Y3 - Module 1 - Installing Electrical Lighting System
Y3 - Module 1 - Installing Electrical Lighting System
mhar cueto
Technology Teachers:
M R. M ARINO C. CUETO
Community Vocational High School
MinSCAT Calapan City Campus,
Masipit, Calapan City
Contextual Teachers:
Facilitator:
Encoder
Inside this module you will find the activities for you to complete and
relevant information sheets for each learning outcome. Each learning
outcome may have more than one learning activity.
i
Course BUILDING W IRING INSTALLATION
INTRODUCTION:
LO1. Layout and install electrical wiring using knob and tube method
LO2. Layout and install PVC raceway/molding
LO3. Layout and install rigid non-metallic conduit
LO4. Layout and install flexible non-metallic conduit
LO5. Assemble fluorescent lighting fixtures
LO6. Layout and install fluorescent lighting fixtures
LO7. Layout and install incandescent lamps
ASSESSMENT CRITERIA:
PREREQUISITES:
ii
TECHNICAL TERMS
Ballast is an induction coil which produces high voltage to start the
lamp into operation.
iii
Course : BUILDING W IRING INSTALLATION
References:
4. www.diydata.com/tool/drills/drills.php
5. www.powertoolinstitute.com
6. www.technologystudent.com
1
LEARNING EXPERIENCES/ACTIVITIES
Learning Outcome # 1: Layout and install electrical wiring using knob and
tube methods
1. Read the Information sheet 1.1 You can ask assistance from
about the principle of knob your teacher to show you and
and tube. explain further the topic you
cannot understand well.
2
INFORMATION SHEET 1.1
1. Commercial Garages
2. Theaters
3. Motion Picture Studios
4. Hoist ways
5. Hazardous Locations
In the open or exposed wiring method, the wires are visible and are
supported by the knobs. These knobs may be a split or solid type. This is
shown in figure 1.
Split knobs are used to support wires smaller than No. 8. Solid knobs
are used to support or anchor wires as big as No. 8 or even bigger. Screws or
nails may be used to fasten the knobs. When a nail is used a leather washer
should be placed between the nail head and the insulator to form cushion
and protect the insulator from breaking. See figure 2.
3
Height of Knob
Figure 3. Shows the correct and wrong ways of tying wires to the
groove of a solid knob.
30 cm. 1 Ft.
Whenever wires pass through studs, rafters, floor joists or any wooden
part of a building, the wires are inserted in porcelain tubes or flexible mica
tubing. Porcelain tubes and mica tubing are also provided whene ver wires
cross each other. It gives the wire extra protection from injury.
4
Figure 5. Application of Porcelain Tubes and Mica Tubing
5
Safety reminders when installing knob and tube wiring
2. Have the auger brace oiled regularly especially the ratchet type.
5. Be sure that the conductors in contact with the wiring surface are
enclosed in mica tubing.
6. Be sure that your teacher has checked your work before testing.
7. Be sure that the safety switch is off before making any connection.
Apply tape on all joints/splices.
9. Be sure to test the insulation for short and ground circuit before
putting on the power.
6
JOB SHEET 1.1
Installing one bulb controlled by one single pole single throw (SPST) switch
in one location.
I – M aterials Required
III – Procedure
7
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria. Follow the pictorial diagram.
Safety Switch
Assessment Criteria
VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Verticality,
Horizontality
2. Accuracy: Dimension;(optional) Accurate function of
the elements
3. M ethod: Observance of the safety measures
Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below
8
I do hereby certify that my student has satisfactorily passed this
performance test by demonstrating their ability in installing one outlet
controlled from one location.
Conforme: Attested:
9
JOB SHEET 1.2
I – M aterials Required
II – Tools Needed
Set of screwdrivers
Set of pliers
hammer
gimlet
electrician’s knife
III- Procedure
10
7. Fasten switches with base under it.
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and rate your performance using the
assessment criteria. Follow the pictorial diagram.
Assessment Criteria
VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Verticality,
Horizontality
2. Accuracy: Dimension;(optional) Accurate function of
the elements
3. M ethod: Observance of safety measures
11
Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below
Conforme: Attested:
12
JOB SHEET 1.3
I – M aterials Required
II – Tools Needed
Set of screwdrivers
Set of pliers
hammer
gimlet
electrician’s knife
III- Procedure
13
7.Fasten switches with base under it.
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria. Follow the pictorial diagram.
