Starvert Ig5: Ower in Motion

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

ower in Motion

LG Variable Frequency Drive(VFD) : Inverter

Starvert iG5
0.37 - 4.0kW (0.5 - 5.4HP) 1 and 3 phase 200 - 230 Volts, 3 phase 380 - 460 Volts
Contents
Overview 02

Features & Selection Guide 04

Specifications & Wiring 06

Terminal Configuration, Keypad & Parameter Navigation 08

Program Parameter Descriptions 10

Dimension 12

DB Resistor, Options & Peripheral Devices 14


Overview

Standard features
kW / Voltage Ratings:
0.5 ~ 2HP, 200-230VAC, 1phase
0.5 ~ 5HP, 200-230VAC, 3phase
0.5 ~ 5HP, 380-460VAC, 3phase
Enclosure: IP00 ~ IP20
Inverter Type: PWM with IGBT
Control Method: Volts / Hertz with Space Vector Technology
Built-in RS-485
Built-in ModBus-RTU
Compact iG5, Built-in PID control
is the best for a small and cost Removable keypad (Able to read & write parameter)
150% torque at 0.5Hz
effective configuration. Trip-free operation algorithm
8 preset speeds
3 jump(skip) frequencies
3 Multifuctional inputs
1 Multifuctional output
Analog output (0~12V)
PNP and NPN dual directional signals
Speed search
3 wire operation
1 to 10 kHz carrier frequency
Built-in Braking transistor
Manual/Auto torque boost

Options
Cable for Remote Keypad Operations(2,3 and 5 meters)
DIN rail base for easy installation

Application
Converting Commercial washing machine
Fan Grinder
Pump Textile machine
Food processing machine Material handling machine
Electric shutter Centrifuge
Dryer Elevator door
Running machine Tooling machine
Overheat

Conformity to global standards


UL and cUL listed for North America
CE marked for Europe
Quality process controlled by ISO9001, ISO14000

02
Starvert iG5

Reduced size
Enhancing its performance the iG5 shows much smaller size
compares to the previous model, the iG series.
Maximum 50% of total volume has been reduced in iG5 in order to
mount it easily on smaller control panel and DIN rail with less weight.
It allows more cost effective panel construction and system design.

Built-in communication interface and PC monitoring software


The iG5 has built-in the most popular communication interfaces such as Modbus-RTU and RS232/485.
The iG5 has the small inverter features and standard medium drive features together.
The "DriveviewTM" software offers Window® based computer monitoring tool through RS485 interface with
graphic capture, keypad emulator, parameter edit and text monitor. It is applicable for all LG inverters.

RS - 485
TM
ModBus-RTU

Built-in PID control


It is valuable in process control. The built-in PID controller controls flow, temperature, pressure, etc.
through the proportional, integral and differential calculus between the feedback value and reference
value in closed loop.

Space vector PWM technology


The Space vector technology is being adopted in all LG drives. It features outstanding performance in its
control characteristics. It has low total harmonic distortion, low current ripple, low torque ripple, low motor
temperature rise, and better voltage utilization. It is a basic control platform of the iG5 drive. The advantages of
Space vector PWM technology are being proved in many applications.

Better Efficiency (Low Iron Loss in Motor)


Low Total
Harmonic Distortion Low Motor Heat (Extended Motor)

High Voltage Utilization (15.9%)


Low Torque Ripple Low Current Ripple
Stable & Smooth Operation

High and Stable Torque

03
Features & Selection Guide

Optimum acceleration and deceleration


To achieve a maximum torque during the acceleration and deceleration, "trip free" function is activated.
The 32-bit DSP CPU monitors the current transition during the acceleration and deceleration to program an
optimum curve that is under the trip-triggering level.
Stopped Stopped
CH1=2V CH3=5V CH4=2V 1s/div CH1=2V CH3=5V CH4=2V 1s/div
DC 10:1 DC 10:1 DC 10:1 [1s/div] DC 10:1 DC 10:1 DC 10:1 [1s/div]
NORM:1kS/s NORM:1kS/s

Trip
=Filter= =Offset= =Record Length= =Trigger= =Filter= =Offset= =Record Length= =Trigger=
Smoothing : OFF Ch1 : 0.00V Main : 10k Mode : AUTO Smoothing : OFF Ch1 : 0.00V Main : 10k Mode : AUTO
BW : FULL Ch2 : 0.00V Zoom : 500 Type : EDGE CH1 BW : FULL Ch2 : 0.00V Zoom : 500 Type : EDGE CH1
CH3 : 0.00V Delay : 0.0ns CH3 : 0.00V Delay : 0.0ns
CH4 : 0.00V Hold Off : MINIMUM CH4 : 0.00V Hold Off : MINIMUM

Traditional curve Optimum curve

PNP and NPN switchable duals signals


The iG5 has both PNP and NPN signals in order to controlled by PLC or outside controller.
Regardless the type of PLC or type of control signal, iG5 can work with positive 24Vdc and negative 24Vdc.

Inverter rating selection guide

Inverter type nomenclature


SV 008 iG5 -4

LG Starvert drive

004 0.37kW iG5 iG5 series -1 1 phase 200~230V

008 0.75kW iS5 iS5 series -2 3 phase 200~230V

015 1.5kW iH iH series* -4 3 phase 380~460V


. . iV5 iV5 series
* iH drive has a different designation in kW.
220 22kW

04
Starvert iG5

Specifications 200 ~230V Class(0.5~ 5.4 HP)


Drive Type (SV_ _ _iG5-_) 004-1 008-1 015-1 004-2008-2 015-2 022-2 037-2 040-2
1) [HP] 0.5 1 2 0.5 1 2 3 5 5.4
Motor Rating* [kW] 0.37 0.75 1.5 0.370.75 1.5 2.2 3.7 4
2)
Capacity[kVA]* 1.1 1.9 3 1.1 1.9 3 4.5 6.1 6.5
Output ratings FLA[A] 3 5 8 3 5 8 12 16 17
Frequency 0 ~ 400 Hz 3)
Voltage 200 ~ 230V*
Voltage 1 phase 200 ~ 230 V( 10%) 3 phase 200 ~ 230 V( 10%)
Input ratings
Frequency 50 ~ 60 Hz ( 5%) 50 ~ 60 Hz ( 5%)
Weight[kg] 1.2 1.8 2.1 1.2 1.2 1.8 2.1 2.2 2.2
Braking circuit On board
Average braking torque 20% (with optional external braking resistor : 100%, 150%)
Braking torque Max. continuous braking time 15 seconds
Max. duty 0 ~ 30 % ED
Cooling method Forced air cooling Natural Forced air cooling
Enclosure IP00

