Airedale CCU
Airedale CCU
Airedale CCU
Chilled Water
6kW - 60kW
Technical Manual
EasiCool™ Precision Air Conditioning
Warranty, Commissioning & Maintenance
Introduction
As standard, Airedale guarantees all non consumable parts only for a period of 12 months, variations tailored to suit
product and application are also available; please contact Airedale for full terms and details.
To further protect your investment in Airedale products, Airedale can provide full commissioning services,
comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland).
For a free quotation contact Airedale or your local Sales Engineer.
All Airedale products are designed in accordance with EU Directives regarding prevention of build up of water,
associated with the risk of contaminants such as Legionella.
For effective prevention of such risk it is necessary that the equipment is maintained in accordance with Airedale
recommendations.
SafeCool
In addition to commissioning, a 24 hour, 7 days a week on-call service is available throughout the year to UK mainland
sites. This service will enable customers to contact a duty engineer outside normal working hours and receive
assistance over the telephone. The duty engineer can, if necessary, attend site, usually within 24 hours or less.
Full details will be forwarded on acceptance of the maintenance agreement.
CAUTION
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance being carried out
in accordance with the recommendations provided during the warranty period. Failure to have the maintenance
procedures carried out will invalidate the warranty and any liabilities by Airedale International Air Conditioning Ltd.
Spares
A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on
request.
Training
As well as our comprehensive range of products, Airedale offers a modular range of Refrigeration and Air Conditioning
Training courses, for further information please contact Airedale.
Customer Services
For further assistance, please e-mail: enquiries@airedale.com or telephone:
Introduction
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of the Airedale unit.
Safety
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/
electrical equipment, care must be taken if you are to obtain the best results.
CAUTION
When working with any air conditioning units ensure that the electrical isolator is switched off prior to servicing or repair
work and that there is no power to any part of the equipment.
Also ensure that there are no other power feeds to the unit such as fire alarm circuits, BMS circuits etc.
Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent and
trained personnel in accordance with local relevant standards and codes of practice.
The refrigerant used in this range of products is classified under the COSHH regulations as an irritant, with set
Workplace Exposure Levels (WEL) for consideration if this plant is installed in confined or poorly ventilated areas.
A full hazard data sheet in accordance with COSHH regulations is available should this be required.
Freeze Protection
Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes
the units subject to low ambient temperatures.
Units with supply water temperatures below +5°C
Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be
exposed to freezing temperatures.
Units subject to ambient temperatures lower than 0°C
Glycol of an appropriate concentration (1) is used within the system to ensure adequate protection. Please ensure that
the concentration is capable of protection at least 3°C lower than ambient.
Water / glycol solution is constantly circulated through all waterside pipe work and coils to avoid static water from
freezing.
Ensure that pumps are started and running even during shut down periods, when the ambient is within 3°C of the
solution freeze point (1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).
●● Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
●● Train personnel in sound environmental practices.
●● Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
●● Manufacture products in a responsible manner with minimum impact on the environment.
●● Reduce our use of chemicals and minimise their release to the environment.
●● Measure, control and verify environmental performance through internal and external audits.
●● Continually improve our environmental performance.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:
To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.
Introduction
Warranty, Commissioning & Maintenance 2
Customer Services 2
Health and Safety 3
Environmental Considerations 4
Freeze Protection 4
Environmental Policy 4
Specifiers Guide 7
Nomenclature 7
Introduction 7
Unit Overview 8
Construction 9
Chilled Water Components 10
Airflow Components 11
Electrical Components 14
Heating and Humidification 15
Humidification 17
Controls 18
General Features 23
Sound Measurement Method 26
Dimensional & Installation Data 27
Dimensions 27
Positioning 32
Minimum Unit Clearances 33
Weights 35
Ethylene Glycol Correction Factors 36
Water Detector Tape Installation 37
Interconnecting Wiring 38
pLAN Termination 38
Humidifier Bottle Information 39
Technical Data Downflow 42
Performance Data 42
Noise Data 44
DF6CW 46
DF8CW 48
DF10CW 50
DF13CW 52
DF15CW 54
DF17CW 56
DF20CW 58
DF22CW 60
DF26CW 62
DF28CW 64
DF31CW 66
DF35CW 68
DF40CW 70
DF45CW 72
DF50CW 74
DF55CW 76
DF60CW 78
Chilled Water Pressure Drop 80
Hydronic Data Low Pressure Hot Water 81
Performance Data 82
Noise Data 84
V6CW 86
V8CW 88
V10CW 90
V13CW 92
V15CW 94
V17CW 96
V20CW 98
V22CW 100
V26CW 102
V28CW 104
V31CW 106
V35CW 108
V40CW 110
V45CW 112
V50CW 114
V55CW 116
V60CW 118
Chilled Water Pressure Drop 120
Hydronic Data Low Pressure Hot Water 121
Fan Data 122
Calculating Total Static Pressure 122
Fan Speed Data 123
EZRE Chilled Water 400V 50Hz (-0) 124
EZRE Chilled Water 380V 60Hz (-1) 134
EZRE Chilled Water 220V 60Hz (-2) 144
After Sales 147
Specifiers Guide
Introduction
Nomenclature
Example DF 60 X2 EZRE 0
DF Downflow
V Upflow
X DX Air Cooled
WX DX Water Cooled
Introduction
Designed to provide environmental Precision air conditioning for applications such as Telecommunication Facilities,
Computer Rooms, Data Centres, Clean Rooms and laboratories.
Full function units provide full control of temperature, humidification, de-humidification, heating and filtration.
The modular design of the EasiCool allows grouping of differing model types and capacities to be installed side by side.
The flexibility of this type of installation provides for multi-circuit functionality.
A full range of air cooled condensers is available with the direct expansion indoor units to provide a matched system
with optional performance upgrade.
Also available is a full range of Airedale water chillers to complement the chilled water indoor units.
Downflow
Air Filters
Cooling Coil
Control Panel
Heating
●Electric Humidifier
●Low Pressure Hot Water
Upflow
Control Panel
Cooling Coil
Air Filters
Humidifier
Introduction
The cabinet comprises an anodised aluminium frame with black nylon corners and removable galvanised sheet steel
panels. The unit panels are manufactured from galvanised sheet steel coated with epoxy baked powder paint to provide
a durable finish.
Standard unit colour is Black Grey (RAL 7021). Optional Light Grey (RAL 7035).
Cabinets are lined internally with fire resistant foam (UL94 V0) thermal and acoustic insulation:
The cabinet doors are full height, hinged and key lock secured. Hinge arrangement allows flexible door opening/removal
for improved access.
Unit design incorporates a series of M6 fixings to the top and bottom face for connecting to customer ductwork, please
contact Airedale for further details.
Sizes 6 - 26
Dependent upon model type, components such as the expansion valve, compressor, humidifier and sight glass are
contained within an acoustically lined enclosure to provide both ease of maintenance and to minimise sound emission.
System Configuration
Downflow Upflow
Hydrophilic Epoxy Coated
RTPF Chilled Water Coil ● ●
Chilled Water
The cooling coil shall be mounted over a full width stainless steel condensate tray.
3 Port Chilled Water Regulating Valve (Raise/Lower)
For control of water flow, a 3 port, modulating mixing regulating valve shall be fitted as standard. Raise / Lower.
3 Port Chilled Water Regulating Valve (0-10 Volts)
For control of water flow, a 3 port, modulating mixing regulating valve shall be fitted with 0-10 Volts control.
The factory test pressure shall not be less than 20Bar and the maximum operating pressure shall not be less than 10
bar.
The shut off pressure of the valves is 13.6 Bar.
Sweat copper pipe for brazed connection shall be standard. Optional threaded connections shall be available.
Threaded Water Pipe Connection
As an alternative to brazed water pipe connections, BSP brass male taper threaded connections shall be factory fitted.
Introduction
Pleated Disposable Panel Filter EC Direct Drive Backward EC Direct Drive Forward
Curve Fan Curve fan
System Configuration
Downflow Upflow
AC Fans* ● ●
Airflow Components
EC Fans* ● ●
AC Larger Fan Motor* ○ ○
2 way Discharge Grille – ○
3 Way Discharge Grille – ○
Return Air Grille ○ ○
G4 Return Door Air Filter ○ ○
● Standard Feature ○ Optional Feature – Not Available
* Model Dependant
Airflow Switch
An adjustable differential pressure switch activates a visual alarm at the status panel and breaks the power supply in the
event of a fan or motor failure.
Filters
Pleated disposable panel filters in a rigid frame. Conform to BS EN 779-G4.
As standard the microprocessor provides an alarm following a preset run time limit being exceeded,
Sizes 6 - 26
(Direct Drive)
Units utilise a double inlet, forward curved, direct drive centrifugal fan with integral shaft mounted EC motor which is
statically and dynamically balanced for quiet operation. Impellers and casings are galvanised for protection against
corrosion. The integral motor runs in sealed for life, lubricated bearings and features automatic thermal overload
protection.
Fan speed, airflow and external static pressure are controlled by the use of a manually adjustable voltage controller via
the microprocessor display keypad which offers easy on site adjustment.
Sizes 6 - 17
As above except with AC motors.
Sizes 20 - 26
As above except with AC motors.
Sizes 28 - 60 (50Hz / 60Hz)
(Belt & Pulley)
Double inlet forward curved centrifugal fan(s) with galvanised impellers and casing.
Fan and drive assembly design is based on a minimum of 25,000 hours life expectancy.
Each fan assembly is separately driven by a high efficiency air cooled AC motor through a pulley and ‘V’ belt drive. The
complete motor assembly is mounted on a fully adjustable platform for belt tensioning. Motor specification conforms to
Efficiency Class 1(IE2).
Large AC fan motor options available to most sizes, refer to Mechanical Data.
