Type Test Certificate: 18 November, 2016 Daniel Kassner, Compliance Department Date

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Type Test Certificate

SEL-2505

This document contains references to the test procedures followed by SEL to


certify the product(s) specified above to national and international standards.

18 November, 2016
Daniel Kassner, Compliance Date
Department

Schweitzer Engineering Laboratories, Inc.


2350 NE Hopkins Court. Pullman, WA 99163 – USA
Phone: +1.509.332.1890; Fax: +1.509.332.7990
www.selinc.com
SEL-2505
Type Test Certificate

Electromagnetic Compatibility (EMC); Emissions


Radiated Emissions EN 60255-25:2000
EN 55011:1998 + A1:1999 + A2:2002
FCC 47 CFR Part 15.109(g) Class A
CISPR 22:1997
ANSI C63.4:2003
Conducted Emissions EN 60255-25:2000
EN 55011:1998 + A1:1999 + A2:2002
Class A
FCC 47 CFR Part 15.107
ANSI C63.4:2003

Electromagnetic Compatibility (EMC); Immunity


Radiated Immunity EN 60255-22-3:2008 10 V/m;
EN 61000-4-3:2006 + A1:2008 80 MHz – 1 GHz; 1.4 GHz – 2.7 GHz: Swept;
80, 160, 380, 450, 900, 1850 & 2150 MHz: Spot
(>15 V/m_w/80% AM 1 kHz sine wave)
Conducted Immunity EN 60255-22-6:2001 10 VRMS; 150 kHz – 80 MHz: Swept Frequency;
EN 61000-4-6:2003 + A1:2004 + A2:2006 27 MHz & 68 MHz: Spot Frequency
(w/80% AM 1 kHz sine wave)
Electrostatic Discharge Immunity EN 60255-22-2:2008 Contact: ± 2; 4; 6; & 8 kV
EN 61000-4-2:2009 Air: ± 2; 4; 8; & 15 kV
IEEE C37.90.3 – 2001
Fast Transient/Burst Immunity EN 60255-22-4:2008 Class A: Power Input; I/O: ± 4.0 kV; 5 kHz
EN 61000-4-4:2004 + Corr_1:2007 + Communication Ports: ± 2.0 kV; 5 kHz
Corr_2:2007 + A1:2010
Slow Damped Oscillatory Wave EN 60255-22-1:2008 Common Mode:
Power Input; CT; PT & I/O: ± 2.5 kV
Communication Ports: ± 1.0 kV
Differential Mode:
Power Input; PT & I/O: ± 1.0 kV
IEEE Surge Withstand Capability IEEE C37.90.1 – 2002 Damped Oscillatory (1 MHz):
Power Input; PT & I/O: ± 2.5 kV (CM & DM)
Comm Ports & CT: ± 2.5 kV (CM Only)
Fast Transient (2.5 kHz):
Power Input; PT & I/O: ± 4.0 kV (CM & DM)
Comm Ports & CT: ± 4.0 kV (CM Only)
Surge Immunity EN 60255-22-5:2011 ± 0.5; 1.0 kV; (Line – Line)
EN 61000-4-5:2006 ± 0.5; 1.0; 2.0 kV; (Line – Earth)
± 0.5; 1.0 kV; (Line – Earth)
Power Supply Immunity EN 61000-4-11:2004 A.C Dips & Interruptions
EN 61000-4-29:2000 D.C. Dips & Interruptions
EN 61000-4-17:1999 + A1:2004 + A2:2009 15% Ripple on D.C. Power Input
EN 60255-26:2013; Clause 7.2.13 Gradual Shutdown/Start-up
EN 60255-27:2014; Clause 5.1.3 Accessible & Non-accessible Capacitor Discharge
EN 60255-27:2014; Clause 10.6.6 Slow Ramp Down/Up & Reverse Polarity

Page 2 of 3
SEL-2505
Type Test Certificate

Environmental
Cold EN 60068-2-1:1993 + A1:1993 + A2:1994 Cold; Profile Ad; -40°C ≥ 16 Hrs
Operational
Dry Heat EN 60068-2-2:1993 + A1:1993 + A2:1994 Dry Heat; Profile Bd; +85°C ≥ 16 Hrs
Operational
Damp Heat; Cyclic EN 60068-2-30:2005 Damp Heat; Profile Db; +25°C to +55°C;
Relative Humidity ≥ 93%; 6 Cycles
Vibration EN 60255-21-1:1995 Class 1 – Vibration Endurance
Class 2 – Vibration Response
Shock & Bump EN 60255-21-3:1995 Class 1 – Shock Withstand
Class 2 – Shock Response
Class 1 – Bump
Seismic EN 60255-21-3:1995 Class 2 – Quake Response

Safety
Insulation Coordination EN 60255-5:2000 Hi-Pot: 3.1 kVdc – Power Supply;
IEEE C37.90 – 2005 2.5 kVac –I/O, CT & PT
2.2 kVdc – Communication Ports (RJ-45)
Impulse: 0.5 J; 5 kV; 1.2/50 uS