Product Data Sheet: Trihal Cast Resin Dry Type Transformer 1600 kVA 20 KV Eco-Design Dyn05 IP00
Product Data Sheet: Trihal Cast Resin Dry Type Transformer 1600 kVA 20 KV Eco-Design Dyn05 IP00
Product Data Sheet: Trihal Cast Resin Dry Type Transformer 1600 kVA 20 KV Eco-Design Dyn05 IP00
Main
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product range Trihal
Product or component type Dry type transformer
Network type AC
Directives 2015/2014/548/EC- ecodesign
Type of installation Indoor
Maximum altitude < 1000 m
Cooling mode AN (air natural)
Winding material Aluminium
Insulation material Cast resin (HV)
Pre-impregnated (LV)
Degree of protection IP00 no enclosure
Mounting mode Withdrawable
Fixed
Complementary
Phase 3 phases
Rated power 1600 kVA
Rated frequency 50 Hz
Rated primary voltage 20 kV
Secondary voltage ( at no-load) No load: 400 V
Insulation voltage to industrial 24 kV primary
frequency ( 50 Hz 1 mn) 1.1 kV secondary
Rated insulation level Primary circuit: 50 kV AC
Secondary circuit: 10 kV AC
Lighting impulse whistand voltage 125 kV for primary circuit
( BIL) , 1.2/50 µs
Vector group Dyn05
HV tappings (off circuit) +/- 2 x 2.5 %
Short circuit impedance 6 %
No-load losses 2200 W
Load losses at 75°C/120 °C 13000 W at 120 °C
Temperature rise of windings 100 K (winding)
Sep 1, 2021
1
Thermal class F
Sound power level 68 dB at 1 m
Height 2344 mm
Width 963 mm
Length 1970 mm
Total weight 5235 kg
Environment
Ambient air temperature for operation -25…40 °C for C2
Ambient air temperature for storage -50…40 °C C4
Environmental certification 0…95 % (E4)
Fire certificate F1
Standards IEC 60076-11:2018
Corrosion category C3M
Packing Units
Package 1 Weight 5235.000 kg
Package 1 Height 2344.000 mm
Package 1 width 963.000 mm
Package 1 Length 1970.000 mm
Offer Sustainability
EU RoHS Directive Not applicable, out of EU RoHS legal scope