This document provides calculations to determine the amount of NOVEC clean agent required for a fire suppression system protecting a data room measuring 20m x 5.25m x 4.3m. It calculates the net volume as 270 cubic meters. Using the NFPA 2001 standard, it determines the design concentration as 5.04% and accounts for a safety factor of 1.2, resulting in a required concentration of 5.04%. The calculation then determines the required amount of NOVEC agent is 195.6 kg or 97.8 kg in bottles. It also includes tables listing specifications for DOT and TPED transport containers, as well as manifolds with varying inlet sizes and configurations.
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
155 views

Novec Calculator

This document provides calculations to determine the amount of NOVEC clean agent required for a fire suppression system protecting a data room measuring 20m x 5.25m x 4.3m. It calculates the net volume as 270 cubic meters. Using the NFPA 2001 standard, it determines the design concentration as 5.04% and accounts for a safety factor of 1.2, resulting in a required concentration of 5.04%. The calculation then determines the required amount of NOVEC agent is 195.6 kg or 97.8 kg in bottles. It also includes tables listing specifications for DOT and TPED transport containers, as well as manifolds with varying inlet sizes and configurations.
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 10

Design calculation sheet

Project no: D0271 Date: 44482 Sheet no.: of


1 1 Computed by: R.G.H
Subject: FAURECIA Checked by: M.A
IT DATA ROOM Approved by:

Basis : NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems,

The amount of NOVEC agent required to achieve the design concentration shall be calculated from
the following Formula
Lenght = 20
Wide = 5.25
Hight = 4.3

Hazard Class = Class C


W = Weight of NOVEC (kg)
V = Net Volume of the Hazard = 270 (m3)
C = NOVEC Design Concentration = 4.2 %
sf = Safety factor = 1.2
Resulting Concentration = 5.04 %
t = Minimum anticipated temp. = 25 º C
of the protected volume
S = Specific Volume of superheated = 0.07325 (m3/kg)
agent vapor at 1 atmosphere and
the temperature t

W = 270 x [ 5.04 ]
0.07325 100 - 5.04

W = 195.6347347 kg of NOVEC agent 106 Litres 97.81736733 Kg/Btls 0.922805352


2 Btls
Class A Fires : Fire in ordinary combustible materials, such as wood, cloth, paper, rubber, and many plastics. 80
Class B Fires : Fire in flammable liquids, oils, greases, tars, oil-base paints, lacquers, and flammable gases.
Class C Fires : Fire that involves energized electrical equipment where the electrical resistivity of the
the extinguishing media is of importance. 19.56347347

3-4 Design Concentration Requirements.


3-4.2.1 The flame extinguishing concentration for Class B fuels shall be determined by the cup burner method
described in Appendix B.
3-4.2.2 The flame extinguishing concentration for Class A fuels shall be determined by test as part of a
listing program. As a minimum, the listing program shall conform to UL 2127, Standard for Inert Gas
Clean Agent Extinguishing System Units, or UL 2166, Standard for Halocarbon Clean Agent Extinguishing
System Units, or equivalent.
3-4.2.3 The minimum design concentration for a Class B fuel hazard or an only manually actuated system
shall be the extinguishing concentration, as determined in 3-4.2.1, times a safety factor of 1.3.
3-4.2.4 The minimum design concentration for a Class A surface fire hazard shall be the extinguishing
concentration as determined in 3-4.2.2, times a safety factor of 1.2.
3-4.2.5 Minimum design concentration for Class C hazards shall be at least that for Class A surface fire.

of
Design calculation sheet
Project no: D0271 Date: 37867 Sheet no.: 1 of1 Computed by:R.G.H
Subject: Dubai Royal Airwing Checked by: M.A
FM200 Total Flooding Quantity Approved by:

Basis : NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 2000 Edition

Temperature Specific Vapor Temperature Specific Vapor


t Volume t Volume
ºF (ft3/lb) ºC (m3/kg)
10 1.9264 -10 0.06366
20 1.9736 -5 0.06503
30 2.021 0 0.0664
40 2.0678 5 0.06777
50 2.1146 10 0.06914
60 2.1612 15 0.07051
70 2.2075 20 0.07188
80 2.2538 25 0.07325
90 2.2994 30 0.1425
100 2.3452 35 0.145
110 2.3912 40 0.1476
120 2.4366 45 0.1502
130 2.482 50 0.1527
140 2.5272 55 0.1553
150 2.5727 60 0.1578
160 2.6171 65 0.1604
170 2.6624 70 0.1629
180 2.7071 75 0.1654
190 2.7518 80 0.1679
200 2.7954 85 0.1704
from Table A-3-5.1 (k) 90 0.173
from Table A-3-5.1 (l)

Design
Conctentration
% per Volume
4.2
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
6
Table 4: DOT Container details.

Part No. Nominal Volu Minimum FillsMaximum FillsValve Size

kg mm (in)
4.5 303.207.010 (4.5 litre) 2.3 5 25
8 303.207.001 (8 litre) 4 9.5 25
16 303.207.002 (16 litre) 8 19 25
32 303.207.003 (32 litre) 16 38 25
52 303.207.004 (52 litre) 26 62 50
106 303.207.005 (106 litre) 53 127 50
147 303.207.006 (147 litre) 73.5 176 50
180 303.207.007 (180 litre) 90 208 50
343 303.207.008 (343 litre) 171.5 386 80

Table 5: TPED Container details.

Part No. (Nominal VoluMinimum FillsMaximum FillsValve Size


kg mm (in)
303.207.020 (8 litre) 4 to 9.5 9.5 25
303.207.021 (16 litre) 8 to 19 19 25
303.207.022 (32 litre) 16 to 38 38 25
303.207.023 (52 litre) 26 to 62 62 50
303.207.024 (106 litre) 53 to 127 127 50
303.207.025 (147 litre) 73.5 to 176 176 50

Table 6: Manifolds
Part No. No.of Inlets Manifold Pipe Inletto EndCa Inletto Inlet
307209022 2 65mm (2.5”) 150 (6”) 350 (14”)
307209023 3 65mm (2.5”) 150 (6”) 350 (14”)
307209024 4 65mm (2.5”) 150 (6”) 350 (14”)
307209001 2 65mm (2.5”) 150 (6”) 350 (14”)
307209002 3 65mm (2.5”) 150 (6”) 350 (14”)
307209003 4 65mm (2.5”) 150 (6”) 350 (14”)
307209025 2 80mm (3”) 150 (6”) 508 (20”)
307209026 3 80mm (3”) 150 (6”) 508 (20”)
307209027 4 80mm (3”) 150 (6”) 508 (20”)
307209028 5 80mm (3”) 150 (6”) 508 (20”)
307209029 6 80mm (3”) 150 (6”) 508 (20”)
307209004 2 80mm (3”) 150 (6”) 508 (20”)
307209005 3 80mm (3”) 150 (6”) 508 (20”)
307209006 4 80mm (3”) 150 (6”) 508 (20”)
307209007 5 80mm (3”) 150 (6”) 508 (20”)
307209008 6 80mm (3”) 150 (6”) 508 (20”)
307209030 2 100mm (4”) 150 (6”) 508 (20”)
307209031 3 100mm (4”) 150 (6”) 508 (20”)
307209032 4 100mm (4”) 150 (6”) 508 (20”)
307209033 5 100mm (4”) 150 (6”) 508 (20”)
307209034 6 100mm (4”) 150 (6”) 508 (20”)
307209009 2 100mm (4”) 150 (6”) 508 (20”)
307209010 3 100mm (4”) 150 (6”) 508 (20”)
307209011 4 100mm (4”) 150 (6”) 508 (20”)
307209012 5 100mm (4”) 150 (6”) 508 (20”)
307209013 6 100mm (4”) 150 (6”) 508 (20”)
307209014 3 150mm (6”) 150 (6”) 508 (20”)
307209015 4 150mm (6”) 150 (6”) 508 (20”)
307209016 5 150mm (6”) 150 (6”) 508 (20”)
307209017 6 150mm (6”) 150 (6”) 508 (20”)
307209018 7 150mm (6”) 150 (6”) 508 (20”)
307209019 8 150mm (6”) 150 (6”) 508 (20”)
307209020 9 150mm (6”) 150 (6”) 508 (20”)
307209021 10 150mm (6”) 150 (6”) 508 (20”)
307209038 2 100mm (4”) 150 (6”) 711 (28”)
307209039 3 100mm (4”) 150 (6”) 711 (28”)
307209040 4 100mm (4”) 150 (6”) 711 (28”)
307209035 2 100mm (4”) 150 (6”) 711 (28”)
307209036 3 100mm (4”) 150 (6”) 711 (28”)
307209037 4 100mm (4”) 150 (6”) 711 (28”)
307209041 2 150mm (6”) 150 (6”) 711 (28”)
307209042 3 150mm (6”) 150 (6”) 711 (28”)
307209043 4 150mm (6”) 150 (6”) 711 (28”)
307209044 5 150mm (6”) 150 (6”) 711 (28”)
307209045 6 150mm (6”) 150 (6”) 711 (28”)
307209046 7 150mm (6”) 150 (6”) 711 (28”)

