prevent the entry of foreign matter. End 
caps and permanent markers shall be placed flush with footpath 
/ roadways at both the ends. The pipes and ducts shall be 
cleaned again immediately before the cables are drawn in. 
g) The internal diameter of the pipe / duct should be such that the 
cables occupy only 40% of the area of the pipe / duct to avoid 
de‐rating. 
3.7  Joint Bays  The contractor shall provide all help so as to enable jointers to carry out 
their work efficiently and expeditiously. The method of securing and 
supporting cable joints and cables also the bonding and earthing thereof, 
shall be detailed on the drawing. The details shall be approved by BSES 
prior to commencement or work. The joint position should be staggered. 
3.8  Back filling of  a) Filling in of trenches shall not be commenced until BSES has 
trenches  inspected and approved the cables and accessories at site. The 
inspection should be got done on daily basis so that the trenches 
do not remain open unnecessarily, to avoid inconvenience to 
public. 
b) The trench shall be backfilled after putting all protections for 
cables.  
c) Soft soil shall be backfilled for 300 mm above the cable 
protection cover. 
d) Caution Tape shall be laid all along the cable route above the soft 
soil filling. 
e) Complete backfilling shall be done above the caution tape. 
3.9  temporary  a) Where cables routes are in public highways, footpaths, gardens 
Reinstatement  etc., the method of reinstatement will be subject to approval by 
MCD. All costs incurred will be at the contractor’s expenses. 
b) The contractor shall be responsible for proper permanent 
reinstatement of the upper levels, which shall be carried out to 
the satisfaction of BSES and the MCD authorities concerned. 
c) Before finally leaving site, permanent reinstatement shall be 
executed by the contractor to the approval of MCD and the 
property owners and all costs incurred shall be to the 
contractor’s account. 
3.10  Permanent  a) In public roads and footways the surfaces and foundations shall 
Reinstatement  be temporarily reinstated by the contractor. After settlement, 
of Public Road,  temporary reinstatement material shall be removed as necessary 
and the permanent reinstatement shall be carried out to the 
approval of the appropriate highway authority / MCD. Stone and 
pre‐cast concrete paving kerbs and channels shall also be finally 
reinstated by the contractor. 
b) Temporary reinstatement shall be maintained by the contractor 
until commencement of final reinstatement to ensure that the 
surface is always safe for the passage of pedestrians and 
vehicular traffic. 

Page 11 of 44
                                                                                             GN101-03-SP-06-R3 

3.11  Identification  All cables shall be identified below the gland at each end, at joint 


position and at approved positions by means of bands engraved or 
punched with cable no. feeder name, size of cable, number of cores, 
phase colour etc. The bands shall be secured fastened in a permanent 
manner, and shall be made of material able to resist corrosion, 
dampness and mechanical damage. 
3.12  Cable Route  All cables routes shall have markers at suitable location with a gap not 
Markers  exceeding 30 meters. The route markers shall be approved design. 
Additional markers shall be provided at joint locations with approved 
markings. 
3.13  Cable supports  a) The contractor shall supply and install all the supports, racks, 
/ Clamps  trays, cleats, saddles, clips and other parts required to carry and 
secure the cables, without risk so that there is no undue 
mechanical load or stress due to weight of the cable at each end. 
Cleats, saddles and clips shall be of the design as approved by 
BSES. No cable shall be laid on the trench floor. They shall be run 
in a neat and orderly manner and the crossing of cables within 
the trench shall be avoided as far as possible. Where cable runs 
unavoidably cross, a suitable supporting arrangement shall be 
provided to maintain an adequate gap between the cables 
b) Every cable shall be supported at a point not more than 500 mm 
from its termination. 
3.14  Installation of  a) The design of cable support for cables installed in air in cable 
Cables in  tunnels, basements etc. shall consist of vertical steel members 
tunnels /  spaced at approved interval and secured to the walls, floors and 
basement /  ceilings as necessary by means of bolts either cemented in 
below the  position or expanded into cored holes. Each vertical support shall 
panels etc  have bolted to it a number of steel brackets spaced at the 
intervals and designed to support and retain trays constructed of 
galvanized sheet steel of adequate section to carry the weight of 
the cables, plus space for an additional quantity of future cables 
at least 25% by weight and dimensions in excess of the cables 
installed under the contract and an additional load of 100 kg at 
the extremity without distortion. The trays shall be designed 
with raised edges to retain the cables and shall incorporate an 
interlocking feature so as to prevent movement between 
supports. 
b) The design and construction of all cable cleating and supporting 
arrangements shall suit the cable system design. The spacing of 
cable supports shall be approved by BSES. 
c) Cable run on trays shall be neatly dressed and where not 
provided with cleats shall be secured by heavy gauge, type 
approved metal reinforced, clips or saddles. Not more than six 
cables shall be embraced by one clip. 
d) Mild steel of appropriate sections, duly painted in an approved 
manner, shall be used for fabrication of cable supports. The steel 
shall be free from blisters, scales, laminations or other defects. 
Before final painting, the steel sections shall be provided with 
double coat of red primer. 

Page 12 of 44
                                                                                             GN101-03-SP-06-R3 

3.15  Cable  Where the cables terminate on overhead line poles or towers located 


Protection at  outside substation compounds the contractor shall provide suitable cable 
overhead  supporting galvanized steel work attached to the pole or tower and 
Towers or  comprising backboard, runners, sheet, steel cover of not less than 3.0mm 
Poles  thickness, stays, cable cleats, anti climbing guard and all incidental items 
to provide secure protection for the cables. Isolators and Lightning 
arrestor if required to be installed shall be provided as free issue item to 
the contractor, however the erection and steel structure required shall 
be in scope of the contractor. 
3.16  Sun Shades  All cables shall be protected from direct solar radiation by ventilated sun 
shields as approved by BSES. 
3.17  Route Plan  a) BSES intents to show all the cable routes, location of joints and 
other underground obstructions on a GPS map.  
b) During the progress of the contract works the contractor shall 
record on a set of route plans and cross section drawings of an 
approved form, these details so that the same can be transferred 
on the GPS maps. Such particulars will allow an accurate 
reference to be made in the case of any fault or projected 
modification. These records shall show, amongst other data, 
both indoors and outdoors the exact position of every joint, 
cable end termination and also the particulars of the depth of 
the trench, the arrangement of the cables, with cable numbers 
and the position of all obstructions revealed during the course of 
excavations. These completed records shall be submitted to BSES 
within 15 days of completion of any particular route/feeder. The 
final bill shall not be processed by BSES unless this activity has 
been completed to the entire satisfaction of BSES 
3.18  Site Facilities to  a) The contractor shall arrange for all the tools and tackles required 
be maintained  for cable laying as per this specification. BSES shall arrange for all 
by the  the material and manpower required for jointing and end 
Contractor  termination. 
b) Illumination and Power supply shall be arranged by the 
contractor so that the work can be carried out round the clock. 
c) The contractor shall maintain functional dewatering pumping 
facility with suitable power supply so as to protect the cables and 
the joints from ingress of water due to rain or otherwise 
d) The contractor shall make arrangement to provide suitable 
scaffolding arrangement to carry out the termination work 
e) The contractor shall carry out proper barricading of the dug cable 
route and the joint bays and shall take all necessary precautions 
to avoid any public hazard 
f) Also refer Annexure‐7: Barricading and Safety. 
3.19  Type of Roads  The typical section of type of Roads (based on width) under PWD and 
and guidelines  MCD are :‐ 
for road  ‐ 20 Feet Wide road 
restoration  ‐ 30 Feet wide road 
‐ 40 to 60 Feet Road 
‐ Other ( which include Kota stone, Agra stone, Cement 
concrete, interlocking paving tiles, brick road, chequered tiles 

Page 13 of 44
                                                                                             GN101-03-SP-06-R3

and asphalted road) 
 
The drawing are shown in annexure IV 
 
The guidelines for road restoration for various type of roads 
and surfaces are indicated in annexure V as :‐ 
‐ Bituminous road Type I (category I & II) 
‐ Bituminous road Type II (category III) 
‐ Cement concrete road 
‐ Kota/Rajasthan stone Road 
‐ Brick Road 
‐ Interlocking paving tiles. 
‐ Agra stone road 
‐ Chequered tiles road 
‐ Asphalted road 
 

