Airedale CCU

Download as pdf or txt
Download as pdf or txt
You are on page 1of 150

EasiCool™ EZRE

Downflow and Upflow - Precision Air Conditioning

Chilled Water

6kW - 60kW

Technical Manual
EasiCool™ Precision Air Conditioning
Warranty, Commissioning & Maintenance
Introduction

As standard, Airedale guarantees all non consumable parts only for a period of 12 months, variations tailored to suit
product and application are also available; please contact Airedale for full terms and details.

To further protect your investment in Airedale products, Airedale can provide full commissioning services,
comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland).
For a free quotation contact Airedale or your local Sales Engineer.

All Airedale products are designed in accordance with EU Directives regarding prevention of build up of water,
associated with the risk of contaminants such as Legionella.

For effective prevention of such risk it is necessary that the equipment is maintained in accordance with Airedale
recommendations.
SafeCool
In addition to commissioning, a 24 hour, 7 days a week on-call service is available throughout the year to UK mainland
sites. This service will enable customers to contact a duty engineer outside normal working hours and receive
assistance over the telephone. The duty engineer can, if necessary, attend site, usually within 24 hours or less.
Full details will be forwarded on acceptance of the maintenance agreement.

CAUTION
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance being carried out
in accordance with the recommendations provided during the warranty period. Failure to have the maintenance
procedures carried out will invalidate the warranty and any liabilities by Airedale International Air Conditioning Ltd.

Spares
A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on
request.
Training
As well as our comprehensive range of products, Airedale offers a modular range of Refrigeration and Air Conditioning
Training courses, for further information please contact Airedale.

Customer Services
For further assistance, please e-mail: enquiries@airedale.com or telephone:

UK Sales Enquiries + 44 (0) 113 239 1000 enquiries@airedale.com


International Enquiries + 44 (0) 113 239 1000 enquiries@airedale.com
Spares Hot Line + 44 (0) 113 238 7878 spares@airedale.com
Airedale Service + 44 (0) 113 239 1000 service@airedale.com
Technical Support + 44 (0) 113 239 1000 tech.support@airedale.com
Training Enquiries + 44 (0) 113 239 1000 marketing@airedale.com

For information, visit us at our Web Site: www.airedale.com


Airedale Ltd endeavours to ensure that the information in this document is correct and fairly stated, but none of the
statements are to be relied upon as a statement or representation of fact. Airedale Ltd does not accept liability for any
error or omission, or for any reliance placed on the information contained in this document. The development of Airedale
products and services is continuous and the information in this document may not be up to date. It is important to check
the current position with Airedale Ltd at the address stated. This document is not part of a contract or licence unless
expressly agreed. No part of this document may be reproduced or transmitted in any form or by any means, electronic
or mechanical, including photocopying, recording, or information storage and retrieval systems, for any purpose other
than the purchaser’s personal use, without the express written permission of Airedale Ltd.
© 2018 Airedale International Air Conditioning Limited. All rights reserved. Printed in the UK.

2 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Health and Safety

Introduction
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of the Airedale unit.
Safety
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/
electrical equipment, care must be taken if you are to obtain the best results.

CAUTION
When working with any air conditioning units ensure that the electrical isolator is switched off prior to servicing or repair
work and that there is no power to any part of the equipment.
Also ensure that there are no other power feeds to the unit such as fire alarm circuits, BMS circuits etc.

Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent and
trained personnel in accordance with local relevant standards and codes of practice.

The refrigerant used in this range of products is classified under the COSHH regulations as an irritant, with set
Workplace Exposure Levels (WEL) for consideration if this plant is installed in confined or poorly ventilated areas.

A full hazard data sheet in accordance with COSHH regulations is available should this be required.

Protective Personal Equipment


Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning
equipment.
Ecodesign Directive 2009/125/EC
The EasiCool range is exempt from Ecodesign when applied in process cooling applications (i.e. data centres). When
the easiCool range is applied in comfort cooling applications above 12kW they are non-Ecodesign compliant. Please
refer to your Airedale account manager for full details
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regard to manual
handling. This requirement is down to the discretion of the engineer.

Remember do not perform a lift that exceeds your ability.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 3


EasiCool™ Precision Air Conditioning
Environmental Considerations
Introduction

Freeze Protection
Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes
the units subject to low ambient temperatures.
Units with supply water temperatures below +5°C
Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be
exposed to freezing temperatures.
Units subject to ambient temperatures lower than 0°C
Glycol of an appropriate concentration (1) is used within the system to ensure adequate protection. Please ensure that
the concentration is capable of protection at least 3°C lower than ambient.

Water / glycol solution is constantly circulated through all waterside pipe work and coils to avoid static water from
freezing.

Ensure that pumps are started and running even during shut down periods, when the ambient is within 3°C of the
solution freeze point (1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).

(1) Refer to your glycol supplier for details


Environmental Policy
It is our policy to:

●● Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
●● Train personnel in sound environmental practices.
●● Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
●● Manufacture products in a responsible manner with minimum impact on the environment.
●● Reduce our use of chemicals and minimise their release to the environment.
●● Measure, control and verify environmental performance through internal and external audits.
●● Continually improve our environmental performance.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:

Electromagnetic Compatibility Directive (EMC) 2014/30/EU


Machinery Directive (MD) 89/392/EEC version 2006/42/EC
Pressure Equipment Directive (PED) 2014/68/EU

To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.

4 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Contents

Introduction
Warranty, Commissioning & Maintenance 2
Customer Services 2
Health and Safety 3
Environmental Considerations 4
Freeze Protection 4
Environmental Policy 4
Specifiers Guide 7
Nomenclature 7
Introduction 7
Unit Overview 8
Construction 9
Chilled Water Components 10
Airflow Components 11
Electrical Components 14
Heating and Humidification 15
Humidification 17
Controls 18
General Features 23
Sound Measurement Method 26
Dimensional & Installation Data 27
Dimensions 27
Positioning 32
Minimum Unit Clearances 33
Weights 35
Ethylene Glycol Correction Factors 36
Water Detector Tape Installation 37
Interconnecting Wiring 38
pLAN Termination 38
Humidifier Bottle Information 39
Technical Data Downflow 42
Performance Data 42
Noise Data 44
DF6CW 46
DF8CW 48
DF10CW 50
DF13CW 52
DF15CW 54
DF17CW 56
DF20CW 58
DF22CW 60
DF26CW 62
DF28CW 64
DF31CW 66
DF35CW 68
DF40CW 70
DF45CW 72
DF50CW 74
DF55CW 76
DF60CW 78
Chilled Water Pressure Drop 80
Hydronic Data Low Pressure Hot Water 81

EasiCool Technical Manual 7535768 V1.12.0_04_2018 5


EasiCool™ Precision Air Conditioning
Technical Data Upflow 82
Introduction

Performance Data 82
Noise Data 84
V6CW 86
V8CW 88
V10CW 90
V13CW 92
V15CW 94
V17CW 96
V20CW 98
V22CW 100
V26CW 102
V28CW 104
V31CW 106
V35CW 108
V40CW 110
V45CW 112
V50CW 114
V55CW 116
V60CW 118
Chilled Water Pressure Drop 120
Hydronic Data Low Pressure Hot Water 121
Fan Data 122
Calculating Total Static Pressure 122
Fan Speed Data 123
EZRE Chilled Water 400V 50Hz (-0) 124
EZRE Chilled Water 380V 60Hz (-1) 134
EZRE Chilled Water 220V 60Hz (-2) 144
After Sales 147

6 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Specifiers Guide

Introduction
Nomenclature

Example DF 60 X2 EZRE 0

DF Downflow
V Upflow

60 Nominal Cooling Capacity kW

X DX Air Cooled

WX DX Water Cooled

CW Chilled Water Cooling

EZE EasiCool R407C


EZRE EasiCool R410A

0 400V / 3PH / N / 50Hz


1 380V / 3PH / N / 60Hz
2 220V / 3PH / 60Hz

Introduction
Designed to provide environmental Precision air conditioning for applications such as Telecommunication Facilities,
Computer Rooms, Data Centres, Clean Rooms and laboratories.

The EasiCool range comprises of:-


34 models as Single circuit chilled water. (Covered in this document).(-0, -1 and -2 ranges)
38 models as direct expansion air cooled and 38 models as water cooled (Seperate document) (-0 range)
23 Models as direct expansion air cooled and 23 models as water cooled (Seperate document ) (-1 range)
36 Models as direct expansion air cooled and 36 models as water cooled (Seperate document ) (-2 range)

Full function units provide full control of temperature, humidification, de-humidification, heating and filtration.

The modular design of the EasiCool allows grouping of differing model types and capacities to be installed side by side.
The flexibility of this type of installation provides for multi-circuit functionality.

A full range of air cooled condensers is available with the direct expansion indoor units to provide a matched system
with optional performance upgrade.
Also available is a full range of Airedale water chillers to complement the chilled water indoor units.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 7


EasiCool™ Precision Air Conditioning
Unit Overview
Introduction

Downflow

Air Filters
Cooling Coil

Control Panel

Heating
●Electric Humidifier
●Low Pressure Hot Water

Fan Motor Assembly

Upflow

Fan Motor Assembly

Control Panel

Cooling Coil

Air Filters

Humidifier

8 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Construction

Introduction
The cabinet comprises an anodised aluminium frame with black nylon corners and removable galvanised sheet steel
panels. The unit panels are manufactured from galvanised sheet steel coated with epoxy baked powder paint to provide
a durable finish.
Standard unit colour is Black Grey (RAL 7021). Optional Light Grey (RAL 7035).

Cabinets are lined internally with fire resistant foam (UL94 V0) thermal and acoustic insulation:

●● 30mm deep for removable panels


●● 12mm deep for remaining internal surfaces

The cabinet doors are full height, hinged and key lock secured. Hinge arrangement allows flexible door opening/removal
for improved access.

Rubberised door seals reduce sound breakout and eradicate leakage.

Simple bolt on type doors are available as a cost effective option.

Unit design incorporates a series of M6 fixings to the top and bottom face for connecting to customer ductwork, please
contact Airedale for further details.

Sizes 6 - 26
Dependent upon model type, components such as the expansion valve, compressor, humidifier and sight glass are
contained within an acoustically lined enclosure to provide both ease of maintenance and to minimise sound emission.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 9


EasiCool™ Precision Air Conditioning
Chilled Water Components
Introduction

System Configuration
Downflow Upflow
Hydrophilic Epoxy Coated
RTPF Chilled Water Coil ● ●
Chilled Water

Chilled Water Regulating Valve


(3 Way) Raise / Lower ● ●
Chilled Water Regulating Valve
(3 Way) 0-10 Volts ○ ○
Threaded Connections ○ ○
● Standard Features ○ Optional Features – Feature Not Available
Chilled Water Coil
Large surface area coil shall be ideally positioned to optimise airflow and heat transfer, they shall be manufactured
from refrigeration quality copper tubes with mechanically bonded aluminium fins. Fins shall be coated with a non-stick
acrylic film (hydrophilic) to provide additional corrosion protection and efficient surface water removal for improved
performance. Plain aluminium shall not be acceptable.

The cooling coil shall be mounted over a full width stainless steel condensate tray.
3 Port Chilled Water Regulating Valve (Raise/Lower)
For control of water flow, a 3 port, modulating mixing regulating valve shall be fitted as standard. Raise / Lower.
3 Port Chilled Water Regulating Valve (0-10 Volts)
For control of water flow, a 3 port, modulating mixing regulating valve shall be fitted with 0-10 Volts control.

The factory test pressure shall not be less than 20Bar and the maximum operating pressure shall not be less than 10
bar.
The shut off pressure of the valves is 13.6 Bar.

Sweat copper pipe for brazed connection shall be standard. Optional threaded connections shall be available.
Threaded Water Pipe Connection
As an alternative to brazed water pipe connections, BSP brass male taper threaded connections shall be factory fitted.

10 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Airflow Components

Introduction
Pleated Disposable Panel Filter EC Direct Drive Backward EC Direct Drive Forward
Curve Fan Curve fan

System Configuration
Downflow Upflow
AC Fans* ● ●
Airflow Components

EC Fans* ● ●
AC Larger Fan Motor* ○ ○
2 way Discharge Grille – ○
3 Way Discharge Grille – ○
Return Air Grille ○ ○
G4 Return Door Air Filter ○ ○
● Standard Feature ○ Optional Feature – Not Available
* Model Dependant
Airflow Switch
An adjustable differential pressure switch activates a visual alarm at the status panel and breaks the power supply in the
event of a fan or motor failure.
Filters
Pleated disposable panel filters in a rigid frame. Conform to BS EN 779-G4.

Access and removal from unit front.

As standard the microprocessor provides an alarm following a preset run time limit being exceeded,

EasiCool Technical Manual 7535768 V1.12.0_04_2018 11


EasiCool™ Precision Air Conditioning

EC Motor Direct Drive(50Hz)


Introduction

Sizes 6 - 26
(Direct Drive)
Units utilise a double inlet, forward curved, direct drive centrifugal fan with integral shaft mounted EC motor which is
statically and dynamically balanced for quiet operation. Impellers and casings are galvanised for protection against
corrosion. The integral motor runs in sealed for life, lubricated bearings and features automatic thermal overload
protection.

Fan speed, airflow and external static pressure are controlled by the use of a manually adjustable voltage controller via
the microprocessor display keypad which offers easy on site adjustment.

Adjustable by increments of 1% within + / - 10% of the set point.


Sizes 6 - 17
Units have a single fan and motor assembly.
Sizes 20 - 26
Units have 2 fan and motor assemblies.
AC Motors Direct Drive(60Hz)
Sizes 6 - 26
As above except with AC motors.

Sizes 6 - 17
As above except with AC motors.
Sizes 20 - 26
As above except with AC motors.
Sizes 28 - 60 (50Hz / 60Hz)
(Belt & Pulley)
Double inlet forward curved centrifugal fan(s) with galvanised impellers and casing.

Mild steel fan shaft with lifetime lubricated ball bearings.

Fan and drive assembly design is based on a minimum of 25,000 hours life expectancy.

Each fan assembly is separately driven by a high efficiency air cooled AC motor through a pulley and ‘V’ belt drive. The
complete motor assembly is mounted on a fully adjustable platform for belt tensioning. Motor specification conforms to
Efficiency Class 1(IE2).

With integrated plummer block bearings (4kW motors only).


Sizes 28 - 45
Units have a single fan and motor assembly.
Sizes 50 - 60
Units have 2 fan and motor assemblies.

Large AC fan motor options available to most sizes, refer to Mechanical Data.
Energy efficient Electronically Commutated (EC) fans are also available.

12 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Fan & Motor Assembly Optional Features

Introduction
Larger & Next Larger Fan Motor
(AC Fan Motors Only)
For applications where higher static air pressures are required, a larger fan and motor assembly size can be fitted to
replace the standard assembly and is available to most models.
Electronically Commutated (EC) Fan Motor
Sizes 6 - 60
Backward curved impellers, direct drive centrifugal fan assemblies with integral rotor mounted motor which is statically
and dynamically balanced for quiet operation.

Designed for high corrosion resistance, the impellers are laser welded aluminium with a galvanised rotor and die cast
aluminium EC power module.

EC motors incorporate integrated electronics to convert AC power to DC for efficient and accurate speed control and are
adjustable via the microprocessor display keypad.

The fans offer maximum airflow performance while keeping sound levels to a minimum.

The fans are mounted within a floorstand complete with adjustable feet, optional legs and floor tile lip.
Electronically Commutated (EC) Fan Motor Option
EC motors are DC motors with integrated AC to DC conversion; this gives the flexibility of connecting to AC mains with
the efficiency and simple speed control of a DC motor. The EC fan offers significant power reduction in comparison
with equivalent AC fan at both full and modulated fan speeds. The inbuilt EC fan control module allows for fan speed
modulation from 15-100%, a standard AC fans modulating range is typically 40 to 100% of full fan speed.

The EC fan presents superior energy efficiency at full and reduced fan speed compared to the equivalent AC fan motor.

Standard voltage regulated (VR) fan speed controllers offer a linear response. By comparison the EC fan is adjusted on
demand via the unit microprocessor with precision, offering substantial energy savings.

The following illustration shows a comparison of the typical power input required by each method.
Input Power

Airflow
Key

EC (Electronically Commutated) Fan Speed Control

Regulated (VR) Fan Speed Control

EasiCool Technical Manual 7535768 V1.12.0_04_2018 13


EasiCool™ Precision Air Conditioning
Electrical Components
Introduction

System Configuration
Downflow Upflow
Electrical Switch Gear ● ●
Door Electric Isolator ● ●
Electrical

Energy Manager ○ ○
Phase Rotation Monitoring ○ ○
Thyristor Controlled Electric Heat ○ ○
● Standard Feature ○ Optional Feature – Not Available
Electrical
The control panel contains the necessary compressor starter contactors, transformer, sub circuit protection, volt free
contacts for a common alarm and mains and inter-connecting terminals. The panel is situated within the cabinet and can
be removed for essential maintenance of other components within the unit. The electrical control panels are wired to the
latest European standards and codes of practice.
Sub Fusing
The electrical mains supply for the system’s outdoor unit is supplied via the indoor unit.
MCBs are fitted for protection.
Main Electric Isolator
To ensure complete unit isolation of the electrical panel during adjustment and maintenance a door interlocking isolator
is provided as standard.
Energy Manager
Analysis of system energy consumption can be monitored via a dedicated LCD display. Unit parameters can be adjusted
via the unit microprocessor control to affect energy usage in line with the system need.

14 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Heating and Humidification

Introduction
System Configuration
Downflow Upflow
Electric Heat ○ ○
Heating

Hot gas Reheat ○ ○


Low Pressure Hot Water ○ ○

Humidifier ○ ○
○ ○
Humidification

Hot Water Condensate Pump


Low Conductivity (Soft Water) Bottle ○ ○
Standard Conductivity (Moderate/Hard Water) Bottle ○ ○
High Conductivity (Very Hard Water) Bottle ○ ○
Cleanable Humidifier Bottle ○ ○
● Standard Feature ○ Optional Feature – Not Available
Heating
Electric Heating
Multi-stage finned electric heating elements complete with auto and manual reset overheat cut-out protection.

Standard electric heating elements are phase balanced for increased efficiency.
Electric Heating Thyristor Control
In addition to the electric heat option a 0 – 100% Thyristor shall be provided to deliver accurate heating control.

Or
Low Pressure Hot Water
A low pressure hot water coil constructed of refrigeration quality copper tube and mechanically bonded aluminium fins
can be factory fitted.

Frost protection is fitted to prevent freezing of the low pressure hot water coil assembly.
Proportional heating control is provided by a factory fitted 3 port, raise/lower type, modulating valve.

Access to the Right hand side of the unit is required to set up the regulating valve

EasiCool Technical Manual 7535768 V1.12.0_04_2018 15


EasiCool™ Precision Air Conditioning
Humidifier - Intelligent Modulation
Introduction

Humidification is provided by an electrode boiler. The sealed humidifier design ensures that only clean sterile steam
is supplied to the conditioned area and corrosive salts and minerals are held in the disposable bottle. The steam is
distributed through a sparge pipe fitted to the coil assembly.

Featuring modulating capacity output control as standard, the system provides continuous modulation of steam output
in response to a proportional control signal. The output control range is 20%-100% of the humidifier rated value and
is designed to give an approximate steam output of +/- 3% at 25°C at the sensor, thus ensuring precise control of the
conditioned space.

The cylinder operating life time is automatically optimised via the integrated water conductivity sensor, which combined
with the controls monitors and regulates the water refill cycle to reduce excessive salt deposits and the progressive
wear of the cylinder.

All humidifier parameters and alarms are accessible and adjustable via the microprocessor display keypad unit, main
features include:
●● Supply water conductivity (µS/cm)
●● Actual steam output (kg/h)
●● Required steam output (kg/h)
●● Actual current rating (A)
●● Required current rating (A)
●● Status mode (Start Up, Running, Filling, Draining)

Water Conductivity & Cylinder Type Conductivity is a measure of the ability of water to pass an electric current,
measured in micro Siemens / centimetre (µS/cm). 3 different cylinders are available which correspond to the supply
water conductivity.

Matching the correct cylinder type with the conductivity of the supply water ensures optimum performance and increases
the life span of the cylinder.

1 Low Conductivity (Soft Water) 100 to 350 µS/cm


2 Standard Conductivity (Moderate/Hard Water) 350 to 750 µS/cm
3 High Conductivity (Very Hard Water) 750 to 1250 µS/cm

As standard the humidifier is fitted with the standard conductivity cylinder which covers the majority of water supplies.
Where the water conductivity is known, please specify at order. For further details please contact Airedale.

CAUTION
The supply water pressure to the humidifier assembly must be between 1 - 8 barg.

