G12 Module Electrical Wiring System
G12 Module Electrical Wiring System
G12 Module Electrical Wiring System
Definition of Equipment
o In a wiring run, there are many locations at which wiring is
being sinterrupted. At these locations, many different types of
equipment or hardware are required to mechanically support
the electrical system or to complete the interrupted electrical
circuits.
Material Standards
These interruptions in the wiring system are
required wherever:
o All of the materials that are used in electrical systems must be
approved for the uses for which they’re intended. Safety must
1. Wires require a splice
be a concern to everyone who works with electricity, and it’s
2. Wires connect to loads
the responsibility of every electrician to ensure safety to the
3. Wires require a junction
consumer. Therefore, quality and safety standards have been
4. Wires connect to safety devices established that are used to gage approval of individual
5. Wires connect to control devices materials.
6. Wires connect at outlets for lighting fixtures or o Safety standards for electrical equipment and materials are
receptacles necessary to protect not only the public, but also those who
manufacture and install the equipment. The standards
o The materials that are used to mechanically support the include specifications that cover the main features of various
electrical system are called fittings, and the materials products with regard to safety and durability.
that are used to conduct or interrupt electricity are o Typical examples are the National Electrical
called devices. Devices don’t actually use electricity like Manufacturers Association (NEMA) standard for electric
an electrical load does. Therefore, a switch is an example heating equipment and the Certified Ballast Manufacturers
(CBM) standard for fluorescent lamp ballasts.
of a device, since it’s used to conduct or interrupt
o Underwriters’ Laboratories, Inc. (UL) is a service
electricity.
organization that tests devices, systems, and materials in
o An electric light bulb is an example of a load, since it
order to gage compliance with accepted standards. The
actually uses electricity to perform a function. The term qualifying tests ensure the installer, as well as the final
equipment is a general term that covers all of the items in purchaser, that the materials will safely fulfill their intended
an electrical system, including the switch and light bulb. purposes.
o The UL also publishes a List of Inspected Electrical Equipment, 1. ampacity – The current-carrying capacity of electrical
a publication that lists the products that meet the standards conductors, expressed in amperes.
of the UL and that comply with the National Electrical Code 2. appliance, fixed – An appliance that’s fastened or
(NEC), the counterpart of the Philippine Electrical Code in the otherwise secured at a specific location.
US. Products that have been listed by the UL bear the UL
3. appliance, portable – An appliance that can easily be
label. For very small items, the UL listing mark may be
moved from one place to another in normal use.
placed on the shipping carton or reel rather than on the item
4. appliance, stationary – An appliance that isn’t easily
itself.
moved from one place to another in normal use.
5. branch circuit – The circuit conductors between the
circuit breaker or fuse that protects the circuit and the
outlet or outlets.
6. cabinet – An enclosure that’s designed to be either
surface-mounted or flush-mounted and that’s provided
with a frame, mat, or trim in which swinging doors are
hung.
7. conduit body – A separate portion of a conduit or tubing
system that provides access (through a removable cover)
to the interior of the system and that’s located at a
junction of two or more sections of a system (or at a
terminal point of a system).
COMMON WIRING TERMS 8. equipment – A general term that includes materials,
fittings, devices, appliances, and fixtures that are used
o It’s especially important that you become familiar with the as a part of, or in connection with, an electrical
terms that are used in wiring in order to fully understand installation.
the explanations in your study units and to interpret the 9. labeled – Equipment or materials to which has been
rules and regulations that are applicable in the field. attached a label, symbol, or other identifying mark of an
Some of the more common terms that are used in wiring organization that is acceptable to the authority having
are listed here. jurisdiction and concerned with product evaluation, that
maintains periodic inspection of production of labeled
The following list contains some of the more common equipment or materials, and by whose labeling the
terms that apply to wiring: manufacturer indicates compliance with appropriate
standards or performance in a specified manner.
10. lighting outlet – An outlet that’s intended for the direct o Electrical boxes and cabinets are device-housing and
connection of a lamp holder, a lighting fixture, or a wire-housing structures. Electrical boxes and cabinets
pendant cord that terminates in a lampholder. don’t conduct electric current.
11.listed – Equipment, materials, or services included in a list
published by an organization that is acceptable to the authority
having jurisdiction and concerned with evaluation of products
or services, that maintains periodic inspection of production of
listed equipment or materials or periodic evaluation of services,
and whose listing states that the equipment, material, or
services either meets appropriate designated standards or has
been tested and found suitable for a specified purpose.