Energy efficient Electronically Commutated (EC) fans are also available.
Introduction
Larger & Next Larger Fan Motor
(AC Fan Motors Only)
For applications where higher static air pressures are required, a larger fan and motor assembly size can be fitted to
replace the standard assembly and is available to most models.
Electronically Commutated (EC) Fan Motor
Sizes 6 - 60
Backward curved impellers, direct drive centrifugal fan assemblies with integral rotor mounted motor which is statically
and dynamically balanced for quiet operation.
Designed for high corrosion resistance, the impellers are laser welded aluminium with a galvanised rotor and die cast
aluminium EC power module.
EC motors incorporate integrated electronics to convert AC power to DC for efficient and accurate speed control and are
adjustable via the microprocessor display keypad.
The fans offer maximum airflow performance while keeping sound levels to a minimum.
The fans are mounted within a floorstand complete with adjustable feet, optional legs and floor tile lip.
Electronically Commutated (EC) Fan Motor Option
EC motors are DC motors with integrated AC to DC conversion; this gives the flexibility of connecting to AC mains with
the efficiency and simple speed control of a DC motor. The EC fan offers significant power reduction in comparison
with equivalent AC fan at both full and modulated fan speeds. The inbuilt EC fan control module allows for fan speed
modulation from 15-100%, a standard AC fans modulating range is typically 40 to 100% of full fan speed.
The EC fan presents superior energy efficiency at full and reduced fan speed compared to the equivalent AC fan motor.
Standard voltage regulated (VR) fan speed controllers offer a linear response. By comparison the EC fan is adjusted on
demand via the unit microprocessor with precision, offering substantial energy savings.
The following illustration shows a comparison of the typical power input required by each method.
Input Power
Airflow
Key
System Configuration
Downflow Upflow
Electrical Switch Gear ● ●
Door Electric Isolator ● ●
Electrical
Energy Manager ○ ○
Phase Rotation Monitoring ○ ○
Thyristor Controlled Electric Heat ○ ○
● Standard Feature ○ Optional Feature – Not Available
Electrical
The control panel contains the necessary compressor starter contactors, transformer, sub circuit protection, volt free
contacts for a common alarm and mains and inter-connecting terminals. The panel is situated within the cabinet and can
be removed for essential maintenance of other components within the unit. The electrical control panels are wired to the
latest European standards and codes of practice.
Sub Fusing
The electrical mains supply for the system’s outdoor unit is supplied via the indoor unit.
MCBs are fitted for protection.
Main Electric Isolator
To ensure complete unit isolation of the electrical panel during adjustment and maintenance a door interlocking isolator
is provided as standard.
Energy Manager
Analysis of system energy consumption can be monitored via a dedicated LCD display. Unit parameters can be adjusted
via the unit microprocessor control to affect energy usage in line with the system need.
Introduction
System Configuration
Downflow Upflow
Electric Heat ○ ○
Heating
Humidifier ○ ○
○ ○
Humidification
Standard electric heating elements are phase balanced for increased efficiency.
Electric Heating Thyristor Control
In addition to the electric heat option a 0 – 100% Thyristor shall be provided to deliver accurate heating control.
Or
Low Pressure Hot Water
A low pressure hot water coil constructed of refrigeration quality copper tube and mechanically bonded aluminium fins
can be factory fitted.
Frost protection is fitted to prevent freezing of the low pressure hot water coil assembly.
Proportional heating control is provided by a factory fitted 3 port, raise/lower type, modulating valve.
Access to the Right hand side of the unit is required to set up the regulating valve
Humidification is provided by an electrode boiler. The sealed humidifier design ensures that only clean sterile steam
is supplied to the conditioned area and corrosive salts and minerals are held in the disposable bottle. The steam is
distributed through a sparge pipe fitted to the coil assembly.
Featuring modulating capacity output control as standard, the system provides continuous modulation of steam output
in response to a proportional control signal. The output control range is 20%-100% of the humidifier rated value and
is designed to give an approximate steam output of +/- 3% at 25°C at the sensor, thus ensuring precise control of the
conditioned space.
The cylinder operating life time is automatically optimised via the integrated water conductivity sensor, which combined
with the controls monitors and regulates the water refill cycle to reduce excessive salt deposits and the progressive
wear of the cylinder.
All humidifier parameters and alarms are accessible and adjustable via the microprocessor display keypad unit, main
features include:
●● Supply water conductivity (µS/cm)
●● Actual steam output (kg/h)
●● Required steam output (kg/h)
●● Actual current rating (A)
●● Required current rating (A)
●● Status mode (Start Up, Running, Filling, Draining)
Water Conductivity & Cylinder Type Conductivity is a measure of the ability of water to pass an electric current,
measured in micro Siemens / centimetre (µS/cm). 3 different cylinders are available which correspond to the supply
water conductivity.
Matching the correct cylinder type with the conductivity of the supply water ensures optimum performance and increases
the life span of the cylinder.
As standard the humidifier is fitted with the standard conductivity cylinder which covers the majority of water supplies.
Where the water conductivity is known, please specify at order. For further details please contact Airedale.
CAUTION
The supply water pressure to the humidifier assembly must be between 1 - 8 barg.
Introduction
Control Principles
In a humidifier with electrodes, steam shall be produced by passing a current between electrode plates to generate heat.
The higher the current being passed between the electrodes, the greater the quantity of steam that is produced.
To modulate the rate of steam production, this system shall vary the level of water within the cylinder, thereby increasing
the immersion level of the electrodes and the current being passed between them. The more conducting area that is
available to pass current between the electrodes, the larger the amount of steam that shall be produced.
Modulated by the controller, the water level is varied so that the level of steam being produced ensures that the room
humidity set-point is continually maintained within a tight tolerance.
Optimised Lifetime
The life span of the Airedale humidification system shall be optimised by the inclusion of a water conductivity sensor
into the bottle feed. This sensor shal determine the conductivity level of the supply water and by using an algorithm
embedded in the software, determines the frequency that the bottle should be drained.
The return temperature is monitored during de-humidification to ensure that the temperature does not fall to a critical
level. If the temperature reaches the low limit de-humidification is cancelled until the return air temperature increases.
Rapid De-humidification
Controlled by the microprocessor, electronic expansion valves are unlike their conventional thermostatic counterparts in
that they can modulate independently of the suction line temperature. This unique feature allows the controller to raise
the superheat set-point, in turn dropping the evaporating temperature to a point at which considerable de-humidification
takes place.
System Configuration
Downflow Upflow
Microprocessor Control ● ●
Graphical Display ● ●
Controls
The standard display keypad visually displays operating alarms by flashing the relevant icon, however, as an optional
extra; a display keypad with audible alarms is available.
The default screen shows the unit status and room condition (°C/RH %) without the need for interrogation and an easy
to navigate menu structure for further interrogation and adjustment.
Standard Icons
Fan Operating
De-humidification
Cooling - Up to 2 Stages
Humidification - Variable
Heating - Up to 3 Stages
Introduction
Temperature Control
A temperature sensor is mounted in the return air with an option for a humidity sensor on full function units.
The temperature sensor is a NTC type thermistor accurate up to +/- 0.25°C and the humidity sensor accurate to +/- 3%
RH at 25°C at the sensor.
The microprocessor senses the return air conditions and maintains the return air temperature and humidity conditions by
controlling cooling, heating, humidification and dehumidification outputs accordingly.
Monitoring
The microprocessor monitors and displays the following values:
●● Return Air Temperature
●● Return Air Humidity (Optional on Full Function units)
●● Coil Temperature Sensor (Indoor)
The maintenance of key components such as compressors and air filters can be monitored via a service indicator which
visually demonstrates the status relative to the component service intervals.
Alarm Log
The controller logs and allows viewing of the last 100 conditions recorded in descending chronological order through the
keypad display.
The standard display keypad visually displays operating alarms, however, as an optional extra, a display keypad with
audible alarms is available.
Modbus/Carel BMS Connection
The Airedale controllers shall be able to communicate directly using the Modbus® protocol.
The Modbus® card shall be a small PCB (60mm x 30mm), which can be plugged into the controller to provide it with the
following protocol support
The data communication shall be asynchronous serial, 8 data bits, 2 stop bits and no parity (in total 11 bits/datum).
The data/parameters from the controller shall be represented within Modbus® registers, each register containing
information pertaining to temperatures, pressures, setpoint, status, etc and is available to the site integration company in
a spreadsheet format
Controls
Introduction
Alarm Handling
An alarm will be generated under the following conditions and will be visually displayed through the alarm log. In
addition, under certain conditions the relevant Icon will flash repeatedly as indicated below:
Sizes 6 - 26
●● Return air temperature high limit
●● Return air temperature low limit
●● Return air humidity high limit (Optional on Full Function units)
●● Return air humidity low limit (Optional on Full Function units)
●● Frost protection low limit (LPHW option only)
●● Filter change alarm
●● Manual override
●● Common alarm
●● Power fail reset
●● Communications failure
●● Maintenance - fan and compressor (once hours run limit exceeded)
●● Airflow failure ( )
Sizes 28 - 60
●● Airflow failure ( )
Controls
Introduction
Password Protection
The control system integrity can be maintained by restricting access with a password PIN number.
IMPORTANT
To change the PIN number, please contact Airedale at time of order with the preferred 4 digit number.
Remote On/Off
Terminals for interlocking are provided to enable or disable the unit remotely.
Fire Shut Down
Terminals for interlocking are provided to shut down the unit in the event of fire.
Evaporator Fan Hours Run Log & Reset
Allows the user to monitor the running times of the evaporator fans and reset after maintenance.
Hours run log or visual service indicator provided.
Filter Change Alarm
Filter change is managed by the AireTronix software, and is based on fan(s) hours run with an alarm being generated
when the pre-set run time limit has been exceeded. The set-point value can be adjusted to suit each application and is
factory set to 4000 hours.
