31 02 20 Final Report
31 02 20 Final Report
FORWARDED TO,
TRUETZSCHLER INDIA PVT. LTD.
AHMEDABAD.
CONTENTS
2. Field Work. 01
3. Laboratory Work. 02
4. Soil Stratifications. 03
7. Summary. 07
9. Appendix…
1) Tables… 10-19
2) Drawings…
0
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
1.0 INTRODUCTION:
The purpose of the investigations was to determine the sub soil stratification, geotechnical
information & safe bearing capacity, so as to provide information that will assist the structural
engineers in the design of the foundations and the relevant works.
The Job was carried out under the guidance and supervision of the soil personnel of M. K.
Soil Testing Laboratory and client’s engineer.
2.1 Borehole
Eight boreholes having 150mm diameter were drilled using rotary drilling method upto 10.0m
depth below existing ground level (EGL).
The location of the boreholes were decided with due consideration of client /consultant of the
project.
The location of the boreholes are shown in location plan in drawing part of report.
Disturbed representative samples were collected, logged, labelled and placed in polythene
bags.
Undisturbed soil samples are collected in 100 mm diameter thin walled samplers (Shelby
tube). The sampler used for the sampling had smooth surface and appropriate area ratio and
cutting edge angle thereby minimizing disturbance during sampling.
Sampler is coupled together with a sampler head to form a sampling assembly. The sampler
head provides a non-flexible connection between the sampling tube and the drill rods. Vent
holes are provided in the sampler head to allow escape of water/air from the top of sampler
tube during penetration. The sampling tubes are made free from dust and rust. Coating of oil
is applied on both sides to obtain the undisturbed samples in best possible manner.
1
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
The sampler is then lowered inside the bore hole on a string of rods and driven to a pre-
determined level. On completion of driving the sampler is first rotated within the
borehole to shear the soil sample at bottom and then pulled out. Upon removal of the
sampling tubes ends covered with tight wrapper. The identification mark is then made on
each sample.
The standard penetration tests are conducted in bore as per IS: 2131: 1981 (Reaffirmed
1987). The split spoon sampler resting on the bottom of bore hole is allowed to sink under its
own weight, then the split spoon sampler is seated 15cm with the blows of hammer falling
through 750mm. The driving assembly consists of a driving head and a 63.5 kg weight.
It is ensured that the energy of the falling weight is not reduced by friction between the drive
weight and the guides or between ropes. The rods to which the sampler is attached for
driving are straight, tightly coupled and straight in alignment. Thereafter the split spoon
sampler is further driven by 30cm. The number of blows required to drive each 15cm
penetration is recorded. The first 15cm of drive considered as seating drive. The total blows
required for the second and third 15cm penetration is termed as a penetration
resistance - N value.
The laboratory tests on soil samples were started immediately after the receipt of the same
in the laboratory. All laboratory tests are carried out as per the respective Indian Standards.
The results of the laboratory tests were performed on various samples are presented in the
form of Table No. 2 and drawing part end of report.