12. outlet – A point in a wiring system from which current is
taken to supply utilization equipment. o Electrical boxes and cabinets are device-housing and
13. receptacle – A contact device installed at an outlet for the wire-housing structures. Electrical boxes and cabinets
connection of a single attachment plug. A single receptacle don’t conduct electric current.
is a single contact device, with no other contact device. A o A device connects the wiring and conducts the electricity
multiple receptacle, more commonly called a duplex from place to place in a circuit.
receptacle, is a single device that contains two or more
receptacles.
14. receptacle outlet – An outlet in which one or more
receptacles are installed.
15. switchboard – An assembly of switches, fuse holders, and
circuit breakers. Usually installed on a free-standing
structure made up of panels of insulating material
mounted on a metal frame.
16. utilization equipment – Equipment that uses electrical
energy for mechanical, chemical, heating, lighting, or
similar purposes.
Nonmetallic boxes
shall be permitted only with open wiring on insulators,
concealed knob-and-tube wiring, nonmetallic-sheated
cable, and nonmetallic raceways. (Section 3.70.1.3)
Boxes and conduit bodies shall be of sufficient size to provide free space for
all enclosed conductors. In no case shall the volume of the box, as
calculated in (a), be less than the fill calculation as calculated in (b).
(a) Box Volume Calculations. The volume of a wiring enclosure (box) shall
be the total volume of the assembled sections, and, where used, the space
provided by plaster rings, domed covers, extension rings, etc., that are
marked with their volume in cubic centimeter or are made from boxes the
dimension are listed in Table 3.70.2.2(a)
(1) Standard Boxes. The volumes of standard boxes that are not marked
with a cubic centimeter capacity shall be as given in Table 3.70.2.2(a).
(2) Other Boxes. Boxes 1,640 cm3 or less, other than those described in
Table 3.70.2.2(a), and nonmetallic boxes shall be durably and legibly
marked by the manufacturer with their cubic centimeter capacity. Boxes
described in Table 3.70.2.2(a) that have a larger cubic centimeter capacity
than is designated in the table shall be permitted to have their cubic
centimeter capacity marked as required by this section.
100 x 32 square 295 12 10 9 8 7 6 3
100 x 55 x 40
165 6 5 5 4 4 3 FS-Minimum internal
device
depth 45 single 220 9 7 6 6 5 4
cover/gang
100 x 55 x 48
device 210 8 7 6 5 5 4
FD-Minimum
100 x 55 x 55 internal depth 60 295 12 10 9 8 7 6
device 235 9 8 7 6 5 4
single cover/gang
FS-Minimum internal
depth 45 multiple 295 12 10 9 8 7 6
cover/gang
FD-Minimum
internal depth 60 390 16 10 12 10 9 8
multiple cover/gang
(3) Support Fittings Fill. Where one or more fixture studs or hickeys
are present in the box, a single volume allowance in accordance with Table
3.70.2.2(b) shall be made for each type of fitting based on the largest
conductor present in the box. The Volume of a Box
(4) Device or Equipment Fill. For each yoke or strap containing one Section 3.70.2.2 can be summarized into 7 points:
or more devices or equipment, a double volume allowance in accordance
with Table 3.70.2.2(b) shall be made for each yoke or strap based on the 1. Count each circuit conductor that enters the box and
largest conductor connected to a device(s) or equipment supported by that doesn’t pass through the box as one.
yoke or strap.
2. Count as one any wire that runs through the box
(5) Equipment Grounding Conductor Fill. Where one or more without a splice or tap.
equipment grounding conductors or equipment bonding jumpers enters a
3. Each switch, receptacle, or similar device counts as two.
box, a single volume allowance in accordance with Table 3.70.2.2(b) shall be
made based on the largest equipment grounding conductor or equipment 4. Don’t count any wires, such as a receptacle ground, that
bonding jumper present in the box. Where an additional set of equipment originate and end in the same box.
grounding conductors, as permitted by Section 2.50.7.17(d), is present in
the box, an additional volume allowance shall be made on the largest 5. One or more bare grounding wires count as one.
equipment grounding conductor in the additional set.
6. All the fixture studs, hickeys, and cable clamps count as The location where a box is placed depends on the use for which the
one, no matter how many there actually are. box is intended. Since round, square, and octagonal boxes are
normally used for mounting lighting fixtures, they’re required
7. Don’t count conductors from a fixture as wires in the wherever these fixtures are needed. Rectangular device boxes are
box. normally used to mount light switches and receptacles.
Example 1: A 80 mm by 50 mm device box with internal cable clamps
Special Boxes
may be used to wire a toggle switch with two 3-wire type NM cables.