Specifications 380 ~460V Class(0.5~ 5.4 HP)


Drive Type (SV_ _ _iG5-_) 004-4 008-4 015-4 022-4 037-4 040-4
1) [HP] 0.5 1 2 3 5 5.4
Motor Rating*
[kW] 2)
0.37 0.75 1.5 2.2 3.7 4
Capacity[kVA]* 1.1 1.9 3 4.5 6.1 6.5
FLA[A] 1.1 2.5 4 6 8 9
Output ratings
Frequency 0 ~ 400 Hz 3)
Voltage 380 ~ 460V*
Voltage 3 phase 380 ~ 460 V( 10%)
Input ratings
Frequency 50 ~ 60 Hz ( 5%)
Weight[kg] Weight [kg] 1.7 1.7 1.8 2.1 2.2 2.2
Braking circuit On board
Average braking torque 20% (with optional external braking resistor : 100%, 150%)
Braking torque
Max. continuous braking time 15 seconds
Max. duty 0 ~ 30 % ED
Cooling method Forced air cooling
Enclosure IP00
*1) Indicates the maximum applicable capacity when using 4 pole LG standard motor.
*2) Rated capacity ( 3*V*I) is based on 220V for 200V class and 440V for 400V class.
*3) Maximum output voltage will not be greater than the input voltage. Output voltage less than the input voltage can be set.

Control method V/F control


Frequency setting resolution Digital reference : 0.01 Hz (below 100 Hz), 0.1 Hz (over 100 Hz) Analog reference : 0.03 Hz / 50 Hz
Frequency accuracy Digital : 0.01% of max. output frequency Analog : 0.1% of max. output frequency
Control V/F ratio Linear, Square pattern, User V/F
Overload capacity 150 % of rated current for 1 min., 200% of rated current for 0.5 sec. (characteristic is inversely proportional to time)
Torque boost Manual torque boost (0 ~ 15 %), Auto torque boost
Operation method Keypad / terminal / communication operation
Frequency setting Analog : 0 ~ 10V / 4 ~ 20 mA Digital : keypad
Start signal Forward, Reverse
Multi-step Up to 8 speeds can be set (use multi-function terminal)
Input signal

Multi-step accel/decel time 0 ~ 6,000 sec, up to 8 types can be set and selected for each setting (use the multi- function terminal),
Accel/Decel pattern : linear pattern, U pattern, S pattern, Optimum, Minimum
Emergency stop Interrupts the output of the drive
Operation Jog Jog operation
Fault reset Resets fault when protective function is active
Output signal

Operation status Frequency level detection, Overload alarm, stalling, overvoltage, undervoltage, drive overheating, running, stop,
constant speed, speed searching
Fault output Contact output (30A,30C,30B) - AC250V 1A, DC30V 1A
Indicator Choose 1 from output frequency, output current, output voltage, DC voltage (Output pulse: 500Hz, Output voltage: 0 ~ 10V)
Operation DC braking, frequency limit, frequency jump, second function, slip compensation, reverse rotation prevention,
function auto restart, PID control
Drive trip Overvoltage, undervoltage, overcurrent, drive overheating, motor over heating, input/output phase loss,
Protective input/output mis-wiring, overload protection, communication error, loss of speed command, hardware fault.
function Inverter alarm Stall prevention, overload alarm
Momentary power loss Less than 15 msec : continuous operation, more than 15 msec : auto restart possible
Display Operation information Output frequency, output current, output voltage, frequency value setting, operating speed, DC voltage
Keypad Trip information Indicates the fault when the protection function activates, memorizes up to 5 faults
Ambient temperature -10 °C ~ 40 °C
Storage temperature -20 °C ~ 65 °C
Environment Ambient humidity 90 % RH max.(Non condensing)
Altitude . Vibration Below 1,000 m ˙ below 5.9m/sec2(=0.6g)
Application site No corrosive gas, combustible gas, oil mist, or dust

05
Specifications & Wiring

Wiring

DB Resistor*2

B1 B2
MCCB
1ø 230V
R U
or
3ø S V MOTOR
230/460V
50/60Hz T W

24 +
FM FM
Forward Run/Stop Output Frequency Meter
FX (0 ~ 12V : pulse output)
Reverse Run/Stop
RX CM
Drive gate block
BX
Fault Reset RST
Jog
JOG
Multi-function Input 1 P1 Factory Setting
Multi-function Input 2 `Speed-L`
P2
`Speed-M`
Multi-function Input 3 P3 `Speed-H`
A Fault output relay
Common Terminal Iess than AC250V, 1A
CM C
Iess than DC30V, 1A
B
Shield
Potentiometer
MO
(1kohm, 1/2W) Multi-function output
Power supply for
VR speed signal: Iess than DC24V, 50mA
MG
+12V, 100mA Factory setting:`RUN`

V1 Speed signal input:


0 ~10V
Speed signal input: S+ ModBus-RTU
I Communication port
4 ~ 20mA(250ohm)
S- RS-485

CM Common for
VR, V1, I
Speed signal Input*1

Note) " " display main circuit terminals, " " display control circuit terminals.
1. Analog speed command can be set by Voltage, Current and both of them.
2. DB resistor is optional.