2
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
Field and laboratory test data reveal the borehole vise stratification as under:
Soil Stratification of borehole
BH No Depth Stratification Observed
(m) SPT value
BH-1 0.0-0.8 Blackish brown silty clay having medium plasticity (CI) -
0.8-2.0 Yellowish brown silty clay having high plasticity (CH) 31
2.0-8.5 Yellowish brown silty clay having medium plasticity (CI) 41-52
8.5-10.0 Yellowish brown silty clay having high plasticity (CH) 67-70
BH-2 0.0-1.5 Blackish to yellowish brown silty clay having medium plasticity -
(CI)
1.5-10.0 Yellowish brown silty clay having high plasticity (CH) 36-68
BH-3 0.0-7.5 Blackish brown & Yellowish brown silty clay having high 12-46
plasticity (CH)
7.5-10.0 Yellowish brown silty clay having medium plasticity (CI) 54-70
BH-4 0.0-0.8 Blackish brown silty clay having medium plasticity (CI) -
0.8-2.5 Yellowish brown silty clay having high plasticity (CH) 27
2.5-10.0 Yellowish brown silty clay having medium plasticity (CI) 32-70
BH-5 0.0-10.0 Blackish to Yellowish brown silty clay having medium 31-58
plasticity (CI)
BH-6 0.0-1.5 Blackish brown silty clay having medium plasticity (CI) 16
1.5-3.5 Yellowish brown silty clay having high plasticity (CH) 33
3.5-7.0 Yellowish brown silty clay having medium plasticity (CI) 48
7.0-10.0 Yellowish brown silty clay having high plasticity (CH) 56-68
BH-7 0.0-10.0 Blackish to Yellowish brown silty clay having medium 20-62
plasticity (CI)
BH-8 0.0-1.8 Blackish brown silty clay having medium plasticity (CI) -
1.8-3.5 Yellowish brown clayey sand (SC) 16
3.5-10.0 Yellowish brown silty clay having medium plasticity (CI) 25-50
The Ground water table was not encountered upto 10.0m depth below EGL at the time of
investigation (February – 2020)
3
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
Following soil properties are adopted at 2.00m depth for calculation of safe bearing capacity.
C = 0.65 Kg/cm2
The ultimate net bearing capacity (Qnd) for footing on soil and mixed shear failure is given
by equation,
Where,
= DD x D = 0.246 kg/cm2
4
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
Qnd = [2/3 x 0.65 x 9.61 x 1.30 x 1.0 x 1.0] + [0.246 x (3.18 - 1) x 1.20 x 1.0 x 1.0]
= 6.307 Kg/cm2
Where,
Qnd 6.307
qs = ------------ = ------------
FS 3.0
P x 2.00 x 2.00
δp = ---------------------- = 0.25P
4.00 x 4.00
Sc = 6.060 cm
Immediate Settlement,
q x B x (1- 2) x I
Si = -----------------------------
Es
Where
Total settlement = Sc + Si
For L/B = 1.0 and LB/D = 1.0, depth factor Df = 0.72 and rigidity factor = 0.80
= 4.961 cm = 49.6 mm
6
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
7.0 SUMMARY:
Type & Size of Depth NET SAFE BEARING CAPACITY Recommended Net
Footing Below (t/m2) Safe Bearing
EGL Shear Settlement Capacity
(m) Criterion Criterion (t/m2)
C & Value Consolidation (for permissible
Results settlement of
50mm)
Square footing 2.0 21.5 48.0 20.0
1.50m x 1.50m
3.0 22.0 60.0 22.0
Note: Depth and size mentioned in the above table is guideline for design of foundation, the
foundation may be laid at depth as per structural stability requirement. Interpolation is
applicable for SBC having intermediate footing width.
Since the Water Table is not encountered upto 10.0m depth below EGL, its effect is
not considered in SBC calculations. SBC calculated based on data obtain at specific
location as mention in borelog, during execution the strata found at the site should be
verified by a competent Engineer.
7
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
8
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
2. The Ground water table was not encountered upto 10.0m depth below EGL at the
time of investigation (February – 2020)
3. The net safe bearing capacity of different size is recommended in para 7.1 with
permissible settlement of 50mm in natural condition of soil.
4. The clayey soil is having moderate to high swelling properties hence it is not suitable
to use for back/plinth filling purpose. The filled up soil is having debris is not suitable
to use for back/plinth filling purpose.
5. Granular backfill having thickness of 0.25m need to be provide between footing and
natural ground if footing will design to place at 2.0m depth below EGL.
As a guideline the granular back fill material for use in the foundation trenches or in
the building plinths and in the subgrade of pavements shall not contain rocks or hard
lumps greater than 75 mm in maximum dimension and should have at least 80
percent passing the 9.5mm sieve and at least 5 percent passing the 0.075 mm sieve.
The fill materials should be free of organics, debris, or other deleterious materials.