Determine the minimum allowable size of the box. The cables consist o Special boxes are cast
of two 2.0 mm2 (1.6 mm) wires and a grounding wire.
boxes, masonry boxes
Solution: Both the cable clamps and the toggle switch are counted as and floor boxes, and
conductors to make the box selection easier. The following are the they’re used to mount
total number of “conductors” in this box: devices.
Also, the distance between conduits that contain the same wire
Straight and Right Angle Pull Boxes
must be at least six times the diameter of the larger conduit.
8.0 (3.2) 40 -- -- --
14 50 -- -- --
22 75 -- -- --
30 90 -- -- --
38 115 -- -- --
L2 = the distance given in Table 3.73.1.6(b) for the given size of conductor as 60 150 150 190 --
listed in the “one wire per terminal” column.
165 165
L3 = six times the inside diameter of the conduit. 80 200 --
(12) (12)
Table 3.73.1.6(b)
(c) Nonmetallic Boxes. Nonmetallic boxes shall be suitable for the lowest
500 510 -- -- --
temperature-rated conductor entering the box. Where nonmetallic boxes are
used with open wiring or concealed-knob-tube wiring, the conductors shall
600 560 -- -- -- enter the box through individual holes. Where flexible tubing is used to
encase the conductors, the tubing shall extend from the last insulating
725 610 -- -- -- support to no less than 6.4 mm inside the box. Where nonmetallic-sheated
cable is used, the cable assembly, including the sheat, shall extend into the
850 610 -- -- -- box no less than 6.4 mm through a nonmetallic-sheated cable knockout
opening. In all instances, all permitted wiring methods shall be secured to
the boxes.
At the end of every module, you’ll be asked to check your 17.(For items 17 – 19) Enumerate the 3 main uses of outlet boxes.
understanding of what you’ve just learned by completing a “Self
20. What section in the PEC states that round boxes shall not be used
Check.” Writing the answers to these questions will help you review
where conduits or connectors requiring the use of locknuts or bushings
what you’ve learned so far. Please complete Self Check 8 now.
are to be connected to the side of the box?
1. (For items 1 – 6) Enumerate the 6 locations where wiring is required
to be interrupted.
Enclosures constructed (without knockouts) for indoor use to provide a degree of Enclosures constructed for indoor use in hazardous (classified) locations
7
protection to personnel against access to hazardous parts; to provide a degree of classified as Class I, Division 1, Groups A, B, C, or D as defined in NFPA 7
protection of the equipment inside the enclosure against ingress of solid foreign
12
objects (falling dirt and circulating dust, lint, fibers, and flyings); and to provide a
degree of protection with respect to harmful effects on the equipment due to the
ingress of water (dripping and light splashing).
Enclosures constructed for either indoor or outdoor use in hazardous The service disconnecting means shall not be installed in
8 (classified) locations classified as Class I, Division 1, Groups A, B, C, and D as bathrooms.
defined in NFPA 70. The location of the service entrance is usually specified by the
power company, which may also have restrictions on the type
and minimum size of service-disconnect switches or
Enclosures constructed for indoor use in hazardous (classified) locations panelboards that are used.
9
classified as Class II, Division 1, Groups E, F, or G as defined in NFPA 70. For example, the Manila Electric Company (Meralco) requires
to provide a service disconnecting means in the service
entrance poles if the distance of the protective device to
Enclosures constructed to meet the requirements of the Mine Safety and customer’s unit is greater than 15 meters.
10
Health Administration, 30 CFR, Part 18.
SWITCHES
Single Pole Switch
Poles and Throws
When you want to control a light from two different places, you When a light is to be controlled from more than two places, one or
must use two three-way switches. more four-way switches are used in combination with two three-way
A three-way switch is an SPDT switch that can be identified by its switches.
three terminals and plain handle. A four-way switch is an DPDT switch that does not have also
Unlike single-pole, single-throw switches, three-way switches don’t markings on its handles. The four-way switch appears identical to
have ON or OFF positions marked on their handles. Instead, one the three-way switch except that it has one more terminal.
terminal is usually a marked as 0 and the other two terminals are Four-way switches are basically two three-way switches combined.
marked 1 and 3. Terminal 1 and 3 serves as common terminals while terminals 2 and
The typical wiring of a two location lamp control using 2 three- 4 are traveler terminals
way switches is shown in the figure in the right. The typical wiring of a three location lamp control using 2 three-way
switch and a four-way switch is shown in the figure in the right. If
the wiring between switches is incorrect, no harm
is done except that the light won’t light.
The ordinary toggle switch is the most common type of switch. The handle
is moved up to close the circuit and down to open the circuit.