06
Starvert iG5

Power terminal configuration


Symbol Function
R
S AC Line input (1 phase 200~230 Vac for "-1" units 3 phase, 200~230 Vac for "-2" units and 380~460 Vac for "-4" units)
T
U
V 3 phase output terminals to motor
W
B1
External additional dynamic braking resistor connection terminals.
B2
G Chassis ground (The gound terminal("G") may be located on heat sink instead of terminal strip depend on the model name)

Control terminal configuration


Type Symbol Name Descripton
P1, P2, P3 Multi function input 1,2,3 Used for multi function input. Factory default is set to step frequency 1, 2, 3.
FX Forward run command Forward run when closed and stop when opened.
RX Reverse run command Reverse run when closed and stop when opened.
JOG Jog frequency reference Runs at jog frequency when the jog signal is on. The direction is set by the FX (or RX) signal.
Input signal

Starting Contact
BX Drive gate block When the BX signal is ON, the output of the drive is cut off. When the motor uses an mechanical brake to stop,
Function Slection
BX is used to cut off the output signal. When the BX signal, which does not cut off by latching, is OFF and the
FX signal (or the RX signal) is ON, the motor keeps running, so be cautious.
RST Fault reset Used to release the protective status when the protective circuit is active.
CM Sequence common Used for the common terminal for contact input terminals.
VR Frequency setting power(+12V) Used as power for the analog frequency setting. Maximum output is +12V, 100mA.
Analog Frequency V1 Frequency reference (Voltage) Used for frequency reference and uses 0-10V for input. Input resistance is 20 k
Setting I Frequency reference(Current) Used for frequency reference and uses DC 4-20mA for input. Input resistance is 250
CM Frequency setting common terminal Common terminal for the analog frequency reference signal and the FM (for monitoring).
FM.CM Analog/digital output Outputs one of the followings: output frequency, output current, output voltage, DC link voltage.
Pulse (For external monitoring) Factory default is set to output frequency. Maximum output voltage and output current is 0-12V, 1mA.
Output signal

Output frequency is set to 500Hz.


30A, 30C, 30B Fault contact output Activates when the protective function is operating. AC250V 1A or less, DC30V 1A or less
Fault : 30A-30C short (30B-30C open)
Contact Nomal : 30A-30C short (30B-30C open)
MO.MG Multi-function output
Used for multi-function output
(Open collector output)
RS232 S+, S- Communication port Communication ports for RS-485

Keypad
Class Display Name Description
FUNC Program key Press to change the parameter setting.
UP Up key Press to move through codes or to increase the parameter values.
KEY DOWN Down key Press to move through codes or to decrease the parameter values.
RUN Run key Use to operate the drive
STOP/RESET STOP/RESET key Press to stop during operation. Press to reset when a fault has occurred.
REV Reverse run During reverse run.
FWD Forward run During forward run.
LED
SET Setting When the user is setting the parameters using the FUNC key
RUN Operating When in constant speed and blinks when accelerating or decelerating.

Parameter group Group name Description

Drive Group Basic parameters of Command frequency, Accel/Decel time etc.

Function 1 Group Basic parameters of Max. Frequency, Torque boost etc.

Function 2 Group Application parameters of Frequency jump, Frequency limit etc.

Input / Output Group Multifunction terminal setting and Sequence operation parameters

07
Terminal Configuration, Keypad & Parameter Navigation

Parameter navigation

1. Drive Group SET FWD

RUN REV

SET FWD SET FWD

RUN REV RUN REV

SET FWD SET FWD

RUN REV RUN REV

SET FWD SET FWD

RUN REV RUN REV

SET FWD SET FWD

RUN REV RUN REV

SET FWD SET FWD

RUN REV RUN REV

SET FWD SET FWD

RUN REV RUN REV

SET FWD SET FWD

RUN REV RUN REV

SET FWD SET FWD

RUN REV RUN REV

2. Function Group 3. I/O Group

SET FWD SET FWD

RUN FU I REV RUN I0 REV

FUNC FUNC

SET FWD SET FWD

RUN F O REV RUN I 0 REV

SET FWD SET FWD

RUN REV RUN REV

FUNC FUNC

SET FWD SET FWD

RUN FU I REV RUN I0 REV

08
Program parameter descriptions
1. Drive Group [DRV]
Factory Adjustable
Code Description Keypad Display Setting Range Units
Default during run
DRV-00 Output Frequency during running, Reference Frequency during stop 0.00 0 to Max. Freq. (FU1-20) 0.01 60.00 [Hz]* Yes
DRV-01 Acceleration Time ACC 0 to 6000 [sec] 0.1 10.0 [sec] Yes
DRV-02 Deceleration Time 0 to 6000 [sec] 0.1 10.0 [sec] Yes
DRV-03 Drive Mode (Run/Stop method) 0 (keypad) - 1 No
1 (Keypad-2)
2 (Fx/Rx-2)
3 (ModBus-RTU)
DRV-04 Frequency Mode (Freq. setting method) 0 [Keypad-1] - 0 No
1 (Keypad-2)
2 (V1)
3 (I)
4 (V1+I)
5 (ModBus-RTU)
DRV-05 Step Frequency 1 Starting freq (FU1-22) Yes
to Max. freq (FU1-20) 0.01 10.00 [Hz]
DRV-06 Step Frequency 2 0.01 20.00 [Hz]
DRV-07 Step Frequency 3 0.01 30.00 [Hz]
DRV-08 Output Current * [A] - - [A] -
DRV-09 Motor Speed * [rpm] - - [rpm] -
DRV-10 DC link Voltage * [V] - - [V] -
DRV-11 User Display selection , , Selected in FU2-73 - - -
(User disp)
DRV-12 Fault Display - - nOn -
DRV-13 Motor Direction set F (Forward) r (Reverse) F Yes
DRV-20 FU1 Group selection
DRV-21 FU2 Group selection
DRV-22 I/O Group selection