307209047 8 150mm (6”) 150 (6”) 711 (28”)


307209048 9 150mm (6”) 150 (6”) 711 (28”)
0.188110322

Height from fl Diameter Nominal Tare 195.6347347

(nominal) mmmm Weight kg 39.12694693


280 178 7.7 208
304 254 14.8
502 254 18.4
833 254 26.1 5
596 406 49.1
1021 406 71.8 19.56347347
1354 406 89.9
1634 406 105.8 3.912694693
1466 610 207

Height from fl Diameter Nominal Tare


mm mm Weight kg
304 254 17.4
502 254 23.4
833 254 27.5
596 406 68.7
1021 406 88.8
1354 406 108.8

Overall Length
Inletto End C Container Sizemm EndThread Connection
150 (6”) 4.5 L to 32 L 650 (25.6”) BSPT
150 (6”) 4.5 L to 32 L 1000 (39.4”) BSPT
150 (6”) 4.5 L to 32 L 1350 (53.1”) BSPT
150 (6”) 4.5 L to 32 L 650 (25.6”) NPT
150 (6”) 4.5 L to 32 L 1000 (39.4”) NPT
150 (6”) 4.5 L to 32 L 1350 (53.1”) NPT
150 (6”) 52 L to 180 L 808 (31.8”) BSPT
150 (6”) 52 L to 180 L 1316 (51.8”) BSPT
150 (6”) 52 L to 180 L 1824 (71.8”) BSPT
150 (6”) 52 L to 180 L 2332 (91.8”) BSPT
150 (6”) 52 L to 180 L 2840 (111.8”) BSPT
150 (6”) 52 L to 180 L 808 (31.8”) NPT
150 (6”) 52 L to 180 L 1316 (51.8”) NPT
150 (6”) 52 L to 180 L 1824 (71.8”) NPT
150 (6”) 52 L to 180 L 2332 (91.8”) NPT
150 (6”) 52 L to 180 L 2840 (111.8”) NPT
150 (6”) 52 L to 180 L 808 (31.8”) BSPT
150 (6”) 52 L to 180 L 1316 (51.8”) BSPT
150 (6”) 52 L to 180 L 1824 (71.8”) BSPT
150 (6”) 52 L to 180 L 2332 (91.8”) BSPT
150 (6”) 52 L to 180 L 2840 (111.8”) BSPT
150 (6”) 52 L to 180 L 808 (31.8”) NPT
150 (6”) 52 L to 180 L 1316 (51.8”) NPT
150 (6”) 52 L to 180 L 1824 (71.8”) NPT
150 (6”) 52 L to 180 L 2332 (91.8”) NPT
150 (6”) 52 L to 180 L 2840 (111.8”) NPT
200 (8”) 52 L to 180 L 1416 (55.7”) Flange
200 (8”) 52 L to 180 L 1924 (75.7”) Flange
200 (8”) 52 L to 180 L 2432 (95.7”) Flange
200 (8”) 52 L to 180 L 2940 (115.7”) Flange
200 (8”) 52 L to 180 L 3448 (135.7”) Flange
200 (8”) 52 L to 180 L 3956 (155.7”) Flange
200 (8”) 52 L to 180 L 4464 (175.7”) Flange
200 (8”) 52 L to 180 L 4972 (195.7”) Flange
150 (6”) 343 L 1011 (40”) BSPT
150 (6”) 343 L 1722 (68”) BSPT
150 (6”) 343 L 2433 (96”) BSPT
150 (6”) 343 L 1011 (40”) NPT
150 (6”) 343 L 1722 (68”) NPT
150 (6”) 343 L 2433 (96”) NPT
200 (8”) 343 L 1111 (43.7”) Flange
200 (8”) 343 L 1822 (71.7”) Flange
200 (8”) 343 L 2533 (99.7”) Flange
200 (8”) 343 L 3244 (127.7”) Flange
200 (8”) 343 L 3955 (155.7”) Flange
200 (8”) 343 L 4666 (183.7”) Flange