4.0 Testing 

S.  Parameter  Details 


No. 
4.1  Tests to be  Testing of cable before jointing – 
carried  ‐ Cable shall be tested for Insulation Resistance prior to laying by opening 
out during and  the end and resealing end properly. 
after completion   
of  Testing on complete Cable Installation – 
Cable Laying  a) Insulation resistance of each core shall be measured against all 
the other cores and the metal screen connected to earth.  
b) The resistance of the conductor shall be measured. 
c) DC High voltage. For old cables test voltage shall be 1.5 times 
rated voltage or less depending on age of cable.(refer annexure # 
2 for values) 
d) Charging of Cable at No‐Load at Nominal working voltage for 24 
Hours. 
e) After laying and before termination of cable a sheath test shall 
be conducted for 66KV Single core Cable as under :‐ 
 
At both ends the cable shall be raised from ground. From the end 
graphite coat applied over the outer PVC jacket shall be removed 
with a piece of glass for a length of 300mm. A spiked steel rod 
with an eye for attaching a wire shall be driven into the ground 
and connected to a nearby water or hydrant pipe. Insulation 
resistance of PVC jacket shall be measured between the 
aluminium wire armour and the spike with a 500/1000V 
insulation tester. Measured resistance shall not be less than 
2.5M OHM per KM. Thereafter 10KV DC shall be applied for one 
minute in the same way. After the test the armour shall be kept 
earthed to the steel spike for 15 minutes for discharging residual 
charge. 
4.2  Statutory  a) Road cutting permission 

Page 14 of 44
                                                                                             GN101-03-SP-06-R3 

clearance  Road cutting permission shall be taken from competent authority by 
vendor. How ever official fees shall be paid by BRPL. 
b) Electrical inspector clearance 
Electrical Inspector clearance shall be in vendor scope. How ever 
official fees shall be paid by BRPL.  
 

5.0 Progress Reporting: 

S.  Parameter  Details 


No. 
5.1 Detailed Progress  Progress report to be submitted by Contractor to BSES once in 
report  a Week containing 
i) Excavation status 
ii) Cable laying status 
iii) Status of preparedness for Jointing 
iv) Reason for any delay in total programme 
v) Details of damage to cable during laying. 
vi) Progress on final completion / Constraints / Forward path 
6.0 Drawing, Data & Manuals: 

S.  Parameter  Details 


No. 
6.1  To be  submitted  As the works is completed the following reports in quadruplicate shall be 
After Completion  submitted to BSES for record purpose and shall be incorporated in the 
of the Job  ‘As constructed Records’. 
a) Feeder details ( sending end, receiving end, SAP number 
of project etc) 
‐ Type of cables, cross section area, rated voltage. Details of construction, 
cable number & drum number. 
‐ Year and month of laying. 
‐ Actual total route length, cable length, length between joint to joints or 
end. 
‐ Location of cables and joints in relation to certain fixed reference 
points, for example buildings, hydrant, boundary stones etc. 
‐ Jointing reports detailing the date, weather conditions, jointers and 
supervising Engineers names, details of type of cable and type of joint or 
termination, location and joint bay number, ambient temperature. 
‐ Results of original electrical measurements and testing on cable 
installation. 
‐ Full written reports will be required of any damage occurring to cable or 
equipment together with remedial action proposed which will be subject 
to the approval of BSES. 
6.2  Drawing and  Standard size paper A0, A1, A2, A3, A4 
document sizes 
 

Page 15 of 44
                                                                                             GN101-03-SP-06-R3 

7.0.0 Deviations 
 
Deviations from this Specification shall be stated in writing by the contractor. Written approval shall 
be obtained from BSES by the contractor. In absence of such a statement, it will be assumed by BSES 
that the Contractor complies fully with this specification during execution of the job. 
 
Deviation mentioned in any other submitted tender docs like in GTP, QAP, Old PO, old WO, BRPL 
Standard, vendor standards etc. shall not be considered as a deviation at any stage of contract.  
 
 The format for approval of deviation attached in annexure # 1 
 
Annexure # 1 – DEVIATION REPORT FORMAT 
 
S.  Clause No. of  Details about  Reason for  Approved by (Sign & 
NO.  Specification  deviation  deviation  Name) 
         
         
         
         
         
 

Annexure # 2 – DC HIGH VOLTAGE TEST 

 
Rated Voltage   Test Voltage Between  Duration in Min. 
of cable in KV 
  Any conductor and  Conductor to    
metallic sheath /  conductor (for 
Screen / armour  unscreened Cables) 
0.65 / 1.1  3  3  15 Min 
6.35 / 11  18  30 
19 / 33  60  ‐‐‐‐ 
38 / 66  90  ‐‐‐‐ 
 
Reference value for DC High voltage Test. 

Page 16 of 44
                                                                                             GN101-03-SP-06-R3 

Annexure # 3 – CABLE TRENCH DETAILS 
 
S. No.  Cable Size  Trench    Cable Trench drawing 
reference 
    Width (mm)  Depth (mm)   
1  1.1 kV LT Cables       
a  3.5Cx150 mm2 ‐ Single  400  875  A – 1 (Drg. # 9) 
Circuit 
b  3.5Cx150 mm2 ‐ Double  400  875  A – 1 (Drg. # 9) 
Circuit 
c  3.5Cx150 mm2 ‐ Triple  400  875  A – 1 (Drg. # 9) 
Circuit 
d  3.5Cx300 mm2 ‐ Single  400  875  A – 1 (Drg. # 8) 
Circuit 
e  3.5Cx300 mm2 ‐ Double  400  875  A – 1 (Drg. # 8) 
Circuit 
f  3.5Cx300 mm2 ‐ Triple  400  875  A – 1 (Drg. # 8) 
Circuit 
         
2  11 KV Cables       
a  3Cx150 / 300 mm2 ‐ Single  400  1055  A – 2 (Drg. # 6) 
Circuit 
b  3Cx150 / 300 mm2 ‐Double  650  1055  B – 1 (Drg. # 7) 
Circuit 
         
3  33 kV Cables       
a  3Cx400 mm2 ‐ Single Circuit  400  1235  A – 3 (Drg. # 3) 
b  3Cx400 mm2 ‐ Double  650  1235  B – 2 (Drg. # 4) 
Circuit 
c  3Cx400 mm2 ‐ Quadruple  650  1235  B – 2 (Drg. # 5A) 
Circuit 
d  3Cx400 mm2 ‐ Quadruple  650  1545  B – 3 (Drg. # 5B) 
Circuit 
e  3Cx400 mm2 ‐ Quadruple  1200  1235  C – 1 (Drg. # 5C) 
Circuit 
         
4  66 kV Cables       
a  1Cx630/1000 mm2 ‐ Single  650  1445  B – 4 ( Drg. # 1) 
Circuit 
b  1Cx630/1000 mm2 ‐ Double  1200  1445  C – 2 (Drg. # 2) 
circuit 
c  3Cx300 mm2 ‐ Double circuit 1200  1445  C – 2 (Drg. # 2A) 
 

Page 17 of 44
 

                                                                                             GN101-03-SP-06-R3 

 
Annexure # 4 – Standard Road Profile 
 

 
 

Page 18 of 44
 

                                                                                             GN101-03-SP-06-R3 

Page 19 of 44
 

                                                                                             GN101-03-SP-06-R3 

Annexure # 5 – Road Restoration Sectional Drawing 
 

 
 

Page 20 of 44
 

                                                                                             GN101-03-SP-06-R2 

 
 

Page 21 of 44
 

                                                                                             GN101-03-SP-06-R3 

 
 

Page 22 of 44
GN101-03-SP-06-R3

Annexure # 6 – DRAWINGS ( CABLE TRENCH AND RCC CABLE COVER)

Page 23 of 44
Page 24 of 44
Page 25 of 44
Page 26 of 44
Page 27 of 44
Page 28 of 44
Page 29 of 44
Page 30 of 44
Page 31 of 44
Page 32 of 44
Page 33 of 44
Page 34 of 44
Page 35 of 44
Page 36 of 44
Page 37 of 44
GN101-03-SP-06-03

