05-01 1 HVAC Load Calculations Mechanical - HVAC
05-01 1 HVAC Load Calculations Mechanical - HVAC
ACCEPTABLE
Action Description
Yes No NA
1 Check the HVAC requirements for each space as follows:
d. Check the amount of outside air required to suit building pressurization, exhaust
requirements or based on number of occupants
e. Check for the ventilated spaces the number of air changes/hour required to suit a
minimum rate of change, a design space temperature or number of occupants
f. Check air flow required to a space for equipment that requires air to function properly
such as engines, compressors, cooking appliances
2 Check the outside weather air conditions as follows:
b. Check construction for verifying U-value (overall heat transfer coefficient) of each wall,
floor and ceiling. This will include exterior surface material, internal construction including
any insulation provided and the interior surface material.
c. Check solar heat loads on the walls and roof as applicable with their compass orientation
(north/south/east/west)
d. Check window area and verify U-value based on double pane, shading, tinting, etc.
c. Check for any equipment load (sensible and latent) and any use factor as applicable
d. Check for during the winter season any credit to be taken from heat generating equipment
within a room.
5 Check miscellaneous system loads:
d. Check weather air infiltration into the building – applies to air conditioned systems.
c. Check entering and leaving air temperatures (dry and wet bulb) at the cooling coil
d. Check rated capacity for other heaters not mounted in ducts. (Convection or unit heaters)
Revision Notes:
0. Revision 0 issue. December 2003.
1. Removed Comment Review Code Box. October 2007.