Filling and compaction shall be carried in accordance with standard specifications.
6. Alternately Under-Reamed pile with single bulb is also recommended to support the
structure in para 7.2 of summary.
7. The results of the laboratory tests are incorporated in the form of table at the later
part of the report.
9
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
10
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
11
JOB NO.: MK/31/02-20 M.K. SOIL TESTING LABORATORY. AHMEDABAD – 380054
Table No: 2/1 SOIL CHARACTERISTICS FOR BOREHOLE NO.: – BH – 1
Project: Geotechnical investigation work for construction of Factory at Plot No. SM-45, Sanand Industrial Estate-2, Tal: Sanand. Dist: Ahmedabad. State: Gujarat.
UNCONFINED COMPRESSIVE
2720(P:4) (IS: 2720(P:5)
SWELLING PRESSURE
TYPE OF SHEAR TEST
SHRINKAGE LIMIT(%)
(kg/cm2) (IS: 2720(P:10)
% SAND
SPECIFIC GRAVITY
CLASSIFICATION
WEIGHT (gm/cm3)
INSITU DRY UNIT
(IS: 2720(P/11/13)
FRICTION, Φ ( º )
(IS: 2720(P:3-1/2)
COMPRESSION
ANGLE OF INT.
INSITU WATER
COHESION C,
SAMPLE TYPE
SPT – N Value
(IS: 2720(P:29)
CONTENT (%)
(IS: 2720(P:2)
WT (gm/cm3)
(IS: 2720(P:15)
(IS: 2720(P:40)
(IS: 2720(P:41)
STRENGTH
(IS: 2720(P:6)
DEPTH (m)
INDEX, Cc
PLASTIC LIMIT
GRAVEL (%)
(IS: 1498)
LIQUID LIMIT
(kg/cm2)
PLASTICITY
kg/cm2
CLAY (%)
INDEX, IP
I.S.
SILT &
COARSE
(%)
(%)
(%)
MED.
FINE
0.00 DS - - - - - 1 2 9 20 68 41 20 21 CI - - - - - 40 - -
1.00 SPT 31 - - - - 4 2 10 25 59 52 25 27 CH - - - - - 50 - -
3.00 SPT 41 - - - - - - - - - - - - - - - - - - - - -
5.00 SPT 43 - - - - - - - - - - - - - - - - - - - - -
9.00 SPT 67 - - - - 0 2 4 18 76 52 27 25 CH - - - - - - - -
10.0 SPT 70 - - - - - - - - - - - - - - - - - - - - -
* UCS was performed on remoulded specimen having degree of saturation nearest to 90%.
* UU test were performed on test specimen having degree of saturation nearest to 90%.
12
JOB NO.: MK/31/02-20 M.K. SOIL TESTING LABORATORY. AHMEDABAD – 380054
Table No: 2/2 SOIL CHARACTERISTICS FOR BOREHOLE NO.: – BH – 2
Project: Geotechnical investigation work for construction of Factory at Plot No. SM-45, Sanand Industrial Estate-2, Tal: Sanand. Dist: Ahmedabad. State: Gujarat.
UNCONFINED COMPRESSIVE
2720(P:4) (IS: 2720(P:5)
SWELLING PRESSURE
TYPE OF SHEAR TEST
SHRINKAGE LIMIT(%)
(kg/cm2) (IS: 2720(P:10)
% SAND
SPECIFIC GRAVITY
CLASSIFICATION
WEIGHT (gm/cm3)
INSITU DRY UNIT
(IS: 2720(P/11/13)
FRICTION, Φ ( º )
(IS: 2720(P:3-1/2)
COMPRESSION
ANGLE OF INT.