Annexure-7: Barricading and Safety


1. Dimensions of barricading- Height- 2 mtr, Length- 1.5 mtr. Refer drawing
enclosed with tech spec for more details.
2. There shall not have any gap in between two barricades. Edge to edge shall be
intact.
3. LED Bacon light shall be placed at 1st and 4th barricade and same shall be
continue
4. Name, painting, colour, clean ness etc. shall be done on regular basis.
5. Vendor to ensure that traffic management shall not be excuse of work
execution. The contactor shall not undertake loading and unloading at
carriageways obstructing the free flow of vehicular traffic and encroachment
of existing roads by the contactor applying the excuse of work execution.
6. Full height fence, barriers, barricades etc. shall be erected around the site in
order to prevent the working area from the risk of accidents due to speedy
vehicular movement. Same the way barricades protect the road users from the
danger due to construction equipment and temporary structures.
7. The structure dimensions of the barricades , material and composition, its
colour scheme, BSES logo and details shall be in accordance with
specification and drawing laid down in the tender documents.
8. All the barricades shall be erected as per the design requirements of employer,
numbered painted and maintained in good condition and also barricade in
charge maintain a barricade register at site
9. All barricades shall be conspicuously seen in the dark/night time by the road
users so that no vehicle hits the barricades. Conspicuity shall be ensured by
affixing retro reflective strips of required size and shape at appropriate angle at
bottom and middle portion of the barricades at a minimum gap of 1000 mm. In
addition minimum one red light /red blinker and red beacon light should be
placed at the top of each barricade.
10. No dust deposit at the front side of barricades.
11. Cable drum shall be returnable and vendor shall take it back (by bye back
process) from site at their own risk and cost.
12. Once cable lying complete of a drum, within two days empty drum shall be
removed from site by bye back process.
13. Trained traffic marshal with all PPE and traffic control light (Red and Green)
shall be placed at site for 24x7.
14. No excuse of theft (beyond 6 hrs. of FIR) shall be acceptable.
15. During execution of job, any damage to other agency’s properties shall be
counted in vendor account and necessary action shall be taken by vendor to
recover, repair etc.
16. Excess earth shall be removed from site after back filling. Site to be cleared to
avoid flowing of dust. Barricades to be removed from site with in 24 hrs. after
completion of job.
17. During non working hrs. vendor to ensure presence of supervisor for
controlling any event from locals.
18. PPEs

• Helmets

Page 38 of 44
GN101-03-SP-06-03
• Mask
• Jacket
• Shoes
• First Aid Box etc.
Shall be available at site 24x7. Zero tolerance on absence of PPEs to the
working personnel. No excuse shall be acceptable in this regards.

19. GPR/Scanning shall be done by vendor of whole the route and same shall be
submitted to BRPL. This work shall be done by vendor before execution of
job.
20. Jointing TAT- Jointing to start within 48 hrs. and shall be completed by 96
hrs.+1 day.
21. Lifting of cable drums with hydraulic machine, pulling of cable from top end
of drum with pulling machine (hydraulic winch) is mandatory.
22. Violation on barricading guideline and safety norms, a fine of Rs.5000 /day
shall be imposed. BRPL inspector/engineer in-charge shall be empowered to
impose the above penalty.

Page 39 of 44
GN101-03-SP-06-03

Annexure # 8 – ROUTE MARKER AND BARRICADING DRAWING

Page 40 of 44
Page 41 of 44
Page 42 of 44
Annexure#9-Note for HDPE Pipe Diameter in Cable Laying

1) Primarily our intent for laying cable will be through open trench only.
2) Trench dimensions shall be as per the standards which mentioned as below
table

Trench Details (mm)


Sl. no. Cable Depth (single and Width (Single Width (Double
double run) Run) Run)
1 LT Cable 875 400 400
2 11 kv 1055 400 650
3 33 kv 1235 400 650
4 66 Kv 1445 650 1200

3) QC team will do stage inspection after completion of digging to validate the depth
of trench and will give approval for issuing of cable.
4) Execution in charge to ensure the cable laying work.
5) QC team will also inspection the laying work to validate the laying as per
standards before back filling.
6) In case of site constraints, trench less cable laying shall be allowed as per the
followings-
a) Cable laying up to 50 mtr through trenchless will be allowed with approval of
circle head (O&M) for road crossing or site constraints. Site photos of
constraints shall be reviewed before approval by circle head.
b) Absence of permission for digging- written disapproval by road owing agency
and appropriate approval by circle head (for O&M Jobs), by O&M head (for
11kV, P&C job) and by EHV head (for EHV Jobs)
c) The size of HDPE (PN6, PE80) pipe shall be as per the guidelines of IS-1255,
1983, clause no-6.3.4.3. Details mentioned below in below table-

Sl. No Cable Recommended Dia of HDPE pipe (mm)

1 66kV, 3CX300 225


2 66kV, 1CX630 180
3 66kV, 1CX1000 180
4 33kV, 3CX400 180
5 11kV, 3CX300 160
6 11kV, 3CX150 160

Page 43 of 44
d) In-case of using lower size of HDPE pipe due to site conditions, the deviation
for using lower HDPE pipe from above table, written approval must be taken
through technical committee. Photos of the challenges while apparently the
same will be reviewed by technical committee.

(However, HDPE pipe size with less than 1.5XOD of cable shall not be
allowed at any stage)

Page 44 of 44
Technical Specification for

Feeder Pillar Panel

(Distribution panel without ACB)

Specification no – GN101-03-SP-18-01

Prepared / Reviewed by Approved by: Rev Date

Hemanshi Kaul Devender Sharma R1 January 12,2010

___________________________________________________________________________________________
Page 1 of 25
GN101-03-SP-17-01

Index

1.  Scope of supply ............................................................................................... 3 

2.  Codes & Standards .......................................................................................... 3 

3.  Service Conditions ........................................................................................... 3 

4.  Feeder Pillar Configuration ............................................................................. 4 

5.  Panel Construction .......................................................................................... 4 

6.  Fuse Base ......................................................................................................... 7 

7.  Operational requirements................................................................................ 7 

8.  Name Pate and Finish ...................................................................................... 7 

9.  Compacted feeder pillars. ............................................................................... 8 

10.  Testing and Inspection .................................................................................... 8 

11.  Packing and Delivery ....................................................................................... 9 

12.  Deviation ……………………………………………………………………………..9 

List of Annexure……………………………………………………………………..……..10

___________________________________________________________________________________________
Page 2 of 25
GN101-03-SP-17-01

1. Scope of supply

This shall include Design, manufacture, testing at manufacturers works before


dispatch, packing, delivery of material to BSES Stores and submission of documents
to purchaser.

2. Codes & Standards

The equipment shall confirm to this specification and latest revision of following codes
with all amendments:-

Title Indian Standard


2.1 IS 5039 Specification for distribution pillars below 1000v AC
2.2 IS 13947 part 2 Low Voltage switchgear
2.3 IS 8623 Specification for low voltage switchgear
2.4 IS 12063 Classification of degrees of protection provided by
enclosures of electrical equipment
2.5 IS 13703 Low voltage HRC fuses
2.6 IS 5 Color of ready mixed paints
2.7 IS 191 Specification for copper
2.8 IS 5082 Wrought Aluminum & Al alloy plates & sheets for electrical
applications

3. Service Conditions

The feeder pillar panel shall be designed to work satisfactorily under following service
conditions:-
Title Indian Standard
3.1 Supply Voltage 3 phase neutral, AC 433Volt +/-10%
3.2 Supply Frequency 50 Hz +/- 5%
3.3 Location of panel Outdoor, on foot path or roadside
3.4 Pollution Heavily Polluted and Dry
3.5 Humidity 90% maximum
3.6 Ambient Temperature Average 40 Deg C, Maximum 50 Deg C
3.7 Incoming supply to feeder From distribution transformer or Main feeder
pillar panel pillar panel
3.8 Seismic Zone 4

___________________________________________________________________________________________
Page 3 of 25
GN101-03-SP-17-01

4. Feeder Pillar Configuration

The feeder pillar panel shall have following configuration:-

4.0 Feeder Pillar Type Incoming feeder ( Circuit Outgoing feeder ( Circuit
ways ) & Cable size ways ) & Cable size
4.1 A-1 , 8-Way 2 X 400A TP fuse / cable 6 X 250A TP fuse / cable
size 4CX300Sqmm size 4CX150Sqmm