16 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Humidification

Introduction
Control Principles
In a humidifier with electrodes, steam shall be produced by passing a current between electrode plates to generate heat.
The higher the current being passed between the electrodes, the greater the quantity of steam that is produced.
To modulate the rate of steam production, this system shall vary the level of water within the cylinder, thereby increasing
the immersion level of the electrodes and the current being passed between them. The more conducting area that is
available to pass current between the electrodes, the larger the amount of steam that shall be produced.

Modulated by the controller, the water level is varied so that the level of steam being produced ensures that the room
humidity set-point is continually maintained within a tight tolerance.
Optimised Lifetime
The life span of the Airedale humidification system shall be optimised by the inclusion of a water conductivity sensor
into the bottle feed. This sensor shal determine the conductivity level of the supply water and by using an algorithm
embedded in the software, determines the frequency that the bottle should be drained.

Example: (Optimised Lifetime with High Water Conductivity Supply)


As liquid water is boiled off into steam, mineral deposits are left in solution increasing the conductivity of the water.
To counter this, the intelligent software increases the frequency of drain meaning that the replenishing supply water
keeps the concentration of minerals diluted. By maintaining an acceptable mineral concentration, the bottle life span is
maximised.
De-humidification
(With Electric Heating and Humidification only)
Controlled by the microprocessor the de-humidification feature reduces fan speeds by 20% (adjustable). The reduction
of fan speed increases de-humidification which means that the time taken to reduce the room humidity to the required
level is drastically decreased, along with the energy required to do so.

The return temperature is monitored during de-humidification to ensure that the temperature does not fall to a critical
level. If the temperature reaches the low limit de-humidification is cancelled until the return air temperature increases.
Rapid De-humidification
Controlled by the microprocessor, electronic expansion valves are unlike their conventional thermostatic counterparts in
that they can modulate independently of the suction line temperature. This unique feature allows the controller to raise
the superheat set-point, in turn dropping the evaporating temperature to a point at which considerable de-humidification
takes place.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 17


EasiCool™ Precision Air Conditioning
Controls
Introduction

System Configuration
Downflow Upflow
Microprocessor Control ● ●
Graphical Display ● ●
Controls

Filter Change Monitoring ○ ○


Water Detection ○ ○
Fire / Smoke Detection ○ ○
● Standard Feature ○ Optional Feature – Not Available
Units are fitted with the microprocessor controller which offers powerful analogue and digital control to meet a wide
range of monitoring and control requirements. Includes a communication port plus networking and BMS connections.
An 8 x 22 character, white backlit LCD door mounted display keypad assembly is used to view the unit status and allow
operator adjustment. Using a combination of text and standard Icons, the unit display is easy to read and interpret.

The standard display keypad visually displays operating alarms by flashing the relevant icon, however, as an optional
extra; a display keypad with audible alarms is available.
The default screen shows the unit status and room condition (°C/RH %) without the need for interrogation and an easy
to navigate menu structure for further interrogation and adjustment.
Standard Icons

Fan Operating
De-humidification

Cooling - Up to 2 Stages

Humidification - Variable

Heating - Up to 3 Stages

18 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Controls

Introduction
Temperature Control
A temperature sensor is mounted in the return air with an option for a humidity sensor on full function units.

The temperature sensor is a NTC type thermistor accurate up to +/- 0.25°C and the humidity sensor accurate to +/- 3%
RH at 25°C at the sensor.

The microprocessor senses the return air conditions and maintains the return air temperature and humidity conditions by
controlling cooling, heating, humidification and dehumidification outputs accordingly.
Monitoring
The microprocessor monitors and displays the following values:
●● Return Air Temperature
●● Return Air Humidity (Optional on Full Function units)
●● Coil Temperature Sensor (Indoor)

The maintenance of key components such as compressors and air filters can be monitored via a service indicator which
visually demonstrates the status relative to the component service intervals.
Alarm Log
The controller logs and allows viewing of the last 100 conditions recorded in descending chronological order through the
keypad display.

The standard display keypad visually displays operating alarms, however, as an optional extra, a display keypad with
audible alarms is available.
Modbus/Carel BMS Connection
The Airedale controllers shall be able to communicate directly using the Modbus® protocol.

The Modbus® card shall be a small PCB (60mm x 30mm), which can be plugged into the controller to provide it with the
following protocol support

Modbus® - JBus slave


RTU mode (Remote Terminal Unit) with 8 bit encoding and error handling using 16 bit CRC
Communication standard connection options of RS485 (multipoint) or RS232 (point-point)
Maximum Baud Rate of 19200

The data communication shall be asynchronous serial, 8 data bits, 2 stop bits and no parity (in total 11 bits/datum).

The data/parameters from the controller shall be represented within Modbus® registers, each register containing
information pertaining to temperatures, pressures, setpoint, status, etc and is available to the site integration company in
a spreadsheet format

EasiCool Technical Manual 7535768 V1.12.0_04_2018 19


EasiCool™ Precision Air Conditioning

Controls
Introduction

Alarm Handling
An alarm will be generated under the following conditions and will be visually displayed through the alarm log. In
addition, under certain conditions the relevant Icon will flash repeatedly as indicated below:

Sizes 6 - 26
●● Return air temperature high limit
●● Return air temperature low limit
●● Return air humidity high limit (Optional on Full Function units)
●● Return air humidity low limit (Optional on Full Function units)
●● Frost protection low limit (LPHW option only)
●● Filter change alarm
●● Manual override
●● Common alarm
●● Power fail reset
●● Communications failure
●● Maintenance - fan and compressor (once hours run limit exceeded)

●● Airflow failure ( )

●● Electric Heating Overheat cut-out ( )

●● Humidifier alarm (Full Function units only) ( )

Sizes 28 - 60

●● Return air temperature high limit


●● Return air temperature low limit
●● Return air humidity high limit (Optional on Full Function units)
●● Return air humidity low limit (Optional on Full Function units)
●● Frost protection low limit (LPHW option only)
●● Filter change alarm
●● Manual override
●● Common alarm
●● Power fail reset
●● Communications failure
●● Maintenance - fan and compressor (once hours run limit exceeded)
●● Fire
●● Flood
●● Phase Failure
●● Critical
●● Non-critical

●● Airflow failure ( )

●● Electric Heating Overheat cut-out ( )

●● Humidifier alarm (Full Function units only) ( )

20 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Controls

Introduction
Password Protection
The control system integrity can be maintained by restricting access with a password PIN number.

IMPORTANT
To change the PIN number, please contact Airedale at time of order with the preferred 4 digit number.
Remote On/Off
Terminals for interlocking are provided to enable or disable the unit remotely.
Fire Shut Down
Terminals for interlocking are provided to shut down the unit in the event of fire.
Evaporator Fan Hours Run Log & Reset
Allows the user to monitor the running times of the evaporator fans and reset after maintenance.
Hours run log or visual service indicator provided.
Filter Change Alarm
Filter change is managed by the AireTronix software, and is based on fan(s) hours run with an alarm being generated
when the pre-set run time limit has been exceeded. The set-point value can be adjusted to suit each application and is
factory set to 4000 hours.
Hours run log or visual service indicator provided.
Standard Network Features
As standard the AireTronix controller is capable of the providing a platform for the following and can be enabled on
request for 2 to 8 units, please specify at order:
Networking
A Local Area Network can be used to connect up to 6 units to offer intercommunication and Duty/Standby control. This
also allows the connection of computers, printers and modems on the same communications ring.
For further details, please contact Airedale Controls.
CAUTION
When adding to an existing network, please consult Airedale to ensure strategy compatibility.
Duty/Standby Operation
The controller enables units to operate in run/standby mode, with up to 6 units networked together, without the need for
additional hardware or controllers. Standby units can be configured to start when the run unit has a critical alarm and/or
a high/low return air temperature alarm.
During peak demand, the standby units can temperature assist.
Duty Rotation
Networked units can be configured to duty rotate, providing equal hours run of fans and compressors.
Audible Alarm
The display keypad can be upgraded to include audible alerts.
BMS Interface Card
Enables Controlled units to be interfaced with most BMS, factory fitted, please contact Airedale.
A wide range of protocols can be accommodated through the use of interface devices. Available as a standard option
are: ModBus/Jbus, Carel and Trend.
For interfaces such as SNMP, LonWorks, Metasys and BACnet, please contact Airedale.
Also available is Airedale’s own supervisory plug-in BMS card pCOWEB.
Based on Ethernet TCP/IP secure technology with SNMP features.
Requires no proprietary cabling or monitoring software and supplied pre programmed with an IP address for ease of set
up.
Smoke Detector
Supplied loose for remote mounting to shut down the unit and activate the alarm upon sensing the presence of smoke.
Firestat
Installed in the return air stream to shut down the unit in the event of an unusually high return air temperature.
Water Detector Installation Tape
Monitored by a sensing relay, the water detection tape will provide an alarm when in contact with several drops of
conductive liquid. High humidity should normally not cause an alarm unless it results in condensation dripping on the
tape surface or condensation present on the surface to which the tape is applied.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 21


EasiCool™ Precision Air Conditioning
General Features
Introduction

System Configuration
Downflow Upflow
Secure Door Locks ● ●
Return Air Grille – –
Cold Water Condensate Pump ○ ○
Open Floorstand ○ ○
Enclosed Floorstand ○ ○
Ceiling Duct Extension ○ ○
● Standard Feature ○ Optional Feature – Not Available
Open & Enclosed Floorstand
Open or enclosed floorstands are available, complete with adjustable feet and floor tile lip. Enclosed floorstands
incorporate an air turning vane. Height of the floorstand; please specify at order.
Discharge Air Configuration
Standard configuration is forward air discharge. Reverse air discharge is available, please specify at order.
Ceiling Duct Extension
Straight and ‘L’ shaped duct extensions up to a height of 1350 mm constructed and finished to match the unit are
available.

For extensions greater than 1350 mm, please contact Airedale.

Height; please specify at order.


Services Side Access Gland Plate
As standard services can be routed through the gland plate in the base of the units. A gland plate can be optionally
located to the lower left hand side face of the unit, if required.
Bolt on Doors
Simple bolt on cabinet doors can be factory fitted as a cost reduction option. The cabinet doors are full height and
secured by M6 bolts, a 4 mm Allen key is provided for access.
Plain Doors - No Display Keypad
Networking is a standard option of the AireTronix microprocessor; refer to Controls, for full details. To reduce costs, the
“slave” units can be supplied with plain doors (no display keypad), in all door types, please specify at order.
Threaded Water Pipe Connection
As an alternative to brazed water pipe connections, BSP brass male taper threaded connections can be factory fitted.
Export Packing
Units can be supplied packed inside a case to provide additional protection during transportation, (not required for
container delivery).

Standard construction material is solid wood.


Sterling Board LAT (Wooden Case) Packing
Units shall be supplied complete with additional LAT corner protection and cross braces to afford extra transit protection.
Sterling board heat treated man made material shall be used (including pallet) to comply with phytosanity import
regulations (please contact Airedale for this option).

22 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Optional Extras General

Introduction
Condensate Pump
A Condensate Pump
C B Condensate pump discharge line; 10mm
(3/8”) copper tube
C Swan Neck with Tundish
D D Drain line from Tundish, > 10mm (3/8”)
tube (MUST BE copper tube when
coupled with humidifier drain),
minimum fall 1 : 20
B

Condensate and Humidifier


All drain trays are fitted with their own trap assembly.
Condensate drain may be run to waste via ordinary plastic waste pipe.
Humidifier drain may be run to waste via pipe suitable for liquid temperatures of 100°C.
All drain pipework operating under gravity should be sloped away from the equipment and the gradient should be made
as steep as possible.
Suitable rodding positions should be incorporated particularly if the run is long.
Safe Operation of Humidifier
To protect the humidifier bottle from dangerous pressures in event of the steam supply pipe becoming blocked, a tundish
is installed between the water inlet solenoid and the cylinder to act as a reservoir and to feed water to the humidifier inlet
manifold as required.

An overflow weir is incorporated in the common fill/drain tundish. Any pressure build up in the
cylinder would be allowed to vent through the tundish to atmosphere. It is MOST IMPORTANT that
CAUTION the steam distribution pipe is not damaged or kinked at any time to avoid the risk of unacceptably
high pressure building up in the electrode bottle.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 23


EasiCool™ Precision Air Conditioning
Condensate Pump
Introduction

The following graphs illustrate the TOTAL static (head) pressure available. The system horizontal pipe losses and
vertical lift should be factored in when calculating the condensate pump performance.
Cold Water Condensate Pump
6

Head (m) 4

0
0.0 0.5 1.0 1.5 2.0 2.5 3.0
Pump Flow Rate (l/min)

Use only 10mm (3/8”) copper tube when connecting the discharge stub to the condensate pump.
IMPORTANT The discharge line from the pump should rise no more than 4 metre before being interrupted with a
swan neck air break and tundish.

Hot water Condensate Pump

6 - 26 28-60
12
12
10
10
8
Head (m)

Head (m)

6
6
4
4

2 2

0 0
5 7 9 11 13 15 5 7 9 11 13 15
Pump Flow Rate (l/min) Pump Flow Rate (l/min)

Sizes 6 - 26 Sizes 28 - 60
The condensate pump has a 3 litre The condensate pump has a 6 litre
reservoir with a capacity of 5 l/m at reservoir with a capacity of 5 l/m at a head
a head of 8m and is mounted in the of 10.8m and is mounted in the unit base.
unit base.

Use only 10mm (3/8”) copper tube when connecting the discharge stub to the condensate pump.
IMPORTANT The discharge line from the pump should rise no more than 6 meters vertically and no more than 8
metres in total length before being interrupted with a swan neck air break and tundish.

24 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Sound Measurement Method

Introduction
Measurement Of Sound Power
All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated
sound intensity meter in accordance with BS EN ISO9614 Part 1 : 2009.

All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1 :
2009.
Semi hemispherical
Sound Pressure Levels are calculated from sound power using the semi-hemispherical method where the noise source
is in junction with 2 boundaries i.e. the floor and 1 wall.
Free field
For comparison, the semi hemispherical figures can typically be reduced by 3dB to provide free field conditions.

IMPORTANT
The sound data quoted is based on the unit having a ducted return air, ducted (or underfloor) discharge air and standard
forward curved fan and AC motors fitted, refer to illustration below. Case breakout sound data is therefore independent
of the discharge air and return air sound data.

For non-ducted return air applications, the overall case breakout sound levels may increase, due to the return air sound
being predominant.
Within the conditioned space, sound from in-room ducted discharge air grilles and other equipment will contribute to the
overall sound level and should therefore be considered as part of sound calculations.

Specialist acoustic advice is recommended for noise critical applications.

(1)
(3) (1)Return Air
(2)Case Breakout
(3)Discharge Air

(2)

(2)

(1)
(3)

(1) Return Air


(2) Case Breakout
(3) Discharge Air

EasiCool Technical Manual 7535768 V1.12.0_04_2018 25


EasiCool™ Precision Air Conditioning

Dimensional & Installation Data


Dimensions
DF6 - DF26 - Standard Airflow Configuration (mm) with Standard EC Fan Motors
Installation

1940

6 - 10 13 - 17 20 - 26

670 990 1310


3

C D C D C D E D
F 1 2
7 5
6
G
640
670

270

B 4
200

B B B
15

200
A 15 A A

WxDxH A B C(8) D(8) E F(9) G(8)


DF6 CW mm 670 x 670 x 1940 640 270 216 (183) 238 (304) N/A 50 (157) 268 (268)
DF8 CW mm 670 x 670 x 1940 640 270 183 (167) 304 (337) N/A 50 (157) 268 (295)
DF10 CW mm 670 x 670 x 1940 640 270 167 (N/A) 337 (N/A) N/A 50 (186) 295 (N/A)
DF13 CW mm 990 x 670 x 1940 960 590 326 (N/A) 337 (N/A) N/A 50 (186) 295 (N/A)
DF15 CW mm 990 x 670 x 1940 960 590 294 (N/A) 401 (N/A) N/A 50 (210) 347 (N/A)
DF17 CW mm 990 x 670 x 1940 960 590 294 (N/A) 401 (N/A) N/A 50 (210) 347 (N/A)
DF20 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (186) 295 (N/A)
DF22 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (186) 295 (N/A)
DF26 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (186) 295 (N/A)

(1) Standard forward airflow direction.


(2) Optional reverse airflow direction.
(3) Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale.
(4) Base mains cable entry.
(5) Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
(6) Shaded area denotes fan discharge aperture. Optional EC fan motor discharge aperture provided with protective mesh, not shown.
(7) M6 fixing hole positions.
(8) Figures in brackets represent position of fan discharge aperture when larger AC fan motor option is fitted.
(9) Figures in brackets represent optional reverse air discharge configuration when fitted with standard AC fan motors.
(10) Units fitted with optional EC fan motors require a floorstand.

26 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Dimensional & Installation Data


Dimensions
DF28 - DF60 - Standard Airflow Configuration (mm) with Standard AC Fan Motors

Installation
1940

28 - 31 35 - 45 50 - 60

1460 1835 2170


3

C D C D 7 C D E D 1 2
F
6 5
330
710
750

B B B 210 B B B
4 B B B B
210
20

A 20 A A

WxDxH A B C(8) D(8) E F(9) G(8)


DF28 CW mm 1460 x 750 x 1940 1420 347 540 379 N/A 91 (113) 546
DF31 CW mm 1460 x 750 x 1940 1420 347 540 379 N/A 91 (113) 546
DF35 CW mm 1460 x 750 x 1940 1795 472 679 477 N/A 91 (113) 546
DF40 CW mm 1835 x 750 x 1940 1795 472 679 477 N/A 91 (113) 546
DF45 CW mm 1835 x 750 x 1940 1795 472 679 477 N/A 91 (113) 546
DF50 CW mm 2170 x 750 x 1940 2130 438 206 401 543 76 (257) 345
DF55 CW mm 2170 x 750 x 1940 2130 438 206 401 543 76 (257) 345
DF60 CW mm 2170 x 750 x 1940 2130 438 206 401 543 76 (257) 345

(1) Standard forward airflow direction.


(2) Optional reverse airflow direction.
(3) Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale.
(4) Base mains cable entry.
(5) Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
(6) Shaded area denotes fan discharge aperture. Optional EC fan motor discharge aperture provided with protective mesh, not shown.
(7) M6 fixing hole positions.
(8) Figures in brackets represent position of fan discharge aperture when larger AC fan motor option is fitted.
(9) Figures in brackets represent optional reverse air discharge configuration when fitted with standard AC fan motors.
(10) Units fitted with optional EC fan motors require a floorstand.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 27


EasiCool™ Precision Air Conditioning

Dimensional & Installation Data


Dimensions
V6 - V26 - Standard Airflow Configuration (mm) with Standard EC Fan Motors
C D C D C D E D
F 7
10 9
G
640
670

270

8 1 2
200

B B B B
Installation

15

200
A 15 A A

30
30

6 - 10 13 - 17 10 9 20 -726
1940

C DC D C CD D C DC E DD E D
640
670

270

F F 5 5 6 7
G G 8
4
640
670

270

B
200

B 4B B
15

200
640
670

270

A 15 A A
1 2
200

B B B BB
15

200 B
200

B B
15

200
A670 15
A 15 A 990 A A 1310
A
3
1 2

6 - 10 6 - 10 13 - 17 13 - 17 20 - 26 20 - 26
1940

1940

6 3 7 4

670 670 990 990 1310 1310 3 6


5

D )
(10) (10 (11) (10)
WxDxH A B C E F G
V6 CW mm 670 x 670 x 1940 640 270 216 (183) 238 (304) N/A 50 (352) 268 (268)
V8 CW mm 670 x 670 x 1940 640 270 183 (167) 304 (337) N/A 50 (352) 268 (295)
V10 CW mm 670 x 670 x 1940 640 270 167 (N/A) 337 (N/A) N/A 50 (325) 295 (N/A)
V13 CW mm 990 x 670 x 1940 960 590 387 (N/A) 337 (N/A) N/A 50 (325) 295 (N/A)
V15 CW mm 990 x 670 x 1940 960 590 355 (N/A) 401 (N/A) N/A 50 (273) 347 (N/A)
V17 CW mm 990 x 670 x 1940 960 590 355 (N/A) 401 (N/A) N/A 50 (273) 347 (N/A)
V20 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (325) 295 (N/A)
V22 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (325) 295 (N/A)
V26 CW mm 1310 x 670 x 1940 1280 455 166 (N/A) 337 (N/A) 303 50 (325) 295 (N/A)

(1) Standard forward airflow direction.