2. Function Group1[FU1]
FU1-00 Jump to desired code # F0 1 to 99 1 3 Yes
FU1-03 Run Prevention F3 0 (None) 0 No
1 (Forward Prev)
2 (Reverse Prev)
FU1-05 Acceleration Pattern F5 0 (Linear) 0 No
1 (S-curve)
2 (U-curve)
3 (Minimum)
4 (Optimum)
FU1-06 Deceleration Pattern F6 0 (Linear) 0 No
1 (S-curve)
2 (U-curve)
3 (Minimum)
4 (Optimum)
FU1-07 Stop Mode F7 0 (Decel) 0 No
1 (DC-brake)
2 (Free-run)
FU1-08 DC Injection Braking Frequency F8 FU1-22 to 50 [Hz] 0.01 5.00 [Hz] No
FU1-09 DC Injection Braking On-delay Time F9 0 to 60 [sec] 0.01 0.5 [sec] No
FU1-10 DC Injection Braking Voltage FI0 0 to 200 [%] 1 50 [%] No
FU1-11 Starting DC Injection Braking Time FI I 0 to 60 [sec] 0.1 1.0 [sec] No
FU1-12 Starting DC Injection Braking Voltage FI2 0 to 200 [%] 1 50 [%] No
FU1-13 Starting DC Injection Braking Time FI3 0 to 60 [sec] 0.1 0.0 [sec] No
FU1-20 Maximum Frequency F20 40 to 400 [Hz] 0.01 60.00 [Hz]* No
FU1-21 Base Frequency F2 I 30 to FU1-20 0.01 60.00 [Hz]* No
FU1-22 Starting Frequency F22 0.1 to 10 [Hz] 0.01 0.50 [Hz] No
FU1-23 Frequency Limit selection F23 0 (No) - No
1 (Yes)
FU1-24 Low Limit Frequency F24 FU1-22 to FU1-25 0.01 0.50 [Hz] No
FU1-25 High Limit Frequency F25 FU1-24 to FU1-20 0.01 60.00 [Hz]* No
FU1-26 Manual/Auto Torque Boost selection F26 0 (Manual) - 0 No
1 (Auto)
FU1-27 Torque Boost in Forward Direction F27 0 to 15 [%] 0.1 5.0 [%] No
FU1-28 Torque Boost in Reverse Direction F28 0 to 15 [%] 0.1 5.0 [%] No
FU1-29 Volts/Hz Pattern F29 0 (Linear) - 0 No
1 (Square)
2 (User V/F)
FU1-30 User V/F - Frequency 1 F30 0 to FU1-32 0.01 15.00 [Hz]* No
FU1-31 User V/F - Voltage 1 F3 I 0 to 100 [%] 1 25 [%] No
FU1-32 User V/F - Frequency 2 F32 FU1-30 to FU1-20 0.01 30.00 [Hz]* No
FU1-33 User V/F - Voltage 2 F33 0 to 100 [%] 1 50 [%] No
FU1-34 User V/F - Frequency 3 F34 FU1-32 to FU1-20 0.01 45.00 [Hz]* No
FU1-35 User V/F - Voltage 3 F35 0 to 100 [%] 1 75 [%] No
FU1-36 User V/F - Frequency 4 F36 FU1-34 to FU1-20 0.01 60.00 [Hz]* No
FU1-37 User V/F - Voltage 4 F37 0 to 100 [%] 1 100 [%] No
FU1-38 Output Voltage Adjustment F38 40 to 110 [%] 0.1 100[%] No
FU1-39 Energy Save Level F39 F39 0 to 30 [%] 1 0 [%] Yes
FU1-50 Electronic Thermal selection F50 0 (No) - 0 Yes
1 (Yes)
FU1-51 Electronic Thermal Level for 1 minute F5 I FU1-52 to 150 [%] 1 150 [%] Yes
FU1-52 Electronic Thermal Level for continuous F52 50 to FU1-51 1 150 [%] Yes
FU1-53 Electronic Thermal Characteristic selection (Motor type) F53 0 (Self-cool) - 0 Yes
1 (Forced-cool)
09
Program Parameter Descriptions

Factory Adjustable
Code Description Keypad Display Setting Range Units
Default during run
FU1-54 Overload Warning Level F54 30 to 150 [%] 1 150 [%] Yes
FU1-55 Overload Warning Hold Time F55 0 to 30 [sec] 0.1 10.0 [sec] Yes
FU1-56 Overload Trip selection F56 0 (No) - 1 Yes
1 (Yes)
FU1-57 Overload Trip level F57 30 to 200 [%] 1 180 [%] Yes
FU1-58 Overload Trip Delay Time F58 0 to 60 [sec] 1 60.0 [sec]
FU1-59 Stall Prevention Mode selection F59 000 - 111 (bit set) bit 000 No
Bit 0: during Accel.
Bit 1: during Steady speed
Bit 2: during Decel.
FU1-60 Stall Prevention Level F60 30 to 150 [%] 1 150 [%] No
FU1-99 Return Code - - -

3. Function Group2 [FU2]


FU2-00 Jump to desired code # H0 1 to 99 1 30 Yes
FU2-01 Previous Fault History 1 HI - - 0 Yes
FU2-02 Previous Fault History 2 H2 nOn Yes
FU2-03 Previous Fault History 3 H3 nOn
FU2-04 Previous Fault History 4 H4 nOn Yes
FU2-05 Previous Fault History 5 H5 nOn
FU2-06 Erase Fault History H6 0 (No) - 0 Yes
1 (Yes)
FU2-07 Dwell Frequency H7 0 to FU1-20 0.01 5.00 [Hz] No
FU2-08 Dwell Time H8 0 to 10 [sec] 0.1 0.0 [sec] No
FU2-10 Frequency Jump selection HI0 0 (No) - 0 No
1 (Yes)
FU2-11 Jump Frequency 1 Low HI I FU1-22 to FU2-12 0.01 0.00 [Hz] No
FU2-12 Jump Frequency 1 High HI2 FU1-11 to FU2-20 0.01 0.00 [Hz] No
FU2-13 Jump Frequency 2 Low HI3 FU1-22 to FU2-14 0.01 0.00 [Hz] No
FU2-14 Jump Frequency 2 High HI4 FU2-13 to FU1-20 0.01 0.00 [Hz] No
FU2-15 Jump Frequency 3 Low HI5 FU1-22 to FU2-16 0.01 0.00 [Hz] No
FU2-16 Jump Frequency 3 High HI6 FU2-15 to FU1-20 0.01 0.00 [Hz] No
FU2-19 Input/Output Phase Loss Protection HI9 00 - 11 (bit set) - 00 Yes
Bit 0: Output phase
loss protection
Bit 1: Intput phase
loss protection
FU2-20 Power ON Start selection H20 0 (No) - 0 Yes
1 (Yes)
FU2-21 Restart after Fault Reset H2 I 0 (No) - 0 Yes
1 (Yes)
FU2-22 Speed Search selection H22 0000 - 1111 (bit set) - 0000 No
Bit 0: during Accel.
Bit 1: after fault reset
Bit 2: after instant power
failure restart
Bit 3: when FU2-20 is set to
1 (Yes).
FU2-23 Current Limit Level during Speed Search H23 80 to 200 [%] 1 100 [%] Yes
FU2-24 P Gain during Speed Search H24 0 to 9999 1 100 Yes
FU2-25 I Gain during speed search H25 0 to 9999 1 1000 Yes
FU2-26 Number of Auto Restart Attempt H26 0 to 10 1 0 Yes
FU2-27 Delay Time before Auto Restart H27 0 to 60 [sec] 0.1 1.0 [sec] Yes
FU2-30 Rated Motor selection H30 0.4 (0.37kW) 0.8 (0.75kW) - No
1.5 (1.5kW) 2.2 (2.2kW)
FU2-31 Number of Motor Poles H3 I 2 to 12 1 4 No
FU2-32 Rated Motor Slip H32 0 to 10 [Hz] 0.01 No
FU2-33 Rated Motor Current in RMS H33 0.1 to 99.9 [A] 1 No
FU2-34 No Load Motor Current in RMS H34 0.1 to 99.9 [A] 1 No
FU2-36 Motor Efficiency H36 50 to 100 [%] 1 No
FU2-37 Load Inertia H37 0 to 2 1 0 No
FU2-39 Carrier Frequency H39 1 to 10 [kHz] 1 3 kHz Yes
FU2-40 Control Mode selection H40 0 (V/F) - 0 No
1 (Slip Compen)
2 (PID)
FU2-50 PID Feedback Signal selection H50 0 (I) - 0 No
1 (V1)
FU2-51 P Gain for PID Control H5 I 0 to 9999 1 3000 Yes
FU2-52 I Gain for PID Control H52 0 to 9999 1 300 Yes
FU2-53 D Gain for PID Control H53 0 to 9999 1 0 Yes
FU2-54 Limit Frequency for PID Control H54 0 to FU1-20 0.01 60.00 [Hz]* Yes
FU2-70 Reference Frequency for Accel and Decel H70 0 (Max Freq) - 0 No
1 (Delta Freq)
FU2-71 Accel/Decel Time Scale H7 I 0 (0.01 sec) - 1 Yes
1 (0.1 sec)
2 (1 sec)
FU2-72 Power On Display H72 0 (Cmd. Freq) 1 (Acc. Time) 1 0 Yes
2 (Dec. Time) 3 (Drv mode)
4 (Freq mode) 5 (Step Freq 1)
6 (Step Freq 2) 7 (Step Freq 3)
8 (Current) 9 (Speed)
10(DC link Vtg) 11 (User disp)
12 (Fault Display)
13 (Motor direction)
10
Starvert iG5

