Transparent Ready

User Guide
TCSEAD02E01

10/2005
31006929.00
2 31006929.00 10/2005
Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 1 Transparent Ready . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Transparent Ready . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Transparent Ready Service Classes Offered . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Users of this Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
How this Guide Is Organized. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Chapter 2 Physical Planning, Design and Installation of a


Transparent Ready Industrial Ethernet Network . . . . . . . . . . . 29
2.1 Required Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
On-going Industrial Ethernet Standardization Efforts . . . . . . . . . . . . . . . . . . . . . 31
Required Standards for Planning and Installation . . . . . . . . . . . . . . . . . . . . . . . . 34
2.2 Physical Planning and Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Industrial Ethernet Cable Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Structured Cabling Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Cabling in a Transparent Ready Industrial Ethernet System . . . . . . . . . . . . . . . 42
Understanding Basic Network Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Developing Network Architecture for Industrial Ethernet Networks. . . . . . . . . . . 52
Redundant Ring Topology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
LAN Technologies and Network Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
LAN Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Other LAN Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
WAN Technologies and Network Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
WAN Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
2.3 Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Environmental Standards Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Mechanical Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Climate Protection Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Ingress Protection Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Electromagnetic Emission and Immunity Requirements . . . . . . . . . . . . . . . . . . . 79

31006929.00 10/2005 3
2.4 Selection of Industrial Ethernet Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Ethernet Copper Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Fiber Optic Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
10/100BaseF Physical Layer Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Ethernet Connectors for Copper Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Fiber Optic Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Recommended Infrastructure Devices for Industrial Ethernet . . . . . . . . . . . . . . . 95
2.5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
EMC Installation Rules for Ethernet Networks. . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Equipotential Bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Equipotentially Bonding Your Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Local Equipotential Bonding of Equipment and Machines. . . . . . . . . . . . . . . . . 101
EMC-compatible Ethernet Wiring and Cable Runs . . . . . . . . . . . . . . . . . . . . . . 102
Ethernet Copper Cable Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Ethernet Copper Cable Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
How to Make an Ethernet Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Cabling Administration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Cabling Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
2.6 Verification of a Transparent Ready Industrial Ethernet . . . . . . . . . . . . . . . . . . 117
Transparent Ready Industrial Ethernet Verification Recommendations . . . . . . 118
Permanent Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Testing a Copper Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
2.7 Additional Considerations for Designing a Transparent Ready
Industrial Ethernet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Internet and IP Technologies in an Automation Environment . . . . . . . . . . . . . . 125
Open System Interconnection Model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
The TCP/IP Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Transparent Ready Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
IP Addresses and Classes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Multicasting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Multicast Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Network Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Routing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Introduction to Remote Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Remote Access Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Network Access Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
PLC Connected to the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Security Issues. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153

4 31006929.00 10/2005
Chapter 3 Services Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
3.1 Evaluating System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Common Services at each Level in the Plant . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Company Level Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Inter-PLC Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Field Level Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Communication Service Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Transparent Ready Support Services and Protocols . . . . . . . . . . . . . . . . . . . . 165
3.2 I/O Scanning Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
I/O Scanning Service Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
I/O Scanner Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Repetition Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Some Common Fault Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
3.3 Modbus Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Modbus Messaging Service Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Devices that Support Ethernet Modbus Services . . . . . . . . . . . . . . . . . . . . . . . 189
Modbus Client Operations in Quantum Systems . . . . . . . . . . . . . . . . . . . . . . . 190
Modbus Client Operations in Premium Systems. . . . . . . . . . . . . . . . . . . . . . . . 191
Modbus Client Operations in Momentum Systems . . . . . . . . . . . . . . . . . . . . . . 193
Modbus Server Operations in Quantum Systems . . . . . . . . . . . . . . . . . . . . . . . 194
Modbus Server Operations in Premium Systems . . . . . . . . . . . . . . . . . . . . . . . 197
Modbus Server Operations in Momentum Systems . . . . . . . . . . . . . . . . . . . . . 199
Modbus Servers and Socket Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Modbus Messaging Retry Times and Time-outs. . . . . . . . . . . . . . . . . . . . . . . . 201
3.4 Global Data Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
The Global Data Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Global Data Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
3.5 Faulty Device Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Faulty Device Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Devices that Support the FDR Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
3.6 Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Time Synchronization Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Time Synchronization Service Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Time Synchronization Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Schneider Devices Implementing Time Synchronization Service . . . . . . . . . . . 221
3.7 Electronic Mail Notification Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Electronic Mail Notification Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Electronic Mail Notification Service Operation . . . . . . . . . . . . . . . . . . . . . . . . . 225
Devices that Support Email Notification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
3.8 Standard Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Web Server Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Web Server Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Devices that Support Standard Web Server Services. . . . . . . . . . . . . . . . . . . . 234

31006929.00 10/2005 5
3.9 FactoryCast Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
FactoryCast Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
FactoryCast Web Server Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Devices that Support FactoryCast Web Server Services . . . . . . . . . . . . . . . . . 240
3.10 FactoryCast HMI Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
FactoryCast HMI Web Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Devices that Support The FactoryCast HMI Web Service . . . . . . . . . . . . . . . . . 247
3.11 Other Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
FTP Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
SNMP Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
TFTP Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Telnet Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Quantum Device Support for Other Services. . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Other Services Supported by Premium Devices . . . . . . . . . . . . . . . . . . . . . . . . 257
Other Services Supported by TSX Micro Devices . . . . . . . . . . . . . . . . . . . . . . . 259
Other Services Supported by Momentum Devices . . . . . . . . . . . . . . . . . . . . . . 260
Other Services Supported by Advantys STB Devices . . . . . . . . . . . . . . . . . . . . 261
Other Services Supported by Power Logic Gateways/Bridges . . . . . . . . . . . . . 262
Other Services Supported by ConneXium Cabling Systems . . . . . . . . . . . . . . . 263
3.12 OPC Factory Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
OPC Factory Server. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
OFS Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 269
OFS Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272
Runtime Architecture for Unity/OFS/SCADA: a Simple Example . . . . . . . . . . . 275
Build-time/Runtime Architecture for Unity/OFS/SCADA Systems
that Are Not Frequently Modified . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
Build-time/Runtime Architecture for Unity/OFS/SCADA Systems
that Require Frequent Modification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Build-time/Runtime Architecture for a System with Multiple
SCADA Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
3.13 SCADA/HMI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
I/O Server to Field Device Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
SCADA Communications to Field Devices: Socket and Request Usage . . . . . 290
I/O Server and Display Client Communications. . . . . . . . . . . . . . . . . . . . . . . . . 294
Schneider Product Implementation Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
3.14 Redundancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
Network Redundancy and Communication Services. . . . . . . . . . . . . . . . . . . . . 297
Redundancy within a SCADA System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301
SCADA in a Quantum Hot-Standby System . . . . . . . . . . . . . . . . . . . . . . . . . . . 304
Hot Standby Swap and Ethernet Services. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
3.15 Gateway/Bridge Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 313
Gateway and Bridge Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314
Gateway and Bridge Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 318

6 31006929.00 10/2005
3.16 Supported Services per Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
Ethernet Services and the Transparent Ready Devices that Support Them. . . 321
3.17 System Performance Evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
System Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333
Modbus Messaging Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 334
Modbus Server Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 335
Modbus Messaging Client Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
I/O Scanner Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
Total Load on Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
System Performance Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
Gateway Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 352

Chapter 4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 355


4.1 About Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356
Introduction to Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 357
General Problem Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 358
4.2 Network Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 359
Introduction to Network Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360
Connection Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 362
Intermittent Connection Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 364
Slow Connection Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 365
Remote Access Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366
4.3 Services Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368
Services Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 369
Modbus Messaging and I/O Scanner Troubleshooting . . . . . . . . . . . . . . . . . . . 370
SNMP Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 372
Telnet and FTP Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373
Faulty Device Replacement/BootP Troubleshooting. . . . . . . . . . . . . . . . . . . . . 374
SMTP Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Time Synchronization (NTP) Troubleshooting Table . . . . . . . . . . . . . . . . . . . . 377
Web Troubleshooting Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 378
4.4 SCADA/HMI System Slow Response Time Troubleshooting . . . . . . . . . . . . . . 379
Slow Response Time (SCADA/HMI) Troubleshooting . . . . . . . . . . . . . . . . . . . 379
4.5 Bridge Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380
4.6 Lost Packet Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 381
Lost Packet Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 382
Using a Packet Capture Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 383
Packet Capture Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 384

31006929.00 10/2005 7
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 387

Appendix A I/O Scanning Response Times . . . . . . . . . . . . . . . . . . . . . . . . 389


A.1 Premium PLC I/O Scanner Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . 390
Premium I/O Scanner Response Times: Remote Input to Remote Output . . . . 391
Premium I/O Scanner Response Times: Remote Input to a Local Output . . . . 395
Premium I/O Scanner Response Times: PLC Memory to Remote Output . . . . 399
A.2 Quantum PLC I/O Scanner Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . 403
Quantum I/O Scanner Response Tmes: Remote Input to Remote Output . . . . 404
Quantum I/O Scanner Response Tmes: Remote Input to Local Output . . . . . . 408
Quantum I/O Scanner Response Times: Local Input to Remote Output . . . . . . 412

Appendix B Modbus Server Throughput Capacity . . . . . . . . . . . . . . . . . . 417


Quantum Modbus Server Throughput Capacity: Unity v2.0 . . . . . . . . . . . . . . . 418
Premium Modbus Server Throughput Capacity: Unity v2.0. . . . . . . . . . . . . . . . 420

Appendix C Modbus Client Response Times. . . . . . . . . . . . . . . . . . . . . . . 421


Modbus Client Response Times: Premium TSXP575634M . . . . . . . . . . . . . . . 422
Modbus Client Response Times: Premium TSXP57304M . . . . . . . . . . . . . . . . 429
Modbus Client Response Times: Quantum 140 CPU65150
with an Embedded Ethernet Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
Modbus Client Response Times: Quantum 140 CPU65150
with a 140 NOE77101 Ethernet Communications Module. . . . . . . . . . . . . . . . . 441
Modbus Client Response Times: Quantum 140 CPU65150
with a 140 NOE77111 Ethernet Communications Module. . . . . . . . . . . . . . . . . 446
Modbus Client Response Times: Quantum 140 CPU43412A
with a 140 NOE77101 Ethernet Communications Module. . . . . . . . . . . . . . . . . 451
Modbus Client Response Times: Quantum 140 CPU43412A
with a 140 NOE77111 Ethernet Communications Module. . . . . . . . . . . . . . . . . 456

Appendix D Gateway Response Time and Timeout Measurements . . . . 461


D.1 EGX200 Gateway Serial Server Response Time and
Timeout Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 462
EGX200 Serial Server Response Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 463
EGX200 Serial Server Response Measurements with One
Request Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 468
D.2 EGX400 Gateway Serial Server Response Time and
Timeout Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 473
EGX400 Gateway Serial Server Response Times . . . . . . . . . . . . . . . . . . . . . . 474
EGX400 Serial Server Response Measurements with One
Request Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 479

8 31006929.00 10/2005
D.3 174CEV30020 Gateway Serial Server Response Time and
Timeout Measurements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 484
174CEV30020 Gateway Serial Server Response Times . . . . . . . . . . . . . . . . . 485
174CEV30020 Serial Server Response Measurements with One
Request Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 490

Appendix E Standards and Other Considerations for Industrial Ethernet


Networks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 495
Standards and Organizations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 496
Electromagnetic Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 506
Copper Connector Standards Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 510
Conforming to Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 511
Transparent Ready Industrial Ethernet Conformance. . . . . . . . . . . . . . . . . . . . 514

Appendix F Earthing (Grounding) Procedures. . . . . . . . . . . . . . . . . . . . . . 517


Well-made Earthing (Ground) Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 518
Making an Earthing Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 519
Cable Shielding Connection Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 525
Copper Ethernet Testing Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 527
Performance Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 528
Definitions of Performance Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 530

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 535

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 561

31006929.00 10/2005 9
10 31006929.00 10/2005
Safety Information
§

Important Read these instructions carefully, and look at the equipment to become familiar with
Information the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn
of potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a Danger or Warning safety label indicates
that an electrical hazard exists, which will result in personal injury if the
instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.

DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will
result in death, serious injury, or equipment damage.

WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result
in death, serious injury, or equipment damage.

CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result
in injury or equipment damage.

PLEASE NOTE Electrical equipment should be serviced only by qualified personnel. No responsi-
bility is assumed by Schneider Electric for any consequences arising out of the use
of this material. This document is not intended as an instruction manual for untrained
persons.
© 2005 Schneider Electric. All Rights Reserved.

31006929.00 10/2005 11
Safety Information

12 31006929.00 10/2005
About the Book

At a Glance

Document Scope This user guide deals with the broad topic of industrial Ethernet, a key element of
Schneider Electric’s Transparent Ready strategy. The purposes of the guide are
twofold:
z to describe the impact of industrial Ethernet on new control system designs
z to give you the information you need to implement and support a Transparent
Ready solution that best meets your application requirements
The guide describes four key parts of a successful system implementation:
z planning a system for optimal performance
z selecting the right Ethernet services and devices for your application
z making the right choices as you design and install the system
z troubleshooting system problems effectively
The guide is written for:
z design engineers, system integrators and maintenance engineers who
understand industrial control systems and requirements but may not be familiar
with Ethernet products and services
z plant IT staff who understand the principles of Ethernet system design and
installation but may not be familiar with industrial control requirements and
environments
Ethernet technology is well established in the business and commercial worlds, but
it is relatively new to the automation industry. Because it is an open technology,
Ethernet offers a wide range of products and services from multiple vendors. The
advantages of an open approach are clear; you are no longer subject to the
communication constraints, costs, and development schedules of a proprietary
vendor for your system needs.
However, some Ethernet components may not interoperate optimally in an industrial
environment, and not all Ethernet devices support all the services you may want. To
successfully design and troubleshoot an industrial Ethernet system, you need a mix
of Ethernet IT and traditional automation knowledge. This guide is designed to help
bridge the gap between these two disciplines.

31006929.00 10/2005 13
About the Book

The guide should be used as a supplement to product-specific Transparent Ready


user manuals. To learn more about commercially available Transparent Ready
products, refer to the latest Transparent Ready catalog or go to
www.telemecanique.com.

Validity Note The data and illustrations found in this book are not binding. We reserve the right to
modify Schneider Automation’s products in line with Schneider Automation’s policy
of continuous product development. The information in this document is subject to
change without notice and should not be construed as a commitment by Schneider
Electric.

Related
Documents
Title of Documentation Reference Number
ConneXium Ethernet Switch, 499NES25100 5-Port, 10/100 Base-TX 31005153
Quick Reference Guide
ConneXium Ethernet Switch, 499NES18100 8-Port, 10/100 Base-TX 31005416 (E)
Quick Reference Guide 31006210 (F)
31006211 (G)
31006212 (S)
ConneXium Ethernet Cabling System Switch Management Manual 31005844 (E)
31005845 (F)
31005846 (G)
31005847 (S)
ConneXium Ethernet Cabling System Quick Reference Guide 31005848 (E)
(Electrical Switch 10/100 Mbps 7TX 499NES17100/Optical Switch 31005849 (F)
10/100 Mbps 5TX/2FX 499NOS17100) 31005850 (G)
31005851 (S)
499NTR10100 ConneXium Transceiver Quick Reference Guide 35004254
Modicon Quantum Ethernet TCP/IP Module User Guide 840 USE 107
Modicon Quantum Ethernet Web Embedded Server User Guide 840 USE 115
Quantum 140 NOE 771 xx Ethernet Modules User Guide 840 USE 116
140NOE771xx/140NWM10000/140CPU651x0, Unity Pro 2.0 User 33002479 (E)
Guide 33002480 (F)
33002481 (G)
33002482 (S)
FactoryCast User’s Guide For Quantum, Premium and Micro 31001229 (E)
31003182 (F)
31003183 (G)
31003184 (S)
31004698 (I)

14 31006929.00 10/2005
About the Book

Title of Documentation Reference Number


FactoryCast HMI Setup Manual for Premium and Quantum HMI 35007632 (E)
Modules 35007633 (G)
35007634 (F)
35007635 (S)
35007636 (I)
Momentum 170ENT11001/170ENT11000 Ethernet Communication 870 USE 114
Adapter User Guide
174 CEV 200 30 Modicon TSX Momentum Modbus Plus to Ethernet 890 USE 151
Bridge User Guide
174 CEV 300 20 Modbus to Ethernet Bridge User Guide 890 USE 195
Advantys STB Ethernet Modbus TCP/IP Network Interlace 890 USE 177
Applications Guide
TSX Micro TSX ETZ 410/510 Modules User Manual 35004734 (E)
35004735 (F)
35004736 (G)
35004737 (I)
35004738 (S)
Premium and AtriumUsing Unity Pro Ethernet Network Modules User 35006192 (E)
Manual 35006193 (F)
35006194 (G)
35006195 (S)
Ethernet Module MAnuals for Unity UNYUSE20110V20E
Altivar 58 Ethernet Modbus TCP/IP Communication Option VVDED300053
Instruction Bulletin
Sepam series 80 functions Catalog
EGX Installation Guide 63230-314-200B1
EGX User’s Guide 63230-208A1
EGX Reference Guide 63230-314-202A2

You can download these technical publications and other technical information from
our website at www.telemecanique.com.

31006929.00 10/2005 15
About the Book

Product Related Schneider Electric assumes no responsibility for any errors that may appear in this
Warnings document. If you have any suggestions for improvements or amendments or have
found errors in this publication, please notify us. No part of this document may be
reproduced in any form or by any means, electronic or mechanical, including
photocopying, without express written permission of the publisher, Schneider
Electric.
All pertinent state, regional and local safety regulations must be observed when
installing and using this product. For reasons of safety and to assure compliance
with documented system data, only the manufacturer should perform repairs to
components.

User Comments We welcome your comments about this document. You can reach us by e-mail at
[email protected]

16 31006929.00 10/2005
Transparent Ready

1
At a Glance

Overview This chapter introduces you to Transparent Ready, a major strategic program to
deploy Internet technologies in Schneider Electric products and services.

What's in this This chapter contains the following topics:


Chapter?
Topic Page
Transparent Ready 18
Transparent Ready Service Classes Offered 21
Users of this Guide 25
How this Guide Is Organized 26

31006929.00 10/2005 17
Transparent Ready

Transparent Ready

What Is In 1996, Schneider Electric proposed a combination of technologies that


Transparent transformed industrial automation. This approach employed a combination of the
Ready? physical and data link layers of Ethernet, as defined by the OSI model (see p. 127),
with TCP/IP and Modbus for industrial Ethernet solutions. The concept, originally
known as Transparent Factory, has evolved to become the Transparent Ready
initiative.
Transparent Ready is a major strategic initiative that deploys Internet technologies
into Schneider Electric’s products and services. Any Schneider Electric product or
service that supports Internet technologies is a Transparent Ready product.

What Are Internet Internet technologies describes a set of technological innovations that allow
Technologies? information to be managed through the Internet and related hardware, software,
languages and protocols. They are used to transfer, present, and manage
information. Examples include:
z Ethernet (wireless, fiber optic, copper, and other) media through which
information is transferred
z Ethernet frame, the Internet protocol suite (TCP/IP), SOAP, and other protocols
that transfer information
z Java, HTML, XML, and other language protocols that present the information

What Is Industrial Ethernet refers to the way that data accesses the network, how the messages are
Ethernet? framed for transmission and reception, and the physical characteristics of the
network: topology, cables, connectors and infrastructure.
Industrial Ethernet is the commercial name adopted by the industrial automation
market segment to refer to the use of Ethernet in an industrial environment. The term
is now so generic that other Internet technologies are included even if Ethernet itself
is not present. For example, Ethernet is not used in an industrial wireless 802.11
communication, but it is still considered an industrial Ethernet application.
A detailed analysis of industrial Ethernet (see p. 29) is presented in this manual, in
which the different characteristics and origins of Ethernet, TCP/IP and Modbus are
explained.

18 31006929.00 10/2005
Transparent Ready

Industrial and In an industrial control environment, programmable logic controllers (PLCs) around
Commercial the plant act as servers for the input and output (I/O) modules. PLCs may be
Ethernet interconnected by industrial fieldbuses, further distributing the data storage and
Comparison management responsibilities. A PLC may act as a server for some devices and as
a client for others:

The industrial network shown above is very different from a typical business and
commercial applications. Due to the critical nature of many control applications,
client devices throughout the industrial Ethernet system tend to be more intelligent
than standard commercial Ethernet clients. The ways in which the client and server
devices communicate with each other are defined by the Transparent Ready
services that they use.
A business Ethernet network is designed with a bank of servers residing in a control
room. Business data is stored and managed in this centralized area, and is sent to
and from the clients through switches and routers dispersed throughout the
enterprise. Firewalls secure the enterprise from unauthorized entry.
Industrial Ethernet is different from commercial Ethernet in three main areas:
environmental, layout, and performance requirements.
Office Ethernet Industrial Ethernet
Environment Suitable for human occupancy Light-duty and heavy-duty industry
and work
Normal temperature range Potential harsh environments
Little dust, moisture, and vibration Exposure to electromagnetic noise
Hardly any mechanical loads or Extreme temperatures, climatic
problems with chemicals variables
Low EMC requirements Dust, moisture and vibration possible

31006929.00 10/2005 19
Transparent Ready

Office Ethernet Industrial Ethernet


Minimum pulling requirements Risk of mechanical damage or
problems with chemicals
Required grounding and bonding of
industrial equipment and cabling
Layout Limited floor size in vertical Large manufacturing areas in only one
buildings floor
Star topology Star, bus, and daisy chain topologies
may be used
In accordance with office Self-healing ring and redundant self-
standards healing ring to maximize up-time
Performance High network availability with High network availability (typically,
reliable connections 24X7 with redundancy)
Large data packets Low bandwidth usage always
recommended (no higher than 40% at
all times)
Acceptable level of predictability Small data packets. Predictability is
essential

There are other areas of differentiation as well, such as the Ethernet services
required.

The Transparent Transparent Ready offers a three-stage strategy:


Ready Strategy 1 Expose industrial control information via open or de facto standards
OPC and embedded Web server products open Schneider Automation devices
to several systems that can access information and knowledge buried in the
devices. Standard Web server technology allows any qualified personnel in the
enterprise to interact with the automation system.
2 Create interfaces and integration points between automation systems and
business applications
Using the device as a data server within a client/server architecture allows
Schneider alliances to develop interfaces to business systems in Windows or
UNIX environments.
3 Develop an open infrastructure that supports real-time and deterministic behavior
The network is the backbone for an efficient information exchange. Ethernet,
TCP/IP and Modbus are Schneider's primary choices for delivering an open
network. Switches and hubs help to build real-time and highly available
subnetworks and to address a broad range of applications.