TOGGLE SWITCHES
TOGGLE SWITCHES
DESPARD SWITCHES
Canopy switches are control devices found right at the electrical load
being controlled.
Canopy or miniature switches are generally used to control only one
load, and usually have current ratings between 0.5A and 6.0 A.
PUSHBUTTON SWITCHES
CANOPY SWITCHES
Besides its regular use for residences as a control for door bells and
chimes, there are many commercial and industrial uses for the
pushbutton switch.
For example, a pushbutton switch may be used in a hospital to notify
a nurse on duty that a patient requires some service.
A switch used for this application will usually remain in contact until
the nurse triggers a release button.
ENCLOSED SWITCHES
Canopy switches are the small or miniature switches that you see
mounted in electrical appliances and light fixtures.
Pull switches were quite popular in the past, but their use is
now diminishing, and they’re largely being replaced by wall
switches.
Pull switches are commonly located in basements, attics,
garages, and closets.
DIMMER SWITCHES
FLOAT SWITCHES
Switch Locations
Switch Ratings
The clock-type timer finds considerably greater application in lighting
control than the interval timer. In effect, this is a clock which may be Switches, like other electrical equipment, must be applied within
set to close a switch at a certain time and to open it at a certain time. their ratings. Most switches are approved for use at currents up to 10
Unlike a conventional clock, the clock-type timer switch generally has A (amperes) at voltages up to 125 V (volts). In this case, for voltages
a 24-hour cycle. Its widest use is in the operation of lights in store up to 250 V, the reduced current rating would be 5 A. The switch
windows and signs. rating is marked on each switch
A switch that’s marked “10A125V-5A250V T” will have heavier
contacts to withstand the high inrush current of incandescent lamps.
A switch with such a rating is called a T-rated switch. T-rated
switches are also available with mercury contacts. The letter “T” in
the name stands for the tungsten from which incandescent filaments
are made. 5.
A switch that’s marked “10A125V-5A250V AC” is a general-use
alternating current (AC) switch. These switches can be used up to their
full current rating to control lamps that are fed from an AC source.
Quiet operation is another advantage of the general-use AC switch.
6.
At the end of
every module, you’ll be asked to check your understanding of what
you’ve just learned by completing a “Self Check.” Writing the answers 8.
to these questions will help you review what you’ve learned so far.
Please complete Self Check 10 now.
(For items 5 – 10) Identify what device is being represented by the symbols. 9.
An overload is an overcurrent that is confined to normal current
paths. There is no insulation breakdown. Overloads are either
sustained or temporary.
Sustained overloads are commonly caused by installing excessive
equipment such as additional lighting fixtures. They are also caused
10. by overloading mechanical equipment and by equipment breakdown
such as failed bearings. If not disconnected within established time
11. (For items 11 – 13) Enumerate at least 3 kinds of manually operated limits, sustained overloads eventually overheat circuit components
switch. causing thermal damage to insulation and other system components.
Temporary overloads occurs frequently. They may be caused by
14.(For items 14 – 20) Identify the 7 nonelectrical parameters for temporary equipment overload such as a machine tool taking too
controlling the automatic operation of switches. deep of a cut, or may result from starting inductive loads, such as
PROTECTIVE DEVICES motors. Since temporary overloads are, by definition, harmless,
overcurrent protective devices should not open the circuit.
All electrical systems require protective devices. The most common A short-circuit is a current flowing outside its normal path. It is
protective devices are fuses, circuit breakers, and ground-fault circuit caused by a breakdown of insulation or by a faulty equipment
interrupters (GFCIs). The function of these devices is to protect connections. In a short circuit, current by-passes the normal load.
electrical wiring and equipment by stopping the flow of current Short-circuit currents may vary from fractions of an ampere to
whenever the current becomes abnormally high as the result of a 200,000 amperes or more. Short-circuits are divided into bolted
short circuit, overload or ground fault. faults, arcing faults, and ground faults.
When current flows through a conductor, it generates heat that’s Bolted fault is a short-circuit that has no electrical resistance at the
proportional to the square of the current flowing in the conductor. point of the fault. It results from a firm mechanical connection
This means that if the current is doubled, the amount of heat is between two conductors, or a conductors and ground. Bolted faults
increased to four times the original amount. An overload or short are characterized by a lack of arcing. Examples of bolted faults are a
circuit causes increased current, which will generate sufficient heat to heavy wrench lying across two bare bus bars, or a crossed-phase
cause rapid deterioration of conductors’ insulation (or even a fire). condition due to in-correct wiring.
