OPC Mix Design (Sample)

The document outlines the design specifications for a normal RCC concrete mix with mild exposure conditions and a target grade of 20 MPa. It specifies a water-cement ratio of 0.36, maximum aggregate size of 20mm, and zone IV aggregates. A trial mix is then designed meeting the specifications with 392 kg/m3 cement, 141 kg/m3 water, 1336 kg/m3 coarse aggregate, and 586 kg/m3 fine aggregate. Site corrections are then made to the trial mix.

Uploaded by

satish yadav
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
316 views20 pages

OPC Mix Design (Sample)

The document outlines the design specifications for a normal RCC concrete mix with mild exposure conditions and a target grade of 20 MPa. It specifies a water-cement ratio of 0.36, maximum aggregate size of 20mm, and zone IV aggregates. A trial mix is then designed meeting the specifications with 392 kg/m3 cement, 141 kg/m3 water, 1336 kg/m3 coarse aggregate, and 586 kg/m3 fine aggregate. Site corrections are then made to the trial mix.

Uploaded by

satish yadav
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 20

STEP 1 - DESIGN SPECIFICATIONS

TYPE OF DESIGN Normal


TYPE OF CONCRETE = RCC
EXPOSURE CONDITION = Mild
GRADE OF CONCRETE TO BE DESIGNED 20
MINIMUM REQUIRED CONCRETE GRADE 20
FINAL DESIGN GRADE 20
MAXIMUM CEMENT CONTENT = 450
MINIMUM CEMENT CONTENT = 300
MAXIMUM W/C RATIO = 0.55
TYPE OF CEMENT USED = OPC 43 /PPC
DO YOU WISH TO ENTER W/C RATIO MANNUALLY ?? YES
ENTER THE MANNUAL VALUE = 0.36
WATER CEMENT RATIO AS PER DESIGNER = 0.36
MAXIMUM NOMINAL SIZE OF AGGREGATE = 20
ZONE OF AGGREGATE = IV
MAXIMUM WATER CONTENT = 186
EXPECTED WORKABILITY = 75
METHOD OF TRANSPORTING AND PLACING = Non-pumpable
Subangular
TYPE OF AGGREGATE = Aggregate
PLASTICIZER NO
SUPERPLASTICIZER YES
PLASTICIZER/SUPERPLASTICIZER PERCENTAGE AS A WEIGHT OF
CEMENT 1
CONGESTED REINFORCEMENT NO

STEP 2 - DETERMINATION OF INGREDIENT PRO

SPECIFIC GRAVITY
CEMENT 2.88
SPECIFIC GRAVITY WATER ABSORBTION(%)
COARSE AGGREGATE 2.74 0.5
SPECIFIC GRAVITY WATER ABSORBTION(%)
FINE AGGREGATE 2.65 1
SPECIFIC GRAVITY EXPT. WATER REDUCTION(%)
ADMIXTURE (IF ANY) 1.145 23
SPECIFIC GRAVITY
WATER 1

STEP 4 - SELECTION OF WATER


STEP 3 :TARGET MEAN STRENGTH MAXIMUM PERMISSIBLE WATER CEMENT R
K= 1.65 σ= 4 X WATER CEMENT RATIO FROM CHART
f'ck = 26.6 Mpa 5.5 FINAL WATER CEMENT RATIO
f'ck = 25.5 Mpa
STEP 5 - AIR CONTENT EST
FINAL TARGET STRENGTH 26.6 % Air content

STEP 6 - SELECTION OF WATER CONTENT


BASIC WATER CONTENT =
WATER CONTENT AFTER AGGREGATE SHAPE CORRECTION=
WATER CONTENT AFTER EXCESS SLUMP CORRECTION=
WATER CONTENT AFTER ADMIXURE CORRECTION=

STEP 7 - CALCULATION OF CEMENTITIOUS CONTENT


FINALIZED WATER CEMENT RATIO = 0.36
WATER CONTENT = 141
CALCULATED CEMENT CONTENT = 391.666666666667
MAXIMUM CEMENT CONTENT= 450
FINAL CEMENT CONTENT = 392