20 31006929.00 10/2005
Transparent Ready

Transparent Ready Service Classes Offered

Summary The Transparent Ready service classes make it possible to identify the services
provided by each product:
z Diagnostic, display and control services via Web technologies
z Ethernet communication services

Transparent Ready

Ethernet T CP/IP Web techn ologies


techno lo gies and and services
services

Web Service Transparent Ready Web services are defined by 4 classes identified by letters:
Classes z Class A: no Web services
z Class B: standard Web services
z Class C: configurable Web services
z Class D: active Web services
Transparent Ready products with an embedded Web server can provide 4 types of
Web service:
z maintenance Web services
z control Web services
z diagnostic Web services
z optional Web services such as documentation or configuration

31006929.00 10/2005 21
Transparent Ready

The following chart specifies the services provided by each Web service class:
Web Server Web Services
Class Maintenance Monitoring and IT Link Diagnostics Optional
D Active Web User Website Autonomous execution of User-defined states User documentation
Server update specific services (e.g., alarm
notification by E-mail,
exchange with databases,
calculations)
SOAP/XML (client/server)
C Configurable PLC variables editor Communication
Web Server Remote commands service diagnostics
User Web pages State of internal
SOAP/XML (server) product resources
B Standard Remote device Device description Device diagnostics Configuration of
Web Server software update Data viewer network parameters
Remote auto- and Ethernet
tests communication
services
Device
documentation
A No Web No Web services
Server

Ethernet The Ethernet communication services provided by a product are defined in 3


Communication classes. Each class is identified by a number:
Service Classes z Class 10: standard Ethernet communication services
z Class 20: Ethernet communication management services (network level and
product level)
z Class 30: advanced Ethernet communication services
Transparent Ready products can provide 8 types of Ethernet communication
services:
z Modbus TCP messaging
z I/O scanning
z Faulty device replacement
z Network management (SNMP)
z Global data
z Bandwidth management
z Time synchronization (NTP)
z Email event notification (SMTP)

22 31006929.00 10/2005
Transparent Ready

The following table specifies the services provided for each Ethernet communication
service class:
Service Ethernet Communication Services
Class Modbus I/O Scanning FDR SNMP Global SMTP Bandwidth NTP
Messaging Data Management
30 Direct read/ Periodic read/ Automatic Use of the Publica- Event Monitoring of Device
write of I/O write of I/O control/ MIB library tion and notifica- local load clock
Configuration update of by an subscrip- tion by level synchro-
of the list of device SNMP tion of email nization
devices parameter manager network
scanned configuration variables
20 Automatic Product
assignment detection
of IP address of by an
and network SNMP
parameters manager
Control/
update of
configuration
and product
parameters
by the user
10 Read/Write Local
data words assignment
of IP address
Verification
of duplicate
IP addresses

31006929.00 10/2005 23
Transparent Ready

Choice of The services provided by a Transparent Ready product are identified by a letter
Transparent defining the level of Web service, followed by a number defining the level of Ethernet
Ready Products communication service. For example:
z A class A10 product is a product with no Web service and standard Ethernet
services.
z A class C30 product is a product with a configurable Web server and advanced
Ethernet communication services.
The services provided by a higher class include all the services supported by a lower
class.
Transparent Ready products are chosen from 4 main families:
z sensor and preactuator type field products (simple or intelligent)
z controllers and PLCs
z human-machine interface (HMI) applications
z dedicated gateways and servers
The following selection chart can be used for choosing Transparent Ready products
according to the required service classes.

Web services

Ethernet C lass A Class B Class C Class D


com municatio n
services No se rvice Stand ard Con fi gura ble Active
Adva nced
service

Class 30
B30
C ommun icatio n
mana geme nt

C ontrol lers an d PLCs


servi ces

Class 20
B20 C20

Simp le an d intel lig ent


pro ducts
A10 B 10 D10
Sta nda rd
service s

Class 10

24 31006929.00 10/2005
Transparent Ready

Users of this Guide

Summary To successfully design and troubleshoot an industrial Ethernet system, you need a
mix of Ethernet IT and traditional automation knowledge. A collaborative relationship
between the industrial control engineer and the plant IT professional is key to the
success of a Transparent Ready system.

Audiences This table describes the two audience groups for whom this guide is written, their
Analysis for this areas of expertise and their information needs. It also gives references to the
Guide sections of this guide where the needed information can be found:
Audience Expertise Knowledge Needs
IT z TCP/IP protocol z Industrial plant environment and
Professionals z Architectural alternatives, conditions
such as Ethernet switching z Network shielding from noise and
z Network security issues interference
z Hardware component z Physical network implementation in
selection an industrial setting
z Open systems z Operational priorities: redundancy,
z Standards interpretation by quick recovery
different vendors z Safety issues associated with the
z Network component selection failure of automation controls
Industrial z Control device interaction z Ethernet technology requirements
Control z Industrial installation z Transparent Ready service selection
Professionals requirements Transparent Ready services
z Data transfer speed (see p. 157)
requirements z Open system environment
z Recovery and redundancy requirements
needs z Open system communications issues
z Integration of products from multiple
vendors
z System design and protocols
z System security issues

31006929.00 10/2005 25
Transparent Ready

How this Guide Is Organized

Summary A Transparent Ready system comprises two key elements:


z the Ethernet network over which the devices exchange application data
z the services that enable the transactions that happen on the network
The three chapters that follow contain stand-alone discussions of the major topics
you will need to consider as you design a new Transparent Ready system or
maintain an existing system. The chapters may be read in any order, based on the
topics that interest you the most.

Physical Physical Planning, Design and Installation of a Transparent Ready Industrial


Planning, Design Ethernet Network, p. 29 describes how to design, install and verify your Transparent
and Installation Ready industrial Ethernet network to best meet your application requirements,
including the following considerations:
z design standards
z choice of cabling and components
z Internet technology overview
z environmental requirements
z protective earthing recommendations
z testing your network
z IP Addressing
z routing
z security

Transparent Services Overview, p. 157 describes each of the Transparent Ready services, the
Ready Services appropriate device choices for each, and the Transparent Ready devices that
support each service. Service support is a very important device selection criterion.
Choosing the right services enables you to account for the following system design
issues:
z appropriate device response times
z avoidance of device overload
z application throughput requirements for the entire system
This chapter also explains how the different services operate and their expected
performance.

26 31006929.00 10/2005
Transparent Ready

Trouble- Troubleshooting, p. 355 provides procedures for how to maintain a Transparent


shooting Ready system after installation. These procedures include how to:
z identify problems such as
z network infrastructure issues
z device incompatibility
z performance issues
z environmental interference
z identify sources by:
z device query and response times
z device incompatibility
z identify resolutions such as:
z device replacement
z system redesign
z work-arounds for an unfixable problem

Supporting A set of appendixes containing the results of performance measurements is


Information presented at the end of the guide. The results compare the response times and
throughput rates of different Transparent Ready devices that use some of the key
network services. There is also a detailed section on Standards.

31006929.00 10/2005 27
Transparent Ready

28 31006929.00 10/2005
Physical Planning, Design and
Installation of a Transparent
Ready Industrial Ethernet Network 2
At a Glance

Overview This chapter discusses the topics concerning Ethernet that an automation or control
engineer should consider when planning, installing, and verifying a Transparent
Ready industrial Ethernet network.
In designing a Transparent Ready industrial Ethernet network to fit your facility, you
should have a general knowledge of network layout, criteria for choosing
components, issues pertinent to the design process and the existing standards for
office network components and layout that guide industrial network development.
You may consult your IT personnel or a variety of written and electronic sources for
more detailed information.
The planning section provides a description of network topologies, an overview of
applicable standards for offices and plants, overall design considerations, and
recommendations for selecting components. The installation section describes EMC
installation and the installation of cables and connectors. The section on verification
discusses methods for your network.

What's in this This chapter contains the following sections:


Chapter?
Section Topic Page
2.1 Required Standards 30
2.2 Physical Planning and Layout 36
2.3 Environmental Requirements 70
2.4 Selection of Industrial Ethernet Components 80
2.5 Installation 96
2.6 Verification of a Transparent Ready Industrial Ethernet 117
2.7 Additional Considerations for Designing a Transparent Ready 124
Industrial Ethernet Network

31006929.00 10/2005 29
Planning and Layout

2.1 Required Standards

At a Glance

Overview Office-based Ethernet standards are being enhanced and modified to meet
industrial Ethernet requirements. These Ethernet standards are being combined
with industrial standards to account for the environment in which an industrial
Ethernet must operate and its performance and topology requirements.
Many standards are used to define industrial Ethernet. These standards are
developed and maintained by different standards organizations and are related to
the following:
z protocols
z the physical layer
z environmental requirements
z cabling structures
z cable specifications
Many of these standards are regional and may apply only to specific areas or
countries.

What's in this This section contains the following topics:


Section?
Topic Page
On-going Industrial Ethernet Standardization Efforts 31
Required Standards for Planning and Installation 34

30 31006929.00 10/2005
Planning and Layout

On-going Industrial Ethernet Standardization Efforts

Introduction There are as yet no industrial Ethernet planning standards to refer to for guidelines
and rules. There are, however, many recommendations for industry, based on the
office environment standards (TIA/EIA-568-B, ISO/IEC-11801, and EN 50173), that
have been placed before standards committees by several industrial networking
organizations.
The most significant international standardization effort is by a collaborative group
of experts from IEC TC65, TIA TR-42.9, and CENELEC TC215 WG1. Their work will
be published as the ISO/IEC 24702 standard.

TIA TR-42.9 CLC TC215 WG1 PTP ISO/IEC JTC1SC26 IFTG

ISO/IEC 24702 Publication of the ISO/IEC 24702 standard is planned for sometime in 2006.
Standard: Time The ISO/IEC 24702 standard defines generic cabling for industrial premises and
Table and related IT specifications. For its definition of balanced cabling and optical fiber, it
Definitions takes the following from ISO/IEC 11801:
z applications
z link and channel transmission classes
z transmission performance components
It also adds new concepts such as the classification environment (as presented
below in the MICE table), suitable components, and a modified cabling structure.

31006929.00 10/2005 31
Planning and Layout

MICE Concept The IEC TC65C working group originated the MICE concept of mechanical rating to
Mechanical define environmental parameters and their requirements. MICE includes three
Rating environmental classes:
z Class 1: for general (non-industrial/non-residential)
z Class 2: for light industrial
z Class 3: for heavy industrial
It also defines the environmental parameters on which its name is based:
z mechanical
z ingress
z climatic
z electromagnetic
Each environmental parameter has a low-level (1), medium-level (2), and high-level
(3) rating that is indicated in subscript beside each parameter's letter, for example
M2I2C3E. As you can see from this example, parameter levels may be mixed and
may vary along a single channel.
Each environmental class has a worst case scenario as given below:
z M1I1C1E1: for a general (ISO/IEC 11801) environment
z M2I2C2E2: for a light industrial environment
z M3I3C3E3: for a heavy industrial environment
The MICE table is shown below:
---> Increasing Severity --->
Class
Mechanical Shock/Bump M1 M2 M3
Vibration
Tensile Force
Crush
Impact
Ingress Particulate I1 I2 I3
Immersion
Climatic Temperature C1 C2 C3
Ambient
Rate of Change
Humidity
UV Radiation
Solar Radiation
Liquid Pollution
Gaseous Pollution

32 31006929.00 10/2005
Planning and Layout

---> Increasing Severity --->


Class
Electromagnetic ESD E1 E2 E3
Radiated RF
Conducted RF
EFT
Surge
Magnetic Field

ISO/IEC 24702: To avoid different proprietary developments, the Customer Premises Cabling
Unification of working group (ISO/IEC JTC 1 SC 25 WG3) was created. This group in turn
Major Standards launched the Industrial Premises Task Group (ISO/IEC JTC 1 SC 25 WG3.IPTG).
Committees To achieve maximum cooperation and expedite the development of an international
standard, the Industrial Premises group has directly involved experts from the major
standards organization committees (IEC TC65C, TIA TR42.9, and CENELEC
TC215 WG1). The purpose of this new group is to standardize the characteristics of
cabling systems for industrial facilities. The standard will be published as ISO/IEC
24702.
The Industrial Premises Task Group is jointly led by ISO/IEC JTC 1/SC 25 and IEC
SC 65C.
z The JTC 1/SC 25 subcommittee is responsible for cabling for building sites.
z The IEC SC 65C subcommittee is responsible for cabling for process control. The
IEC SC 65C is a subcommittee of the IEC TC65C in charge of developing
standards for industrial networks.
Due to the fact that the ISO/IEC 24702 standard is currently being developed,
Schneider Electric suggests that you follow the guidelines that are defined in this
chapter.

31006929.00 10/2005 33
Planning and Layout

Required Standards for Planning and Installation

Ethernet The Ethernet standard to consider when you plan an industrial Ethernet network is
Standards the one defined by the IEEE and adopted by ISO/IEC:
IEEE standard 802.3, 2002 Edition, Part 3: Carrier sense multiple access IEEE 802.3
with collision detection (CSMA/CD) access method and physical layer
specifications.
Information Technology. Telecommunication and Information exchange ISO/IEC 8802-3
between systems. Part 3: Carrier sense multiple access with collision
detection (CSMA/CD

IT Structured Cable manufacturers, suppliers, building designers, network architects, and service
Cabling technicians all rely on cable standards to provide the specifications for their projects.
Standards These specifications include all aspects of the planning, design, and installation
phases, as well as the configuration, performance, conformance testing, and
verification of the final system.
The three major world standards shown in the table below are the foundations for
cabling planning, selection, installation, and performance of IT networks. Each
standard in the table is based on the one that precedes it. As a result, all of the
standards are very similar.
Area and Standard Standards Description
Organizations
United TIA/EIA-568-B Telecommunications Commercial Building
States Industry Association Telecommunication Cabling
Electronic Industries standard - defines how to
Association design, build, and manage a
structured wiring system.
International ISO/IEC 11801 International Generic Customer Premises
Organization for Cabling standard - defines
Standardization general cabling specifications
International for customer premises; based
Engineering on TIA/EIA-568.
Consortium
Europe CENELEC EN 50173 Comité Européen de Defines generic cabling and
Normalisation European open-market cabling
Electrotechnique components; based on ISO
11801.

34 31006929.00 10/2005
Planning and Layout

Environmental Environmental standards are not specifically related to industrial Ethernet, but apply
Standards to any device or equipment located in the particular environment.
Schneider Electric has defined three types of environments that coincide with the
MICE table:
z office environment, where standard Ethernet can be used
z light industrial environment
z heavy industrial environment
The environmental requirements for industrial Ethernet are defined by the same
specifications that cover other industrial automation devices (see p. 70).

31006929.00 10/2005 35
Planning and Layout

2.2 Physical Planning and Layout

At A Glance

Overview This section presents cabling standards for an industrial Ethernet network. It also
describes layouts for a Transparent Ready industrial network. To assist in
understanding this structure, basic network topologies are reviewed. LAN
technologies and issues relevant to an industrial Ethernet network are discussed, as
are WAN technologies and hardware.

What's in this This section contains the following topics:


Section?
Topic Page
Industrial Ethernet Cable Planning 37
Structured Cabling Standards 38
Cabling in a Transparent Ready Industrial Ethernet System 42
Understanding Basic Network Structure 46
Developing Network Architecture for Industrial Ethernet Networks 52
Redundant Ring Topology 56
LAN Technologies and Network Design 58
LAN Hardware 62
Other LAN Considerations 64
WAN Technologies and Network Design 65
WAN Hardware 68

36 31006929.00 10/2005
Planning and Layout

Industrial Ethernet Cable Planning

Introduction Because there are as yet no defined standards for the physical layout of an industrial
Ethernet network, Schneider Electric has chosen to conform to the recommen-
dations submitted by standards organizations such as Modbus-IDA, IAONA, PNO,
and the work in progress by the IEC.
An industrial manufacturing site is a physical facility in which manufacturing or
process control activities take place. In most cases, the site consists of multiple
buildings or plants that manage interconnected, but separate, processes. The
physical layout and environmental variables inherent in each of these facilities may
result in different requirements for the cabling system at each site. This section
describes Schneider Electric’s recommendations for planning industrial Ethernet
networks for manufacturing and process control environments.

Cable Planning A network site plan communicates the physical and logical layout of a network that
is specific to your site requirements. This plan is an important part of the network
design process for your facility. The site may be an industrial facility or an
infrastructure site. Infrastructure sites include environments, such as tunnels, water
treatment plants and airports, with additional requirements to those of an industrial
site. Both types of site have environmental variables that may be extreme compared
to office environments. The existing standards for office environments, though
useful and valid, have limited application in such environments. Application
performance under rigorous environmental requirements, including climatic
conditions and ingress protection, has a higher priority in an industrial environment.
The following topics provide general information on planning an industrial Ethernet
network for industrial and infrastructure applications. This information does not
attempt to cover every possible variation of these two environments. You should
adapt this information to the specific needs of your site.

31006929.00 10/2005 37
Planning and Layout

Structured Cabling Standards

Introduction Schneider Electric recommends the use of structured cabling standards including
TIAEIA 568B, ISO/IEC 11801 and CENELEC EN 50173 (see p. 34). Standards for
cabling are currently being developed by a working group of the standards
organizations.

Elements of a The table below shows the elements of a cabling system as defined by the ISO/IEC
Cabling System 11801 standard. This standard also identifies the interfaces through which different
network components are connected to the cabling system.
Elements Abbreviation Purpose
(Hierarchical Order)
Campus Distributor CD distributor from which the campus backbone cable
emanates
Campus Backbone cabling between buildings that share
Cable telecommunications facilities
Building Distributor BD the distributor where the bldg. backbone cable
terminates, connections to campus backbone
cable are made
Building Backbone intermediate cable & connecting hardware
Cable
Floor Distributor FD connects the horizontal cable system to other
cabling subsystems
Horizontal Cable cabling between and including the
telecommunications outlet and the horizontal
distributor
Transition Point TP location in horizontal cabling subsystem where flat
(optional) undercarpet cabling connects to round cabling
Telecommunications TO female telecommunications device found in the
Outlet work area

Cabling For a cabling installation to conform to the ISO/IEC-11801 standard, the


Subsystems configuration must connect the following subsystems of a cabling system:
z campus backbone; campus uses building distributors
z building backbone; every building has a building distributor
z horizontal cabling; every floor has a floor distributor

38 31006929.00 10/2005
Planning and Layout

Structure of The generic cabling system defined by the ISO/IEC 11801 standard is a hierarchical
Cabling Systems star structure (see p. 47). The diagram below shows a central campus distributor
and a campus backbone cabling system linking multiple building distributors. Each
building is required to have at least one building distributor. Each building distributor
connects to the central campus distributor using a star topology. The campus
distributor becomes the central communication unit. As a backup and safety
precaution, you should create redundant links between buildings. Within a building,
every floor has its own floor distributor that serves up to 2000 m2 of office space.

1 Central campus distributor


2 Campus backbone cabling
3 Building distributor
In a campus that has only one building, the primary distribution point becomes the
building distributor in that building. However, it is possible for a large building to act
as a campus and have one campus backbone with several building distributors.
The number of subsystems and type of elements included in your implementation
depend on the following:
z size of the campus or building
z geography of the site
z purpose of the cabling system (applications and equipment)
z types of end user

31006929.00 10/2005 39
Planning and Layout

Configuration It is possible to configure a generic cabling system to your specific needs by


rearranging the distributors to support different topologies (see p. 46), such as bus,
star, and ring. The following diagram shows the linear connections of a cabling
system from campus distributor to the terminal outlet and equipment.

1 Campus distributor
2 Backbone cabling
3 Building distributor
4 Secondary cabling
5 Floor distributor
6 Tertiary cabling
7 Telecommunication outlet

40 31006929.00 10/2005
Planning and Layout

The next two diagrams show how a generic cabling system can be physically
implemented in a single building or multiple buildings along a campus backbone.

CD

BD BD BD

FD FD FD FD

TO TO TO
TP

TO TO
Optional

2 Backbone cabling
4 Secondary cabling

2 4 6 8

2 Backbone cabling
4 Secondary cabling
6 Tertiary cabling
8 Patch cord
9 Generic cabling system

31006929.00 10/2005 41
Planning and Layout

Cabling in a Transparent Ready Industrial Ethernet System

Introduction The Transparent Ready approach to planning a cabling system is similar to that of
industrial Ethernet organizations such as Modbus-IDA, based on the accepted ISO/
IEC 11801, EN 501731, and TIA/EIA 568B standards.

Multiple Plant The following diagram shows a cabling system with the following parameters:
Site Example z an industrial site distributor that acts as the central communication unit instead of
a campus distributor (see p. 38) and connects plant distributors along an
industrial site backbone
z plant distributors that connect office plant and plant floor distributors along a plant
backbone
z plant floor distributors that connect to cabinet distributors (CD, also called
machine or field distributors, FD) and the devices and device outlets (DO) inside
the cabinet
z office plant distributors that connect to telecommunications outlets that are
themselves connected to printers and computers
It is important to understand that a site may have many plants within it. The following
example shows an overview of a grain site with 6 plants.
Industrial Site

Administration Office 2 3
Port Plant
5
1
Shipping
Plant

4
Mill/Crushing Plant

Oil Extraction Plant

Mixing Plant Silo Plant

1 SD Site distributor
2 PD Plant distributor
3 POD Plant office distributor
4 PFD Plant floor distributor
5 FW Firewall

42 31006929.00 10/2005
Planning and Layout

SIngle Plant The following illustration is a closer view of a single grain plant within the site shown
Example in the previous figure.

4 1

2 2

6 6 6

7
7
7
8

7
7

1 SD Site distributor
2 PD Plant distributor
3 POD Plant office distributor
4 FW Firewall
5 PFD Plant floor distributor
6 CD Cabinet distributor
7 DO Device outlet
8 FD Field distributor

31006929.00 10/2005 43
Planning and Layout

Industrial Site An industrial site distributor plays the same role as a campus distributor in the ISO/
Distributor IEC 11801 standard, as the distributor from which the backbone cable emanates.
This distributor is managed by IT personnel and can be one or more devices (racked
switches) with multiple numbers of ports. Typically, it is located in an office
environment and provides the connection for the entire manufacturing site to the
Internet and to other physical sites in the same company or organization. Traffic in
and out of the site is isolated by a router (see p. 68) and secured by a firewall.

Industrial Site The industrial site backbone is the cabling system that extends from the industrial
Backbone site distributor to the plant distributors. Typically, the industrial site is a self-healing
ring (see p. 54) that can be made redundant with a dual self-healing ring (see p. 56).

Plant Distributor The plant distributor connects the industrial site backbone to a plant. It acts as a
building distributor. Most industrial sites consist of one or more separate plants.
These different plants may have control rooms from which the plant is operated, or
motor control centers where the MCC and control devices are located. Typically, the
plant distributor is located in either the control or MCC room. The environmental
requirement for a plant distributor is either office or light-industrial.

Office Plant As mentioned previously, the plant distributor is usually located either in the control
Distributor and or MCC room; the plant distributor is connected to the other distributors, such as the
Plant Floor office plant distributor and the plant floor distributor. The office plant distributor
Distributor manages the terminal outlets for the plant office. These terminals are used to
connect printers, computers, and video conferencing devices. The plant floor
distributor manages equipment on the plant floor. In most cases, these two
distributors are located in either an office or a light-industrial environment. The office
plant distributor is usually managed and maintained by IT personnel. The plant floor
distributor is managed by personnel responsible for the cabinet distributors (also
called field distributors or machine distributors). The traffic between the plant floor
distributor and the plant distributor is isolated with a router and secured with a
firewall.

44 31006929.00 10/2005
Planning and Layout

Cabinet, Field, Typically, cabinets contain devices with a low number of ports or connections, such
and Machine as switches. Cabinet distributors (also called field distributors or machine
Distributors distributors) provide connectivity to the devices located inside a cabinet, in a
machine, or on the plant floor.
The following table shows the environmental requirements based on the location of
the devices.
Device Location Environmental Requirement
Inside a cabinet Light industrial environment
In a machine Light or heavy industrial environment
On plant floor Heavy industrial environment

Inside the cabinets, the configuration is star or daisy chain (using devices with
two Ethernet ports). The next topic (see p. 46) presents some typical network
topologies and how they can be developed in an Ethernet environment. These
topologies are usually deployed beginning with the plant floor distributor. Device
outlets (DOs) are located inside the cabinet. If the devices are located on the
plant floor, there can be either a DO or a new distributor for devices in the field
(called a field distributor or FD).

