Close Control EC Plug Fan Range: Engineering Data Manual Chilled Water & Air Cooled R410A 50/60Hz
Close Control EC Plug Fan Range: Engineering Data Manual Chilled Water & Air Cooled R410A 50/60Hz
Close Control EC Plug Fan Range: Engineering Data Manual Chilled Water & Air Cooled R410A 50/60Hz
Index
Description Page
Equipment Nomenclature 4
Guide Specifications 6
While every precaution has been taken to ensure accuracy and completeness in this manual, EDPAC assumes no responsibility, and disclaims
all liability for damages resulting from use of this information or for any errors or omissions.
2
EDPAC COMPANY PROFILE
HISTORY
Formed in 1968, EDPAC has grown through worldwide distribution to an installed base of over 50,000 units. EDPAC currently
services the markets of Europe, the Americas, the Middle East, and the Far East. As one of the pioneers of Precision Air Conditioning
the EDPAC name has become synonymous with quality and reliability. With its highly skilled and experienced team EDPAC has
established not only a modern manufacturing plant, but also a sophisticated and innovative product development programme. Since
1987 EDPAC International located in Cork Ireland, has controlled the entire activities of the group.
PRODUCT RANGE
EDPAC manufactures a broad range of Precision Air Conditioning equipment for the Computer Room, Telecoms and other critical
Building Services applications. EDPAC systems are designed to provide optimum operating conditions in close control
environments.
QUALITY
All suppliers of materials and components used in manufacturing are assessed and qualified by EDPAC. The EDPAC guarantee of
quality is also complimented by rigorous in-factory quality assessment and quality control testing prior to product dispatch. The
overall activity of the factory is customer focused and conforms to the strict norms of IS/ISO9001/EN29001. EDPAC was awarded
and has retained this certificate since 18th March 1992.
3
EQUIPMENT NOMENCLATURE
The EDPAC Close Control Plug Fan Range are precision environmental control units designed for 24 hour, year-round use. The unit
simultaneously controls air temperature, air humidity, air distribution and air cleanliness in the conditioned space. It is fitted with a
central microprocessor controller which monitors air temperature/humidity and air cleanliness and ensures accurate stepped response
to room load changes. To maximise energy efficiency, all units are fitted with wide surface area coils, compliant scroll compressors
and EC plug fans. Sound levels are kept to a minimum with double skin panels (optional), a unique wide area air chamber and coil
mounted filtration and fully isolated compressor compartment. All major components are fully serviceable from the front.
D ECP A 060 B S 1 1 S
S = STANDARD CONTROLS
G = GRAPHIC CONTROLS
HUMIDIFIER
0 = NONE
1 = STANDARD DISPOSABLE
2 = LOW CONDUCTIVITY
3 = CLEANABLE
4 = ULTRASONIC
HEATING
0 = NONE
1 = 2 STAGE
2 = 3 STAGE
3 = PROPORTIONAL
4 = HOT WATER
S = STANDARD SCROLL
COMPRESSOR
V = VARIABLE SPEED
COMPRESSOR
X = CHILLED WATER
VOLTAGE
B = 380-415/3/50
E = 220/3/60
H = 460/3/60
J = 380/3/60
NOMINAL CAPACITY
060 = 20 kW 200 = 80 kW
080 = 30 kW 240 = 100 kW
120 = 45 kW 280 = 115 kW
160 = 65 kW 320 = 140 kW
A = AIR COOLED
C = CHILLED WATER
D = DUAL COOLING
Dimensions (mm)
Weight (kg)
4
AIR COOLED CONDENSERS - DIMENSIONS AND WEIGHTS
CONDENSERS
Notes:
1. Standard condensers have 4 Pole motors. For 6 Pole & 8 Pole low noise versions, consult factory.
2. All condensers are shipped with mounting feet. When mounted in the horizontal, condenser models AGHS 501 – 504 are 850
mm high and Condenser models AGHS 633 – 635 are 1170 mm high.
3. All condenser data is per condenser.
5
GUIDE SPECIFICATIONS
STANDARD FEATURES
Unit is set up with a discrete fan speed based on a fixed 0-10V DX Units
output to the EC motor based on the design point of operation
Each unit shall have 2 independent refrigerant circuits, each
of the fan. This is the default setting on units shipped.
with a liquid distributor, expansion valve, sight glass and filter
drier.