(2) Optional reverse airflow direction.
(3) Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale.
(4) Base mains cable entry.
(5) Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
(6) Shaded area denotes fan discharge aperture. Optional EC fan motor discharge aperture provided with protective mesh, not shown.
(7) M6 fixing hole positions.
(8) Figures in brackets represent position of fan discharge aperture when larger AC fan motor option is fitted.
(9) Figures in brackets represent optional reverse air discharge configuration when fitted with standard AC fan motors.
(10) Figures in brackets represent position of the Fan discharge aperture when larger fan motor option is fitted.
(11) Figures in brackets represent optional reverse air discharge configuration

28 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Dimensional & Installation Data


Dimensions
V28 - V60 - Standard Airflow Configuration (mm) with Standard AC Fan Motors

C D E D
F
C D E D 10 C D E D

9
G
330
710
750

7
8

Installation
B B B 210 B B B B B B B 1 2
210
20

A 20 A A

40 10 7
40

CC DD EE DD CC DD EE DD 9 CC DD EE DD
FF FF FF
1940
330330
710710
750750

28 - 31 35 - 45 50 - 60
GG GG 6 7 GG
210 210 330
20 20 710
750

B B B 210 B B B
8 B B B
5B5
1 2
BB BB BB 210 BB BB BB 210 44 BB BB A BB 3 BB 210
210

1460 A 210 1835 A 2170


210 210
20 1 2
20

AA 20 AA 20 AA 20
20 20 20
8 1 2
1940

28 - 31 35 - 45 50 - 60
1940
1940

28
28--31
31 35
35- -45
45 50
50- -60
60
6 7
36 47

1460 1835 2170 3


1460
1460 1835
1835 2170
2170 63
5
8

HxDxW A B C D E F(10) G
V28 CW mm 1940 x 750 x 1460 1420 347 175 271 208 123 (335) 292
V31 CW mm 1940 x 750 x 1460 1420 347 175 271 208 123 (335) 292
V35 CW mm 1940 x 750 x 1835 1795 472 304 337 258 123 (335) 292
V40 CW mm 1940 x 750 x 1835 1795 472 304 337 258 123 (335) 292
V45 CW mm 1940 x 750 x 1835 1795 472 304 337 258 123 (335) 292
V50 CW mm 1940 x 750 x 2170 2130 438 277 401 544 78 (327) 345
V55 CW mm 1940 x 750 x 2170 2130 438 277 401 544 78 (327) 345
V60 CW mm 1940 x 750 x 2170 2130 438 277 401 544 78 (327) 345

(1) Standard forward airflow direction.


(2) Optional reverse airflow direction.
(3) Optional gland plate and panel for side services access via the right side of unit. For services details contact Airedale.
(4) Base mains cable entry.
(5) Standard base gland plate entry for refrigeration/water services. For services details contact Airedale.
(6) Shaded area denotes fan discharge aperture. Optional EC fan motor discharge aperture provided with protective mesh, not shown.
(7) M6 fixing hole positions.
(8) Figures in brackets represent position of fan discharge aperture when larger AC fan motor option is fitted.
(9) Figures in brackets represent optional reverse air discharge configuration when fitted with standard AC fan motors.
(10) Figures in brackets represent position of the Fan discharge aperture when larger fan motor option is fitted.
(11) Figures in brackets represent optional reverse air discharge configuration

EasiCool Technical Manual 7535768 V1.12.0_04_2018 29


EasiCool™ Precision Air Conditioning

Dimensional & Installation Data


Upflow

Options

370
Discharge Air Plenum

370
Installation

1 Discharge air plenum shows as 3 way, also available is front discharge only
Rear Return Air Aperture A
(mm) V6 CW mm 540
V8 CW mm 540
V6 - V26 V10 CW mm 540
V13 CW mm 860
V15 CW mm 860
325

325
V17 CW mm 860
V20 CW mm 1180
65 A 65 V22
65 CW H mm
651180
65

65
V26 CW mm 1180

V28 - V60 A
V28 CW mm 1310
V31 CW mm 1310
V35 CW mm 1685
V40 CW mm 1685
435

V45 CW mm 1685
V50 CW mm 3020
V55 CW mm 3020
V60 CW mm 3020
75 A 75
75

1 25 mm flange required to return air duct work, supplied by others.


2 M6 fixings holes required.

30 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Dimensional & Installation Data


Positioning
Downflow
Standard Return and EC Fan Motors Standard Return and Optional EC Fan Motors

Installation
(1) With adjustable feet fitted
(2) With variable size leg and adjustable feet fitted

IMPORTANT
When placing the unit on the floorstand ensure appropriate air seal is used to prevent leakage at the join.
It is also important to place all locking bolts in place to secure the unit to its base (EC fan floorstands only).

EasiCool Technical Manual 7535768 V1.12.0_04_2018 31


EasiCool™ Precision Air Conditioning

Dimensional & Installation Data


Minimum Unit Clearances

Open & Enclosed Floorstands Option

A B C - Floorstand(3) D(4)
DF6 - DF10 mm 670 610 Min 200 - Max 750 Min 300
DF13 - DF17 mm 990 610 (+ 50mm Feet Min 300
DF20 - DF26 mm 1310 610 Adjustable +/- 20mm) Min 300
Installation

DF28 - DF31 mm 1460 700 Min 300 - Max 800 N/A


DF35 - DF45 mm 1835 700 (+ 50mm Feet N/A
DF50 - DF60 mm 2170 700 Adjustable +/- 20mm) N/A
EC Fan Motor Option

C (3)
A B With Feet Only (4) With Leg & Feet (4) D(5)
Min Max Min Max
DF6 - DF10 mm 670 610 284 329 604 1074 Min 300
DF13 - DF17 mm 990 610 362 407 697 1152 Min 300
DF20 - DF26 mm 1310 610 362 407 697 1152 Min 300
DF28 - DF31 mm 1460 700 356 401 686 1146 Min 300
DF35 - DF45 mm 1835 700 356 401 686 1146 Min 300
DF50 - DF60 mm 2170 700 356 401 686 1146 Min 300

Minimum Ceiling Clearance

E
Forward Only Forward & 1 Side Forward & 2 Sides All Faces
DF6 - DF10 mm 470 240 160 120
DF13 - DF17 mm 550 330 240 170
DF20 - DF26 mm 560 370 280 190
DF28 - DF31 mm 620 410 310 210
DF35 - DF45 mm 640 450 350 230
DF50 - DF60 mm 640 480 380 240

(1) Shown with optional open floor stand.


(2) Shaded area indicates minimum service and maintenance requirements.
(3) Dimension C denotes recommended minimum/maximum floorstand height, refer to Airedale for special applications, please specify at order.
(4) Min = Threaded foot at minimum extension.
Max = Threaded foot at maximum extension.
(5) Dimension D refers to units fitted with LPHW which require access to the RHS of the unit to set up the regulating valve.
(6) SERVICES SIDE ACCESS GLAND PLATE, OPTIONAL POSITION; ensure appropriate clearance is available to the base of the RHS of the unit if this option is
selected.

32 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Dimensional & Installation Data


Positioning
Upflow

(1) (1)
(2)
(2)

Installation
(6)
(7)

(7)

(5)

(4)

The unit is designed for use with either ducted discharge or a plenum. If neither is used, protection
CAUTION from rotating parts in the form of a grille must be used on the discharge air outlet.
Placing objects near an unguarded fan may cause injury.

Minimum Unit Clearance

A B C - Floorstand(3)
V6 - V10 mm 670 610 Min 200 - Max 750
V13 - V17 mm 990 610 (+ 50mm Feet
V20 - V26 mm 1310 610 Adjustable +/- 20mm)
V28 - V31 mm 1460 700 Min 300 - Max 800
V35 - V45 mm 1835 700 (+ 50mm Feet
V50 - V60 mm 2170 700 Adjustable +/- 20mm)

(1) Reversed discharge air.


(2) Forward discharge air.
(3) Shaded area indicates minimum service and maintenance requirements
(4) Shown with optional open floor stand.
(5) Optional base return.
(6) Optional rear return.
(7) SERVICES SIDE ACCESS GLAND PLATE, OPTIONAL POSITION; ensure appropriate clearance is available to the base of the RHS of the unit if this option is selected.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 33


EasiCool™ Precision Air Conditioning

Dimensional & Installation Data


Weights
Downflow
Standard Evaporator Fan - Fwd EC Motor Optional Evaporator Fan - Bkwd EC Motor

EZRE Machine(1) Operating(1) Machine(1) Operating(1) Floorstand

DF6CW kg 164 146 26


DF8CW kg 167 151 26
Installation

DF10CW kg 163 151 26


DF13CW kg 190 179 29
DF15CW kg 204 176 29
DF17CW kg 204 176 29
DF20CW kg 242 216 44
DF22CW kg 242 216 44
DF26CW kg 242 216 44
DF28CW kg 351 317 125
DF31CW kg 354 310 125
DF35CW kg 410 363 128
DF40CW kg 431 370 128
DF45CW kg 442 381 128
DF50CW kg 486 427 190
DF55CW kg 499 440 190

DF60CW kg 495 430 190

(1) Weights quoted for units fitted with the standard AC fan motor include the cooling fan weight within the unit cabinet (AHU).
(2) Weights quoted for units fitted with the optional EC fan motor exclude the cooling fan weight within the unit cabinet (AHU).
(3) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.

Standard Evaporator Fan - Fwd EC Motor Optional Evaporator Fan - Bkwd EC Motor

EZRE Machine(1) Operating(1) Machine(1) Operating(1)

V6CW kg 147 138


V8CW kg 149 142
V10CW kg 145 142
V13CW kg 185 187
V15CW kg 199 184
V17CW kg 199 184
V20CW kg 236 232
V22CW kg 236 232
V26CW kg 236 232
V28CW kg 349 352
V31CW kg 347 342
V35CW kg 408 399
V40CW kg 429 407
V45CW kg 440 418
V50CW kg 485 475
V55CW kg 498 488

V60CW kg 498 488

(1) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.

34 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Ethylene Glycol Correction Factors
For conditions outside those quoted, please refer to Airedale.

The Use of Glycol


Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be
exposed to freezing temperatures.

The presence of glycol in the system has a direct effect upon the Cooling Duty, the Design Flow Rate and the unit
Pressure Drop.

Installation
To approximate the effect of glycol on unit performance, the following correction factors when applied can be used as a
guide.

Where:

&
V = Corrected Flow Rate
Q = Equivalent Cooling Duty (kW), refer to Cooling Duties ,
∆T = Temperature difference between Water/Glycol Inlet/Outlet (°C).
∆P = Maximum Water/ Glycol Pressure Drop for the indoor unit (kPa).
∆Pw = Equivalent Water Pressure Drop for indoor unit (kPa), use the corrected flow rate  V&.

Ethylene Glycol (Volume) / Freezing Point °C


10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C

&
V Corrected Flow Rate = Q / ∆T Flow Rate 0.240 0.250 0.250 0.260
x by
∆P Corrected Pressure Drop = ∆Pw Pressure Drop 1.041 1.083 1.133 1.200

Example: V26WX2-EZ Condensing Entering / Leaving at 30°C/35°C, Based on ΔT of 5°C,


24°C/45% RH Ambient, 20% Ethylene Glycol

Ethylene Glycol (Volume) / Freezing Point °C


10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C
Q (35.2) / ∆T
&
V 1.76 l/s = 7.04 0.240 0.250 0.250 0.260
(12 - 7 = 5∆T) = x by
∆P 157Pa = ∆Pw 145 kPa 1.041 1.083 1.133 1.200

EasiCool Technical Manual 7535768 V1.12.0_04_2018 35


EasiCool™ Precision Air Conditioning
Water
Water Detector
Detector Tape
Tape Installation
Installation

Monitored by a sensing relay, the water detection tape will provide an alarm when in contact with several drops of
conductive liquid. High humidity should normally not cause an alarm unless it results in condensation dripping on the
tape surface or condensation present on the surface to which the tape is applied.

The recommended installation process is as follows:


• When applying to a surface such as concrete, the most popular method is to press the tape firmly onto a
continuous film of approved adhesive or glue. When properly glued to the floor the tape lies flat on the floor
Installation

avoiding “bridging” (where the detector lifts off the floor allowing water to run under the detector without detection)
and avoids damage to the detector
• When applying the tape directly to the piping, the tape is simply strapped to the pipe
• Care should be taken to prevent the wire detectors in the tape from coming into contact with any electrically
conductive material causing a “fault” condition. Anything used in applying the tape which interferes with the
capability of the fleece substrate may adversely affect the detector’s function
• The tape should not be installed under piping or equipment that can condense liquid as the condensation could
drip on the tape causing an alarm
• The tape should not be installed directly under an air handling unit, but around the unit
• In the sub-floor of a computer room the tape should be installed after the raised floor, conduit and piping are
installed and the sub-floor cleaned and sealed

Any adhesive which alters the chemical composition of the tape must be avoided and any use
thereof voids any warranty, expressed or implied. 3M Scotch-Weld™ 77 adhesive is strongly
recommended to ensure the warranty will be maintained. When adhesive is used, adhesive with
an oily or greasy base MUST be avoided as this will affect the tape’s ability to detect moisture.
IMPORTANT
When the use of an adhesive is not desirable or practical, staples, clips or other devices may be
used. When applying the tape to piping a combination of glue and plastic or nylon straps or wire
ties may be used. The straps or ties help to cut down installation time and secures the tape to the
pipe while the adhesive cures and dries.

Any electrically conductive attachment devices used must not touch the wires that are within the
tape fabric. The maximum length of a detector loop, including wire and detector tape is 50 metres.
However, this tape length is not practical for most applications. Where the tape is concealed or not
easily accessible, tape runs should be limited to no more than 30 metres, and 10 to 15 metres per
zone is generally used. If the water detector tape is to be attached to or covered by a metallic or
CAUTION conductive surface, care should be taken not to short the conductors.

When installing tape to any surface, be careful not to short circuit or ground out the conductors
(such as over/under conduit or sharp edges of cable trays etc.). This also applies to any covering
which may be applied over the tape. Before installing the tape, be sure to inspect areas where the
tape is to be applied for presence of chemical materials that could create problems. If in doubt, it is
recommended to clean the floor with a mild detergent.

For further information, please refer to Airedale’s Technical Bulletin and Loose Part Instruction Manual.

36 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Interconnecting Wiring

CW Models L1  

L2  
Mains Incoming Supply
INDOOR UNIT L3  
400V / 3PH + N / 50Hz
N  

PE  

Installation
Sizes 6-26
560   Common Alarm Normally Open

561   Common

562   Common Alarm Normally Closed

INDOOR UNIT

583   Fire Detection

502   24Vac

560   Non-Critical Alarm Normally Open

561   Common
Sizes 28-60 562   Non-Critical Alarm Normally Closed

563   Critical Alarm Normally Open

INDOOR UNIT 564   Common

565   Critical Alarm Normally Closed

583   Fire Detection

502   24Vac

Remote On / Off 522   Remote On/Off


INDOOR UNIT
502   24Vac

Rx-Tx-  

Rx+Tx+   Network Connections (Inward connection)


Network GND  
INDOOR UNIT

Rx-Tx-  

Rx+Tx+   Network Connections (Outward connection)

GND  
pLAN Termination

Customer Side

The plugged termination ensures


that the connections are made
simultaniously. Failure to attached the
cables this this way may cause damage
RxTx -
to the controller.

RxTx +

GND
RxTx -

RxTx +

GND

Panel Side

EasiCool Technical Manual 7535768 V1.12.0_04_2018 37


EasiCool™ Precision Air Conditioning
Humidifier Bottle Information

Limit Values for the supply water with Medium to High conductivity in an immersed electrode humidifier.

Min Max
Hydrogen ions pH 7 8.5
Specific conductivity at 20°C σR, 20°C μS/cm 300 1250
Total dissolved solids TDS mg/l (1) (1)
Dry residue at 180°C R180 mg/l (1) (1)
Installation

Total hardness TH mg/l CaCO3 100(2) 400


Temporary hardness mg/l CaCO3 60(3) 300
Iron + Manganese mg/l Fe + Mn 0 0.2
Chlorides ppm- Cl 0 30
Silica mg/l SiO2 0 20
Residual chlorine mg/l Cl 0 0.2
Calcium sulphate mg/l CaSO4 0 100
Metallic impurities mg/l 0 0
Solvents, diluents, soaps, lubricants mg/l 0 0

(1) Values depending on specific conductivity; in general: TDS σ 0.93 * σ20; R180 ≅ 0.65 * σ20
(2) not lower than 200% of the chloride content in mg/l of Cl-
(3) not lower than 300% of the chloride content in mg/l of Cl-

Limit Values for the supply water with Medium to Low conductivity in an immersed electrode humidifier.

Min Max

Hydrogen ions pH 7 8.5


Specific conductivity at 20°C σR, 20°C μS/cm 125 500
Total dissolved solids TDS mg/l (1) (1)
Dry residue at 180°C R180 mg/l (1) (1)
Total hardness TH mg/l CaCO3 50(2) 250
Temporary hardness mg/l CaCO3 30(3) 150
Iron + Manganese mg/l Fe + Mn 0 0.2
Chlorides ppm- Cl 0 20
Silica mg/l SiO2 0 20
Residual chlorine mg/l Cl 0 0.2
Calcium sulphate mg/l CaSO4 0 60
Metallic impurities mg/l 0 0
Solvents, diluents, soaps, lubricants mg/l 0 0
(1) Values depending on specific conductivity; in general: TDS σ 0.93 * σ20; R180 ≅ 0.65 * σ20

(2) not lower than 200% of the chloride content in mg/l of Cl-

(3) not lower than 300% of the chloride content in mg/l of Cl-

Warning: no relation can be demonstrated between water hardness and conductivity.


CAUTION

Do not treat water with softeners!


IMPORTANT This could cause corrosion of the electrodes or the formation of foam, leading to potential
operating problems or failures.
The water supply should conform to Local Water Regulations and within the following guidelines:
Supply water pressure between 1.0 barg to 8.0 barg, > 8.0 bar a pressure reducing valve should
CAUTION be fitted.
A minimum flow rate of 1.21 l/min is required.
The humidifier inlet is fitted with a braided flexible hose, having 3/4” BSPF connection.

Ensure the union between the humidifier assembly and supply hose is fully tightened. Any
IMPORTANT
looseness, misalignment or damage to the union can lead to water leakage.

It is recommended that a shut off valve and a mechanical strainer be fitted to the water supply prior
CAUTION
to the humidifier assembly.

38 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Notes

Installation

EasiCool Technical Manual 7535768 V1.12.0_04_2018 39


EasiCool™ Precision Air Conditioning

Technical Data
Operating Limits
Indoor Air Temperature +18°C to +28°C
Indoor RH% +40% to +55% (Based upon 24°C Dry Bulb)
Water Entering Temperature +5°C to +10°C
Water Leaving Temperature +10°C to +16°C

ir)
yA
g Dr
(J/
ion
rat
atu
ts a
lpy
Technical

tha
En

25
)
(°C
re

Moisture Content kg/kg Dry Air


0%
tu

%
10
ra

ity
90

%
pe

id
80

um
%
m

H
70

20
Te

e
iv
%

at
60
lb

el
R
Bu

%
50
et
W
DF

%
15 40

Moisture Content
Operating Band
10

2 0%
5
0

10%

0 5 10 15 20 25 30 35 40

18 28
Dry Bulb Temperature (°C)

● Nominal Design Operating Condition 24°C Dry Bulb 45% RH

Fan Power Input (Fan Gain) must be added to the room load to establish full gross cooling
capacity requirements.
IMPORTANT
Fan Power Input can be found in the mechanical data sections.
Chilled Water

Fan Power Input is taken at the operating conditions based on 25Pa ESP.

40 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow


Performance Data

Cooling Capacity (1) Chilled Water Inlet/Outlet °C


Air On 5/10°C 7/12°C 8/14°C 10/16°C
(DB°C/%RH) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
22/50 8.5 6.9 6.7 6.0 5.1 5.1 4.1 4.1
DF6CW-
24/45 9.8 8.1 8.0 7.1 6.3 6.3 5.3 5.3
EZRE
26/40 11.1 9.4 8.9 8.4 7.6 7.6 6.6 6.6
22/50 10.6 8.9 7.7 7.7 6.6 6.6 5.3 5.3
DF8CW-
24/45 12.3 10.5 9.2 9.2 8.1 8.1 6.8 6.8
EZRE
26/40 13.9 12.2 10.9 10.9 9.8 9.8 8.4 8.4
22/50 12.4 10.8 9.3 9.3 7.9 7.9 6.3 6.3
DF10CW-
24/45 14.6 12.9 11.1 11.1 9.8 9.8 8.1 8.1

Technical
EZRE
26/40 16.4 14.7 13.1 13.1 11.7 11.7 10.2 10.2
22/50 16.2 13.0 12.4 11.3 9.7 9.7 7.7 7.7
DF13CW-
24/45 18.7 15.2 14.8 13.5 12.0 12.0 10.1 10.1
EZRE
26/40 21.2 17.6 17.2 15.8 14.4 14.4 12.4 12.4
22/50 18.5 15.2 14.0 14.0 11.3 11.3 9.0 9.0
DF15CW-
24/45 21.4 17.7 17.5 15.6 13.9 13.9 11.7 11.7
EZRE
26/40 24.3 20.5 19.4 18.4 16.7 16.7 14.4 14.4

DF
22/50 20.7 17.2 15.0 15.0 12.9 12.9 10.2 10.2
DF17CW-
24/45 23.9 20.1 19.6 17.7 15.8 15.8 13.2 13.2
EZRE
26/40 27.2 23.3 21.9 21.1 19.0 19.0 16.4 16.4
22/50 24.2 19.5 18.5 17.0 14.7 14.7 11.7 11.7
DF20CW-
24/45 28.0 22.6 22.1 20.2 18.0 18.0 15.1 15.1
EZRE
26/40 31.8 26.3 25.7 23.7 21.5 21.5 18.7 18.7
22/50 26.0 21.3 20.5 18.5 15.9 15.9 12.7 12.7
DF22CW-
24/45 30.1 24.9 24.6 22.0 19.6 19.6 16.4 16.4
EZRE
26/40 34.2 29.0 27.5 26.1 23.6 23.6 20.3 20.3
22/50 29.2 24.4 21.3 21.3 18.1 18.1 14.4 14.4
DF26CW-
24/45 33.8 28.6 27.8 25.1 22.3 22.3 18.7 18.7
EZRE
26/40 38.5 33.2 30.7 29.9 26.9 26.9 23.2 23.2

TC = Total Cooling SC = Sensible Cooling


(1) All data quoted is gross.
(2) Deduct fan motor gain for nett duties, refer to Mechanical Data.
(3)
Chilled Water

Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors.
(4) Refer to Waterside Pressure Drop (kPa).