31006929.00 10/2005 45
Planning and Layout

Understanding Basic Network Structure

Summary The physical layout, or topology, of a network consisting of cables, components and
devices can be structured in any of several architectures:
z bus
z star
z daisy chain
z ring
z dual ring
z mesh
Illustrations of each type of layout are included. Each layout has its advantages and
disadvantages, as shown in the tables. Switches and hubs are mentioned in
conjunction with the network architecture. Schneider Electric recommendations for
network layout are also discussed.

Bus Topology A bus topology has a similar layout to a more traditional automation network such
as the Modbus Plus. A single backbone cable connects all the devices on the
network. Terminators are placed at each end of the backbone to allow signals to be
sent and cleared over the network. Devices, usually connected using T-connectors,
can be installed anywhere along the bus.

1 1
2 3
1 terminator
2 backbone
3 T-connector
A section of backbone cable is known as a segment. Several segments can be
connected using bridges or repeaters, as shown in the illustration below.

46 31006929.00 10/2005
Planning and Layout

1 Segment 1
2 Repeater
3 Segment 2

Only one device at a time can send or transmit a packet of information. The packet
travels the entire bus backbone cable. For this reason, a bus topology is considered
a shared medium. Terminators are very important because a cable break can result
in all devices losing their ability to communicate.
Advantages Disadvantages
Low cost. Scalability is a problem; it is difficult to change
the network as your needs change. As traffic
and the number of devices increase, the
performance of the network decreases.
Easy installation; all network devices are The devices are usually connected using taps
connected to a cable segment, and you into the trunk cable. If a device or segment is
need only enough cable to connect the lost, all the devices further down the line could
equipment that you have. become unavailable.
The backbone follows the a path around the Because all the devices share the same
plant much like a proprietary automation backbone cable, the throughput is limited; only
network, making the network design easy to one device can communicate at any time.
understand for designers new to Ethernet- The speed of all devices on a bus network must
in-automation applications. be the same.

Star Topology In a star topology, all the devices are connected though a central device. A star
topology is a common network layout for office environments and also for newer
automation environments.

star star

31006929.00 10/2005 47
Planning and Layout

In a star topology, devices can use dedicated sections of the network for various
services.
Advantages Disadvantages
Network throughput is much higher than on Star topologies are more costly because a
a shared-media bus topology. dedicated cable must be run to each device.
Network reconfiguration is much easier. To offset this disadvantage, network
infrastructure components (switches, hubs,
Centralizing network components makes
etc.) are used in cabinets on the factory floor
administration easier; centralized
so that a group of local devices can be
management and monitoring of network
connected together. A single long cable can be
traffic enhances network performance.
run back to a central point to support the
Diagnostics are simple; if a network segment group, rather than using separate cables for
fails, it affects only the devices directly each device.
connected to that segment.
Infrastructure components use monitoring
software and device-based LEDs to indicate
failures; most single points of failures can be
diagnosed and repaired quickly.
Resilience; a cable failure takes only that
device out of service.
You can have more devices on a single
network than on a bus topology.

Daisy Chain In daisy chain topology, the device is part of the trunk cable, unlike in bus topology
Topology where the device is connected to the cable through a tap connector and is not
considered part of the trunk cable. Every device in a daisy chain has two network
ports; information flows through the device. Although a daisy chain is linear, there
are branching devices available that allow the development of more complex
topologies.
The Interbus is an example of as daisy chain network.
Advantages Disadvantages
Low cost; there is In a linear configuration, if a device fails, the network gets cut.
no need to consider If not properly designed, the devices in a daisy chain may become
Tap connectors. overloaded trying to manage the information flowing through them.
Potential network overload; all devices share the same trunk cable.

48 31006929.00 10/2005
Planning and Layout

Ring Topology In a ring topology, all devices or network infrastructure components are connected
in a loop with no beginning or end. Packets travel in a single direction on the ring as
they are passed from one device to the next. Each device checks a packet for its
destination and passes it on to the next device.

Ring topologies provide redundancy. The failure of a single link is handled by routing
traffic in the opposite direction. A ring may be based on token rotation or random/
shared access. Alternatively, it may be a switched network where all the devices
access the network at the same time at different speeds.
Advantages Disadvantages
Redundancy; the failure of a single link High cost; more cabling is needed to complete the
or infrastructure component does not ring.
affect the entire network.
A ring topology uses software to Network infrastructure components need
monitor the network links. intelligence to respond to device failures; they are
more costly than simple bus or star components.

31006929.00 10/2005 49
Planning and Layout

Dual Ring When industrial automation systems are used in critical applications where
Topology downtime is unacceptable, a dual ring topology may be deployed.

A dual ring has all the features of a single ring with more fault tolerance. It comprises
infrastructure components connected together with multiple rings. Each device is
connected to two infrastructure components. Each infrastructure component is
connected to a separate ring. When a single link or infrastructure device fails, all
other devices can still communicate.
Dual ring topologies used in automation environments have additional features not
always found in typical data communications environments. For example, hot
standby links are used between rings. When a link fails, the standby becomes active
and prevents any interruption in network communications. Watchdog packets are
sent out to inactive connections and they create logs if the connection remains
inactive. The watchdog packets create log entries that are monitored by the network
administrator.

Advantages Disadvantages
Redundancy; the failure of multiple devices or Cost, compared to a single ring, since
cables does not cause the network to fail. the amount of equipment is doubled.
Separate power supplies can be used for each ring. The need to regularly monitor unused
Multiple interfaces within a device can connect the links so that they are known to be
device to different rings so that the flooding of one healthy in the event that they are
ring with collisions or broadcast traffic does not needed.
cause the system to fail.

50 31006929.00 10/2005
Planning and Layout

Mesh Topology A mesh topology is used in very large networks or network backbones where every
end device or infrastructure device has a connection to one or more components of
the network. Ideally, each device is directly connected to every other device in the
mesh.
Another mesh implementation is as a network backbone that connects separate star
structures. This combined topology provides fault tolerance to the backbone without
the high cost of a mesh topology throughout the entire network.

Star

Mesh

Mesh topologies are used less frequently because of cost and complexity.
Advantages Disadvantages
Fault tolerance; if a break occurs Complexity; difficult to manage and administer.
anywhere in the network cable segment, High cost; more cabling and interfaces are
traffic can be rerouted. needed to support the redundant connections.

31006929.00 10/2005 51
Planning and Layout

Developing Network Architecture for Industrial Ethernet Networks

Introduction Along with a basic understanding of network architecture (topologies) and Ethernet
for office environments, there are some further considerations when deploying
Ethernet in a plant environment. The various topologies and their application in an
automation plant layout are discussed, with suggestions for appropriate hardware.

Ethernet Bus An Ethernet bus can be deployed by interconnecting hubs and/or switches in line
Topology and considering each one of them as the connection for a device. A limited number
of hubs and an unlimited number of switches can be interconnected to achieve this
purpose.

1 1 1 1

2 2
2
2

1 Ethernet switches
2 Ethernet devices

52 31006929.00 10/2005
Planning and Layout

Ethernet Star In an Ethernet star, the intermediate device may be a hub or a switch. A star is the
Topology most commonly used topology in office networks and has been adopted in most
automation applications. For industrial Ethernet applications, the use of a full duplex
switch as the central device, rather than a hub, is strongly recommended.
2

1 2

1 Ethernet switches
2 Ethernet devices

Ethernet Daisy To develop an Ethernet daisy chain network, devices with dual Ethernet ports are
Chain Topology required. Schneider Electric is releasing industrial Ethernet devices with this type of
functionality (dual Ethernet ports for daisy chain connectivity) at the present time.

31006929.00 10/2005 53
Planning and Layout

Ethernet Ring Ethernet rings usually form the backbone for high-availability applications. Two
Topology paths are available to reach the same device. If ring topology is required, switches
that support either a proprietary ring topology or spanning tree protocol (either
spanning tree or rapid spanning tree) need to be used.
Spanning tree protocol (STP; IEEE 802.1D) or rapid spanning tree protocol (RSTP;
IEEE 802.1w) are protocols that avoid communication loops and find a new
communication path when the initial one is no longer available. The recovery time
(time to find a new path) is about 30 s with STP. With RSTP and proper network
design, recovery time could be as low as 100 ms.

54 31006929.00 10/2005
Planning and Layout

Ethernet Mesh An Ethernet mesh network offers more redundancy than an Ethernet ring
Topology architecture. In a ring, two paths are typically available to the same device. In a mesh
network, more than two paths are typically available.
To develop an Ethernet mesh topology, switches that support spanning tree or rapid
spanning tree protocol are required.

31006929.00 10/2005 55
Planning and Layout

Redundant Ring Topology

Summary A redundant ring topology is recommended for automation environments where


there is a critical need for a fault tolerant network. Unlike a dual ring topology where
there are two links on every device, a redundant ring uses logical management on
the switch to reroute traffic across a single link structure.

Self Healing When a link on the redundant ring fails, a standby link is activated within a fraction
Operation of second. Through the use of a redundancy manager, the switch monitors the ring
using watch-dog packets. If one link in the ring fails, the redundant connection
performs self healing by activating the redundant link to take over data packet
transmission. Once the broken link is resolved, the self healing link is re-activated.

4
5

6 2

3 7

1 Process control
2 Production line 1
3 Production line 2
4 Production line 3
5 Redundancy connection
6 Redundancy manager active on switch
7 Watch dog packets

56 31006929.00 10/2005
Planning and Layout

1
5

7 2

3 8

1 Process control
2 Production line 1
3 Production line 2
4 Production line 3
5 Network fault
6 Redundancy connection takes over data packet transmission
7 Redundancy manager active on switch
8 Data packet able to reach all nodes

Advantages Disadvantages
Less complex, requiring only a single physical connection. If two links fail simultaneously,
More cost effective; a single interface and network are used. connectivity could be lost to
critical devices.
Automatic self healing that detects faults and reroutes data
packets.

31006929.00 10/2005 57
Planning and Layout

LAN Technologies and Network Design

Summary Avoiding disruptions in data transfer is an issue of paramount importance to an


industrial network planner, perhaps even more of a priority than throughput (speed
of information transfer). Discussed below are issues of network design such as
congestion, collision management, and broadcasting that can influence the smooth,
fast transfer of information along the network. Suggestions are given for proper
network design that can minimize the potential for disruptions.
Whereas several technologies can be used to build an IP network, Ethernet has
emerged as the preferred technology for both office and industrial environments.

Ethernet Among the LAN technologies, Ethernet has become the most popular because it
Advantages and offers the benefits of speed, cost, and ease of installation. It can support virtually all
Standards popular network protocols and has gained wide acceptance in the computer
marketplace as an excellent networking technology for most network environments.
The IEEE defines rules for configuring an Ethernet network and specifying how
elements in an Ethernet network interact with one another in IEEE Standard 802.3.
Adherence to IEEE 802.3 enables your network equipment and network protocols
to communicate efficiently. Refer to the information on the OSI (see p. 127) model.

Fast Ethernet Ethernet networks that require higher transmission speeds may use the fast
and Gigabit Ethernet standard (IEEE 802.3u), which raises the Ethernet speed limit from 10 to
Ethernet 100 Mbps with only minimal changes to the cabling. The fast Ethernet 100Base-TX
has become the most popular standard because it is very compatible with the
existing Ethernet 10Base-T. Gigabit Ethernet (1000 Mbps) is a technology under
development (IEEE 802.3z) that may allow the next generation of networks to
support even higher data transfer speeds.

Ethernet Frames/ The network sends data in units called frames (also called data frames or packets).
Packets Each frame can carry between 46 and 1500 bytes of data. A frame includes protocol
information for proper routing.

58 31006929.00 10/2005
Planning and Layout

Ethernet and Because Ethernet allows multiple devices to exchange data simultaneously,
Collisions collisions can occur when two devices transmit data at the same time. When this
happens, both devices stop transmitting and use a random back-off algorithm to wait
a certain amount of time before attempting to transmit the data again.

End Device A

sent packet sent packet

Collision
End Device B

Collisions can be managed by careful network planning and design. The following
design and operation factors may affect the collision rate of an Ethernet network:
z the number of devices on the network; the more devices, the more likely collisions
become
z the length of the network; the greater the chance for collisions
z the packet length or MTU size; a larger packet length takes longer to transmit,
thus increasing the chance for a collision. The larger the frame size, the more
chance for a collision.

Switched Switches, when properly designed into the network structure, are the key to avoiding
Networks and network slowdowns due to collision or congestion. Intelligent switches create less
Collision network traffic by sending data only to the destination that requires it. They can also
Domains filter out bad packets, preventing them from being forwarded further. Switches also
divide a network into separate, shorter domains that each carry less traffic. Full-
duplex switches (see p. 62), which allow transmission of data in both directions, can
increase bandwidth and completely eliminate collisions on the segments where they
are used. Schneider Electric recommends the use of full-duplex switching in
automation networks.

31006929.00 10/2005 59
Planning and Layout

Network Performance on a shared network deteriorates when more devices or applications


Congestion that require more data are added. Increased collisions can be the result of too many
end devices or too much traffic on the network. For example, actual throughput on
a moderately loaded 10 Mb/s Ethernet network is approximately 35% of capacity,
which is about 2.5 Mb/s (after figuring for packet overhead, interpacket gaps, and
collisions). A moderately loaded fast Ethernet shares 25 Mb/s of real data in the
same situation. Collisions increase on both networks as more nodes and/or more
traffic are added to the shared collision domain. Again, good planning, in
segmenting the network and by using intelligent switches, aids in reducing
congestion and maintaining good performance.

Ethernet A broadcast is the transmission of the same message to multiple recipients on the
Broadcast network. Any device configured for network broadcast receives that message.
Domains Broadcasting can be very useful. However, if the domain created in the network
design is too large, a broadcast can create such a large amount of traffic that delays
result. Some types of broadcast data may cause more delays than others, but the
delays impact the performance of every device on the network. Limit the size of the
broadcast domain with a router or intelligent switch that controls the delay from
excessive broadcasts.
Using components such as routers to delineate broadcast domains can improve
overall performance on a network. Routers between multiple LANs form logical
broadcast domain boundaries. Since routers filter network traffic, a router can be
configured to forward only specific broadcasts to other domains. Using a router for
this process may add time, but increase the efficiency of transmission.

VLANs A virtual LAN groups devices that may be in different physical locations into a virtual
network, sharing resources, servers and other devices among a workgroup. Using
a VLAN to segment traffic can increase network performance by reducing the size
of collision domains and of traffic loads. It offers a flexible and less expensive way
to modify groups in an environment that could change. The grouping also adds
consistency to addressing and protocols, an advantage to the administrator, and
needs less local server resources. A VLAN adds security safeguards as well.
There are several ways of grouping devices into a VLAN. Port-based VLANS are
end-stations that are grouped by ports on a switch. If they are plugged into certain
end ports, they belong to the same group. VLAN ports can be configured using
intelligent switches that support VLAN configurations. Another type of VLAN
configuration is protocol VLAN (PVLAN), in which the switch automatically looks at
all ports and groups end-stations by protocol. End-stations can also be grouped by
IP network address.

60 31006929.00 10/2005
Planning and Layout

Once an IP address is assigned to an end-station, it is placed in a specific VLAN.

End-stations can also be grouped on the basis of their IP addresses. After the IP
address is assigned to an end-station, it is placed into a specific VLAN.

VLANs can be implemented on layer 3 switches (see p. 63) to create multiple


broadcast domains, similarly to routers. The switching engine can then route from
one VLAN to another, improving performance on the LAN.
Some limitations of VLANs include those on the number of broadcasts and Ethernet
addresses and constraints on ports

Wireless IP Wireless communication (IEEE 802.11a/b/g) allows mobile communications without


the expense of cable runs or fixed-location maintenance. It does not replace wired
networks; it does allow a single device to access the network from various locations.
Wireless technology for industrial environments must create the same reliability,
performance, and redundancy that exist today with wired networks.

31006929.00 10/2005 61
Planning and Layout

LAN Hardware

Summary An overview of the hardware used on a local area network is useful in planning a
robust network for your industrial application. The following discussion gives a brief
overview and some recommendations for the LAN hardware you should use to
construct a Transparent Ready industrial Ethernet application (see p. 80).

Hardware and Its The following table shows on which layer each hardware element falls, according to
Operation Layer the OSI model (see p. 127):
Layer Layer Number Hardware
Application 7 gateway (If the gateway also converts protocol)
Network 3 routers/gateways, layer 3 switches
Data link 2 switches
Physical 1 hubs

Hubs A hub is an active device with multiple ports that interconnect devices and extend
(Repeaters) the network length. In general, hubs are plug-and-play devices that require no
configuration. Hubs are transparent to other devices and are essentially repeaters
that extend network segments. They receive information through any of their ports
and pass along that information to all of their other ports. A limited number of hubs
can be cascaded to extend the length of the network.
Devices interconnected by hubs are in the same collision domain—they are in the
same network segment where information packets can collide. Thus, hub devices
decrease network efficiency.

Switches Switches are active devices used to interconnect devices and to extend network
length. Unlike hubs, switches receive information through any of their ports and
forward that information only to the port where the target device of the incoming
information is connected. An unlimited number of switches can be cascaded to
extend the length of the network.
Switches are transparent for the devices in the network. They offer many features to
manage traffic and to provide security (see p. 140).
Switches break up collision domains so that devices interconnected by switches are
in different collision domains.

62 31006929.00 10/2005
Planning and Layout

Types of There are two types of switching: cut-through and store-and-forward. Cut-through
Switches switching begins to forward a packet once it is received, which can cause network
disruption if the packet is bad. Store-and-forward switching waits for the entire
packet to arrive and checks the packet for corruption before forwarding it out the
correct port. This prevents corrupt packets from being forwarded across the entire
network. A switch also stops a corrupt packet at the first switch it reaches after it has
been corrupted. The time delay for the process is minimal, less than 1 ms on an
industrial network. Store-and-forward switches are recommended by Schneider
Electric for automation networks.

Transceivers Transceivers change the physical medium: in most of the cases that transition is
between copper and fiber optic.

Bridges A bridge has been used to connect two LAN segments with different protocols
(Ethernet, Token-ring) or to connect two LANs, using Ethernet addresses. However,
because bridges supply lower throughput performance, lower port density, higher
transport cost, and less flexibility, switches are recommended for use over bridges.

Routers An Ethernet router is also known as gateway or default gateway. Routers connect
(Gateways) two separate networks. They create or maintain a table of the available networks
and use this information to determine the best route for a given data packet from the
source network to the destination network.
Routers can be used to break up broadcast domains.

Layer 3 Routing A layer 3 switch is a router implemented in hardware. It functions the same as a
Switches router but at an increased speed.

31006929.00 10/2005 63
Planning and Layout

Other LAN Considerations

Summary Below are some additional considerations for planning a robust industrial application
network.

Full-Duplex vs. Schneider Electric recommends the use of full-duplex switches wherever possible.
Half-Duplex Full-duplex switches:
z give greater bandwidth (100 MB in both directions on certain networks)
z allow a device to send responses while receiving additional requests or other
traffic
z result in less delays and errors with a device

When to Use a Switches should always be used in the design of your new network. They offer more
Switch intelligence than hubs at an equal or lesser cost.
The industrial switches available today work reliably under extreme conditions such
as with electromagnetic interference, high operating temperatures, and heavy
mechanical loads. Protect industrial switches by using field-attachable connectors
up to IP67 (see p. 77) and redundant ring cabling.

Bandwidth 10 MB of bandwidth can be used for smaller end devices, but not for links to PLC/
SCADA or to main network links.
100 MB is adequate for most automation systems.
1 GB is useful for the main network link. This capacity is not required, but ensures
that more bandwidth is available if needed. 1 GB is necessary if other services share
the network with the automation system.

64 31006929.00 10/2005
Planning and Layout

WAN Technologies and Network Design

Summary Several LANs that reside in widely separate physical locations can be joined into a
Wide Area Network WAN. The WAN usually uses leased services for the
connection. These may include;
z point-to-point leased lines
z circuit switching
z packet switching
z virtual circuits
z dial-up
WAN technologies function at the lower three layers of the OSI model (see p. 127):
the physical layer, the data link layer, and the network layer.
When planning a Transparent Ready industrial Ethernet application, some factors
you should consider about your WAN include the size and locations of the proposed
network, the amount of traffic and the cost and speed of various commercial
transmission services.

Point-to-Point Point-to-point links furnish a single, pre-established WAN communication path from
Links (Leased your site through a service provider’s network to your remote network. The service
Lines) provider dedicates wiring and bandwidth to meet the needs of your enterprise. Cost
is dependent on how much bandwidth you require and the distance between
connection points.

Circuit Switching A router can initiate circuit-switched connections when they are needed, then
disconnect the circuit when the communication is complete. The cost depends on
the time that the circuit is used, making circuit switching a popular backup solution
for other WAN technologies.
ISDN is one example of this cost effective technology. When used as a backup,
routers can be configured to reroute traffic automatically if other WAN lines fail.
ISDN supports data transfer rates of 64 kb/s. There are two types of ISDN:
z BRI, a basic service, comprises two 64 kb channels and one D-channel for
transmitting control information
z PRI, for users with requirements for greater capacity, comprises 23 B-channels
and 1 D-channel (U.S.) or 30 B-channels and 1 D-channel (Europe).

31006929.00 10/2005 65
Planning and Layout

Packet Switching Packet switching involves sharing resources at a service provider. The service
provider allocates portions of a line or of virtual circuits for the use of your enterprise.
Packet switching breaks up the packets and labels them individually, sends them
sequentially over the network by the most expedient route, and reassembles them
at the destination. It is more efficient and cost-effective for the carrier, making the
cost to the user less expensive than dedicated services. The most common
examples of packet-switched WAN technologies are frame relay, ATM, and MPLS.
Frame relay (which is based on packet-switching technology) supports data
transfers rates of T-1 (1.544 Mb/s) and T-3 (45 Mb/s). Frame relay can provide a
cost-effective solution for industrial applications.

Router Plant A

T1
Router
Frame T1
Relay
Switch Frame
Relay
Switch
Frame Fast Packet
Router T1
Relay Network
Switch
Frame
Relay
Switch
Frame
T1
Relay
Switch Router

Router

T1

Plant B

66 31006929.00 10/2005
Planning and Layout

Virtual Circuits Virtual circuits are logical circuits created within a shared network. There aretwo
kinds:
z switched virtual circuits (SVCs), which are dynamically established on demand
and terminated when transmission is complete
z permanent virtual circuits (PVCs), a more expensive option for situations where
data transfer between devices is constant

Dial-up Services Dial-up services for a WAN can be an economical solution when your enterprise
does not generate a lot of transmission traffic. Dial-up is also frequently used as a
backup for other WAN technologies. Network managers can perform remote
troubleshooting on a modem connected over an inexpensive dial-up line to a router
if the main link is down.

31006929.00 10/2005 67
Planning and Layout

WAN Hardware

Summary In order to connect from your network to other networks, some devices are needed:
z routers
z WAN switches
z access servers
z modems
z CSU/DSUs
z ISDN terminal adapters

Routers A router is a logical switch that joins your network to the WAN and to connect from
the WAN to your other network location. There is a router at each end of the WAN.
Some routers may have the physical connection inside, but sometimes the physical
connection device is external.

WAN Switches Switches have layer 3 capabilities, which combine the advantages of switching and
routing in a single device.