Unit set up to track the control temperature band with set
voltage limits whereby max voltage / fan air volume is at set
point plus/minus control band & min voltage / fan air volume Electronic Expansion Valve
at set point. Max air volume is typically design air volume & DX circuits are fitted with electronic expansion valves which
min air volume is around 60% for chilled water units & 75% provide precision proportional control and annualised energy
for air cooled units. This is something that can be proven on savings of 15-20% with floating condenser head pressure
site. Minimum value needs to ensure there are no hot spots control.
due to lack of airflow & that there is no loss of sensible
cooling capacity to latent cooling capacity at the cooling Motors
coil.
The motor shall comply with IP55 TEFC insulated to Class F.
Unit set up to give a reduced fan air volume in
dehumidification mode to conserve energy in Filtration
dehumidification while quickly achieving the
The filters shall be 100mm thick disposable pleated panel
dehumidification effect at the cooling coil. This output voltage
filter rated G4 in accordance with EN779. They shall be fitted
is again user selectable.
in the return air stream and be accessible from the front of a
Upflow unit and the top of a Downflow unit & Displacement
Unit is set up via an underfloor pressure transducer to give a
unit.
fixed underfloor pressure all the time. Underfloor pressure
setpoint is input through the unit user display.
Compressors
Unit is set up to provide a guaranteed supply air temperature Compressors shall be high efficiency hermetically sealed
in the cold aisle. scroll type. High and low pressure switches, motor overload
protection and crankcase heaters shall be provided. The
Unit is set up to be controlled by a BMS with minimum & compressors shall be mounted on resilient neoprene
maximum voltage values & 0-100% output over these values mountings for vibration isolation.
by BMS.
Electrical Panel
Unit is set to have an airflow setpoint on controller with the
addition of a fan inlet measuring ring & pressure transducer in The electrical panel shall be constructed and assembled in
the unit. compliance with IEC standards with all components VDE
approved. All sub circuits are protected by MCB’s. The high
and low voltage sections shall be segregated and all high
Cabinet
voltage electrical components shall be touch safe.
The cabinet frames shall be constructed of formed 2.0 mm
Zintec steel sections. Paint finish is Epoxy Powder Coated Electric Heaters
with an “Orange Peel” textured finish. Interior panels to be
manufactured from galvanised steel in all cases. Exterior Electric heaters shall have stainless steel sheathed elements
panels are to be as cabinet except in 1.2 mm Zintec. Paint with stainless steel finning, balanced over three phases and
Colour to be RAL 9018. The front panels shall be fastened to rated to operate at black heat. Control shall be in two stages.
the frame using quarter turn fasteners. Side panels shall be Protection is by a high temperature safety cut-out stat. The stat
secured to the frame using chrome plated screws. All panels shall be a capillary type mounted in the airstream resettable
shall be flush fitting, sealed to the frame sections with closed from the control section of the electrical panel.
cell foam and insulated with a non-shedding material, which
shall be non-combustible, when tested in accordance with B.S.
476 Part 6 and 7. The units shall be fully accessible and
serviceable from the front.
6
GUIDE SPECIFICATIONS
Manual Procedure: With the unit powered off & the controls
Humidification powered on it shall be possible to check all analogue & digital
outputs & to run the devices.
The humidifier shall be of the electrode-boiler type. Features
shall include selectable steam output and microprocessor
control with alarms and diagnostic facilities. The humidifier Temperature & Humidity Zone setback: It shall be possible to
control system shall allow the use of a wide range of mains create up to 4 periods in a 24 hour period with dedicated set
water conditions namely: inlet mains water pressure of 1-10 points of temperature & humidity.
bar, total hardness of 15-30 French degrees & water inlet
electrical conductivity of 400-800 micro siemens. Unit shall System Auto Restart: For start up after power failure, the unit
optimise drain down frequency for maximum operational shall automatically restart with an ability to stagger the
economy. starting of multiple units by setting a time delay of up to 999
seconds.
Microprocessor Controls
Security: The microprocessor shall have multiple levels of
All units shall be fitted as standard with the latest Delta range
security (5 no. 4 digit passwords) to prevent unauthorised
of DIN rail mounted Microprocessor Controls. The Control
parameter adjustment.