Assessment Criteria
VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Verticality,
Horizontality
2. Accuracy: Dimension;(optional) Accurate function of
elements
3. M ethod: Observance of safety measures
Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
14
NI – Needs Improvement = 6 and below
Conforme: Attested:
15
Course : BUILDING W IRING INSTALLATION
Assessment Criteria:
References:
4. www.diydata.com/tool/drills/drills.php
5. www.powertoolinstitute.com
6. www.technologystudent.com
16
LEARNING EXPERIENCES/ACTIVITIES
17
INFORMATION SHEET 2.1
The fittings are available for each size raceway and color option. Single
or Dual gang, junction boxes are versatile enough for any electrical
application. Boxes are equipped with concentric knockouts for all 3 sizes of
raceway. Knockouts are provided on all four sides. Junction boxes come
with adhesive strips and #6 screws to secure the box to the base.
18
The National Electrical Code permits surface raceways in dry locations for
exposed or surface work. The raceway can be extended through dry ways,
dry partitions, and dry floors if one continuos length of raceway is used
throughout the concealed section.
The raceway cannot be used for concealed work on locations subject to
severe to corrosive vapors, or in hoist ways and hazardous location.
19
JOB SHEET 2.1
I. Materials Required
Quantity Unit Descriptions
1 pc single pole switch (flush type)
1 pc safety switch
1 pc incandescent bulb (25 w)
1 pc receptacle
1 pc junction box
2 pcs fuse 15 A (cartridge type)
1 pc metal/plastic box
1 roll electrical tape
1 ft mica tubing or loom
2 pcs plastic molding
20 pcs wood screw (1/2)
III. Procedure
1. Prepare all the materials needed
2. Wear appropriate PPE.
3. Install lamp receptacle, junction box, metal box, safety switch to
the desired location.
4. Fasten the PVC molding to its proper location following the desired
measurements.
5. Connect the wires to where it is intended. Refer to the schematic
diagrams.
6. Mount the bulb and fuses on their respective locations.
7. Connect the power and test the installation.
20
Assessment Criteria
CRITERIA Points
Accuracy of connection 15
Workmanship
- Cutting of PVC molding 15
- Measurements 5
Use of tool 5
Speed 5
Housekeeping 5
50 pts
21
BUILDING W IRING INSTALLATION
Course :
Assessment Criteria:
References:
4. www.diydata.com/tool/drills/drills.php
5. www.powertoolinstitute.com
6. www.technologystudent.com
22
LEARNING EXPERIENCES/ACTIVITIES
5. Perform job sheet 3.1 on how You can ask assistance from
to install by two bulbs your teacher to show you and
controlled by two three-way explain furtherly information
switch and one SPST with two that you cannot understand
convenience outlets. well.
23
INFORM ATION SHEET 3.1
24
INSTALLATION OF NON-M ETALLIC CONDUIT PEC REQUIREM ENTS
25
80 450
90 525
100 600
125 750
150 900
26
Identifying Different Types of Bend
Since PVC conduits are somewhat easier to bend than a rigid conduit,
it likewise requires patience as in any other type of conduit. It is first pre -
heated over a fire or a heat gun to a desired softness. Little by little, it is
bent to its desired shape. When such is attained, it is then hardened by
soaking it to cold or lukewarm water or dampened with a wet rag.
1. Elbow
27
Bend Defects
1. Burned
2. Kinks or groove
Kinks
28
OPERATION SHEET 3.1
Equipment:
Heat gun - 1 unit
M aterials:
Pencil or Chalk - 1 pc
PVC pipe - 1m
Tools:
Steel meter stick/Straight edge - 1 pc
Try square - 1 pc
Pull and push rule - 1 pc
Wet rug - 1 pc
Personal Protective Equipment:
Gloves - 1 pair
Respirator - 1 pc
Procedure:
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria.
Respirator Gloves
29
3. Draw a right angle on the floor using your try square and chalk. This
will serve as your guide when forming your conduit into 90 o angle. (A
tile on the floor can serve as a guide.)
4. If you are in a room with a tiled floor, you can use it as your guide for
90o angle.
5. Draw an arc near the corner with a radius of 100 mm; this will aid
you in forming your elbow correctly.
100 mm
30
6. Mark off 200 mm from the end of PVC pipe. This will be the center of
your elbow bend.
7. Plug-in the heat gun and apply heat to the conduit. Apply heat
100mm on both sides of your marking. Apply heat evenly by turning
over the conduit while swaying your heat gun back and forth to avoid
kinks during bending.
31
9. If the conduit is soften, turn off the heat gun and bend the PVC to the
desired shape using your arc and 90 o angle guide drawn on the floor.
10. If the desired shape is formed, damp the conduit with wet rug to
harden it immediately. (You can use your foot to hold one end of the
conduit while wiping.)
