DMX-K-DRV-34 Integrated NEMA 34 Step Motor + Driver + Basic Controller Manual
DMX-K-DRV-34 Integrated NEMA 34 Step Motor + Driver + Basic Controller Manual
DMX-K-DRV-34 Integrated NEMA 34 Step Motor + Driver + Basic Controller Manual
Integrated
NEMA 34 Step Motor + Driver
+ Basic Controller
Manual
ARCUS TECHNOLOGY copyrights this document. You may not reproduce or translate into
any language in any form and means any part of this publication without the written permission
from ARCUS.
Revision History:
1.01 – 1st release
1.02 – 2nd release
1.03 – 3rd release
1.04 – 4th release
1.05 – 5th release
1.06 – 6th release
1.07 – 7th release
Firmware Compatibility:
†V12
†If your module’s firmware version number is less than the listed value, contact Arcus for the appropriate
documentation.
Features
DMX-K-DRV-34
DMX-K-DRV-34-
Notes:
o Standard sizes available for NEMA 34 are single and double.
o No motor option is available on special request. Minimum order quantity may
be required.
Figure 4.0
Table 4.0
Table 5.0
† Even though NEMA 34 triple stack motors are rated for 6.0A (RMS), maximum current DMX-
K-DRV-34 supports is 4.5A (peak).
Torque Curves
1 2
Figure 6.0
Table 6.0
Table 6.1
Interface Circuit
DMX-K-DRV-34
Figure 6.2
Two-clock uses CW as clockwise pulse input and CCW as counter clockwise pulse input for
position control.
Figure 6.3
Depending on the direction polarity setting, actual direction of the rotation can be configured for
the application.
Figure 6.4
Figure 6.5
Important Note: The recommended voltage between the differential inputs is 5V. An additional
current limiting resistor is required to support larger voltages.
Alarm Output
Alarm output is an opto-isolated output with 100 Ohm resistor.
Figure 6.6
Current Control
DMX-K-DRV-34 has a configurable current setting from 100mA to 4.5A peak current.
Driver current is set to Run Current when the pulse input is detected and remains in run current
while the pulse input is detected.
Idle Current is used when the pulse input is idle for the duration set by the Idle Time.
Run Current and the Idle Current should not go over the maximum rated current for each motor
size. Use the chart below as a reference on maximum rated current setting.
Table 7.0
The automatic temperature shutdown feature can be enabled or disabled during the configuration
process. Refer to Section 8 for further details.
DIO Control
The DMX-K-DRV-34 has built-in controller capability. When configured in controller mode, the
DIR, ENABLE, PUL and ALARM signals are used for DIO Control. See below for the signal
descriptions.
Table 7.1
Important Notes:
- While in controller mode, the motor is always enabled.
- If the direction signal is toggled while the enable signal is off, the alarm signal will
turn on because of its use in the Dynamic Configuration algorithm. Therefore, it is
advised to toggle the enable signal before selecting a motion profile. This will
prevent the alarm output from erroneously triggering.
Table 7.2
Assuming that the parameters shown in Table 7.2 are stored in the DMX-K-DRV-34, Figure 7.1
and Table 7.3 provide example usage of DIO control.
Table 7.3
Figure 7.1
6 1 0 0 DMX-K-DRV is idle.
Table 7.4
1) Microstep Setting: 1/2, 1/8, 1/10, 1/16, 1/20, 1/32, 1/40, 1/64
2) Run Current: 100mA to 4.5A peak current
3) Idle Current: 100mA to 4.5A peak current
4) Idle Time: 100 msec to 10 sec
5) Direction Polarity
6) One-clock or Two-clock mode
7) Controller or Driver mode:
A. Driver mode requires pulse and direction signals to move the motor.
B. Controller mode uses the Enable and Direction inputs to specify a set of
motion parameters and the Pulse input to start and stop motion.
8) Over Temperature Shutdown: Determines whether or not the DMX-K-DRV-34
disables when the temperature rises above a specified threshold. See Figure 7.0 for
details.
9) DIO motion parameters: Up to four motion profiles can be set and used when the
DMX-K-DRV-34 is in controller mode.
DMX-K-DRV-34 uses patented Dynamic Configuration Method to read and write the driver
parameters using the control signals (Pulse, Dir, Enable, and Alarm) of the driver. Dynamic
Configuration eliminates the need for jumpers, switches, resistors, potentiometers and
communication port for reading and setting the driver parameters. This results in a simple and
cost-effective device.
Table 7.0
Important Note: When setting the run and idle current, make sure to keep the current value
below the maximum allowed current that each motor can handle. Note the following maximum
current that each product can handle. See Table 8.0 for motor current specifications.
Motion
Profile Move Target Speed
Type Position
ENA DIR
0 0 ABS 10000 10000
Table 8.1
Configuration Cables
The DMX-CFG-USB-A2 is used to configure the DMX-K-DRV-34.
Connections
See Figures 8.0 to see how the configuration cables are connected to the DMX-K-DRV-34.
Figure 8.0
Software
Make sure that the USB driver is installed properly before running the controller. Note that
newer versions of the DMX-CFG-USB-A2 cables use HID protocol, which do not require USB
driver installation.
See the DMX-CFG-USB Cables manual for details on configuration. Figure 8.1 shows the
configuration interface.
DMX-K-DRV-34 should be mounted securely to a metallic bracket that can also act as a heat-
sink. During operation, the step motor section typically becomes hotter than the driver section.
Having the step motor mounted to a heat sink will help dissipate the heat generated by the step
motor.
DMX-K-DRV-34 mounting orientation should be such that the fins are oriented vertically for
better convection and heat dissipation. See Figure A.0 below.
Figure A.0
www.arcus-technology.com