System utilises a main Microprocessor Interface Board
equipped with a set of terminals necessary to connect the
Time Delays: It shall be possible to create or adjust if
Board to the controlled devices (e.g. valves, compressors,
necessary the unit on time delay, settle delay, unit off time
fans, reheats, sensors and humidifiers). All software is
delay, compressor interstage delay, compressor minimum run
permanently stored in flash RAM and is therefore protected
time, compressor minimum stop time, heater interstage delay,
even in the event of a power failure. Unit software is uploaded
winter start time delay, temperature alarm time delay,
to the Microprocessor using a RAM key or personal
humidity alarm time delay, serious alarm time delay & non-
computer. On multi unit sites this quickens unit
serious alarm time delay.
commissioning. The software can also be easily changed or
upgraded on site by qualified service personnel.
Sensor Calibration: It shall be possible to recalibrate the
temperature & humidity sensors in software.
The Microprocessor based Terminal Unit is complete with a 4
line x 20 character backlit LCD Display, keypad and LED
Inputs / Outputs: It shall be possible to view the current status
Indicators allowing the user to easily set the main control
of all inputs & outputs while the unit is running.
parameters (set-points, differentials and alarm thresholds) and
carry out the main working operations (on/off and displaying
Set & Hysteresis adjustment: It shall be possible to adjust the
controlled variables).
set & hysteresis % values of stepped outputs within the
control.
Main features of controller are:
BMS / BAS interfacing: It shall be possible with the addition
Status: The display shall indicate current temperature, current
of a simple communications card to communicate all Analog,
humidity, temperature & humidity set points, cooling status,
Digital & Integer variables in the following protocols : LON
heating status, humidification status & dehumidification status
FTT 10, BACnet over RS485 MSTP, BACnet over TCP/IP,
SNMP over TCP/IP, MODBUS over RS485, Metasys & OPC
Redundancy Management & Master Control: The controls
Server.
shall be capable of redundancy management & master control
setup / “Handshake” of groups of up to 16 units without Remote Display panel: It shall be possible to connect an
addition of any hardware. additional shared LCD display which is wired back to the unit
& this remote display shall have full control access to the unit
Alarms: Controls shall be capable of storing last 100 alarms, from a distance of up to 100m.
identified by type, date stamped & indicating also the Remote Temperature & Humidity sensing: It shall be possible
temperature & humidity conditions when the alarm occurred to remotely locate the Temperature/Humidity sensor to better
& also the setpoints of temperature & humidity when the meet the sites cooling needs. The sensor can be located a
alarm occurred. There are 36 alarms & all alarms can be either distance of up to 30m from the unit.
set as “serious” or “non-serious”. A serious alarm shuts down
the unit.
7
GUIDE SPECIFICATIONS
OPTIONAL FEATURES
Rear Return
3 Stage Reheat For upflow units. Required when unit is located in a service
Available instead of 2 stage by adding an electrical contactor area outside the conditioned space. Return air is taken in the
& configuring the software to 3 stage. rear. Rear panel generally has a duct connection and filters are
withdrawable from outside the unit.
Proportional Electric Reheat
Bottom Return
Units shall be fitted with electric reheat controlled by a
thyristor giving a fully proportional 0-10V output of the reheat For upflow units. Required if air is returned from a floor void.
capacity. Bottom of unit is opened up and base components are
mounted on rails. Filters cannot be fitted in unit and are
Hot Water Reheat shipped loose for installation beneath the unit on site.
Units shall be fitted with a Low Pressure Hot Water (LPHW) Displacement
heating coil in place of the standard electrical heating. Water
flow through the coil is controlled by a 2 or 3 way modulating For units where the air is discharged at a low level above the
valve. Duties of these coils are nominally the same as standard floor.
electric heating, based on flow and return hot water
temperatures of 82°C and 71°C respectively. Fan Under Floor
For units where the fan is placed in the base of the unit and the
Cleanable Humidifier Cylinder coil is extended to give an increased capacity.
Humidifier cylinder is serviceable whereas standard
humidifier cylinder is disposable. Return Air Attenuator 500mm high
Attenuator mounted on top of downflow unit. Attenuators
Low Conductivity Humidifier Cylinder have internal baffles and provide 8-10 dB reduction on
Disposable type but for water supply with low electrical airborne noise.
conductivity.
F5/6/7 Panel Filters
Floor Stand Upgrade of standard G4 disposable panel filters to F5/6/7
Floorstands are shipped flat-pack and need to be assembled on disposable panel filters.
site. They are suitable for raised floor heights of 150mm to
600mm. The legs are notched at 50mm intervals for cutting G2 Pre-filter with G4 Main Filter
on site. There is also a final adjustment on the foot of +/-
100mm G4 disposable filter replaced with 50mm G2
50mm. Floorstands are manufactured from galvanised steel.
disposable plus 50mm G4 disposable filter.