4.2 B-1, 5-Way 1 X 400A TP fuse / cable 4 X 250A TP fuse / cable


size 4CX300Sqmm size 4CX150Sqmm

4.3 C-1, 7-Way 1 X 250A TP fuse / cable 5 X 100A TP fuse


size 4CX150Sqmm 1 X 250A TP fuse /
cable size 4CX95Sqmm

5. Panel Construction

The feeder pillar panel construction shall confirm to following features:-

5.0 Panel Construction Free Standing floor mounted with steel frame,

Welded Construction Continuous welding from inside, Spot welding not


acceptable.
5.1 Ingress Protection IP 55 as per IS 12063
class for enclosure

5.2 Material Galvanized sheet Steel CRCA

5.3 Sheet Steel Thickness 3mm - Support frames


2mm Galv. - Covers, Doors & Canopy

5.4 Base frame for 8 Way 3mm MS Channel 50mm height painted in Black
& 7 way panel Color
5.5 Bottom holes on four Oval Shape, for grouting bolts
Sides
5.6 Pedestal for 5 way Of height 400mm with side covers of FRP or
Galvanized MS painted in black

5.7 Cable entry From Bottom only

5.8 Lifting Lug 2 nos lug welded on top

5.9 Canopy on top With minimum 10 Deg C slope extended 50mm


outside panel front and rear

___________________________________________________________________________________________
Page 4 of 25
GN101-03-SP-17-01

5.10 Door type for front & Centre Opening double leaf with insulating rubber grip
rear access handle

5.11 Double leaf doors Right hand side leaf can be opened only after left
hand side leaf

5.12 Door Hinges Minimum three anti theft type hinges


MS screw -3mm dia & 8mm length
Tight fit brass tube – 100mm ID, 12.7mm OD & 20mm
length
5.13 Door Opening angle Min 120 Deg

5.14 Padlocking facility For Front and Rear door by total 4 nos L- drop
arrangement. 2 nos front door and 2 nos rear door.

5.15 Locking facility on By L- drop type arrangement


door
5.16 Tower bolts at top and On left hand side door
bottom of door
5.17 External hardware Galvanized steel nut and bolts

5.18 Phase & Neutral bus Aluminum grade 19501 ( H2 )


as per IS 5082
5.19 Bus bar color coding Heat shrinkable tape of color Red , Yellow , Blue &
for R, Y , B and Black respectively.
Neutral
5.20 Bus Bar size in mm Phase Neutral

5.20.1 8 - Way 50X10 mm 50X10 mm

5.20.2 5 - Way 50X6 mm 50X6 mm

5.20.3 7 - Way 50X6mm 50X6 mm

5.21 Bus for 8 – Way Bolted type removable link to be provided at middle of
all the phases and neutral bus bar to adapt two
incomers from separate source.
5.22 Earth Bus at panel 25X6mm Aluminum
bottom
5.23 Bus bar arrangement Horizontal, with R phase bus at top

5.24 Neutral bus bar With holes for connection incoming and outgoing
cables up to 300Sqmm
5.25 Bus Bar support SMC / DMC, 1100v Grade
insulators

5.26 Bus Bar phase FRP / Acrylic insulating sheet


barriers

___________________________________________________________________________________________
Page 5 of 25
GN101-03-SP-17-01

5.27 Cable size


4CX300Sqmm cable
Incoming for 8 way
panel
5.28 Incoming for 5 & 7- 4CX300Sqmm cable for 5 Way & 4CX150Sqmm
Way panel cable for 7 Way panel
5.29 Outgoing for 8 way 4CX150Sqmm cable
panel
5.30 Outgoing for 5 & 7- 4CX150Sqmm cable for 5 Way & 4CX95Sqmm cable
Way panel for 7 Way panel
5.31 Terminals for cables Al grade 19501 ( H2) as per IS 5082, with galvanized
steel nut bolts size M10 & two plane washers + spring
washers & spacers
M16 size nut bolt for incomer of 8 way panel

5.32 Terminal shape ‘ z ‘ Strips , 2nos per terminal


5.33 Z Strip dimensions 8 way panel incomer 50 X 10 mm
supported on
insulators 5 & 7 way panel incomer 50X6 mm

All outgoing feeders 40X6mm

5.34 Ease of taking current Possible with Z Strip terminal


reading with open
clamp type ammeter

5.35 Gland plate at panel Galvanized MS, 3mm thick for multi core cable
bottom

5.36 Cable supports Non ferrous clamps at bottom

5.37 Cable termination 300mm minimum


clearance from gland
plate
5.38 Earth studs on both With M10 galvanized steel nut bolts
side of panel bottom
5.39 Flexible earth Flexible PVC Cu wire 2.5Sqmm green color
connection to doors
5.40 Panel maximum Width Depth Height
dimensions in mm
8 - Way 1225 650 1650
5 - Way 900 550 1850
7- Way 1050 650 1650
5.41 Holder for lamp for 8 230v Incandescent lamp controlled through 2amp
way panel SPMCB
5.42 Small power socket 5/15 amp 3pin socket controlled through 16amp
for 8 way panel SPMCB

___________________________________________________________________________________________
Page 6 of 25
GN101-03-SP-17-01

6. Fuse Base

The equipment shall have all the following features –


6.1 Fuse base connection to main bus By bus bar and not by flexible jumpers
bar
6.2 Size 2as per IS 13703 for 400A

6.3 Current rating of fuse base at 8 way & 5 way 400A,


maximum ambient temperature 7 way – 250A
50Deg C
6.4 Fuse base current carrying part Plated copper as per IS191
6.5 Fuse base insulating material DMC / Porcelain
6.6 Make For DMC - GE, Siemens, L& T, ABB
For porcelain – Sample to be
approved by BSES.
6.7 Fuse base mounting screws With insulating caps
6.8 FRP Barriers for open live parts 1.6mm thick white colored sheet
6.9 HRC fuse pullers – 1 no / Type of Suitable for 400A, 250A & 100A HRC
fuse fuse

7. Operational requirements

7.1 Clearance between phase to Minimum 25mm


phase and phase to earth
7.2 Continuous rated operating 433 volt +/- 10 %
voltage
7.3 Power frequency high voltage 2000Volt
withstand capacity for one minute
7.4 Insulation resistance value for Minimum 100MOhm with 500V
phase and neutral bus bar Megger
7.5 Temperature rise above ambient As per IS 13947_1
45 Deg C

8. Name Pate and Finish

8.1 Name plate On front door top left side showing


1) Purchase name and PO number
2) Manufacturer name
3) Month & year of manufacturing
4) No of ways
5) Property of BSES
8.2 Labels for incoming and outgoing Sticker type labels inside panel door
feeders
8.3 SLD SLD to be screen printed inside the
front door.
___________________________________________________________________________________________
Page 7 of 25
GN101-03-SP-17-01

8.4 Marking for panel earth stud Green letter ‘E’, on riveted AL label

8.5 Danger board in English and local Red color background with black
language, riveted on doors lettering on 1.6mm thick Al plate

8.6 Surface preparation for painting Sand blasting or 7 tank process


8.7 Painting Powder coated grade A polyester paint
with min thickness 60 microns
8.8 Paint shade Shade – 538 as per IS:5 – Post office
red
8.9 Fluorescent strip painting on 50mm wide horizontal strip of
panel fluorescent paint around panel in the
middle of panel

9. Compacted feeder pillars.

9.1 Door type for front access Centre Opening double leaf with
insulating rubber grip handle only front
side.
9.2 Rear side No door at read side. Panel to be
access only from front.
9.3 All other constructions shall be as per above mentioned construction
9.4 Use of compacted feeder pillars Where sufficient space at rear side is
not available due to space constraints
at site.

10. Testing and Inspection

The equipment shall have all the following features –


10.1 Type test Only type tested components – fuse
base, insulators and aluminum bus
bar shall be accepted
Test reports as per relevant IS to be
submitted by vendor
10.2 Test report validity Valid for last 5 years
10.3 Acceptance and routine test 1) Visual inspection, dimension
(Inspection test witness by checks and paint thickness check.
purchaser) 2) Bill of material check
3) Wiring checks.
4) Insulation resistance test for main
and auxiliary circuit
5) High voltage test on main and
auxiliary circuit
6) Operational check
10.4 Tolerances on panel dimensions Maximum +/- 5mm

___________________________________________________________________________________________
Page 8 of 25
GN101-03-SP-17-01

10.2.9 No negative tolerance on bus bar dimensions and bus bar clearances

10.2.10 Prototype panel to be approved by BSES

11. Packing and Delivery

11.1 Packing protection Against Shocks, vibration and


corrosion
11.2 Packing identification labels To show purchaser name, PO
number, Manufacturer serial
number
11. 3 Handling instruction To be marked on packing boxes

12. Deviation

Deviation to specification to be submitted in writing by vendor. Bidder to submit copy


of specification and GTP along with company seal and signature on each page.