INSITU WATER
COHESION C,
SAMPLE TYPE
SPT – N Value
(IS: 2720(P:29)
CONTENT (%)
(IS: 2720(P:2)
WT (gm/cm3)
(IS: 2720(P:15)
(IS: 2720(P:40)
(IS: 2720(P:41)
STRENGTH
(IS: 2720(P:6)
DEPTH (m)
INDEX, Cc
PLASTIC LIMIT
GRAVEL (%)
(IS: 1498)
LIQUID LIMIT
(kg/cm2)
PLASTICITY
kg/cm2
CLAY (%)
INDEX, IP
I.S.
SILT &
COARSE
(%)
(%)
(%)
MED.
FINE
0.00 DS - - - - - 2 11 11 18 58 39 19 20 CI - - - - - 30 - -
2.00 SPT 36 - - - - 8 3 12 20 57 52 25 27 CH - - - - - - - -
4.00 SPT 48 - - - - - - - - - - - - - - - - - - - - -
5.00 UDS/ - - - - - 0 8 22 16 54 52 26 26 CH - - - - - - - -
DS
6.50 SPT 53 - - - - 6 4 20 20 50 51 25 26 CH - - - - - - - -
7.50 SPT 58 - - - - - - - - - - - - - - - - - - - - -
9.00 SPT 62 - - - - - - - - - - - - - - - - - - - - -
10.0 SPT 68 - - - - 8 4 16 14 58 50 24 26 CH - - - - - - - -
13
JOB NO.: MK/31/02-20 M.K. SOIL TESTING LABORATORY. AHMEDABAD – 380054
Table No: 2/3 SOIL CHARACTERISTICS FOR BOREHOLE NO.: – BH – 3
Project: Geotechnical investigation work for construction of Factory at Plot No. SM-45, Sanand Industrial Estate-2, Tal: Sanand. Dist: Ahmedabad. State: Gujarat.
UNCONFINED COMPRESSIVE
2720(P:4) (IS: 2720(P:5)
SWELLING PRESSURE
TYPE OF SHEAR TEST
SHRINKAGE LIMIT(%)
(kg/cm2) (IS: 2720(P:10)
% SAND
SPECIFIC GRAVITY
CLASSIFICATION
WEIGHT (gm/cm3)
INSITU DRY UNIT
(IS: 2720(P/11/13)
FRICTION, Φ ( º )
(IS: 2720(P:3-1/2)
COMPRESSION
ANGLE OF INT.
INSITU WATER
COHESION C,
SAMPLE TYPE
SPT – N Value
(IS: 2720(P:29)
CONTENT (%)
(IS: 2720(P:2)
WT (gm/cm3)
(IS: 2720(P:15)
(IS: 2720(P:40)
(IS: 2720(P:41)
STRENGTH
(IS: 2720(P:6)
DEPTH (m)
INDEX, Cc
PLASTIC LIMIT
GRAVEL (%)
(IS: 1498)
LIQUID LIMIT
(kg/cm2)
PLASTICITY
kg/cm2
CLAY (%)
INDEX, IP
I.S.
SILT &
COARSE
(%)
(%)
(%)
MED.
FINE
0.00 DS - - - - - 2 2 10 22 64 45 22 23 CI - - - - - 40 - -
1.00 SPT 12 - - - - 0 0 2 36 62 38 19 19 CI - - - - - 40 - -
3.00 SPT 31 - - - - - - - - - - - - - - - - - - - - -
5.00 SPT 46 - - - - 0 2 18 20 60 42 20 22 CI - - - - - - - -
6.50 UDS/ - - - - - 4 2 18 19 57 46 22 24 CI - - - - - - - -
DS
7.50 SPT 54 - - - - 2 2 26 28 42 41 20 21 SC - - - - - - - -
9.00 SPT 65 - - - - - - - - - - - - - - - - - - - - -
10.0 SPT 70 - - - - 0 2 24 26 48 41 20 21 SC - - - - - - - -
14
JOB NO.: MK/31/02-20 M.K. SOIL TESTING LABORATORY. AHMEDABAD – 380054
Table No: 2/4 SOIL CHARACTERISTICS FOR BOREHOLE NO.: – BH – 4
Project: Geotechnical investigation work for construction of Factory at Plot No. SM-45, Sanand Industrial Estate-2, Tal: Sanand. Dist: Ahmedabad. State: Gujarat.