Access Servers Access servers allow users to have dial-in and dial-out connections (see p. 148).

68 31006929.00 10/2005
Planning and Layout

Modems Modems convert analog and digital signals and support connections to the network
over voice-grade telephone lines. They can be built into other network components
or purchased separately.
Three device options may be used to plug into a router:
z modems
z CSU/DSUs
z ISDN terminal adapters
CSU/DSU hardware connects to a router to provide the connection to a digital
network such as a T1 line. This hardware may connect as an external component or
may be built into more advanced network components. Service providers often offer
CSU/DSUs; if not, they can help you to configure your CSU/DSU properly to work
with their line configuration.
An ISDN terminal adapter is modem used to connect ISDN basic rate interface (BRI)
connections to a router. These adapters may be separate devices or built into a
router.

WAN Topology The diagram below shows a WAN consisting of a main site connected to several
remote sites.
Remote Plant A
Dial-up
Connection
CSU/DSU

Remote Plant B
Modem

Modem
Access CSU/DSU
Server ISDN
Circuit
High-end Switched
Router Remote Plant C

Main Plant Modem Service Provider


Frame Relay Virtual
Circuit CSU/DSU
Circuits
Switched (PVCs)
ISDN
Dynamic backup configuration CSU/DSU
for critical plant

Modem
Remote Plant D

The main plant is connected to the remote plants C and D by a packet-switched


frame relay connection using virtual circuits (PVCs in this case). The main plant is
connected to remote plant A by ISDN lines. There is one critical site (Remote Plant
D) that is also connected with a circuit-switched ISDN connection acting as a backup
to the frame relay link. This IDSN connection is dynamically configured on the high-
end router to connect only if the frame relay connection fails. A dial-up access server
is also depicted (top left); it supports network management troubleshooting from
remote locations in case all WAN connectivity to the main site is lost. Other WAN-
specific hardware includes routers, modems, CSU/DSUs (at Remote Plants A,B, C
and D), and an ISDN terminal adapter (at Remote Plant D).

31006929.00 10/2005 69
Planning and Layout

2.3 Environmental Requirements

At a Glance

Overview A Transparent Ready industrial Ethernet network supports the connection of


industrial automation devices with Ethernet connectivity (PLCs, I/O, sensors,
actuators, etc.) and industrial Ethernet infrastructure devices (cables, connectors,
switches, hubs, etc.)
Schneider Electric proposes three environmental categories:
z office
z light industrial
z heavy industrial
This section describes the environmental requirements for an industrial Ethernet
network.
Industrial refers to extreme environmental conditions (mechanical, climatic and
ingress protection) to which the devices are exposed, and to noise immunity
variables.
An industrial Ethernet must have predictable performance and a higher level of user
friendliness under these extreme conditions.

What's in this This section contains the following topics:


Section?
Topic Page
Environmental Standards Summary 71
Mechanical Requirements 72
Climate Protection Requirements 74
Ingress Protection Requirement 76
Electromagnetic Emission and Immunity Requirements 79

70 31006929.00 10/2005
Planning and Layout

Environmental Standards Summary

Standards for The value range for a system’s environmental variables (for example, temperature
Environmental as a climate variable) is defined in industry standards set by UL, CE, IEC, CSA
Variables CENELEC, and others (see p. 72).
Even though many standards are international and globally accepted, efforts
continue among the major standards organizations to reconcile existing standards
and create new ones that agree with each other. Standards often differ from region
to region, application to application, and device to device. Schneider Electric
recommends that you take this into account when designing your Transparent
Ready network.

Industrial and There are two additional concerns that relate to industrial Ethernet standards.
Telecommuni- z Information Technology and Telecommunication groups such as TIA define
cations standards for industrial Ethernet in addition to the traditional industrial standards
Standards organizations.
z Unlike industrial automation standards, standards for industrial Ethernet
infrastructure devices (hubs, switches, routers, etc.), cables, and connectors not
yet are clearly defined. Many industrial Ethernet infrastructure devices have
adopted the standards in use for industrial automation devices (PLCs, I/O, etc.)
and present these standards as appropriate for Ethernet devices.

Standards This section attempts to bring together the recommendations for environmental
Compliance safety set forth by the emerging industrial Ethernet standards and the Information
Technology and Telecommunications standards. In addition to the recommen-
dations, it is important to note:
z When you design an industrial Ethernet installation, you must comply with the
regulations set forth by your regional standards organizations, both for the types
of devices you plan to use and the applications you plan to target. These
standards usually provide well-defined rules and guidelines for industrial
automation devices.
z For cables and connectors, emerging standards are being defined. Industrial
Ethernet organizations such as Modbus, IDA, and IAONA provide recommen-
dations for cables and connectors. Other topics in this section reference their
ongoing work in cable and connector standardization.

31006929.00 10/2005 71
Planning and Layout

Mechanical Requirements

Introduction Mechanical requirements apply to any mechanical, electrical, or electronic


component or assembly of components. Tests and ratings for mechanical
compliance with standards include the following:
z shock
z vibration
z tensile strength
z flexing
z crush
z impact

Shock The following table shows the recommended allowable degrees of shock for an
Requirements industrial Ethernet.
Environment Shock Limits Reference
Light Industrial 15 g/11 ms (3/axis IEC 60068-2-27 (Environmental testing.
Environment (Light Duty) in both directions Part 2: Tests. Test Era and guidance: Shock
EN 60068-2-27
Heavy Industrial 20 g/11 ms (3/axis IEC 60068-2-27 27 (Environmental testing.
Environment (Heavy Duty) in both directions Part 2: Tests. Test Era and guidance: Shock
EN 60068-2-27

Vibration Vibrations are defined as mechanical oscillations produced by movements of a


Requirements member or body from its rest position at regular or irregular time periods. Vibration
can result in equipment damage, loss of control in equipment, and reduced
efficiency in machine operation.
The following table shows the recommended allowable degrees of vibration for an
industrial Ethernet.
Environment Shock Limits Reference
Light Industrial 2 g @ 10 - 500 Hz IEC 60068-2-6 (Environmental testing. Part
Environment (Light Duty) 2: Tests. Test Fc: Vibration (sinusoidal)
EN 60068-2-6
Heavy Industrial 5 g @ 10 - 500 Hz IEC 60068-2-6 (Environmental testing. Part
Environment (Heavy Duty) 2: Tests. Test Fc Vibration (sinusoidal)
EN 60068-2-6

72 31006929.00 10/2005
Planning and Layout

Tensile Strength The following table shows the recommended degree of tensile strength acceptable
Requirements for industrial Ethernet cables.
Environment Tensile Strength Reference
Requirement
Light Industrial Environment (Light Duty) 75/100/200 N for 1 min IEC 60966-1
Heavy Industrial Environment (Heavy Duty 100/200 N for 1 min IEC 60966-1

Flexing The following table shows the recommended degrees of flexing allowable for
Requirements industrial Ethernet cables.
Environment Flexing Requirement
Light Industrial Environment (Light Duty) 5 N 1000 operations
+/-90 degrees
Heavy Industrial Environment (Heavy Duty 5 N 1000 operations
+/-90 degrees

Crush The following table shows the recommended allowable degrees of crush for an
Requirements industrial Ethernet cable.
Environment Crush Requirement
Light Industrial Environment (Light Duty) ISO/IEC is writing a draft standard document
Heavy Industrial Environment (Heavy Duty which has not yet been released.

31006929.00 10/2005 73
Planning and Layout

Climate Protection Requirements

Introduction Climate requirements for an industrial Ethernet include:


z ambient temperature during operation
z storage temperature
z humidity
z UV exposure

Temperature Temperature can affect industrial automation devices and Ethernet infrastructure
Requirements components such as cables, connectors and accessories in many different ways.
Extremes in temperature can affect performance. For example, extreme cold can
cause cable to become stiff, brittle and hard to work with, whereas elevated
temperature can soften or even melt the plastic used in a cable. Attenuation in the
standard off-the-shelf CAT 5E cable increases at a rate of 0.4% per degree Celsius,
above 20.
The ambient temperature is the temperature of the environment surrounding the
device. Measure the ambient temperature for a device at 30 to 40 cm from the
exterior surface of the device, in order to allow for the effect of heat and airflow in
the immediate vicinity.
The two tables that follow show the ambient temperature ranges for operation and
storage. If the ambient operating temperature is within the given range while the
device is in operation, that device is being used within its temperature specifications.

Operating
Temperature
Environment Operating Range Reference
Table
Light Industrial 0 to 60 degrees C IEC 60654-1
Heavy Industrial -20 to +85 degrees C IEC 60654-1

Storage
Temperature
Environment Operating Range
Table
Light Industrial -25 to +70 degrees C
Heavy Industrial -25 to +70 degrees C

74 31006929.00 10/2005
Planning and Layout

Other Humidity and UV exposure can also affect cable performance.


Environmental The tables below show the acceptable humidity range (by percentage) for operation
Factors and the acceptable number of hours of UV exposure.

Humidity Table
Environment Humidity
Light Industrial 5 to 95% noncondensing
Heavy Industrial 0.1 to 95% noncondensing

UV Exposure
Table
Environment UV Exposure
Light Industrial 3000 hr
Heavy Industrial 6000 hr

31006929.00 10/2005 75
Planning and Layout

Ingress Protection Requirement

Introduction Ingress is the ability of solid foreign bodies such as dust, water, moisture, and other
pollutants to enter an industrial equipment enclosure. Ingress protection refers to the
ability of the enclosure to keep these objects out. This requirement also includes
keeping people away from moving parts within the enclosure.
Two types of regulations define ingress protection variables:
z degree of pollution
z degree of protection

Degree of Pollution, such as moisture or dust, on the surface of devices can reduce their
Pollution insulation capability. The IEC 1010 standard specifies different types of pollution
environments. Heavily polluted environments require more insulation. Another
option is to create clean micro-environments for circuits and sensitive equipment
using enclosures, encapsulating methods, and hermetic sealing.
Four levels of pollution are defined by standard IEC 60664-1 (Insulation coordination
for equipment within low-voltage systems - Part 1: Principles, requirements and
tests):
Pollution Level Description
Grade 1 Nonpollution or only dry, nonconductive pollution. This type of pollution
has no electromagnetic or other influence.
Grade 2 Normally only nonconductive pollution. Temporary conductivity caused by
condensation may also occur.
Grade 3 Conductive pollution or dry nonconductive pollution that becomes
conductive due to condensation. Grade 3 pollution occurs in industrial
environments and construction environments that are considered harsh.
Grade 4 Pollution that generates persistent conductivity caused by conductive
dust, rain, or snow.

Pollution Table The following table shows the recommended levels of pollution allowed for industrial
for Industrial automation devices and Ethernet infrastructure components:
Ethernet
Environment Pollution Level Allowed Reference
Light Industrial (Light Duty) Grade 2 IEC 1010
IEC 60664-1
Heavy Industrial (Heavy Duty) Grade 3 IEC 1010
IEC 60664-1

76 31006929.00 10/2005
Planning and Layout

Degree of The degree of protection is defined by the IEC 60529 standard. This standard
Protection: IP describes an international classification system that uses the letters IP (for ingress
Rating Code protection) followed by two or three digits. This IP code defines the effectiveness of
the seal on electrical equipment enclosures against the intrusion of solid foreign
objects such as dust, tools, fingers, etc.
The first (leftmost) digit in the IP code indicates the degree to which persons are
protected against contact with moving parts (excluding smooth rotating shafts), as
well as the degree to which the equipment is protected against the entry of solid
foreign objects into its enclosure.
First Digit Degree of protection: Solid objects
0 no special protection.
1 Protection from a large human body part, such as a hand, and from solid objects
greater than 50 mm in diameter. It has no protection from deliberate access.
2 Protection against fingers or other objects not greater than 80 mm in length and
12 mm in diameter.
3 Protection from entry by tools, wires, and other solid objects with a diameter or
thickness greater than 1.0 mm.
4 Protection from entry by solid objects with a diameter or thickness greater than
1.0 mm.
5 Protection from the amount of dust that would interfere with the operation of the
equipment.
6 Dust-tight enclosure.

The second digit of the IP code indicates the degree of protection the equipment has
against the harmful intrusion of water and moisture in varying forms.
Second Digit Degree of protection: Moisture
0 No special protection.
1 Protection from dripping water.
2 Protection from vertically dripping water.
3 Protection from sprayed water.
4 Protection from splashed water.
5 Protection from water projected from a nozzle.
6 Protection against heavy seas or powerful jets of water.
7 Protection against immersion.
8 Protection against complete continuous submersion in water.The end user must
specify submersion depth and time. The requirement must be greater than IP67.

A third digit is sometimes used if there is only one class of protection, and an X is
used for one of the digits. For example, IPxI indicates that the equipment is
protected against dripping water only.

31006929.00 10/2005 77
Planning and Layout

Recommended
Degrees of
Environment Degree of Reference
Protection for
Protection
Industrial
Recommended
Ethernet
Light Industrial IP20 IEC 60529 (Degrees of protection provided by
(Light Duty) enclosures (IP code)
EN 60529
Heavy Industrial IP67 IEC 60529 (Degrees of protection provided by
enclosures (IP Code)
EN 60529

78 31006929.00 10/2005
Planning and Layout

Electromagnetic Emission and Immunity Requirements

Introduction There are two types of EMC requirement:


z emission: how much EMC a product or cable can emit.
z immunity: the degree of tolerance for EMC that a product or cable has
The standards that apply depend on the environment for which you are designing
your Transparent Ready system.
The two main EMC standards organizations are IEC and CENELEC. The two main
international standards for electromagnetic emission and immunity are:
z IEC 61000-6-2: 1999 Electromagnetic compatibility - Part 6-2: Generic standards
- Immunity for industrial environments
z IEC 61000-6-4: 1997 Electromagnetic compatibility - Part 6: Generic Standards -
Section 4: Emission standard for industrial environments

IEC 1000-4 The IEC 1000-4 standard establishes a common reference for evaluating the
Standard performance of industrial-process measurement and control instrumentation when
exposed to electric or electromagnetic interference. The standard describes
interference susceptibility tests that demonstrate the ability of equipment to function
correctly in working environments.
When determining the type of tests to run, base your choices on the types of
interference to which your equipment is exposed when installed. Take the following
factors into consideration:
z the method by which the electrical circuit and shields are tied to earth ground
z the quality of the shielding
z the environment
Sections IEC1000-4-2 through 1000-4-5 (see p. 501) are discussed in more detail
later in this manual.

31006929.00 10/2005 79
Planning and Layout

2.4 Selection of Industrial Ethernet Components

At a Glance

Overview This section provides information about the proper selection of industrial Ethernet
components. It discusses recommended connectors for office or light industrial use
and for heavy industrial use. Copper cables for an industrial Ethernet network and
the tooling needed to manufacture the cables are also discussed.

What's in this This section contains the following topics:


Section?
Topic Page
Ethernet Copper Cables 81
Fiber Optic Cabling 85
10/100BaseF Physical Layer Specification 89
Ethernet Connectors for Copper Networks 90
Fiber Optic Connectors 93
Recommended Infrastructure Devices for Industrial Ethernet 95

80 31006929.00 10/2005
Planning and Layout

Ethernet Copper Cables

Introduction Ethernet cables route transmitted signals from one device to another. When you
make cables, you need to know what types of devices you will be connecting. Most
Ethernet systems use routers, switches, and hubs to manage information flow.
These devices require a different type of cable than the type installed between two
end devices that communicate with each other directly.
Transparent Ready’s industrial Ethernet must use shielded CAT 5E twisted pair
cables, or better.

Twisted Pair Twisted pair cabling is a common form of wiring in which two conductors are wound
Cables around each other to cancel electromagnetic interference (crosstalk). The number
of twists per meter make up part of the specification; more twists produce less
crosstalk.The twisting of pairs, the quality of the conductive material, the type of
insulator, and the shielding largely determine the rate at which data can be
transmitted.

Classification LAN cables are generically called unshielded twisted pair (UTP) and are identified
and Cable with a category rating. The American National Standards Institute/Electronic
Categories Industries Association (ANSI/EIA) standard 568 is one of several standards that
specify categories of twisted pair cabling systems (wires, junctions, and connectors)
in terms of the data rates that they can sustain effectively.
The specifications describe the cable material and the types of connectors and
junction blocks needed to conform to a category.
Category Maximum Usual application
data rate
CAT 1 up to 1 Mb/ Traditional unshielded twisted-pair telephone cable that is suited for
s (1 MHz voice. It is not recommended for network use.
CAT 2 4 Mb/s Unshielded twisted-pair cable certified for data transmissions up to
4 Mbit/s. This cable has four twisted pairs. This cable should not be
used for high-speed networking.
CAT 3 16 Mb/s Rated for signals up to 16 MHz and supports 10 Mbit/s Ethernet,
4 Mbit/s token ring, and 100 VG-AnyLAN networks. The cable is
twisted for noise immunity. This cable is installed at many sites as
telephone cabling.
CAT 4 20 Mb/s Rated for signals up to 20 MHz and is certified to handle 16-Mbit/s
token ring networks. The cable has four pairs.

31006929.00 10/2005 81
Planning and Layout

Category Maximum Usual application


data rate
CAT 5 100 Mb/s Rated for signals up to 100 MHz at a maximum distance of 100 m.
1000 Mb/s Ethernet 100Base-TX, FDDI, and ATM at 155 Mbit/s use this
(4 pairs) cabling. It has low capacitance and exhibits low crosstalk due to the
high number of twists/ft. The predominant cable in new buildings
since the early 1990s. No longer supported; replaced by 5E.
CAT 5E up to (Enhanced CAT 5) has all the characteristics of CAT 5, but is
350 Mb/s manufactured with higher quality to minimize crosstalk. It has more
twists and is rated at frequencies up to 200 MHz, double the
transmission capability of CAT5. However, at these frequencies,
crosstalk can be a problem, and the cable does not have shielding
to reduce crosstalk. This cable is defined in TIA/EIA-568A-5
(Addendum 5).
CAT 6 up to Designed to support frequencies over 200 MHz using specially
400 MHz designed components that reduce delay distortion and other
problems. The TIA and ISO are cooperating on this category.
CAT 7 600- Designed to support frequencies up to 600 MHz. Each pair is
700 MHz individually shielded, and the entire cable is surrounded by a
shielded jacket. Connectors are expected to be specially designed
proprietary components. TIA and ISO are cooperating on this
category.

The two most widely installed categories are CAT 3 (for 10Base-T) and CAT 5 (for
100Base-T). While the two cables may look identical, CAT 3 is tested to a lower set
of specifications and can cause transmission errors if pushed to faster speeds. CAT
3 cabling is near-end crosstalk-certified for only a 16 MHz signal; CAT 5 cable must
pass a 100 MHz test. CAT 5E has recently replaced CAT 5 as the prevalent
standard.

Twisted Pair There are two main types of twisted pair: shielded twisted pair (STP) and unshielded
Cable Shielding twisted pair (UTP).
Usually STP and UTP cables have two pairs of cables (4 conductors). Screened
twisted pair (ScTP) is four-pair 100 Ω UTP, with a single foil or braided screen
surrounding all four pairs to minimize EMI radiation and susceptibility to outside
noise. ScTP is also called foil twisted pair (FTP), or screened UTP (sUTP). It can be
thought of as a shielded version of the CAT 3, 4, and 5 UTP cables. It may be used
in Ethernet applications in the same manner as the equivalent category of UTP
cabling.

Note: Transparent Ready’s industrial Ethernet must use shielded CAT 5E cables.

82 31006929.00 10/2005
Planning and Layout

Other Cable UTP and STP cables comes in two forms: solid and stranded. Solid refers to the fact
Characteristics that each internal conductor is made up of a single solid, wire. Stranded means that
each connection comprises multiple smaller wires. The only benefit of using
stranded cable (which is typically more expensive) is its smaller bend- radius (you
can squeeze it around tighter corners with lower loss). In most other respects, the
performance of the two cable types is the same.

Physical Layer The following table provides a summary of some of the various physical layer
Specification specifications defined for Ethernet.
Standard Data Rate Connector Medium Maximum Cable
Technology Segment Length
Half- Full-
Duplex Duplex
10Base-T 10 Mb/s (20 Mb/s in RJ45 two pairs of 100 Ω 100 m 100 m
optional full duplex) CAT 3 or better
UTP cable
100Base-TX 100 Mb/s ((200 Mb/ RJ45 two pairs of 100 Ω 100 m 100 m
s in optional full- CAT 5 UTP cable
duplex mode)
1000Base-T 1 Gb/s RJ45 four pairs of 100 Ω 100 m 100 m
CAT 5 or better
cable

100Base-TX supports transmission over up to 100 m of 100 Ω CAT 5 UTP cabling.


CAT 5 cabling (used with 100Base-T) is a higher grade wiring than CAT 3 (used with
10Base-T). It is rated for transmission at frequencies up to 100 MHz. CAT 3 cabling
supports transmission only up to 16 MHz. The 100Base-TX standard supports the
option of using 150 Ω STP cabling.

31006929.00 10/2005 83
Planning and Layout

Cable Color The EIA/TIA-568B standard defines the pinout for wires in RJ45 8-pin modular
Specifications connectors plugs and jacks. It also defines the color code for the 8 wires in the four
pairs. (The color coding specification is independent of the type of network.) Refer
to the EIA/TIA-568B standard for all pinout specifications.
The colors defined for the 4 pairs/8 cables are:
Pair 1 Blue/White with Blue stripe
Pair 2 Orange/White with Orange stripe
Pair 3 Green/White with Green stripe
Pair 4 Brown/White with Brown stripe

The pinout color code specified for the RJ45 connector is shown below.

PIN #
Orange striped
Orange
Green Stripped
Blue striped
Blue
Green
Brown Striped
Brown
Wire Pair
RJ45 Jack T568B - AT&T

Schneider recommends that the jacket of the cable be green RAL 6018.

Difference The difference between the color codes is that pair 2 (orange) and pair 3 (green) are
between EIA/TIA interchanged. The EIA/TIA 568B standard is the most widely used.
568A and EIA/TIA
568B
Note: There is no difference between the two wiring schemes, in connectivity or
performance when connected from one modular device to another (jack to Patch
panel, RJ-45 to RJ-45, etc.), so long as the two devices are wired for the same
scheme (A or B).
Also, refer to Installation (see p. 96) for more detailed information regarding the
installation of cabling.

84 31006929.00 10/2005
Planning and Layout

Fiber Optic Cabling

Summary Fiber optic cabling offers an alternative to copper wiring, replacing traditional UTP
and STP cable. Typically, fiber optic cable is used for backbone networks in
buildings and campuses. Improvements in fiber optic performance, connectivity, and
testing make it the best choice for LAN connections across long distances, as for
example between manufacturing plants or industrial facilities. Additional
advancements in transceiver products and lower cable costs add to its attraction as
a high-performance option.

Standards for The existing TIA/EIA fiber optics standards do not define an architecture like the TIA/
Fiber Optic Cable EIA 568-B and ISO/IEC 11801 standards. Instead, the fiber optic standards are
written to apply to all fiber installations regardless of their location or use. Today, the
same standards apply to all installations; there are no distinctions made for fiber
cable suspended under water or in the air, inside or outside a building, used for
backbone networks or installed in airplanes.