Operating Limits
Indoor Air Temperature +18°C to +28°C
Indoor RH% +40% to +55% (based upon 24°C Dry Bulb)
Water Entering Temperature +5°C to +10°C
Water Leaving Temperature +10°C to +16°C

(1) Conditions quoted at 100% Water.


(2) For conditions outside those quoted, please refer to Airedale.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 41


EasiCool™ Precision Air Conditioning

Technical Data Downflow


Performance Data

Cooling Capacity (1) Chilled Water Inlet/Outlet °C


Air On 5/10°C 7/12°C 8/14°C 10/16°C
(DB°C/%RH) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)
22/50 37.8 30.2 29.1 26.3 23.2 23.2 18.7 18.7
DF28CW-
24/45 43.5 35.1 34.5 31.1 28.1 28.1 23.6 23.6
EZRE
26/40 49.2 40.6 39.8 36.4 33.5 33.5 29.1 29.1
22/50 42.3 34.1 32.4 29.8 26.1 26.1 21.1 21.1
DF31CW-
24/45 48.6 39.8 38.4 35.3 31.8 31.8 26.8 26.8
EZRE
26/40 55.1 46.1 44.6 41.7 37.9 37.9 32.8 32.8
22/50 49.4 40.5 39.1 35.1 30.6 30.6 24.5 24.5
DF35CW-
24/45 57.0 47.2 44.8 42.1 37.4 37.4 31.3 31.3
Technical

EZRE
26/40 64.8 54.9 52.2 49.5 44.8 44.8 38.7 38.7
22/50 53.6 44.4 42.9 38.9 33.5 33.5 26.8 26.8
DF40CW-
24/45 61.8 51.9 50.8 45.8 40.9 40.9 34.3 34.3
EZRE
26/40 70.3 60.2 56.4 54.3 49.1 49.1 42.4 42.4
22/50 58.9 47.1 45.1 41.0 35.7 35.7 28.6 28.6
DF45CW-
24/45 67.9 54.8 53.6 48.5 43.6 43.6 36.6 36.6
EZRE
26/40 77.7 68.2 61.5 61.5 55.1 55.1 47.4 47.4
DF

22/50 58.5 50.1 43.4 43.4 36.8 36.8 29.1 29.1


DF50CW-
24/45 68.1 58.6 51.9 51.9 45.6 45.6 37.9 37.9
EZRE
26/40 77.0 63.7 62.0 56.7 52.3 52.3 45.2 45.2
22/50 65.1 53.1 45.9 45.9 39.5 39.5 31.2 31.2
DF55CW-
24/45 75.4 62.0 59.0 55.1 48.6 48.6 40.5 40.5
EZRE
26/40 85.0 71.6 64.8 64.8 58.6 58.6 50.4 50.4
22/50 69.6 57.3 49.5 49.5 42.5 42.5 33.6 33.6
DF60CW-
24/45 80.7 66.9 59.2 59.2 52.4 52.4 43.8 43.8
EZRE
26/40 90.3 77.3 70.0 70.0 63.1 63.1 54.4 54.4

TC = Total Cooling SC = Sensible Cooling


(1) All data quoted is gross.
(2) Deduct fan motor gain for nett duties, refer to Mechanical Data.
(3) Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors.
(4) Refer to Waterside Pressure Drop (kPa).

Operating Limits
Chilled Water

Indoor Air Temperature +18°C to +28°C


Indoor RH% +40% to +55% (based upon 24°C Dry Bulb)
Water Entering Temperature +5°C to +10°C
Water Leaving Temperature +10°C to +16°C

(1) Conditions quoted at 100% Water.


(2) For conditions outside those quoted, please refer to Airedale.

42 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow


Noise Data
Sound Overall Frequency (Hz) dB
Measurement dB(A) 63 125 250 500 1000 2000 4000 8000
DA 71 65 69 67 67 67 66 58 54
RA 62 68 68 66 59 54 51 49 39
DF6CW
CB 57 64 66 58 54 51 47 43 37
S @ 3m 43 50 51 43 40 36 32 29 23
DA 77 70 74 73 72 72 71 64 59
RA 68 73 74 72 65 59 56 54 44
DF8CW
CB 63 70 71 63 60 56 52 49 43
S @ 3m 48 55 57 49 45 41 37 34 28
DA 80 73 77 76 75 75 74 67 62
RA 71 76 77 75 68 62 59 57 47
DF10CW
CB 66 73 74 66 63 59 55 52 46

Technical
S @ 3m 51 58 60 52 48 44 40 37 31
DA 77 71 74 72 72 72 71 64 59
RA 67 73 74 72 65 59 56 54 44
DF13CW
CB 62 70 71 63 60 56 52 48 42
S @ 3m 48 56 57 49 45 41 37 34 28
DA 73 70 75 72 69 68 67 62 57
RA 66 73 74 71 62 55 52 53 42
DF15CW

DF
CB 61 70 72 63 57 52 48 47 40
S @ 3m 46 55 57 48 42 37 33 32 26
DA 77 74 78 76 73 72 70 66 61
RA 70 77 78 75 66 59 55 56 46
DF17CW
CB 65 73 76 67 60 56 51 50 44
S @ 3m 50 59 61 52 46 41 37 36 30
DA 81 74 78 77 76 77 75 68 63
RA 72 77 78 76 69 63 60 59 48
DF20CW
CB 67 74 76 68 64 60 56 53 47
S @ 3m 52 59 61 53 49 46 41 38 32
DA 81 74 78 77 76 77 75 68 63
RA 72 77 78 76 69 63 60 59 48
DF22CW
CB 67 74 76 68 64 60 56 53 47
S @ 3m 52 59 61 53 49 46 41 38 32
DA 85 79 83 81 80 81 79 72 67
RA 76 81 82 80 73 67 64 63 52
DF26CW
CB 71 78 80 72 68 64 60 57 51
S @ 3m 56 64 65 57 54 50 46 42 36
Chilled Water

Key:
DA = Discharge Air Sound Power
RA = Return Air Sound Power
CB = Case Breakout Sound Power
S @ 3m = Sound Pressure at 3m

(1) dB(A) is the overall sound level, measured on the A scale.


(2) All sound data measured at nominal conditions.

The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false
floor (Base return air only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values
may vary to those stated, typically increasing by 3dB for each side added. Values stated do not include for room reverberation
conditions.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 43


EasiCool™ Precision Air Conditioning

Technical Data Downflow


Noise Data
Sound Overall Frequency (Hz) dB
Measurement dB(A) 63 125 250 500 1000 2000 4000 8000
DA 87 77 80 79 81 81 82 79 76
RA 68 77 71 64 66 63 57 56 47
DF28CW
CB 69 78 70 63 67 66 59 56 48
S @ 3m 55 63 56 49 52 51 45 42 33
DA 91 78 84 83 85 84 85 83 80
RA 71 77 75 67 69 66 60 60 52
DF31CW
CB 73 78 74 67 70 69 62 60 52
S @ 3m 58 64 59 52 55 55 48 46 38
DA 90 77 83 82 87 83 84 82 79
RA 71 76 74 66 70 64 59 59 51
DF35CW
Technical

CB 72 77 73 66 71 67 61 59 51
S @ 3m 58 62 58 51 57 53 47 45 37
DA 92 80 86 85 89 86 86 85 81
RA 73 78 76 68 73 67 61 62 53
DF40CW
CB 74 79 75 68 74 70 63 62 54
S @ 3m 60 64 61 54 59 55 49 47 40
DA 92 80 86 85 89 86 86 85 81
RA 73 78 76 68 73 67 61 62 53
DF45CW
DF

CB 74 79 75 68 74 70 63 62 54
S @ 3m 60 64 61 54 59 55 49 47 40
DA 89 78 84 86 82 83 84 81 76
RA 69 76 75 70 66 64 59 57 48
DF50CW
CB 71 77 74 69 67 67 61 58 49
S @ 3m 56 63 59 55 53 53 46 43 34
DA 89 78 84 86 82 83 84 81 76
RA 69 76 75 70 66 64 59 57 48
DF55CW
CB 71 77 74 69 67 67 61 58 49
S @ 3m 56 63 59 55 53 53 46 43 34
DA 91 80 85 89 84 85 86 83 79
RA 71 78 76 73 68 66 61 60 51
DF60CW
CB 73 79 75 73 69 69 63 60 51
S @ 3m 58 65 60 58 55 54 49 45 37

Key:
DA = Discharge Air Sound Power
Chilled Water

RA = Return Air Sound Power


CB = Case Breakout Sound Power
S @ 3m = Sound Pressure at 3m

(1) dB(A) is the overall sound level, measured on the A scale.


(2) All sound data measured at nominal conditions.

The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false floor (Base return air
only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values may vary to those stated, typically
increasing by 3dB for each side added. Values stated do not include for room reverberation conditions.

44 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical
DF
Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 45


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF6CW


Mechanical Data
DF6CW-EZRE-0 DF6CW-EZRE-1 DF6CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 7.6 7.6 7.6
Fan Power Input (Fan Gain) (2) kW 0.25 1.50 1.50
Dimensions
WxDxH mm 670 x 670 x 1940 670 x 670 x 1940 670 x 670 x 1940
Weight
Machine (3) kg 164 165 164
Panels: Galvanised Sheet Steel, Epoxy Baked
Construction
Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Technical

Fan Transmission Type Direct Drive


Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Maximum ESP Pa 328 196 196
Nominal Airflow m³/s 0.55 0.55 0.55
Connections
Inlet/Outlet mm 22 22 22
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 1 1 1
DF

OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1335 / 2215 1335 / 2215 1335 / 2215
Maximum ESP Pa 475 475 475
Fan Power Input (Fan Gain) (2) kW 0.23 0.23 0.23
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 6.5 6.5 6.5
Water Flow (Nominal) l/s 0.14 0.14 0.14
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 3/4 3/4 3/4
Chilled Water

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

46 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF6CW


Electrical Data

DF6CW-EZRE-0 DF6CW-EZRE-1 DF6CW-EZRE-2

Unit Data Full Function - CW (1)


Nominal Run Amps A 18.9 20.4 31.2

Maximum Start Amps A 18.9 20.4 31.2

Recommended Mains Fuse Size A 25 32 40

Unit Data Cooling Only - CW


Nominal Run Amps (2) A 4.8 5.6 5.6

Maximum Start Amps A 4.8 14 14

Recommended Mains Fuse Size A 16 16 16

Max Mains Incoming Cable Size mm² 6 6 35

Technical
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ

Control Circuit VAC 24 24 24

Evaporator Fan - EC Motor Per Fan


Electrical Input Power (3) kW 1.1 1 1

Full Load Amps A 4.8 5.6 5.6

Locked Rotor Amps A 4.8 14 14

OPTIONAL EXTRAS

DF
Electric Heating
Stage of Reheat 1 1 1

Number of Elements 3 3 3

Rating kW 7.5 7.5 7.5

Curent per Phase A 10.83 11.4 19.68

Humidifier
Capacity kg/hr 3 3 3

Rating kW 2.25 2.25 2.25

Full Load Amps A 3.25 3.42 5.9

Evaporator Fan Options


Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A 1.6 1.6

Full Load Amps A N/A 6.8 6.8

Locked Rotor Amps A N/A 17 17

Standard Size Motor - EC Motor - Per Fan


Electrical Input Power (3) kW 0.94 0.94 0.94
1.5 1.5 1.5
Chilled Water

Full Load Amps A

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 47


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF8CW


Mechanical Data
DF8CW-EZRE-0 DF8CW-EZRE-1 DF8CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 9.7 9.2 9.2
Fan Power Input (Fan Gain) (2) kW 0.54 1.60 1.60
Dimensions
WxDxH mm 670 x 670 x 1940 670 x 670 x 1940 670 x 670 x 1940
Weight
Machine (3) kg 167 165 167
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 1 1
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 233 140 140
Nominal Airflow m³/s 0.75 0.75 0.75
Connections
Inlet/Outlet mm 22 22 22
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 1 1 1
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
DF

Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1705 / 2215 1705 / 2215 1705 / 2215
Maximum ESP Pa 295 295 295
Fan Power Input (Fan Gain) (2) kW 0.43 0.43 0.43
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 7.5 7.5 7.5
Water Flow (Nominal) l/s 0.17 0.17 0.17
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 3/4 3/4 3/4

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

48 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF8CW


Electrical Data

DF8CW-EZRE-0 DF8CW-EZRE-1 DF8CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 18.9 23.3 34.1
Maximum Start Amps A 18.9 23.3 34.1
Recommended Mains Fuse Size A 25 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 8.5 8.5
Maximum Start Amps A 4.8 21.2 21.2
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 1.6 1.6
Full Load Amps A 4.8 8.5 8.5

Technical
Locked Rotor Amps A 4.8 21.2 21.2
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25

DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A 2.2 2.2
Full Load Amps A N/A 9.1 9.1
Locked Rotor Amps A N/A 22.8 22.75
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 49


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF10CW


Mechanical Data
DF10CW-EZRE-0 DF10CW-EZRE-1 DF10CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 11.7 11.2 11.2
Fan Power Input (Fan Gain) (2) kW 0.77 2.20 2.20
Dimensions
WxDxH mm 670 x 670 x 1940 670 x 670 x 1940 670 x 670 x 1940
Weight
Machine (3) kg 163 168 163
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 1 1
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 274 118 118
Nominal Airflow m³/s 0.95 0.95 0.95
Connections
Inlet/Outlet mm 22 22 22
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 1 1 1
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
DF

Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2145 / 2215 2145 / 2215 2145 / 2215
Maximum ESP Pa 50 50 50
Fan Power Input (Fan Gain) (2) kW 0.77 0.77 0.77
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 8.4 8.4 8.4
Water Flow (Nominal) l/s 0.19 0.19 0.19
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 3/4 3/4 3/4

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

50 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF10CW


Electrical Data

DF10CW-EZRE-0 DF10CW-EZRE-1 DF10CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 18.9 24.4 35.2
Maximum Start Amps A 18.9 24.4 35.2
Recommended Mains Fuse Size A 25 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 9.6
Maximum Start Amps A 4.8 24 24
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25

DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 51


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF13CW


Mechanical Data
DF13CW-EZRE-0 DF13CW-EZRE-1 DF13CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 14.7 14.7 14.7
Fan Power Input (Fan Gain) (2) kW 0.62 2.20 2.20
Dimensions
WxDxH mm 990 x 670 x 1940 990 x 670 x 1940 990 x 670 x 1940
Weight
Machine (3) kg 190 195 190
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 1 1
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 443 294 294
Nominal Airflow m³/s 1.00 1.00 1.00
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 2 2 2
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
DF

Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1105 / 1560 1105 / 1560 1105 / 1560
Maximum ESP Pa 310 310 310
Fan Power Input (Fan Gain) (2) kW 0.37 0.37 0.37
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 11.5 11.5 11.5
Water Flow (Nominal) l/s 0.26 0.26 0.26
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

52 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF13CW


Electrical Data

DF13CW-EZRE-0 DF13CW-EZRE-1 DF13CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 18.9 24.4 35.2
Maximum Start Amps A 18.9 24.4 35.2
Recommended Mains Fuse Size A 25 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 9.6
Maximum Start Amps A 4.8 24 24
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1,1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25

DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 53


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF15CW


Mechanical Data
DF15CW-EZRE-0 DF15CW-EZRE-1 DF15CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 16.6 16.6 16.6
Fan Power Input (Fan Gain) (2) kW 0.67 1.90 1.90
Dimensions
WxDxH mm 990 x 670 x 1940 990 x 670 x 1940 990 x 670 x 1940
Weight
Machine (3) kg 204 200 204
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 1 1
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 324 120 120
Nominal Airflow m³/s 1.20 1.20 1.20
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 2 2 2
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
DF

Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1310 / 1560 1310 / 1560 1310 / 1560
Maximum ESP Pa 195 195 195
Fan Power Input (Fan Gain) (2) kW 0.56 0.56 0.56
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (3) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 12.5 12.5 12.5
Water Flow (Nominal) l/s 0.28 0.28 0.28
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

54 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF15CW


Electrical Data

DF15CW-EZRE-0 DF15CW-EZRE-1 DF15CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 21.3 22.6 33.4
Maximum Start Amps A 21.3 22.6 33.4
Recommended Mains Fuse Size A 32 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 7.2 7.8 7.8
Maximum Start Amps A 7.2 19.5 19.5
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.6 1.9 1.9
Full Load Amps A 7.2 7.8 7.8

Technical
Locked Rotor Amps A 7.2 19.5 19.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25

DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 55


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF17CW


Mechanical Data
DF17CW-EZRE-0 DF17CW-EZRE-1 DF17CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 18.1 18.1 18.1
Fan Power Input (Fan Gain) (2) kW 1.05 1.90 1.90
Dimensions
WxDxH mm 990 x 670 x 1940 990 x 670 x 1940 990 x 670 x 1940
Weight
Machine (3) kg 204 200 204
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 1 1
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 245 34 34
Nominal Airflow m³/s 1.40 1.40 1.40
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 2 2 2
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
DF

Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1515 / 1560 1515 / 1560 1515 / 1560
Maximum ESP Pa 45 45 45
Fan Power Input (Fan Gain) (2) kW 0.82 0.82 0.82
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (3) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 13.3 13.3 13.3
Water Flow (Nominal) l/s 0.3 0.3 0.3
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

56 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF17CW


Electrical Data

DF17CW-EZRE-0 DF17CW-EZRE-1 DF17CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 21.3 22.6 33.4
Maximum Start Amps A 21.3 22.6 33.4
Recommended Mains Fuse Size A 32 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 7.2 7.8 7.8
Maximum Start Amps A 7.2 19.5 19.5
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.6 1.9 1.9
Full Load Amps A 7.2 7.8 7.8

Technical
Locked Rotor Amps A 7.2 19.5 19.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25

DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 57


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF20CW


Mechanical Data
DF20CW-EZRE-0 DF20CW-EZRE-1 DF20CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 21.8 21.8 21.8
Fan Power Input (Fan Gain) (2) kW 0.80 2.20 2.20
Dimensions
WxDxH mm 1310 x 670 x 1940 1310 x 670 x 1940 1310 x 670 x 1940
Weight
Machine (3) kg 242 252 242
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 2 2 2
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 404 260 260
Nominal Airflow m³/s 1.50 1.50 1.50
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 15 15 15
DF

Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1745 / 2165 1745 / 2165 1745 / 2165
Maximum ESP Pa 450 450 450
Fan Power Input (Fan Gain) (2) kW 0.48 0.48 0.48
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 16.1 16.1 16.1
Water Flow (Nominal) l/s 0.36 0.36 0.36
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water

(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

58 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF20CW


Electrical Data

DF20CW-EZRE-0 DF20CW-EZRE-1 DF20CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 29.7 35.8 64.5
Maximum Start Amps A 29.7 35.8 64.5
Recommended Mains Fuse Size A 40 50 100
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 19.2
Maximum Start Amps A 4.8 24 48
Recommended Mains Fuse Size A 16 16 25
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25

DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 59


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF22CW


Mechanical Data
DF22CW-EZRE-0 DF22CW-EZRE-1 DF22CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 23.4 23.4 23.4
Fan Power Input (Fan Gain) (2) kW 1.16 2.20 2.20
Dimensions
WxDxH mm 1310 x 670 x 1940 1310 x 670 x 1940 1310 x 670 x 1940
Weight
Machine (3) kg 242 252 242
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 2 2 2
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 342 194 194
Nominal Airflow m³/s 1.70 1.70 1.70
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 15 15 15
DF

Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2055 / 2165 2055 / 2165 2055 / 2165
Maximum ESP Pa 145 145 145
Fan Power Input (Fan Gain) (2) kW 0.79 0.79 0.79
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 16.1 16.1 16.1
Water Flow (Nominal) l/s 0.36 0.36 0.36
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water

(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

60 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF22CW


Electrical Data

DF22CW-EZRE-0 DF22CW-EZRE-1 DF22CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 29.7 35.8 64.5
Maximum Start Amps A 29.7 35.8 64.5
Recommended Mains Fuse Size A 40 50 100
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 19.2
Maximum Start Amps A 4.8 24 48
Recommended Mains Fuse Size A 16 16 25
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25

DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 61


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF26CW


Mechanical Data
DF26CW-EZRE-0 DF26CW-EZRE-1 DF26CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 25.6 25.6 25.6
Fan Power Input (Fan Gain) (2) kW 1.86 2.20 2.20
Dimensions
WxDxH mm 1310 x 670 x 1940 1310 x 670 x 1940 1310 x 670 x 1940
Weight
Machine (3) kg 242 252 242
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 2 2 2
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 192 43 43
Nominal Airflow m³/s 2.00 2.00 2.00
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 15 15 15
DF

Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 1 1 1
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2055 / 2165 2055 / 2165 2055 / 2165
Maximum ESP Pa 145 145 145
Fan Power Input (Fan Gain) (2) kW 0.79 0.79 0.79
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 16.6 16.6 16.6
Water Flow (Nominal) l/s 0.37 0.37 0.37
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water

(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

62 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF26CW


Electrical Data

DF26CW-EZRE-0 DF26CW-EZRE-1 DF26CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 29.7 35.8 64.5
Maximum Start Amps A 29.7 35.8 64.5
Recommended Mains Fuse Size A 40 50 100
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 19.2
Maximum Start Amps A 4.8 24 48
Recommended Mains Fuse Size A 16 16 25
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25

DF
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 63


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF28CW


Mechanical Data
DF28CW-EZRE-0 DF28CW-EZRE-1 DF28CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 34.2 34.2 34.2
Fan Power Input (Fan Gain) (2) kW 2.60 2.60 2.60
Dimensions
WxDxH mm 1460 x 750 x 1940 1460 x 750 x 1940 1460 x 750 x 1940
Weight
Machine (3) kg 351 351 351
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 2.2 2.2 2.2
Technical

Speed @ 25Pa / Maximum ESP rpm 871 / 909 871 / 909 871 / 909
Maximum ESP Pa 75 75 75
Nominal Airflow m³/s 2.40 2.40 2.40
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF

Humidifier
Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 3.0 / 4.0 3.0 / 4.0 3.0 / 4.0
Speed @ Maximum ESP rpm 1144 / 1439 1144 / 1439 1144 / 1439
Maximum ESP Pa 362 / 722 362 / 722 362 / 722
Fan Power Input (Fan Gain) (2) kW 3.5 / 4.6 3.5 / 4.6 3.5 / 4.6
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1570 / 2165 1570 / 2165 1570 / 2165
Maximum ESP Pa 595 595 595
Fan Power Input (Fan Gain) (2) kW 1.70 1.70 1.70
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Chilled Water

Quantity x Motor Size (4) kW N/A N/A N/A


Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 21.3 21.3 21.3
Water Flow (Nominal) l/s 0.48 0.48 0.48
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

64 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF28CW


Electrical Data

DF28CW-EZRE-0 DF28CW-EZRE-1 DF28CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 46.3 48.6 83.7
Maximum Start Amps A 46.3 48.6 83.7
Recommended Mains Fuse Size A 63 63 125
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 5.1 5.3 8.9
Maximum Start Amps A 33 34.3 59.1
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 35 35 50
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 2.6 2.6 2.6
Full Load Amps A 4.64 4.83 8.37

Technical
Locked Rotor Amps A 32.5 33.81 58.59
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6

DF
Full Load Amps A 8.66 9.12 15.75
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 65


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF31CW


Mechanical Data
DF31CW-EZRE-0 DF31CW-EZRE-1 DF31CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 38.0 38.0 38.0
Fan Power Input (Fan Gain) (2) kW 4.60 4.60 4.60
Dimensions
WxDxH mm 1460 x 750 x 1940 1460 x 750 x 1940 1460 x 750 x 1940
Weight
Machine (3) kg 354 354 354
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 4.0 4.0 4.0
Technical

Speed @ 25Pa / Maximum ESP rpm 1008 / 1171 1008 / 1171 1008 / 1171
Maximum ESP Pa 265 265 265
Nominal Airflow m³/s 2.80 2.80 2.80
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF

Humidifier
Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity N/A N/A N/A
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1775 / 2165 1775 / 2165 1775 / 2165
Maximum ESP Pa 390 390 390
Fan Power Input (Fan Gain) (2) kW 2.50 2.50 2.50
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water

Capacity Gross (5) kW 22.7 22.7 22.7


Water Flow (Nominal) l/s 0.51 0.51 0.51
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

66 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF31CW


Electrical Data

DF31CW-EZRE-0 DF31CW-EZRE-1 DF31CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 49.8 52.1 89.7
Maximum Start Amps A 61.4 58.9 101.7
Recommended Mains Fuse Size A 63 80 125
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 8.6 8.8 15
Maximum Start Amps A 61.4 58.9 101.7
Recommended Mains Fuse Size A 16 16 20
Max Mains Incoming Cable Size mm² 35 35 50
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 4.6 4.6 4.6
Full Load Amps A 8.12 8.34 14.45

Technical
Locked Rotor Amps A 60.9 58.38 101.15
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6

DF
Full Load Amps A 8.66 9.12 15.75
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 67


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF35CW


Mechanical Data
DF35CW-EZRE-0 DF35CW-EZRE-1 DF35CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 43.7 43.7 43.7
Fan Power Input (Fan Gain) (2) kW 4.60 4.60 4.60
Dimensions
Dimensions - W x D x H mm 1835 x 750 x 1940 1835 x 750 x 1940 1835 x 750 x 1940
Weight
Machine (3) kg 410 410 410
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 4.0 4.0 4.0
Technical

Speed @ 25Pa / Maximum ESP rpm 980 / 1078 980 / 1078 980 / 1078
Maximum ESP Pa 165 165 165
Nominal Airflow m³/s 3.30 3.30 3.30
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF

Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 5.50 5.50 5.50
Speed @ Maximum ESP rpm 1196 1196 1196
Maximum ESP Pa 322 322 322
Fan Power Input (Fan Gain) (2) kW 6.30 6.30 6.30
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1895 / 2165 1895 / 2165 1895 / 2165
Maximum ESP Pa 285 285 285
Fan Power Input (Fan Gain) (2) kW 2.78 2.78 2.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water

Capacity Gross (5) kW 30.0 30.0 30.0


Water Flow (Nominal) l/s 0.67 0.67 0.67
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

68 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF35CW


Electrical Data

DF35CW-EZRE-0 DF35CW-EZRE-1 DF35CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 57.3 60.1 103.5
Maximum Start Amps A 61.4 60.1 103.5
Recommended Mains Fuse Size A 80 80 160
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 8.6 8.8 15
Maximum Start Amps A 61.4 58.9 101.7
Recommended Mains Fuse Size A 16 16 20
Max Mains Incoming Cable Size mm² 35 35 95
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 4.6 4.6 4.6
Full Load Amps A 8.12 8.34 14.45

Technical
Locked Rotor Amps A 60.9 58.38 101.15
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25

DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 6.3 6.3 6.3
Full Load Amps A 10.9 10.9 25.63
Locked Rotor Amps A 69.8 69.8 197.35
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 69


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF40CW


Mechanical Data
DF40CW-EZRE-0 DF40CW-EZRE-1 DF40CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 47.6 47.6 47.6
Fan Power Input (Fan Gain) (2) kW 6.30 6.30 6.30
Dimensions
WxDxH mm 1835 x 750 x 1940 1835 x 750 x 1940 1835 x 750 x 1940
Weight
Machine (3) kg 431 431 431
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 5.50 5.50 5.50
Technical

Speed @ 25Pa / Maximum ESP rpm 1094 / 1186 1094 / 1186 1094 / 1186
Maximum ESP Pa 175 175 175
Nominal Airflow m³/s 3.70 3.70 3.70
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF

Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2135 / 2165 2135 / 2165 2135 / 2165
Maximum ESP Pa 70 70 70
Fan Power Input (Fan Gain) (2) kW 3.78 3.78 3.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (4) kW 31.5 31.5 31.5
Water Flow (Nominal) l/s 0.70 0.70 0.70
Chilled Water

LPHW Connection Sizes mm 22 22 22


Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

70 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF40CW


Electrical Data

DF40CW-EZRE-0 DF40CW-EZRE-1 DF40CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 60.1 63.6 109.5
Maximum Start Amps A 70.3 91.7 158
Recommended Mains Fuse Size A 80 80 160
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 11.4 12.3 21
Maximum Start Amps A 70.3 91.7 158
Recommended Mains Fuse Size A 16 16 32
Max Mains Incoming Cable Size mm² 35 35 95
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 6.3 5.5 5.5
Full Load Amps A 10.9 11.84 20.46

Technical
Locked Rotor Amps A 69.8 91.2 157.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25

DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 71


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF45CW


Mechanical Data
DF45CW-EZRE-0 DF45CW-EZRE-1 DF45CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 50.6 50.6 50.6
Fan Power Input (Fan Gain) (2) kW 5.50 5.50 5.50
Dimensions
WxDxH mm 1835 x 750 x 1940 1835 x 750 x 1940 1835 x 750 x 1940
Weight
Machine (3) kg 442 442 442
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 5.50 5.50 5.50
Technical

Speed @ 25Pa / Maximum ESP rpm 1094 / 1186 1094 / 1186 1094 / 1186
Maximum ESP Pa 175 175 175
Nominal Airflow m³/s 3.70 3.70 3.70
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 20 20 20
DF

Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (3) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2135 / 2165 2135 / 2165 2135 / 2165
Maximum ESP Pa 70 70 70
Fan Power Input (Fan Gain) (2) kW 3.78 3.78 3.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (4) kW 31.5 31.5 31.5
Water Flow (Nominal) l/s 0.70 0.70 0.70
Chilled Water

LPHW Connection Sizes mm 22 22 22


Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

72 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF45CW


Electrical Data

DF45CW-EZRE-0 DF45CW-EZRE-1 DF45CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 60.1 63.6 109.5
Maximum Start Amps A 70.3 91.7 158
Recommended Mains Fuse Size A 80 80 160
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 11.4 12.3 21
Maximum Start Amps A 70.3 91.7 158
Recommended Mains Fuse Size A 16 16 32
Max Mains Incoming Cable Size mm² 35 35 95
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 6.3 5.5 5.5
Full Load Amps A 10.9 11.84 20.46

Technical
Locked Rotor Amps A 69.8 91.2 157.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 8 8 8
Rating kW 20 20 20
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25

DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 73


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF50CW


Mechanical Data
DF50CW-EZRE-0 DF50CW-EZRE-1 DF50CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 51.3 51.3 51.3
Fan Power Input (Fan Gain) (2) kW 5.20 5.20 5.20
Dimensions
WxDxH mm 2170 x 750 x 1940 2170 x 750 x 1940 2170 x 750 x 1940
Weight
Machine (3) kg 486 486 486
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 2 2 2
Motor Shaft Power (4) kW 2.20 2.20 2.20
Technical

Speed @ 25Pa / Maximum ESP rpm 1167 / 1170 1167 / 1170 1167 / 1170
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 4.20 4.20 4.20
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
DF

Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW 3.0 / 4.0 3.0 / 4.0 3.0 / 4.0
Speed @ Maximum ESP rpm 1448 / 1498 1448 / 1498 1448 / 1498
Maximum ESP Pa 310 / 360 310 / 360 310 / 360
Fan Power Input (Fan Gain) (2) kW 7.0 / 9.2 7.0 / 9.2 7.0 / 9.2
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1265 / 1510 1265 / 1510 1265 / 1510
Maximum ESP Pa 320 320 320
Fan Power Input (Fan Gain) (2) kW 3.78 3.78 3.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water

Capacity Gross (5) kW 38.3 38.3 38.3


Water Flow (Nominal) l/s 0.85 0.85 0.85
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

74 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF50CW


Electrical Data

DF50CW-EZRE-0 DF50CW-EZRE-1 DF50CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 69.3 72.8 125.5
Maximum Start Amps A 69.3 72.8 125.5
Recommended Mains Fuse Size A 100 100 160
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 9.8 10.2 17.2
Maximum Start Amps A 65.5 68.1 117.7
Recommended Mains Fuse Size A 16 16 25
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 2.6 2.6 2.6
Full Load Amps A 4.64 4.83 8.37

Technical
Locked Rotor Amps A 32.5 33.81 58.59
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25

DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 75


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF55CW


Mechanical Data
DF55CW-EZRE-0 DF55CW-EZRE-1 DF55CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 58.5 58.5 58.5
Fan Power Input (Fan Gain) (2) kW 5.20 5.20 5.20
Dimensions
WxDxH mm 2170 x 750 x 1940 2170 x 750 x 1940 2170 x 750 x 1940
Weight
Machine (3) kg 499 499 499
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 2 2 2
Motor Shaft Power (4) kW 2.20 2.20 2.20
Technical

Speed @ 25Pa / Maximum ESP rpm 1167 / 1170 1167 / 1170 1167 / 1170
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 4.20 4.20 4.20
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
DF

Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW 3.0 / 4.0 3.0 / 4.0 3.0 / 4.0
Speed @ Maximum ESP rpm 1448 / 1498 1448 / 1498 1448 / 1498
Maximum ESP Pa 310 / 360 310 / 360 310 / 360
Fan Power Input (Fan Gain) (2) kW 7.0 / 9.2 7.0 / 9.2 7.0 / 9.2
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1265 / 1510 1265 / 1510 1265 / 1510
Maximum ESP Pa 320 320 320
Fan Power Input (Fan Gain) (2) kW 3.78 3.78 3.78
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water

Capacity Gross (5) kW 38.3 38.3 38.3


Water Flow (Nominal) l/s 0.85 0.85 0.85
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

76 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF55CW


Electrical Data

DF55CW-EZRE-0 DF55CW-EZRE-1 DF55CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 69.3 72.8 125.5
Maximum Start Amps A 69.3 72.8 125.5
Recommended Mains Fuse Size A 100 100 160
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 9.8 10.2 17.2
Maximum Start Amps A 65.5 68.1 117.7
Recommended Mains Fuse Size A 16 16 25
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 2.6 2.6 2.6
Full Load Amps A 4.64 4.83 8.37

Technical
Locked Rotor Amps A 32.5 33.81 58.59
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25

DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 77


EasiCool™ Precision Air Conditioning

Technical Data Downflow DF60CW


Mechanical Data
DF60CW-EZRE-0 DF60CW-EZRE-1 DF60CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 62.3 62.3 62.3
Fan Power Input (Fan Gain) (2) kW 7.00 7.00 7.00
Dimensions
WxDxH mm 2170 x 750 x 1940 2170 x 750 x 1940 2170 x 750 x 1940
Weight
Machine (3) kg 495 495 495
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 2.00 2.00 2.00
Motor Shaft Power (4) kW 3.00 3.00 3.00
Technical

Speed @ 25Pa / Maximum ESP rpm 1307 / 1311 1307 / 1311 1307 / 1311
Maximum ESP Pa 75 75 75
Nominal Airflow m³/s 4.60 4.60 4.60
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
DF

Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW 4.00 4.00 4.00
Speed @ Maximum ESP rpm 1497 1497 1497
Maximum ESP Pa 275 275 275
Fan Power Input (Fan Gain) (2) kW 9.20 9.20 9.20
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity x Motor Size 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1390 / 1510 1390 / 1510 1390 / 1510
Maximum ESP Pa 185 185 185
Fan Power Input (Fan Gain) (2) kW 4.92 4.92 4.92
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water

Capacity Gross (5) kW 39.8 39.8 39.8


Water Flow (Nominal) l/s 0.89 0.89 0.89
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

78 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow DF60CW


Electrical Data

DF60CW-EZRE-0 DF60CW-EZRE-1 DF60CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 72.4 76 131
Maximum Start Amps A 87.1 90.5 156.5
Recommended Mains Fuse Size A 100 100 200
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 12.9 13.4 22.8
Maximum Start Amps A 87.1 90.5 156.5
Recommended Mains Fuse Size A 20 20 32
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.43 11.14

Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25

DF
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 4.6 4.6 4.6
Full Load Amps A 8.12 8.12 14.45
Locked Rotor Amps A 60.9 60.9 101.15
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8

Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 79


EasiCool™ Precision Air Conditioning

Technical Data Downflow


Chilled Water Pressure Drop

DF6CW - DF26CW

300 6 - 10 13 - 17 20 - 26
Waterside Pressure Drop (kPa)

250

200

150
Technical

100

50

0
0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5
Waterflow (l/s)
DF

DF28CW - DF60CW

500 28 - 31 35 - 40 45
Waterside Pressure Drop (kPa)

400

50

300
55 - 60

200

100
Chilled Water

0
0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

Waterflow (l/s)

(1) Includes coil, 3 port valve and pipework.

(2) To calculate 3 port valve pressure drop

2
Q  Kv 
∆P valve =   where ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =  
M   36 
(3) Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors.

80 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow


Hydronic Data Low Pressure Hot Water

DF6CW - DF26CW 40

20 - 26
Waterside Pressure Drop (kPa) 35

30

25 6 - 10

20
13 - 17
15

Technical
10

0
0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50
Waterflow (l/s)

DF
DF28CW - DF60CW

80

70
Waterside Pressure Drop (kPa)

60 50-60

50

40
35-45
30

20
28-31
Chilled Water

10

0
0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Waterflow (l/s)

(1) Includes coil, 3 port valve and pipework.

(2) To calculate 3 port valve pressure drop

2
Q  Kv 
∆P valve =   where ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =  
M   36 
(3) Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 81


EasiCool™ Precision Air Conditioning

Technical Data Upflow


Performance Data
Cooling Duties: V CW

Cooling Capacity (1) Chilled Water Inlet/Outlet °C


Air On 5/10°C 7/12°C 8/14°C 10/16°C

(DB°C/%RH) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)

22/50 8.3 6.8 6.5 5.9 5.0 5.0 4.0 4.0


V6CW-EZRE 24/45 9.6 8.0 7.8 7.0 6.2 6.2 5.2 5.2
26/40 10.9 9.2 8.8 8.2 7.5 7.5 6.4 6.4
22/50 10.3 8.7 7.6 7.6 6.5 6.5 5.2 5.2
V8CW-EZRE 24/45 12.0 10.3 9.0 9.0 8.0 8.0 6.6 6.6
26/40 13.7 11.9 10.6 10.6 9.6 9.6 8.2 8.2
Technical

22/50 12.1 10.6 9.1 9.1 7.8 7.8 6.1 6.1


V10CW-EZRE 24/45 14.3 12.7 10.8 10.8 9.6 9.6 8.0 8.0
26/40 16.1 14.4 12.9 12.9 11.5 11.5 10.0 10.0
22/50 15.8 12.8 12.1 11.1 9.5 9.5 7.6 7.6
V13CW-EZRE 24/45 18.3 14.9 14.5 13.3 11.8 11.8 9.9 9.9
26/40 20.8 17.3 16.8 15.5 14.1 14.1 12.2 12.2
22/50 18.1 14.9 13.7 13.7 11.1 11.1 8.8 8.8
V15CW-EZRE 24/45 21.0 17.3 17.1 15.3 13.7 13.7 11.4 11.4
26/40 23.9 20.1 19.2 18.1 16.4 16.4 14.2 14.2
22/50 20.3 16.9 14.7 14.7 12.6 12.6 10.0 10.0
V17CW-EZRE 24/45 23.4 19.7 19.2 17.4 15.5 15.5 12.9 12.9
26/40 26.7 22.8 21.5 20.6 18.6 18.6 16.1 16.1
22/50 23.8 19.1 18.1 16.6 14.4 14.4 11.5 11.5
V20CW-EZRE 24/45 27.4 22.2 21.7 19.8 17.6 17.6 14.8 14.8
26/40 31.2 25.8 25.2 23.3 21.1 21.1 18.3 18.3
V

22/50 25.5 20.9 20.1 18.1 15.6 15.6 12.4 12.4


V22CW-EZRE 24/45 29.5 24.4 24.1 21.6 19.2 19.2 16.1 16.1
26/40 33.6 28.4 26.9 25.6 23.1 23.1 19.9 19.9
22/50 28.6 23.9 20.9 20.9 17.8 17.8 14.1 14.1
V26CW-EZRE 24/45 33.1 28.0 27.2 24.6 21.9 21.9 18.3 18.3
26/40 37.8 32.5 30.1 29.3 26.4 26.4 22.8 22.8

TC = Total Cooling SC = Sensible Cooling


(1) All data quoted is gross.
(2) Deduct fan motor gain for nett duties, refer to Mechanical Data.
(3) Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors.
Chilled Water

(4) Refer to Waterside Pressure Drop (kPa).