Hours run log or visual service indicator provided.
Standard Network Features
As standard the AireTronix controller is capable of the providing a platform for the following and can be enabled on
request for 2 to 8 units, please specify at order:
Networking
A Local Area Network can be used to connect up to 6 units to offer intercommunication and Duty/Standby control. This
also allows the connection of computers, printers and modems on the same communications ring.
For further details, please contact Airedale Controls.
CAUTION
When adding to an existing network, please consult Airedale to ensure strategy compatibility.
Duty/Standby Operation
The controller enables units to operate in run/standby mode, with up to 6 units networked together, without the need for
additional hardware or controllers. Standby units can be configured to start when the run unit has a critical alarm and/or
a high/low return air temperature alarm.
During peak demand, the standby units can temperature assist.
Duty Rotation
Networked units can be configured to duty rotate, providing equal hours run of fans and compressors.
Audible Alarm
The display keypad can be upgraded to include audible alerts.
BMS Interface Card
Enables Controlled units to be interfaced with most BMS, factory fitted, please contact Airedale.
A wide range of protocols can be accommodated through the use of interface devices. Available as a standard option
are: ModBus/Jbus, Carel and Trend.
For interfaces such as SNMP, LonWorks, Metasys and BACnet, please contact Airedale.
Also available is Airedale’s own supervisory plug-in BMS card pCOWEB.
Based on Ethernet TCP/IP secure technology with SNMP features.
Requires no proprietary cabling or monitoring software and supplied pre programmed with an IP address for ease of set
up.
Smoke Detector
Supplied loose for remote mounting to shut down the unit and activate the alarm upon sensing the presence of smoke.
Firestat
Installed in the return air stream to shut down the unit in the event of an unusually high return air temperature.
Water Detector Installation Tape
Monitored by a sensing relay, the water detection tape will provide an alarm when in contact with several drops of
conductive liquid. High humidity should normally not cause an alarm unless it results in condensation dripping on the
tape surface or condensation present on the surface to which the tape is applied.
System Configuration
Downflow Upflow
Secure Door Locks ● ●
Return Air Grille – –
Cold Water Condensate Pump ○ ○
Open Floorstand ○ ○
Enclosed Floorstand ○ ○
Ceiling Duct Extension ○ ○
● Standard Feature ○ Optional Feature – Not Available
Open & Enclosed Floorstand
Open or enclosed floorstands are available, complete with adjustable feet and floor tile lip. Enclosed floorstands
incorporate an air turning vane. Height of the floorstand; please specify at order.
Discharge Air Configuration
Standard configuration is forward air discharge. Reverse air discharge is available, please specify at order.
Ceiling Duct Extension
Straight and ‘L’ shaped duct extensions up to a height of 1350 mm constructed and finished to match the unit are
available.
Introduction
Condensate Pump
A Condensate Pump
C B Condensate pump discharge line; 10mm
(3/8”) copper tube
C Swan Neck with Tundish
D D Drain line from Tundish, > 10mm (3/8”)
tube (MUST BE copper tube when
coupled with humidifier drain),
minimum fall 1 : 20
B
An overflow weir is incorporated in the common fill/drain tundish. Any pressure build up in the
cylinder would be allowed to vent through the tundish to atmosphere. It is MOST IMPORTANT that
CAUTION the steam distribution pipe is not damaged or kinked at any time to avoid the risk of unacceptably
high pressure building up in the electrode bottle.
The following graphs illustrate the TOTAL static (head) pressure available. The system horizontal pipe losses and
vertical lift should be factored in when calculating the condensate pump performance.
Cold Water Condensate Pump
6
Head (m) 4
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0
Pump Flow Rate (l/min)
Use only 10mm (3/8”) copper tube when connecting the discharge stub to the condensate pump.
IMPORTANT The discharge line from the pump should rise no more than 4 metre before being interrupted with a
swan neck air break and tundish.
6 - 26 28-60
12
12
10
10
8
Head (m)
Head (m)
6
6
4
4
2 2
0 0
5 7 9 11 13 15 5 7 9 11 13 15
Pump Flow Rate (l/min) Pump Flow Rate (l/min)
Sizes 6 - 26 Sizes 28 - 60
The condensate pump has a 3 litre The condensate pump has a 6 litre
reservoir with a capacity of 5 l/m at reservoir with a capacity of 5 l/m at a head
a head of 8m and is mounted in the of 10.8m and is mounted in the unit base.
unit base.
Use only 10mm (3/8”) copper tube when connecting the discharge stub to the condensate pump.
IMPORTANT The discharge line from the pump should rise no more than 6 meters vertically and no more than 8
metres in total length before being interrupted with a swan neck air break and tundish.
Introduction
Measurement Of Sound Power
All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated
sound intensity meter in accordance with BS EN ISO9614 Part 1 : 2009.
All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1 :
2009.
Semi hemispherical
Sound Pressure Levels are calculated from sound power using the semi-hemispherical method where the noise source
is in junction with 2 boundaries i.e. the floor and 1 wall.
Free field
For comparison, the semi hemispherical figures can typically be reduced by 3dB to provide free field conditions.
IMPORTANT
The sound data quoted is based on the unit having a ducted return air, ducted (or underfloor) discharge air and standard
forward curved fan and AC motors fitted, refer to illustration below. Case breakout sound data is therefore independent
of the discharge air and return air sound data.
For non-ducted return air applications, the overall case breakout sound levels may increase, due to the return air sound
being predominant.
Within the conditioned space, sound from in-room ducted discharge air grilles and other equipment will contribute to the
overall sound level and should therefore be considered as part of sound calculations.
(1)
(3) (1)Return Air
(2)Case Breakout
(3)Discharge Air
(2)
(2)
(1)
(3)
1940
6 - 10 13 - 17 20 - 26
C D C D C D E D
F 1 2
7 5
6
G
640
670
270
B 4
200
B B B
15
200
A 15 A A
Installation
1940
28 - 31 35 - 45 50 - 60
C D C D 7 C D E D 1 2
F
6 5
330
710
750
B B B 210 B B B
4 B B B B
210
20
A 20 A A
270
8 1 2
200
B B B B
Installation
15
200
A 15 A A
30
30
6 - 10 13 - 17 10 9 20 -726
1940
C DC D C CD D C DC E DD E D
640
670
270
F F 5 5 6 7
G G 8
4
640
670
270
B
200
B 4B B
15
200
640
670
270
A 15 A A
1 2
200
B B B BB
15
200 B
200
B B
15
200
A670 15
A 15 A 990 A A 1310
A
3
1 2
6 - 10 6 - 10 13 - 17 13 - 17 20 - 26 20 - 26
1940
1940
6 3 7 4
D )
(10) (10 (11) (10)
WxDxH A B C E F G
V6 CW mm 670 x 670 x 1940 640 270 216 (183) 238 (304) N/A 50 (352) 268 (268)
V8 CW mm 670 x 670 x 1940 640 270 183 (167) 304 (337) N/A 50 (352) 268 (295)
V10 CW mm 670 x 670 x 1940 640 270 167 (N/A) 337 (N/A) N/A 50 (325) 295 (N/A)
V13 CW mm 990 x 670 x 1940 960 590 387 (N/A) 337 (N/A) N/A 50 (325) 295 (N/A)
V15 CW mm 990 x 670 x 1940 960 590 355 (N/A) 401 (N/A) N/A 50 (273) 347 (N/A)
V17 CW mm 990 x 670 x 1940 960 590 355 (N/A) 401 (N/A) N/A 50 (273) 347 (N/A)
V20 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (325) 295 (N/A)
V22 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (325) 295 (N/A)
V26 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (325) 295 (N/A)
C D E D
F
C D E D 10 C D E D
9
G
330
710
750
7
8
Installation
B B B 210 B B B B B B B 1 2
210
20
A 20 A A
40 10 7
40
CC DD EE DD CC DD EE DD 9 CC DD EE DD
FF FF FF
1940
330330
710710
750750
28 - 31 35 - 45 50 - 60
GG GG 6 7 GG
210 210 330
20 20 710
750
B B B 210 B B B
8 B B B
5B5
1 2
BB BB BB 210 BB BB BB 210 44 BB BB A BB 3 BB 210
210
AA 20 AA 20 AA 20
20 20 20
8 1 2
1940
28 - 31 35 - 45 50 - 60
1940
1940
28
28--31
31 35
35- -45
45 50
50- -60
60
6 7
36 47
HxDxW A B C D E F(10) G
V28 CW mm 1940 x 750 x 1460 1420 347 175 271 208 123 (335) 292
V31 CW mm 1940 x 750 x 1460 1420 347 175 271 208 123 (335) 292
V35 CW mm 1940 x 750 x 1835 1795 472 304 337 258 123 (335) 292
V40 CW mm 1940 x 750 x 1835 1795 472 304 337 258 123 (335) 292
V45 CW mm 1940 x 750 x 1835 1795 472 304 337 258 123 (335) 292
V50 CW mm 1940 x 750 x 2170 2130 438 277 401 544 78 (327) 345
V55 CW mm 1940 x 750 x 2170 2130 438 277 401 544 78 (327) 345
V60 CW mm 1940 x 750 x 2170 2130 438 277 401 544 78 (327) 345
Options
370
Discharge Air Plenum
370
Installation
1 Discharge air plenum shows as 3 way, also available is front discharge only
Rear Return Air Aperture A
(mm) V6 CW mm 540
V8 CW mm 540
V6 - V26 V10 CW mm 540
V13 CW mm 860
V15 CW mm 860
325
325
V17 CW mm 860
V20 CW mm 1180
65 A 65 V22
65 CW H mm
651180
65
65
V26 CW mm 1180
V28 - V60 A
V28 CW mm 1310
V31 CW mm 1310
V35 CW mm 1685
V40 CW mm 1685
435
V45 CW mm 1685
V50 CW mm 3020
V55 CW mm 3020
V60 CW mm 3020
75 A 75
75
Installation
(1) With adjustable feet fitted
(2) With variable size leg and adjustable feet fitted
IMPORTANT
When placing the unit on the floorstand ensure appropriate air seal is used to prevent leakage at the join.