STEP 8 - QUANTITY OF ADMIXTURE


PERCENTAGE BY MASS OF ADMIXTURE AS A MASS
OF CEMENT = 1
QUANTITY OF CHEMICAL ADMIXTURE = 3.92

STEP 9 - FINDING OUT VOLUME PROPORTIONS FOR COARSE AGGREGATE


AND FINE AGGREGATE
ZONE OF AGGREGATE = IV
BASIC PROPORTION OF COARSE AGGREGATE = 0.66
CHANGE IN W/C RATIO= -0.14
CHANGE IN WC RATIO FACTOR= -2.8
PROPORTION AFTER APPLYNG W/C CORRECTION= 0.688
PROPORTION AFTER APPLYING REINFORCEMENT
CONGESTION OR PUMPABLE CORRECTION 0.688

STEP 10 - MIX CALCULATIONS


VOLUME OF CONCRETE = 1
VOLUME OF AIR = 0.01
VOLUME OF CEMENT = 0.137
VOLUME OF WATER = 0.141
VOLUME OF ADMIXTURE = 0.0035
VOLUME OF TOTAL AGGREGATE = 0.7085
MASS OF C.A = 1336
MASS OF F.A = 586

TRIAL 1 - MIX PROPORTIONS


CEMENT CONTENT = 392
WATER CONTENT = 141
COARSE AGGREGATE = 1336
FINE AGGREGATE = 586
CHEMICAL ADMIXTURE = 3.92

C W CA FA
LAB MIX DESIGN 1 0.36 3.409 1.495

STEP 10 - SITE CORRECTIONS


FINE AGGREGATE 580
COARSE AGGREGATE 1330
EXTRA WATER TO BE # POSITIVE INDICATES ADD
ADDED/REMOVED 12 NEGATIVE INDICATES R
FINAL WATER CONTENT 153

FINAL MIX PROPORTIONS


CEMENT CONTENT = 392
WATER CONTENT = 153
COARSE AGGREGATE = 1330
FINE AGGREGATE = 580
CHEMICAL ADMIXTURE = 3.92

C W CA FA
IN-SITU MIX DESIGN 1 0.36 3.393 1.48
TIONS

KG/CU.M
KG/CU.M

PLEASE ENTER THE VALUE

KG/CU.M

OK

OK

MINATION OF INGREDIENT PROPERTIES

R ABSORBTION(%) FREE SURFACE MOISTURE(%)


0.5 0
R ABSORBTION(%) FREE SURFACE MOISTURE(%)
1 0
ATER REDUCTION(%)
23
TEP 4 - SELECTION OF WATER CEMENT RATIO
RMISSIBLE WATER CEMENT RATIO = 0.55
CEMENT RATIO FROM CHART 0.36
AL WATER CEMENT RATIO 0.36

STEP 5 - AIR CONTENT ESTIMATION


% Air content 1

WATER CONTENT
186 KG/CU.M
176 KG/CU.M
182 KG/CU.M
141 KG/CU.M

CONTENT

KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M

MIXTURE

1 %
3.92 KG/CU.M

COARSE AGGREGATE

IV
0.66
-0.14
-2.8
0.688
0.688

CU.M
CU.M
CU.M
CU.M
CU.M
CU.M
KG/CU.M
KG/CU.M

KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M

AD
0.01

RECTIONS

# POSITIVE INDICATES ADDITION AND


NEGATIVE INDICATES REMOVAL

KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M

AD
0.01
Curve from IS 10262:2019
80

OPC 33
70 OPC 43/ PPC
28 DAY COMPRESSIVE STRENGTH OF CONCRETE, (MPa)