Assessment Criteria
VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Bending 90°,
Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below
32
OPERATION SHEET 3.2
Equipment:
Heat gun - 1 unit
M aterials:
Pencil or Chalk - 1 pc
PVC pipe - 1m
Tools:
Steel meter stick/Straight edge - 1 pc
Try square - 1 pc
Pull and push rule - 1 pc
Wet rug - 1 pc
Personal Protective Equipment:
Gloves - 1 pair
Respirator - 1 pc
Procedure:
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria.
Respirator Gloves
3. Measure the elevation of the obstruction. In this case, let’s use this
wooden box.
33
Note: Remember, offset bent is used if the conduit crosses an
obstruction. In this case, the elevation is about 70 mm.
6. Mark off 100 mm from the end of PVC pipe. This will be the center
of the first bend of the offset.
34
7. Put another mark of about 200 mm from your first marker.
8. Plug-in the heat gun and apply heat to the conduit. Apply heat
between your markers. Apply heat evenly by turning over the
conduit while swaying your heat gun back and forth to avoid kinks
during bending.
35
9. If the conduit is soften, turn off
the heat gun and bend the PVC to
the desired shape using your
guide drawn on the floor. Pull the
left portion of the conduit while
pushing the other end.
Assessment Criteria
VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Offset Bending
Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below
36
JOB SHEET 3.1
Install two bulbs controlled by two (2) three-way switches and one
(1) SPST switch with two convenience outlet.
Please refer to the Learning Outcome No. 2. Layout and Install PVC
raceway/molding for the important PEC provisions in installing rigid non-
metallic conduit and personal safety
Equipment:
Heat gun 1 unit
M aterials:
Pencil or Chalk 1 pc
PVC pipe 3 pcs
PVC adapter with lock nuts 18 pcs
Utility box 5 pcs
Junction box 4 pcs
Lamp socket 2 pcs
Safety switch 1 pc
3 way switch 2 pcs
SPST switch 1 pc
1 gang plate cover 3 pcs
2 gang plate cover 2 pcs
Conduit clamps/straps 15 pcs
Wood screws (1/4 x ½) 50 pcs
Tools:
Steel meter stick/Straight edge 1 pc
Try square 1 pc
Pull and push rule 1 pc
Wet rug 1 pc
Personal Protective Equipment:
Gloves 1 pair
Respirator 1 pc
Procedure:
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria.
37
3. Mark on the wiring board the location of the safety switch, utility
boxes, and junction boxes.
4. Fasten the safety switch and PVC boxes with wood screws at the
desired locations.
6. Install and connect ends of PVC pipe to the electrical boxes, safety
switch.
8. Place the cover of junction box, utility box, and convenience outlet.
38
10. Have your teacher check your work.
S 3w S 3w S
Line diagram of the two bulbs controlled by two (2) three-way switches
and one (1) SPST switch with two convenience outlets in different
location.
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria.
Assessment Criteria
VS S NI
Dimensions
5 3 1
1. Quality: Workmanship, Appearance, Offset Bending,
Bending 90º
2. Accuracy: Dimension, Accurate bending
Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below
39
Course : BUILDING W IRING INSTALLATION
Assessment Criteria:
References:
4. www.diydata.com/tool/drills/drills.php
5. www.powertoolinstitute.com
6. www.technologystudent.com
40
LEARNING EXPERIENCES/ACTIVITIES
41
INFORM ATION SHEET 4.1
1. A smooth seamless inner core and cover bonded together and having
one or more reinforcement layers between the core and cover
designated as Type LFNC-A.
This conduit is flame resistant and, with fittings, is approved for the
installation of electrical conductors.
Uses.
(3) For outdoor locations where listed and marked as suitable for
the purpose. FFN: For marking requirements, see Section
110.1.21
(4) For direct burial where listed and marked for the purpose.
42
(6) As a listed manufactured prewired assembly, 15, mm (20mm)
through 25 mm (32 mm) conduit, as defined in Section 3.51
.2.1(2).
(b) Not Permitted. Liquid tight flexible nonmetallic conduit shall not be
used in the following:
Size. The electrical trade sizes of liquid tight flexible nonmetallic conduit
shall be in accordance with (a) or (b):
Fittings. Liquid tight flexible non - metallic conduit shall be used only with
listed terminal fittings. Angle connectors shall not be used for concealed
raceway installations.
43
(a) The conduit shall be securely fastened at intervals not exceeding
900 mm and within 300 mm on each side of every outlet box,
junction box, cabinet, or fitting.
