Nexus Control System - IO
Nexus Control System - IO
—I/O
www.bhge .com
Fully-covered Industrial Power Supply • Fuse for each DC branch
• Cabinet: Dual redundant 110V/220V
IO Types AC (±10%)
• Dimension: 127mm x 120mm x
23mm(High x Width x Depth)
Most of the applications could be
• Module: Dual redundant 24V DC
fulfilled by general IO modules (AI, Analog Input: MAI50 (MAI52)
(±10%)
AO, DI, DO, TC/RTD) with simplified IO • 16(8) Channels in 2(1) groups (8
design and reduced spare parts. The Environment channels in 1 group)
scalable system design can fit any • Working Temperature: -20~70℃ • Resolution: 16 bit
applications with different scope. • Humidity: 5-95% Relative (Non- • Signal Range: ±10V, ±5V, 0(4)-
Condensing) 20mA
Rugged IO with
Standard Cabinet • Accuracy: 0.1%
Distributed Installation • IP Rating: IP56
The feature of distributed installation • Channel to channel isolation:
• Cabinet Dimension: 250VAC
bring customer great feasibility to
800×600×2200mm (W×D×H)
install the IO modules inside or outside • Channel to ground isolation: 500VAC
the room, individually or in group. Field • Module Dimension:
• Channel to system isolation:
installation with equipment would save 209×129.5×51mm (H×W×D)
1500VAC
lots of cables and installation cost. • Capacity: 28 IO modules max
Temperature Input MAI51
Compact and low power consumption Regulation and Standard • 16 Channels in 2 groups
design make the IO module more • Certification: CE, FCC, UL, KC, CU-
reliable working in the harsh • Resolution: 16bit
TR, Russian Metrology, UL508A, CSA
environment with shock/vibration and C22.2 • RTD Type (2-wire or 3-wire): Pt10,
pollution. Pt100, Cu10, Cu50, BA1, Cu100,
• Safety Standard: IEC61010
Cu53
Higher availability • EMC Standard: IEC61326
• TC Type: E, J, K, N, R, S, T, B
with Fault-tolerant I/O Communication Bus: iLINK • Accuracy: 0.2%
Technology • Speed: 2Mbps
• Channel to ground isolation: 500VAC
Redundancy is the basic concept in • 1:1 Redundancy
• Channel to system isolation:
the system design including controller, • Capability: 14 IO modules per iLink 1500VAC
communication and power supply. The
• Time synchronization: ±100us
system can work normally without any Analog Input: MAI54
performances degrade at any single iLink Extension Module: MCD51 • 8 Channels, individual ADC
point failure situation. • Power Input: Dual 24V DC • Resolution: 16 bit
• Power Output: Dual 24V DC x 2 + 2 • Signal Range: ±10V, ±5V, 0(4)-20mA
Reduced Maintenance groups aux 24V DC (4 outputs/group)
• Accuracy: 0.1%
Cost • iLink extension input: Two DB-9
• Channel to channel isolation:1000VAC
High diagnostic coverage helps female connectors
customer to quickly identify any • Channel to ground isolation: 1000VAC
• iLink extension output: Four DB-9
defect or potential failure and fix it to male connectors (iLink R/iLink S, 2 • Channel to system isolation: 1500VAC
minimize un-planned outage. Hot-Swap pairs)
capability helps customer to conduct
online replacement.
Analog Output MAO50 Discrete Output MDO55(MDO56) Valve Position Control Module
• 8 Channels with individual DAC • 16 Channels Transistors output, MVP50
• Resolution: 12 bit souring(sinking) • 2 Channels LVDT Input
• Signal type: 0(4)-20mA, 0/1-5V • Output voltage: 24V/48V DC • 2 Channels Analog Input (±10V,
• Output Capability: 0.5A for each ±5V, 0(4) - 20mA)
• Accuracy: 0.2%
channel, total 2A for one module • 6 Channels Discrete Input
• Channel to ground isolation: 500VAC
• Aux Power Supply (MDO55): Dual • 2 Channels Servo Output (±40mA)
• Channel to system isolation: redundant 24/48V DC
1500VAC • 2 Channels Analog Output (0-5V)
Analog Input with HART MHT50 TMR Emergency Trip Module MLP50/
Discrete Input MDI50 (MDI52) • 8 Input Channels
• 32(16) Channels, Dry contact BLP50
• Resolution: 16 bit • Triple Redundancy Configuration
• Wetting Voltage: 48V DC (Internal
Provided) • Signal Range: ±10V, ±5V, 0(4)- • 3 Channels Speed Input
20mA • 42 Channels Discrete Input
• SOE Function
• Accuracy: 0.1% • 6 Channels Discrete Output
• Pulse Input Function, 0-1.5KHz
• Support HART protocol V5/V6/V7 • Onboard protection logic processing
• 220VAC Protection
• Channel to channel isolation: • 2 out of 3 hard-wired protection
• Channel to ground isolation: 500VAC 250VAC output voting
• Channel to system isolation: • Channel to ground isolation: 500VAC
1500VAC
• Channel to system isolation:
Discrete Input MDI53 1500VAC
• 16 Channels, dry contact
Analog Output with HART MHO50
• Wetting Voltage: 24/48/125 V DC • 8 Input Channels
• Aux Power: Dual Redundant 125V DC • Resolution: 12 bit
• Pulse Input 0-1.2KHz • Signal Range: 0(4)-20mA, 0/1-5V
• 220VAC Protection • Accuracy: 0.2%
• Channel to ground isolation: 500VAC • Support HART protocol V5/V6/V7
• Channel to system isolation: • Channel to ground isolation: 500VAC
1500VAC
• Channel to system isolation:
Discrete Output MDO53(MDO53A) 1500VAC
• 16 Channels Relay output (8 Relay
outputs+8 Discrete outputs) Speed Measuring & Protection
Module MSP50
• Relay Contact: 250VAC@12A; • 1 Channel Speed Input
30VDC@12A
• 6 Channels Analog Input
• Discrete output 24VDC@100mA
• 8 Channels Discrete Input
Discrete Output MDO54
• 6 Channels Discrete Output
• 16 Channels Transistors output
• Fail-safe output
• Output Capability: 24VDC @ 100mA
• Overspeed protection
• Pair with BDO20 to provide 220VDC
Relay output (500VAC@16A, • Load dump anticipation
220VDC@10A)
GE Digital Solutions