Fiber Optic Cable Fiber optic cable uses long, thin strands of ultra-pure glass (silica) or plastic that
Technical transmit light signals over long distances. The glass strands are very thin, about the
Description size of a human hair, and are arranged in bundles called optical cables.
A fiber optic cable consists of a center glass core surrounded by glass cladding and
a plastic jacket. Light photons are transmitted through the center core and reflected
back along the sides by the reflective material of the cladding. A thick plastic jacket
(strengthened with special fibers) surrounds and protects these two inner cores. In
certain types of cable, the fiber can have a metal core that gives the cable additional
strength.
Fiber optic cable has the ability to transmit signals over longer distances and at
faster speeds than copper cable. Also, because fiber optic cable transmits light, it
does not present the problems of electromagnetic interference associated with
copper cabling. It is ideal for harsh industrial environments and outside connections
between plants due to its high immunity to moisture, as well as to lighting.

31006929.00 10/2005 85
Planning and Layout

Parts of a Fiber Typically, a fiber optic cable consists of three parts:


Cable z core: thin glass center of the fiber that transmits light
z cladding: outer optical material that surrounds the core and reflects light back into
the core
z buffer jacket: outer plastic jacket or coating that protects the fiber from damage
and moisture

1 cladding
2 core
3 buffer coating

Fiber Cable A light signal can propagate through the core of a fiber along a single path (called
Types: single-mode fiber) or multiple paths (called multimode fiber).
Introduction

Single-mode fiber

Multimode fiber

86 31006929.00 10/2005
Planning and Layout

Fiber Cable Multimode fiber has a large core diameter (about 2.5 × 10 –3 in or 62.5 μm) and
Types: transmits infrared light (wavelength = 850 to 1300 nm) from light-emitting diodes
Multimode Cable (LEDs). Multimode fiber cable is most often used in LED-based LAN systems,
campus networks and short distance metropolitan networks.
There are two types of multimode cable:
z Step-index: has an abrupt change between core and cladding; is limited to about
50Mb/s.
z Graded-index: has a gradual change between core and cladding; is limited to
1Gb/s.

Note: The core specifications for step-index and graded-index multimode cables
are typically 50, 60.5 or 100 μm. The cladding diameter for step-index cable is
125 μm.
When cable is graded, the amount of refraction is reduced gradually outward from
the core. Because light travels faster when refraction is lower, light travelling
through the outer material travels faster than light at the center of the core.

The following illustration shows step-index multimode, graded-index multimode and


single-mode cable:

High-order mode Dispersion

Step-index
Multimode

Low-order mode
Dispersion

Graded-index
Multimode

Single-mode

31006929.00 10/2005 87
Planning and Layout

Fiber Cable Single-mode fiber has a small core diameter (about 3.5 × 10 – 4 in or 9 μm) and
Types: Single transmits infrared laser light (wavelength = 1300 to 1550 nm). it provides only one
Mode Cable optical mode that forces light along a linear path through the cable end and allows
significantly more bandwidth than multimode. Single-mode fiber cable is often used
in laser-based long-distance, interoffice LAN applications, cross-country networks,
and international submarine links. SIngle-mode cables used for long-distance
networks can include 100 to 800 fibers/cable.

Advantages of The advantages of single-mode fiber are a higher data capacity, low attenuation,
Single vs. and low fiber cost. It is the most expensive cable and is harder to handle, but has
Multimode the highest bandwidth and distance ratings. The advantages of multimode fiber is a
lower connection and electronics cost that can lead to lower installation costs.

Advantages of Fiber optic cable has several advantages compared to copper wire cable. Fiber optic
Fiber Optic vs. cable is selected for use in backbones and other areas of LAN and Ethernet
Copper Cable networks.
The advantages are:
z Lower cost: Optical cable is less expensive to make than copper wire of an
equivalent length.
z Higher information capacity: There are more optical fibers bundled in a cable,
which means more information can flow over an optical cable than a copper cable
of similar diameter.
z Less signal degradation: Optical fiber has less signal loss over equivalent
distances than copper wire.
z Thinner, more flexible and light weight: Optical fiber can be drawn thinner than
copper wire, making it lighter, more flexible, and easier to position through small
spaces.
z Low power: Optical fiber signals degrade less and therefore require lower-power
transmitters to boost signals.
z No disturbance or other risks: Because no electricity passes through optical
fibers, there is no electromagnetic interference and no fire or earthing hazard.

88 31006929.00 10/2005
Planning and Layout

10/100BaseF Physical Layer Specification

Introduction 10/100BaseF refers to specific physical layer specifications for fiber optic cable
carrying Ethernet signals.

10Base-FL Cable The traditional Ethernet (10Mb/s) includes specifications for the 10Base-FL physical
Specification layer. 10Base-FL supports fiber optic cable backbones of up to 4 km. The TIA/EIA
Commercial Building Wiring standard approves 10Base-FL for cross-connections
between campus buildings. The 10Base-FL has a transmission rate of 10Mb/s
(20Mb/s in optional full-duplex mode) and the maximum segment length is
2000 mts. The typical cable is multi-mode fiber, 62.5/125 (62.5 μm fiber core with
125 μm outer cladding), 850 nm light wavelength.

100Base-FX The 100Base-FX physical layer specification is approved by the IEEE 802.3u
Cable standard for Fast Ethernet (100 Mb/s) over fiber optic cable. The 100Base-FL has a
Specification transmission rate of 100 ms/s (200 Mb/s in optional full-duplex mode) and the
maximum segment length is 2000 mts (full-duplex). The typical cable is multimode
(62.5 μm fiber core with 125 μm outer cladding), 1300 nm wavelength.

Schneider For Transparent Ready industrial Ethernet applications, Schneider recommends the
Optical Fiber use of 62.5/125 type fiber, using the minimal amount and maximal quality of fiber.
Recommen- Schneider supports communications on wavelengths from 850 nm (for 10Base-FL)
dations to 1300 nm (for 100Base-FX). The cable may contain other fibers or electrical
conductors. The protection specifications for the cable must be compatible with your
installation conditions.
Environment Physical Layer Recommended Wave Maximum Segment
Fiber Length Length
Light and Heavy 10Base-FL 62.5/125 850 nm 2000 mts
Industrial (multimode)
Environment 100Base-FX 62.5/125 1300 nm 200 mts (full-duplex
(multimode)

31006929.00 10/2005 89
Planning and Layout

Ethernet Connectors for Copper Networks

Summary After a thorough analysis of market trends, industry proposals, and on-going
standardization work, and in the absence of international standards for copper
cabling in industrial Ethernet networks, Schneider Electric has defined the types of
connectors to use in Transparent Ready industrial Ethernet products, as of this
writing.
Schneider Electric recommends the RJ45 connector for use in office and light
industrial environments (see p. 70) and the M12 4 pole with D-coding circular
connector for use in heavy industrial environments.

Recommended The following table lists specifications for the industrial Ethernet copper connectors
Ethernet Copper recommended by Schneider Electric.
Connectors
Environment Connectors General Reference
Specifications
Light Industrial RJ45 IEC 60603-7 and TIA/
(Light Duty) Pin assignment: ISO/ EIA 568B
IEC 8802-3
Pinout Color Coding:
TIA/EIA 568B
Shielded
Heavy Industrial M12 4 pole with D- IEC 61076-2-101
(Heavy Duty) coding Shielded

RJ45 Connector As defined in the Ethernet IEEE 802.3 and the ISO/IEC 8802-3 standards, the
connector specified for the Ethernet 10Base-T and 100Base-TX physical layers is
the RJ45 (copper installations). RJ (registered jack) is defined in the United States
Code of Federal Regulations.
The RJ45 is a connector used to terminate twisted pair cables. A typical RJ45
connector is shown here:

90 31006929.00 10/2005
Planning and Layout

Shielded (or Schneider Electric recommends shielded RJ45 connectors in office and light
Screened) RJ45 industrial environments, and shielded CAT 5E cables for 10Base-T and 100Base-
Connector TX industrial Ethernet networks. If you have devices that use shielded jack
connectors and are externally grounded, the cable shield is grounded at both ends
of the cable.

RJ45 Pins and The RJ45 connector has 8 (eight) pins or electrical connections that are numbered
Ethernet Signals 1-8 from left to right.

pin 1
pin 8

For Ethernet 10Base-T and 100Base-TX, the RJ45 pins are used as follows:
RJ45 pin Ethernet Signal
1 Transmit + (TX+)
2 Transmit - (TX-)
3 Receive + (RX+)
4 Unused
5 Unused
6 Receive - (RX-)
7 Unused
8 Unused

When making Ethernet cables, if you plan to only use 2 pairs (4 cables), you connect
all of them. If you use 4 pairs (4 cables), Schneider recommends that you connect
them as suggested in the EIA/TIA 568B specification, even though pins 4, 5, 7, and
8 do not have signals assigned. For the recommended color coding based on the
TIA/EIA 568B standard, see p. 84.

Note: When you use CAT 5/5e cabling, pins 4, 5, 6, and 8 are not required for
10Base-T or 100Base-TX physical layers.

31006929.00 10/2005 91
Planning and Layout

M12 Circular The usage of M12 circular Cocnnectors is not yet a defined standard, although the
Connectors M12 circular connector is used at the field bus level in many heavy-duty industrial
applications. Schneider Electric recommends the M12-4 (4 poles) with D-coding for
Transparent Ready Industrial Ethernet networks in heavy industrial environments.

M12 Circular
Connector Pins
and Ethernet
Signals

male connector female connector

For Ethernet 10Base-T and 100Base-TX, the M12 circular connector pins have the
following designated Ethernet signals:
M12 Ethernet Signal
1 Transmit + (TD+)
2 Receive + (RD+)
3 Transmit - (TD-)
4 Receive - (RD-)

92 31006929.00 10/2005
Planning and Layout

Fiber Optic Connectors

Development of Several types of fiber connectors have been developed. The fiber connector (FC)
Fiber was the first connector to use a 2.5 mm ceramic ferrule. The ferrule is the connector
Connectors cap that surrounds the end of an optic sheath and creates the connection. The
straight terminus (ST) connector was introduced slightly later. It had the same
ceramic ferrule, but was easier to insert because of its lock. The subscriber
connector (SC) appeared next and has gained popularity. The mass termination
(MT) and the MT/RJ connectors are the most recent developments in the connector
industry.

SC Connectors The SC connector is becoming the most popular connector in use with fiber cable.
It has a square front and is easier to install in confined spaces.

ST Connectors The ST connector was introduced by AT&T. It is the most frequently found connector
in installed fiber optic networks, since it has been the most popular connector to use
in recent years. It has a barrel shape that looks similar to a BNC connector with a
bayonet-like lock that makes it fast and easy to insert.

LC Connectors The LC connector resembles a small SC connector. It was developed by Lucent for
use in telecommunications environments. It has been standardized in the EIA/TIA-
604-10 standard.

MT/RJ Small form factor (SFF) connectors like the MT connector are a more recent addition
Connectors to the class of optical connectors. The MT (Mass Termination) connector refers to
the 12 or 24 fibers that it connects. The name of its duplex cousin the MT/RJ refers
to the RJ-45 style of copper connector it resembles.

31006929.00 10/2005 93
Planning and Layout

Fiber Optic Schneider Electric recommends the use of the following connectors for the
Connectors Transparent Ready Industrial Ethernet:
Environment Physical Recommended Appearance
Layer Connector
Light industrial 10Base-FL ST
and heavy
industrial
environment

100Base-FX SC

100Base-FX MT-RJ

94 31006929.00 10/2005
Planning and Layout

Recommended Infrastructure Devices for Industrial Ethernet

General Use switches as much as possible to eliminate


collisions. increase performance and simplify
network design. Avoid using hubs whenever
possible.
Understand network traffic and segment
network properly.
Follow environmental recommendations
provided in this manual.
When high bandwidth availability is Use full-duplex switches (10Base-T/100Base-
required TX).
Understand network traffic and segment
network properly.
For applications where minimum Use self-healing ring or redundant self-healing
application downtime is required ring.
For networks that require basic level Use unmanaged switches with alarm relay.
diagnostics
(e.g. no link or failure of one P/S)
For networks that require high-level Use managed switches.
services and traffic administration
For applications that require network Use managed switches.
discovery and monitoring
For applications that require Use fiber optic products.
interconnecting devices separated by long Multimode fiber: Up to 2 km between nodes.
distances (> 100 mts) Monomode fiber: Up to 15 km between nodes.
Note: Depending on the fiber and the optical
budget, could reach 4 km on multimode and 30
km on monomode.
For networks that require immunity to Use products with fiber optic ports.
electromagnetic noise
For applications that require physical Use transceivers or use switches with a
medium change combination of copper and fiber optic ports.
For applications that require external (IP67) Use IP67 switches and cables.
mounting of the switch

31006929.00 10/2005 95
Planning and Layout

2.5 Installation

At a Glance

Overview This section describes measures you can take to prevent electromagnetic
interference (EMI) from seriously impeding your network or from causing intermittent
problems that are difficult to diagnose. Earthing (also referred to as grounding), the
equipotential bonding of equipment, cabinets, buildings, and the planning of cable
runs within the site are discussed in detail, with a focus on measures to be taken for
an industrial automation communications system.

What's in this This section contains the following topics:


Section?
Topic Page
EMC Installation Rules for Ethernet Networks 97
Equipotential Bonding 98
Equipotentially Bonding Your Building 99
Local Equipotential Bonding of Equipment and Machines 101
EMC-compatible Ethernet Wiring and Cable Runs 102
Ethernet Copper Cable Types 108
Ethernet Copper Cable Tools 111
How to Make an Ethernet Cable 112
Cabling Administration 114
Cabling Documentation 115

96 31006929.00 10/2005
Planning and Layout

EMC Installation Rules for Ethernet Networks

Introduction When properly incorporated into the planning of your network, the following methods
can help you avoid electromagnetic disturbances and create an EMC-compliant
environment.
Protecting the Ethernet network from electromagnetic interference (EMI) is an issue
that involves your complete installation. Although it is important to be concerned
about EMI immunity throughout your entire system, this section describes only
methods that apply to your Ethernet network. By equipotentially bonding, earthing,
proper wiring, and shielding your site and equipment, you can significantly reduce a
large percentage of EMI issues.
For more information on EMC, see p. 70.
For more information on EMI, see p. 506.

Installation The following list describes key measures you need to consider in your installation
Measures to in order to reduce EMI in an industrial Ethernet network:
Combat EMI in z earthing and equipotential bonding
Ethernet z EMC-compatible wiring and cable runs
Networks z balancing circuits
z cable selection
z shielding
z filtering
z placement of devices
z placement of wires
z transposition of outgoing and return lines
z electrical isolation

Earthing and Earthing is the method used to carry an electric charge to the ground (earth) along
Equipotential a conductive path. Examples of conductors include: a wire, metal conduit, or metal
Bonding Defined cabinet.
Equipotential bonding is the process of connecting conductive parts in order to
create a low-resistance electrical contact for direct current and lower-frequency
alternating currents. This interconnection spreads the flow of interference over
multiple paths so that it avoids any one junction.
In most cases an equipotential bonding system is earthed. The flow of interference
terminates in the earth. The flow of an electric charge is dispersed into the ground
and away from sensitive equipment and communication lines. The EN 50310
standard requires buildings with information systems to be fitted with a common
bonding network that consists of multiple conductive elements.

31006929.00 10/2005 97
Planning and Layout

Equipotential Bonding

Introduction Equipotential bonding creates an interconnection of conductive parts that disperses


the flow of EMI disturbances over multiple paths, connecting to the earth through an
earthing system. The design of an earthing system is determined by local conditions
and requirements. The layout of your building and of all the machinery within it
determines how simple or complex your earthing system needs to be.
The topics that follow describe at a high level what you can do to create equipotential
bonding and earthing systems at your site so that it can be protected against EMI
disturbance. For more details, see p. 506.

Earthing System The typical earthing system consists of three components:


Components z actual earth: which conducts current into the ground through an earth electrode,
a pipe, or a metal conductor
z earthing main conductor: a conductive system to which the earth and all
necessary parts of the installation are connected
z earthing conductors: which connect parts of the installation to the earthing main
conductor

98 31006929.00 10/2005
Planning and Layout

Equipotentially Bonding Your Building

Introduction The EN 50310 standard requires buildings with telecommunications systems to be


fitted with a common bonding network (CBN) that consists of multiple elements. This
requires the creation of an earthing main conductor and the attachment of all metal
structures and objects in the building to that main conductor. The CBN is then
connected to an exterior earthing electrode system that terminates in the earth.

Terminology Earth plane: A mesh grid made of welded reinforcing rods cast into the concrete slab
or placed in a false floor with the grid made of copper conductors.
An earthing ring bus is the most effective form of earthing main conductor. It is
typically installed in the basement or ground floor of buildings that contain
telecommunications systems. The metal sheaths of cables, conduits, cabinets, and
heating and water pipes are connected to the earthing main conductor using the
shortest path.
The diagram below shows an earthing system with an earth plane and earthing ring
bus:

3 to 5 m

31006929.00 10/2005 99
Planning and Layout

Procedure The following procedure describes how to create an earthing system for a building.
The installation of an earthing system is the first step to creating an EMC
environment (see p. 506).
Step Action
1 Create an earth plane and a ring bus.
2 Interconnect all metal structures in the building.

Metal structures include: metal structural elements, welded concrete


reinforcements, metal pipes and ducts, cable troughs, power conduits, conveyors,
metal doors and window frames, and gratings. The interconnection forms a common
bonding network that is the principal means for effecting earthing inside the building.

Note: Design and create a fine-meshed earth plane in areas where sensitive
hardware, such as data processing and measuring equipment, will be stored or
used.

100 31006929.00 10/2005


Planning and Layout

Local Equipotential Bonding of Equipment and Machines

Introduction After creating an equipotential bond for the building (see p. 99), you can create local
low frequency (LF) and high frequency (HF) equipotential bonding of equipment and
machines.
Step Action Considerations
1 Systematically interconnect all the metal Everything from cabinets and the earth
structures of single equipment items to plane plate beneath them to cable
create local earthing systems (earth troughs, pipes, and metal frames of the
frames). machines must be interconnected.
2 If necessary, add earth conductors for Make sure that the used and unused
interconnections between exposed ends of any cable conductor are
conductive parts. connected to the earthing system.
3 Connect the local frame earthing system -
to the earthing system of the site by
providing the maximum number of
distributed connections.

Connecting Make sure that there is an earth plane plate at the bottom of every cabinet.
Cabinets to a All the exposed metal parts of components and units fitted in a cabinet must be
Local Earthing bolted directly onto the earth plane plate to provide high-quality, durable metal-to-
System metal contact.

Note: Because of its excessive length, the main green/yellow earth conductor
cannot generally provide HF quality earthing.

31006929.00 10/2005 101


Planning and Layout

EMC-compatible Ethernet Wiring and Cable Runs

Classification of In an industrial environment, signals are classified into four categories according to
Signals their EMC performance. This classification is required to apply the cabling rules.
EMC Performance
Class Sensitivity Interference Circuit or Device Example
- PLCs Transformers in the -
cabinet
PCBs Contactors
Regulators circuit-breakers
Cables connected to Fuses
inputs and outputs
Switching power supplies
Class 1 or 2 cables Frequency converters
carrying analog signals
Variable speed drives
DC power supplies
Microprocessor clocks
Cables connected to
such components
Power supply lines
Power cables
1: Sensitive Signal is very sensitive - Low-level circuits with analog outputs)
Sensors
Measuring circuits (probes, sensors, etc.)
2: Sightly Signal is sensitive. Can - Control circuits connected to resistive loads
Sensitive disturb class 1 cables
Low-level digital circuits)
Low-level circuits with all-or-nothing outputs
Low-level d.c. power supplies
3: Slightly - Signal disturbs class 1 Control circuits with inductive loads and
Interfering and 2 cables suitable protection
Clean AC power supplies
Main power supplies connected to power
devices
4: Interfering - Signal disturbs other Welding machines
class signals
Power circuits
Electronic speed controllers
Switching power supplies

Data transmission, such as that on an Ethernet network, is a class 2 signal.

102 31006929.00 10/2005


Planning and Layout

General Wiring z Equipotentially bond the site and the cabinets.


Recommen- z Position possible sources of interference away from sensitive equipment.
dations z Do not combine Ethernet signals with class 3 or 4 signals in the same cable or
conductor bundle.
z Always try to maximize the distance between the Ethernet cable and cables
carrying signals of different classes, especially interfering signals (3-4). The
longer the cable run, the greater the clearance required between cables.
z To take advantage of the HF protection effects, flatten any connection against
equipotentially exposed conducting structures. For internal connections to
cabinets and machines, systematically flatten the cables against the metal
supports.
z Make sure Ethernet cables cross any cables carrying interfering signals (3-4) at
a right angle as shown in the diagram below:

31006929.00 10/2005 103


Planning and Layout

z If you need to collocate cables carrying signals of different classes in a single


cable trough, use shielded cables as shown in the diagram below:

1 2

1 unshielded cables
2 shielded cables
z Establish continuity of the earth plane between two cabinets, machines, or pieces
of equipment. Place all conductors against the earth plane end to end (panel at
bottom of cabinet, exposed conductive parts of metal enclosures, equipotential
structures of machine or building, accompanying conductors, cable troughs,
etc.).
z Follow the shielding rules described in this chapter.

Cable Run z Use metal cable troughs. Correctly connected, they provide very effective cable
Recommen- shielding.
dations z The shielding, protective, or screening effects of a metal cable trough depend on
the position of the cable. Install Ethernet cables in the corners of a cable duct as
shown in the diagram below:

104 31006929.00 10/2005


Planning and Layout

2
3

1 open cable trough


2 area exposed to EMI disturbances
3 corner angle
4 area specially protected against EMI disturbances
z If for special reasons Ethernet cable must be installed in the same trough as type
3 and 4 cables, leave the cable trough open. This type of installation is not
recommended.
z Whenever possible, use two metal ducts, one for interfering signals (power,
relays and varistors) and the other for signal cables (sensors, data, telecoms.).
These two ducts can be in contact if they are shorter than 30 m. From 30 to
100 m, space them 10 cm apart, either side-by-side or one above the other.
z At all times, overlap and bolt the ends of the metal cable troughs together. If this
is not possible, install a wide braided strap joining the two troughs under every
table as shown in the diagram below:

31006929.00 10/2005 105


Planning and Layout

Recommen- z Follow good wiring guidelines.


dations for Cable z Follow the cable run recommendations in this chapter.
Routing inside a z Always try to separate and segregate interfering and sensitive components and
Cabinet cables in different cabinets.
z In small cabinets, partitioning signal types by sheet metal panels bolted to the
chassis may be sufficient. In large cabinets, allocate one cabinet for every class
of components. When possible, lay the cables in metal ducts.

1 2

3 4 5 6

1 power
2 low level
3 to power components
4 mains
5 actuators
6 sensors

106 31006929.00 10/2005


Planning and Layout

Cable Routing z Use metal for all ducts that are longer than 3 m.
outside and z Bolt the ends of metal cable troughs and conduits onto metal cabinets to make
between satisfactory connections, as shown in the diagram below:
Cabinets

Cable Routing There is usually a lack of equipotential bonding between two buildings. The two
Outside and ground connections (one at each building) should be connected. All cable runs
Between between two buildings must be doubled up with a large section of equipotential line
Buildings (35 mm 2). Use optical fiber cable for data links between buildings in any
Transparent Ready application. A fiber link eliminates loop problems between
buildings.

31006929.00 10/2005 107


Planning and Layout

Ethernet Copper Cable Types

Ethernet Cables You can make two types of Ethernet cable: straight cable or crossover cable.

