Transformer Vector Groups v1
Transformer Vector Groups v1
Transformer Vector Groups v1
School of Engineering.
Question One.
Draw all the transformer vector groups showing winding around the core.
Solution:
A vector group is a method of categorizing the high voltage and low voltage winding configurations of a
three phase transformers. It indicates the configurations and the difference in phase angle between the
primary and secondary voltage and current waveforms.
• Delta Configuration
o Polarity end of one winding is connected to the end of the next.
• Start Configuration.
o Non – polarity ends are connected together
There are 12 vector groups, from 0 to 11. These vector groups are analogous to the wall clock, in that
the phase difference between one vector group and the immediate following it is 300 .
The relationship between primary and secondary voltage waveforms shifts depending on the way coils
are arranged. Voltages can be in phase or 1800 apart. When 3 coils are used as in the case of a 3 phase
transformers a number of options exists.
Vector 0 1 2 3 4 5 6 7 8
Group
Phase 00 300 600 900 1200 1500 1800 -1500 -1200
difference
Vector 9 10 11
Group
Phase -900 -600 -300
difference
Y
B
C B
Y4 A 1200 A B C
Y
C
B
Y8 A 1200 Lead
A B C
C B
Y6 A 1800
C Y B
B
A B C
Y10 A 600 Lead
C
B
A B C
Y2 A 600 Lag
C B
A B C
C
B
D5 A 1500 lag B C
A
C B
D9 A 900 lead B C
A
C B
D11 300 lag A B C
A
C B
D3 900 lag
A B C
A
C B
D7 1500 lead
A B C
A
C B
C
B
B
C
Z7 1500 lead A B C
A
Z5 1500 lag
Examples:
Yd7
A
A
Y
B
C B
C B
Y0 D5 1500 PHASE
LEAD
A B C A B C
Star Connected
Delta CT
Connected CT transformers
transformers
A B C
A B C
Restraining Coils
Operating Coil.
Operation.
The above figure shows the differential protection of Yd7 power transformer. The primary side is a star
connection while the secondary side is a delta with a phase shift of 150 degrees. To perform differential
protection, the primary side current transformers should be connected in delta in a configuration that
compliments the secondary side. Whereas the secondary side current transformers should be connected
in a start connection.
The restraining coils can be adjusted so as to increase or reduce sensitivity of the power transformer.
During operation current from the secondary and primary current transformers flow to the restraining
coil, these currents are additive (they obey Kirchoff’s current Law). When there is no fault in either of
the windings, these currents sum to zero and the operating coil doesn’t get magnetized.
In case of a fault, the currents don’t add up to zero causing current to flow in the operating coil bringing
about magnetization of the relay, which in turn sends a trip signal to the circuit breaker for isolation.