Factory Adjustable
Code Description Keypad Display Setting Range Units
Default during run
FU2-73 User Display selection H73 0 (Voltage) - 0 Yes
1 (Watt)
2 (Torque)
FU2-74 Gain for Motor Speed Display H74 1 to 1000 [%] 1 100 [%] Yes
FU2-75 DB(Dynamic Braking)Resistor H75 0 [None] - 0 Yes
Mode selection 1 [None]
2 (Ext.DB-R)
FU2-76 Duty of Dynamic Braking Resistor H76 0 to 30 [%] 1 10 [%] Yes
FU2-79 Software Version H79 - . E -
FU2-81 2nd Acceleration Time H8 I 0 to 6000 [sec] 0.1 5.0 [sec] Yes
FU2-82 2nd Deceleration Time H82 0 to 6000 [sec] 0.1 10.0 [sec] Yes
FU2-83 2nd Base Frequency H83 30 to FU1-20 0.01 60.00 [Hz]* No
FU2-84 2nd V/F Pattern H84 0 (Linear) - 0 No
1 (Square)
2 (User V/F)
FU2-85 2nd Forward Torque Boost H85 0 to 15 [%] 0.1 5.0 [%] No
FU2-86 2nd Reverse Torque Boost H86 0 to 15 [%] 0.1 5.0 [%] No
FU2-87 2nd Stall Prevention Level H87 30 to 150 [%] 1 150 [%] No
FU2-88 2nd Electronic Thermal Level for 1 minute H88 FU2-89 to 150 [%] 1 150 [%] Yes
FU2-89 2nd Electronic Thermal Level for continuous H89 50 to FU2-88(maximum 150%) 1 100 [%] Yes
FU2-90 2nd Rated Motor Current H90 0.1 to 99.9 [A] 0.1 1.8 [A] No
FU2-91 Read Parameters into Keypad from Inverter H9 I 0 (No) - 0 No
1 (Yes)
FU2-92 Write Parameters to Inverter from Keypad H92 0 (No) - 0 No
1 (Yes)
FU2-93 Initialize Parameter H93 0 (No) - 0 No
1 (All Groups)
2 (DRV)
3 (FU1)
4 (FU2)
5 (I/O)
FU2-94 Parameter Write Protection H94 0 to 255 1 0 Yes
FU2-99 Return Code - 1 Yes

4.Input / Output Group [I/0]