(b) Securing and supporting of the conduit shall not be required where
it is fished, installed in lengths not exceeding 900 mm at
terminals where flexibility is required, or where installed in
lengths not exceeding 1 800 mm from a fixture terminal
connection for tap conductors to lighting fixtures as permitted
in Section 4.10.13.4(c)
Splices and Taps. Splices and taps shall be made in accordance with
Section 3.0.1 13. See Article 3.70 for rules on the installation and use
of boxes and conduit bodies.
Bends-Number in One Run. There shall not be more than the equivalent of
four quarter bends (360 degrees total) between pull points, e.g., conduit
bodies and boxes.
Coupling
44
Adapter
45
Job Sheet 4.1
Install conduit and electrical wiring from indoor unit to outdoor unit
using flexible nonmetallic tubing.
Equipment:
o *Electric drill - 1 unit
M aterials:
o Pencil or Chalk - 1 pc
o Installation plan or working drawing - 1 pc
o Flat head screw, ¾ in X 10 - 15 pcs
o *Fisher, # 6 (Tox) - 15 pcs
o Flexible nonmetallic tubing - 5m
o Mica tube, ¼ in. dia. - 1m
o Stranded wire, 2.0 mm2 TW -
o Safety switch, 30 A -
Tools:
o Pull and push rule or any measuring - 1 pc
device suited for the activity
o Steel meter stick/Straight edge - 1 pc
Personal Protective Equipment:
o Safety glass - 1 pc
o Gloves - 1 pair
o Goggles - 1 pc
o Safety shoes - 1 pair
Introduction:
In installing electrical circuit, you may use any type of approved
wiring method for the purpose. It has been a practice in this field to use
flexible nonmetallic tubing because flexibility is required for installation ,
operation, and maintenance. You may use rigid nonmetallic conduit (PVC)
as taught in the previous instruction sheets.
Procedure
1. Wear appropriate PPE
2. Measure the required length of flexible nonmetallic conduit from the
outdoor unit to the indoor unit. You may use any measuring device
suited for the job or you may use the actual material by practically
tracing its path as shown in the picture.
46
3. Cut the flexible nonmetallic tubing.
4. Insert the wires first before laying out the tubing permanently.
47
7. Tie the conductors securely to the guide wires.
8. Pull the guide wires at the other end of the tubing. The tubing
should be laid straight forward for easy pulling of conductors.
48
10. Lay out the tubing with conductors permanently.
Wire
allowance
11. Just simply lay the electrical tubing on the path where the
refrigeration system tubing is installed.
12. Secure the flexible nonmetallic tubing wrapping it with cable tie .
49
14. Secure the tubing to the raceway on the indoor unit.
50
18. Be sure that the connections are tightened correctly.
19. You have just finished the electrical circuit from indoor to outdoor
unit. Now, you are ready for the installation of the main power
supply. The main supply line is usually pre-wired by the
manufacturer, you have to do is to terminate it from the circuit
protection.
21. Test the circuit for ground short or open wiring. If fault is found,
rectify it.
51
22. Turn on the circuit and test run the unit.
Assessment Criteria
VS S NI
Dimensions
Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below
52
SELF-CHECK 4.1
1.
2.
3.
4.
5.
53
Course : BUILDING W IRING INSTALLATION
Assessment Criteria:
References:
4. www.diydata.com/tool/drills/drills.php
5. www.powertoolinstitute.com
6. www.technologystudent.com
54
LEARNING EXPERIENCES/ACTIVITIES
55
INFORM ATION SHEET 5.1
Article 6.3.1.3 Live Parts. Fixtures, lamp holders, lamps, rosettes, and
receptacles shall have no live parts normally exposed to contact. Exposed
accessible terminals in lamp holders, receptacles, and switches shall not be
installed in metal fixture canopies or in open bases of portable table or floor
lamps.
All joints/splices to be done must be properly insulated with
spaghetti sleeving, wrapped with electrical tape having a similar thickness of
the conductor used.
2. Cold cathode – Requires high voltage in its operation. This lamp has
electrodes made of thimble-type iron. It is not pre-heated and does not
require a starter for starting. Special high voltage transformers operate it.
Neon and mercury lamps are classified under cold cathode lamps.
56
Operation of pre-heat type fluorescent lamp
The tube filaments, starter (glow switch), and ballast are all connected
in series, which constitute a complete circuit once the switch, is closed. As a
current flow through, the gas (inert) inside the starter glows and the
electrodes are heated. Since one of the electrodes is a bi-metal, it bends and
makes contact with the other. At this instant, the circuit is metallically
complete. The filaments of the fluorescent tube are then heated and partial
ionization takes place. The bi-metals in the starter cools and the contacts
open. The magnetic field in the ballast collapses rapidly producing an
inductive kick, which establishes a current between the filaments and fires
the tube into operation.