It is also important to place all locking bolts in place to secure the unit to its base (EC fan floorstands only).
A B C - Floorstand(3) D(4)
DF6 - DF10 mm 670 610 Min 200 - Max 750 Min 300
DF13 - DF17 mm 990 610 (+ 50mm Feet Min 300
DF20 - DF26 mm 1310 610 Adjustable +/- 20mm) Min 300
Installation
C (3)
A B With Feet Only (4) With Leg & Feet (4) D(5)
Min Max Min Max
DF6 - DF10 mm 670 610 284 329 604 1074 Min 300
DF13 - DF17 mm 990 610 362 407 697 1152 Min 300
DF20 - DF26 mm 1310 610 362 407 697 1152 Min 300
DF28 - DF31 mm 1460 700 356 401 686 1146 Min 300
DF35 - DF45 mm 1835 700 356 401 686 1146 Min 300
DF50 - DF60 mm 2170 700 356 401 686 1146 Min 300
E
Forward Only Forward & 1 Side Forward & 2 Sides All Faces
DF6 - DF10 mm 470 240 160 120
DF13 - DF17 mm 550 330 240 170
DF20 - DF26 mm 560 370 280 190
DF28 - DF31 mm 620 410 310 210
DF35 - DF45 mm 640 450 350 230
DF50 - DF60 mm 640 480 380 240
(1) (1)
(2)
(2)
Installation
(6)
(7)
(7)
(5)
(4)
The unit is designed for use with either ducted discharge or a plenum. If neither is used, protection
CAUTION from rotating parts in the form of a grille must be used on the discharge air outlet.
Placing objects near an unguarded fan may cause injury.
A B C - Floorstand(3)
V6 - V10 mm 670 610 Min 200 - Max 750
V13 - V17 mm 990 610 (+ 50mm Feet
V20 - V26 mm 1310 610 Adjustable +/- 20mm)
V28 - V31 mm 1460 700 Min 300 - Max 800
V35 - V45 mm 1835 700 (+ 50mm Feet
V50 - V60 mm 2170 700 Adjustable +/- 20mm)
(1) Weights quoted for units fitted with the standard AC fan motor include the cooling fan weight within the unit cabinet (AHU).
(2) Weights quoted for units fitted with the optional EC fan motor exclude the cooling fan weight within the unit cabinet (AHU).
(3) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.
Standard Evaporator Fan - Fwd EC Motor Optional Evaporator Fan - Bkwd EC Motor
(1) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.
The presence of glycol in the system has a direct effect upon the Cooling Duty, the Design Flow Rate and the unit
Pressure Drop.
Installation
To approximate the effect of glycol on unit performance, the following correction factors when applied can be used as a
guide.
Where:
&
V = Corrected Flow Rate
Q = Equivalent Cooling Duty (kW), refer to Cooling Duties ,
∆T = Temperature difference between Water/Glycol Inlet/Outlet (°C).
∆P = Maximum Water/ Glycol Pressure Drop for the indoor unit (kPa).
∆Pw = Equivalent Water Pressure Drop for indoor unit (kPa), use the corrected flow rate V&.
&
V Corrected Flow Rate = Q / ∆T Flow Rate 0.240 0.250 0.250 0.260
x by
∆P Corrected Pressure Drop = ∆Pw Pressure Drop 1.041 1.083 1.133 1.200
Monitored by a sensing relay, the water detection tape will provide an alarm when in contact with several drops of
conductive liquid. High humidity should normally not cause an alarm unless it results in condensation dripping on the
tape surface or condensation present on the surface to which the tape is applied.
avoiding “bridging” (where the detector lifts off the floor allowing water to run under the detector without detection)
and avoids damage to the detector
• When applying the tape directly to the piping, the tape is simply strapped to the pipe
• Care should be taken to prevent the wire detectors in the tape from coming into contact with any electrically
conductive material causing a “fault” condition. Anything used in applying the tape which interferes with the
capability of the fleece substrate may adversely affect the detector’s function
• The tape should not be installed under piping or equipment that can condense liquid as the condensation could
drip on the tape causing an alarm
• The tape should not be installed directly under an air handling unit, but around the unit
• In the sub-floor of a computer room the tape should be installed after the raised floor, conduit and piping are
installed and the sub-floor cleaned and sealed
Any adhesive which alters the chemical composition of the tape must be avoided and any use
thereof voids any warranty, expressed or implied. 3M Scotch-Weld™ 77 adhesive is strongly
recommended to ensure the warranty will be maintained. When adhesive is used, adhesive with
an oily or greasy base MUST be avoided as this will affect the tape’s ability to detect moisture.
IMPORTANT
When the use of an adhesive is not desirable or practical, staples, clips or other devices may be
used. When applying the tape to piping a combination of glue and plastic or nylon straps or wire
ties may be used. The straps or ties help to cut down installation time and secures the tape to the
pipe while the adhesive cures and dries.
Any electrically conductive attachment devices used must not touch the wires that are within the
tape fabric. The maximum length of a detector loop, including wire and detector tape is 50 metres.
However, this tape length is not practical for most applications. Where the tape is concealed or not
easily accessible, tape runs should be limited to no more than 30 metres, and 10 to 15 metres per
zone is generally used. If the water detector tape is to be attached to or covered by a metallic or
CAUTION conductive surface, care should be taken not to short the conductors.
When installing tape to any surface, be careful not to short circuit or ground out the conductors
(such as over/under conduit or sharp edges of cable trays etc.). This also applies to any covering
which may be applied over the tape. Before installing the tape, be sure to inspect areas where the
tape is to be applied for presence of chemical materials that could create problems. If in doubt, it is
recommended to clean the floor with a mild detergent.
For further information, please refer to Airedale’s Technical Bulletin and Loose Part Instruction Manual.
CW Models L1
L2
Mains Incoming Supply
INDOOR UNIT L3
400V / 3PH + N / 50Hz
N
PE
Installation
Sizes 6-26
560 Common Alarm Normally Open
561 Common
INDOOR UNIT
502 24Vac
561 Common
Sizes 28-60 562 Non-Critical Alarm Normally Closed
502 24Vac
Rx-Tx-
Rx-Tx-
GND
pLAN Termination
Customer Side
RxTx +
GND
RxTx -
RxTx +
GND
Panel Side
Limit Values for the supply water with Medium to High conductivity in an immersed electrode humidifier.
Min Max
Hydrogen ions pH 7 8.5
Specific conductivity at 20°C σR, 20°C μS/cm 300 1250
Total dissolved solids TDS mg/l (1) (1)
Dry residue at 180°C R180 mg/l (1) (1)
Installation
(1) Values depending on specific conductivity; in general: TDS σ 0.93 * σ20; R180 ≅ 0.65 * σ20
(2) not lower than 200% of the chloride content in mg/l of Cl-
(3) not lower than 300% of the chloride content in mg/l of Cl-
Limit Values for the supply water with Medium to Low conductivity in an immersed electrode humidifier.
Min Max
(2) not lower than 200% of the chloride content in mg/l of Cl-
(3) not lower than 300% of the chloride content in mg/l of Cl-
Ensure the union between the humidifier assembly and supply hose is fully tightened. Any
IMPORTANT
looseness, misalignment or damage to the union can lead to water leakage.
It is recommended that a shut off valve and a mechanical strainer be fitted to the water supply prior
CAUTION
to the humidifier assembly.
Notes
Installation
Technical Data
Operating Limits
Indoor Air Temperature +18°C to +28°C
Indoor RH% +40% to +55% (Based upon 24°C Dry Bulb)
Water Entering Temperature +5°C to +10°C
Water Leaving Temperature +10°C to +16°C
ir)
yA
g Dr
(J/
ion
rat
atu
ts a
lpy
Technical
tha
En
25
)
(°C
re
%
10
ra
ity
90
%
pe
id
80
um
%
m
H
70
20
Te
e
iv
%
at
60
lb
el
R
Bu
%
50
et
W
DF
%
15 40
Moisture Content
Operating Band
10
2 0%
5
0
10%
0 5 10 15 20 25 30 35 40
18 28
Dry Bulb Temperature (°C)
Fan Power Input (Fan Gain) must be added to the room load to establish full gross cooling
capacity requirements.
IMPORTANT
Fan Power Input can be found in the mechanical data sections.
Chilled Water
Fan Power Input is taken at the operating conditions based on 25Pa ESP.
