Bladder Tank Sunshade Drawing R1-15.04.21 - Compressed
Bladder Tank Sunshade Drawing R1-15.04.21 - Compressed
Bladder Tank Sunshade Drawing R1-15.04.21 - Compressed
1 C Channel ( 100*50 )
C Channel ( 100*50 )
+3000
B H Beam ( 100*60 ) 2
3000
A H Beam ( 100*60 )
H Beam ( 100*60 )
+0
H Beam ( 100*60 )
1400
CORROGATED SHEET
1
B
3d
GRID A
2
1 2
A B
+3000
500
500
B
3D VIEW
2400
2600
3000
2700
A
1400
+0
1600
2400
PLAN @+0
GRID @1
G
#12 @ 250C/C
1600
#12 @ 250C/C
A
3000
100
Marked B/1, B/2 & B/3 50 2600
A
SECTION
A SCALE: 1:5 G
2000
200 mm
80
80
0 mm
400
40 -200 mm
Marked B/4 & B/5
100
B SECTION
B SCALE: 1:5 2600
G SECTION
SCALE: 1:20
FOOTING SCHEDULE
100
BILL OF MATERIALS
23
23
WEIGHT IN KGS.
60 MARK. ITEM MATL. LENGTH REQD.
38 38 SECTION
NO. SPCN. IN mm. NOS. PC. WT. TOTAL WT.
SECTION
SECTION B Marked C/1 & C/2 E E SCALE: 1:5 B/1, B/2 & B/3
B SCALE: 1:5
1 S275 BLU100*50*6 3000.0 3 17.71 78.68
100
C/3 & C/4
23
23
NOTES :-
1.ALL DIMENSIONS ARE IN 'MM' UNLESS OTHERWISE NOTED.
2.ANCHOR BOLT MUST BE SET STRAIGHT AND TO THE GIVEN DIMENSIONS AND THE PROJECTIONS WITH A
MAXIMUM OF 5 MM TOLERANCES.
3.ANCHOR BOLT THREADS MUST BE PROTECTED WHILE POURING THE CONCRETE AND MUST BE THOROUGHLY
CLEANED AND THE TEMPLATES ARE TO BE REMOVED AFTER POURING CONCRETE.
4.THE CUSTOMER / CONTRACTOR IS RESPONSIBLE FOR LOCATING THE BUILDING LINES AND BENCH MARKS AT
5.THE FOLLOWING ARE THE MAXIMUM ALLOWABLE TOLERANCES FOR SETTING UP THE THE ANCHOR BOLTS.
TOLERANCES. 2 MM BETWEEN ANY TWO ANCHOR BOLTS IN ANY ANCHOR BOLT GROUP.
THE SITE.
6. ALL THE ANCHOR BOLTS MUST BE SET PERPENDICULAR TO THE THEORETICAL BEARING NOTED SURFACE
UNLESS OTHERWISE.
7. COMPRESSIVE STRENGTH OF CONCRETE FC' = 4 KIP/IN2 AND YIELD STRENGTH OF BAR FY' = 60 KIP/IN2
ASSUMED IN DESIGN WHEREVER REQUIRED.