57
2. Compact Fluorescent Lamp
58
Parts of Fluorescent tube
59
Different types of Starter
4. Lamp holder and starter socket are the point of connection of the
fluorescent and starter.
60
Parts of fluorescent lamp starter
Starter housing
Base contact
Connecting
wire
Current moves in utilizing the rare gas as conducting means and the
rare gas produces a “glow”. The glow generates heat and causes the
bimetallic blade to expand.
When the bimetallic blade is heated, it changes shape and touches the
fixed contact. The close contacts of the two starter contacts produce an easy
path for the current to flow.
Coil inside
Terminal block
Ballast frame
61
In common with all gaseous discharge lamps, the fluorescent must be
provided with some device for limiting the current drawn by the discharge.
Without a limiting device, the current would rise to a value that would
destroy the lamp. A device or auxiliary called ballast can best meet this
requirement.
62
JOB SHEET 5.1
M aterial:
Fluorescent Lamp (20 watts) - 1 set
Tools:
Philip Screw driver - 1 pc
Flat Screw driver - 1 pc
Side cutting pliers - 1 pc
Long nose pliers - 1 pc
Personal Protective Equipment:
Gloves - 1 pair
Goggles - 1 pc
Procedures:
63
Use bolt and nut in fixing the ballast to the frame
5. Mount the connection terminal socket to the frame. Make sure that it
is fixed not too loose or too tight.
64
Schematic Diagram, Preheat Fluorescent Lamp.
7. Test the circuit for ground short or open wiring. If fault is found,
repair it.
8. Perform housekeeping
Assessment Criteria
Points
Dimensions
1. Accuracy of connections
10
2. Functionality of the fluorescent lamp
10
3. Use of tool
5
4. Speed 5
5. Housekeeping 5
35 points
65
JOB SHEET 5.2
M aterials:
Fluorescent Lamp (40 watts) - 2 set
Fixture Frame - 1 pc
Tools:
Philip Screw driver - 1 pc
Flat Screw driver - 1 pc
Side cutting pliers - 1 pc
Long nose pliers - 1 pc
Personal Protective Equipment:
Gloves - 1 pair
Goggles - 1 pc
Procedure:
66
4. Cut the fixture wires and make the necessary joints or connection by
referring to the schematic diagram.
7. Check the wiring connections and plug in the fixture to the source to
test the assembled fixture for normal operation
8. Perform housekeeping
67
Assessment Criteria
Points
Dimensions
1. Accuracy of connections
10
2. Functionality of the fluorescent lamp
10
3. Use of tool
5
4. Speed 5
5. Housekeeping 5
35 points
68
JOB SHEET 5.3
M aterials:
Fluorescent Lamp (40 watts) - 2 set
Fixture Frame - 1 pc
Tools:
Philip Screw driver - 1 pc
Flat Screw driver - 1 pc
Side cutting pliers - 1 pc
Long nose pliers - 1 pc
Personal Protective Equipment:
Gloves - 1 pair
Goggles - 1 pc
Procedure:
3. Mount the GE rapid start ballast inside the frame (same procedure of
mounting as stated in the Activity Sheet No. 2).
Blue/White
Blue/White
Black/White
White
Red
Red
69
Red
Black
W hite
Yellow
70
Instant start (Cold Cathode)
7. Test the circuit for ground short or open wiring. If fault is found,
repair it.
8. Perform housekeeping
71
Instruction: When you are ready to perform this task, ask your teacher to
observe the procedure and rate your performance using the
assessment criteria.
(Refer the procedure to the activity sheet 1 .1 and 1.2)
Assessment Criteria
Needs
Very Good Good Fair
CRITERIA Improvement
(5) (4) (3)
(2)
1. Accuracy Lamp lights Lamp lights Lamp lights Lamp does not
(25%) but flickers light
Wirings are Wirings are Wirings are Wirings are
secured, secured, not secured; loose; finished
2. Quality neat and neat and finished work is not
(25%) clean clean work is not presentable.
presentation presentation presentable
of the work. of the work.
Followed Followed Incorrect Did not follow
procedure procedure usage of the required
correctly, correctly, tools. procedures.
economical economical
3. Method use of tools use of tools
(25%) is followed; is followed;
and and
observed observed
safety while safety while
working. working.
Submitted Submitted Submitted Unable to
work two (2) work on a work two (2) finish the
4. Speed minutes given time. or more work.
(25%) ahead of minutes
time. after the
given time.