200 (8”) 343 L 5377 (211.7”) Flange


200 (8”) 343 L 6088 (239.7”) Flange
Table 14 : Equivalent Length for Pipe Fittings
Diameter 90° Elbow 45° Elbow Thru Tee Side Tee Union
m (in) m m m m m
15 (1/2) 0.52 0.24 0.3 1.04 0.12
20 (3/4) 0.67 0.3 0.42 1.37 0.15
25 -1 0.85 0.4 0.55 1.74 0.18
32 (1¼) 1.13 0.52 0.7 2.29 0.24
40 (1½) 1.31 0.61 0.82 2.65 0.27
50 -2 1.68 0.79 1.06 3.41 0.37
65 (2½) 2.01 0.94 1.25 4.08 0.43
80 -3 2.5 1.16 1.55 5.06 0.55
100 -4 3.26 1.52 2.01 6.64 0.73
125 -5 4.08 1.92 2.56 8.35 0.91
150 -6 4.94 2.32 3.08 10 1.07

Table 15 : Equivalent Length for other system components


Hardware Set Size Equivalent length

25 mm (1 ”) 6.096
50 mm (2 ”) 10.668
Valve 80 mm (3 ”) 25.91
25 mm (1 ”) 3.14
50 mm (2 ”) 5.36
Flex Hose 80 mm (3 ”) 1.55
25 mm (1 ”) 3.54
50 mm (2 ”) 12.02
Flex Hose and 80 mm (3 ”) 15.85

25 mm (1 ”) 0.18
50 mm (2 ”) 0.37
80 mm (3 ”) 0.55
80 mm Flared(3 ”) 0.55
Valve Outlet 80 mm Flared(3 ”) 0.55

Pipe Size
Altitude Correction Factor Minimum flowMaximum flow
ft (km) kg/s kg/s mm
-3000 -0.92 1.11 0.454 1.361 15
-2000 -0.61 1.07 0.907 2.495 20
-1000 -0.3 1.04 1.588 3.855 25
0 0 1.00 2.722 5.67 32
1000 0.3 0.96 4.082 9.072 40
2000 0.61 0.93 6.35 13.61 50
3000 0.91 0.89 9.072 24.95 65
4000 1.22 0.86 13.61 44.92 80
5000 1.52 0.82 24.95 56.7 100
6000 1.83 0.78 40.82 90.72 125
7000 2.13 0.75 54.43 136.1 150
8000 2.45 0.72
9000 2.74 0.69
10000 3.05 0.66
Table 15 : Equivalent Length for other system components
Hardware Set Size Equivalent length
Valve 25 mm (1 ”) 6.096 m
50 mm (2 ”) 10.668 m
80 mm (3 ”) 25.91 m
Flex Hose 25 mm (1 ”) 3.14 m
50 mm (2 ”) 5.36 m
80 mm (3 ”) 1.55 m
Flex Hose and 25 mm (1 ”) 3.54 m
50 mm (2 ”) 12.02 m
80 mm (3 ”) 15.85 m
Valve Outlet 25 mm (1 ”) 0.18 m
50 mm (2 ”) 0.37 m
80 mm (3 ”) Flared to NPT 0.55 m
80 mm (3 ”) Flared to Groov 0.55 m
80 mm (3 ”) Flared to BSP 0.55 m