Straight Cable Ethernet infrastructure devices, such as switches and hubs, are always located
between two end devices. Typically these infrastructure devices cross the signal,
and therefore the cable between the end device and the hub or switch must be a
straight cable.

Straight Cable The EIA/TIA 568B and IEEE 802.3u standards define the pinout for an Ethernet
Pinout straight cable as shown in the diagram below:

1 2 1

3 3

1 end device
2 intermediary device
3 straight cable

108 31006929.00 10/2005


Planning and Layout

The RJ45 pinout connection from an end device to an intermediary device uses
straight cables that follow the color-code and signal specifications (see p. 84).

Signal Signal
(in jack end device) RJ45 Pin RJ45 Pin (in jack intermediary device)
TX+ RX+

TX- RX-

RX+ TX+

Unused Unused

Unused Unused

RX- TX-

Unused Unused

Unused Unused

Straight Cable Intermediate Device


End Device

1 orange striped
2 orange
3 green striped
4 blue
5 blue striped
6 green
7 brown striped
8 brown

Crossover Cable When two end devices on an Ethernet network communicate with each other over
a direct connection, the transmit signals of one device must connect with the receive
signals of the other and vice versa.
Use a crossover cable whenever you make a direct connection between two end
devices. A direct connection has no intermediary device between the two end
devices you are connecting.

1 1

1 end device
2 crossover cable

31006929.00 10/2005 109


Planning and Layout

Crossover Cable The EIA/TIA 568B standard defines the pinout for an Ethernet crossover cable. A
Pinout direct pinout connection between two end devices uses a crossover cable that
follows the specifications shown in the diagram below.

Signal Signal
(in jack end device) RJ45 Pin RJ45 Pin (in jack end device)
TX+ RX+

TX- RX-

RX+ TX+

Unused Unused

Unused Unused

RX- TX-

Unused Unused
Unused Unused

End Device Crossover Cable End Device

1 orange striped
2 orange
3 green striped
4 blue
5 blue striped
6 green
7 brown striped
8 brown

MDI/MDI-X Today most of the infrastructure devices offered on the market (hubs, switches,
routers, etc.) support the medium independent interface (MDI/MDI-X) functionality
in their Ethernet ports. This functionality allows the auto-switching of transmit and
receive wire pairs. To connect this type of infrastructure device, use either straight
or crossover cable; the device senses and accommodates the TX/RX pairs.

110 31006929.00 10/2005


Planning and Layout

Ethernet Copper Cable Tools

Introduction You need the following three tools to make an Ethernet copper cable:
z cable stripper
z cable cutter
z cable crimper
For instructions on how to use these tools when making cables, see p. 112.

Cable Stripper A cable stripping tool strips away the outer protective wrapping from the cable and
uncovers the core conductive material.

Cable Cutter A cable cutting tool cleanly cuts through the diameter of a length of cable, separating
it into two lengths. When selecting a cable cutter, choose a tool that is appropriately
sized for the diameter of the cable you want to cut.

Cable Crimper A crimper tool is used to secure the jack to the cable end by the use of pressure.

31006929.00 10/2005 111


Planning and Layout

How to Make an Ethernet Cable

Before You Start Make sure you have the following equipment available:
z RJ45 connectors (two for each cable plus extras)
z Ethernet cable
For 10Base-T, STP Ethernet cable CAT 3 or CAT 5, 5e, or 6 are recommended;
100 m or less
z For 100Base-TX, STP Ethernet cable CAT 5, 5e, or 6 are recommended; 100 m
or less
z basic cable-making tools (see p. 111)

112 31006929.00 10/2005


Planning and Layout

Procedure
Step Action Comment
1 With the stripper tool, strip 2 inches of the -
plastic jacket at one end of the cable.
2 Hold the base of the plastic jacket with one Keep colored pairs of wire together and in
hand and spread the wires apart with the the same order: brown, blue, green, and
other hand. Do not allow the wires to orange.
become untwisted inside the jacket.
3 Hold the wires tightly at the point where Make sure your cutters are aligned
they enter the plastic jacket. Line up your straight across the wires to ensure that all
cutter across the separated wires about the wires will be cut at the same 0.5 in
0.5 in from the edge of the plastic jacket. length.
4 Make a clean cut across the four wire Maintain a firm grasp on the jacket as you
pairs. do this. Do not allow the wires to untwist
inside the jacket as you cut.
5 Grasp the RJ45 jack firmly between two If the wires resist your efforts, keep
fingers and slide the wires into the jack. Be working them forward until you have
sure to follow the pinout color code them fitted into the jack where you want
specifications for the type of cable you are them. Do not release the wires while you
making. are fitting them.
6 Work the wires forward until they almost The plastic jacket should be positioned
touch the front of the jack. about 3/8 in inside the jack.
7 Insert the jack into the crimper and firmly If you do not get a good crimp the first
squeeze the crimper until the jack is time, reposition the crimper and try again.
securely crimped to the cable end.
8 Inspect the jack to make sure you have a Look at the front end of the jack to make
secure crimp. sure the copper connections are not
pressing down into the wires.
Look at the back of the jack to make sure
the plastic jacket extends into the jack
about 3/8 in.
Note: It is very important to make sure no
wires extend out of the back of the jack.

Making an Making an Ethernet fiber cable requires special procedures and tools. Consult a
Ethernet Fiber trained and certified technician for assistance.
Cable

31006929.00 10/2005 113


Planning and Layout

Cabling Administration

Introduction The EN 50174-1 standard describes the specification for cabling administration.
Cabling administration includes the management of:
z identification codes and methods
z cable and component labeling
z label application and location
z durability and quality of labels
z inspection and label updating
Currently, there is no international standard for these areas of cabling.

Standard EN For general guidelines about cable labeling and identifiers, refer to chapter 7.2 and
50174-1 and 7.5 of the EN 50174-1:2000 standard. A summary of those guidelines is included
Identifiers here.
The components of a cabling system are typically maintained by more than one
person and, therefore, require the use of identifiers to indicate relevant information
about the component. For example, you should place an identifier, in the form of a
label or code, indicating where a shielded twisted pair CAT 5E cable is installed in
the horizontal cabling system in a building. Chapter 7.5 of the EN 50174 standard
specifies which cabling components require such identification.

Labeling Cables Labeling cables and components is a required practice in installation. Either attach
and Components labels to the component or affix them as part of the component itself. In some cases,
certain components are labeled more than once. A general rule is to label a cable at
both ends as the minimum requirement.
The following requirements are specified in the EN 50174-1 standard:
z Labels need to be:
z easy to access.
z easy to read.
z easy to change or modify (if required).
z Labels need to be robust and their markings readable for the lifetime of the
cabling.
z Labels should not be affected by dampness or become smudged when handled.
z Labels intended for outdoor use or use in harsh environments need to be
designed to withstand the rigorous conditions of such environments.
z When you make changes to a cabling system, for example at a patch panel,
inspect the labels to determine if the information is correct or requires updating.

114 31006929.00 10/2005


Planning and Layout

Cabling Documentation

Introduction The ISO/IEC 14763-1 and EN 50174-1 standards describe the specifications for
documentation of cabling. This section summarizes the guidelines and requirements
specified in standard EN 50174-1:2000, chapter 6.1 and provides recommendations
for managing documentation.

Creating When installing cabling, you need to create documentation both during and following
Documentation the installation. This documentation needs to provide sufficient detail about the
installation specifications. The recommendations presented here can help you
determine the level of documentation that is appropriate for your installation.

Note: You should maintain the same level of documentation detail throughout the
design and installation phases.

Recommen- Commercial documentation should include any technical and contractual


dation 1: information that relates to end-user requirements and the installation undertaken.
Commercial It should also include the following:
Installations
Installation specification See standard EN 50174-1:200, chapter 5.2
Quality plan See standard EN 50174-1:200, chapter 5.3
Final cabling documentation See standard EN 50174-1:200, chapter 6.2

Recommen- When appropriate, the documentation you supply should include detailed
dation 2: information about component acceptance testing. Such documentation includes:
Component z evidence of conformance (for example: for cables, connectors, and cable
Acceptance Type assemblies)
z cable acceptance test records and other information
z cable assembly acceptance test records and related information
z delivery information (for example: unique product identifiers of cables and
components, such as dates of receipt and batch numbers, or identifier codes

31006929.00 10/2005 115


Planning and Layout

Recommen- Before you begin, choose a labeling scheme. To match cable test results to
dation 3: Cabling corresponding components, make sure that the name on the cable test matches the
Identifiers printed label on the patch panel or outlet. For best results, follow the guidelines for
labeling described in Labeling Cables and Components (see p. 114).

Recommen- It is important that you carefully organize and store your test data. Proper
dation 4: Test management of test results is key to determining whether an installation is
Results successful. Test results validate the performance and EMC compliance of a
Management cabling system, allowing assessment of specific components, and providing
valuable historic data. Performing accurate cabling tests is the only way to
verify that your installation meets your original design requirements, and
conforms to regional and international standards. Depending on the type of
installation, you may be required to include test data in your installation
documentation (see Recommendation 2, p. 115).

116 31006929.00 10/2005


Planning and Layout

2.6 Verification of a Transparent Ready Industrial


Ethernet

At a Glance

Overview This section focuses on the process of verifying your cable installation based on the
requirements of the ISO/IEC 11801 standard. Verification is a critical step in making
your installation conform to all applicable standards. You should test the complete
cable installation as well as the individual components of the network. You can
choose to test each section of the network as it is installed (recommended) and/or
plan a final verification stage when you can test everything. Because testing is the
only way to verify that your installation conforms to local and international standards,
Schneider Electric recommends that you become familiar with the recommen-
dations in this section and also refer to Services Overview, p. 157.
At this time, there is no international standard for planning and installing an industrial
Ethernet network. However, there are recommendations from industrial Ethernet
organizations and on-going activities that have resulted in the creation of a draft for
such a standard. Plans are to publish this standard as ISO/IEC 24702 by the end of
2006.

What's in this This section contains the following topics:


Section?
Topic Page
Transparent Ready Industrial Ethernet Verification Recommendations 118
Permanent Links 119
Channels 121
Testing a Copper Installation 123

31006929.00 10/2005 117


Planning and Layout

Transparent Ready Industrial Ethernet Verification Recommendations

Introduction Schneider Electric recommends that you follow the requirements for industrial
Ethernet networks described previously in this chapter.
A certified Transparent Ready industrial Ethernet network must comply with the
following requirements:.
Transparent Ready Industrial Ethernet Requirements
(1) - Installation Correct installation as set forth by ISO/IEC 11801.Correct installation
Requirements as instructed in this guide. Correct installation as required by the
application, for example, wiring of a device or machine according to the
specifications supplied by the manufacturer.
(2) - Performance Performance criteria as set forth by ISO/IEC 11801.
Requirements
(3) - Environmental Environmental protection as described in this guide.
Requirements

The following discussion provides information about how to test a network and verify
its conformance with requirements for items (1) and (2) in the table above.

Additional In addition to the requirements presented in the ISO/IEC 11801, Schneider Electric
Recommen- recommends that you:
dations 1 Select the right components as defined in this guide so that the network conforms
to the performance and environmental requirements of a properly installed
industrial Ethernet. Read this guide carefully before you select components or
begin to install your Transparent Ready industrial Ethernet network.
2 Use approved tools to measure and verify the quality of your installation and its
conformance to regulations.
3 Use local and/or internationally certified installers of Ethernet networks.

118 31006929.00 10/2005


Planning and Layout

Permanent Links

Summary A permanent link, used for testing, is a horizontal cable with an outlet for a
workstation, a patch panel and 2 m of extra cable at each end for testing. It can be
a maximum of 90 m in length, in accordance with standard 568B of TIA/EIA. It
consists of only the passive sections of a cable and the connecting hardware. A
transition point, where cables can be connected, may be included in the horizontal
subsystem of a link.
The permanent link goes from the RJ45 jack connector on one end of a cable to the
RJ45 jack on the other. When a tester is connected to the cable, the effect of the
tester cable and the other tester equipment connected to the cable is automatically
removed from the measurement by the tester. The same removed measurement
occurs with the cable between the last RJ45 jack and the remote indicator required
by the tester.

Example 1 A permanent link between a floor distributor (FD) and terminal outlet (TO) is shown
below. A transition point (TP) is included in the horizontal subsystem:
FD
TP TO

1 permanent link

31006929.00 10/2005 119


Planning and Layout

Example 2 Below is an example of terminal equipment in a work area connected to a host


server using three permanent links, two optical fiber links and a balanced cable link:

CD BD FD
1
TP TO

3 5
2 4

1 terminal equipment
2 host
3 optical fiber cable
4 optional opto-electronic converter
5 balanced cable channel
The optical fiber and balanced cable links are connected together using an optical
fiber to balanced cable converter, a cross-connect, and two equipment cables.
There are interfaces to the cabling at each end of the permanent link. Interfaces to
the cabling are specified at the terminal outlet and at any point where application-
specific equipment is connected to the cabling. The work area and equipment cables
are not included in the permanent link.

120 31006929.00 10/2005


Planning and Layout

Channels

Introduction A channel is a collection of permanent links formed by passive sections of cable,


connecting hardware, work area cords, equipment cords, and patch cords.
Channels do not cross switches or hubs, which are considered end points in any
channel. You should test all permanent links individually and then test the channels.

Example 1 The diagram below shows an example of terminal equipment in a work area
connected to a host server using two channels, an optical fiber channel and a
balanced cabling channel:

CD BD FD
1
TP TO

3 5
2 4

1 terminal equipment
2 host
3 optical fiber cable
4 optional opto-electronic converter
5 balanced cable channel
The optical fiber and balanced cabling channels are connected together using an
optical fiber-to-balanced cable converter. There are four channel interfaces, one at
each end of the copper channel and one at each end of the optical fiber channel.
Equipment connections are not considered to be part of the channel. All work area
cords, equipment cables, and patch cords are included in the channel.

31006929.00 10/2005 121


Planning and Layout

Example 2 The diagram below shows a cable channel that connects a workstation to
telecommunications closets (TC). Channels, unlike links, include the connecting
hardware, equipment cords, work area cords, and patch cords. The cable channel
runs from the patch cord (1) at the workstation to the patch cord (8) inside an
extended closet. It connects the work area to the closets over a horizontal
subsystem that includes two cables and a transition point (TP).

1 patch cord
2 patch panel
3a horizontal cable
3b horizontal cable
4 transition point
5 patch panel
6 patch cord
7 patch panel
8 patch cord
3a = 3b = 90 m max
1 + 6 + 8 = 10 max

122 31006929.00 10/2005


Planning and Layout

Testing a Copper Installation

Introduction You must test a copper installation for correct installation and performance
conformance as defined by the ISO/IEC 11801 standard. For testing the installation
and performance of permanent links and channels, Schneider Electric recommends
that you use market available tools and testers. For more information on testing
(see p. 527).
Some of these tools are described below. Schneider Electric recommends the use
of appropriate tools to certify copper cabling installations and performance.

Example Testers The OMNIscanner 2 and the DSP-4000 are examples of standard tools. Both are
used to test, certify, and document high-speed copper and fiber networks. They are
available from Fluke Networks.

Comparison of The following table compares the features of the two testers. The testers have
Testers complementary functionality. To measure and record the specification parameters
required by the ISO/IEC 11801 standard, you must use both tools.
DSP-4300 OMNIScanner 1
Schematic diagnostics display x -
Shows crosstalk vs length x -
Shows NEXT vs length - x
Shows NEXT phase information - x
Shows impedance vs. length X -
Shows return loss vs length - x
Includes pass/fail S-bands x -
Time domain plots can be saved x -
Magnitude and phase information can be exported - x

31006929.00 10/2005 123


Planning and Layout

2.7 Additional Considerations for Designing a


Transparent Ready Industrial Ethernet Network

At a Glance

Overview This section discusses some important additional topics to consider when
incorporating Transparent Ready capabilities into your network design.

What's in this This section contains the following topics:


Section?
Topic Page
Internet and IP Technologies in an Automation Environment 125
Open System Interconnection Model 127
The TCP/IP Model 128
Transparent Ready Model 130
IP Addresses and Classes 133
Multicasting Considerations 138
Multicast Filtering 139
Network Management 140
Routing 142
Introduction to Remote Access 144
Remote Access Types 146
Network Access Methods 148
PLC Connected to the Internet 151
Security Issues 153

124 31006929.00 10/2005


Planning and Layout

Internet and IP Technologies in an Automation Environment

Network Design Transparent Ready provides a wide range of devices and strategies with which you
Considerations can develop a network infrastructure that supports your plant’s communications.
The openness and flexibility of a Transparent Ready Ethernet network require that
you make some decisions about your system as you design it. These decisions
include:
z how the network will be used
z what communication services it needs to support
z what paths the network will take
z response time/throughput requirements
z redundancy and resilience requirements

Why Use The challenge in today’s world is agility, not only in the technology itself but in your
Ethernet willingness to adopt and refine collaborative approaches for sharing data in real
time. Your communications network should be open to support emerging services,
physical connections, and components. Because Ethernet TCP/IP is so widely
embraced in the commercial world, its technologies are evolving much faster than
proprietary networks, leading to more alternative solutions and more affordable
components.
A standards-based Ethernet solution lets you move away from expensive
proprietary systems while you maintain the security, performance, and availability
required to support critical applications. With proper planning and design, you can
improve processes, reduce expenses, and improve productivity.

31006929.00 10/2005 125


Planning and Layout

Open Standards In both the commercial and the automation domains, Ethernet TCP/IP supports all
Support types of communication including:
z Internet Web pages
z file transfer
z industrial messages
z other standards-based services
For every communication task you need to perform, there is an existing service,
standard, and managing organization. Each of these services need to be run over
the most suitable network layer.
The following list indicates some of the physical media and protocols supported by
open TCP/IP standards and the benefits they bring to industrial automation
environments:
z twisted pair copper cables for simplicity and low cost
z optical fiber for immunity to interference over long distances
z the IP protocol for the communication redundancy inherent in it
z radio and satellite to overcome wiring restrictions
z telephone or Internet for remote point-to-point access at costs comparable to
local calls
z infrastructure components with low-cost that are industrially hardened

126 31006929.00 10/2005


Planning and Layout

Open System Interconnection Model

OSI Model The OSI model defines a seven-layer model for data communications:

7 Application Layer

6 Presentation Layer

5 Session Layer

4 Transport Layer

3 Network Layer

2 Data Link Layer

1 Physical Layer

Layers 1 ... 6 each provide a set of functions to the layer above it, and layers 7 ... 2
each rely on functions provided by the layer below it. Messages can pass vertically
through the stack from layer to layer. Logically each layer can communicate directly
with a peer layer on other nodes.
The following paragraphs focus on the layers and functions of the OSI model that
apply to automation systems. For a complete OSI description, refer to OSI 7498.

OSI and When the OSI model is applied to an automation environment, standards are
Automation applied at each layer. Each layer can perform its function (for example, the Modbus
application layer transfers data around the plant) without knowing anything about
the layers below it. You may adopt any suitable standard for each layer; for example,
wireless or wired at the lower layers and FTP for file transfer or Modbus for data
transfer at the higher layers. All this can be put in place without modifications to any
other layer.
Ethernet is a standard physical and data transport system common to all automation
vendors. Application protocols can vary to suit the environment; some are standard,
others are specific. For example, FTP and HTTP are standard and common to all
vendors, while Modbus and others are vendor-specific. Some protocols (Modbus,
for instance) are open standards; others are available from only a single vendor.

31006929.00 10/2005 127


Planning and Layout

The TCP/IP Model

Summary The TCP/IP model was developed at the same time as the OSI model (see p. 127)
and has become the protocol of choice for most data communication networks. TCP/
IP consists of a four-layer protocol stack that is a compressed version of the OSI
model.

4 Application Layer

3 Transport Layer

2 Internetwork Layer

1 Network Interface Layer

This protocol stack has no specific mapping to layers 5 and 6 of the OSI model.

Application The application layer runs the actual application and protocol. Common applications
Layer include Modbus, Ethernet IP, Profinet, Telnet, FTP, SMTP and Gopher. Interfaces
between the application and transport layers are defined by port numbers and
sockets. TCP/IP can run different application layers simultaneously, allowing an
automation network to carry SCADA (see p. 283) traffic, video, data, programming
data and Web pages at the same time on the same network.

Transport Layer The transport layer provides end-to-end data transfer. It is responsible for reliable
information exchange. There are different transport layer protocols, the main one
being TCP. UDP is another protocol that may run in the transport layer; it is used for
applications that require a fast transport mechanism. Unlike TCP, UDP does not
have the ability to divide long messages and reassemble their packets in the correct
order on the other side, and it is unable to send retries. The application that is
sending the message is required to make sure that the messages are sent in their
entirety or, if required, retransmit the message.

128 31006929.00 10/2005


Planning and Layout

Internetwork The internetwork layer separates the physical network from the layers above. IP is
Layer the most important protocol in this layer. IP is a data-oriented protocol used by
source and destination hosts for communicating data across a packet-switched
internetwork. IP is a connectionless protocol that does not assume reliability from
the lower layers. It is sometimes referred to as the Internet layer or network layer.
IP does not provide flow control or error recovery. These functions need to be
provided at either the transport layer (if you use TCP) or the application layer (if you
use UDP).
The message unit in an IP network is called an IP datagram or packet. An IP
datagram is transmitted across TCP/IP networks. IP provides routing functions for
distributing datagrams to the correct recipient for the protocol stack.
Other internetwork protocols include ICMP, IGMP, ARP and RARP. These protocols
do not replace IP, but they can work alongside it.

Network The network interface layer is the interface to the actual hardware. It is sometimes
Interface Layer referred to as the link layer or the data link layer. It supports packet-oriented or
stream-oriented interfaces and does not guarantee reliable delivery.
TCP/IP does not specify any particular protocol for this layer. It can use almost any
network interface, making it a flexible network with backward compatibility for a
legacy infrastructure. IEEE 802.3, ATM, and FDDI are examples of network
interface protocols supported by TCP/IP.
The ability to run the application layer and TCP/IP over different physical layers
allows the data (SCADA traffic, for example) to run across a fiber link to remote sites
and then across a star-based copper link to the PLC or even a satellite link. All this
can be done without changing the application layer or the TCP and IP layers for
addressing and data delivery.

31006929.00 10/2005 129


Planning and Layout

Transparent Ready Model

Summary The following diagram shows how Transparent Ready implements the four-layer
TCP/IP model (see p. 128):

ta

en
Da
MP

Op

s
CP

u
P

TP

TP

TP
al

db
NT
SN

P
DH

P
lob

TF

HT

SM
FT

Mo
TC
G

(4)

(3) UDP TCP

(2) IP

(1) Ethernet 802.3


and Ethernet II

1 the internetwork layer is Ethernet 802.3 and Ethernet II


2 the network interface layer is implemented with IP
3 the transport layer comprises UDP and TCP
4 the application layer comprises 10 Transparent Ready services

Ethernet II and Ethernet II is the product of a joint development effort by Xerox, Intel and Digital. It
IEEE 802.3 was introduced to the market in 1982. A year later, the IEEE released their 802.3
specification. Functionally, they are very similar, but the way in which the two
formats frame one of the data fields make them incompatible with one another.
Ethernet II and IEEE 802.3 refer only to the physical characteristics of the network:
z the way in which information accesses the network (CSMA/CD)
z how the network frames the data messages
z the physical characteristics of the network itself (its topology, cable requirements,
connectors, infrastructure, and so on)
IEEE 802.3 and Ethernet II can coexist on the same physical cable and use the
same signals. The only difference between the two is the data format.