When excessive current flows, the weakest part of the conducting Arcing fault is a short-circuit that arcs at the point of fault. The arc
circuit will break first and open the circuit. A protective device is impedance (resistance) tends to reduce the short-circuit current.
installed in each circuit to deliberately provide such a weak point. Arcing faults may turn into bolted faults by welding of the faulted
A protective device must be matched to the current-carrying capacity, components. Arcing faults may be phase-to-phase or phase-to-
or ampacity, of the conductor. Ampacity represents the amount of ground.
current a specific size and type of conductor can carry. Ground fault is a short-circuit caused by insulation breakdown
An overcurrent is any current that exceeds the ampere rating of between a phase conductor and a grounded object or conductor.
conductors, equipment, or devices under conditions of use. The term
“overcurrent” includes both overloads and short-circuits.
Effects of Short-circuits Fuses
1. Heating
2. Magnetic stress
3. Arcing
PROTECTIVE DEVICES
601 –
L TIME-DELAY 200,000 600
4,000
Fuse Interrupting-Current Ratings
200 –
The interrupting current in a circuit is the amount of current that 2,000
could be delivered to the circuit if a severe fault or short circuit
should develop. Current-limiting fuses are designed to withstand
RK1 TIME-DELAY 200,000 250 0.1 –
600 RENEWABLE 250
H FUSES FAST- 10,000 1 – 60
ACTING 600
250
RK1 FAST-ACTING 200,000 1 – 600
600
J FAST-ACTING 200,000 600 1 – 600 4. Special-purpose fuses are used for specific, nonstandard
protection of electrical components and equipment.
0.1 – 30
Plug Fuses
CC TIME-DELAY 200,000 600
0.25 – 30
250
K5 FAST-ACTING 50,000 1 – 600
600 Both plug and cartridge fuses are used in residential wiring. Plug
fuses have two types of bases, the Edison Base (Type T fuses) and the
Rejection Base (Type S fuses), also known as a "tamper-proof base".
The Edison Base Type T fuse works with the typical socket used in the This feature permits you to select a fuse that’s much closer to the
fuse box seen in older homes and the fuse base looks like a light bulb actual load current. The high-current element is designed to blow on
base. a very high over current, such as a short circuit. When this element
melts, the spring pulls the elements apart and breaks the circuit.
The main element (which doesn’t have to respond to such overloads)
can be made larger and with less resistance. Therefore, it can operate
cooler and with a lower voltage drop.
Dual-element fuses have been developed to permit operation with a
temporary overload, a condition that often exists when equipment is
first energized (especially equipment with motors).
Cartridge Fuses
A Rejection Base Type S fuse actually consists of two components, an
adapter base that screws and locks into the Edison socket in the fuse
box, and the fuse itself.
Each different amperage rating of a Type S fuse has a matching
socket base adapter with a different sized thread that prevents
mismatching (rejection base). It stops a person from putting a 20 Amp
rated fuse in a 15 Amp circuit.
Cartridge fuses are often used as main service fuses and large-
appliance fuses when the current exceeds 30 A and are typically
found in industrial applications. Cartridge fuses come in ferrule or
blade type.
Supplementary Fuses
Cartridge fuses operate on the principle of internal heating. The There are three types of supplementary fuses: micro fuses, miniature
conducting element, which is called the link, is connected between the fuses, and miscellaneous fuses. These types are used in individual
two ferrules. The ferrules make electrical contact when the fuse is pieces of electrical and electronic equipment and for the protection of
plugged into a mating fuse holder, or cutout. individual circuits or components.
Cartridge fuses operate on the principle of internal heating. The
conducting element, which is called the link, is connected between the
two ferrules. The ferrules make electrical contact when the fuse is
plugged into a mating fuse holder, or cutout.
Cartridge fuses (which are common in nonresidential use) are made
in three classifications: 250 V, 300 V, and 600 V. The use of the
different classifications varies depending on the maximum voltage
rating of the circuit in which they’re used.
The knife-blade fuse is made only in sizes larger than 60 A. The size of
the fuse changes with the voltage and current ratings, which prevents
the substitution of a fuse with a much different rating in a circuit.
Circuit Breaker
Receptacles, or convenience outlets, are provided for the quick
connection of electrical equipment to the wiring system and the
source of power. Many different types of receptacles are
manufactured, but the duplex receptacle, which provides two
outlets, is the most common one.
Wires are terminated to receptacles either through screw
terminals or pressure terminals referred to as stab locks. A
stripping gage is included on the duplex receptacle to aid in
removing the correct amount of insulation.