72
Course : BUILDING W IRING INSTALLATION
Assessment Criteria:
References:
4. www.diydata.com/tool/drills/drills.php
5. www.powertoolinstitute.com
6. www.technologystudent.com
73
LEARNING EXPERIENCES/ACTIVITIES
74
JOB SHEET 6.1
Install three (3) fluorescent lamp controlled by three (3) SPST switch
using Flexible Non-metallic Conduit.
M aterials:
Fluorescent Lamp (20 watts) - 3 set
Lamp socket - 3 pcs
Utility box - 2 pcs
Safety switch - 1 set
SPST switch - 3 pcs
Junction box - 5 pcs
Adapter with lock nuts - 15 pcs
Conduit clamps/straps - 25 pcs
1 gang plate cover - 1 pc
2 gang plate cover - 1 pc
Wood screws (¼ x ½) - 50 pcs
Electrical tape - 1 roll
Tools:
Philip Screw driver - 1 pc
Flat Screw driver - 1 pc
Side cutting pliers - 1 pc
Long nose pliers - 1 pc
Push pull tape rule - 1 pc
Personal Protective Equipment:
Gloves - 1 pair
Goggles - 1 pc
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria. Strictly follow the line diagram and the
teacher will determine the distance of each circuit.
75
S S2
Line diagram of the three (3) fluorescent lamps controlled by three
(3) SPST switch using Flexible Non-metallic Conduit.
Procedure:
5. Install/mount the conduit. Place the desired kind and size of the
support according the manufacturer’s specification.
6. Cut and bend wire ways to the desired length and bends based on the
job requirements. Avoid installing nicked conduits.
9. Strip wires in the boxes then connect them to the terminals of the
switches and fuse clip holder. Note: All loop termination must be
turning clockwise and be tightened snugly according to the
manufacturer’s torque specifications. Avoid excess wire termination.
10. Splice and joint wires in junction boxes based on the circuit design
operation. Joining or splicing of conductors inside conduits raceways
is strictly prohibited. Make sure that the joined wires have 6-8”
allowances from the edge of the box to the outstripped joined end of
wires.
76
13. When installation is completed, ask your teacher to evaluate your
performance based on the assessment criteria.
Assessment Criteria
77
JOB SHEET 6.2
Install two (2) fluorescent lamps controlled by the two (2) three –way-
switch and One (1) SPST switch using Flexible Non-metallic
Conduit.
M aterials:
Fluorescent Lamp (20 watts) - 2 set
Lamp socket - 2 pcs
Utility box - 3 pcs
Safety switch - 1 set
SPST switch - 1 pcs
Junction box - 4 pcs
Adapter with lock nuts - 15 pcs
Conduit clamps/straps - 25 pcs
1 gang plate cover - 3 pcs
Wood screws (¼ x ½) - 50 pcs
Electrical tape - 1 roll
Flexible non metallic conduit - 5 mts
Tools:
Philip Screw driver - 1 pc
Flat Screw driver - 1 pc
Side cutting pliers - 1 pc
Long nose pliers - 1 pc
Push pull tape rule - 1 pc
Personal Protective Equipment:
Gloves - 1 pair
Goggles - 1 pc
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria. Strictly follow the line diagram and your
teacher will determine the distance of each circuit.
78
S S 3w S 3w
Line diagram of the two (2) fluorescent lamp controlled by two (2) three –
way-switch and One (1) SPST switch using Flexible Non-metallic Conduit.
Procedure:
5. Install/mount the conduit. Place the desired kind and size of the
support according the manufacturer’s specification.
6. Cut and bend wire ways to the desired length and bends based on the
job requirements. Avoid installing nicked conduits.
8. Cut wire according to the desired length. Always provide allowance (6-
8” for smaller size of wire) for future tapping or termination.
9. Strip wires in the boxes then connect them to the terminals of the
switches and fuse clip holder. Note: All loop termination must be
turning clockwise and be tightened snugly according to the
manufacturer’s torque specifications. Avoid excess wire termination.
79
10. Splice and joint wires in junction boxes based on the circuit design
operation. Joining or splicing of conductors inside conduits raceways
is strictly prohibited. Make sure that the joined wires have 6-8”
allowances from the edge of the box to the outstripped joined end of
wires.
Assessment Criteria
Needs
Very Good Good Fair
CRITERIA Improvement
(5) (4) (3)
(2)
1. Accuracy Lamp lights Lamp lights Lamp lights Lamp does not
(25%) but flickers light
Wirings are Wirings are Wirings are Wirings are
completely neat and not secured; loose; finished
2. Quality installed and clean; the finished work is not
(25%) energized work is work is not presentable.
presentable presentable
80
Course : BUILDING W IRING INSTALLATION
Assessment Criteria:
References:
4. www.diydata.com/tool/drills/drills.php
5. www.powertoolinstitute.com
6. www.technologystudent.com
81
LEARNING EXPERIENCES/ACTIVITIES
1. Read Information sheet 7.1 on the You can ask assistance from
history and development of your teacher to show you and
incandescent lamp explain furtherly topics you
can’t understand well.
