Septic Tank Sizing - SPLENDOR

This document provides guidance on sizing septic tanks using a spreadsheet tool. It outlines steps to calculate the daily liquid volume and total sludge/scum volume based on user numbers, water availability, retention time, solids accumulation rate, desludging period and temperature. The tool then sizes the septic tank dimensions based on the calculated volumes. Dimensions are provided for a dual compartment tank with the first compartment twice as long as the second.

Uploaded by

Rashel Hasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
1K views1 page

Septic Tank Sizing - SPLENDOR

This document provides guidance on sizing septic tanks using a spreadsheet tool. It outlines steps to calculate the daily liquid volume and total sludge/scum volume based on user numbers, water availability, retention time, solids accumulation rate, desludging period and temperature. The tool then sizes the septic tank dimensions based on the calculated volumes. Dimensions are provided for a dual compartment tank with the first compartment twice as long as the second.

Uploaded by

Rashel Hasan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Project Name:Shanta The Waada Occupancy : A ( Residential ) Building Storey : G.

F+L-1 to
Calculation by: Engr. Ahammed Rashel Hasan Check by : Engr.Md. Mozzammel Hossan L-4.

F401/2016A - MSEXCEL SEPTIC TANK SIZING CALCULATION TOOL


 This sizing calculation tool has been designed to assist UNHCR and WASH actors correctly size septic tanks in
displaced settings taking into account numbers of users, wastewater and sewage flows, sludge and scum
accumulation rates, desludging periods, liquid retention times, and average annual ambient temperatures.
 The tool can be used for any size of septic tank from individual household units, to larger structures treating
communal toilet blocks, or groups of households connected by a communal sewer.
 Septic tanks should only be used where there is at least 40 litres/pers/day of combined wastewater and sewage.
 Note that septic tanks are only effective at reducing between 30% - 40% of COD (Chemical Oxygen Demand) and
BOD (Biological Oxygen Demand). Anaerobic Baffled Reactors (ABRs) may be a more suitable treatment option
where the quality of septic tank effluents are regulated by local governments (e.g. urban contexts).
 It is good practice to discuss the results of these septic tank sizing calculations with local government authorities
and members of the displaced community before finalizing the design.
 To use the spreadsheet enter data in the orange cells below. Blue cells are calculated automatically!

UNHCR SEPTIC TANK SIZING CALCULATION TOOL

A) Total daily liquid volume calculation


 Total number of users (P) 200 (persons)
 Per capita water availability (Q) 120 (litres/person/day)
 Percentage of water entering wastewater and sewerage flow (Z) 70% typically 50% - 90% 16.8
 Septic tank retention time (T) 12 (hours) see table below – larger tanks require smaller retention times.
 Wastewater and sewage vol. (A) = P x (Q/1000) x Z x (T/24) = 200 x 0.120 x 0.70 x 0.50 = 8.40   m3
Daily liquid volume (A) Retention time (T)
If A < 6m3/day T = 24 hours
3 3
If A is 6m – 14m /day T = 33 - 1.5 x A hours
If A > 14m3/day T = 12 hours
Source: Franceys, Pickford & Reed (1992) ‘Guide to the development of on-site sanitation’. World Health Organization, Geneva.

B) Total sludge and scum volume calculation


 Total number of users (P) 200 (persons) value taken from cell H22 above.
3
 Solids accumulation rate (S) 0.04 (m /person/year) typically 0.04 – 0.06 m 3 /pers/yr depending on anal cleansing.
 Desludging period (N) 1 (years) should be at least 3 years or greater for proper sludge reduction.
 Average Annual Ambient Temperature 10°-20°C (°C) used to calculate sizing factor - see table below.
 Sizing factor (F) 1.5 see table below – colder climates and shorter desludge periods require larger compartments.
 Total sludge and scum volume (B) = P x S x N x F = 200 x 0.04 x 1 x 1.5 = 12.00   m3
Desludge Ambient Temperature
10°-
Period >20°C <10°C
20°C
1 1.3 1.5 2.5
2 1 1.2 1.5
3 1 1 1.3
4 1 1 1.2
5 1 1 1.1
6+ 1 1 1
Source: Franceys, Pickford & Reed (1992) ‘Guide to the development of on-site sanitation’. World Health Organization, Geneva.

C) Septic tank compartment dimensions


3
 Total septic tank volume (V) = daily liquid volume (A) + sludge and scum volume (B) = 8.40 + 12.00 = 20.40 m
Assuming a dual compartment septic tank with the first compartment (of length 2W) twice as long as the second
compartment (of length, width and height W) we end up with a septic tank with the following dimensions:
Total septic tank volume (V) = length (3)W x width (W) x height (W) = 3W 3 m3
Rearranging we get..

1.89 m

Adding 0.3m of freeboard we end up with the following inner chamber dimensions:
Chamber Length (m) Width (m) Height (m)
#1 3.79 1.89 2.19
#2 1.89 1.89 2.19