If a wire must be removed, a screwdriver is placed in the slot to
release the pressure terminal and to permit the wire to be
withdrawn. The pressure terminal is usually designed to accept
only two sizes of solid copper wire, such as No. 12 and No. 14.
Either the screw terminals or the pressure terminals may be used
with solid copper wires, but only the screw terminals can be used
with stranded copper wires.
Ordinary receptacle outlet has 1 terminal (L) for the hot wire from
circuit breaker and 1 terminal (N) for the neutral wire from the
neutral bus bar when installed in a line-to-neutral circuits. If you
are wiring line-to-line circuits, however, the second hot wire is
terminated at the neutral terminal (N) of the outlet.
Electricity wants to flow to ground through easiest path. Since
you are standing on wet surface that is touching ground,
electricity can jump from power tool and race through your body
to ground. This faulted circuit will kill instantly.
Three prong receptacle outlets has a third terminal (G) where the
ground wire is terminated. The ground terminal is usually labeled
with the symbol like the figure in the right. The GFCI instantly detects open circuit, and cuts power so
electricity is stopped. The PEC requires that outdoor plugs,
kitchen plugs and bathroom plugs should be GFCI protected.
GFCI Receptacle Convenience Outlet
GFCI outlet is different than an ordinary outlet. There are two set
of screws on GFCI outlet, same as ordinary outlet except each
screw is independent and not connected by metal. So all 4 GFCI
screws are independent. In the back of GFCI device identifies Line
screws and Load screws. Load screws are usually covered with
yellow tape when device is fresh out of box.
Hot and neutral wires or the two hot conductors from breaker box
attach to Line screws. At this point, anything plugged into the
GFCI outlet is protected from fault. Both outlets are GFCI
protected at this point, and Load screws are not used. Load
screws are usually covered with yellow tape when device is
and phase characteristics. The National Electrical Manufacturers
Association lists the NEMA configuration standards for the various
sets of plug and receptacle characteristics. If an L precedes the NEMA
designation, the plug or receptacle is constructed with locking prongs
and is called a twist-lock receptacle.
CONVENIENCE DEVICES
Receptacle Configurations
Receptacles and plugs are also used in circuits with higher voltage
and current ratings, and also in circuits that supply one-phase or
three-phase voltages. Since electrical equipment is designed for use at
a particular combination of voltage, current, and phase, the plug for
the equipment can’t be inserted into a receptacle that supplies a
different combination of voltage, current, and phase.
For this reason, the manufacturers of electrical devices have
standardized prong configurations for each set of voltage, current,
Receptacle Configurations
Receptacle Location
A convenient recommended height for a the installation of a duplex
receptacle is 300 mm above the floor, because the outlet is more
accessible and small-appliance cords will drag less. In a kitchen, Receptacles will usually be equally spaced. However, the spacing
bathroom, laundry room, or garage, a good height for installation is may be changed somewhat for convenience in probable placement
1,200 mm above the floor. This results in the receptacles being about of furniture. The receptacles that are installed for countertops in
300 mm above a countertop or work bench. kitchens and dining rooms should be installed so that no wall
space (measured horizontally) is more than 600 mm from a
The PEC requires electricians to provide enough receptacles so that
receptacle outlet. (Section 2.10.3a2)
no point in a room is more than 1,800 mm from a receptacle. (Section
2.10.3a1) This means that the distance between receptacles is always
less than 3,600 mm, which is convenient because the cord length on
most appliances is about 1,800 mm. Any wall space that’s greater
than 600 mm should be counted when receptacles are located.
(Section 2.10.3a2)
Sliding panels (such as sliding glass doors leading to patios) also
should be counted as wall space. When sliding doors are used, special
floor receptacles may be needed, but they must be within 450 mm of
the wall to be counted in the wall receptacle requirement. (Section
2.10.3a3) For commercial applications, receptacles must be provided
as needed which means that they can be much closer or farther apart
than 3,600 mm.
The PEC also requires that GFCI protected receptacle outlets be installed in
dwelling units (Section 2.10.1.8a) at:
1. Bathrooms,
2. Garages and also accessory buildings that have a
floor located at or below grade level not intended
as habitable rooms and limited to storage areas,
work areas, and areas of similar use
The PEC also requires that GFCI protected receptacle outlets be installed in
dwelling units (Section 2.10.1.8a) at:
1. Outdoors,
2. Crawl spaces below grade level,
3. Unfinished basements
4. Kitchens, and
5. Wet bar sinks
SELF CHECK NO. 2
10. (For items 10 – 13) Give the 4 prime reasons for excessive current.
