The AJ-D Series Batch Controller from Silver Automation Instruments is designed to precisely measure and control batch quantities in flow applications. It can interface with various flow sensors, measure flow rate and totalized flow, and provide output signals. The controller also includes features like temperature compensation, alarm functions, communication interfaces, and batch control capability. It is suited for batching applications that require measuring quantities of liquids to within 0.2% accuracy.

Uploaded by

Butch Benavidez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views3 pages

Aj D Series Batch Controller

The AJ-D Series Batch Controller from Silver Automation Instruments is designed to precisely measure and control batch quantities in flow applications. It can interface with various flow sensors, measure flow rate and totalized flow, and provide output signals. The controller also includes features like temperature compensation, alarm functions, communication interfaces, and batch control capability. It is suited for batching applications that require measuring quantities of liquids to within 0.2% accuracy.

Uploaded by

Butch Benavidez
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

SILVER AUTOMATION INSTRUMENTS HTTP://WWW.SILVERINSTRUMENTS.

COM RUNYI GROUP

AJ-D Series Batch Controller

AJ-D series Batch Controller is suited to flow applications


where precise measurement and control of batch quantities
is required.
1
Overview
AJ-D series Batch Controller has the following main
Features:
 It is suitable for various liquid; it can display instant flow, totalized flow and control
purpose.
 Input a variety of flow sensor signals , such as vortex flow meter, turbine flow meter,
electromagnetic flow meter, roots flow meter, oval gear flow meter, orifice plate, V-cone flow
meter, Annubar, mass flow meter.,etc.
 Flow input channel: can receive frequency signal and a variety of analog current signals;
 Temperature input channel: can receive a variety of analog current signal;
 Can provide transmitter with +12V DC or + 24V DC power supply with short circuit
protection function, simplify the system;
 Fault-tolerant function: when temperature/density compensation measuring signal is
abnormal, carry out compensation operation manually and set the corresponding value;
 Flow re-transmission function, it can output current signal, update cycle is 1 second to
realize auto-control function.
 Meter clock and timing automatic meter reading function, print function, provides the
convenience for measurement management;
 Rich self-test and self diagnosis function makes it easy maintenance.
 Three password prevents unauthorized personnel changes.
 The instrument without any potentiometer, code switch adjustable device, so as to
improve the instrument seismic resistance, stability and reliability;
 Communication function: can carry out data communication through a variety of means
of communication with the host computer, RS-485; RS-232;

Main Technical Specification


1. Input signals
Analogue
• Resistance: Standard thermal resistance --Pt100;
• Current: 0~10mA, 4~20mA,input impedance≤250Ω)
Pulse
• Wave form: an rectangular shape, sine wave and triangular wave;
• Amplitude: more than 4V;
• Frequency: 0 ~ 10KHz (or according to user requirements).
2. Output signal
Analog output:
·DC 0~10mA(Load resistance≤750Ω);
SILVER AUTOMATION INSTRUMENTS HTTP://WWW.SILVERINSTRUMENTS.COM RUNYI GROUP

·DC 4~20mA(Load resistance≤500Ω);


3. Switch output
·Relay output –with hystersis, AC220V/3A; DC24V/6A(Resistance Load)
4. Communication
·Interface mode-RS232C,RS485,Ethernet;
·Baud rate:600, 1200, 2400, 4800,9600Kbps
5. Feed output 2
·DC24V,load≤100mA;
·DC12V,load≤200mA
6. Characteristics
Measuring accuracy: ± 0.2%FS ± 1 word or ± 0.5%FS ± 1 word
Frequency conversion accuracy: ± 1 pulse (LMS), generally better than 0.2%
Measuring range: -999999 ~ 999999 words (instantaneous, compensation value)
In 0 ~ 99999999.9999 words (Totalized value)
Resolution: ± 1 word
7. Display mode
• Historical cumulative flow, instantaneous flow, medium temperature, medium density,
flow (differential current, frequency), clock, alarm status;
8. Control / alarm
Select relay up/lower limit control (or alarm) output
Control (or alarm) is with hysteresis
Alarm: flow rate up and lower limit; temperature up and lower limit;
9. Protection
• Power accumulated value time more than 20 years;
• Automatic reset, power supply under pressure;
• Abnormal automatic reset (Watch Dog);
• Resettable fuse, short circuit protection.
10. Working environment
Environment temperature: -20 ℃~60 ℃
Relative humidity: ≤ 85%RH, avoid corrosive gas
11. Power supply
Conventional type: AC 220V % (50Hz ± 2Hz);
Special type: AC 80~265V switching power supply;
DC 24V ± 1V switching power supply;
Backup power: +12V, 20AH, can last 72 hours.
12. Power consumption
≤10W(AC220V)
SILVER AUTOMATION INSTRUMENTS HTTP://WWW.SILVERINSTRUMENTS.COM RUNYI GROUP

Dimensions

Sample
Vortex flow sensor to measure the quantity of hot water, average flow coefficient is 9.2187
pulses / L. With Pt100 temperature compensation. Each time we need to batch 10 tons of
water. Batch without password or IC card to confirm.