2. Perform Job Sheet 7.1 on the You can ask assistance from
Installation of incandescent lamp your teacher while performing
using Rigid Non-metallic Conduit. the task
82
Information Sheet 7.1
Much later, in 1860, the English physicist Sir Joseph W ilson Swan
(1828-1914) was determined to devise a practical, long-lasting electric light.
He found that a carbon paper filament worked well, but burned up quickly.
In 1878, he demonstrated his new electric lamps in Newcastle, England.
The inventor Thomas Alba Edison (in the USA) experimented with
thousands of different filaments to find just the right materials to glow well
and be long-lasting. In 1879, Edison discovered that a carbon filament in
an oxygen-free bulb glowed but did not burn up for 40 hours. Edison
eventually produced a bulb that could glow for over 1500 hours.
Coiled tungsten filament. The metal wires that glow brightly when
electricity flows through them.
Connecting wires . The wires that carry electricity from the bulb's electrical
contact to the filament.
Electrical contacts . The metallic base of the bulb, which connects to the
electrical contacts of the lamp when the bulb is in the lamp.
Glass envelope . The thin layer of glass that surrounds the light bulb
mechanism and the inert gases.
83
Glass fuse enclosure -Glass that insulates the bulb's fuses located within
the stem of the bulb.
M ixture of inert gases at low pressures . The bulb is filled with inert (non-
reactive) gases.
Screw cap . The threaded base of the bulb that secures it to a lamp.
84
many among us learn their history through films, and the vast majority of
early films were made in America by patriotic Americans.
As one final nugget of trivia, the term "limelight" comes from the
incandescent light produced by a rod of lime bathed in a flame of oxygen
and hydrogen. At the time it was invented, limelight was the brightest
source of artificial light known. One of its first uses was for lighting theater
stages, and actors and actresses were keen to position themselves "in the
limelight" so as to be seen to their best effect.
Furthermore, in 1880, Swan gave the world's first large -scale public
exhibition of electric lamps at Newcastle, England.
The thin wire, or filament, inside a light bulb resists the flow of
current through it. When electricity is passed through the bulb, the filament
becomes hot and glows brightly. To prevent the filament burning away
completely, the glass bulb filled with a mixture of inert gas (usually argon
and nitrogen). The filament in most light bulbs is made of tungsten.
85
Elements used in the manufacturing incandescent lamp
1. Lead-in wire
2. Glass
3. Argon gas
4. Inert gas
5. Coiled tungsten
6. Brass
7. Mica
8. Copper
9. Nitrogen
1. Large lamps are those normally used for interior and exterior general
and task lighting. (See figure next page)
86
2. M iniature lamps are generally used in automotive, aircraft, and
appliance applications.
87
Kinds of High Intensity discharge lamp
88
3. High-pressured sodium lamp is an electric discharged lamp in which
the radiation is produced by an excitation of sodium vapor in which
the partial pressure of the vapor during operation is of the order of 10 4
N/m2.
Construction
89
90
JOB SHEET 7.1
Installation of the incandescent lamp using the Rigid Non-metallic
Conduit
M aterials:
Incandescent Lamp (25 watts) - 2 set
Lamp socket - 2 pcs
Utility box - 3 pcs
Safety switch - 1 set
SPST switch - 1 pcs
Junction box - 4 pcs
Adapter with lock nuts - 15 pcs
Conduit clamps/straps - 25 pcs
1 gang plate cover - 3 pcs
Wood screws (¼ x ½) - 50 pcs
Electrical tape - 1 roll
Rigid non metallic conduit 0-
Tools:
Philip Screw driver - 1 pc
Flat Screw driver - 1 pc
Side cutting pliers - 1 pc
Long nose pliers - 1 pc
Push pull tape rule - 1 pc
Personal Protective Equipment:
Gloves - 1 pair
Goggles - 1 pc
Instruction: When you are ready to perform this task, ask your teacher to
observe the process and to rate your performance using the
assessment criteria. Strictly follow the line diagram and the
teacher will determine the distance of each circuit.
91
S S 3w S 3w
Line diagram of two (2) incandescent lamp controlled by two (2) three –
way-switch and One (1) SPST switch using Flexible Non-metallic Conduit.