14. Since heat is the primary actor that will trip a breaker, a short period
of _____ seconds must be allowed to let the breaker cool before it can be
reset.
16. What section in the PEC states that receptacles shall be installed so
that no point along the floor line in any wall space is more than 1,800
mm from an outlet in that space?
20.What section in the PEC states all 15A and 20A circuits in a dwelling
bedroom shall be AFCI protected?
Lighting Receptacle
Special lamp holders are used for exterior use and in wet places Fluorescent lamp holders have four electrical contacts, two at
such as the weatherproof lamp holder that’s called a pigtail socket each end of the lamp. This is accomplished in the standard line of
by electricians. lamps by the use of a miniature bipin for T-8 and T-12 bulbs and
It has short leads that are sealed into a lamp holder made of mogul bipin for T-17 bulbs. In circline lamps, the cathodes are
either rubber or a composition material. This isn’t a permanent connected to a four-pin base located between the junction of the
type of lamp holder, and it’s usually used only for construction two ends of the lamp.
sites or temporary lighting purposes. High Output and Very High Output lamps have recessed double
contact (RDC) type bases. Slimline (Instant Start) lamps require
only two electrical contacts, one at each lamp end and have single
Lamp Holder Classification pin bases.
1. Candelabra
2. Intermediate
3. Medium
4. Mogul base
Light Fixtures and Luminaires • Semi-recessed: Housing is partially set into the ceiling or wall
A light fixture, light fitting, or luminaire is an electrical device • Portable: Fixture can be moved and plugged into a standard
used to create artificial light by use of an electric lamp. A fixture’s outlet
components consist of one or more lamps and one or more of the
following:
Bollard Light Fixture Light Fixture for Fence 2. Install fixtures away from insulation. The second type of
hazard results when recessed lighting fixtures are
installed too close to a dwelling’s thermal insulation.
This hazard often occurs because the fixture wasn’t
rated for the type of insulation used.
The PEC states that fixtures must be labeled as suitable for their intended
location and purpose. The following lists some of the labels that may be
found on a lighting fixture. Section 4.10 of the PEC lists requirements
concerning the specific locations where you would install these and other
lighting fixtures.
Electrical Loads and Control Diagrams
ELECTRICAL LOADS
There are three main types of electrical loads: resistive, inductive, and Inductive loads are electrical loads which pulls a large amount of
capacitive loads. current (an in-rush current) when first energized. After a few cycles or
seconds the current "settles down" to the full-load running current.
The time required for the current to "settle down" depends on the
frequency or/and the inductance value of the inductive load.
Inductive loads draw real power (W) and inductive reactive power
(VAR) from the source.
The real power does useful work, such as provide light or create
torque to do work.
The inductive reactive power, on the other hand, is required for the
loads to work (ex. creates magnetic field for induction motors), but it
increases the current the source must provide.
PAR 64 8 200
A parabolic aluminized reflector lamp (also PAR light, PAR can, or PAR 56 7 175
simply PAR) is a type of electric lamp that is widely used in
commercial, residential, and transportation illumination. PAR 46 5¾ 145
A PAR lamp is a type of halogen or LED light bulb wherein the lens
and reflector are internal parts of the lamp.
PAR 38 4¾ 120
The gas within PAR lamp bulbs rebuilds the filament and creates a
bulb that is longer-lasting than many other types of halogen lighting.
PAR 36 4½ 115
PAR lamps are sturdy enough to be exposed to various types of
weather without needing any fixtures for protection.
PAR 30 3¾ 95
PAR 20 2½ 65
PAR 16 2 50
1,000
PAR 64 500 Halogen bulbs are a variation of incandescent bulb technology. These
bulbs work by passing electricity through a tungsten filament, which
is enclosed in a tube containing halogen gas.
250
This halogen gas causes a chemical reaction to take place which
removes the tungsten from the wall of the glass and deposits it back
500 onto the filament. This extends the life of the bulb.
In order for the chemical reaction to take place, the filament needs to
be hotter than what is needed for incandescent bulbs. The good news
PAR 56 300 is that a hotter filament produces a brilliant white light and is more
efficient (more lumens per watt).
200 The bad news is that a hotter filament means that the tungsten is
evaporating that much faster. Therefore a denser, more expensive fill
gas (krypton), and a higher pressure, are used to slow down the
150 evaporation.
This means that a thicker, but smaller glass bulb (envelope) is
needed, which translates to a higher cost. Due to the smaller glass
PAR 38 100
envelope (bulb), the halogen bulb gets much hotter than other bulbs.
A 300 watt bulb can reach over 300 degrees C.