OPC 53
60

50

40

30

20

10

0
0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65

Water -Cement Ratio


Normal Concrete

10
PCC Mild 15
RCC Moderate 20

10 208
20 186
III 165
IV

Pumpable YES OPC 33


Non-pumpable NO OPC 43 /PPC
OPC 53
Angular Aggregate PPC 43
Subangular Aggregate

FREE MOISTURE
CA -0.5
FA -1

EXCESS SLUMP = 25
EXCESS SLUMP FACTOR= 1
Curve 1 Curve 2 Curve 3
0.25 60 67 75
0.3 50 57 64
0.35 42 48 55
0.4 35.5 41 48
0.45 30 35 42
0.5 25 30 37
0.55 20.5 25.5 32
0.6 17 22 28
0.65 14 19 25

25 MM
1
STEP 1 - DESIGN SPECIFICATIONS

TYPE OF DESIGN Bridges

TYPE OF STRUCTURE= Imp. Bridges and PSC Bridges

TYPE OF CONCRETE = PSC


EXPOSURE CONDITION = Severe
GRADE OF CONCRETE TO BE DESIGNED 20
MINIMUM REQUIRED CONCRETE GRADE 40
FINAL DESIGN GRADE 40
MAXIMUM CEMENTITIOUS CONTENT = 500
MINIMUM CEMENT CONTENT = 430
MAXIMUM W/C RATIO = 0.4
TYPE OF CEMENT USED = OPC 43
DO YOU WISH TO ENTER W/C RATIO MANNUALLY ?? NO
ENTER THE MANNUAL VALUE = 0.36
WATER CEMENT RATIO AS PER DESIGNER = 0.33
MAXIMUM NOMINAL SIZE OF AGGREGATE = 10
ZONE OF AGGREGATE = IV
MAXIMUM WATER CONTENT = 208
EXPECTED WORKABILITY = 75
METHOD OF TRANSPORTING AND PLACING = Non-pumpable

TYPE OF AGGREGATE = Angular Aggregate


PLASTICIZER NO
SUPERPLASTICIZER YES
PLASTICIZER/SUPERPLASTICIZER PERCENTAGE AS A WEIGHT OF
CEMENT 1
CONGESTED REINFORCEMENT NO

STEP 2 - DETERMINATION OF INGREDIENT PRO

SPECIFIC GRAVITY
CEMENT 2.88
SPECIFIC GRAVITY WATER ABSORBTION(%)
COARSE AGGREGATE 2.74 0.5
SPECIFIC GRAVITY WATER ABSORBTION(%)
FINE AGGREGATE
FINE AGGREGATE 2.65 1
SPECIFIC GRAVITY EXPT. WATER REDUCTION(%)
ADMIXTURE (IF ANY) 1.145 23
SPECIFIC GRAVITY
WATER 1

STEP 4 - SELECTION
STEP 3 :TARGET MEAN STRENGTH MAXIMUM PERMISSIBLE WATER
K= 1.65 σ= 6.6 X WATER CEMENT RATIO FR
f'ck = 50.89 Mpa 5.5 FINAL WATER CEMENT
f'ck = 45.5 Mpa
STEP 5 - AIR CO
FINAL TARGET STRENGTH 50.89 % Air content

STEP 6 - SELECTION OF WATER CONTENT


BASIC WATER CONTENT =
WATER CONTENT AFTER AGGREGATE SHAPE CORRECTION=
WATER CONTENT AFTER EXCESS SLUMP CORRECTION=
WATER CONTENT AFTER ADMIXURE CORRECTION=

STEP 7 - CALCULATION OF CEMENTITIOUS CONTENT


FINALIZED WATER CEMENT RATIO = 0.33
WATER CONTENT = 213
CALCULATED CEMENT CONTENT = 645.454545454545
MAXIMUM CEMENT CONTENT= 500
FINAL CEMENT CONTENT = 500

STEP 8 - QUANTITY OF ADMIXTURE


PERCENTAGE BY MASS OF ADMIXTURE AS A MASS
OF CEMENT = 1
QUANTITY OF CHEMICAL ADMIXTURE = 5

STEP 9 - FINDING OUT VOLUME PROPORTIONS FOR COARSE AGGREGATE


AND FINE AGGREGATE
ZONE OF AGGREGATE = IV
BASIC PROPORTION OF COARSE AGGREGATE = 0.44
CHANGE IN W/C RATIO= -0.17
CHANGE IN WC RATIO FACTOR= -3.4
PROPORTION AFTER APPLYNG W/C CORRECTION= 0.474
PROPORTION AFTER APPLYING REINFORCEMENT
CONGESTION OR PUMPABLE CORRECTION 0.474