Operating Limits
Indoor Air Temperature +18°C to +28°C
Indoor RH% +40% to +55%
Water Entering Temperature +5°C to +10°C
Water Leaving Temperature +10°C to +16°C

(1) Conditions quoted at 100% Water.


(2) For conditions outside those quoted, please refer to Airedale.

82 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow


Performance Data
Cooling Duties: V CW

Cooling Capacity (1) Chilled Water Inlet/Outlet °C


Air On 5/10°C 7/12°C 8/14°C 10/16°C

(DB°C/%RH) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)

22/50 37.1 29.6 28.5 25.8 22.7 22.7 18.3 18.3


V28CW-EZRE 24/45 42.7 34.4 33.9 30.5 27.6 27.6 23.2 23.2
26/40 48.2 39.8 39.1 35.7 32.9 32.9 28.5 28.5
22/50 41.5 33.5 31.8 29.2 25.6 25.6 20.7 20.7
V31CW-EZRE 24/45 47.6 39.0 37.7 34.6 31.1 31.1 26.3 26.3
26/40 54.0 45.2 43.7 40.9 37.2 37.2 32.2 32.2

Technical
22/50 48.5 39.8 38.4 34.4 30.0 30.0 24.0 24.0
V35CW-EZRE 24/45 55.9 46.3 43.9 41.2 36.7 36.7 30.7 30.7
26/40 63.5 53.8 51.2 48.5 44.0 44.0 37.9 37.9
22/50 52.5 43.6 42.1 38.1 32.8 32.8 26.3 26.3
V40CW-EZRE 24/45 60.6 50.9 49.8 44.9 40.1 40.1 33.6 33.6
26/40 68.9 59.1 55.3 53.3 48.2 48.2 41.6 41.6
22/50 57.8 46.1 44.2 40.2 35.0 35.0 28.0 28.0
V45CW-EZRE 24/45 66.6 53.8 52.6 47.5 42.7 42.7 35.9 35.9
26/40 76.1 66.9 60.3 60.3 54.0 54.0 46.4 46.4
22/50 57.4 49.1 42.6 42.6 36.1 36.1 28.5 28.5
V50CW-EZRE 24/45 66.8 57.5 50.9 50.9 44.7 44.7 37.2 37.2
26/40 75.5 62.5 60.8 55.6 51.3 51.3 44.3 44.3
22/50 63.8 52.0 45.0 45.0 38.7 38.7 30.6 30.6
V55CW-EZRE 24/45 74.0 60.8 57.9 54.0 48.7 47.7 39.8 39.8
26/40 83.3 70.2 63.6 63.6 57.4 57.4 49.4 49.4

V
22/50 68.3 56.2 48.5 48.5 41.7 41.7 33.0 33.0

V60CW-EZRE 24/45 79.2 65.6 58.0 58.0 51.4 51.4 42.9 42.9

26/40 88.6 75.8 68.6 68.6 61.9 61.9 53.3 53.3

TC = Total Cooling SC = Sensible Cooling


(1) All data quoted is gross.
(2) Deduct fan motor gain for nett duties, refer to Mechanical Data.
(3) Water flow rate (l/s) = TC ÷ (4.19 x ∆T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors.
(4) Refer to Waterside Pressure Drop (kPa).

Operating Limits
Chilled Water

Indoor Air Temperature +18°C to +28°C


Indoor RH% +40% to +55%
Water Entering Temperature +5°C to +10°C
Water Leaving Temperature +10°C to +16°C

(1) Conditions quoted at 100% Water.


(2) For conditions outside those quoted, please refer to Airedale.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 83


EasiCool™ Precision Air Conditioning

Technical Data Upflow


Noise Data
Sound Overall Frequency (Hz) dB

Measurement dB(A) 63 125 250 500 1000 2000 4000 8000


DA 72 66 70 68 68 68 67 59 55
RA 53 63 64 55 49 47 42 36 26
V6CW
CB 53 63 64 55 49 47 42 36 26

S @ 3m 39 49 50 40 34 32 27 22 11
DA 78 71 75 74 73 73 72 65 60
RA 59 68 70 60 54 52 47 42 31
V8CW
CB 59 68 70 60 54 52 47 42 31

S @ 3m 44 54 55 45 40 38 32 27 17
DA 81 74 78 77 76 76 75 68 63
RA 62 71 73 63 57 55 50 45 34
V10CW
Technical

CB 62 71 73 63 57 55 50 45 34

S @ 3m 47 57 58 48 43 41 35 30 20
DA 78 72 75 73 73 73 72 65 60
RA 59 69 70 60 54 52 47 41 31
V13CW
CB 59 69 70 60 54 52 47 41 31

S @ 3m 44 54 55 45 39 38 32 27 17
DA 74 71 76 73 70 69 68 63 58
RA 57 68 70 60 51 48 43 40 29
V15CW
CB 57 68 70 60 51 48 43 40 29

S @ 3m 43 54 56 45 37 34 28 25 14
DA 78 75 79 77 74 73 71 67 62
RA 61 72 74 63 55 52 46 43 33
V17CW
CB 61 72 74 63 55 52 46 43 33

S @ 3m 47 58 59 49 40 37 32 29 18
DA 82 75 79 78 77 78 76 69 64
V

RA 63 73 74 64 58 56 51 46 35
V20CW
CB 63 73 74 64 58 56 51 46 35

S @ 3m 48 58 59 50 44 42 37 31 21
DA 82 75 79 78 77 78 76 69 64
RA 63 73 74 64 58 56 51 46 35
V22CW
CB 63 73 74 64 58 56 51 46 35

S @ 3m 48 58 59 50 44 42 37 31 21
DA 86 80 84 82 81 82 80 73 68
RA 67 77 78 68 62 61 55 50 40
V26CW
CB 67 77 78 68 62 61 55 50 40

S @ 3m 53 62 64 54 48 46 41 35 25
Chilled Water

Key:
DA = Discharge Air Sound Power
RA = Return Air Sound Power
CB = Case Breakout Sound Power
S @ 3m = Sound Pressure at 3m

(1) dB(A) is the overall sound level, measured on the A scale.


(2) All sound data measured at nominal conditions.

The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false floor (Base return air
only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values may vary to those stated, typically
increasing by 3dB for each side added. Values stated do not include for room reverberation conditions.

84 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow


Noise Data
Sound Overall Frequency (Hz) dB

Measurement dB(A) 63 125 250 500 1000 2000 4000 8000


DA 90 102 95 86 84 85 81 81 78
RA 77 87 80 79 74 73 66 60 53
V28CW
CB 77 87 80 79 74 73 66 60 53

S @ 3m 63 73 65 64 60 59 52 46 39
DA 93 105 96 89 86 88 84 84 82
RA 80 90 80 81 76 76 69 63 57
V31CW
CB 80 90 80 81 76 76 69 63 57

S @ 3m 65 75 65 66 62 61 55 48 42
DA 92 111 98 90 87 82 82 83 80
RA 80 96 82 83 78 71 68 63 56
V35CW

Technical
CB 80 96 82 83 78 71 68 63 56

S @ 3m 65 81 67 68 64 56 53 48 41
DA 94 113 99 92 89 84 85 85 83
RA 81 98 83 84 80 72 70 65 58
V40CW
CB 81 98 83 84 80 72 70 65 58

S @ 3m 67 83 69 70 65 58 55 50 44
DA 94 113 99 92 89 84 85 85 83
RA 81 98 83 84 80 72 70 65 58
V45CW
CB 81 98 83 84 80 72 70 65 58

S @ 3m 67 83 69 70 65 58 55 50 44
DA 97 115 109 95 92 84 86 84 80
RA 83 98 93 85 82 73 70 63 55
V50CW
CB 83 98 93 85 82 73 70 63 55

S @ 3m 69 84 78 71 67 59 56 49 40
DA 97 115 109 95 92 84 86 84 80

V
RA 83 98 93 85 82 73 70 63 55
V55CW
CB 83 98 93 85 82 73 70 63 55

S @ 3m 69 84 78 71 67 59 56 49 40
DA 98 116 110 97 93 86 87 86 82
RA 85 101 94 89 84 74 72 66 58
V60CW
CB 85 101 94 89 84 74 72 66 58

S @ 3m 71 86 79 74 69 60 58 51 43

Key:
DA = Discharge Air Sound Power
RA = Return Air Sound Power
CB = Case Breakout Sound Power
Chilled Water

S @ 3m = Sound Pressure at 3m

(1) dB(A) is the overall sound level, measured on the A scale.


(2) All sound data measured at nominal conditions.

The Sound Pressure data quoted is only valid where the unit is installed on a solid floor (Front and Rear return air only) or false floor (Base return air
only) and against a rear wall. If the equipment is placed adjacent to any other vertical reflective walls, values may vary to those stated, typically
increasing by 3dB for each side added. Values stated do not include for room reverberation conditions.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 85


EasiCool™ Precision Air Conditioning

Technical Data Upflow V6CW


Mechanical Data
V6CW-EZRE-0 V6CW-EZRE-1 V6CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 7.6 7.6 7.6
Fan Power Input (Fan Gain) (2) kW 0.22 1.50 1.50
Dimensions
WxDxH mm 670 x 670 x 1940 670 x 670 x 1940 670 x 670 x 1940
Weight
Machine (3) kg 147 138 147
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved EC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 x 0.56 1 x 0.30 1 x 0.30
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 369 237 237
Nominal Airflow m³/s 0.55 0.55 0.55
Connections
Inlet/Outlet mm 22 22 22
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 1 1 1
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
V

Quantity x Motor Size 1 1 1


Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1340 / 2215 1340 / 2215 1340 / 2215
Maximum ESP Pa 350 350 350
Fan Power Input (Fan Gain) (2) kW 0.19 0.19 0.19
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 6.6 6.6 6.6
Water Flow (Nominal) l/s 0.15 0.15 0.15
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 3/4 3/4 3/4

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

86 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V6CW


Electrical Data

V6CW-EZRE-0 V6CW-EZRE-1 V6CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 18.9 20.4 31.2
Maximum Start Amps A 18.9 20.4 31.2
Recommended Mains Fuse Size A 25 32 40
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 5.6 5.6
Maximum Start Amps A 4.8 14 14
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 1 1
Full Load Amps A 4.8 5.6 5.6

Technical
Locked Rotor Amps A 4.8 14 14
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A 1.6 1.6
Full Load Amps A N/A 6.8 6.8
Locked Rotor Amps A N/A 17 17
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 87


EasiCool™ Precision Air Conditioning

Technical Data Upflow V8CW


Mechanical Data

V8CW-EZRE-0 V8CW-EZRE-1 V8CW-EZRE-2


Capacity
Nom Cooling (Gross) (1) kW 9.2 9.2 9.2
Fan Power Input (Fan Gain) (2) kW 0.48 1.60 1.60
Dimensions
HxDxW mm 1940 x 670 x 670 1940 x 670 x 670 1940 x 670 x 670
Weight
Machine (3) kg 149 147 149
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved EC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Technical

Quantity 1 x 0.56 1 x 0.55 1 x 0.55


Motor Shaft Power (4) kW N/A N/A N/A
Maximum ESP Pa 303 209 209
Nominal Airflow m³/s 0.75 0.75 0.75
Connections
Inlet/Outlet mm 22 22 22
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 1 1 1
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
V

Fan Transmission Type Direct Drive


Quantity x Motor Size 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1705 / 2215 1705 / 2215 1705 / 2215
Maximum ESP Pa 220 220 220
Fan Power Input (Fan Gain) (2) kW 0.36 0.36 0.36
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 7.9 7.9 7.9
Water Flow (Nominal) l/s 0.18 0.18 0.18
Chilled Water

LPHW Connection Sizes mm 22 22 22


Threaded Connections
Brass Male Taper in 3/4 3/4 3/4

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

88 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V8CW


Electrical Data

V8CW-EZRE-0 V8CW-EZRE-1 V8CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 18.9 23.3 34.1
Maximum Start Amps A 18.9 23.3 34.1
Recommended Mains Fuse Size A 25 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 8.5 8.5
Maximum Start Amps A 4.8 21.2 21.2
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 0,55 1.6
Full Load Amps A 4.8 6,8 8.5

Technical
Locked Rotor Amps A 4.8 17 21.2
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A 2.2 2.2
Full Load Amps A N/A 9.1 9.1
Locked Rotor Amps A N/A 22.8 22.75
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 89


EasiCool™ Precision Air Conditioning

Technical Data Upflow V10CW


Mechanical Data
V10CW-EZRE-0 V10CW-EZRE-1 V10CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 11.2 11.2 11.2
Fan Power Input (Fan Gain) (2) kW 0.65 2.20 2.20
Dimensions
HxDxW mm 1940 x 670 x 670 1940 x 670 x 670 1940 x 670 x 670
Weight
Machine (3) kg 145 150 145
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor Centrifugal Forward Curved EC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 x 0.56 1 x 0.60 1 x 0.60
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 378 199 199
Nominal Airflow m³/s 0.95 0.95 0.95
Connections
Inlet/Outlet mm 22 22 22
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 1 1 1
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
V

Quantity x Motor Size 1 1 1


Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2140 / 2215 2140 / 2215 2140 / 2215
Maximum ESP Pa 45 45 45
Fan Power Input (Fan Gain) (2) kW 0.62 0.62 0.62
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 8.9 8.9 8.9
Water Flow (Nominal) l/s 0.2 0.2 0.2
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 3/4 3/4 3/4

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

90 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V10CW


Electrical Data

V10CW-EZRE-0 V10CW-EZRE-1 V10CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 18.9 24.4 35.2
Maximum Start Amps A 18.9 24.4 35.2
Recommended Mains Fuse Size A 25 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 9.6
Maximum Start Amps A 4.8 24 24
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1,1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 0.94 0.94 0.94
Full Load Amps A 1.5 1.5 1.5

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 91


EasiCool™ Precision Air Conditioning

Technical Data Upflow V13CW


Mechanical Data
V13CW-EZRE-0 V13CW-EZRE-1 V13CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 14.7 14.7 14.7
Fan Power Input (Fan Gain) (2) kW 0.61 2.20 2.20
Dimensions
WxDxH mm 990 x 670 x 1940 990 x 670 x 1940 990 x 670 x 1940
Weight
Machine (3) kg 185 190 185
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - EC Motor Centrifugal Forward Curved EC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 1 1
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 448 266 266
Nominal Airflow m³/s 1.00 1.00 1.00
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 2 2 2
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
V

Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1125 / 1560 1125 / 1560 1125 / 1560
Maximum ESP Pa 275 275 275
Fan Power Input (Fan Gain) (2) rpm 0.36 0.36 0.36
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 11.5 11.5 11.5
Water Flow (Nominal) l/s 0.26 0.26 0.26
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

92 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V13CW


Electrical Data

V13CW-EZRE-0 V13CW-EZRE-1 V13CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 18.9 24.4 35.2
Maximum Start Amps A 18.9 24.4 35.2
Recommended Mains Fuse Size A 25 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 9.6
Maximum Start Amps A 4.8 24 24
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1,1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 93


EasiCool™ Precision Air Conditioning

Technical Data Upflow V15CW


Mechanical Data
V15CW-EZRE-0 V15CW-EZRE-1 V15CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 16.6 16.6 16.6
Fan Power Input (Fan Gain) (2) kW 0.66 1.90 1.90
Dimensions
HxDxW mm 1940 x 670 x 990 1940 x 670 x 990 1940 x 670 x 990
Weight
Machine (3) kg 199 195 199
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - EC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 1 1
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 331 127 127
Nominal Airflow m³/s 1.20 1.20 1.20
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 2 2 2
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
V

Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1330 / 1560 1330 / 1560 1330 / 1560
Maximum ESP Pa 165 165 165
Fan Power Input (Fan Gain) (2) rpm 0.54 0.54 0.54
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 12.7 12.7 12.7
Water Flow (Nominal) l/s 0.28 0.28 0.28
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

94 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V15CW


Electrical Data

V15CW-EZRE-0 V15CW-EZRE-1 V15CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 21.3 22.6 33.4
Maximum Start Amps A 21.3 22.6 33.4
Recommended Mains Fuse Size A 32 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 7.2 7.8 7.8
Maximum Start Amps A 7.2 19.5 19.5
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.6 1.9 1.9
Full Load Amps A 7.2 7.8 7.8

Technical
Locked Rotor Amps A 7.2 19.5 19.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 95


EasiCool™ Precision Air Conditioning

Technical Data Upflow V17CW


Mechanical Data
V17CW-EZRE-0 V17CW-EZRE-1 V17CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 18.1 18.1 18.1
Fan Power Input (Fan Gain) (2) kW 1.03 1.90 1.90
Dimensions
HxDxW mm 1940 x 670 x 990 1940 x 670 x 990 1940 x 670 x 990
Weight
Machine (3) kg 199 195 199
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - EC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 1 1 1
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 253 42 42
Nominal Airflow m³/s 1.40 1.40 1.40
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 2 2 2
OPTIONAL EXTRAS
Electric Heating (Total) kW 7.5 7.5 7.5
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
V

Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1560 / 1560 1560 / 1560 1560 / 1560
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) rpm 0.79 0.79 0.79
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Quantity x Motor Size (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 13.7 13.7 13.7
Water Flow (Nominal) l/s 0.31 0.31 0.31
LPHW Connection Sizes mm 22 22 22
Chilled Water

Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

96 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V17CW


Electrical Data

V17CW-EZRE-0 V17CW-EZRE-1 V17CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 21.3 22.6 33.4
Maximum Start Amps A 21.3 22.6 33.4
Recommended Mains Fuse Size A 32 32 50
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 7.2 7.8 7.8
Maximum Start Amps A 7.2 19.5 19.5
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 6 6 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.6 1.9 1.9
Full Load Amps A 7.2 7.8 7.8

Technical
Locked Rotor Amps A 7.2 19.5 19.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1 1 1
Number of Elements 3 3 3
Rating kW 7.5 7.5 7.5
Curent per Phase A 10.83 11.4 19.68
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 1 1 1
Full Load Amps A 1.85 1.85 1.85

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 97


EasiCool™ Precision Air Conditioning

Technical Data Upflow V20CW


Mechanical Data
V20CW-EZRE-0 V20CW-EZRE-1 V20CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 21.8 21.8 21.8
Fan Power Input (Fan Gain) (2) kW 0.80 4.40 4.40
Dimensions
WxDxH mm 1310 x 670 x 1940 1310 x 670 x 1940 1310 x 670 x 1940
Weight
Machine (3) kg 236 246 236
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - EC Motor Centrifugal Forward Curved EC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 2 2 2
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 411 245 245
Nominal Airflow m³/s 1.50 1.50 1.50
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 15 15 15
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
V

Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1830 / 2165 1830 / 2165 1830 / 2165
Maximum ESP Pa 285 285 285
Fan Power Input (Fan Gain) (2) kW 0.47 0.47 0.47
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 19.2 19.2 19.2
Water Flow (Nominal) l/s 0.43 0.43 0.43
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water

(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

98 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V20CW


Electrical Data

V20CW-EZRE-0 V20CW-EZRE-1 V20CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 29.7 35.8 64.5
Maximum Start Amps A 29.7 35.8 64.5
Recommended Mains Fuse Size A 40 50 100
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 19.2
Maximum Start Amps A 4.8 24 48
Recommended Mains Fuse Size A 16 16 25
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 99


EasiCool™ Precision Air Conditioning

Technical Data Upflow V22CW


Mechanical Data
V22CW-EZRE-0 V22CW-EZRE-2 V22CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 23.4 23.4 23.4
Fan Power Input (Fan Gain) (2) kW 1.13 4.40 4.40
Dimensions
WxDxH mm 1310 x 670 x 1940 1310 x 670 x 1940 1310 x 670 x 1940
Weight
Machine (3) kg 236 246 236
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - EC Motor Centrifugal Forward Curved EC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 2 2 2
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 350 203 203
Nominal Airflow m³/s 1.70 1.70 1.70
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 15 15 15
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
V

Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2165 / 2165 2165 / 2165 2165 / 2165
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) kW 0.79 0.79 0.79
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 19.2 19.2 19.2
Water Flow (Nominal) l/s 0.43 0.43 0.43
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water

(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

100 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V22CW


Electrical Data

V22CW-EZRE-0 V22CW-EZRE-1 V22CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 29.7 35.8 64.5
Maximum Start Amps A 29.7 35.8 64.5
Recommended Mains Fuse Size A 40 50 100
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 19.2
Maximum Start Amps A 4.8 24 48
Recommended Mains Fuse Size A 16 16 25
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 101


EasiCool™ Precision Air Conditioning

Technical Data Upflow V26CW


Mechanical Data
V26CW-EZRE-0 V26CW-EZRE-1 V26CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 25.6 25.6 25.6
Fan Power Input (Fan Gain) (2) kW 1.82 4.40 4.40
Dimensions
WxDxH mm 1310 x 670 x 1940 1310 x 670 x 1940 1310 x 670 x 1940
Weight
Machine (3) kg 236 246 236
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - EC Motor Centrifugal Forward Curved EC - Designed to 25Pa ESP
Motor Type EC AC AC
Fan Transmission Type Direct Drive
Quantity 2 2 2
Technical