75 Therefore attention must be paid to where halogen bulbs are used, so
that they don't accidentally come in contact with flammable
materials, or burn those passing by.
Care must be taken not to touch the glass part of the bulb with our
fingers. The oils from our fingers will weaken the glass and shorten
the bulb’s life. Many times this causes the bulb to burst when the
filament finally burns out.
Circline lamps, which are circular, are available in four sizes: 6 1/2
inches, 8 inches, 12 inches and 16 inches outside diameter.
In a fluorescent lamp, the voltage must be regulated because the
current in the gas discharge causes resistance to decrease in the
tube. The AC voltage will cause the current to climb on its own. If this
current isn’t controlled, it can cause the blow out of various
components.
There are primarily two types of ballasts - magnetic and electronic.
Magnetic ballasts are not energy efficient and they generate flicker
and humming sounds noticeable in the fluorescent lamp. When the
power switch is turn on, the fluorescent lamp will flicker for a few
times before it can give a steady light.
Generally, there are three different types of compact fluorescent lamp
systems:
1. Integrated systems contain a lamp, base, and ballast in one unit. This
entire unit is disposed of at the end of its life.
CFL Incandescent
40 Watts HID lamps produce light by striking an electrical arc across tungsten
7–10 Watts
electrodes housed inside a specially designed inner glass tube. This
tube is filled with both gas and metals. The gas aids in the starting of
15-18 Watts 60 Watts
the lamps. Then, the metals produce the light once they are heated to
a point of evaporation.
20 Watts 75 Watts HID lamps are typically used not only when energy efficiency and/or
long life are desired, but also when high levels of light are required
100 Watts over large areas. Such areas include gymnasiums, large public areas,
20-25 Watts
outdoor activity areas, roadways, pathways, and parking lots.
High Pressure Sodium (HPS), Metal Halide, Mercury Vapor and Self-
Ballasted Mercury Lamps are all high intensity discharge lamps (HID).
With the exception of self-ballasted lamps, auxiliary equipment such
as ballasts and starters must be provided for proper starting and
operation of each type bulb. Compared to fluorescent and
incandescent lamps, HID lamps produce a large quantity of light from
a relatively small bulb.
Light Emitting Diodes (LED) are bulbs without a filament, that are low
in power consumption and have a long life span. LEDs are just
starting to rival conventional.
LED’s are becoming more and more popular because of its high light
output and low power consumptions. LED lamps however must be
produced in large scale to compare to the light output given by a
single incandescent bulb.
Nevertheless, technology is advancing everyday, and it will not be long
until the LED bulb will be the bulb of choice for most applications in
the home and work place.
A control diagram for a complex automated machine is shown in
figures at the left. These diagram is typical of those used by industrial
electricians every day.
Each diagram is followed by the sequence of operation for the particular
machine and notes on some of the switches.
1. The numbers down each side of each diagram are reference numbers
for the rungs of the “ladder.”
2. Relay coils, solenoids, and timers are located near the right side of the
diagram, and their functions are listed to the right of the ladder.
These devices are actually the loads of the control circuit itself. Each
rung of the ladder must have a load, or the rung would be a short
circuit.
Schematic Symbols
In ladder diagrams, the load device (lamp, relay coil, solenoid coil,
etc.) is almost always drawn at the right-hand side of the rung.
While it doesn't matter electrically where the relay coil is located
within the rung, it does matter which end of the ladder's power
supply is grounded, for reliable operation.
However, consider what would happen to the circuit with the same
fault (wire #1 coming in contact with ground), except this time we'll
swap the positions of switch and fuse (L2 is still grounded):
This time the accidental grounding of wire #1 will force power to the
lamp while the switch will have no effect.
It is much safer to have a system that blows a fuse in the event of a
ground fault than to have a system that uncontrollably energizes
lamps, relays, or solenoids in the event of the same fault.
7. INDUCE POWER AND COMMISSION THE INSTALLED SYSTEM.
Performing power test to the installed circuit will conclude whether it is
WIRING ELECTRICAL CIRCUITS functional or not. When the intended function of the system was not met,
In wiring electrical circuits, a good electrician/installer should follow the then the installer will have to perform troubleshooting.
following standard operating procedures:
3. CHECK ALL THE DEVICES FOR FAULTS AND FUNCTIONALITY. Most Example:
circuit troubles are caused by installing faulty or non-functional devices. It
is a mortal sin in the electrical field to by-pass this procedure to ensure
reliability of the installed circuit.
NAME: _____________________________________DATE:________________ 17.What do you mean by the acronym CRI in the lamp technology?
11. ___________ lamps are fluorescent lamps that are circular in shape.