UNCONFINED COMPRESSIVE
2720(P:4) (IS: 2720(P:5)
SWELLING PRESSURE
TYPE OF SHEAR TEST
SHRINKAGE LIMIT(%)
(kg/cm2) (IS: 2720(P:10)
% SAND
SPECIFIC GRAVITY
CLASSIFICATION
WEIGHT (gm/cm3)
INSITU DRY UNIT
(IS: 2720(P/11/13)
FRICTION, Φ ( º )
(IS: 2720(P:3-1/2)
COMPRESSION
ANGLE OF INT.
INSITU WATER
COHESION C,
SAMPLE TYPE
SPT – N Value
(IS: 2720(P:29)
CONTENT (%)
(IS: 2720(P:2)
WT (gm/cm3)
(IS: 2720(P:15)
(IS: 2720(P:40)
(IS: 2720(P:41)
STRENGTH
(IS: 2720(P:6)
DEPTH (m)
INDEX, Cc
PLASTIC LIMIT
GRAVEL (%)
(IS: 1498)
LIQUID LIMIT
(kg/cm2)
PLASTICITY
kg/cm2
CLAY (%)
INDEX, IP
I.S.
SILT &
COARSE
(%)
(%)
(%)
MED.
FINE
0.00 DS - - - - - 0 1 7 15 77 38 16 22 CI - - - - - 30 - -
1.00 SPT 27 - - - - 0 2 2 10 86 53 21 32 CH - - - - - 50 - -
3.00 SPT 32 - - - - 8 5 3 3 81 46 22 24 CI - - - - - - - -
5.00 SPT 39 - - - - - - - - - - - - - - - - - - - - -
7.50 SPT 56 - - - - - - - - - - - - - - - - - - - - -
9.00 SPT 65 - - - - 2 3 4 3 88 41 17 24 CI - - - - - - - -
10.0 SPT 70 - - - - - - - - - - - - - - - - - - - - -
15
JOB NO.: MK/31/02-20 M.K. SOIL TESTING LABORATORY. AHMEDABAD – 380054
Table No: 2/5 SOIL CHARACTERISTICS FOR BOREHOLE NO.: – BH – 5
Project: Geotechnical investigation work for construction of Factory at Plot No. SM-45, Sanand Industrial Estate-2, Tal: Sanand. Dist: Ahmedabad. State: Gujarat.
UNCONFINED COMPRESSIVE
2720(P:4) (IS: 2720(P:5)
SWELLING PRESSURE
TYPE OF SHEAR TEST
SHRINKAGE LIMIT(%)
(kg/cm2) (IS: 2720(P:10)
% SAND
SPECIFIC GRAVITY
CLASSIFICATION
WEIGHT (gm/cm3)
INSITU DRY UNIT
(IS: 2720(P/11/13)
FRICTION, Φ ( º )
(IS: 2720(P:3-1/2)
COMPRESSION
ANGLE OF INT.
INSITU WATER
COHESION C,
SAMPLE TYPE
SPT – N Value
(IS: 2720(P:29)
CONTENT (%)
(IS: 2720(P:2)
WT (gm/cm3)
(IS: 2720(P:15)
(IS: 2720(P:40)
(IS: 2720(P:41)
STRENGTH
(IS: 2720(P:6)
DEPTH (m)
INDEX, Cc
PLASTIC LIMIT
GRAVEL (%)
(IS: 1498)
LIQUID LIMIT
(kg/cm2)
PLASTICITY
kg/cm2
CLAY (%)
INDEX, IP
I.S.
SILT &
COARSE
(%)
(%)
(%)
MED.