130 31006929.00 10/2005


Planning and Layout

A data frame can be pictured as a block in which information travels along the
network wire:

Modbus 1

TCP

IP

Ethernet Frame
3

4
1 application protocols
2 internet protocols
3 Ethernet II or IEEE 802.3
4 Ethernet topology
5 access to network (CSMA/CD)

The Internet Industrial automation professionals initially viewed Ethernet as a nondeterministic


Suite of approach to a set of applications that depended heavily on real-time solutions. Most
Protocols suppliers preferred to focus on other technologies, mostly proprietary. What finally
brought Ethernet acceptance in the industrial world is a combination of features
called the Internet suite of protocols.
This suite, known as TCP/IP, was introduced to the market in 1983 as a reliable and
simple way to communicate from multiple sites with different network types. TCP/IP
is independent of the underlying network technology. It can run on top of Ethernet,
IEEE 802.3, token ring, PPP, ATM, DSL or several other technologies.
The suite comprises many protocols, the best known of which are TCP and IP. Other
parts of the suite include:
z the ARP and RARP data link layer protocols
z transport protocols such as UDP
z management and information protocols such as SNMP, DNS, BootP and NTP
z routing protocols such as EGP
z application protocols such as FTP, TFTP, Telnet, SMTP and NFS
These protocols each provide different functions and are located on different layers
in the model.

31006929.00 10/2005 131


Planning and Layout

Model Support The Transparent Ready model supports universal Ethernet services such as HTTP,
for Transparent BootP/DHCP, and FTP. The model also supports these Transparent Ready-specific
Ready Services services:
z Modbus TCP messaging
z I/O scanning
z faulty device replacement (FDR)
z SNMP network administration
z global data
z bandwidth management
z NTP time synchronization
z notification of SMTP events via electronic mail
z optional TCP open
At the transport layer, UDP supports six services and TCP supports four services:
Transport Layer Application Layer Service Provided
UDP SNMP/MIB Network management
NTP Time synchronization
RTPS Global data transfer
DHCP Faulty device replacement (FDR)
TFTP
TCP FTP
HTTP Web server
SMTP Email notification
TCP Open
Modbus Message handling
Modbus I/O scanning

132 31006929.00 10/2005


Planning and Layout

IP Addresses and Classes

Summary An IP address allows a device to have a unique logical address to locate the device
on the TCP/IP network and group it with others for network design and management
purposes.

Dotted Decimal A computer sees an IP address in a binary form of 32 bits. For ease of use, the 32
Notation bits have been divided into four 8-bit groups. Each group is converted into its
decimal equivalent, which results in four decimal numbers separated by dots. As an
example, an IP address in binary 10001011.00101101.00100100.00001100 can be
written in a simpler format by converting each individual octet into a decimal
value,139.45.36.12.

10001011 00101101 00100100 00001100


139 45 36 12

Network Address An IP address consists of two parts, the network address and the host or device
Defined address. The subnet mask is a filter that is applied to the IP address to determine
which part of the IP address is the network address and which part is the host or
device address. The network address is the part of an IP address that identifies the
subnet that the address is a part of. The mask is a 32-bit value that uses one-bits for
the network and subnet portions and zero-bits for the host portion. In classful
addressing, the network address portion of the IP address consists of one, two or
three octets, starting from the left.

IP Address 11000000 10100000 00010100 00110000 192.160.20.48


Subnet Mask 11111111 11111111 11111111 00000000 255.255.255.0
Network Portion of 11000000 10100000 00010100 00000000 192.160.20.0
IP Address

31006929.00 10/2005 133


Planning and Layout

Classful In classful addressing, there are three possible classes of IP address to use,
Addressing depending on the size of your enterprise:
Class A = 1.01010/9 through 127.0.0.08
Class B = 128.0.0.0/16 through 191.255.0.0/16
Class C = 192.0.0.0/24 through 223.255.255.0/24
Class D = 224.0.0.0 through 239.255.255.255 is used for multicasting (see p. 138).
The remaining addresses known as Class E are reserved for experimental use.
An address comprises 2 parts:
z the network information
z the host (node or end device) information
The IP address comprises 4 sets of decimal numbers called octets, each separated
by a period, with a value from 0 to 255 that represents a converted binary-to-decimal
number

Classless Classless addressing (also known as CIDR or supernetting) was developed to


Addressing improve current Internet problems regarding the efficient utilization of address
space. It also is used to add to the routing scalability of networks. Allocating portions
of the large but limited number of addresses to an enterprise all at one time often
resulted in the waste of some reserved addresses. Including each network in a table
resulted in overload. Also, medium-sized enterprises that fit the class B category
have multiplied the fastest, using much of the space in that class. Classless
addressing, by allowing the delineation point between network information and host
information to be flexible, has expanded the number of addresses available to all
sizes of enterprise and has reduced the size of routing tables.

Choosing an Public addresses, for use on the Internet, are assigned by a governing organization
Address Range called the Internet Assigned Numbers Authority (IANA). However, your company
may already have been assigned a section of addresses and your IT person can
allocate the quantity that you need. If you have not been given a predefined set of
IP ranges, you should be aware that the following three blocks have been reserved
by IANA for private Internets:
10.0.0.0 - 10.255.255.255 (10/8 prefix)
172.16.0.0 - 172.31.255.255 (172.16/12 prefix)
192.168.0.0 - 192.168.255.255 (192.168/16 prefix)

134 31006929.00 10/2005


Planning and Layout

Special There are three types of special addresses that should be mentioned:
Addresses z broadcast
z loopback
z network
A broadcast message, usually used for network management and diagnostic
purposes, is addressed to all stations on the network. The destination address in a
broadcast message is made up of all 1s (255.255.255.255).
A loopback address is used to test the implementation of the TCP/IP protocol on a
host. The lower layers are bypassed by sending to a loopback address. This allows
the higher layers (IP and above) to be tested without exposing problems at the lower
layers. 127.0.0.1 is the address typically used for loopback testing.
As described in the previous section, network address refers to the network portion
of an IP (Internet Protocol) address.

Sufficient In planning for your network, you should anticipate the need for these addresses:
Addresses z for the gateway (one address)
z for broadcast
z for the number of services
z for future devices added to the network
Tools can be found on the Internet to help calculate the number of addresses your
network requires.

Subnetting Forming subnets divides a large network into more manageable segments; it can
allow you to expand the number of networks, while using only the single IP address.
You need not apply for more of the limited number of IP address numbers.
Network traffic is reduced by sending messages to only a limited segment of the
network. Subnetting can be particularly helpful on a network that handles a lot of
broadcast traffic. It can also be useful if you have a slow WAN link connecting your
far-flung locations.
To subnet, the default subnet mask for a network is extended to cover bits of the
address that would otherwise be part of the host field. Once these bits are masked,
they become part of the network field and are used to identify subnets of the larger
network.
Choose a subnet of a size (number of addresses) appropriate for the number of
devices on it; a size that allows for growth, but is not wasteful of addresses. For
example, if you have 50 devices, choose a subnet of 64 addresses, not 1024. The
following table contains one column presenting the number of addresses and
another with the corresponding mask.

31006929.00 10/2005 135


Planning and Layout

Subnet Mask Number of Addresses


0.0.0.0 4,294,964,086
128.0.0.0 2,147,482,048
192.0.0.0 1,073,741,024
224.0.0.0 536,870,512
240.0.0.0 268,435,256
248.0.0.0 134,217,628
252.0.0.0 67,108,864
254.0.0.0 33,554,432
255.0.0.0 16,777,216
255.128.0.0 8,388,608
255.192.0.0 4,194,304
255.224.0.0 2,097,152
255.240.0.0 1,048,576
255.248.0.0 524,288
255.252.0.0 262,144
255.254.0.0 131,072
255.255.0.0 65,536
255.255.128.0 32,768
255.255.192.0 16,384
255.255.224.0 8,192
255.255.240.0 4,096
255.255.248.0 2,048
255.255.252.0 2048
255.255.254.0 1024
255.255.255.0 512
255.255.255.128 128
255.255.255.192 64
255.255.255.224 32
255.255.255.240 16
255.255.255.248 8
255.255.255.252 4
255.255.255.254 2
255.255.255.255 1

136 31006929.00 10/2005


Planning and Layout

For a subnet with 64 addresses, the subnet mask is 255.255.255.192. The IP


address would therefore be 192.168.1.1, the network address would be 192.168.0
and the host range would be from 0.1 to .63.

Using Subnets in By using subnets in your plant, you can divide the plant into sections to avoid traffic
a Plant overload. Use a router to pass traffic between subnets. There should be no more
than 200 to 300 devices per network. However, it is preferable to have a smaller
network with 50 to 100 devices. Add networks if you must accommodate more
devices than the preferred number.

Assigning You may obtain addresses from the governing organization or use a group of those
Addresses already assigned to your company. The next step is to assign a unique address to
each end device by one of several methods. In static addressing, each user is
assigned one fixed IP address to be used every time the user connects to the
Internet. Dynamic addressing assigns the IP automatically, as needed. BootP
(Bootstrap Protocol) as its name suggests, allows a workstation to configure itself
without a hard drive or floppy disk. The workstation can discover its own IP address,
the IP of a server and a file to be loaded into memory to boot the machine. DHCP
assigns a different address to a device when it requests one. The software, rather
than the administrator as in static addressing, keeps track of the IP addresses.

31006929.00 10/2005 137


Planning and Layout

Multicasting Considerations

Summary IP multicast, a method of selectively sending messages promoted by an industry


consortium of prominent companies, is an up-and-coming technology that will be
used increasingly for:
z monitoring: manufacturing and other types of real-time information, sensor
equipment or security systems.
z announcements: network time, multicast session schedules, random numbers,
keys, configuration updates, etc.
z file distribution and caching: Web site content, executable binaries
z scheduled distribution of audio and video
z push media: news headlines, weather updates, sports scores, etc.

On the Internet You should make sure that your router and/or switches support multicast, your
workstations are configured to join a multicast group and that you have installed any
specific applications needed to receive the multicast.

IP Multicasting The UDP protocol is used for IP multicasting. The multicast address selected is
Transport important in allowing network managers to control the way hosts (end devices) join
groups and how routers exchange multicast information.

IP Multicast In IP multicasting, each group has a multicast group ID, a set of Class D IP
Addresses addresses used to specify the destination of a message. The addresses range from
224.0.0.0 to 239.255.255.255. Each multicast IP address can have a number of
hosts listening to it. Hosts can belong to a multicast group, and the IP addresses are
associated with that group. Each configured device has a multicast IP address that
is in addition to its own IP address.
Class D addresses can be classified as follows:
z permanently assigned: addresses in the range 224.0.0.0 to 224.0.0255,
permanently assigned by IANA for certain applications such as routing protocols;
for example:
z 224.0.0.0 for the base address
z 224.0.0.1 for all systems on this subnet
z 224.0.0.2 for all routers on this subnet
z 224.0.0.4 for DVMRP routers
z nonpermanent: addresses in the range 224.0.1.0 to 238.255.255.255, used for
assignment as needed on the Internet
z administered nonpermanent: addresses in the range 239.0.0.0 to
239.255.255.255, reserved for use in private Intranets

138 31006929.00 10/2005


Planning and Layout

Multicast Filtering

Summary Two services and one variation can be used for multicast filtering:
z IGMP
z IGMP snooping
z GMRP

IGMP IGMP is used by a router to establish multicast group membership and send a
message to a particular network that has multicast members. It stops forwarding the
message when the last destination on a segment receives the message. IGMP is
used for the routing of multicast messages on the Internet, as well as on a LAN.
IGMP operates at layer 3; it does not provide filtering at the switch level.

IGMP Snooping This method passively snoops on the registration information of IGMP packets to
learn about group membership. This information is used to compile a list of
destinations to receive a given message. IGMP filters at the switch level by listening
to device and router messages and the IGMP Querier. (The querier is normally the
router, but if this is not the case, an IGMP Querier is required.)

GMRP GMRP is used to dynamically configure switch ports so that IP multicast traffic is
forwarded only to those ports associated with IP multicast end users (hosts). A
switch can exchange information about groups with other switches, stop (or prune)
broadcast traffic after all subscribed destinations have received the message, as
well as create and manage multicast groups. GMRP operates in layer 2 with layer 2
devices such as Ethernet switches. Transparent Ready supports GMRP.

MAC Address NICs exchange information using a unique MAC address, not an IP address. To join
Mapping with a multicast group, you must run an application on a host that can inform its network
Class D device driver that it wants to be a member of a specified group. The device driver
Addresses maps the multicast IP address to a physical multicast address.

Obtaining Group Group memberships are dynamic. Members are able to join and leave a group
Membership anytime they want. Senders need the multicast IP address only to send information,
regardless of whether or not any hosts are listening at that time. When a host wants
to join a multicast group, it signals its intention to the router that sits on the same
subnet.

31006929.00 10/2005 139


Planning and Layout

Network Management

Summary Managing your network allows you to monitor:


z who is on the network
z network traffic
z network traffic errors
z device errors

Network Network management is accomplished by the use of a management system, a


Management protocol that allows the management system to communicate with the devices, and
Components end devices such as switches and routers that are configured to support the
protocol.

SNMP Protocol SNMP has become the standard protocol for network management. It comprises
z an agent, the software module for network management that resides in a device
z a manager (NMS) that can query and get responses from agents and set
variables in them
z a managed device with a MIB

MIB A management information base (MIB) is a data base of managed objects such as
broadcast messages sent and received or corrupted packets. Each specific instance
of a managed object is called a MIB variable. Most devices support MIB II with some
extensions for switches.

Private MIBs A private MIB, installed in addition to the standard MIB, is supplied by a vendor and
is specific to that vendor’s products. Schneider has a set of MIBs to load into a
management package in order to manage devices.

Setup of a In order to set up a network management system, load the MIB file into the manager.
Network The manager knows the required data and addresses needed to discover the
Management devices on the network. It will feed the MIB files and begin to monitor the network.
System

140 31006929.00 10/2005


Planning and Layout

Security A community string, configured on a router or switch, is a password that defines a


community of end users that can access SNMP information on a network device.
The community string should be an alpha-numeric string of at least 8 characters.
Designating access to devices in this way aids in providing security for your network.
Security in the latest SNMP version v3 controls:
z the modification of information
z masquerading
z the modification of the message stream
z the disclosure of information
SNMP version 3 provides better security features than versions 1 and 2.

Effects on the When setting up a network management system, be aware of the effect that the
Network system might have on network speed and congestion. If you program the system to
monitor the network at too frequent a rate, you could overload the network with
traffic. An update rate of every 30 s to 1 min should be sufficient to provide data
without generating unnecessary traffic.

31006929.00 10/2005 141


Planning and Layout

Routing

Summary Routing is a method of finding paths to move messages from one network to another
network. The Internet uses a process in which each node (router) looks at a packet’s
header information, calculates the next hop on the route to the destination and
delivers the packet to the next node, which repeats the process. The process occurs
at Layer 3.

Routers A router is a device that connects two or more networks at a gateway and forwards
packets along the network. It has an Ethernet card or another interface for each
network.

Routing Process The message is looked at by the sending device. If the destination is local, the
message is sent directly to the end device. If the destination is remote (not on the
same network), the message is sent to the default gateway (the local router). This
router uses its own information about connected networks to pass the message,
either to the final network (if it is directly connected) or to the next router closer to
the final destination.

Routing Tables A routing table contains a record of the best routes possible to reach a number of
given network destinations. A routing table includes information needed for
determining that route; the destination IP address, the gateway IP address and the
physical interface identification. Each router knows only its local networks, but
passes this information on to other routers, which builds up tables. The router may
be programmed to know just the first attached network or it may know several
downstream. If it does not know where to send a message, it will pass the message
to its own default router, which is farther upstream in the network, for processing.
Routing tables are created either by hand for a small system or automatically using
routing protocols.

142 31006929.00 10/2005


Planning and Layout

Routing Routing protocols decide on the contents of routing tables. In a small stable system,
Protocols it is often best to program the routing tables by hand. In a larger system or one that
requires redundancy, a routing protocol needs to be chosen.
Protocols used within a system include RIP, a distance vector protocol that is the
most widely used, and OSPF, a more recent link-state routing protocol.
A distance vector protocol uses distance, as measured in routing hops, to determine
a packet’s optimal path. Each node shares its routing table with the neighboring
routers. In a link-state routing protocol, every switching node (router) receives a full
map of network connections, passed from one node to another, which it uses to
calculate the best next hop from it to all possible destinations on the network.
RIP is robust, its configuration is simple and its algorithm does not impose a burden
on storage or computation capacity. However, it does not directly support
subnetting, requires a lot of bandwidth, may be hard to debug, may have problems
making the many hops on a larger network and has weak security.
OSPF, among its other advantages, supports subnetting, verifies a link by sending
a small packet and can work with a larger network. It does, however, use a lot of
memory and computation capacity and is rather more complex.
When considering which protocol to use, look at the ability to handle the number of
routers in our system, convergence time (how long it takes to build the routing tables
after a change), and the amount of traffic generated by the protocol itself.

Path Cost Path cost, usually based on criteria such as hop count and media bandwidth, is used
to compare the cost of passing a packet over various paths on a network. Path cost
is defined for each network and is used by the routers to choose the optimal path to
the final destination; the lower the cost, the better the path. This is one way to
prevent the data from being sent around and around the router network.

31006929.00 10/2005 143


Planning and Layout

Introduction to Remote Access

Summary In a plant environment, access to the industrial control system is essential for
capturing data, troubleshooting, control, and minor adjustments. With critical
applications and industrial processes demanding 24x7 attention, the ability to
administer network devices from a remote location is increasingly desirable. Remote
access is useful for:
z OEMs whose machines may be installed anywhere in the world
z end users who may not maintain local support staff
z system integrators looking to add more value to their offer
z systems requiring remote data gathering

Examples For example, an alarm for tank overflow is paged to an operator. The operator logs
in, checks the status of the tank, determines that it is safe to halt pumps, and pauses
the process until morning so that the situation can be investigated and corrected.
Another example is that of an OEM who ships a machine to a customer in another
country. The customer chooses to use a different type of sensor than the one the
specified by the OEM. After start-up, the system does not work as planned. With
remote access, the OEM is able to log into the plant, modify the program, and get
the customer’s machine running without a costly, time-consuming on-site visit.

144 31006929.00 10/2005


Planning and Layout

Methods Three methods of remote access are commonly used, each via a different protocol:
z direct access to a PLC via dial-up
z remote control of a PC via dial-up
z remote access to the complete network
To determine the most suitable type of connection, you need to establish a list of
functions that your remote connection must provide. Common features include:
z data gathering
z remote troubleshooting
z programming software
z SCADA
z remote programming
z security
For corporate private networks, several considerations are important with respect to
a remote access capability:
z reliability
z performance
z scalability
z manageability
z secure connectivity through encryption and/or authentication of users and
devices
z accessibility

31006929.00 10/2005 145


Planning and Layout

Remote Access Types

Direct Dial-up to Direct dial-up is handled by a modem attached directly to a plant PLC or other
the Device device. An operator is able to dial into the modem and access the device port as in
a local connection. The operator is restricted to serial protocol access to only a
single PLC or device via Modbus.

Remote Control Remote control dial-up involves taking control of one of the PCs on the site. The
of a PC via remote operator actually uses the PC on site. All inputs from the remote keyboard/
Dial-up mouse are sent to the site PC, and the screen image of the site PC is shown on the
remote PC.

Network Access Network access involves extending the Ethernet network to a remote station. It may
be implemented using either a RAS server or by VPN. The Ethernet connection
allows full access to all PLCs and other devices on the site’s Ethernet. The remote
station can access Web pages, implement diagnostics, do programming, connect to
network printers, and access documents from servers.

Connection of When a connection from a PLC to the Internet is established, any client connected
the PLC to the to the Internet can access the PLC. Remote clients can access Web pages,
Internet implement diagnostics, programming and perform many other functions.

146 31006929.00 10/2005


Planning and Layout

Comparison of
Remote Access
Options
Method Accessible PLC Web Setup Ongoing Setup Client Requirements
Systems Protocol Page Cost Cost Difficulty
Access Access
Direct Dial- Single PLC Yes No Low Phone Low Must run full PLC/SCADA
up to Device charges software etc.
Remote All devices Yes Yes Low Phone or Low to Remote control software
Control or PC Internet high must be installed on local
via Dial-up Charges and remote PC. Note of
caution: in this case, security
may be compromised
Remote All devices Yes Yes Medium Phone or Low to PLC/SCADA software Web
Access via on the local Internet high browser
RAS or VPN Ethernet Charges
network
PLC All devices Yes Yes Medium ISP costs High PLC/SCADA software Web
Connected to have an (High) browser
the Internet Internet
connection

31006929.00 10/2005 147


Planning and Layout

Network Access Methods

Summary The cost and the number of users you need to support are the determining factors
when choosing a remote access method. You should not deploy VPNs or any
security technology without an associated policy (see p. 153) in place. Be aware of
the data on your network that is considered sensitive so that it can be properly
protected when transported over the Internet.

Remote Access Two general layouts of a remote access system are shown below, one with a
Server dedicated RAS server and one using a Windows server PC.

5
3
1

1 4

1 remote PC
2 modem
3 RAS server
4 modem
5 network

RAS System z A new global IP address is not needed. The IP address of the PLC can be the
Advantages one assigned on the company network.
z No ISP is needed.
z There are no ongoing service costs for the company running the PLC.
z You can deliver a configured system anywhere in the world that becomes
operational when a phone line is connected. (A modem compatible with the
location must be installed prior to shipping.)

148 31006929.00 10/2005


Planning and Layout

RAS System A direct phone connection is required between the remote client and the RAS
Disadvantages server. Potential problems include:
z cost
z poor quality phone connection
z slow speed

RAS System z A RAS server needs to be added to the Ethernet network that is connected to the
Components PLC.
z The default gateway of the PLC is set to the IP address of the RAS server.
z A modem is added to the RAS server. A good quality locally supplied modem
should be adequate.
z The RAS server should be configured for any security or firewall settings that are
required.
z A modem is added to the remote client.
z The remote client is configured for dial-up access.

RAS Server Whether your company requires a dedicated RAS server with security and firewall
Implementation features or just a simple Windows NT server or workstation, consider the following
security and system factors in your network design:
z support for external modems: Some standalone RAS servers do not support
serial style modem connections.
z security verification: including Chap, PAP or Windows authentication. Many
systems provide an additional security layer before the user can access a
Windows style network. If there are no Windows servers on the network, the RAS
server becomes the main verification point.
z dial-back: so that the RAS server and modem can be configured to dial a user
back at a pre-configured phone number. This security feature requires that
anyone attempting to access the system be at a specific phone number. The
client dials the RAS server and enters a name and password; the RAS server
hangs up and dials the user back at a fixed phone number. While this feature
provides excellent security, it can also be a very limiting option. When an OEM
ships a dial-back machine to a customer, the end user pays most of the cost of
the RAS connections because the phone connection is initiated from the PLC end
of the line.
z allowed protocols: Many RAS servers can be configured to allow only specific
protocols, such as IP traffic. Make sure that all the protocols you require are in
the list of allowed protocols.
z firewalls: Some RAS servers can incorporate or add a firewall. A firewall can
provide a very secure environment for the PLC and prevent almost all
unauthorized attempts to access the PLC or network.

