WEEK 2 MODULE 2 - Process Instrumentation - Edited
WEEK 2 MODULE 2 - Process Instrumentation - Edited
MODULE 2:
Control System Instrumentation
Analog signals
- Analog signal transmission is made possible through the
development in solid state electronics
- They have been in use since 1960s
- The standard signal ranges for electronic analog instruments
are 4 – 20mA for current signal and 1 – 5V/1 – 12V for voltage
signals
- Current signal transmission is usually preferred over voltage
because voltage is affected by wire and connector resistances
that change with wire length, temperature and aging.
- Voltage signal transmission is better suited for short distances.
Generally analog signal transmission allow for signal transmission
over a long distance than pneumatic
Obafemi Awolowo University 9
Chemical Engineering
Instrumentation Signals and Data Networks
Digital signals
Digital instruments and devices became increasingly important starting
in the 1960s. A microprocessor in each instrument or controller is
responsible for communicating periodically over a data highway, either
receiving or requesting information from other devices.
A major advantage of digital communication is the significant reduction
in wiring and maintenance costs, compared to analog systems.
Major advances in computing equipment (e.g., microprocessors and
personal computers) and control technology during the 1970s and
1980s led to proprietary computer networks (i.e., distributed control
systems) and smart sensors with digital memory and logic
capabilities.
Gain=
0.16mA/oC
(2.1)
(2.2)
(2.3)
where is the steady-state gain
is the measurement time constant
Obafemi Awolowo University 17
Chemical Engineering
More Control Elements
Transducer: This is a device that can receive one type of energy and
convert it to another type of energy. E.g., Current to pressure transducer
(I/P).
Valve Positioners are devices used to put the valve in the correct
position by increasing or decreasing the air load pressure on the
actuator.
Valve positioners are used for controlling valve where accurate and
rapid control is required without error or hysteresis.
Usually, an I/P converter sends the opening-closing request to the
valve but cannot confirm the position of the valve actuator. The
process controller tells the required position to the positioner, and
the positioner senses the current position of the actuator and
compares with the required setpoint. Then give the control action
through the flapper-nozzle amplification system.
Fig.2.6a Fig.2.6b
(a) A–O (fail-close) to make sure (b) A–O (fail-close) to prevent the
that a transmitter failure will not reactor from being flooded with
cause the reactor to overheat, which excessive reactants.
is usually more serious than having it
operate at too low a temperature.
Fig.2.6d
Fig.2.6c
(2.4)
Fig. 2.7: Nonideal control valve behavior: (a) hysteresis; (b) deadband; (c) stick-slip
Actuator
Positioner
Body
(2.6)
(2.9)
(a) For five values of ΔPvd (10, 20, 40, 100, and 200 psi),
determine the
corresponding values of Cv, assuming the valve is half-
open.
(b) Determine the maximum and minimum values of q (qmax
and qmin) for each value of Cv.
Fig. 2.9: A control valve placed in series with a pump and other
equipment. Pump discharge pressure is constant.
Solution
(a) Recall,
(2.6)
(2.10)
(2.12b)
(2.14)
(2.15)
10 20 40 100 200
50 60 80 140 240
126.5 89.4 63.2 36.5 28.3
83 67 55 49 44
N.B.:
This example demonstrates that the choice of the ratio, (ΔPvd/ΔP),
is a key decision in control valve design. It represents an
engineering tradeoff between lower cost (small Cv) and more
effective control (large Cv).
Reported guidelines suggest values of 1/4 to 1/2 for this ratio at
the design flow rate. However, Example 2.2 demonstrates that the
range of operating conditions and the control objectives are
important and should be considered. Another rule of thumb is that
the control valve Cv should correspond to a size that is one less
than the size of the pipe diameter (Woods, 2007).
Three types of valve characteristic (or valve trim) are widely used. For a
fixed pressure drop across the valve ΔPv, the fractional flow rate,
is related to the fractional stem position by the
following valve trim relations:
(a) A linear valve that is half open at the design flow rate.
(b) An equal percentage valve (R = 50 in Eq.2.16c) that is sized to be
completely open at 110% of the design flow rate.
(c) Same as (b), except with a Cv that is 20% higher than
calculated.
(d) Same as (b), except with a Cv that is 20% lower than
calculated.
Fig. 2.11: A control valve placed in series with a pump and other equipment. Pump
discharge pressure is constant.
Solution
Recall, ΔPs = Kq2 (2.8)
where (2.17)
Thus, ΔPs = q2 (2.18)
(2.20)
Use , for an equal percentage valve,
(2.23)
(2.24)
N.B.:
Note that in all four cases, ΔPvd/ΔPs = 10/30 = 33%.
From the installed characteristics in Fig.2.13, we
conclude that an equal percentage valve with Cv =
115 would give a reasonably linear installed
characteristic over a large range of flow rates and
have sufficient capacity to accommodate flow rates as
high as 110% of the design flow rate.
(d) If the valves are now 10% open, determine the minimum flow rates
they can accommodate. By how much has this flow decreased wrt the
design flow?
(e) Calculate the turn down ratio for the two valves
(f) Which of the two valves will be preferred for installation and why?
, (2.27)
(2.28)
(2.29)
At the maximum flow rate, Eq.2.5 becomes:
(2.30)
Where (2.31)
Substituting Eq.2.29 into 2.31, we have:
(2.32)
Substituting Eq.2.32 into 2.30, we have:
(2.33)
(2.37)
(i) Data: , , , ,
gpm, psi
Substituting for the parameters in Eq.2.37, we have:
(2.38)
From where, gpm
The flow has decreased by 66.7% below the design value.
(ii) Data: , , , ,
gpm, psi
Substituting for the parameters in Eq.2.37, we have:
(2.39)
From where, gpm
The flow has decreased by 75.8% below the design value.
(e) Turn down ratio, (2.40)
Case (i): (2.41a)
Case (ii): (2.41b)
(f) Summary of Results
Valve I Valve II
Pressure drop(psi) 20 80
Cv 44.72 22.36
Range of flows (gpm) (33.3 – 115) (24.2 – 141)