Procedure:
Assessment Criteria
Needs
Very Good Good Fair
CRITERIA Improvement
(5) (4) (3)
(2)
1. Accuracy Lamp lights Lamp lights Lamp lights Lamp does not
(25%) but flickers light
Wirings are Wirings are Wirings are Wirings are
completely neat and not secured; loose; finished
2. Quality installed and clean; the finished work is not
(25%) energized work is work is not presentable.
presentable presentable
92
Followed Followed Incorrect Did not follow
procedure procedure usage of the required
correctly, correctly, tools. procedures.
observed economical
3. Method safety while use of tools
(25%) working, and is followed;
perform good observed
housekeeping safety while
working.
Submitted Submitted Submitted Unable to
work two (2) work on a work two (2) finish the
4. Speed minutes given time. or more work.
(25%) ahead of minutes
time. after the
given time.
93
SELF-CHECK 7.1
94
ASSESSM ENT PLAN
Evidence Checklist
Competency standard:
Unit of competency:
Title of Module
W ays in which evidence will be collected:
Demonstration
Questioning
Observation
Portfolio
Written
The evidence must show that the student …
Get from assessment criteria of the module (CBC)
LO1. Lay out and install electrical wiring using
knob and tube method
1. Electrical wiring is installed in line with the job
requirements.
2. Electrical wiring is installed in line with the PEC.
3. Safety procedures in installing electrical wiring
are strictly followed in line with the Occupational
Safety and Health Standards.
LO2. Lay out and install PVC raceway/molding
1. Materials, tools and equipment for installing PVC
raceway are prepared in line with the job
requirements.
2. PVC raceway is installed in line with the job
requirements.
3. Workplace is cleaned and made safe upon the
completion of the job.
95
96
3. Fluorescent lighting fixtures are installed in line
with the job requirements.
4. Switching control is applied in accordance with
the work plan.
5. Workplace is cleaned and made safe upon the
completion of the job.
LO 7 Lay out and Install incandescent lamps
1. Types and sizes of incandescent lamps are
identified.
2. Tools, instrument and materials are selected and
identified according to the job requirement.
3. Incandescent lamps are installed according to the
plan.
4. Diameter of hole is appropriately fitted to the
incandescent lamps.
NOTE: *Critical aspects of competency
97
Observation Checklist
Student name:
Teacher name:
Name of School:
Competency
standards
Unit of
competency:
Instructions for the teacher:
1. Observe the student [insert description of activity being observed].
2. Describe the assessment activity and the date on when it was undertaken.
3. Put a check in the box to show that the student has completed each area of the
activity according to the standard expected in the enterprise.
4. Complete the feedback section of the form.
Date of observation
Description of assessment
activity
Location of assessment
activity
The student can: If completed, check
the box.
Did the student’s overall performance meet the Yes No
standard?
Teacher’s feedback:
98
Observation and Questioning Checklist
Student’s name:
Teacher’s name:
Name of the
School:
Competency
standards
Unit of
competency:
Instructions for the teacher:
1. Observe the student [insert description of activity being observed].
2. Describe the assessment activity and the date on when it was undertaken.
3. Place a check in the box to show that the student has completed each area of
the activity according to the standard expected in the enterprise.
4. Ask the student using the questions in the attached list to confirm his/her
underpinning knowledge.
5. Put a check in the box to show that the student has answered the questions
correctly.
6. Complete the feedback sections of the form.
Date of observation
Description of assessment
activity
Location of assessment
activity
The student can: If completed, check
the box.
Did the student’s overall performance meet the Yes No
standard?
Feedback to student:
99
Demonstration
Student’s name:
Teacher’s name:
Unit of competency:
Competency standards:
Date of assessment:
Time of assessment:
Instructions for demonstration
Given the necessary materials the student must be able to:
The student’s demonstration was:
Satisfactory Not Satisfactory
100
W ritten report
Student’s name:
Teacher’s name:
Name of School:
Competency
standards
Unit of
competency:
Task:
Your task is to:
[insert description of task]
Submission date:
Use the checklist below as a the basis for judging whether the student’s
report meets the required competency standards.
The student’s report…. If met, check the box
Student’s
Date:
signature:
Teacher’s
Date:
signature:
101
PERFORMANCE TEST
PERFORMANCE STANDARDS
For acceptable achievement, check YES; for Yes No N/A
unacceptable achievement, check NO; for unachieved
skill, check N/A.
102
ANSW ER KEY 4.1
Test – I - Identification
1. Photographic lamps
2. Miniature lamps
3. Large lamps
4. Coiled tungsten filament
5. Connecting wires
6. Glass envelope
7. Glass fuse enclosure
8. Glass fuse enclosure
9. Screw cap
10. Support wires
103