___________________________________________________________________________________________
Page 9 of 25
GN101-03-SP-17-01

List of Annexure

Annexure A – Guaranteed Technical Particular

Annexure B – General arrangement drawing for 8 Way Panel

Annexure C – General arrangement drawing for 5 Way Panel

Annexure D – General arrangement drawing for 7 Way Panel

Annexure E – General arrangement drawing for compacted type 8 Way Panel

___________________________________________________________________________________________
Page 10 of 25
GN101-03-SP-17-01

ANNEXURE A Guaranteed Technical Particulars

Bidder to submit hard copy duly filled and signed along with techno commercial offer.
Bidder to submit separate GTP for each type of feeder pillar panel

S. BRPL / BYPL
Particulars Vendor Data
No Requirement
Name

1 Manufacturer Address

Contact no.

2 Type of Panel Offered 8-way , 5-Way & 7-Way

3 Main bus bar rating As per clause 4.1 to 4.3

Quantity

Rating in amp
4 No. of Incoming feeders

HRC fuse type / make

Quantity

Rating in amp
5 No. of Outgoing feeders

HRC fuse type / make

Galvanized CRCA sheet


6 Panel construction
steel
MinIP55- ingress protection
7 Panel enclosure class

Galvanized sheet steel 2MM min. for cover, doors


8
thickness & canopy

3mm MS channel 50mm


Base frame for 8 way &
9 height painted in black
7 way only
color

___________________________________________________________________________________________
Page 11 of 25
GN101-03-SP-17-01

Of height 400mm with side


10 Pedestal for 5 Way covers of FRP or Galv. MS
painted in black.

Centre opening double leaf


Door type for front &
11 with insulating rubber grip
rear access
handle

Minimum three anti theft


12 Door Hinges
type hinges
13 Padlocking facility Provided

L- drop type locking 2 nos of each front and


14
arrangement at door rear door
15 External steel hardware Galvanized nut & bolts

Aluminum grade 19501 (


16 Phase & neutral bus bar
H2 ) as per IS5082

Heat shrinkable tape of


Bus bar color coding for
17 Red, Yellow, Blue & Black
R, Y , B & neural.
color

18 Bus bar size in mm


Phase= 50X10MM
8 Way
Neutral= 50X10MM
Phase= 50X6MM
7 Way
Neutral= 50X6MM

Phase= 50X6MM
5 Way
Neutral= 50X6MM

18 Earth bus size 25x6mm Aluminum


Main bus bar short
19 circuit withstand ……………In KA for 1sec
capacity
Main bus bar maximum
20 above ambient of 45 deg C
temperature rise
Bus bar support
21 SMC / DMC, 1100V grade
insulators
Al grade 19501 ( H2) as
per IS 5082, with
Terminals suitable for galvanized steel nut bolts
22
cables size size M16 & two plane
washers + spring washers
& spacers

___________________________________________________________________________________________
Page 12 of 25
GN101-03-SP-17-01

Incoming cable for 8 & 5


23 4CX300Sqmm
way panel
Incoming cable for 7
24 4CX150Sqmm
way panel
Outgoing cable for 8 & 5
25 4CX150Sqmm
way panel
Outgoing cable for for 7
24 4CX95Sqmm
way panel
Z' strips supported on
25 Terminal shape
insulator, 2per terminal

8 way panel 50x10mm


Z Strips dimensions
26
7 & 5 way panel 40x6mm
Gland plate at panel Galv. MS 3mm thick for
27
bottom multi core cable
Cable termination
28 300mm minimum from
clearance
gland plate
Earth studs on both side With M10 galvanized steel
29
of panel bottom nut bolts
Panel maximum
30
dimensions in mm
Width - 1225, Depth - 650,
8 - Way
Height - 1650

Width - 1050, Depth - 650,


7- Way
Height - 1650

Width - 900, Depth - 550,


5- Way
Height - 1850
Holder for 230V Controlled through 2amp
31
Incandescent Lamp SPMCB

5/15 amp 3pin socket Controlled through 16amp


32
power socket SPMCB

Fuse base size as per Size 1 for 250A


33 IS13703
Size 2 for 400A
Current rating of fuse
base at max. ambient
8 & 5 -WAY - 400A
34 temperature 48deg C
7- way - 250A
Fuse base current
carrying part
Fuse base current Plated copper as per IS
35
carrying part 191

___________________________________________________________________________________________
Page 13 of 25
GN101-03-SP-17-01

36 Fuse base material DMC/ Porcelain

For DMC - GE, Siemens,


37 Make L&T or ABB
For Porcelain - -----------
HRC fuse pullers - 1no/ Suitable for 400A, 250A
38
Type of HRC Fuse and 100A HRC fuse & link

Phase- phase &


Clearance between live
39 parts minimum 25mm
Phase -earth

Continuous rated
40 433volt +/- 10%
operating voltage
High voltage withstand
41 2000V at 50Hz for 1 min.
capacity

Insulation resistance Minimum 100Mohm with


42
Ph- Ph & Ph-earth 500v Meggar

43 Labels & name plates As per specification

Surface preparation for Sand blasting or 7 tank


44
painting process

Power coated grade A


45 Painting polyester paint min.
thickness 50 microns

46 Shade - Post office red Shade - 538 as per IS:5

Fluorescent paint strip 50mm wide painted in the


47 on panel middle of panel

Foundation Bolts Required


48

___________________________________________________________________________________________
Page 14 of 25
GN101‐03‐SP‐80‐00 
 
                                 TECHNICAL SPECIFICATION OF NUT, BOLTS & WASHERS 
 
 
 
 
 
INDEX 
 

1.  SCOPE OF SUPPLY 3 

2.  CLIMATIC CONDITION 3 

3.  CODES & STANDARDS 3 

4.  TESTS 3 

5.  INSPECTION 4 

6.  TEST CERTIFICATES 4 

7.  INSPECTION AFTER RECEIPT AT STORE 4 

8.  MARKING 4 

9.  PACKING 4 

10.  GTP FOR NUT,BOLTS & WASHERS 5 

11.  INSPECTION TESTING CRITERIA 7 


 

Page 2 of 9 
 
GN101‐03‐SP‐80‐00 
 
                                 TECHNICAL SPECIFICATION OF NUT, BOLTS & WASHERS 
 
 
 
1. SCOPE OF SUPPLY 

The specification covers the manufacturing, testing and inspection of Nut, Bolts & Washers. 

2.   CLIMATIC CONDITION 
The  material  to  be  supplied  against  this  specification  shall  be  suitable  for  satisfactory 
operation under following climatic condition 
 
Location  At various location in the Delhi 
Maximum ambient temperature (⁰C)  50 
Minimum ambient temperature (⁰C)  0 
Maximum altitude above mean sea level  1000 
(m) 
Relative Humidity (%)  100 
Rainy month  June to October 
Maximum Rainfall (mm)  1450 
Wind Pressure (Kg/Sq.m)  195 
Seismic Zone  Zone IV as per IS : 1893 

3. CODES & STANDARDS 
The Nut & bolt shall be designed, manufactured and tested in Accordance with the following 
Indian standards. 

IS‐ 12427  Specification for Transmission Tower Bolts 
IS‐4072  Steel for Spring Washer 
IS‐3063  Single Coil Rectangular section Spring Washer for bolt, nut & Screw 
IS‐1586  Methods for Rockwell Hardness test for steel 
IS‐2016  Plain Washer 
ISO 898/1‐1988  Metric Bolts, Screws and Studs 
IS‐2633  Methods of testing of uniformity of coating of zinc coated articles  
IS‐6745  Method of determining of mass zinc coating on zinc coated iron &  
steel articles 
IS‐1363 (All parts)  Hexagonal bolts & nuts 
IS‐1367 (Part‐iii)  Technical supply condition for threaded steel Fastner 
IS‐4759  Hot dip Zinc coating on structural Steel & other allied Products 
DIN 127 A  Spring Lock Washers 

4. TESTS 
All types of test including routine test shall be carried out according to IS : 1367‐1967 or its latest 
amendment. 