Motor Shaft Power (4) kW N/A N/A N/A


Maximum ESP Pa 204 55 55
Nominal Airflow m³/s 2.00 2.00 2.00
Connections
Inlet/Outlet mm 28 28 28
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 50mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 15 15 15
Humidifier
Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 8 8 8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Optional Fan - EC Motor Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
V

Quantity 1 1 1
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2165 / 2165 2165 / 2165 2165 / 2165
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) kW 0.79 0.79 0.79
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 19.9 19.9 19.9
Water Flow (Nominal) l/s 0.44 0.44 0.44
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1 1

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
Chilled Water

(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

102 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V26CW


Electrical Data

V26CW-EZRE-0 V26CW-EZRE-1 V26CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 29.7 35.8 64.5
Maximum Start Amps A 29.7 35.8 64.5
Recommended Mains Fuse Size A 40 50 100
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 4.8 9.6 19.2
Maximum Start Amps A 4.8 24 48
Recommended Mains Fuse Size A 16 16 25
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 1.1 2.2 2.2
Full Load Amps A 4.8 9.6 9.6

Technical
Locked Rotor Amps A 4.8 24 24
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2 2 2
Number of Elements 6 6 6
Rating kW 15 15 15
Curent per Phase A 21.65 22.79 39.36
Humidifier
Capacity kg/hr 3 3 3
Rating kW 2.25 2.25 2.25
Full Load Amps A 3.25 3.42 5.9
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 103


EasiCool™ Precision Air Conditioning

Technical Data Upflow V28CW


Mechanical Data
V28CW-EZRE-0 V28CW-EZRE-1 V28CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 34.2 34.2 34.2
Fan Power Input (Fan Gain) (2) kW 3.50 3.50 3.50
Dimensions
WxDxH mm 1460 x 750 x 1940 1460 x 750 x 1940 1460 x 750 x 1940
Weight
Machine (3) kg 349 349 349
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 3.0 3.0 3.0
Technical

Speed @ 25Pa / Maximum ESP rpm 1420 / 1552 1600 / 1612 1420 / 1552
Maximum ESP Pa 160 160 160
Nominal Airflow m³/s 2.4 2.40 2.40
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 22.5 20 20
Humidifier
Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V

Fan Transmission Type Belt and Pulley


Quantity 1 1 1
Motor Shaft Power (4) kW 4.00 4.00 4.00
Speed @ Maximum ESP rpm 1910 1910 1910
Maximum ESP Pa 470 470 470
Fan Power Input (Fan Gain) (2) kW 4.60 4.60 4.60
Optional Fan - EC Motor Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1700 / 2165 1700 / 2165 1700 / 2165
Maximum ESP Pa 440 440 440
Fan Power Input (Fan Gain) (2) kW 2.02 5.26 5.26
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water

Capacity Gross (5) kW 21.7 23.2 21.7


Water Flow (Nominal) l/s 0.48 0.52 0.48
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

104 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V28CW


Electrical Data

V28CW-EZRE-0 V28CW-EZRE-1 V28CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 47.8 50.2 86.4
Maximum Start Amps A 47.8 50.2 86.4
Recommended Mains Fuse Size A 63 63 125
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 6.7 6.9 11.6
Maximum Start Amps A 43.8 45.5 78.5
Recommended Mains Fuse Size A 16 16 16
Max Mains Incoming Cable Size mm² 35 35 50
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.43 11.14

Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 9 9 9
Rating kW 22.5 22.5 22.5
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6
Full Load Amps A 8.66 9.12 15.75
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 105


EasiCool™ Precision Air Conditioning

Technical Data Upflow V31CW


Mechanical Data
V31CW-EZRE-0 V31CW-EZRE-1 V31CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 38.0 38.0 38.0
Fan Power Input (Fan Gain) (2) kW 4.60 4.60 4.60
Dimensions
WxDxH mm 1460 x 750 x 1940 1460 x 750 x 1940 1460 x 750 x 1940
Weight
Machine (3) kg 347 347 347
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved Belt & Pulley AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 4.0 4.0 4.0
Technical

Speed @ 25Pa / Maximum ESP rpm 1600 / 1612 1600 / 1612 1600 / 1612
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 2.8 2.8 2.8
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 3 3 3
OPTIONAL EXTRAS
Electric Heating (Total) kW 22.5 22.5 22.5
Humidifier
Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V

Fan Transmission Type Belt and Pulley


Quantity N/A N/A N/A
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved DD EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1935 / 2165 1935 / 2165 1935 / 2165
Maximum ESP Pa 225 225 225
Fan Power Input (Fan Gain) (2) kW 3.02 3.02 3.02
Low Pressure Hot Water Copper Tube/Aluminium Fin
Chilled Water

Capacity Gross (5) kW 23.2 23.2 23.2


Water Flow (Nominal) l/s 0.52 0.52 0.52
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

106 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V31CW


Electrical Data

V31CW-EZRE-0 V31CW-EZRE-1 V31CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 49.8 52.1 89.7
Maximum Start Amps A 61.4 58.9 101.7
Recommended Mains Fuse Size A 63 80 125
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 8.6 8.8 15
Maximum Start Amps A 61.4 58.9 101.7
Recommended Mains Fuse Size A 16 16 20
Max Mains Incoming Cable Size mm² 35 35 50
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 4.6 4.6 4.6
Full Load Amps A 8.12 8.34 14.45

Technical
Locked Rotor Amps A 60.9 58.38 101.15
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 9 9 9
Rating kW 22.5 22.5 22.5
Curent per Phase A 32.48 34.19 59.05
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6
Full Load Amps A 8.66 9.12 15.75
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 107


EasiCool™ Precision Air Conditioning

Technical Data Upflow V35CW


Mechanical Data
V35CW-EZRE-0 V35CW-EZRE-1 V35CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 43.7 43.7 43.7
Fan Power Input (Fan Gain) (2) kW 4.60 4.60 4.60
Dimensions
WxDxH mm 1835 x 750 x 1940 1835 x 750 x 1940 1835 x 750 x 1940
Weight
Machine (3) kg 408 408 408
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 4.0 4.0 4.0
Technical

Speed @ 25Pa / Maximum ESP rpm 1440 / 1468 1440 / 1468 1440 / 1468
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 3.3 3.3 3.3
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V

Fan Transmission Type Belt and Pulley


Quantity 1 1 1
Motor Shaft Power (4) kW 5.50 5.50 5.50
Speed @ Maximum ESP rpm 1695 1695 1695
Maximum ESP Pa 240 240 240
Fan Power Input (Fan Gain) (2) kW 6.30 6.30 6.30
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1935 / 2165 1935 / 2165 1935 / 2165
Maximum ESP Pa 260 260 260
Fan Power Input (Fan Gain) (2) kW 3.08 3.08 3.08
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Chilled Water

Quantity x Motor Size (4) kW N/A N/A N/A


Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 29.9 29.9 29.9
Water Flow (Nominal) l/s 0.67 0.67 0.67
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

108 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V35CW


Electrical Data

V35CW-EZRE-0 V35CW-EZRE-1 V35CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 68.2 71.5 123.2
Maximum Start Amps A 68.2 71.5 123.2
Recommended Mains Fuse Size A 100 100 160
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 8.6 8.8 15
Maximum Start Amps A 61.4 58.9 101.7
Recommended Mains Fuse Size A 16 16 20
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 4.6 4.6 4.6
Full Load Amps A 8.12 8.34 14.45

Technical
Locked Rotor Amps A 60.9 58.38 101.15
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Current per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 6.3 6.3 6.3
Full Load Amps A 10.9 10.9 25.63
Locked Rotor Amps A 69.8 69.8 197.35
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 109


EasiCool™ Precision Air Conditioning

Technical Data Upflow V40CW


Mechanical Data
V40CW-EZRE-0 V40CW-EZRE-1 V40CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 47.6 47.6 47.6
Fan Power Input (Fan Gain) (2) kW 6.30 6.30 6.30
Dimensions
WxDxH mm 1835 x 750 x 1940 1835 x 750 x 1940 1835 x 750 x 1940
Weight
Machine (3) kg 429 429 429
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 5.5 5.5 5.5
Technical

Speed @ 25Pa / Maximum ESP rpm 1620 / 1622 1620 / 1622 1620 / 1622
Maximum ESP Pa 25 25 25
Nominal Airflow m³/s 3.7 3.7 3.7
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V

Fan Transmission Type Belt and Pulley


Quantity N/A N/A N/A
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2165 / 2165 2165 / 2165 2165 / 2165
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) kW 4.24 4.24 4.24
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Chilled Water

Quantity x Motor Size (4) kW N/A N/A N/A


Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 31.5 31.5 31.5
Water Flow (Nominal) l/s 0.70 0.70 0.70
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

110 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V40CW


Electrical Data

V40CW-EZRE-0 V40CW-EZRE-1 V40CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 70.9 75 129.2
Maximum Start Amps A 70.9 91.7 158
Recommended Mains Fuse Size A 100 100 200
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 11.4 12.3 21
Maximum Start Amps A 70.3 91.7 158
Recommended Mains Fuse Size A 16 16 32
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 6.3 5.5 5.5
Full Load Amps A 10.9 11.84 20.46

Technical
Locked Rotor Amps A 69.8 91.2 157.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 111


EasiCool™ Precision Air Conditioning

Technical Data Upflow V45CW


Mechanical Data
V45CW-EZRE-0 V45CW-EZRE-1 V45CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 50.6 50.6 50.6
Fan Power Input (Fan Gain) (2) kW 6.30 6.30 6.30
Dimensions
WxDxH mm 1835 x 750 x 1940 1835 x 750 x 1940 1835 x 750 x 1940
Weight
Machine (3) kg 440 440 440
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 1 1 1
Motor Shaft Power (4) kW 5.5 5.5 5.5
Technical

Speed @ 25Pa / Maximum ESP rpm 1620 / 1622 1620 / 1622 1620 / 1622
Maximum ESP Pa 25 25 25
Nominal Airflow m³/s 3.7 3.7 3.7
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 4 4 4
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V

Fan Transmission Type Belt and Pulley


Quantity N/A N/A N/A
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 2165 / 2165 2165 / 2165 2165 / 2165
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) kW 4.24 4.24 4.24
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Chilled Water

Quantity x Motor Size (4) kW N/A N/A N/A


Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 31.5 31.5 31.5
Water Flow (Nominal) l/s 0.70 0.70 0.70
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

112 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V45CW


Electrical Data

V45CW-EZRE-0 V45CW-EZRE-1 V45CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 70.9 75 129.2
Maximum Start Amps A 70.9 91.7 158
Recommended Mains Fuse Size A 100 100 200
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 11.4 12.3 21
Maximum Start Amps A 70.3 91.7 158
Recommended Mains Fuse Size A 16 16 32
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 6.3 5.5 5.5
Full Load Amps A 10.9 11.84 20.46

Technical
Locked Rotor Amps A 69.8 91.2 157.5
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW N/A N/A N/A
Full Load Amps A N/A N/A N/A
Locked Rotor Amps A N/A N/A N/A
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 2.55 2.55 2.55
Full Load Amps A 3.9 3.9 3.9

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 113


EasiCool™ Precision Air Conditioning

Technical Data Upflow V50CW


Mechanical Data
V50CW-EZRE-0 V50CW-EZRE-1 V50CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 51.3 51.3 51.3
Fan Power Input (Fan Gain) (2) kW 7.00 7.00 7.00
Dimensions
WxDxH mm 2170 x 750 x 1940 2170 x 750 x 1940 2170 x 750 x 1940
Weight
Machine (3) kg 485 485 485
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 2 2 2
Motor Shaft Power (4) kW 3.0 3.0 3.0
Technical

Speed @ 25Pa / Maximum ESP rpm 1243 / 1447 1243 / 1447 1243 / 1447
Maximum ESP Pa 255 255 255
Nominal Airflow m³/s 4.2 4.2 4.2
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 5 5 5
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V

Fan Transmission Type Belt and Pulley


Quantity 2 2 2
Motor Shaft Power (4) kW 4.0 4.0 4.0
Speed @ Maximum ESP rpm 1495 1495 1495
Maximum ESP Pa 305 305 305
Fan Power Input (Fan Gain) (2) kW 9.20 9.20 9.20
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1370 / 1510 1370 / 1510 1370 / 1510
Maximum ESP Pa 165 165 165
Fan Power Input (Fan Gain) (2) kW 4.18 4.18 4.18
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Chilled Water

Quantity x Motor Size (4) kW N/A N/A N/A


Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 37.7 37.7 37.7
Water Flow (Nominal) l/s 0.84 0.84 0.84
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

114 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V50CW


Electrical Data

V50CW-EZRE-0 V50CW-EZRE-1 V50CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 72.4 76 131
Maximum Start Amps A 87.1 90.5 156.5
Recommended Mains Fuse Size A 100 100 200
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 12.9 13.4 22.8
Maximum Start Amps A 87.1 90.5 156.5
Recommended Mains Fuse Size A 20 20 32
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.43 11.14

Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 115


EasiCool™ Precision Air Conditioning

Technical Data Upflow V55CW


Mechanical Data
V55CW-EZRE-0 V55CW-EZRE-1 V55CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 58.5 58.5 58.5
Fan Power Input (Fan Gain) (2) kW 7.00 7.00 7.00
Dimensions
WxDxH mm 2170 x 750 x 1940 2170 x 750 x 1940 2170 x 750 x 1940
Weight
Machine (3) kg 498 498 498
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 2 2 2
Motor Shaft Power (4) kW 3.0 3.0 3.0
Technical

Speed @ 25Pa / Maximum ESP rpm 1243 / 1447 1243 / 1447 1243 / 1447
Maximum ESP Pa 255 255 255
Nominal Airflow m³/s 4.2 4.2 4.2
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 5 5 5
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V

Fan Transmission Type Belt and Pulley


Quantity 2 2 2
Motor Shaft Power (4) kW 4.0 4.0 4.0
Speed @ Maximum ESP rpm 1495 1495 1495
Maximum ESP Pa 305 305 305
Fan Power Input (Fan Gain) (2) kW 9.20 9.20 9.20
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1370 / 1510 1370 / 1510 1370 / 1510
Maximum ESP Pa 165 165 165
Fan Power Input (Fan Gain) (2) kW 4.18 4.18 4.18
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Chilled Water

Quantity x Motor Size (4) kW N/A N/A N/A


Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 37.7 37.7 37.7
Water Flow (Nominal) l/s 0.84 0.84 0.84
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

116 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V55CW


Electrical Data

V55CW-EZRE-0 V55CW-EZRE-1 V55CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 72.4 76 131
Maximum Start Amps A 87.1 90.5 156.5
Recommended Mains Fuse Size A 100 100 200
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 12.9 13.4 22.8
Maximum Start Amps A 87.1 90.5 156.5
Recommended Mains Fuse Size A 20 20 32
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.43 11.14

Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.18 11.14
Locked Rotor Amps A 43.3 43.3 77.98
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 117


EasiCool™ Precision Air Conditioning

Technical Data Upflow V60CW


Mechanical Data
V60CW-EZRE-0 V60CW-EZRE-1 V60CW-EZRE-2
Capacity
Nom Cooling (Gross) (1) kW 62.3 62.3 62.3
Fan Power Input (Fan Gain) (2) kW 7.00 7.00 7.00
Dimensions
WxDxH mm 2170 x 750 x 1940 2170 x 750 x 1940 2170 x 750 x 1940
Weight
Machine (3) kg 498 498 498
Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Black, (RAL7021)
Material/Colour Frame: Aluminium Frame with Aluminium Corners
Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins
Cooling/Dehum Stages 1 (Modulated) / 1
Evaporator Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
Fan Transmission Type Belt and Pulley
Quantity 2 2 2
Motor Shaft Power (4) kW 3.0 3.0 3.0
Technical

Speed @ 25Pa / Maximum ESP rpm 1278 / 1324 1278 / 1324 1278 / 1324
Maximum ESP Pa 35 35 35
Nominal Airflow m³/s 4.6 4.6 4.6
Connections
Inlet/Outlet mm 42 42 42
Condensate Drain Hose mm 19 19 19
Filtration Disposable to BS EN 779 - G4 - 75mm
Quantity 5 5 5
OPTIONAL EXTRAS
Electric Heating (Total) kW 30 30 30
Humidifier
Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0
Feed/Drain 3/4” BSPF Braided Flexible Hose / 19mm Hose Connection
Condensate Pump
Head m 10.8 10.8 10.8
Flow l/m 5 5 5
Drain 10mm Stainless Steel Stub Connection
Evaporator Fan Options:
Larger Fan Motor - AC Motor Centrifugal Forward Curved AC - Designed to 25Pa ESP
V

Fan Transmission Type Belt and Pulley


Quantity 2 2 2
Motor Shaft Power (4) kW 4.0 4.0 4.0
Speed @ Maximum ESP rpm 1499 1499 1499
Maximum ESP Pa 230 230 230
Fan Power Input (Fan Gain) (2) kW 9.20 9.20 9.20
Optional Fan - EC Motor Centrifugal Backward Curved EC - Designed to 25Pa ESP
Fan Transmission Type Direct Drive
Quantity 2 2 2
Motor Shaft Power (4) kW N/A N/A N/A
Speed @ 25Pa / Maximum ESP rpm 1510 / 1510 1510 / 1510 1510 / 1510
Maximum ESP Pa 25 25 25
Fan Power Input (Fan Gain) (2) kW 4.18 4.18 4.18
Larger Fan Motor - AC Motor Centrifugal Forward Curved Direct Drive AC - Designed to 25Pa ESP
Chilled Water

Quantity x Motor Size (4) kW N/A N/A N/A


Speed @ Maximum ESP rpm N/A N/A N/A
Maximum ESP Pa N/A N/A N/A
Fan Power Input (Fan Gain) (2) kW N/A N/A N/A
Low Pressure Hot Water Copper Tube/Aluminium Fin
Capacity Gross (5) kW 39.2 39.2 39.2
Water Flow (Nominal) l/s 0.87 0.87 0.87
LPHW Connection Sizes mm 22 22 22
Threaded Connections
Brass Male Taper in 1 1/2 1 1/2 1 1/2

Mechanical
(1) Entering air 24°C/45% RH chilled water in / out: 7°C/12°C.
(2) Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.
(3) With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.
(4) Backward curved EC fan options quote electrical power. All other options quote shaft power.
(5) Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to Low Pressure Hot Water (Optional Extra) - X & WX Models.

118 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Upflow V60CW


Electrical Data

V60CW-EZRE-0 V60CW-EZRE-1 V60CW-EZRE-2


Unit Data Full Function - CW (1)
Nominal Run Amps A 72.4 76 131
Maximum Start Amps A 87.1 90.5 156.5
Recommended Mains Fuse Size A 100 100 200
Unit Data Cooling Only - CW
Nominal Run Amps (2) A 12.9 13.4 22.8
Maximum Start Amps A 87.1 90.5 156.5
Recommended Mains Fuse Size A 20 20 32
Max Mains Incoming Cable Size mm² 35 35 185
Mains Supply V 400V / 3PH + N / 50HZ 380V / 3PH + N / 60HZ 220V / 3PH / 60HZ
Control Circuit VAC 24 24 24
Evaporator Fan - EC Motor Per Fan
Electrical Input Power (3) kW 3.5 3.5 3.5
Full Load Amps A 6.18 6.43 11.14

Technical
Locked Rotor Amps A 43.3 45.01 77.98
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 3 3 3
Number of Elements 12 12 12
Rating kW 30 30 30
Curent per Phase A 43.3 45.58 78.73
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.24 17.09 29.52
Evaporator Fan Options
Larger Fan Motor - AC Motor - Per Fan
Electrical Input Power (3) kW 4.6 4.6 4.6
Full Load Amps A 8.12 8.12 14.45
Locked Rotor Amps A 60.9 60.9 101.15
Standard Size Motor - EC Motor - Per Fan
Electrical Input Power (3) kW 3.1 3.1 3.1
Full Load Amps A 4.8 4.8 4.8

V
Electrical
(1) Values given for full function units (incl. electric heating, humidification) with standard forward curved fan motors, for optional data, please contact Airedale.
(2) Values given for Cooling only units incl. evaporator fan for optional data, please contact Airedale.
(3) Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 119


EasiCool™ Precision Air Conditioning

Technical Data Downflow


Chilled Water Pressure Drop

V6CW - V26CW

Waterside Pressure Drop (kPa) 300 6 - 10 13 - 17 20 - 26

250

200

150

100
Technical

50

0
0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5
Waterflow (l/s)

V28CW - V60CW

500 28 - 31 35 - 40 45
Waterside Pressure Drop (kPa)
V

400

50

300
55 - 60

200

100
Chilled Water

0
0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

Waterflow (l/s)

(1) Includes coil, 3 port valve and pipework.