Technical
EZRE
26/40 16.4 14.7 13.1 13.1 11.7 11.7 10.2 10.2
22/50 16.2 13.0 12.4 11.3 9.7 9.7 7.7 7.7
DF13CW-
24/45 18.7 15.2 14.8 13.5 12.0 12.0 10.1 10.1
EZRE
26/40 21.2 17.6 17.2 15.8 14.4 14.4 12.4 12.4
22/50 18.5 15.2 14.0 14.0 11.3 11.3 9.0 9.0
DF15CW-
24/45 21.4 17.7 17.5 15.6 13.9 13.9 11.7 11.7
EZRE
26/40 24.3 20.5 19.4 18.4 16.7 16.7 14.4 14.4
DF
22/50 20.7 17.2 15.0 15.0 12.9 12.9 10.2 10.2
DF17CW-
24/45 23.9 20.1 19.6 17.7 15.8 15.8 13.2 13.2
EZRE
26/40 27.2 23.3 21.9 21.1 19.0 19.0 16.4 16.4
22/50 24.2 19.5 18.5 17.0 14.7 14.7 11.7 11.7
DF20CW-
24/45 28.0 22.6 22.1 20.2 18.0 18.0 15.1 15.1
EZRE
26/40 31.8 26.3 25.7 23.7 21.5 21.5 18.7 18.7
22/50 26.0 21.3 20.5 18.5 15.9 15.9 12.7 12.7
DF22CW-
24/45 30.1 24.9 24.6 22.0 19.6 19.6 16.4 16.4
EZRE
26/40 34.2 29.0 27.5 26.1 23.6 23.6 20.3 20.3
22/50 29.2 24.4 21.3 21.3 18.1 18.1 14.4 14.4
DF26CW-
24/45 33.8 28.6 27.8 25.1 22.3 22.3 18.7 18.7
EZRE
26/40 38.5 33.2 30.7 29.9 26.9 26.9 23.2 23.2
Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors.
(4) Refer to Waterside Pressure Drop (kPa).
Operating Limits
Indoor Air Temperature +18°C to +28°C
Indoor RH% +40% to +55% (based upon 24°C Dry Bulb)
Water Entering Temperature +5°C to +10°C
Water Leaving Temperature +10°C to +16°C
EZRE
26/40 64.8 54.9 52.2 49.5 44.8 44.8 38.7 38.7
22/50 53.6 44.4 42.9 38.9 33.5 33.5 26.8 26.8
DF40CW-
24/45 61.8 51.9 50.8 45.8 40.9 40.9 34.3 34.3
EZRE
26/40 70.3 60.2 56.4 54.3 49.1 49.1 42.4 42.4
22/50 58.9 47.1 45.1 41.0 35.7 35.7 28.6 28.6
DF45CW-
24/45 67.9 54.8 53.6 48.5 43.6 43.6 36.6 36.6
EZRE
26/40 77.7 68.2 61.5 61.5 55.1 55.1 47.4 47.4
DF
Operating Limits
Chilled Water
Technical
S @ 3m 51 58 60 52 48 44 40 37 31
DA 77 71 74 72 72 72 71 64 59
RA 67 73 74 72 65 59 56 54 44
DF13CW
CB 62 70 71 63 60 56 52 48 42
S @ 3m 48 56 57 49 45 41 37 34 28
DA 73 70 75 72 69 68 67 62 57
RA 66 73 74 71 62 55 52 53 42
DF15CW
DF
CB 61 70 72 63 57 52 48 47 40
S @ 3m 46 55 57 48 42 37 33 32 26
DA 77 74 78 76 73 72 70 66 61
RA 70 77 78 75 66 59 55 56 46
DF17CW
CB 65 73 76 67 60 56 51 50 44
S @ 3m 50 59 61 52 46 41 37 36 30
DA 81 74 78 77 76 77 75 68 63
RA 72 77 78 76 69 63 60 59 48
DF20CW
CB 67 74 76 68 64 60 56 53 47
S @ 3m 52 59 61 53 49 46 41 38 32
DA 81 74 78 77 76 77 75 68 63
RA 72 77 78 76 69 63 60 59 48
DF22CW
CB 67 74 76 68 64 60 56 53 47
S @ 3m 52 59 61 53 49 46 41 38 32
DA 85 79 83 81 80 81 79 72 67
RA 76 81 82 80 73 67 64 63 52
DF26CW
CB 71 78 80 72 68 64 60 57 51
S @ 3m 56 64 65 57 54 50 46 42 36
Chilled Water
Key:
DA = Discharge Air Sound Power
RA = Return Air Sound Power
CB = Case Breakout Sound Power
S @ 3m = Sound Pressure at 3m
The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false
floor (Base return air only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values
may vary to those stated, typically increasing by 3dB for each side added. Values stated do not include for room reverberation
conditions.
CB 72 77 73 66 71 67 61 59 51
S @ 3m 58 62 58 51 57 53 47 45 37
DA 92 80 86 85 89 86 86 85 81
RA 73 78 76 68 73 67 61 62 53
DF40CW
CB 74 79 75 68 74 70 63 62 54
S @ 3m 60 64 61 54 59 55 49 47 40
DA 92 80 86 85 89 86 86 85 81
RA 73 78 76 68 73 67 61 62 53
DF45CW
DF
CB 74 79 75 68 74 70 63 62 54
S @ 3m 60 64 61 54 59 55 49 47 40
DA 89 78 84 86 82 83 84 81 76
RA 69 76 75 70 66 64 59 57 48
DF50CW
CB 71 77 74 69 67 67 61 58 49
S @ 3m 56 63 59 55 53 53 46 43 34
DA 89 78 84 86 82 83 84 81 76
RA 69 76 75 70 66 64 59 57 48
DF55CW
CB 71 77 74 69 67 67 61 58 49
S @ 3m 56 63 59 55 53 53 46 43 34
DA 91 80 85 89 84 85 86 83 79
RA 71 78 76 73 68 66 61 60 51
DF60CW
CB 73 79 75 73 69 69 63 60 51
S @ 3m 58 65 60 58 55 54 49 45 37
Key:
DA = Discharge Air Sound Power
Chilled Water
The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false floor (Base return air
only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values may vary to those stated, typically
increasing by 3dB for each side added. Values stated do not include for room reverberation conditions.
Technical
DF
Chilled Water
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1335 / 2215 1335 / 2215 1335 / 2215
Maximum ESP Pa 475 475 475
Fan Power Input (Fan Gain) (2) kW 0.23 0.23 0.23
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 6.5 6.5 6.5
Water Flow (Nominal) l/s 0.14 0.14 0.14
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 3/4 3/4 3/4
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
OPTIONAL EXTRAS
DF
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Humidifier
Capacity kg/hr 3 3 3
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1705 / 2215 1705 / 2215 1705 / 2215
Maximum ESP Pa 295 295 295
Fan Power Input (Fan Gain) (2) kW 0.43 0.43 0.43
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 7.5 7.5 7.5
Water Flow (Nominal) l/s 0.17 0.17 0.17
LPHW Connection Sizes mm 22 22 22
Chilled Water
Threaded Connections
Brass Male Taper in 3/4 3/4 3/4
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 21.2 21.2
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A 2.2 2.2
Full Load Amps A N/A 9.1 9.1
Locked Rotor Amps A N/A 22.8 22.75
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2145 / 2215 2145 / 2215 2145 / 2215
Maximum ESP Pa 50 50 50
Fan Power Input (Fan Gain) (2) kW 0.77 0.77 0.77
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 8.4 8.4 8.4
Water Flow (Nominal) l/s 0.19 0.19 0.19
LPHW Connection Sizes mm 22 22 22
Chilled Water
Threaded Connections
Brass Male Taper in 3/4 3/4 3/4
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1105 / 1560 1105 / 1560 1105 / 1560
Maximum ESP Pa 310 310 310
Fan Power Input (Fan Gain) (2) kW 0.37 0.37 0.37
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 11.5 11.5 11.5
Water Flow (Nominal) l/s 0.26 0.26 0.26
LPHW Connection Sizes mm 22 22 22
Chilled Water
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1310 / 1560 1310 / 1560 1310 / 1560
Maximum ESP Pa 195 195 195
Fan Power Input (Fan Gain) (2) kW 0.56 0.56 0.56
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (3) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 12.5 12.5 12.5
Water Flow (Nominal) l/s 0.28 0.28 0.28
LPHW Connection Sizes mm 22 22 22
Chilled Water
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 7.2 19.5 19.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1515 / 1560 1515 / 1560 1515 / 1560
Maximum ESP Pa 45 45 45
Fan Power Input (Fan Gain) (2) kW 0.82 0.82 0.82
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (3) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 13.3 13.3 13.3
Water Flow (Nominal) l/s 0.3 0.3 0.3
LPHW Connection Sizes mm 22 22 22
Chilled Water
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 7.2 19.5 19.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1745 / 2165 1745 / 2165 1745 / 2165
Maximum ESP Pa 450 450 450
Fan Power Input (Fan Gain) (2) kW 0.48 0.48 0.48
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 16.1 16.1 16.1
Water Flow (Nominal) l/s 0.36 0.36 0.36
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2055 / 2165 2055 / 2165 2055 / 2165
Maximum ESP Pa 145 145 145
Fan Power Input (Fan Gain) (2) kW 0.79 0.79 0.79
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 16.1 16.1 16.1
Water Flow (Nominal) l/s 0.36 0.36 0.36
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2055 / 2165 2055 / 2165 2055 / 2165
Maximum ESP Pa 145 145 145
Fan Power Input (Fan Gain) (2) kW 0.79 0.79 0.79
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 16.6 16.6 16.6
Water Flow (Nominal) l/s 0.37 0.37 0.37
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 871 / 909 871 / 909 871 / 909
Maximum ESP Pa 75 75 75
Nominal Airflow m³/s 2.40 2.40 2.40
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF
Humidifier
Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 3.0 / 4.0 3.0 / 4.0 3.0 / 4.0
Speed @ Maximum ESP rpm 1144 / 1439 1144 / 1439 1144 / 1439
Maximum ESP Pa 362 / 722 362 / 722 362 / 722
Fan Power Input (Fan Gain) (2) kW 3.5 / 4.6 3.5 / 4.6 3.5 / 4.6
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1570 / 2165 1570 / 2165 1570 / 2165
Maximum ESP Pa 595 595 595
Fan Power Input (Fan Gain) (2) kW 1.70 1.70 1.70
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 32.5 33.81 58.59
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6
DF
Full Load Amps A 8.66 9.12 15.75
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1008 / 1171 1008 / 1171 1008 / 1171