Page 3 of 9 
 
GN101‐03‐SP‐80‐00 
 
                                 TECHNICAL SPECIFICATION OF NUT, BOLTS & WASHERS 
 
 
 
5. INSPECTION: 
The material shall be inspected and tested before dispatch by an authorized representative of 
the BSES in respect of quality. In case the supplier is not in position to get these tests carried out 
at his work, such test may get be carried out by hum at any NABL accredited lab at his own 
expenses. 

6. TEST CERTIFICATES: 
The supplier shall supply one set of test certificates from any NABL accredited lab in respect of 
quality as per IS: 1363‐1967 with latest amendment for approval of the purchaser. 

7. INSPECTION AFTER RECEIPT AT STORE: 
BSES inspector will inspect the material received at BSES Store and shall have right to reject if 
found different from the reports of pre‐dispatch inspection. 

8. MARKING: 
      The material shall be marked with the ISI certification mark. 

I. Manufacture’s name or trade mark. 
II. Place of manufacturers. 
III. The name & designation of consignee 
IV. Ultimate destination as required by the purchaser. 
V. Net weight with description of material. 
VI. The marking shall be stencilled in delible link on gunny bag. 
VII. The manufacturer's identification symbol. 
VIII. The hexagonal head bolts shall be marked with the following symbols on the top surface 
of  the  bolt  head  either  embossed  or  identified  as  given  below.  The  manufacturer's 
identification symbol. 
IX. Minimum height of marking shall be 3.0 mm. When embossed, marking shall project not 
less  than  0.3  mm  above  the  surface  of  the  head  and  total  head  height  (Head  plus 
marking) shall not exceed the specified maximum head height plus 0.4 mm. 

9. PACKING: 
The  supplier  shall  be  responsible  for  suitable  packing  of  all  the  material  and  marking  on  the 
consignment, so as to avoid any damage during transport and storage and to ensure correct dispatch 

Page 4 of 9 
 
GN101‐03‐SP‐80‐00 
 
                                 TECHNICAL SPECIFICATION OF NUT, BOLTS & WASHERS 
 
 
 
to the destination. The packing shall be conforming to the requirement laid down in IS : 3256‐1965 
or its latest amendment.  
Electro galvanized spring washers shall be packed in cartons of 500 or 1000 numbers. 
Each carton containing the spring washers shall be marked with the manufacturer's name 
Or trade mark, type, nominal size and quantity of the washers. 

10. GTP FOR NUT, BOLTS & WASHERS :
S. 
Technical particular  Hot Dip galvanized Hexagonal bolt 
No. 
Mechanical Properties/ particular to which the 
Bolt will confirm IS 1367 (Part ‐2)‐1979 
1  product grade –C   
i  Tensile Strength   N/mm2 (Strength under wedge loading) 
ii  Rockwell hardness  HRB 
iii  Yield Stress  N/mm2 
Iv  Stress under proof load  N/mm2 
v  Strength under wedge loading  Kg/mm2 
vi  Wt of Zinc Coating  g/mm2 
vii  Shear strength  N/mm2 
2.   Specification & standards for M.S. Bolts &  As per IS 1363(part 1 & 3) IS: 1367( part 3 & 6) IS: 1367 
Nuts(Black)   (part 17) & other Relevant standards with latest 
amendments 
3.   Property class:  
a. Bolts   a. I) M10 to M16, length 40 mm to 80 mm 
  min HT 4.8 grade  
  ii)For others  min 4.6 grade  
b.  Nuts   b. Min 5  
4.   Size   Assorted size  
5.   Tolerance   As per IS  
6.   Raw material:  
a) Grade  As per IS :2062  
 b) Type of steel used    
Low Carbon Steel(Grade C) as per IS : 2062 

Page 5 of 9 
 
GN101‐03‐SP‐80‐00 
 
                                 TECHNICAL SPECIFICATION OF NUT, BOLTS & WASHERS 
 
 
 
7.   Chemical composition (%)  
a) For Hexagonal bolts: 
 i) Carbon (Max.) 
 ii) Phosphorous (Maxm.)  
0.55%
iii) Sulphur (Maxm.)  0.05%
 b) For Hexagonal nuts:  0.06%
 i) Carbon (Maxm.)  0.50%
 ii) Phosphorous(Maxm.)   0.06%
iii) Sulphur (Maxm.)    0.15% 
8   Mechanical properties: i) For Hexagonal bolts:  As per IS: 1367( Pt. 3) 400 225 114 Min. to 258 Maxm. 
a) Tensile strength N/mm Sq. Minm. b) Stress  67 Min. to 99.5 Max. 120 Min. to 250 Maxm. 22% 400 
under proof load N/mm Sq.Minm. c) Brinell  No Fracture As per IS: 1367 (Pt.6) 610 130 Min. to 302 
Hardness HB d) Rockwell Hard HRB e) Vickers  Max.  
Hardness HV f) Elongation after fracture g) 
Strength under wedg. Loading N/mm 
Sq.Minm. h) Head soundness ii) For Hexagonal 
nuts a) Proof stress N/mm Sq.min. b) Vicker 
Hardness HV‐HV‐Minm/Maxm  
9  Sampling procedure  As per IS :2614/1969 with latest amendments.  
10   Packing details   Material to be supplied in double gunny bag of 50Kg

PLAIN WASHERS:

The  plain  washers  shall  be  Hot  dip  Galvanized  in  accordance  with  the  requirements  of  lS:4759‐1984   
"Specification for Hot‐Dip Zinc coating on structural steel and other allied products" (Second‐revision) except 
that the minimum value of the average mass of coating shall be 300 g/m2,shall be conforming to lS: 1363-
1967. Plain washers shall be conforming to lS: 2016-1967.

SPRING WASHERS:

Page 6 of 9 
 
GN101‐03‐SP‐80‐00 
 
                                 TECHNICAL SPECIFICATION OF NUT, BOLTS & WASHERS 
 
 
 
 

11. INSPECTION TESTING CRITERIA :
Sr  Testing  Lot Size 
Requirement  Product    BSES lot Size 
No.  Standards  (Manufacturers) 
Chemical  Every 20th 
1  NBW    IS : 228  Each Consignment 
Composition  Consignment 
NBW    Every 20th 
2  Dimension  IS : 2141 ‐ 2000  Each Consignment 
Consignment l 
NBW    As per relevant  Every Fifth  Every 20th 
3  Tensile Strength 
IS  Consignment  Consignment 
NBW    Every Fifth  Every 20th 
4  Proof load Test  IS : 898‐2 1992 
Consignment  Consignment  
NBW   
5  Coating Test          
NBW    Every Fifth  Every Fifth 
5.1  Wt of of Zinc Coating  IS : 6745 ‐ 1972 
Consignment  Consignment 
Uniformity of Zinc  NBW    Every Fifth  Every Fifth 
5.2  IS : 2633 ‐ 1986 
Coating  Consignment  Consignment 
Adhesion of Zinc  NBW    Every Fifth  Every Fifth 
5.3  IS : 4826 ‐ 1979 
Coating  Consignment  Consignment 
 

Page 7 of 9 
 
GN101‐03‐SP‐80‐00 
 
                                 TECHNICAL SPECIFICATION OF NUT, BOLTS & WASHERS 
 
 
 
Note: ‐    

• Corrosion  Protection  (all  items  shall  be  hot‐dip  galvanised  in  accordance  with  AS  4680  or 
AS1214) 
• Hot dip Galvanized Bolt with one Nut, two Plain Washer and one Spring Washer which is electro 
galvanised 
• Nickel  chromium plated bolts with one Nut, two Plain Washer and one Spring Washer which is 
electro galvanised 
• Full  threading  is  required  for  bolts  sizes  up  to  length  100mm  and  minimum  thread  length  of 
38mm for bolts sizes having length more than 100mm 
• All electrical connection hardware ( M10 to M16, length 40 mm to 80 mm) shall be minimum HT
4.8 grade for other size 4.6 grade. 

