Fundamentals in FF Design
Fundamentals in FF Design
Fundamentals in FF Design
SESSION 1 - BASICS
DESIGN OF AUTOMATIC SPRINKLER SYSTEM
SESSION 1 - BASICS
OUTLINE OF SESSION 1
PART 1 – INTRODUCTION
- ELEMENTS OF FIRE
- EXTINGUISHMENT MECHANISMS
PUMP SELECTION/SIZING
CONCEPTS & BEHAVIOR OF FIRE
WHAT IS FIRE?
CONDUCTION
CONVECTION
RADIATION
EXAMPLES:
SMOTHERING – OXYGEN
DEPRIVATION
EXAMPLES:
FUEL REMOVAL
EXAMPLES:
- FOREST FIRES CAN BE EXTINGUISHED
BY CLEARING AN AREA OF TRESS
AROUND THE PERIMETER OF THE FIRE;
EXAMPLE :
SPRINKLERS
PIPING AND TUBING
FITTINGS
HANGERS
VALVES
SOURCE AND SUPPLY (FIRE PUMP, OTHER
AVAILABLE WATER MAINS CAPABLE OF
PROVIDING THE REQUIRED FLOW AND
PRESSURE FOR THE SYSTEM)
BASIC AUTOMATIC SPRINKLER SYSTEM ARRANGEMENT
BASIC COMPONENTS OF AN AUTOMATIC SPRINKLER SYSTEM
SPRINKLER HEADS
WATER FLOW DETECTOR (T-TAP) WATER FLOW DETECTOR (SERIES) SPECIAL PUPOSE
SUPERVISORY SWITCH
TYPES OF AUTOMATIC SPRINKLER SYSTEM
LEGEND:
CROSSMAIN AT PEAK OF CEILING, HIGHER THAN THE BRANCHLINES – DRAINING WOULD BE DIFFICULT
BRANCHLINES
CROSSMAIN
RISER NIPPLE
Building w/ No Ceiling:
- walls that extend to the roof deck
- draft curtains suspending from the roof
Considerations:
Building Geometry
Potential for Hydraulic Advantage
A=SxL
where: A = area covered by the sprinkler
Maximum protection area limitation for sprinkler (Amax) per NFPA 13:
168 ft² - for light hazard system installed in a building of combustible construction
Exposed Construction
- distance between the beams (called bay) on the
column lines is used to determine L dimension.
- in a room with smooth ceilings, dimensions
between walls may be considered in a manner
similar to bay, provided no interferences such
as lights or duct diffusers exist.
NB = 35 ft/15 ft
L = 35/3
L = 11.667 ft or (11’-8”) - - - - spacing b/w branch lines
S = A/L = 130/11.667
S = 11.145 ft (11’-1 11/16”)
Given Amax of 130 ft² for ordinary hazard and a computed L dimension of 11.667 ft, the
maximum distance between sprinklers on a branch line for the given example is
11.145 ft.
Step 12. Determine the Minimum Number of Sprinklers on Each
Branch Line
Sactual = 297/27 = 11 ft
The distance from the end sprinkler to the wall is computed as:
½ Sactual = 11/2 = 5.5 ft (5’-6”)
A=SxL
Since A (128.37 ft²) does not exceed the allowable max. protection
area/sprinkler Amax (130 ft²) for ordinary hazard, the layout complies with
NFPA 13.
Step 16. Determine Crossmain Location
Location:
- as close as possible to the rising main being served
- on an external wall or a boundary of a building
- within 18 m of the adjacent fire apparatus access road or hardstanding
- in a conspicuous position readily visible and accessible to the fire fighters
Maximum distances between hangers vary with pipe size and pipe type. See
NFPA 13 requirements.
Step 21. Add Final Details
Systems with more than 20 sprinklers must have either an electric bell
or a mechanical water motor gong
Valve Supervision
- valves locked in the open position
- valves electrically monitored with tamper switch
- valves located in constantly inspected locked fenced area
Step 22. Use NFPA 13 Design Checklist
Any installed trades can be surveyed, and other building features that
might have been unclear on the contract drawings, or that might have
changed, can be investigated.