STEP 10 - MIX CALCULATIONS


VOLUME OF CONCRETE = 1
VOLUME OF AIR = 0.015
VOLUME OF CEMENT = 0.174
VOLUME OF WATER = 0.213
VOLUME OF ADMIXTURE = 0.0044
VOLUME OF TOTAL AGGREGATE = 0.5936
MASS OF C.A = 771
MASS OF F.A = 828

TRIAL 1 - MIX PROPORTIONS


CEMENT CONTENT = 500
WATER CONTENT = 213
COARSE AGGREGATE = 771
FINE AGGREGATE = 828
CHEMICAL ADMIXTURE = 5

C W CA FA
LAB MIX DESIGN 1 0.43 1.542 1.656

STEP 11 - SITE CORRECTIONS


FINE AGGREGATE 820
COARSE AGGREGATE 768
EXTRA WATER TO BE # POSITIVE INDICATES ADDITION AND
ADDED/REMOVED 11 NEGATIVE INDICATES REMOVAL
FINAL WATER CONTENT 224

FINAL MIX PROPORTIONS


CEMENT CONTENT = 500
WATER CONTENT = 224
COARSE AGGREGATE = 768
FINE AGGREGATE = 820
CHEMICAL ADMIXTURE = 5
C W CA FA
IN-SITU MIX DESIGN 1 0.43 1.536 1.64
TIONS

Bridges 80

dges and PSC Bridges


70

PSC OK

28 DAY COMPRESSIVE STRENGTH OF CONCRETE, (MPa)


Severe
60
20
40
40 50
500 KG/CU.M
430 KG/CU.M
0.4 40
OPC 43
NO
0.36 NO NEED TO INPUT 30
0.33
10
IV 20
208 KG/CU.M
75
10
on-pumpable

gular Aggregate
0
NO 0.25 0.3
YES OK

1 OK
NO

MINATION OF INGREDIENT PROPERTIES

R ABSORBTION(%) FREE SURFACE MOISTURE(%)


0.5 0
R ABSORBTION(%) FREE SURFACE MOISTURE(%)
1 0
ATER REDUCTION(%)
23

STEP 4 - SELECTION OF WATER CEMENT RATIO


AXIMUM PERMISSIBLE WATER CEMENT RATIO = 0.4
WATER CEMENT RATIO FROM CHART 0.33
FINAL WATER CEMENT RATIO 0.33

STEP 5 - AIR CONTENT ESTIMATION


% Air content 1.5

WATER CONTENT
208 KG/CU.M
208 KG/CU.M
215 KG/CU.M
213 KG/CU.M

CONTENT

KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M

MIXTURE

1 %
5 KG/CU.M

COARSE AGGREGATE
IV
0.44
-0.17
-3.4
0.474

0.474

CU.M
CU.M
CU.M
CU.M
CU.M
CU.M
KG/CU.M
KG/CU.M

KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M

AD
0.01

IVE INDICATES ADDITION AND


ATIVE INDICATES REMOVAL

KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M
KG/CU.M
AD
0.01
Curve from IS 10262:2019
80

OPC 33
70 OPC 43/ PPC
28 DAY COMPRESSIVE STRENGTH OF CONCRETE, (MPa)

OPC 53
60

50

40

30

20

10

0
0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6 0.65

Water -Cement Ratio


Railway Bridges

10
Imp. Bridg PCC Moderate 15
Non-PSC BrRCC Severe 20
PSC 25
30
35
40
45
50
55
60
10 208
20 186
III 165
IV

Pumpable YES OPC 33


Non-pumpable NO OPC 43
Angular Aggregate OPC 53
Subangular Aggregate PPC 43

FREE MOISTURE
CA -0.5
FA -1

EXCESS SLUMP = 25
EXCESS SLUMP FACTOR= 1
25 MM
1