S.No Description
  Bolt (G.I)
1  BLT,HEX,M16X150MM;GI
2  BLT,HEX,M16;175MM;GI
3  BLT,HEX,M16;225MM;GI
4  BLT,HEX,M16;250MM;GI
5  BLT,HEX,M16X300MM;GI
6  BLT,HEX,M16;350MM;GI
7  BLT,HEX,M16;125MM;GI
8  BLT,HEX,M10;40MM;GI;4.8
9  BLT,HEX,M12X40MM;GR 4.8
10  BLT,HEX,M16;100MM;GI
11  BLT,HEX,M16;75MM;GI GR 4.8
12  BLT,HEX,M6X20MM;GI
13  BLT,HEX,M16;200MM;GI
14  BLT,HEX,M16;400MM;GI
15  BLT,HEX,M16;25MM;GI GR 4.8
16  BLT,HEX,M12X60MM;GI;FULL THRD GR 4.8
17  BLT,HEX,M16X40MM;GI GR 4.8
18  BLT,HEX,M8X130MM;GI;MET
19  BLT,HEX,M12;60MM;GI; GR 4.8
20  BLT,HEX,M6X35MM;GI;GR 4.6;FULL THRD
  Bolt (Nickel Chromium)
21  BLT,HEX,M16X100MM;NKL CHROMIUM
22  BLT,HEX,M12X50MM;NKL CHROMIUM GR 4.8
23  BLT,HEX,M16X 50MM;NKL CHROMIUM GR 4.8
24  BLT,HEX,M10X75MM;NKL CHROMIUM GR 4.8
25  BLT,HEX,M12X75 MM;NKL CHROMIUM GR 4.8
26  BLT,HEX,M16X75MM;NKL CHROMIUM GR 4.8
  Bolt (MS)
27  BLT,HEX,M16MM;80MM;MS; GR 4.8 MET

Page 8 of 9 
 
GN101‐03‐SP‐80‐00 
 
                                 TECHNICAL SPECIFICATION OF NUT, BOLTS & WASHERS 
 
 
 
28  NUT,HEX,M10X40MM;MS;NUT BLT WSHR
29  BLT HEX MS ‐‐ MC 150MM M16
30  NUT,HEX,M10X40MM;MS;NUT BLT WSHR
31  BLT,HEX,M8X75MM;GALVANIZED ZN COATED MS
 
  Eye Bolt
32  BLT,EYE,25MM;240MM;M12
33  OEM,EYE BLT OPERTG RD;1HYN400075P1
  Washer (Spring)
34  WSHR,SPRNG,21MM;13MM;2.5MM;GALVANIZED MS
35  WSHR,SPRNG,11MM;17MM;2.5MM;GALVANIZED MS
  Washer (Flat)
36  WSHR,FLT,37MM;13MM;3MM;NKL CHROMIUM
37  WSHR,FLT,50MM;17MM;3MM;NKL CHROMIUM
38  WSHR,FLT,24MM;13MM;2MM;GALVANIZED MS
39  WSHR,FLT,21MM;11MM;2.35MM;GALVANIZED MS
40  WSHR,FLT,30MM;10.5MM;2.5MM;NKL CHROMIUM
41  WSHR,FLT,23.8MM;8.4MM;2MM;NI CHROMIUM
  Washer (Sling)
42  WSHR,SLNG,NEOPRENE;FOR M12STM
43  WSHR,SLNG,NEOPRENE;10MM;14MM;2MM
  Washer (Teflon)
44  WSHR,TEFLON;22X32X5MM
45  WSHR,TEFLON;12X20X5MM
46  WSHR,TEFLON;18X22X5MM
47  WSHR,TEFLON;15X30X5MM
48  WSHR,TEFLON;20X30X5MM
49  WSHR,TEFLON;35X22X5MM
50  WSHR,TEFLON;46X32X5MM
51  WSHR,TEFLON;25X15X5MM
  Washer (Brass)
52  WSHR,BRASS;LV FOR 990KVA XMER
53  WSHR,HEX;LV BRASS;FOR 630KVA TRAFO
54  WSHR,PLN;LV BRASS WSHR FOR 100KVA XMER
55  WSHR,CLAMPING MEMBER;AL;FOR HV BSHG
56  WSHR,BRASS;FOR HV SIDE TRNSF
  Hex Nut  (MS)
57  NUT,HEX,M10X40MM;MS;NUT BLT WSHR
58  NUT,LOCK,SHEARING;M6X25MM;5;SHEA;MS;A
59  NUT,HEX,M16;GALVANIZED MS
 

Page 9 of 9 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
 
 
INDEX 
 

1.  SCOPE OF SUPPLY  3 

2.  CLIMATIC CONDITION  3 

3.  CODES & STANDARDS  3 

4.  TESTS  4 

5.  INSPECTION:  4 

6.  TEST CERTIFICATES:  4 

7.  INSPECTION AFTER RECEIPT AT STORE:  4 

8.  MARKING:  4 

9.  PACKING:  4 

10.  GTP FOR G.I. PIPE (40 MM):  5 

11.  GTP FOR G.I. PIPE (20 MM / 32 MM) :  6 

12.  GTP FOR G.I. PIPE (100 MM) :  7 

13.  INSPECTION TESTING CRITERIA:  10 


 

Page 2 of 2 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
 

1. SCOPE OF SUPPLY 

The specification covers the manufacturing, testing and inspection of G.I Conduit & Earthing Pipe 

2.   CLIMATIC CONDITION 
The material to be supplied against this specification shall be suitable for satisfactory operation 
under following climatic condition 
 
Location : At various location in the Delhi 
Maximum ambient temperature (⁰C)  50 
Minimum ambient temperature (⁰C)  0 
Maximum altitude above mean sea level (m)  1000 
Relative Humidity (%)  100 
Rainy month  June to October 
Maximum Rainfall (mm)  1450 
Wind Pressure (Kg/Sq.m)  195 
Seismic Zone  Zone IV as per IS : 1893 

3. CODES & STANDARDS 
The G.I. Conduit Pipe shall be designed, manufactured and tested in Accordance with the 
following Indian standards. 

IS :1239 Part (1)  Steel Tubes, Tubular And Other Wrought Steel Fittings ‐
Specification 
IS: 2633/72 & IS:  For galvanising testing  
6745/72 
 IS 1161 : 1998  Steel Tubes for Structural Purposes 
 IS 1387: 1993  General requirements for the supply of metallurgical 
materials 
 IS 228 :1987  Methods of chemical analysis of steels 
 IS 1161 : 1998  Steel Tubes for Structural Purposes 
 IS 2629 : 1985  Recommended Practice’ for Hot‐Dip Galvanizing of Iron and Steel 

 IS 2633 : 1986  Methods for testing uniformity of coating of zinc coated articles 
 IS 
 IS 2629 : 1985  Recommended Practice for Hot‐Dip Galvanizing of Iron and Steel 
IS 2500 :2000  Sampling of  lot by lot 

Page 3 of 3 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
4. TESTS 
All  types  of  test  including  routine  test  shall  be  carried  out  according  to  IS:  1239‐1  or  its  latest 
amendment. 

5. INSPECTION: 
The material shall be inspected and tested before dispatch by an authorized representative of 
the BSES in respect of quality. In case the supplier is not in position to get these tests carried out 
at his work, such test may get be carried out by hum at any NABL accredited lab at his own 
expenses. 

6. TEST CERTIFICATES: 
The supplier shall supply one set of test certificates from any NABL accredited lab in respect of 
quality as per IS: 1239‐1 with latest amendment for approval of the purchaser. 

7. INSPECTION AFTER RECEIPT AT STORE: 
BSES inspector will inspect the material received at BSES Store and shall have right to reject if 
found different from the reports of pre‐dispatch inspection. 

8. MARKING: 
      The material shall be marked with the ISI certification mark. 

I. Manufacture’s name or trade mark 
II. ISI mark with CML No. 
III. Purchase no.  shall be stencilled indelible link 
IV. The manufacturer's identification symbol 
V. Hot marking at  every running  meter Name/logo of manufacturer, ISI, class of tube i.e. L 
for Light colour of Band 

9. PACKING: 
The  supplier  shall  be  responsible  for  suitable  packing  of  all  the  material  and  marking  on  the 
consignment, so as to avoid any damage during transport and storage and to ensure correct dispatch 
to the destination. 
 