Damper & On/Off Actuator Kit
Washable Filters
Addition of a damper & on/off actuator to isolate a downflow
Upgrade of standard disposable 100mm G4 disposable filters
or upflow unit in standby. Damper is typically fitted on top of
to washable 50mm G3 type plus 50mm G4 disposable filter.
unit. Actuator powered from unit electrical panel.
8
GUIDE SPECIFICATIONS
A fire stat shall be provided & mounted in the return air path
Fresh Air Connection Units can be supplied with a fresh within the unit to interface with the unit controls and indicate
air inlet connection and disposable G4 filter. This will admit an alarm.
approximately 3-5% of the recirculated air volume.
Water Detection – Point Type
Hot Gas Bypass Consists of a water detection module mounted in unit & point
sensor which can be placed in unit or under the floor. Multiple
Hot gas bypass line including hot gas bypass valve fitted to point sensors can be placed in series with each other. A cable
provide capacity control in low load situations. type water warning is also available.
Fire Detector
A fire detector shall be provided & mounted in the return air
path to interface with the unit controls and generate an alarm.
Fire Stat
9
GUIDE SPECIFICATIONS
Graphic Display
An optional Graphical Terminal Unit is also available. This is
a graphical display, LED Backlit with 132 x 64 pixel
graphical resolution.
10
GENERAL ENGINEERING DETAILS – AIR COOLED
STANDARD MODELS
Notes:
1. Indoor unit Freefield SPL dBA levels are measured at 3m.
2. All filters are 97mm thick.
3. Humidifier inlet connection is ¾’’ BSPM & drain connection is 1’’ BSPF.
4. Coil drain pan connection is ¾’’ BSPF.
11
GENERAL ENGINEERING DETAILS – CHILLED WATER
STANDARD MODELS
Model Size 064/6 084/6 124/6 164/6 204/6 244/6 284/6 324/6
Coil Data
Coil Face Area m2 0.58 0.82 1.32 1.82 2.31 2.81 3.32 3.83
Rows No. 4&6 4&6 4&6 4&6 4&6 4&6 4&6 4&6
Air Side Data
Air Volume m3/hr 5665 7830 12420 16830 21235 25735 30330 34920
External Static Pressure ESP Pa 25 25 25 25 25 25 25 25
Fan Type - EC EC EC EC EC EC EC EC
Fan Diameter / Fan Quantity mm 450 / 1 500 / 1 630 / 1 560 / 2 630 / 2 630 / 3 630 / 3 630 / 4
Fan Absorbed Power - 4 Row kW 0.9 1.3 1.8 1.1 1.3 1.0 1.2 0.9
Fan Motor Power kW 1.45 2.6 3.6 3.1 2.8 2.8 2.8 2.8
Fan Absorbed Power - 6 Row kW 1.1 1.6 2.2 1.4 1.7 1.3 1.6 1.2
Fan Motor Power kW 1.45 2.6 3.6 3.1 2.8 2.8 2.8 2.8
Filter Data
Grade - G4 G4 G4 G4 G4 G4 G4 G4
Filter Width mm 490 685 540 490 625 570 670 615
Filter Height mm 660 660 660 660 660 660 660 660
Filter Quantity No. 2 2 4 6 6 8 8 10
Noise Data
Freefield SPL dBA 57 58 58 59 61 61 62 62
Unit Piping Data
Chilled Water F&R Pipe Size mm 35 35 42 54 54 54 54 54
Control Valve Size mm 32 32 32 40 40 50 50 50
Control Valve Quantity No. 1 1 1 1 1 1 1 1
Control Valve Kv - 16 16 16 25 25 40 40 40
12
AIR COOLED SYSTEM SCHEMATIC
1 2 3 4 5 6
Suction
Line
9 Discharge
Line 11
10
8
M
8 7
12
13
14
15 Liquid
Line
System Components
1. Evaporator Coil.
2. Liquid Distributor.
3. Thermostatic Expansion Valve (externally equalised).
4. Liquid Line Solenoid Valve (optional).
5. Liquid Sight Glass (including moisture indicator).
6. Filter Drier.
7. Compressor.
8. Compressor Service Valves.
9. High Pressure Switch (manual reset).
10. Low Pressure Switch (automatic reset).
11. Check Valve (See Note).
12. Fan speed Controller (pressure operated head pressure control, if fitted).
13. Pressure relief Valve (See Note).
14. Air Cooled Condenser.
15. Liquid Receiver (See Note).
Note: Items 11, 13 and 15 are supplied by others and field fitted by others.