Factory Adjustable
Code Description Keypad Display Setting Range Units
Default during run
I/O-00 Jump to desired code # I 0 1 to 99 1 1 Yes
I/O-01 Filtering Time Constant for V1 Signal Input I I 0 to 9999 [ms] 1 1,000 [ms] Yes
I/O-02 V1 Input Minimum Voltage I 2 0 to I/O-04 0.01 0.00 [V] Yes
I/O-03 Frequency corresponding to V1 Input Minimum Voltage I 3 0 to FU1-20 0.01 0.00 [Hz] Yes
I/O-04 V1 Input Maximum Voltage I 4 I/O-02 to 10 [V] 0.01 10.00 [V] Yes
I/O-05 Frequency corresponding to V1 Input Maximum Voltage I 5 0 to FU1-20 0.01 60.00 [Hz]* Yes
I/O-06 Filtering Time Constant for I Signal Input I 6 0 to 9999 [ms] 1 1,000 [ms] Yes
I/O-07 I Input Minimum Current I 7 0 to I/O-09 0.01 4.00 [mA] Yes
I/O-08 Frequency corresponding to I Input Minimum Current I 8 0 to FU1-20 0.01 0.00 [Hz] Yes
I/O-09 I Input Maximum Current I 9 I/O-07 to 20 [mA] 0.01 20.00 [mA] Yes
I/O-10 Frequency corresponding to I Input Maximum Current I I0 0 to FU1-20 0.01 60.00 [Hz]* Yes
I/O-11 Criteria for Analog Input Signal Loss I II 0 (None) - 0 Yes
1 (Half of x1)
2 (Below x1)
I/O-12 Multi-function Input Terminal 'P1' define I I2 0 (Speed-L) - 0 No
8,9, 15, 20, 21, 22, 23, 24, 25, 26(-Reserved-) 1 (Speed-M)
2 (Speed-H)
3 (XCEL-L)
4 (XCEL-M)
5 (XCEL-H)
6 (Dc-brake)
7 (2nd Func)
10 (Up)
11 (Down)
12 (3-Wire)
13 (Ext trip-A)
14 (Ext trip-B)
16 (Open-loop)
17 (Main-drive)
18 (Analog hold)
19 (XCEL stop)
I/O-13 Multi-function Input Terminal 'P2' define I I3 Same as above - 1 No
I/O-14 Multi-function Input Terminal 'P3' define I I4 Same as above - 2 No
I/O-15 Terminal Input Status I I5 00000000 - 11111111 (bit set) - - -
I/O-16 Terminal Output Status I I6 0 - 1 (bit set) - - -
I/O-17 Filtering Time Constant for Multi-function Input Terminals I I7 2 to 50 1 15 Yes
I/O-20 Jog Frequency setting I 20 FU1-22 to FU1-20 0.01 10.00 [Hz] Yes
I/O-21 Step Frequency 4 I 2I FU1-22 to FU1-20 0.01 40.00 [Hz] Yes
I/O-22 Step Frequency 5 I 22 FU1-22 to FU1-20 0.01 50.00 [Hz] Yes
I/O-23 Step Frequency 6 I 23 FU1-22 to FU1-20 0.01 40.00 [Hz] Yes
I/O-24 Step Frequency 7 I 24 FU1-22 to FU1-20 0.1 30.00 [Hz] Yes
I/O-25 Acceleration Time 1 for Step Frequency I 25 0 to 6000 [sec] 0.1 20.0 [sec] Yes
I/O-26 Deceleration Time 1 for Step Frequency I 26 0 to 6000 [sec] 0.1 20.0 [sec] Yes
I/O-27 Acceleration Time 2 I 27 0 to 6000 [sec] 0.1 30.0 [sec] Yes
I/O-28 Deceleration Time 2 I 28 0 to 6000 [sec] 0.1 30.0 [sec] Yes
I/O-29 Acceleration Time 3 I 29 0 to 6000 [sec] 0.1 40.0 [sec] Yes
11 I/O-30 Deceleration Time 3 I 30 0 to 6000 [sec] 0.1 40.0 [sec] Yes
Dimension

Factory Adjustable
Code Description Keypad Display Setting Range Units
Default during run
I/O-31 Acceleration Time 4 I 3I 0 to 6000 [sec] 0.1 50.0 [sec] Yes
I/O-32 Deceleration Time 4 I 32 0 to 6000 [sec] 0.1 50.0 [sec] Yes
I/O-33 Acceleration Time 5 I 33 0 to 6000 [sec] 0.1 40.0 [sec] Yes
I/O-34 Deceleration Time 5 I 34 0 to 6000 [sec] 0.1 40.0 [sec] Yes
I/O-35 Acceleration Time 6 I 35 0 to 6000 [sec] 0.1 30.0 [sec] Yes
I/O-36 Deceleration Time 6 I 36 0 to 6000 [sec] 0.1 30.0 [sec] Yes
I/O-37 Acceleration Time 7 I 37 0 to 6000 [sec] 0.1 20.0 [sec] Yes
I/O-38 Deceleration Time 7 I 38 0 to 6000 [sec] 0.1 20.0 [sec] Yes
I/O-40 FM (Frequency Meter) Output selection I 40 0 (Frequency) - 0 Yes
1 (Current)
2 (Voltage)
3 (DC link Vtg)
I/O-41 FM Output Adjustment I 4I 10 to 200 [%] 1 100 [%] Yes
I/O-42 Frequency Detection Level I 42 0 to FU1-20 0.01 30.00 [Hz] Yes
I/O-43 Frquency Detection Bandwidth I 43 0 to FU1-20 0.01 10.00 [Hz] Yes
I/O-44 Multi-function Output define (MO)15, 16, 18, 19, 20(-Reserved-) I 44 0 (FDT-1) - 12 Yes
1 (FDT-2)
2 (FDT-3)
3 (FDT-4)
4 (FDT-5)
5 (IOL)
6 (IOL)
7 (Stall)
8 (OV)
9 (LV)
10 (OH)
11 (Lost Command)
12 (Run)
13 (Stop)
14 (Steady)
17 (Search)
I/O-45 Fault Output Relay setting (30A, 30B, 30C) I 45 000 - 111 (bit set) - 010 Yes
Bit 0: LV Bit 1: All Trip
Bit 2: Auto retry
I/O-46 Inverter Number I 46 1 to 32 1 1 Yes
I/O-47 Baud Rate I47 I 47 0 (1200 bps) - 3 Yes
1 (2400 bps)
2 (4800 bps)
3 (9600 bps)
4 (19200 bps)
I/O-48 Operating selection at Loss of Freq. Reference I 48 0 (None) - 0 Yes
1 (FreeRun)
2 (Stop)
I/O-49 Waiting Time after Loss of Freq. Reference I 49 0.1 to 120 [sec] 0.1 1.0 [sec] Yes
I/O-50 Communication Protocol selection I 50 0 (LG- BUS) 7 Yes
1~6(ModbusASCII)
7~9 (Modbus-RTU)
I/O-99 Return Code - 1 Yes
Note: Parameters that are set by bit are ON (1) when the upper LED is lit. (F59, H19, H22, I15, I16, I45 are the parameters that are set by bit.)
Note: *marked default value changes depend on the main frequency setting in factory(50 / 60Hz)

Dimension : mm(inch)
4.5

iG5
VARIABLE FREQUENCY DRIVER

00.00
FRCQUENCY 0.2-400Hz
CURRENT 5A
OUTPUT CAPACITY 1.5kVA
SOURCE AC200-230V 50/60Hz

FUNC
International system Co, Ltd Made In Korea

SV015IG5-2
H2

RUN STOP
RESET

CAUTION
Read the manual and follow the safety instruction before installation or operation
Do not the power supply to the drive output terminal (U, V, W)
Before opening the cover, disconnect all power and wait at least 3 minutes untill DC
bus capacitors discharge.
`Risk of Electric Shock`-more than one disconnect switch is required to de -
energize the equipment before servicing.
4