Maximum ESP Pa 265 265 265
Nominal Airflow m³/s 2.80 2.80 2.80
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF
Humidifier
Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity N/A N/A N/A
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1775 / 2165 1775 / 2165 1775 / 2165
Maximum ESP Pa 390 390 390
Fan Power Input (Fan Gain) (2) kW 2.50 2.50 2.50
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 60.9 58.38 101.15
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6
DF
Full Load Amps A 8.66 9.12 15.75
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 980 / 1078 980 / 1078 980 / 1078
Maximum ESP Pa 165 165 165
Nominal Airflow m³/s 3.30 3.30 3.30
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 5.50 5.50 5.50
Speed @ Maximum ESP rpm 1196 1196 1196
Maximum ESP Pa 322 322 322
Fan Power Input (Fan Gain) (2) kW 6.30 6.30 6.30
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1895 / 2165 1895 / 2165 1895 / 2165
Maximum ESP Pa 285 285 285
Fan Power Input (Fan Gain) (2) kW 2.78 2.78 2.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 60.9 58.38 101.15
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 6.3 6.3 6.3
Full Load Amps A 10.9 10.9 25.63
Locked Rotor Amps A 69.8 69.8 197.35
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1094 / 1186 1094 / 1186 1094 / 1186
Maximum ESP Pa 175 175 175
Nominal Airflow m³/s 3.70 3.70 3.70
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2135 / 2165 2135 / 2165 2135 / 2165
Maximum ESP Pa 70 70 70
Fan Power Input (Fan Gain) (2) kW 3.78 3.78 3.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (4) kW 31.5 31.5 31.5
Water Flow (Nominal) l/s 0.70 0.70 0.70
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 69.8 91.2 157.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1094 / 1186 1094 / 1186 1094 / 1186
Maximum ESP Pa 175 175 175
Nominal Airflow m³/s 3.70 3.70 3.70
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2135 / 2165 2135 / 2165 2135 / 2165
Maximum ESP Pa 70 70 70
Fan Power Input (Fan Gain) (2) kW 3.78 3.78 3.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (4) kW 31.5 31.5 31.5
Water Flow (Nominal) l/s 0.70 0.70 0.70
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 69.8 91.2 157.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1167 / 1170 1167 / 1170 1167 / 1170
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 4.20 4.20 4.20
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
DF
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW 3.0 / 4.0 3.0 / 4.0 3.0 / 4.0
Speed @ Maximum ESP rpm 1448 / 1498 1448 / 1498 1448 / 1498
Maximum ESP Pa 310 / 360 310 / 360 310 / 360
Fan Power Input (Fan Gain) (2) kW 7.0 / 9.2 7.0 / 9.2 7.0 / 9.2
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1265 / 1510 1265 / 1510 1265 / 1510
Maximum ESP Pa 320 320 320
Fan Power Input (Fan Gain) (2) kW 3.78 3.78 3.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 32.5 33.81 58.59
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1167 / 1170 1167 / 1170 1167 / 1170
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 4.20 4.20 4.20
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
DF
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW 3.0 / 4.0 3.0 / 4.0 3.0 / 4.0
Speed @ Maximum ESP rpm 1448 / 1498 1448 / 1498 1448 / 1498
Maximum ESP Pa 310 / 360 310 / 360 310 / 360
Fan Power Input (Fan Gain) (2) kW 7.0 / 9.2 7.0 / 9.2 7.0 / 9.2
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1265 / 1510 1265 / 1510 1265 / 1510
Maximum ESP Pa 320 320 320
Fan Power Input (Fan Gain) (2) kW 3.78 3.78 3.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 32.5 33.81 58.59
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1307 / 1311 1307 / 1311 1307 / 1311
Maximum ESP Pa 75 75 75
Nominal Airflow m³/s 4.60 4.60 4.60
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
DF
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW 4.00 4.00 4.00
Speed @ Maximum ESP rpm 1497 1497 1497
Maximum ESP Pa 275 275 275
Fan Power Input (Fan Gain) (2) kW 9.20 9.20 9.20
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1390 / 1510 1390 / 1510 1390 / 1510
Maximum ESP Pa 185 185 185
Fan Power Input (Fan Gain) (2) kW 4.92 4.92 4.92
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 4.6 4.6 4.6
Full Load Amps A 8.12 8.12 14.45
Locked Rotor Amps A 60.9 60.9 101.15
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
DF6CW - DF26CW
300 6 - 10 13 - 17 20 - 26
Waterside Pressure Drop (kPa)
250
200
150
Technical
100
50
0
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
Waterflow (l/s)
DF
DF28CW - DF60CW
500 28 - 31 35 - 40 45
Waterside Pressure Drop (kPa)
400
50
300
55 - 60
200
100
Chilled Water
0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Waterflow (l/s)
2
Q Kv
∆P valve = where ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =
M 36
(3) Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors.
DF6CW - DF26CW 40
20 - 26
Waterside Pressure Drop (kPa) 35
30
25 6 - 10
20
13 - 17
15
Technical
10
0
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
Waterflow (l/s)
DF
DF28CW - DF60CW
80
70
Waterside Pressure Drop (kPa)
60 50-60
50
40
35-45
30
20
28-31
Chilled Water
10
0
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Waterflow (l/s)
2
Q Kv
∆P valve = where ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =
M 36
(3) Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors.
(1) All data quoted is gross.
(2) Deduct fan motor gain for nett duties, refer to Mechanical Data.
(3) Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors.
Chilled Water
Operating Limits
Indoor Air Temperature +18°C to +28°C
Indoor RH% +40% to +55%
Water Entering Temperature +5°C to +10°C
Water Leaving Temperature +10°C to +16°C
Technical
22/50 48.5 39.8 38.4 34.4 30.0 30.0 24.0 24.0
V35CW-EZRE 24/45 55.9 46.3 43.9 41.2 36.7 36.7 30.7 30.7
26/40 63.5 53.8 51.2 48.5 44.0 44.0 37.9 37.9
22/50 52.5 43.6 42.1 38.1 32.8 32.8 26.3 26.3
V40CW-EZRE 24/45 60.6 50.9 49.8 44.9 40.1 40.1 33.6 33.6
26/40 68.9 59.1 55.3 53.3 48.2 48.2 41.6 41.6
22/50 57.8 46.1 44.2 40.2 35.0 35.0 28.0 28.0
V45CW-EZRE 24/45 66.6 53.8 52.6 47.5 42.7 42.7 35.9 35.9
26/40 76.1 66.9 60.3 60.3 54.0 54.0 46.4 46.4
22/50 57.4 49.1 42.6 42.6 36.1 36.1 28.5 28.5
V50CW-EZRE 24/45 66.8 57.5 50.9 50.9 44.7 44.7 37.2 37.2
26/40 75.5 62.5 60.8 55.6 51.3 51.3 44.3 44.3
22/50 63.8 52.0 45.0 45.0 38.7 38.7 30.6 30.6
V55CW-EZRE 24/45 74.0 60.8 57.9 54.0 48.7 47.7 39.8 39.8
26/40 83.3 70.2 63.6 63.6 57.4 57.4 49.4 49.4
V
22/50 68.3 56.2 48.5 48.5 41.7 41.7 33.0 33.0
V60CW-EZRE 24/45 79.2 65.6 58.0 58.0 51.4 51.4 42.9 42.9
(1) All data quoted is gross.
(2) Deduct fan motor gain for nett duties, refer to Mechanical Data.
(3) Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors.
(4) Refer to Waterside Pressure Drop (kPa).
Operating Limits
Chilled Water
S @ 3m 39 49 50 40 34 32 27 22 11
DA 78 71 75 74 73 73 72 65 60
RA 59 68 70 60 54 52 47 42 31
V8CW
CB 59 68 70 60 54 52 47 42 31
S @ 3m 44 54 55 45 40 38 32 27 17
DA 81 74 78 77 76 76 75 68 63
RA 62 71 73 63 57 55 50 45 34
V10CW
Technical
CB 62 71 73 63 57 55 50 45 34
S @ 3m 47 57 58 48 43 41 35 30 20
DA 78 72 75 73 73 73 72 65 60
RA 59 69 70 60 54 52 47 41 31
V13CW
CB 59 69 70 60 54 52 47 41 31
S @ 3m 44 54 55 45 39 38 32 27 17
DA 74 71 76 73 70 69 68 63 58
RA 57 68 70 60 51 48 43 40 29
V15CW
CB 57 68 70 60 51 48 43 40 29
S @ 3m 43 54 56 45 37 34 28 25 14
DA 78 75 79 77 74 73 71 67 62
RA 61 72 74 63 55 52 46 43 33
V17CW
CB 61 72 74 63 55 52 46 43 33
S @ 3m 47 58 59 49 40 37 32 29 18
DA 82 75 79 78 77 78 76 69 64
V
RA 63 73 74 64 58 56 51 46 35
V20CW
CB 63 73 74 64 58 56 51 46 35
S @ 3m 48 58 59 50 44 42 37 31 21
DA 82 75 79 78 77 78 76 69 64
RA 63 73 74 64 58 56 51 46 35
V22CW
CB 63 73 74 64 58 56 51 46 35
S @ 3m 48 58 59 50 44 42 37 31 21
DA 86 80 84 82 81 82 80 73 68
RA 67 77 78 68 62 61 55 50 40
V26CW
CB 67 77 78 68 62 61 55 50 40
S @ 3m 53 62 64 54 48 46 41 35 25
Chilled Water
Key:
DA = Discharge Air Sound Power
RA = Return Air Sound Power
CB = Case Breakout Sound Power
S @ 3m = Sound Pressure at 3m
The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false floor (Base return air
only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values may vary to those stated, typically
increasing by 3dB for each side added. Values stated do not include for room reverberation conditions.