13
CHILLED WATER COOLED SYSTEM SCHEMATIC
1
2
M
4 4
3 3
System Components
14
AIR COOLED UNITS - COOLING CAPACITIES 50Hz
Notes:
1. Capacities are based on R410A refrigerant.
2. For capacities at other conditions, please refer to the Factory or product selection program.
15
CHILLED WATER COOLED UNITS - COOLING CAPACITIES 50/60Hz
Model : Standard 064 084 124 164 204 244 284 324
Air On: 22oC, 50% RH
Total Capacity kW 17.0 24.3 40.5 55.5 72.4 85.2 102.6 119.7
Sensible Capacity kW 17.0 24.3 40.5 55.5 72.4 85.2 102.6 119.7
Chilled Water Flow l/s 0.71 1.02 1.69 2.32 3.03 3.56 4.29 5.02
Unit Pressure Drop kPa 11 15 29 24 43 29 44 61
Air On: 24oC, 50% RH
Total Capacity kW 20.0 28.6 47.2 64.7 84.3 99.8 119.7 125.4
Sensible Capacity kW 20.0 28.6 47.2 64.7 76.1 99.8 108.3 119.7
Chilled Water Flow l/s 0.84 1.19 1.98 2.70 3.52 4.16 5.00 5.22
Unit Pressure Drop kPa 14 19 40 32 58 39 57 66
Airflow m3/hr 5665 7830 12420 16830 21235 25735 30330 34920
No. of Fans No. 1 1 1 2 2 3 3 4
Fan Motor kW 1.45 2.6 3.6 3.1 2.8 2.8 2.8 2.8
EC Fan Diameter mm 450 500 630 560 630 630 630 630
Electric Reheat kW 7.5 9.6 15.0 25.0 25.0 25.0 25.0 25.0
No. of Steps No. 2 2 2 2 2 2 2 2
Humidifier Capacity kg/hr 3 3 8 8 8 8 8 8
Humidifier Power kW 2.2 2.2 5.8 5.8 5.8 5.8 5.8 5.8
Model : Standard 064 084 124 164 204 244 284 324
Air On: 22oC, 50% RH
Total Capacity kW 16.7 23.8 39.4 54.0 70.3 82.9 99.8 116.9
Sensible Capacity kW 16.7 23.8 39.4 54.0 70.3 82.9 99.8 116.9
Chilled Water Flow l/s 0.84 1.20 1.98 2.71 3.52 4.16 5.00 5.84
Unit Pressure Drop kPa 15 19 40 32 58 39 57 81
Air On: 24oC, 50% RH
Total Capacity kW 19.8 28.1 46.3 63.3 76.1 96.9 116.9 129.2
Sensible Capacity kW 19.8 28.1 46.3 63.3 73.2 96.9 116.9 121.6
Chilled Water Flow l/s 0.99 1.41 2.32 3.17 3.82 4.87 5.84 6.46
Unit Pressure Drop kPa 20 27 54 44 67 53 77 100
Airflow m3/hr 5665 7830 12420 16830 21235 25735 30330 34920
No. of Fans No. 1 1 1 2 2 3 3 4
Fan Motor kW 1.45 2.6 3.6 3.1 2.8 2.8 2.8 2.8
EC Fan Diameter mm 450 500 630 560 630 630 630 630
Electric Reheat kW 7.5 9.6 15.0 25.0 25.0 25.0 25.0 25.0
No. of Steps No. 2 2 2 2 2 2 2 2
Humidifier Capacity kg/hr 3 3 8 8 8 8 8 8
Humidifier Power kW 2.2 2.2 5.8 5.8 5.8 5.8 5.8 5.8
Notes:
1. Capacities are based on a 6oC / 7oC chilled water coil entering temperature & the tabulated flow rate.
2. For capacities at other conditions, please refer to the Factory or product selection program.
16
CHILLED WATER COOLED UNITS - COOLING CAPACITIES 50/60Hz
Model : Standard 066 086 126 166 206 246 286 326
Air On: 22oC, 50% RH
Total Capacity kW 16.8 24.2 41.6 57.1 72.0 89.1 106.4 124.5
Sensible Capacity kW 16.8 24.2 41.6 57.1 72.0 89.1 106.4 124.5
Chilled Water Flow l/s 0.71 1.01 1.74 2.39 3.01 3.73 4.46 5.19
Unit Pressure Drop kPa 9 12 29 25 33 36 53 74
Air On: 24oC, 50% RH
Total Capacity kW 20.4 29.2 49.4 67.7 85.5 105.5 125.4 146.3
Sensible Capacity kW 20.4 29.2 46.0 62.8 78.9 96.0 114.0 133.0
Chilled Water Flow l/s 0.85 1.22 2.07 2.83 3.57 4.40 5.25 6.10
Unit Pressure Drop kPa 13 18 42 35 46 49 72 101
Airflow m3/hr 5665 7830 12420 16830 21235 25735 30330 34920
No. of Fans No. 1 1 1 2 2 3 3 4
Fan Motor kW 1.45 2.6 3.6 3.1 2.8 2.8 2.8 2.8
EC Fan Diameter mm 450 500 630 560 630 630 630 630
Electric Reheat kW 7.5 9.6 15.0 25.0 25.0 25.0 25.0 25.0
No. of Steps No. 2 2 2 2 2 2 2 2
Humidifier Capacity kg/hr 3 3 8 8 8 8 8 8
Humidifier Power kW 2.2 2.2 5.8 5.8 5.8 5.8 5.8 5.8
Model : Standard 066 086 126 166 206 246 286 326
Air On: 22oC, 50% RH
Total Capacity kW 16.4 23.6 39.9 54.7 69.1 85.1 101.7 117.8
Sensible Capacity kW 16.4 23.6 39.9 54.7 69.1 85.1 101.7 117.8
Chilled Water Flow l/s 0.83 1.18 2.00 2.75 3.47 4.27 5.10 5.93
Unit Pressure Drop kPa 12 17 39 33 44 46 68 95
Air On: 24oC, 50% RH
Total Capacity kW 20.0 28.4 47.6 65.2 82.3 100.7 120.7 139.7
Sensible Capacity kW 20.0 28.4 45.1 61.7 77.5 94.3 112.1 129.2
Chilled Water Flow l/s 1.00 1.43 2.39 3.27 4.13 5.07 6.04 7.01
Unit Pressure Drop kPa 17 24 55 46 61 63 94 130
Airflow m3/hr 5665 7830 12420 16830 21235 25735 30330 34920
No. of Fans No. 1 1 1 2 2 3 3 4
Fan Motor kW 1.45 2.6 3.6 3.1 2.8 2.8 2.8 2.8
EC Fan Diameter mm 450 500 630 560 630 630 630 630
Electric Reheat kW 7.5 9.6 15.0 25.0 25.0 25.0 25.0 25.0
No. of Steps No. 2 2 2 2 2 2 2 2
Humidifier Capacity kg/hr 3 3 8 8 8 8 8 8
Humidifier Power kW 2.2 2.2 5.8 5.8 5.8 5.8 5.8 5.8
Notes:
1. Capacities are based on an 8oC / 9oC chilled water coil entering temperature & the tabulated flow rate.
2. For capacities at other conditions, please refer to the Factory or product selection program.
17
CHILLED WATER COOLED UNITS - COOLING CAPACITIES 50/60Hz
Notes:
1. Capacities are based on a 14oC / 15oC chilled water coil entering temperature & the tabulated flow rate.
2. For capacities at other conditions, please refer to the Factory or product selection program.
18
CHILLED WATER COOLED UNITS - COOLING CAPACITIES 50/60Hz
Notes:
1. Capacities are based on a 16oC / 17oC chilled water coil entering temperature & the tabulated flow rate.
2. For capacities at other conditions, please refer to the Factory or product selection program.
19
ELECTRICAL DETAILS
Air Cooled Models
Model 080 120 160 200 240 280
400V/3PH/50Hz
EC Fans FLA 4.1 4.2 4.9 4.2 4.2 4.2
Reheat FLA 13.9 21.7 35.9 35.9 35.9 35.9
Humidifier FLA 3.2 8.4 8.4 8.4 8.4 8.4
Scroll Compressor FLA 13.6 23.3 29 36.2 46.6 55.6
Condenser FLA 30°C 3.0 6.0 6.0 6.0 6.0 9.0
Condenser FLA 35°C 6.0 6.0 6.0 6.0 6.0 9.0
Condenser FLA 40°C 6.0 9.0 6.0 9.0 9.0 12.0
Condenser FLA 45°C 6.0 12.0 9.0 9.0 12.0 6.0
Condenser FLA 50°C 9.0 12.0 9.0 12.0 12.0 10.0
220V/3PH/60Hz
EC Fans FLA 7.5 7.6 8.9 7.6 7.6 7.6
Reheat FLA 25.2 39.4 65.6 65.6 65.6 65.6
Humidifier FLA 5.8 15.3 15.3 15.3 15.3 15.3
Scroll Compressor FLA 24.7 42.4 52.7 65.8 84.7 101.1
Condenser FLA 30°C 3.9 7.8 7.8 7.8 7.8 11.7
Condenser FLA 35°C 7.8 7.8 7.8 7.8 7.8 11.7
Condenser FLA 40°C 7.8 11.7 7.8 11.7 11.7 15.6
Condenser FLA 45°C 7.8 15.6 11.7 11.7 15.6 9.9
Condenser FLA 50°C 11.7 15.6 11.7 15.6 15.6 16.5
380V/3PH/60Hz
EC Fans FLA 4.3 4.4 5.1 4.4 4.4 4.4
Reheat FLA 13.2 20.6 34.3 34.3 34.3 34.3
Humidifier FLA 3.4 8.8 8.8 8.8 8.8 8.8
Scroll Compressor FLA 14.3 24.5 30.5 38.1 49.1 58.5
Condenser FLA 30°C 3.9 7.8 7.8 7.8 7.8 11.7
Condenser FLA 35°C 7.8 7.8 7.8 7.8 7.8 11.7
Condenser FLA 40°C 7.8 11.7 7.8 11.7 11.7 15.6
Condenser FLA 45°C 7.8 15.6 11.7 11.7 15.6 5.7
Condenser FLA 50°C 11.7 15.6 11.7 15.6 15.6 9.5
460V/3PH/60Hz
EC Fans FLA 3.6 3.7 4.3 3.7 3.7 3.7
Reheat FLA 15.9 24.9 41.5 41.5 41.5 41.5
Humidifier FLA 2.8 7.3 7.3 7.3 7.3 7.3
Scroll Compressor FLA 11.8 20.3 25.2 31.5 40.5 48.3
Condenser FLA 30°C 1.2 2.4 2.4 2.4 2.4 3.6
Condenser FLA 35°C 2.4 2.4 2.4 2.4 2.4 3.6
Condenser FLA 40°C 2.4 3.6 2.4 3.6 3.6 4.8
Condenser FLA 45°C 2.4 4.8 3.6 3.6 4.8 4.8
Condenser FLA 50°C 3.6 4.8 3.6 4.8 4.8 8.0
Notes:
1. FLA = Full Load Amps.
2. Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions. For units with
humidifier & electric reheat the maximum FLA would be in dehumidification mode ie. cooling & reheat or in cooling and
humidification mode ie. cooling & humidifier.
3. In dehumidification mode, calculate the max FLA based on 1x compressor FLA as only 1x compressor operates in this mode.
4. In cooling and humidification mode, calculate the max FLA based on dual compressor FLA as both compressors and the
humidifier operate in this mode.