4.5 4.5
W2
W1 Inverter HP W1 W2 H1 H2 D1
SV004iG5-1 0.5 100(3.94) 88(3.46) 128(5.04) 117.5(4.63) 130.9(5.15)
SV004iG5-2 0.5 100(3.94) 88(3.46) 128(5.04) 117.5(4.63) 130.9(5.15)
SV008iG5-1 1 130(5.12) 118(4.65) 128(5.04) 117.5(4.63) 150.9(5.94)
SV008iG5-2 1 100(3.94) 88(3.46) 128(5.04) 117.5(4.63) 130.9(5.15)
SV015iG5-1 2 150(5.90) 138(5.43) 128(5.04) 117.5(4.63) 155(6.10)
SV015iG5-2 2 130(5.12) 118(4.65) 128(5.04) 117.5(4.63) 150.9(5.94)
SV022iG5-2 3 150(5.90) 138(5.43) 128(5.04) 117.5(4.63) 155(6.10)
D1

SV037iG5-2 5 150(5.90) 138(5.43) 128(5.04) 117.5(4.63) 155(6.10)


SV040iG5-2 5.4 150(5.90) 138(5.43) 128(5.04) 117.5(4.63) 155(6.10)
SV004iG5-4 0.5 130(5.12) 118(4.65) 128(5.04) 117.5(4.63) 150.9(5.94)
SV008iG5-4 1 130(5.12) 118(4.65) 128(5.04) 117.5(4.63) 150.9(5.94)
SV015iG5-4 2 130(5.12) 118(4.65) 128(5.04) 117.5(4.63) 150.9(5.94)
SV022iG5-4 3 150(5.90) 138(5.43) 128(5.04) 117.5(4.63) 155(6.10)
SV037iG5-4 5 150(5.90) 138(5.43) 128(5.04) 117.5(4.63) 155(6.10)
SV040iG5-4 5.4 150(5.90) 138(5.43) 128(5.04) 117.5(4.63) 155(6.10)
12
Starvert iG5

Dynamic Braking(DB) Resistors


1. Standard application
Resistor capacity Average braking Continuous
Drive Resistor value[ ] Enable duty[%]
[W] torque[%] braking time[sec]
SV004iG5-1 100 400 100 5 5
SV008iG5-1 100 200 100 5 5
SV015iG5-1 100 100 100 3 5
SV004iG5-2 100 400 100 5 5
SV008iG5-2 100 200 100 5 5
SV015iG5-2 100 100 100 3 5
SV022iG5-2 100 60 100 2 5
SV037iG5-2 100 40 100 2 5
SV040iG5-2 100 40 100 2 5
SV004iG5-4 100 1800 100 5 5
SV008iG5-4 100 900 100 5 5
SV015iG5-4 100 450 100 3 5
SV022iG5-4 100 300 100 2 5
SV037iG5-4 100 200 100 2 5
SV040iG5-4 100 200 100 2 5

2. When the braking magnitude is high


Resistor capacity Average braking Continuous
Drive Resistor value[ ] Enable duty[%]
[W] torque[%] braking time[sec]
SV004iG5-1 100 400 100 5 5
SV008iG5-1 100 200 100 5 5
SV015iG5-1 200 100 100 5 5
SV004iG5-2 100 400 100 5 5
SV008iG5-2 100 200 100 5 5
SV015iG5-2 200 100 100 5 5
SV022iG5-2 300 60 100 5 5
SV037iG5-2 500 40 100 5 5
SV040iG5-2 500 40 100 5 5
SV004iG5-4 100 1800 100 5 5
SV008iG5-4 100 900 100 5 5
SV015iG5-4 200 450 100 5 5
SV022iG5-4 300 300 100 5 5
SV037iG5-4 500 200 100 5 5
SV040iG5-4 500 200 100 5 5

Resistor capacity Average braking Continuous


Drive Resistor value[ ] Enable duty[%]
[W] torque[%] braking time[sec]
SV004iG5-1 150 300 150 5 5
SV008iG5-1 150 150 150 5 5
SV015iG5-1 300 60 150 5 5
SV004iG5-2 150 300 150 5 5
SV008iG5-2 150 150 150 5 5
SV015iG5-2 300 60 150 5 5
SV022iG5-2 400 50 150 5 5
SV037iG5-2 600 33 150 5 5
SV040iG5-2 600 33 150 5 5
SV004iG5-4 150 1200 150 5 5
SV008iG5-4 150 600 150 5 5
SV015iG5-4 300 300 150 5 5
SV022iG5-4 400 200 150 5 5
SV037iG5-4 600 130 150 5 5
SV040iG5-4 600 130 150 5 5

Options
Option Description

DIN Rail base Din rail mounting plate


Remote keypad mounting fixture and cable 2 meter, 3 meter and 5 meter cable and mounting fixture.

Peripheral devices
Wire, mm2(AWG) AC
Drive Models kW MCCB, ELB Magnetic Contactor AC Reactor DC Reactor
R,S,T U,V,W Ground Input
SV004iG5-1 0.37 ABS33a, EBS33 SMC-10P 2(14) 2(14) 3.5(12) 10A 2.13mH, 5.7A 7.00mH, 5.4A
SV008iG5-1 0.75 ABS33a, EBS33 SMC-10P 2(14) 2(14) 3.5(12) 10A 2.13mH, 5.7A 7.00mH, 5.4A
SV015iG5-1 1.5 ABS33a, EBS33 SMC-10P 2(14) 2(14) 3.5(12) 10A 2.13mH, 5.7A 7.00mH, 5.4A
SV004iG5-2 0.37 ABS33a, EBS33 SMC-10P 2(14) 2(14) 3.5(12) 10A 2.13mH, 5.7A 7.00mH, 5.4A
SV008iG5-2 0.75 ABS33a, EBS33 SMC-10P 2(14) 2(14) 3.5(12) 10A 2.13mH, 5.7A 7.00mH, 5.4A
SV015iG5-2 1.5 ABS33a, EBS33 SMC-10P 2(14) 2(14) 3.5(12) 15A 1.20mH, 10A 4.05mH, 9.2A
SV022iG5-2 2.2 ABS33a, EBS33 SMC-15P 2(14) 2(14) 3.5(12) 25A 0.88mH, 14A 2.92mH, 13A
SV037iG5-2 3.7 ABS33a, EBS33 SMC-20P 3.5(12) 3.5(12) 3.5(12) 40A 0.56mH, 20A 1.98mH, 19A
SV040iG5-2 4 ABS33a, EBS33 SMC-20P 3.5(12) 3.5(12) 3.5(12) 40A 0.56mH, 20A 1.98mH, 19A
SV004iG5-4 0.37 ABS33a, EBS33 SMC-10P 2(14) 2(14) 2(14) 6A 8.63mH, 2.8A 28.62mH, 2.7A
SV008iG5-4 0.75 ABS33a, EBS33 SMC-10P 2(14) 2(14) 2(14) 6A 8.63mH, 2.8A 28.62mH, 2.7A
SV015iG5-4 1.5 ABS33a, EBS33 SMC-10P 2(14) 2(14) 2(14) 10A 4.81mH, 4.8A 16.14mH, 4.6A
SV022iG5-4 2.2 ABS33a, EBS33 SMC-20P 2(14) 2(14) 2(14) 10A 3.23mH, 7.5A 11.66mH, 7.1A
SV037iG5-4 3.7 ABS33a, EBS33 SMC-20P 2(14) 2(14) 2(14) 20A 2.34mH, 10A 7.83mH, 10A
13 SV040iG5-4 4 ABS33a, EBS33 SMC-20P 2(14) 2(14) 2(14) 20A 2.34mH, 10A 7.83mH, 10A
DB Resistor, Options & Peripheral Devices