S @ 3m 63 73 65 64 60 59 52 46 39
DA 93 105 96 89 86 88 84 84 82
RA 80 90 80 81 76 76 69 63 57
V31CW
CB 80 90 80 81 76 76 69 63 57
S @ 3m 65 75 65 66 62 61 55 48 42
DA 92 111 98 90 87 82 82 83 80
RA 80 96 82 83 78 71 68 63 56
V35CW
Technical
CB 80 96 82 83 78 71 68 63 56
S @ 3m 65 81 67 68 64 56 53 48 41
DA 94 113 99 92 89 84 85 85 83
RA 81 98 83 84 80 72 70 65 58
V40CW
CB 81 98 83 84 80 72 70 65 58
S @ 3m 67 83 69 70 65 58 55 50 44
DA 94 113 99 92 89 84 85 85 83
RA 81 98 83 84 80 72 70 65 58
V45CW
CB 81 98 83 84 80 72 70 65 58
S @ 3m 67 83 69 70 65 58 55 50 44
DA 97 115 109 95 92 84 86 84 80
RA 83 98 93 85 82 73 70 63 55
V50CW
CB 83 98 93 85 82 73 70 63 55
S @ 3m 69 84 78 71 67 59 56 49 40
DA 97 115 109 95 92 84 86 84 80
V
RA 83 98 93 85 82 73 70 63 55
V55CW
CB 83 98 93 85 82 73 70 63 55
S @ 3m 69 84 78 71 67 59 56 49 40
DA 98 116 110 97 93 86 87 86 82
RA 85 101 94 89 84 74 72 66 58
V60CW
CB 85 101 94 89 84 74 72 66 58
S @ 3m 71 86 79 74 69 60 58 51 43
Key:
DA = Discharge Air Sound Power
RA = Return Air Sound Power
CB = Case Breakout Sound Power
Chilled Water
S @ 3m = Sound Pressure at 3m
The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false floor (Base return air
only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values may vary to those stated, typically
increasing by 3dB for each side added. Values stated do not include for room reverberation conditions.
Threaded Connections
Brass Male Taper in 3/4 3/4 3/4
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 14 14
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A 1.6 1.6
Full Load Amps A N/A 6.8 6.8
Locked Rotor Amps A N/A 17 17
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 17 21.2
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A 2.2 2.2
Full Load Amps A N/A 9.1 9.1
Locked Rotor Amps A N/A 22.8 22.75
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Threaded Connections
Brass Male Taper in 3/4 3/4 3/4
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1125 / 1560 1125 / 1560 1125 / 1560
Maximum ESP Pa 275 275 275
Fan Power Input (Fan Gain) (2) rpm 0.36 0.36 0.36
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 11.5 11.5 11.5
Water Flow (Nominal) l/s 0.26 0.26 0.26
LPHW Connection Sizes mm 22 22 22
Chilled Water
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1330 / 1560 1330 / 1560 1330 / 1560
Maximum ESP Pa 165 165 165
Fan Power Input (Fan Gain) (2) rpm 0.54 0.54 0.54
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 12.7 12.7 12.7
Water Flow (Nominal) l/s 0.28 0.28 0.28
LPHW Connection Sizes mm 22 22 22
Chilled Water
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 7.2 19.5 19.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1560 / 1560 1560 / 1560 1560 / 1560
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) rpm 0.79 0.79 0.79
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 13.7 13.7 13.7
Water Flow (Nominal) l/s 0.31 0.31 0.31
LPHW Connection Sizes mm 22 22 22
Chilled Water
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 7.2 19.5 19.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1830 / 2165 1830 / 2165 1830 / 2165
Maximum ESP Pa 285 285 285
Fan Power Input (Fan Gain) (2) kW 0.47 0.47 0.47
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 19.2 19.2 19.2
Water Flow (Nominal) l/s 0.43 0.43 0.43
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2165 / 2165 2165 / 2165 2165 / 2165
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) kW 0.79 0.79 0.79
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 19.2 19.2 19.2
Water Flow (Nominal) l/s 0.43 0.43 0.43
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2165 / 2165 2165 / 2165 2165 / 2165
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) kW 0.79 0.79 0.79
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 19.9 19.9 19.9
Water Flow (Nominal) l/s 0.44 0.44 0.44
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1420 / 1552 1600 / 1612 1420 / 1552
Maximum ESP Pa 160 160 160
Nominal Airflow m³/s 2.4 2.40 2.40
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 22.5 20 20
Humidifier
Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 9 9 9
Rating kW 22.5 22.5 22.5
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6
Full Load Amps A 8.66 9.12 15.75
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1600 / 1612 1600 / 1612 1600 / 1612
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 2.8 2.8 2.8
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 22.5 22.5 22.5
Humidifier
Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 60.9 58.38 101.15
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 9 9 9
Rating kW 22.5 22.5 22.5
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6
Full Load Amps A 8.66 9.12 15.75
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1440 / 1468 1440 / 1468 1440 / 1468
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 3.3 3.3 3.3
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 60.9 58.38 101.15
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Current per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 6.3 6.3 6.3
Full Load Amps A 10.9 10.9 25.63
Locked Rotor Amps A 69.8 69.8 197.35
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1620 / 1622 1620 / 1622 1620 / 1622
Maximum ESP Pa 25 25 25
Nominal Airflow m³/s 3.7 3.7 3.7
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 69.8 91.2 157.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1620 / 1622 1620 / 1622 1620 / 1622
Maximum ESP Pa 25 25 25
Nominal Airflow m³/s 3.7 3.7 3.7
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 69.8 91.2 157.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1243 / 1447 1243 / 1447 1243 / 1447
Maximum ESP Pa 255 255 255
Nominal Airflow m³/s 4.2 4.2 4.2
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 5 5 5
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1243 / 1447 1243 / 1447 1243 / 1447
Maximum ESP Pa 255 255 255
Nominal Airflow m³/s 4.2 4.2 4.2
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 5 5 5
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
Speed @ 25Pa / Maximum ESP rpm 1278 / 1324 1278 / 1324 1278 / 1324
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 4.6 4.6 4.6
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 5 5 5
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V
Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.
Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 4.6 4.6 4.6
Full Load Amps A 8.12 8.12 14.45
Locked Rotor Amps A 60.9 60.9 101.15
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8
V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.
Chilled Water
V6CW - V26CW
250
200
150
100
Technical
50
0
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
Waterflow (l/s)
V28CW - V60CW
500 28 - 31 35 - 40 45
Waterside Pressure Drop (kPa)
V
400
50
300
55 - 60
200
100
Chilled Water
0
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Waterflow (l/s)
∆P valve = 2 where ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M = Kv
Q
36
(3) M for glycol use, refer to Ethylene Glycol Correction Factors.
Fluid 100% water,
V6CW - V26CW 40
20 - 26
Waterside Pressure Drop (kPa) 35
30
25 6 - 10
20
13 - 17
15
Technical
10
0
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.45
0.50
Waterflow (l/s)
V28CW - V60CW
80
V
70
Waterside Pressure Drop (kPa)
60 50-60
50
40
35-45
30
20
28-31
Chilled Water
10
0
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Waterflow (l/s)
(1) Includes coil, 3 port valve and pipework.
2
Q Kv
∆P valve = where ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =
M 36
(3) Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors.