The 30% increase for dry and pre-action pipe systems affects
the area only. The density not modified.
Design Density – the quantity of water per square foot of design area that has been found by
experience to be effective in controlling a fire.
Design Area – an area whose size is related to the occupancy, wherein all sprinklers in the area are
expected to actuate.
Hydraulically Most Demanding Area – a design area protected by a sprinkler system that demands more
water for fire suppression than any other design area on the system.
Geographically Most Remote Area – the area whose linear distance from the sprinkler system riser is
the longest.
Step 3. Determining the Length of the Design Area
L = 1.2 x √A
Example: Classification of Occupancy: Ordinary Group 1
Design Area : 1500 sq. ft. (chosen from the density/area curve)
Proposed Sprinkler Spacing:
Distance b/w sprinklers along the branch line = 12 ft
Distance b/w branch lines = 10 ft.
N.B. This length is minimum, because the length of the design area must be
increased so that the edge of the design area falls at the midpoint between two
sprinklers.
Step 4. Determining the Number of Sprinklers Flowing
Along the Length of the Design Area
Ns = L/S
where:
Ns = no. of sprinklers on the branch line
L = length of the rectangle in the design area
S = spacing between sprinklers along the branch line
LACT = Ns x S = 4 x 12 = 48 ft.
Step 5. Determining the Configuration of Sprinklers in
the Design Area
Once the actual length of the design area is determined, the width of
the rectangular area can be determined
W = A/LACT
Verify the number of sprinklers and check if the total coverage area is equal of above
the design area.
N.B. This falls slightly short of the required 1500 sq. ft design area. Adding one
sprinkler (12x10= 120 ft²) in the design area will met the requirement;
i.e. 1440 + 120 = 1560 sq. ft.
Q = d x As
Q = K x √P
From, Q = K x √P
P = (Q/K)²
= (18/5.6)
P = 10.33 psi
Step 8. Determining Friction Loss
Pf = (4.52) x (Q 1.85)
(C 1.85) x (d 4.87)
Where :
Pf = friction loss of one foot of pipe, psi/ft
Q = water flow, gpm
C = Hazen-Williams roughness coefficient or C-factor
D = internal diameter of the pipe, inches
SAMPLE PROBLEM
GIVEN :
E 4 90 ELBOW F = 10 0.017 Pe = F
T = 42
q= CL 52 D.I.(C-140) L = 55 Pt = 37.82 Pe = 0,433 x 5
T = 113.52
q= CL 52 D.I.(C-140) L = 20 Pt = 40.22
Q = 264.93 Pt = 38.12
q= SCH 40 L = 18 Pt = 10.33
Q = 18 T = 26 Pf = 0.34
Q = 18 T = 9.5 Pf = 0.05
Q (ADJUSTED) = 18 X √ 23.05/11.37
90
80
.
70
PRESSURE, PSI
50
40
. SYSTEM DEMAND
264.93 GPM @ 38.12 PSI
. 700 GPM FLOW@ 35 PSI
RESIDUAL PRESSURE
30
20
10
0
1 2 3 4 5 6 7 8 9 10
FLOWRATE (X100), GPM
STANDPIPE AND HOSE SYSTEM
NFPA 14, STANDARD ON THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM, SUPPLIES THE
MINIMUM CRITERIA FOR THE CALCULATION OF STANDPIPE.
A STANDPIPE IS A SYSTEM OF PIPES THAT SUPPLIES WATER TO HOSE CONNECTION FOR FIRE
DEPARTMENT AND /OR OCCUPANT USE.