FINE
0.00 DS - - - - - 0 2 6 17 75 42 18 24 CI - - - - - 40 - -
2.00 SPT 31 - - - - - - - - - - - - - - - - - - - - -
3.00 UDS - 2.66 1.85 1.65 12.4 5 4 5 15 71 41 17 24 CI TUU 1.05 12 0.065 12.0 - - -
4.00 SPT 34 - - - - - - - - - - - - - - - - - - - - -
6.50 SPT 43 - - - - - - - - - - - - - - - - - - - - -
9.00 SPT 52 - - - - - - - - - - - - - - - - - - - - -
10.0 SPT 58 - - - - 4 6 20 12 58 35 16 19 CI - - - - - - - -
16
JOB NO.: MK/31/02-20 M.K. SOIL TESTING LABORATORY. AHMEDABAD – 380054
Table No: 2/6 SOIL CHARACTERISTICS FOR BOREHOLE NO.: – BH – 6
Project: Geotechnical investigation work for construction of Factory at Plot No. SM-45, Sanand Industrial Estate-2, Tal: Sanand. Dist: Ahmedabad. State: Gujarat.
UNCONFINED COMPRESSIVE
2720(P:4) (IS: 2720(P:5)
SWELLING PRESSURE
TYPE OF SHEAR TEST
SHRINKAGE LIMIT(%)
(kg/cm2) (IS: 2720(P:10)
% SAND
SPECIFIC GRAVITY
CLASSIFICATION
WEIGHT (gm/cm3)
INSITU DRY UNIT
(IS: 2720(P/11/13)
FRICTION, Φ ( º )
(IS: 2720(P:3-1/2)
COMPRESSION
ANGLE OF INT.
INSITU WATER
COHESION C,
SAMPLE TYPE
SPT – N Value
(IS: 2720(P:29)
CONTENT (%)
(IS: 2720(P:2)
WT (gm/cm3)
(IS: 2720(P:15)
(IS: 2720(P:40)
(IS: 2720(P:41)
STRENGTH
(IS: 2720(P:6)
DEPTH (m)
INDEX, Cc
PLASTIC LIMIT
GRAVEL (%)
(IS: 1498)
LIQUID LIMIT
(kg/cm2)
PLASTICITY
kg/cm2
CLAY (%)
INDEX, IP
I.S.
SILT &
COARSE
(%)
(%)
(%)
MED.
FINE
0.00 DS - - - - - 0 2 6 14 78 44 22 22 CI - - - - - 40 - -
3.00 SPT 33 - - - - 2 1 5 5 87 65 30 35 CH - - - - - - - -
5.00 SPT 48 - - - - - - - - - - - - - - - - - - - - -
9.00 SPT 64 - - - - - - - - - - - - - - - - - - - - -
10.0 SPT 68 - - - - 0 1 28 18 53 60 31 29 CH - - - - - - - -
17
JOB NO.: MK/31/02-20 M.K. SOIL TESTING LABORATORY. AHMEDABAD – 380054
Table No: 2/7 SOIL CHARACTERISTICS FOR BOREHOLE NO.: – BH – 7
Project: Geotechnical investigation work for construction of Factory at Plot No. SM-45, Sanand Industrial Estate-2, Tal: Sanand. Dist: Ahmedabad. State: Gujarat.
UNCONFINED COMPRESSIVE
2720(P:4) (IS: 2720(P:5)
SWELLING PRESSURE
TYPE OF SHEAR TEST
SHRINKAGE LIMIT(%)
(kg/cm2) (IS: 2720(P:10)
% SAND
SPECIFIC GRAVITY
CLASSIFICATION
WEIGHT (gm/cm3)
INSITU DRY UNIT
(IS: 2720(P/11/13)
FRICTION, Φ ( º )
(IS: 2720(P:3-1/2)
COMPRESSION
ANGLE OF INT.