RFI Filters
IG5 Series Footprint Filter

Drive Models Power Code Current Tension Leakage Dimensions Mounting Weight Mount Output
Voltage Current LWH YX Chokes

SINGLE PHASE (max.)


SV004iG5-1 0.4kW FFG5-M010-1 10A 250VA 3.5A 173.5 X 103.5 X 40 159.5 X 80 M4 FS-1
SV008iG5-1 0.8kW FFG5-M011-1 11A 250VA 3.5A 173.5 X 133.5 X 40 159.5 X 110 M4 FS-1
SV015iG5-1 1.5kW FFG5-M020-1 20A 250VA 3.5A 173.5 X 153.5 X 40 159.5 X 130 M4 FS-2
THREE PHASE (max.)
SV004iG5-2 0.4kW FFG5-T005-1 5A 250VA 0.3A 18A 173.5 X 103.5 X 40 159.5 X 80 M4 FS-1
SV008iG5-2 0.8kW
SV015iG5-2 1.5kW FFG5-T012-1 12A 250VA 0.3A 18A 173.5 X 133.5 X 40 159.5 X 110 M4 FS-2
SV022iG5-2 2.2kW M4 FS-2
SV037iG5-2 3.7kW FFG5-T020-1 20A 250VA 0.3A 18A 173.5 X 153.5 X 40 159.5 X 130
SV040iG5-2 4.0kW
SV004iG5-4 0.4kW
SV008iG5-4 0.8kW FFG5-T006-1 6A 380VAC 0.5A 27A 173.5 X 133.5 X 40 159.5 X 110 M4 FS-1
SV015iG5-4 1.5kW
SV022iG5-4 2.2kW
SV037iG5-4 3.7kW FFG5-T011-1 11A 380VAC 0.5A 27A 173.5 X 133.5 X 40 159.5 X 130 M4 FS-2
SV040iG5-4 4.0kW

IG5 Series Standard Filter

Drive Models Power Code Current Tension Leakage Dimensions Mounting Weight Mount Output
Voltage Current LWH YX Chokes

SINGLE PHASE (max.)


SV004iG5-1 0.4kW FEG5-T010-(X) 10A 250VA 3.5A 150.5 X 55 X 45 140 X 45 --- FS-1
SV008iG5-1 0.8kW
SV015iG5-1 1.5kW FEG5-T015-(X) 15A 250VA 3.5A 150.5 X 55 X 45 140 X 45 --- FS-2
THREE PHASE (max.)
SV004iG5-2 0.4kW FEG5-T006-(X) 6A 250VA 0.3A 18A 250 X 110 X 60 238 X 76 --- FS-2
SV008iG5-2 0.8kW
SV015iG5-2 1.5kW FEG5-T012-(X) 12A 250VA 0.3A 18A 250 X 110 X 60 238 X 76 --- FS-2
SV022iG5-2 2.2kW
SV037iG5-2 3.7kW FEG5-T020-(X) 20A 250VA 0.3A 18A 270 X 140 X 60 258 X 106 --- FS-2
SV040iG5-2 4.0kW
SV004iG5-4 0.4kW
SV008iG5-4 0.8kW FEG5-T006-(X) 6A 380VAC 0.5A 27A 250 X 110 X 60 238 X 76 --- FS-2
SV015iG5-4 1.5kW
SV022iG5-4 2.2kW
SV037iG5-4 3.7kW FEG5-T012-(X) 12A 380VAC 0.5A 27A 250 X 110 X 60 238 X 76 --- FS-2
SV040iG5-4 4.0kW
(X) (1) Industrial environment EN 50081-1 (A class)
(2) Domestic and industrial environment EN 50081-1 (B class)

FF Series (Footprint) FE Series (Standard) FS Series (output chokes)


H
D H
H
Y
Y

Y X
W

Type D W H X O
CARGA

X
RED

W
W X FS-1 21 85 46 70 5
FS-2 28.5 105 62 90 5
FS-3 48 150 110 125 x 30 5
FS-4 58 200 170 180 x 45 5
L
L

INVERTER

SHIELDED CABLE
FF Series (Footprint) MOTOR

FILTER

INVERTER SHIELDED CABLE


FE Series (Standard) FILTER
MOTOR

14
LG constantly endeavor to improve
our products so that information
in this catalog is subject to HEAD OFFICE
change without notice. LG TWIN TOWERS, 20 Yoido-dong, Youngdungpo-gu, Seoul, 150-721, Korea.
Tel.(82-2)3777- 4640 ~ 4649
Fax.(82-2)3777- 4648
http://www.lgis.com
http://www.fasolution.com

OVERSEAS BRANCHES
Beijing Tel.86-10-6462-3254, 3256, 3259, 6464-8637
Shanghai Tel.86-21-6252-3367, 3795, 6240-3477
Hanoi Tel.84-4-882-0222
Dalian Tel.86-411-730-6495, 730-7580
Tokyo Tel.81-3-3582-9126
Jakarta Tel.62-21-897-4311
New Jersey Tel.1-201-816-2982