CLASSIFICATIONS:
CLASS I – SERVE 2 ½ -INCH FIRE HOSE VALVE FOR FIRE DEPARTMENT USE
CLASS II – SERVE 1 ½ -INCH FIRE HOSE VALVE FOR BUILDING OCCUPANTS USE
(FIRE HOSE REEL – EMPLOYS 1-INCH VALVE WITH SEMI-RIGID HOSE AND NOZZLE ASSY
FOR BUILDING OCCUPANTS USE, NOT PROPERLY CLASSIFIED AS CLASS II BY NFPA)
CLASS III – SERVE BOTH 2 1/2 –INCH FIRE HOSE VALVE FOR FIRE DEPARTMENT USE, AND
1 ½-INCH FIRE HOSE VALVE FOR BUILDING OCCUPANTS USE
STANDPIPE AND HOSE SYSTEM
QCDD REQUIREMENTS FOR STANDPIPE SYSTEM (RISING MAINS)
TYPE
DRY – ANY BUILDING OF HABITABLE HEIGHT 10 M UP TO 28 M ABOVE GROUND LEVEL
WET – BUILDINGS HAVING HABITABLE HEIGHT EXCEEDING 28 M FROM THE GROUND
NFPA 20, STANDARDS FOR THE INSTALLATION OF CENTRIFUGAL FIRE PUMPS, APPLIES TO
THE DESIGN AND INSTALLATION OF PUMPS FOR FIRE PROTECTION.
THE SUCTION SIDE OF A FIRE PUMP IS THE SIDE CONNECTED TO THE WATER SUPPLY.
THE DISCHARGE SIDE OF A FIRE PUMP IS THE SIDE TO WHICH THE SPRINKLER OR
STANDPIPE SYSTEM IS CONNECTED TO RECEIVE PRESSURIZED WATER FROM THE
PUMPS.
CERTAIN CRITERIA MUST BE MEET FOR PIPING AND COMPONENTS OF THE FIRE PUMP:
SINCE MOST SPRINKLERS AND VALVES ARE RATED AT 175 PSI, A PUMP RELIEF
VALVE MAY BE NECESSARY TO PREVENT OVERPRESSURIZATION AND DAMAGE
TO SPRINKLER COMPONENTS WHEN PUMP DISCHARGE PRESSURES EXCEED
175 PSI.
FIRE PUMP TEST HEADER WITH TEST VALVES OR TEST LINES WITH FLOW
METER AND PRESSURE GAUGE RETURNING TO THE WATER TANK IS
REQUIRED ON THE DISCHARGE SIDE OF THE PUMP TO SIMULATE THE RATED
FLOW AND PRESSURE OF THE FIRE PUMP AND COMPARE THE TEST RESULTS
TO THE LISTED CAPACITY/RATING OF THE PUMP.
JOCKEY PUMP - A SMALL PUMP THAT BOOSTS THE STATIC PRESSURE WITHIN THE
PIPING SYSTEM WHEN THE FIRE PUMP IS NOT RUNNING.
THE PRESSURE DIFFERENTIAL BETWEEN THE WATER SUPPLY AND THE SYSTEM DEMAND
DETERMINES WHETHER THE AVAILABLE PRESSURE ON A SUPPLY LINE, SUCH AS AN
EXISTING FIRE WATER SYSTEM NETWORK, CITY WATER SUPPLY, IS CAPABLE OF MEETING
SYSTEM DEMAND.
WHERE:
PA = THE PRESSURE AVAILABLE AT THE WATER SUPPLY AT
THE GPM FLOW OF THE SPRINKLER SYSTEM, IN PSI
PS = THE STATIC PRESSURE, IN PSI
PR = THE RESIDUAL PRESSURE, IN PSI
QA = THE CALCULATED SPRINKLER DEMAND, IN GPM
QT = THE TEST FLOW ASSOCIATED WITH THE RESIDUAL
PRESSURE, IN GPM
PD = PA – PR
= 42.3 – 50
PD = - 7.7 psi
N.B. PD MUST BE POSITIVE SUCH THAT THE WATER SUPPLY EXCEEDS THE
SYSTEM DEMAND. IN THIS CASE THE SPRINKLER SYSTEM CANNOT BE
SUPPLIED FROM THE EXISTING WATER NETWORK, UNLESS THE
PRESSURE DEMAND IS MODIFIED OR LOWERED.