 
 

Page 4 of 4 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
10. GTP FOR G.I. PIPE (40 MM): 
S. 
Technical particular  Unit  BSES Requirement  Vendor Data 
No. 
1  Name of the manufacturer       
2  Ref IS No.  IS: 1239(Part‐1) 2004   
3  Type(Light , Medium, Heavy)  Light   
4  Ends (Plain/ Screwed)  Plain   
5  Size  mm  40mm NB   
6  Thickness  mm  2.90mm   
7  Max & Min outside diameter  mm  48.4 (Max), 47.8 (Min)   
8  Length of pipe  mm   06 Mtrs. (±2%)   
9  Mass of tube  Kg/m  3.23   
10  Tolerance on thickness  %  (+) Not limited, (‐) 8%   
11  Tolerance on Mass  %  +10 %, ‐8%   
12  Galvanizing thickness  Gm/m2  360gm/m2 (Min.)   
13  Tensile strength  N/mm2  320 N/mm2 (Min.)   
14  Elongation percent  %  20% (Min.)   
15  Embossing details    Hot marking on every  Name/logo of 
metre Name/ logo of  manufacturer, 
manufacturer, IS No.,  PO 
Class, ISI monogram  No,ISI,Class of 
tube i.e L for 
light,Colour of 
Band (PO no 
provided in 
stencil) 
16  Color Coding    Yellow color band   
17  Make of steel    Tata/SAIL/Reputed   
make 
18  Chemical composition certificate    As per Table 1 of   
IS:1239 (Pt‐I)‐2004 
19  Max. permissible variation of chemical    As per Table 2 of   
composition  IS:1239 (Pt‐I)‐2004 
20  Leak proof test    5MPA for atleast 3   
sec. 
21  Tests       
21.1  Test of tensile strength    As per  IS:1239 (Pt‐I)‐  
2004 
21.2  Bend test    As per  IS:1239 (Pt‐I)‐  
2004 

Page 5 of 5 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
11. GTP FOR G.I. PIPE (20 MM / 32 MM)  : 
S. 
Technical particular  Unit  BSES Requirement  Vendor Data 
No. 
1  Name of the manufacturer       
2  Ref IS No.  IS: 1239(Part‐1) 2004   
3  Type(Light , Medium, Heavy)  Light   
4  Ends (Plain/ Screwed)  Plain   
5  Size  mm  20mm NB/ 32 mm NB   
6  Thickness  mm  2.30mm/2.60mm   
26.9 (Max), 26.4 (Min) for 20mm 
&42.5 (Max), 41.9 (Min) for 
7  Max & Min outside diameter  mm  32mm     
8  Length of pipe  mm  06 Mtrs. (±2%)   
9  Mass of tube  Kg/m  1.38 for 20 mm  & 2.54 for32 mm   
10  Tolerance on thickness  %  (+) Not limited, (‐) 8%   
11  Tolerance on Mass  %  +10 %, ‐8%   
12  Galvanizing thickness  Gm/m2 360gm/m2 (Min.)   
13  Tensile strength  N/mm2 320 N/mm2 (Min.)   
14  Elongation percent  %  12% (Min.)   
15  Embossing details    Hot marking on every metre  Name/logo of 
Name/ logo of manufacturer, IS  manufacturer, PO 
No., Class, ISI monogram  No,ISI,Class of 
tube i.e L for 
light,Colour of 
Band (PO no 
provided in stencil)
16  Color Coding    Yellow color band   
17  Make of steel    Tata/SAIL/ESSAR   
18  Chemical composition    As per Table 1 of IS:1239 (Pt‐I)‐  
certificate  2004 
19  Max. permissible variation of    As per Table 2 of IS:1239 (Pt‐I)‐  
chemical composition  2004 
20  Leak proof test    5MPA for atleast 3 sec.   
21  Tests       
21.1  Test of tensile strength    As per  IS:1239 (Pt‐I)‐2004   
21.2  Bend test    As per  IS:1239 (Pt‐I)‐2004   
 
 

Page 6 of 6 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
12. GTP FOR G.I. PIPE (100 MM) : 
S. 
Technical particular  Unit  BSES Requirement  Vendor Data 
No. 
1  Name of the manufacturer       
IS: 1239(Part‐1) 
2  Ref IS No.  2004   
3  Type(Light , Medium, Heavy)  Light   
4  Ends (Plain/ Screwed)  Plain   
5  Size  mm  100mm NB   
6  Thickness  mm  3.60 mm   
113.9 (Max), 113.0 
7  Max & Min outside diameter  mm  (Min)   
8  Length of pipe  mm  06 Mtrs. (±2%)   
9  Mass of tube  Kg/m  9.75   
10  Tolerance on thickness  (+) Not limited, (‐) 
%  8%   
11  Tolerance on Mass  %  +10 %, ‐8%   
12  Galvanizing thickness  Gm/m2  360gm/m2 (Min.)   
13  Tensile strength  N/mm2  320 N/mm2 (Min.)   
14  Elongation percent  %  20% (Min.)   
15  Embossing details    Hot marking on  Name/logo of 
every metre  manufacturer, PO 
Name/ logo of  No,ISI,Class of 
manufacturer, IS  tube i.e L for 
No., Class, ISI  light,Colour of 
monogram  Band (PO no 
provided in 
stencil) 
16  Color Coding    Yellow color band   
17  Make of steel    Tata/SAIL/Reputed   
make 
18  Chemical composition certificate    As per Table 1 of   
IS:1239 (Pt‐I)‐2004 
19  Max. permissible variation of chemical    As per Table 2 of   
composition  IS:1239 (Pt‐I)‐2004 
20  Leak proof test    5MPA for atleast 3   
sec. 
21  Tests       
21.1  Test of tensile strength    As per  IS:1239 (Pt‐  
I)‐2004 
21.2  Bend test    As per  IS:1239 (Pt‐  
I)‐2004 

Page 7 of 7 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
13.0 GTP FOR GI EARTHING PIPE DIA 40 MM X 2.50 MTR CLASS B: 

S. No  Parameter  Unit  Requirement  Vendor Data 


1  Name of Manufacturer          
2  Ref IS No     IS 1239 (Part‐1) 2004    
3  Type (Light, Medium, Heavy)*     Medium    
4  Size  mm  40mm NB dia    
5  Thickness   mm  3.2 MM    
Max & Min outside diameter  48.8 mm (max) & 47.9 
6  mm    
of tube  (min) 
2500 MM (+ 6 mm &  ‐ 
7  Length of Pipe   Mtr    
NOT ACCEPTABLE) 
8  Mass of Tube   Kg/m  3.56 Kg/m    
9  Tolerance on thickness      (+) Not limited, (‐) 8%    
10  Tolerance on Mass     (+/‐)10%    
11  Galvanising thickness  Microns 80 Microns (min)    
12  Tensile strength     320 N/mm2 (Mpa) (min)    
13  Elongation percent  %  20%    
Hot marking on every 
meter Name/logo of 
14  Embossing details     manufacturer, ISI    
monogram, Color of band 
(Blue Color) 
Chemical composition test 
Chemical composition  to be carried out on one 
15       
certificate  sample and sealed by BSES 
representative 
Max permissible variation of 
16     As per IS 10748    
chemical composition 
17  Tests       
Leak tightness test    
17.1     NA 
(Hydrostatic test)   
17.2  Test on finished tube     As per IS 1239 (Part‐1)   
17.3  Bend test     As per IS 1239 (Part‐1)    
18  General       
Supply of 6 Nos of 
M10*30mm elctrogalvanised 
18.1     Shall be provided    
Nuts+bolts+Plain & Spring 
Washer 
18.2  Drawing     Shall be submitted    
19  GI Strip Size  mm  50 X 6    
 

*Pipe may be perforated or non‐perforated, BRPL may ask as per requirement. Bidder has to    
provide the same. 
Page 8 of 8 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 

Fig. 1 G.I. EARTHING PIPE DIA 40 MM X 2.50 MTR CLASS B 

Page 9 of 9 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
13. INSPECTION TESTING CRITERIA: 
 

Page 10 of 10 
 
GN101‐03‐SP‐97‐00 
 
                                 TECHNICAL SPECIFICATION OF G.I. CONDUIT PIPES & EARTHING PIPE 
 
 
 
 

Note: ‐    

• GI Earthing pipe : Hot marking on every meter Name/logo of manufacturer, ISI monogram, 
Color of band (Blue Color)  
• GI conduit pipe : Hot marking on every meter Name/logo of manufacturer, ISI monogram, 
Color of band  (Yellow Color)  
 

Page 11 of 11 
 

You might also like