Why Is It Important To Calculate CT Burden (VA) - Newtek Electricals, Current Transformer, Control Transformer, Digital Meter

Newtek has been at the forefront of innovation in current transformers, potential transformers and digital meters in India. With more than two decades of experience, Our expertise and product quality have earned recognition from market leaders across the country. Newtek Electricals is the first company to introduce nylon flame retardant casing current transformers in India, and the product is now exported to other countries as well. we are the leaders of manufacturers and exporters CTs, PTs
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
63 views4 pages

Why Is It Important To Calculate CT Burden (VA) - Newtek Electricals, Current Transformer, Control Transformer, Digital Meter

Newtek has been at the forefront of innovation in current transformers, potential transformers and digital meters in India. With more than two decades of experience, Our expertise and product quality have earned recognition from market leaders across the country. Newtek Electricals is the first company to introduce nylon flame retardant casing current transformers in India, and the product is now exported to other countries as well. we are the leaders of manufacturers and exporters CTs, PTs
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Why is it important

to calculate
CT Burden (VA)?

Transforming l Measuring l Technology


www.newtekelectricals.com
Why Is It Important
To Calculate CT Burden(VA)?
The formula to calculate CT burden is simple
Study the output circuit
(A) Calculate individual burden of instruments
(B) Calculate burden of connected wire
Add (A+B)
Multiply the result by 1.2 to 1.5 as safety factor

(A) Typical burden values of Digital/Analog Meters

(B) How to calculate burden of secondary cable?


For Copper cable
VA = k X L/S
K = 0.5 if is (secondary cable) = 5A
K = 0.02, if is = 1A
Where; L= Length of secondary cable (input/output loop) In meters
and S = Cross Section Area of cables In mm2 .
In this case, the CTs are generally in a controlling or metering panel
within a small distance from actual meter, and technically it is not
necessary to have a large VA.

Transforming l Measuring l Technology


Test Case for CT 100/5A,
VA = k X L/S
K = 0.5 if is = 5A, L = 5 m, S = 2.5 mm 2 .
VA = 0.5X 5/2.5
= 2.5/2.5
B = 1 VA

To take an example, If you connect one analog meter having a 5


meter long secondary lead cable, The total burden will be:
Burden of Meter (A) = 0.75 VA
Burden of 5 meter Cable (B) = 1VA
Total Burden A+B = 0.75+1 = 1.75VA
Multiply the total burden by safety factor 1.2
- 1.2*1.75 = 2.1VA

This means you can use a CT with 2.5VA or 5VA burden.

Conclusion
The CT burden impacts the CT accuracy. If the burden is higher than
required, the CT accuracy can fluctuate.

Transforming l Measuring l Technology


Comprehensive Range of CT/PTs and Multi-Function Meters (MFMs)

Current Transformer Resin Cast-Round ID


Nylon Casing
Metering Type CT'S
Window Type CT’S Metering
(Bus Bar) Type CT'S
WPL Type Resin Cast -
Round ID Type CT’S WPL
Resin Cast -
Protection Type CT'S Bus Bar
Nylon Casing- Resin Cast -
Protective Type Round ID
Bus Bar

Control Transformer Digital Meter

Single-phase Energy Meter


Resin Cast MFM Meter
Three-phase VAF Meter
Resin Cast DPM Meter

M-90 M.I.D.C Waluj, Aurangabad 431136, Maharashtra, India.

+91-0240 2551555 / 9372862651, 9372862647

[email protected]
[email protected]
[email protected]
[email protected]
[email protected]

www.newtekelectricals.com

You might also like