120
110
100
PRESSURE (PSI)
90
80 PSI STATIC SYSTEM DEMAND
80
700 GPM @ 50 PSI
70
PA = PS –(PS-PR) (QA/QT)¹·⁸⁵
60
= 42.3 PSI
50
20 PSI RESIDUAL
40
900 GPM FLOW
30
20
10
0
1 2 3 4 5 6 7 8 9 10
FLOW X 100 (GPM)
GRAPHING A FIRE PUMP SUPPLY
A FIRE PUMP CURVE IS BASED UPON ITS RATED POINT, X-GPM AT Y-PSI.
120
110
PUMP SHUTOFF PRESSURE
100 @ ZERO FLOW:
PRESSURE (PSI)
(1.4) Y = 84 PSI
90 FIRE PUMP RATED CAPACITY
X-GPM = 500 GPM
80 Y-PS1 = 60 PSI
PUMP OVERLOAD (150% POINT)
70 MAXIMUM PUMP CAPACITY
(0.65) Y = 0.65 (60) = 39 PSI
60 (1.5) X = 750 GPM
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10
FLOW X 100 (GPM)
SIZING FIRE PUMPS
ILLUSTRATIVE EXAMPLE # 2:
A FIRE PUMP IS RATED AT 500 GPM AT 60 PSI. SHUT OFF POINT IS AT 140%. THE
CITY SUPPLY HAS BEEN TESTED TO BE 30 PSI STATIC, 15 PSI RESIDUAL, WITH 900
GPM FLOWING. THE SPRINKLER SYSTEM DEMAND IS 550 GPM AT 78 PSI.
DETERMINE THE COMBINED PUMP/CITY SUPPLY CURVE, AND THE PRESSURE
DIFFERENTIAL BETWEEN THE COMBINED SUPPLY AND THE SPRINKLER SYSTEM
DEMAND.
SOLUTION:
DETERMINE THE PRESSURE AVAILABLE AT THE CITY SUPPLY AT THE THREE FIRE
PUMP RATING POINTS (0 GPM, 500 GPM, 750 GPM FLOWS):
ADD THE PUMP SUPPLY AND AVAILABLE PRESURE AT CITY SUPPLY TO GET THE
COMBINED PRESSURE:
160
150
140
120
110
60 PSI + 24.9 PSI = 89.9 PSI
PRESSURE (PSI)
100 84 PSI
90
550 GPM @ 78 PSI
80 SPRINKLER DEMAND
39 PSI + 19.3 PSI = 58.3 PSI
70
60
50
30 PSI STATIC 750 GPM @ 39 PSI
40 500 GPM @ 60 PSI
30
20
GIVEN :
RATED FLOW = 1100/1.5 = 733.3 GPM, SPECIFY NEXT STANDARD PUMP SIZE 750 GPM
FROM PUMP CURVE, 147 % OF RATED CAPACITY PRODUCES 67% OF RATED HEAD
51.59 PSI,
67% OF RATED PRESSURE
50.05 PSI
160
. 0 GPM @ 162.4 PSI
140
130
120
.
1100 GPM @ 85.59 PSI
110 92.4 PSI
. ..
PRESSURE (PSI)
100
750 GPM @ 77 PSI
.
90
80
70
. 70 PSI STATIC
20
10
0
100 200 300 400 500 600 700 800 1000 1100
900
FLOW (GPM)
EXAMPLE # 4. STORAGE TANK - HORT’L CENTRIFUGAL PUMP ARRANGEMENT
THE ESTIMATED WATER DEMAND FOR SPRINKLERS AND HOSE STREAMS IS 1400 GPM @
90 PSI. THE SUCTION SUPPLY IS A GROUND LEVEL STORAGE TANK, AND THE MINIMUM
INLET GAUGE PRESSURE IS 0 PSI AT MAXIMUM FLOW. DETERMINE THE REQUIRED RATED
CAPACITY AND PRESSURE OF THE PUMP.
STEP 1. MEET THE DEMAND OF 1400 GPM WITH THE MAX. CAPACITY OF THE PUMP, WHICH
IS 150% OF RATED CAPACITY,
THEREFORE: THE PUMP RATING SHALL NOT BE LESS THAN 1000 GPM @ 125 PSI.