INSITU WATER
COHESION C,
SAMPLE TYPE
SPT – N Value
(IS: 2720(P:29)
CONTENT (%)
(IS: 2720(P:2)
WT (gm/cm3)
(IS: 2720(P:15)
(IS: 2720(P:40)
(IS: 2720(P:41)
STRENGTH
(IS: 2720(P:6)
DEPTH (m)
INDEX, Cc
PLASTIC LIMIT
GRAVEL (%)
(IS: 1498)
LIQUID LIMIT
(kg/cm2)
PLASTICITY
kg/cm2
CLAY (%)
INDEX, IP
I.S.
SILT &
COARSE
(%)
(%)
(%)
MED.
FINE
0.00 DS - - - - - 0 1 6 12 81 42 22 20 CI - - - - - 30 - -
2.00 SPT 20 - - - - - - - - - - - - - - - - - - - - -
4.00 SPT 25 - - - - - - - - - - - - - - - - - - - - -
6.50 SPT 51 - - - - - - - - - - - - - - - - - - - - -
7.50 SPT 53 - - - - - - - - - - - - - - - - - - - - -
9.00 SPT 54 - - - - 0 2 4 16 78 42 22 20 CI - - - - - - - -
10.0 SPT 62 - - - - - - - - - - - - - - - - - - - - -
18
JOB NO.: MK/31/02-20 M.K. SOIL TESTING LABORATORY. AHMEDABAD – 380054
Table No: 2/8 SOIL CHARACTERISTICS FOR BOREHOLE NO.: – BH – 8
Project: Geotechnical investigation work for construction of Factory at Plot No. SM-45, Sanand Industrial Estate-2, Tal: Sanand. Dist: Ahmedabad. State: Gujarat.
UNCONFINED COMPRESSIVE
2720(P:4) (IS: 2720(P:5)
SWELLING PRESSURE
TYPE OF SHEAR TEST
SHRINKAGE LIMIT(%)
(kg/cm2) (IS: 2720(P:10)
% SAND
SPECIFIC GRAVITY
CLASSIFICATION
WEIGHT (gm/cm3)
INSITU DRY UNIT
(IS: 2720(P/11/13)
FRICTION, Φ ( º )
(IS: 2720(P:3-1/2)
COMPRESSION
ANGLE OF INT.
INSITU WATER
COHESION C,
SAMPLE TYPE
SPT – N Value
(IS: 2720(P:29)
CONTENT (%)
(IS: 2720(P:2)
WT (gm/cm3)
(IS: 2720(P:15)
(IS: 2720(P:40)
(IS: 2720(P:41)
STRENGTH
(IS: 2720(P:6)
DEPTH (m)
INDEX, Cc
PLASTIC LIMIT
GRAVEL (%)
(IS: 1498)
LIQUID LIMIT
(kg/cm2)
PLASTICITY
kg/cm2
CLAY (%)
INDEX, IP
I.S.
SILT &
COARSE
(%)
(%)
(%)
MED.
FINE
0.00 DS - - - - - 3 2 4 15 76 45 22 23 CI - - - - - 40 - -
2.00 SPT 16 - - - - 10 12 15 15 48 34 17 17 SC - - - - - - - -
4.00 SPT 25 - - - - 4 2 6 15 73 43 23 20 CI - - - - - - - -
6.50 SPT 37 - - - - - - - - - - - - - - - - - - - - -
9.00 SPT 44 - - - - 0 1 18 17 64 42 22 20 CI - - - - - - - -
10.0 SPT 50 - - - - - - - - - - - - - - - - - - - - -
19
Job No: MK/31/02-20 M. K. Soil Testing Laboratory, Ahmedabad – 54.
ABBREVIATION
DS Disturbed Sample
UDS Undisturbed Sample
SPT Standard Penetration Test
NP Non Plastic
LL Liquid Limit
PL Plastic Limit
PI Plasticity Index
TUU Triaxial unconsolidated undrain shear test
DCD Direct shear test consolidated drain
DUU Direct shear test unconsolidated undrain
FS Filled up soil
SM Silty sand
SC Clayey sand
ML Sandy silt
CL Silty Clay having low plasticity
CI Silty Clay having medium plasticity
CH Silty Clay having high plasticity
BH Borehole