(2) To calculate 3 port valve pressure drop:

∆P valve = 2 where ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =  Kv 
Q  
   36 
(3)  M for glycol use, refer to Ethylene Glycol Correction Factors.
Fluid 100% water,

120 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™

Technical Data Downflow


Hydronic Data Low Pressure Hot Water

V6CW - V26CW 40

20 - 26
Waterside Pressure Drop (kPa) 35

30

25 6 - 10

20
13 - 17
15

Technical
10

0
0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

0.50
Waterflow (l/s)

V28CW - V60CW

80

V
70
Waterside Pressure Drop (kPa)

60 50-60

50

40
35-45
30

20
28-31
Chilled Water

10

0
0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Waterflow (l/s)
(1) Includes coil, 3 port valve and pipework.

(2) To calculate 3 port valve pressure drop

2
Q  Kv 
∆P valve =   where ∆P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =  
M   36 
(3) Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors.

EasiCool Technical Manual 7535768 V1.12.0_04_2018 121


EasiCool™ Precision Air Conditioning

Fan Data
Calculating Total Static Pressure

Example
Indoor Unit Model Ref = V50-CW-EZRE-2
Design Air Volume = 4.4m³/s
Design External Static Pressure (ESP) = 85Pa

• Plot the Design Air Volume from the X Axis vertically.


• Where the X Axis and the System Curve intersect, plot a line to the Y Axis, to establish the Internal Static Pressure
(ISP)
• Calculate the Total Static Pressure (TSP) of the system thus:
ISP + ESP = TSP
• Using the TSP, plot a line from the Y Axis to intersect with the Design Air Volume line. Where the line intersects, an
approximate Input Voltage can be estimated between those noted on the graphs.
Technical

V50-60 Backward Fan Curve


800
DF 50 - 55

DF 60
1510 RPM
DF

V 50- 60
700
1510 rpm
660

600
575

500 1250 RPM


Static Pressure [Pa]
V

400

1000 RPM
300

200

750 RPM

100
Chilled Water

0
2.00 2.50 3.00 3.50 4.00 4.4 4.50 5.00 5.50 6.00
AirFlow [m 3/s]

Internal Static Pressure + External Static Pressure = Total Static Pressure

e.g. 575+85 = 660

122 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
Fan Speed Data

Key

DF/V 10 - 50Hz
650
10V

600

DF/V 10
550

8V DF 10
500

450

400
Static Pressure [Pa]

350
V 10
6V

Technical
300

250

200

150 4V

100

50
2V

DF
0
0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
Airflow [m 3/s]
Unit
Standard System Curve - System Curve -
Airflow Upflow (V) Downflow (DF)

V28 -60 - EC Forward Fan Curve

V
900
V28 - 31 V50 - 60
V35 - 45

800

700

600
Static Pressure [Pa]

500
Chilled Water

400

300
V40/ 45

200
V50/55

V60
V 31

V35

100
V28

0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]

System Curve Unit Standard Airflow

EasiCool Technical Manual 7535768 V1.12.0_04_2018 123


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 400V 50Hz (-0)
DF/V 6-8 - 50Hz

DF/V 6-8 - 50Hz


500
10V

DF 6 - 8
450

DF/V 6

DF/V 8
400
8V

350

V6- 8
Static Pressure [Pa]

300

250
Technical

6V

200

150

4V
100

50
DF

2V
0
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10
Airflow [m3/s]

DF/V 10 - 50Hz
V

DF/V 10 - 50Hz
650
10V

600
DF/V 10

550

8V DF 10
500

450

400
Static Pressure [Pa]
Chilled Water

350
V 10

300 6V

250

200

150 4V

100

50
2V

0
0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
Airflow [m 3/s]

124 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 400V 50Hz (-0)
DF/V 13 - 50Hz

DF/V 13 -50Hz
600

10V

DF/V 13
8V
500

400
Static Pressure [Pa]

300 6V

Technical
DF 13

200
V 13

4V

100

DF
2V
0
0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30
Airflow [m3 /s]

DF/V 15 - 17 - 50Hz

V
DF/V 15-17 - 50Hz
550
10V

500
DF/V 17
DF/V 15

450
8V

DF 15- 17
400

350 V 15- 17
Static Pressure [Pa]

Chilled Water

300

250 6V

200

150

4V
100

50

2V
0
0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70
Airflow [m3/s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 125


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 400V 50Hz (-0)
DF/V 20 - 26 - 50Hz

DF/V 20-26 - 50Hz


650
10V

600

DF/V 22

DF/V 26
DF/V 20
DF 20 - 26

550
V 20- 26
8V
500

450

400
Static Pressure [Pa]

350
Technical

6V
300

250

200

150 4V

100
DF

50
2V
0
0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40
3
Airflow [m /s]

DF/V 28- 60 - EC Forward Fan Curve


V

DF28 -60 - EC Forward Fan Curve


900

DF28 - 31 DF50 -60


800 DF35 - 45

700

600
Static Pressure [Pa]

500
Chilled Water

400

300

200
DF50 /55
DF40/45
DF35

100
DF31
DF28

DF60

0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]

126 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 400V 50Hz (-0)
V28 - 60 - EC Forward Fan Curve

V28 -60 - EC Forward Fan Curve


900
V28 - 31 V50 - 60
V35 - 45

800

700

600
Static Pressure [Pa]

500

Technical
400

300

V40/ 45
200

V50/55

V60
V 31

V35

DF
100
V28

0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]

DF6 - 10 - EC Backward Fan Curve

V
DF6 -10 EC Backward Fan Curve
800
DF6

DF10
DF8

700

600

500
Static Pressure [Pa]

Chilled Water

400

300

200

100

0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40

Air Volume [m 3/s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 127


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 400V 50Hz (-0)
DF13 - 17 - EC Backward Fan Curve

DF13 - 17 EC Backward Fan Curve


600

500

DF17
400

DF13
Static Pressure [Pa]

DF15
300
Technical

200

100
DF

0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
Air Volume [m 3/s]

DF20 - 26 - EC Backward Fan Curve


V

DF20- 26 EC Backward Fan Curve


1100

1000

900
DF 22

DF 26
DF 20

800

700
Static Pressure [Pa]
Chilled Water

600

500

400

300

200

100

0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40

Air Volume [m 3/s]

128 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 400V 50Hz (-0)
DF28 - 31 - Backward Fan Curve

DF28 -31 Backward Fan Curve


1200

DF 28 - 31

DF31
DF28
2150 RPM
1000

800
1900 RPM
Static Pressure [Pa]

600

Technical
1500 RPM

400

1100 RPM

200

DF
0
1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50
AirFlow [m 3/s]

DF35 - 45 Backward Fan Curve

V
DF35- 45 Backward Fan Curve
1200
DF 40 - 45
DF 35

1000
2150 RPM

800 DF 35 - 45
Chilled Water

1900 RPM
Static Pressure [Pa]

600

1500 RPM
400

200
1100 RPM

0
1.50 2.00 2.50 3.00 3.50 4.00 4.50
AirFlow [m 3/s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 129


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 400V 50Hz (-0)
DF50 - 60 Backward Fan Curve

DF50-60 Backward Fan Curve


900
1510 RPM

DF 60
DF 50 - 60
800

DF 50 - 55
700

600
1250 RPM
Static Pressure [Pa]

500
Technical

400
1000 RPM

300

200 750 RPM


DF

100

0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m3/s]

V6 - 10 EC Backward Fan Curve


V

V6 -10 EC Backward Fan Curve


600
V 10
V6

V8

500

400
Static Pressure [Pa]
Chilled Water

300

200

100

0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
Air Volume [m 3/s]

130 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 400V 50Hz (-0)
V13 - 17 EC Backward Fan Curve

V13 - 17 EC Backward Fan Curve


500

V 13

V 15

V 17
400
Static Pressure [Pa]

300

Technical
1050 rpm

200

100

DF
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
Air Volume [m 3/s]

V20 - 26 - EC Backward Fan Curve

V
V20 - 26 EC Backward Fan Curve
800
V 20

V 22

V 26

700

600

500
Static Pressure [Pa]

Chilled Water

400

300

200

1100 rpm
100

0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20

Air Volume [m 3/s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 131


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 400V 50Hz (-0)
V28 - 31 Backward Fan Curve

V28-31 Backward Fan Curve


1000

2150 RPM V 28 - 31

V 28

V 31
900

800

1900 RPM
700

600
Static Pressure [Pa]

500
Technical

1500 RPM

400

300
1100 RPM

200

100
DF

0
1.00 1.50 2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]

V35 - 45 Backward Fan Curve


V

V35-45 Backward Fan Curve


1000
2150 RPM
V 40 - 45
V35

900

800

1900 RPM
700 V 35 - 45

600
Static Pressure [Pa]
Chilled Water

500

400 1500 RPM

300

200

1100 RPM
100

0
2.00 2.50 3.00 3.50 4.00
AirFlow [m3/s]

132 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 400V 50Hz (-0)
V50 - 60 Backward Fan Curve

V50 -60 Backward Fan Curve


800

V 50-60

DF 50-55
1510 RPM

700

DF 60
600

500 1250 RPM


Static Pressure [Pa]

400

Technical
1000 RPM
300

200

750 RPM

100

DF
0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]

V
Chilled Water

EasiCool Technical Manual 7535768 V1.12.0_04_2018 133


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 380V 60Hz (-1)
DF/V 6 - 60Hz

DF/V 6 - 60Hz
600

DF/V 6
230V

500

400
Static Pressure [Pa]

300
Technical

200

100
DF

0
0.20 0.30 0.40 0.50 0.60 0.70
3/s]
Airflow [m

DF/V8 - 60Hz
V

DF/V 8- 60Hz
600

230V
500

400
Static Pressure [Pa]

DF/V 8
Chilled Water

300

200

100

0
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10
Airflow [m 3/s]

134 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 380V 60Hz (-1)
DF/V10 - 60Hz

DF/V 10- 60Hz


800

700

230V
600

500

DF/V10
Static Pressure [Pa]

400

Technical
300

200

100

DF
0
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
Airflow [m 3 /s]

DF/V13 - 60Hz

V
DF/V 13- 60Hz
800

700

230V
600

500
Static Pressure [Pa]

DF/V13

Chilled Water

400

300

200

100

0
0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20
Airflow [m 3/s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 135


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 380V 60Hz (-1)
DF/V15 - 17 - 60Hz

DF/V 15 -17 - 60Hz


600

DF/V17
DF/V15
500

230V

400
Static Pressure [Pa]

300
Technical

200

100
DF

0
0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70
Airflow [m3/s]

DF/V20 - 26 - 60Hz
V

DF/V 20 -26 - 60Hz


700

230V
600

500
DF/V26
DF/V 20

DF/V 22
Static Pressure [Pa]
Chilled Water

400

300

200

100

0
0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40
Airflow [m3/s]

136 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 380V 60Hz (-1)
DF28 - 60 - EC Forward Fan Curve

DF28-60 - EC Forward Fan Curve


900
DF50 - 60
DF28 - 31 DF35 - 45

800

700

600
Static Pressure [Pa]

500

Technical
400

300

200

DF
100
DF40/45

DF50/55

DF60
DF31

DF35
DF28

0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]

V28 - 60 - EC Forward Fan Curve

V
V28-60 - EC Forward Fan Curve
900
V28 - 31 V35 - 45 V50 - 60

800

700

600
Static Pressure [Pa]

Chilled Water

500

400

300

200
V60
V50/55
V40/45

100
V31
V28

V35

0
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m3/s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 137


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 380V 60Hz (-1)
DF6 - 10 - EC Backward Fan Curve

DF6-10 EC Backward Fan Curve


800

DF6

DF10
DF8
700

600

500
Static Pressure [Pa]
Technical

400

300

200
DF

100

0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
Air Volume [m3/s]

DF13 - 17 - EC Backward Fan Curve


V

DF13- 17 EC Backward Fan Curve


600
DF13

DF17
DF15

500

400
Static Pressure [Pa]
Chilled Water

300

200

100

0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
Air Volume [m 3 /s]

138 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 380V 60Hz (-1)
DF20 - 26 - EC Backward Fan Curve

DF20 - 26 EC Backward Fan Curve


1100

1000

DF 22

DF 26
DF 20
900

800

700
Static Pressure [Pa]

600

Technical
500

400

300

200

DF
100

0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20 2.30 2.40

Air Volume [m 3 /s]

DF28 - 31 - Backward Fan Curve

V
DF28-31 Backward Fan Curve
1100

2150 RPM
1000
DF 28-31
DF31

900
DF28

1900 RPM
800

700
Static Pressure [Pa]

Chilled Water

600

500 1500 RPM

400

300
1100 RPM

200

100

0
1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50
AirFlow [m 3/s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 139


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 380V 60Hz (-1)
DF35 - 45 - Backward Fan Curve

DF35-45 Backward Fan Curve


1000
2150 RPM

900

DF 40 - 45
DF 35
800

1900 RPM DF 35-45

700

600
Static Pressure [Pa]

500
Technical

1500 RPM

400

300

1100 RPM
200

100
DF

0
1.50 2.00 2.50 3.00 3.50 4.00 4.50
AirFlow [m 3/s]

DF50 - 60 - Backward Fan Curve


V

DF50- 60 Backward Fan Curve


900
1510 RPM
DF 50- 55

DF 60

DF 50-60

800

700

600
1250 RPM
Static Pressure [Pa]

500
Chilled Water

400
1000 RPM

300

200 750 RPM

100

0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3/s]

140 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 380V 60Hz (-1)
V6 - 10 - EC Backward Fan Curve

V6 -10 EC Backward Fan Curve


600

V1 0
V8
V6
500

400
Static Pressure [Pa]

300

Technical
200

100

DF
0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
Air Volume [m 3/s]

V13 - 17 - EC Backward Fan Curve

V
V13 - 17 EC Backward Fan Curve
500
V 13

V 17
V 15

400
Static Pressure [Pa]

300
Chilled Water

1050 rpm

200

100

0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
3
Air Volume [m /s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 141


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 380V 60Hz (-1)
V20 - 26 - EC Backward Fan Curve

V20 - 26 EC Backward Fan Curve


800

V 26
V 20

V 22
700

600

500
Static Pressure [Pa]

400
Technical

300

200

1100 rpm
100
DF

0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20

Air Volume [m 3/s]

V28 - 31 - Backward Fan Curve


V

V28-31 Backward Fan Curve


1000
2150 RPM
V 28 -31
V 28

V 31

900

800

1900 RPM
700

600
Static Pressure [Pa]
Chilled Water

500

1500 RPM
400

300

1100 RPM

200

100

0
1.00 1.50 2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]

142 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 380V 60Hz (-1)
V35 - 45 - Backward Fan Curve

V35 -45 Backward Fan Curve


1000
2150 RPM

V 40 -45
900

V35
800

1900 RPM
700 V 35 - 45

600
Static Pressure [Pa]

500

Technical
1500 RPM
400

300

200

1100 RPM

DF
100

0
2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]

V50 - 60 - Backward Fan Curve

V
V50-60 Backward Fan Curve
800
DF 50 - 55

V 50 - 60
DF 60

1510 RPM

700

600

1250 RPM
500
Static Pressure [Pa]

Chilled Water

400

1000 RPM
300

200
750 RPM

100

0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m 3 /s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 143


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 220V 60Hz (-2)
V6 - 10 - EC Backward Fan Curve

V6 -10 EC Backward Fan Curve


600

V6

V 10
V8
500

400
Static Pressure [Pa]
Technical

300

200

100
DF

0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40
Air Volume [m 3/s]

V13 - 17 - EC Backward Fan Curve


V

V13 - 17 EC Backward Fan Curve


500
V 13

V 17
V 15

400
Static Pressure [Pa]

300
Chilled Water

1050 rpm

200

100

0
0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90
Air Volume [m 3/s]

144 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
EZRE Chilled Water 220V 60Hz (-2)
V20 - 26 - EC Backward Fan Curve

V20 - 26 EC Backward Fan Curve


800

V 20

V 26
700

V 22
600

500
Static Pressure [Pa]

400

Technical
300

200

1100 rpm
100

DF
0
1.00 1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00 2.10 2.20

Air Volume [m 3/s]

V28 - 31 - Backward Fan Curve

V
V28 - 31 Backward Fan Curve
1000
V 28

2150 RPM V 28-31


V 31

900

800

1900 RPM
700

600
Static Pressure [Pa]

Chilled Water

500
1500 RPM

400

300
1100 RPM

200

100

0
1.00 1.50 2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]

EasiCool Technical Manual 7535768 V1.12.0_04_2018 145


EasiCool™ Precision Air Conditioning
EZRE Chilled Water 220V 60Hz (-2)
V35 - 45 - Backward Fan Curve

V35-45 Backward Fan Curve


1000
2150 RPM

V 40 - 45
V35
900

800

1900 RPM
V35-45
700

600
Static Pressure [Pa]

500
Technical

1500 RPM
400

300

200

1100 RPM
100
DF

0
2.00 2.50 3.00 3.50 4.00
AirFlow [m 3/s]

V50 - 60 - Backward Fan Curve


V

V50-60 Backward Fan Curve


800
V 50- 60
V50 - 55

V 60

1510 RPM

700

600

1250 RPM
500
Static Pressure [Pa]
Chilled Water

400

1000 RPM
300

200
750 RPM

100

0
2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00
AirFlow [m3/s]

146 EasiCool Technical Manual 7535768 V1.12.0_04_2018


Precision Air Conditioning EasiCool™
After
After Sales
Sales

Warranty
All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by
an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or
18 months from the date of despatch, whichever is the sooner.
Parts or Equipment supplied by Airedale for installation within the UK or for Export that are properly commissioned in
accordance with Airedale standards and specification, not commissioned by an Airedale engineer; carry a 12 month
warranty on non consumable Parts only from the date of commissioning or 18 months from the date of despatch,
whichever is the sooner.
Parts or equipment installed or commissioned not to acceptable Airedale standards or specification invalidate all
warranty.

Warranty is only valid in the event that


In the period between delivery and commissioning the equipment:
• is properly protected & serviced as per the Airedale installation & maintenance manual provided
• where applicable the glycol content is maintained to the correct level.
In the event of a problem being reported and once warranty is confirmed* as valid under the given installation and
operating conditions, the Company will provide the appropriate warranty coverage (as detailed above) attributable to the
rectification of any affected Airedale equipment supplied (excluding costs for any specialist access or lifting equipment
that must be ordered by the customer).
*Once warranty is confirmed, maintenance must be continued to validate the warranty period.

Any spare part supplied by Airedale under warranty shall be warranted for the unexpired period of the warranty or 3
months from delivery, whichever period is the longer. To be read in conjunction with the Airedale Conditions of Sale -
Warranty and Warranty Procedure, available upon request.

Procedure
When a component part fails, a replacement part should be obtained through our Spares department. If the part is
considered to be under warranty, the following details are required to process this requirement. Full description of part
required, including Airedale’s part number, if known. The original equipment serial number. An appropriate purchase
order number.
A spares order will be raised under our warranty system and the replacement part will be despatched, usually within 24
hours should they be in stock. When replaced, the faulty part must be returned to Airedale with a suitably completed and
securely attached “Faulty Component Return” (FCR) tag. FCR tags are available from Airedale and supplied with each
Warranty order.
On receipt of the faulty part, suitably tagged, Airedale will pass to its Warranty department, where it will be fully
inspected and tested in order to identify the reason for failure, identifying at the same time whether warranty is justified
or not.
On completion of the investigation of the returned part, a full “Report on Goods Returned” will be issued. On occasion
the release of this complete report may be delayed as component manufacturers become involved in the investigation.
When warranty is allowed, a credit against the Warranty invoice will be raised. Should warranty be refused the Warranty
invoice becomes payable on normal terms.

Exclusions
Warranty may be refused for the following reasons.
• Misapplication of product or component
• Incorrect site installation
• Incomplete commissioning documentation
• Inadequate site installation
• Inadequate site maintenance
• Damage caused by mishandling
• Replaced part being returned damaged without explanation
• Unnecessary delays incurred in return of defective component

Returns analysis
All faulty components returned under warranty are analysed on a monthly basis as a means of verifying component and
product reliability as well as supplier performance. It is important that all component failures are reported correctly.

EasiCool Technical Manual 7535768 V1.9.0_04_2016147


EasiCool™ Precision Air Conditioning

148 EasiCool Technical Manual 7535768 V1.9.0_04_2016


Precision Air Conditioning EasiCool™

EasiCool Technical Manual 7535768 V1.9.0_04_2016149


Head Office
Airedale International Air Conditioning Ltd
Leeds Road
Rawdon
Leeds LS19 6JY
Tel: +44 (0) 113 2391000
Fax:+44 (0) 113 2507219
E-mail enquiries@airedale.com
Web www.airedale.com

TM_EASICOOL_EZRE_CHILLED_WATER_7535768_v1.12.0_04_2018