HORSEPOWER OF FIRE PUMPS
BHP = 5.83 QP
10,000 X E
OR
BHP = QP/1710 X E
WHERE:
Q = FLOW, IN GPM
P = PRESSURE OR TOTAL HEAD, IN PSI
E = EFFICIENCY
Non-combustible
225 (20.9)
Obstructed and
Unobstructed
200 (18.6) 15 (4.57) 130 (12.0) 15 (4.57) 100 (9.3) 12 (3.6)
For pipe
Combustible
schedule
unobstructed
Combustible
168 (15.6) 15 (4.57) 130 (12.0) 15 (4.57) 100 (9.3) 12 (3.6)
obstructed
Legend:
SSU – Sprinkler Standard Upright (K-factor = 5.6 gpm/psi ; 8.0 lpm/kpa)
SSP – Sprinkler Standard Pendent (K-factor = 5.6 gpm/psi ; 8.0 lpm/kpa)
Table 4-7.2: Protection Areas and Maximum Spacing (Standard Sidewall Spray Sprinkler)
Ordinary Hazard
Light Hazard
Non-combustible Non-combustible
Combustible or Limited Combustible or Limited
Finish combustible Finish combustible
Finish Finish
Maximum distance
14 ft (4.3 m) 14 ft (4.3 m) 10 ft (3.0 m) 10 ft (3.0 m)
along the wall
Maximum room
12 ft (3.7 m) 14 ft (4.3 m) 10 ft (3.0 m) 10 ft (3.0 m)
width (L)
Maximum
120 ft2 (11.1 m2) 196 ft2 (18.2 m2) 80 ft2 (7.4 m2) 100 ft2 (9.3 m2)
protection area
5. PIPE SIZING SCHEDULE
Steel Copper
The required residual pressure at the highest, most remote fire department valve outlet at the required flow rate.
The frictional losses of fittings, valves and lengths of piping in the flow path, adding the friction of subsequent flowing
standpipes from the most remote outlet back to the source fire pump.
The static elevation pressure of the most remote outlet’s location (2.31 ft. = 0.434 psi).
The required residual pressure varies with the codes in question. For example, the requirements are 25 psi in New York, 65
psi in Chicago and 100 psi for the International Building Code and International Fire Code. The 100 psi requirement appears
in NFPA 14, the Standpipe Installation Standard.
The piping design layout influences the frictional losses. The Building Code may dictate requirements for the piping layout,
especially as the building’s overall height increases, resulting in the need for multiple zones.
The estimated discharge pressure for the system is established at the pump’s discharge flange. The estimated gallons per
minute flow rate required for the system’s supply is determined using the required pressure. The duty point or “Primary
Rating Point” of the fire pump expresses the overall system’s 100% Q (flow rate) at 100% P (pressure) requirements.
This is the design point on the pump curve that is normally used to select and specify the fire pump model and the
horsepower.
NFPA 20 prescribes two additional points that must be met on the fire pump curves.
The “Secondary Rating Point” of 150% Q at 65% P expresses the conditions at the normal fire pump test flow point.
The “Shut-Off” condition of 0% Q at 120 to 140% P expresses the pump’s discharge pressure at no flow.
All fire pumps listed for fire protection service must have performance curves that meet these three curve conditions. Fire
pumps are generally selected within a range of 90% to 130% of the primary rating point of a given pump capacity. As an
example, a 750-gpm pump might be selected and utilized for a demand of between 675 gpm and 975 gpm, but once the
primary rating point of the next size pump is reached, the larger pump should be selected.
Once a fire pump is selected from a specific manufacturer’s curve, other important system design points can be evaluated.
Plotting the fire pump’s performance curve on a graph of the project’s water flow test data allows for the prediction of the
system’s maximum churn pressure.
According to NFPA 20, the “Shut-Off”condition pressure, plus the water supply static pressure, should not exceed 175 psi for
single-zone sprinkler/standpipe systems and 350 psi in multiple-zone systems.
ILLUSTRATIVE EXAMPLE # 5:
SOLUTION:
STEP 3. BY FORMULA,