Fan Data
Calculating Total Static Pressure
Example
Indoor Unit Model Ref = V50-CW-EZRE-2
Design Air Volume = 4.4m³/s
Design External Static Pressure (ESP) = 85Pa
DF 60
1510 RPM
DF
V 50- 60
700
1510 rpm
660
600
575
400
1000 RPM
300
200
750 RPM
100
Chilled Water
0
2.00 2.50 3.00 3.50 4.00 4.4 4.50 5.00 5.50 6.00
AirFlow [m 3/s]
Key
DF/V 10 - 50Hz
650
10V
600
DF/V 10
550
8V DF 10
500
450
400
Static Pressure [Pa]
350
V 10
6V
Technical
300
250
200
150 4V
100
50
2V
DF
0
0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
Airflow [m 3/s]
Unit
Standard System Curve - System Curve -
Airflow Upflow (V) Downflow (DF)
V
900
V28 - 31 V50 - 60
V35 - 45
800
700
600
Static Pressure [Pa]
500
Chilled Water
400
300
V40/ 45
200
V50/55
V60
V 31
V35
100
V28
0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]
DF 6 - 8
450
DF/V 6
DF/V 8
400
8V
350
V6- 8
Static Pressure [Pa]
300
250
Technical
6V
200
150
4V
100
50
DF
2V
0
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10
Airflow [m3/s]
DF/V 10 - 50Hz
V
DF/V 10 - 50Hz
650
10V
600
DF/V 10
550
8V DF 10
500
450
400
Static Pressure [Pa]
Chilled Water
350
V 10
300 6V
250
200
150 4V
100
50
2V
0
0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
Airflow [m 3/s]
DF/V 13 -50Hz
600
10V
DF/V 13
8V
500
400
Static Pressure [Pa]
300 6V
Technical
DF 13
200
V 13
4V
100
DF
2V
0
0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30
Airflow [m3 /s]
DF/V 15 - 17 - 50Hz
V
DF/V 15-17 - 50Hz
550
10V
500
DF/V 17
DF/V 15
450
8V
DF 15- 17
400
350 V 15- 17
Static Pressure [Pa]
Chilled Water
300
250 6V
200
150
4V
100
50
2V
0
0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70
Airflow [m3/s]
600
DF/V 22
DF/V 26
DF/V 20
DF 20 - 26
550
V 20- 26
8V
500
450
400
Static Pressure [Pa]
350
Technical
6V
300
250
200
150 4V
100
DF
50
2V
0
0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40
3
Airflow [m /s]
700
600
Static Pressure [Pa]
500
Chilled Water
400
300
200
DF50 /55
DF40/45
DF35
100
DF31
DF28
DF60
0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]
800
700
600
Static Pressure [Pa]
500
Technical
400
300
V40/ 45
200
V50/55
V60
V 31
V35
DF
100
V28
0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]
V
DF6 -10 EC Backward Fan Curve
800
DF6
DF10
DF8
700
600
500
Static Pressure [Pa]
Chilled Water
400
300
200
100
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
500
DF17
400
DF13
Static Pressure [Pa]
DF15
300
Technical
200
100
DF
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
Air Volume [m 3/s]
1000
900
DF 22
DF 26
DF 20
800
700
Static Pressure [Pa]
Chilled Water
600
500
400
300
200
100
0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40
DF 28 - 31
DF31
DF28
2150 RPM
1000
800
1900 RPM
Static Pressure [Pa]
600
Technical
1500 RPM
400
1100 RPM
200
DF
0
1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50
AirFlow [m 3/s]
V
DF35- 45 Backward Fan Curve
1200
DF 40 - 45
DF 35
1000
2150 RPM
800 DF 35 - 45
Chilled Water
1900 RPM
Static Pressure [Pa]
600
1500 RPM
400
200
1100 RPM
0
1.50 2.00 2.50 3.00 3.50 4.00 4.50
AirFlow [m 3/s]
DF 60
DF 50 - 60
800
DF 50 - 55
700
600
1250 RPM
Static Pressure [Pa]
500
Technical
400
1000 RPM
300
100
0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m3/s]
V8
500
400
Static Pressure [Pa]
Chilled Water
300
200
100
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
Air Volume [m 3/s]
V 13
V 15
V 17
400
Static Pressure [Pa]
300
Technical
1050 rpm
200
100
DF
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
Air Volume [m 3/s]
V
V20 - 26 EC Backward Fan Curve
800
V 20
V 22
V 26
700
600
500
Static Pressure [Pa]
Chilled Water
400
300
200
1100 rpm
100
0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20
2150 RPM V 28 - 31
V 28
V 31
900
800
1900 RPM
700
600
Static Pressure [Pa]
500
Technical
1500 RPM
400
300
1100 RPM
200
100
DF
0
1.00 1.50 2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]
900
800
1900 RPM
700 V 35 - 45
600
Static Pressure [Pa]
Chilled Water
500
300
200
1100 RPM
100
0
2.00 2.50 3.00 3.50 4.00
AirFlow [m3/s]
V 50-60
DF 50-55
1510 RPM
700
DF 60
600
400
Technical
1000 RPM
300
200
750 RPM
100
DF
0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]
V
Chilled Water
DF/V 6 - 60Hz
600
DF/V 6
230V
500
400
Static Pressure [Pa]
300
Technical
200
100
DF
0
0.20 0.30 0.40 0.50 0.60 0.70
3/s]
Airflow [m
DF/V8 - 60Hz
V
DF/V 8- 60Hz
600
230V
500
400
Static Pressure [Pa]
DF/V 8
Chilled Water
300
200
100
0
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10
Airflow [m 3/s]
700
230V
600
500
DF/V10
Static Pressure [Pa]
400
Technical
300
200
100
DF
0
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
Airflow [m 3 /s]
DF/V13 - 60Hz
V
DF/V 13- 60Hz
800
700
230V
600
500
Static Pressure [Pa]
DF/V13
Chilled Water
400
300
200
100
0
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
Airflow [m 3/s]
DF/V17
DF/V15
500
230V
400
Static Pressure [Pa]
300
Technical
200
100
DF
0
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70
Airflow [m3/s]
DF/V20 - 26 - 60Hz
V
230V
600
500
DF/V26
DF/V 20
DF/V 22
Static Pressure [Pa]
Chilled Water
400
300
200
100
0
0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40
Airflow [m3/s]
800
700
600
Static Pressure [Pa]
500
Technical
400
300
200
DF
100
DF40/45
DF50/55
DF60
DF31
DF35
DF28
0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]
V
V28-60 - EC Forward Fan Curve
900
V28 - 31 V35 - 45 V50 - 60
800
700
600
Static Pressure [Pa]
Chilled Water
500
400
300
200
V60
V50/55
V40/45
100
V31
V28
V35
0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m3/s]
DF6
DF10
DF8
700
600
500
Static Pressure [Pa]
Technical
400
300
200
DF
100
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
Air Volume [m3/s]
DF17
DF15
500
400
Static Pressure [Pa]
Chilled Water
300
200
100
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
Air Volume [m 3 /s]
1000
DF 22
DF 26
DF 20
900
800
700
Static Pressure [Pa]
600
Technical
500
400
300
200
DF
100
0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40
V
DF28-31 Backward Fan Curve
1100
2150 RPM
1000
DF 28-31
DF31
900
DF28
1900 RPM
800
700
Static Pressure [Pa]
Chilled Water
600
400
300
1100 RPM
200
100
0
1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50
AirFlow [m 3/s]
900
DF 40 - 45
DF 35
800
700
600
Static Pressure [Pa]
500
Technical
1500 RPM
400
300
1100 RPM
200
100
DF
0
1.50 2.00 2.50 3.00 3.50 4.00 4.50
AirFlow [m 3/s]
DF 60
DF 50-60
800
700
600
1250 RPM
Static Pressure [Pa]
500
Chilled Water
400
1000 RPM
300
100
0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]
V1 0
V8
V6
500
400
Static Pressure [Pa]
300
Technical
200
100
DF
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
Air Volume [m 3/s]
V
V13 - 17 EC Backward Fan Curve
500
V 13
V 17
V 15
400
Static Pressure [Pa]
300
Chilled Water
1050 rpm
200
100
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
3
Air Volume [m /s]
V 26
V 20
V 22
700
600
500
Static Pressure [Pa]
400
Technical
300
200
1100 rpm
100
DF
0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20
V 31
900
800
1900 RPM
700
600
Static Pressure [Pa]
Chilled Water
500
1500 RPM
400
300
1100 RPM
200
100
0
1.00 1.50 2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]
V 40 -45
900
V35
800
1900 RPM
700 V 35 - 45
600
Static Pressure [Pa]
500
Technical
1500 RPM
400
300
200
1100 RPM
DF
100
0
2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]
V
V50-60 Backward Fan Curve
800
DF 50 - 55
V 50 - 60
DF 60
1510 RPM
700
600
1250 RPM
500
Static Pressure [Pa]
Chilled Water
400
1000 RPM
300
200
750 RPM
100
0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3 /s]
V6
V 10
V8
500
400
Static Pressure [Pa]
Technical
300
200
100
DF
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
Air Volume [m 3/s]
V 17
V 15
400
Static Pressure [Pa]
300
Chilled Water
1050 rpm
200
100
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
Air Volume [m 3/s]
V 20
V 26
700
V 22
600
500
Static Pressure [Pa]
400
Technical
300
200
1100 rpm
100
DF
0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20
V
V28 - 31 Backward Fan Curve
1000
V 28
900
800
1900 RPM
700
600
Static Pressure [Pa]
Chilled Water
500
1500 RPM
400
300
1100 RPM
200
100
0
1.00 1.50 2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]
V 40 - 45
V35
900
800
1900 RPM
V35-45
700
600
Static Pressure [Pa]
500
Technical
1500 RPM
400
300
200
1100 RPM
100
DF
0
2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]
V 60
1510 RPM
700
600
1250 RPM
500
Static Pressure [Pa]
Chilled Water
400
1000 RPM
300
200
750 RPM
100
0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m3/s]
Warranty
All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by
an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or
18 months from the date of despatch, whichever is the sooner.
Parts or Equipment supplied by Airedale for installation within the UK or for Export that are properly commissioned in
accordance with Airedale standards and specification, not commissioned by an Airedale engineer; carry a 12 month
warranty on non consumable Parts only from the date of commissioning or 18 months from the date of despatch,
whichever is the sooner.
Parts or equipment installed or commissioned not to acceptable Airedale standards or specification invalidate all
warranty.
Any spare part supplied by Airedale under warranty shall be warranted for the unexpired period of the warranty or 3
months from delivery, whichever period is the longer. To be read in conjunction with the Airedale Conditions of Sale -
Warranty and Warranty Procedure, available upon request.
Procedure
When a component part fails, a replacement part should be obtained through our Spares department. If the part is
considered to be under warranty, the following details are required to process this requirement. Full description of part
required, including Airedale’s part number, if known. The original equipment serial number. An appropriate purchase
order number.
A spares order will be raised under our warranty system and the replacement part will be despatched, usually within 24
hours should they be in stock. When replaced, the faulty part must be returned to Airedale with a suitably completed and
securely attached “Faulty Component Return” (FCR) tag. FCR tags are available from Airedale and supplied with each
Warranty order.
On receipt of the faulty part, suitably tagged, Airedale will pass to its Warranty department, where it will be fully
inspected and tested in order to identify the reason for failure, identifying at the same time whether warranty is justified
or not.
On completion of the investigation of the returned part, a full “Report on Goods Returned” will be issued. On occasion
the release of this complete report may be delayed as component manufacturers become involved in the investigation.
When warranty is allowed, a credit against the Warranty invoice will be raised. Should warranty be refused the Warranty
invoice becomes payable on normal terms.
Exclusions
Warranty may be refused for the following reasons.
• Misapplication of product or component
• Incorrect site installation
• Incomplete commissioning documentation
• Inadequate site installation
• Inadequate site maintenance
• Damage caused by mishandling
• Replaced part being returned damaged without explanation
• Unnecessary delays incurred in return of defective component
Returns analysis
All faulty components returned under warranty are analysed on a monthly basis as a means of verifying component and
product reliability as well as supplier performance. It is important that all component failures are reported correctly.
TM_EASICOOL_EZRE_CHILLED_WATER_7535768_v1.12.0_04_2018