5. For all models 2 no. condensers are required, 1 per refrigerant circuit.
6. For compressor & condenser FLA, tabulated values are per component.
ELECTRICAL DETAILS
20
Chilled Water Models - Standard
Model 064/6 084/6 124/6 164/6 204/6 244/6 284/6 324/6
400V/3PH/50Hz
EC Fans FLA 2.4 4.1 5.5 9.8 8.4 12.6 12.6 16.8
Reheat FLA 13.9 13.9 21.7 35.9 35.9 35.9 35.9 35.9
Humidifier FLA 3.2 3.2 8.4 8.4 8.4 8.4 8.4 8.4
Max Unit FLA - Cool only 3.4 5.1 6.5 10.8 9.4 13.6 13.6 17.8
Max Unit FLA - Cool & Dehumidify 17.3 19.0 28.2 46.7 45.3 49.5 49.5 53.7
Max Unit FLA - Heat & Humidify 20.5 22.2 36.6 55.1 53.7 57.9 57.9 62.1
220V/3PH/60Hz
EC Fans FLA 4.4 7.5 10.0 17.8 15.2 22.8 22.8 30.4
Reheat FLA 19.7 25.2 39.4 65.6 65.6 65.6 65.6 65.6
Humidifier FLA 5.8 5.8 15.3 15.3 15.3 15.3 15.3 15.3
Max Unit FLA - Cool only 5.4 8.5 11.0 18.8 16.2 23.8 23.8 31.4
Max Unit FLA - Cool & Dehumidify 25.1 33.7 50.4 84.4 81.8 89.4 89.4 97.0
Max Unit FLA - Heat & Humidify 30.9 39.5 65.7 99.7 97.1 104.7 104.7 112.3
380V/3PH/60Hz
EC Fans FLA 2.5 4.3 5.8 10.2 8.8 13.2 13.2 17.6
Reheat FLA 10.3 13.2 20.6 34.3 34.3 34.3 34.3 34.3
Humidifier FLA 3.4 3.4 8.8 8.8 8.8 8.8 8.8 8.8
Max Unit FLA - Cool only 3.5 5.3 6.8 11.2 9.8 14.2 14.2 18.6
Max Unit FLA - Cool & Dehumidify 13.8 18.5 27.4 45.5 44.1 48.5 48.5 52.9
Max Unit FLA - Heat & Humidify 17.2 21.9 36.2 54.3 52.9 57.3 57.3 61.7
460V/3PH/60Hz
EC Fans FLA 2.1 3.6 4.8 8.6 7.4 11.1 11.1 14.8
Reheat FLA 12.4 15.9 24.9 41.5 41.5 41.5 41.5 41.5
Humidifier FLA 2.8 7.3 7.3 7.3 7.3 7.3 7.3 7.3
Max Unit FLA - Cool only 3.1 4.6 5.8 9.6 8.4 12.1 12.1 15.8
Max Unit FLA - Cool & Dehumidify 15.5 20.5 30.7 51.1 49.9 53.6 53.6 57.3
Max Unit FLA - Heat & Humidify 18.3 27.8 38.0 58.4 57.2 60.9 60.9 64.6
Notes:
1. FLA = Full Load Amps.
2. Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions.
3. Max FLA of cooling only unit: FLA = Controls + Fans.
4. Max FLA of unit with reheat in dehumidification: FLA = Controls + Fans + Reheat.
5. Max FLA of unit with heating & humidifiers: FLA = Controls + Fans + Reheat + Humidifier.
21
ELECTRICAL DETAILS
Chilled Water Models – Fan Under Floor
Model 204/6 244/6 284/6 324/6
400V/3PH/50Hz
EC Fans FLA 11.0 12.6 16.5 16.8
Reheat FLA 35.9 35.9 35.9 35.9
Humidifier FLA 8.4 8.4 8.4 8.4
Max Unit FLA - Cool only 12.0 13.6 17.5 17.8
Max Unit FLA - Cool & Dehumidify 47.9 49.5 53.4 53.7
Max Unit FLA - Heat & Humidify 56.3 57.9 61.8 62.1
220V/3PH/60Hz
EC Fans FLA 20.0 22.8 30.0 30.4
Reheat FLA 65.6 65.6 65.6 65.6
Humidifier FLA 15.3 15.3 15.3 15.3
Max Unit FLA - Cool only 21.0 23.8 31.0 31.4
Max Unit FLA - Cool & Dehumidify 86.6 89.4 96.6 97.0
Max Unit FLA - Heat & Humidify 101.9 104.7 111.9 112.3
380V/3PH/60Hz
EC Fans FLA 11.6 13.2 17.4 17.6
Reheat FLA 34.3 34.3 34.3 34.3
Humidifier FLA 8.8 8.8 8.8 8.8
Max Unit FLA - Cool only 12.6 14.2 18.4 18.6
Max Unit FLA - Cool & Dehumidify 46.9 48.5 52.7 52.9
Max Unit FLA - Heat & Humidify 55.7 57.3 61.5 61.7
460V/3PH/60Hz
EC Fans FLA 9.6 11.1 14.4 14.8
Reheat FLA 41.5 41.5 41.5 41.5
Humidifier FLA 7.3 7.3 7.3 7.3
Max Unit FLA - Cool only 10.6 12.1 15.4 15.8
Max Unit FLA - Cool & Dehumidify 52.1 53.6 56.9 57.3
Max Unit FLA - Heat & Humidify 59.4 60.9 64.2 64.6
Notes:
1. FLA = Full Load Amps.
2. Unit maximum FLA is the total of the components, which operate during maximum electrical load conditions.
3. Max FLA of cooling only unit: FLA = Controls + Fans.
4. Max FLA of unit with reheat in dehumidification: FLA = Controls + Fans + Reheat.
5. Max FLA of unit with heating & humidifiers: FLA = Controls + Fans + Reheat + Humidifier.
22