31006929.00 10/2005 149


Planning and Layout

Virtual Private A VPN creates private networks using a transport mechanism such as the Internet
Network or public telephone network. It routes IP through a secure tunnel created between
two networks. The idea is to create what appears to be a dedicated private link on a
shared network using encryption and tunneling techniques. VPN technology is a
cost-effective way to provide secure connectivity to remote locations over the public
Internet. Site-to-site VPNs can be used to provide connections to remote office
locations. This can save on expenses associated with costly leased lines. VPNs also
provide a secure means of connecting to a private network from any Internet
connection.

Common VPN z remote access VPN: The most common and familiar situation for remote access
Environments may be that of an individual user connecting from a remote location, such as a
residence or travel destination, to a private network at the user’s place of
employment. The most common way to accomplish this today is using a VPN.
which is not only faster, but more cost effective, flexible, and convenient than
leased or private lines.
z point-to-point VPN: VPN technology can also be used to connect remote sites or
branch offices to the organization’s main network. VPNs are replacing such WAN
technologies (see p. 65) as leased lines, frame relay, and ATM. A VPN provides
traditional WAN requirements for this situation, such as multi-protocol support,
high availability, scalability, and security. As mentioned above, it also has
advantages over private WAN services.

150 31006929.00 10/2005


Planning and Layout

PLC Connected to the Internet

Summary Permanently connecting a PLC to the Internet can be costly and difficult for a small
company or OEM. However, for a large company that already has a permanent
Internet connection and is familiar with such issues as hosting its own web servers,
the task is simply an extension of their existing system.

Internet This system offers several benefits over the previous RAS setup:
Connection z The PLC is permanently connected to the Internet. This allows quick access to
Benefits/ the PLC from any PC connected to the Internet, no modem required.
Disadvantages z No long distance phone calls are required to access the PLC; simply connect to
your local ISP.
z The number of simultaneous remote connections to the PLC is not limited by the
number of modems on the RAS server.
However there are some serious disadvantages and difficulties:
z A permanent connection to the Internet is required.
z A permanent globally unique IP address is required for the PLC; this may not
match the address used on your local system.
z There is no easy way to limit access to the PLC, unlike using callback for a RAS
server, although firewalls can be used for access control.

31006929.00 10/2005 151


Planning and Layout

General Internet General system setup is as follows:


System Setup z A local ISP needs to be found to provide a permanent connection from the PLC
to the Internet. This can be very expensive as most permanent connections use
methods other than modems. If you are planning to use a modem, consult with
the ISP and phone company to check that a phone connection can be left
connected indefinitely.
z Obtain a permanent unique IP address for your PLC. For small companies, this
address may be obtained through your ISP. Leasing this address from your ISP
may be expensive as there are a limited number of these addresses worldwide
and the ISP can either lease an address to a single user or share this address
with many users. Larger companies should already have a series of these
addresses.
z Have your ISP or IT staff configure any routers that are needed to access this IP
address from the rest of the Internet. Also configure the PLC’s IP address and
gateway.
z A firewall (see p. 154) should be installed to separate the portion of the network
connecting your PLC to the Internet and the rest of your network. This is done to
prevent users accessing other parts of your network. A firewall can also be
installed between the PLC and the Internet to restrict the type of access users
have to the PLC. Presently no available firewalls permit Modbus data commands
(reading/writing of data) while also preventing programming commands
(programming the PLC using Concept, Proworx or Modsoft).
If you are planning to permanently connect your PLC to the Internet, Schneider
Electric recommends working closely with personnel from your IT department or, if
they are unavailable, partnering with a reputable local ISP.

152 31006929.00 10/2005


Planning and Layout

Security Issues

Summary There are many different aspects to network security. Network security includes
allowing an operator day-to-day access to a PLC, the prevention of damaging but
non-malicious activity, and the enforcement of plant procedures and authorizations.
However, preventing malicious activity is much more difficult than these other areas
of security. Malicious activity includes unauthorized access, interference with
corporate data, virus attacks, denial of service, spoofing of Websites and email, as
well as fraud and other criminal activity. Securing your network against malicious
intent is very difficult to implement and requires the advice of security experts. The
amount of time required to secure the network against breaches depends on the
level of skill the attackers possess, but prevention requires constant monitoring.
Security against non-malicious activity, however, can be implemented by personnel
who do not possess this level of specialized training.

Security Policy Your security policy defines the information and services to be accessed, how they
can be accessed and who will be given access to them. Defining a security policy,
rather than just beginning to implement one without a plan, is more likely to help you
cover all areas. Planning also makes it easy to remember what security to apply
when you add to the network.

Passwords Passwords should be changed monthly. Do not choose simple user names and
passwords if you are trying to prevent malicious access. Default passwords on all
devices should be changed or disabled, since default settings are often easy to find
in user manuals.

Physical Access Preventing physical access to a network is crucial in implementing security against
malicious attacks. It is very easy to get SNMP or telnet passwords when you have
physical access to the network. Therefore, preventing physical access to the
network infrastructure is crucial in keeping control of the network layout. The time
spent organizing network traffic in an efficient way can be negated by users who
make the network inoperable or prevent device communications.

31006929.00 10/2005 153


Planning and Layout

Firewalls A firewall is a device or program that filters the information coming through a
connection into your network. A firewall inspects each packet and decides if that
packet will be allowed to pass, based on:
z source IP address
z destination IP address
z destination TCP port number (which protocol is being used)
Place firewalls ar critical junctions within your networks, such as:
z between the office network and the plant floor
z between areas of your plant
z between contractor laptops and the plant
By filtering with basic firewalls, you can limit access to a certain area of your network
or to a certain device based on the information coming from the computer attempting
access. Since the access is IP based, you cannot filter per person. You can allow
access to a device, but restrict the protocols that can be used. For example, you can
allow web page viewing, but not FTP for firmware transfer.

Modbus Filtering With Modbus filtering, however, you cannot allow data monitoring without allowing
and Firewalls programming as well, since these are both in one protocol. One possible solution is
to allow only several OPC services to perform data access and to block all other
devices. This also prevents monitoring with a programming package.

Advanced More advanced firewalls are appearing that can inspect the upper layers of Ethernet
Firewalls packets and determine if they can pass. This allows application layer filtering, but
also means that these firewalls do not allow Modbus programming commands.
These firewalls are slower than the current type and are not common as yet.

Setting Up a The methodology used for setting up a firewall is important.There are two ways to
Firewall set up a firewall:
z allow all and then deny specific items
z deny all and then allow specific items
The method of deny all is the more secure, because it restricts even those cases you
had not thought of. This is, therefore, the recommended setup method.

Access Control An access control list is implemented in layer 3 switches (see p. 63) and some layer
Lists 2 switches. It provides a filtering service similar to a firewall, but is based on a
source/destination port or VLAN (see p. 60), instead of an IP address. It can be used
at lower levels of a network (on the plant floor) to prevent access from one plant area
to another. Once an access control list is set up, the system stops all types of
access, for example, a person accidentally trying to connect to a PLC in the next
area of the plant. The setup method is the same as for a firewall.

154 31006929.00 10/2005


Planning and Layout

Port Security The Schneider NxS272 device is able to protect each port using port security. Port
security functions similarly to an access control list, but limits incoming connections
based on a MAC address. Settings can be made to control who has access; every
address or only a single address. If an invalid address is detected, settings can
control the response; no response, trap or disable. Settings are made using the web
address.

PLC Access The Ethernet ports of the Quantum/Premium PLCs and ETG Gateway support
Control access control lists for Modbus messaging. They allow you to configure IP
addresses that can send Modbus requests to the PLC. They do not allow access to
other protocols. Use care when setting access control because it restricts the
functioning of active Web pages that use Modbus to retrieve data

Security Issues Wireless networks suffer a great security disadvantage when compared to
with Wireless traditional networks. Because a wireless network transmits over radio waves, it is
easier to get unauthorized physical access to it.
These options for wireless systems exist in automation systems:
z traditional wireless systems for Serial networks, Modbus Plus and custom
Ethernet solutions
z wireless Ethernet based on office standards
Systems based on non-standard wireless are more difficult to intercept since they
do not use standard protocols. However, systems using office-based wireless can
be intercepted using any laptop computer with a wireless connection, putting them
more at risk.
Each wireless network is given an SSID, or network name, to identify it. Normally,
the SSID chosen is a logical name. Do not choose a logical name such as the
hardware vendor or your company name; this gives information about the network.

Access Points An access point (software or a device) provides the connection hub for a wireless
device connected to a cabled LAN. Access points have a setting of broadcast SSID.
If this is set to on, the network name is broadcast and it appears as a choice to
computers trying to connect. Disable the broadcast. This requires all computers to
be pre-configured with the SSID in order to connect to the network. Most wireless
networks use a DCHP server to assign IP addresses to clients. Configure the server
to give IP addresses to specific Modbus Plus addresses. Do not configure any
additional spare addresses. Limit access to known MAC addresses. Access points
can be set up to allow only known IP and MAC addresses to connect. The MAC
address on most PCs, especially laptops, can be changed to match one existing on
the network.

31006929.00 10/2005 155


Planning and Layout

WEP Wired equivalent privacy (WEP) secures the network by encrypting data transmitted
over radio waves so that anyone who wishes cannot simply listen to it. WEP should
be turned on. Choose a WEP key, which allows you to listen to the network. Always
generate a random WEP key; never use a key based on a word. The algorithms for
generating keys from a word are known and programs exist to decipher word-based
WEP keys. Therefore, a word-based WEP key is not secure; it can take from only 3
hours up to a few days to crack.

VPN and The combination of VPN and firewalls is the best security solution, but it is costly in
Firewalls terms of management time. Run a VPN client on the laptops and a VPN endpoint
where the wireless network meets the main network. This adds additional encryption
(stronger than WEP) to the data being transmitted. Run a firewall between the VPN
endpoint and the rest of the network to further restrict access.

156 31006929.00 10/2005


Services Overview

3
Overview This chapter gives you information to select the correct Transparent Ready service
for each task in your automation system. It describes the benefits and limits of each
service, and it discusses the operation of devices that use the service.

Note: The Unity performance data used in this chapter are based on version 2.0 of
the software. Other Unity versions may be significantly different.

What's in this This chapter contains the following sections:


Chapter?
Section Topic Page
3.1 Evaluating System Requirements 158
3.2 I/O Scanning Service 170
3.3 Modbus Messaging 183
3.4 Global Data Service 202
3.5 Faulty Device Replacement 209
3.6 Time Synchronization 213
3.7 Electronic Mail Notification Service 222
3.8 Standard Web Server 228
3.9 FactoryCast Web Server 235
3.10 FactoryCast HMI Web Server 241
3.11 Other Services 248
3.12 OPC Factory Server 264
3.13 SCADA/HMI 283
3.14 Redundancy 296
3.15 Gateway/Bridge Systems 313
3.16 Supported Services per Device 321
3.17 System Performance Evaluation 332

31006929.00 10/2005 157


Services Overview

3.1 Evaluating System Requirements

At a Glance

Overview This section provides an overview of Transparent Ready services that support
Ethernet communications at each level within the plant. It also describes how to
evaluate your communications requirements and select the most appropriate
services.

What's in this This section contains the following topics:


Section?
Topic Page
Common Services at each Level in the Plant 159
Company Level Communication 160
Inter-PLC Level 161
Field Level Communications 162
Communication Service Selection 163
Transparent Ready Support Services and Protocols 165

158 31006929.00 10/2005


Services Overview

Common Services at each Level in the Plant

Summary Transparent Ready industrial products can be integrated into architectures based on
the universal Ethernet TCP/IP network. No additional interfaces are required. The
basic architecture below shows the various communication levels and functions
required by industrial applications to meet the data exchange requirements of a
plant:
Communications may take place at four levels:
z company level communication (see p. 160)—between the control system
products and the manufacturing execution system (MES) or enterprise resource
planning (ERP) supervision or information systems
z inter-PLC level communication (see p. 161)—for programming, diagnostics, and
data transfer as well as communication between PLCs to synchronize
applications
z field level communication (see p. 162)—between PLCs, PCs, and field devices
z transparent remote communication—remote communication via the Internet,
telephone, or radio link

31006929.00 10/2005 159


Services Overview

Company Level Communication

MSE/ERP Company level communications use standard infrastructures and protocols to


Systems and exchange high volumes of data with project management systems. In some cases,
PLCs the PLC must adapt to a protocol specific to the connected system. Response times
are not critical. The Transparent Ready services used are:
z HTTP communication to display data and send commands via Web pages
z data exchange using the OPC standard via an OFS data server (see p. 264)
z Modbus TCP/IP messaging (see p. 183)
z TCP open
z email transmission (see p. 222)
z direct publication in relational databases via the FactoryCast HMI active Web
server (see p. 241)

Supervision Company level communications may transfer high volumes of data from a corporate
Systems and system to a group of PLCs. Response times generally need to be in the 0.5 to 2 s
PLCs range. The Transparent Ready services used are:
z data exchanges using the OPC standard via an OFS data server (see p. 264)
z Modbus TCP/IP messaging (see p. 183)
z TCP open
z HTTP communication, integrated in the supervision system to display Web pages
from the field devices in supervision pages

HMI Applications A basic HMI application must notify maintenance personnel of an event and let them
and PLCs/Field view the status of a field device. The Transparent Ready services used are:
Devices z email notification
z data display and transmission commands via Web pages

SNMP The standard network management protocol (SNMP) can be used from a network
management station to monitor, control, and perform diagnostics on all components
in the Ethernet architecture (see p. 250).

160 31006929.00 10/2005


Services Overview

Inter-PLC Level

Data Transfer When data is sent in point-to-point mode according to PLC programming algorithms
Communication and the required response times are in the 200 ms to 1 s range, the main
Transparent Ready service to be used is Modbus TCP/IP messaging (see p. 183).

Synchronizing Broadcast communication uses real-time exchanges to synchronize several


Applications applications. Data is exchanged in low volumes. Response times in the10 to 500 ms
range are required. The Transparent Ready Global Data service (see p. 202) is
particularly suitable for synchronized data exchanges.

31006929.00 10/2005 161


Services Overview

Field Level Communications

Field PCs and Field level communication is used to configure, monitor, and maintain field devices
Operator for diagnostics and monitoring. Communication procedures must be simple so that
Terminal less qualified personnel can access first-level diagnostics from a standard PC.
Communication The most suitable Transparent Ready service is the display of diagnostic and
customized Web pages (see p. 228).
Modbus and/or other industrial fieldbus protocols are used to control field devices.

162 31006929.00 10/2005


Services Overview

Communication Service Selection

Summary The following description of services (and the services tables that follow in the next
discussion) can help you decide which services are best for your application.

I/O Scanning The I/O scanning service allows you to exchange information repetitively between
one central device and many remote devices without the need for special
programming in either device.
It is used when you want to exchange data repetitively and at a fast rate (every 1 ms
to 5 s). A typical example of a device that can use the I/O scanning service is a
barcode reader that needs to scan all package labels as they travel along a fast-
moving conveyor belt. For details, see p. 170.

Modbus The Modbus messaging service comprises client and server services. The client
Messaging initiates a request to the server using the Modbus protocol; the server responds to
the client’s request, resulting in information exchange. Modbus messaging supports
both reading and writing of data, as well as a set of programming commands.
Modbus messaging should be used when data needs to be exchanged between two
devices at irregular intervals or infrequent periods. An example is a command to
start a process or report on the completion of a process. Modbus messaging lets you
initiate communications only when they are required, making more efficient use of
your network and device resources. For details, see p. 183.

Global Data The global data service allows a device to publish data to a group of devices on the
network. Devices in this distribution group can be configured to subscribe to the
published data.
The global data service should be used when a device contains status information
that more than one other device on the network needs to receive. The publishing
device uses multicasting to efficiently send information across the network to its
distribution group. For details, see p. 202.

Faulty Device The FDR service allows a central device (the FDR server) to store configuration
Replacement parameters for remote devices on the network. If a remote device fails, the server
automatically passes the stored configuration parameters on to a replacement
device so that it can operate using the same configuration parameters as the failed
device. The replacement is accomplished without manually configuring the
parameters.
The FDR service should be used for all devices that are connected to an automation
network. It reduces the need for service personnel to keep configuration records on
hand, and it prevents human error in entering the new configuration. For details, see
p. 209.

31006929.00 10/2005 163


Services Overview

Time The time synchronization service provides distribution of a central time source to
Synchronization multiple devices on the network. Accurate time in all devices allows you to properly
synchronize events and manage the order of operations across a plant.
The time synchronization service should be used in any environment where timing
plays an important role in operations. It eliminates the need to manually set the time
on each network device. Also the accuracy can be as close as 1 ms in all devices,
a level of precision that cannot be achieved when you set the time manually. For
details, see p. 213.

Electronic Mail The electronic mail notification service allows service personnel to be notified of the
Notification plant status via email. The email may include process data, production reports,
alarms, events, and other information needed to evaluate plant status. A device with
the email service can automatically create short electronic mail messages that can
use predefined recipients, email addresses, and message subjects. The message
body can be dynamically modified to include current plant data and other text.
The electronic mail notification service is used whenever email notification is a
convenient communication option for informing someone of plant status, operation
reports, or maintenance requirements. In this case, you are conveniently notified
about maintenance, eliminating the need of regularly checking the equipment to
know when it needs to be serviced. Because of potential delays, this service is not
recommended for time-critical messages where short response times and quick
intervention are important. For details, see p. 222.

Embedded Embedded diagnostics can be used to execute diagnostic and maintenance


Diagnostics functions locally and remotely with a simple Internet browser. The embedded
(Standard Web diagnostics service uses an embedded Web server and a real-time data server. All
Services) data is presented in HTML (standard Web) format, which can be accessed from any
Internet browser.
This service is a convenient way to monitor the health of devices on the network and
operational and configuration information. Some automation devices support
remote configuration via Web pages. For example, Altivar drives provide access to
current speed information and allow acceleration rates to be configured through
their Website. For details, see p. 228.

Web/FactoryCast Using a simple Internet browser, the FactoryCast Web server provides all the
benefits of a standard embedded Web server service with the ability to control,
configure, and monitor plant data locally and remotely. Monitoring and control can
be enhanced with user-customized Web pages.
The Web/FactoryCast service is used to display and modify all plant variables in real
time. It lets you create hyperlinks to external Web servers that can include plant
documentation. The FactoryCast HMI Web incorporates an active Web server in the
device, provides better Web pages, supports more clients, and allows database
connectivity. For details, see p. 235.

164 31006929.00 10/2005


Services Overview

Transparent Ready Support Services and Protocols

SNMP The SNMP service is for managing networks. It is a network management system
that uses SNMP-compliant devices that are queried for information about
themselves and the network. SNMP is in almost every Ethernet device and should
be used as the basis for most network management systems. It can be used to
discover, monitor, and configure devices on a network. SNMP is normally used to
transfer device and network status, not plant status. For details, see p. 250.

FTP FTP is a method for exchanging files between devices over a network. Almost all
operating systems today include an FTP client or server functionality, making file
transfers from one device to the next an easy task. Many network devices implement
FTP as a standard method for transferring information to update its internal software
or firmware. For details, see p. 249.

TFTP TFTP is a simpler file transfer protocol than FTP, typically used for small file
transfers and by less complex devices. For details, see p. 252.

Telnet The Telnet protocol provides an interactive client-host type communication session
where you can type commands to view or manipulate a remote device. It is a text-
based user interface that is integrated with many devices today. Telnet may be used
to configure simple devices such as switches, routers, and serial-to-Ethernet
bridges. For details, see p. 253.

31006929.00 10/2005 165


Services Overview

Plant Data
Transfer
Services
Service Level, Response Data Exchange Examples Communications
Common Time Transfer Confirmation Topology
Use Frequency
I/O scanning field device 10 ms+ 1 ms – 5 s I/O scanner controlling central scanner
and PLC-to- periodic health status for Advantys I/O device exchanging
PLC data transfer and plant status data with one or
levels 2 and 3 fallback values. transfer more remote
Acknowledgmen between PLCs devices
t of each data
transfer with
retry mechanism
Modbus field devices, 50 ms+ occasional or acknowledgment confirmation of Client device-to-
messaging PLC-to-PLC, nonperiodic of each data process server device
and (exception transfer with completion
supervision reports) retry mechanism SCADA/HMI
levels 1, 2, communications
and 3
Global data PLC-to-PLC 20 ms+ 10 ms – 30 s none device status many publishing
level 2 periodic distribution to a devices-to-many
group of devices subscribing
devices
TCP open field device- 100 ms+ 100 ms+ or user programming a one client-to-one
to-PLC, PLC- exception configurable new server
to-PLC, PLC- based communications
to-supervisor protocol (e.g.,
levels 1, 2, Ethernet IP) to
and 3 communicate
with a third-
party device

166 31006929.00 10/2005


Services Overview

Remote Data
Transfer
Services
Service Level, Response Data Transfer Exchange Examples Communications
Common Time Frequency Confirmation Topology
Use
Electronic company minutes exception send maintenance one email client-to-
mail level report, up to confirmation, no reminders many recipients
notification level 1 several/min delivery production
FactoryCast confirmation reports
HMI email
FactoryCast company seconds 1 s – 30 min - sending one device-to-
HMI database level production database
connectivity level 1 reports and
data directly to
a database
OPC company 50 ms - exception confirmation SCADA server- central OPC server
level seconds report or per transaction to-SCADA with Modbus
level 1 periodic clients TCPIP to plant
plant devices, then OPC
monitoring communicates
system-to- plant data to other
plant devices SCADA or HMI
applications

31006929.00 10/2005 167


Services Overview

Diagnostic
Services
Service Recipient of Single- or Device or Plant Examples Communications
Diagnostics Multiple-device Diagnostics Topology
Diagnostics
Embedded people single internal device obtaining module several Web
diagnostics information health and browser clients
configuration
information
remotely with a
Web browser
FactoryCast people single or multiple plant information displaying plant several Web
operation status browser clients
with simple
customized Web
pages
FactoryCast people/ single or multiple plant information remotely viewing many Web browser
HMI machines plant status clients
efficiently with
advanced
customized Web
pages and
applications
SNMP machines single or multiple device network monitoring plant network
information network status by management
network system-to-many
management (HP SNMP devices
Open view)
Telnet people single device monitoring internal one Telnet client-to-
device status Telnet server in a
device

168 31006929.00 10/2005


Services Overview

Configuration
Services
Service Configuration of ... Configured by ... Example
FDR devices on the network an FDR server, providing automatically configuring an Ethernet
by an FDR server automatic configuration distributed I/O device’s operating
of client devices parameters after the device is
connected to the network
Embedded diagnostics a device connected to by a person configuring a variable speed drive’s
a user operating parameters with a Web
browser
SNMP a device connected to by a person or a network configuring network infrastructure
a user or a network management system component parameters with a
management system network management system
Telnet a device connected to by a person configuring the operating parameters
a user of a serial-to-Ethernet bridge network
with a direct connection

Checking Before selecting a service, make sure that the devices involved in the data transfer
Service support the desired service. If a device does not support the selected service, you
Compatibility need to make another service choice. Choosing another, perhaps less optimized,
service does not mean that the interaction between the devices cannot be achieved
but only that the use of the network and device resources may not be optimal. Once
you have selected the service, record it in the list of plant communications.

Combining Data Once all services are selected, interactions between like devices using the same
Transfers service may be combined. This may not be appropriate for all interactions (e.g., FTP
to transfer files for one purpose cannot be combined with a separate FTP transfer)
but may be beneficial for others. For example, using Modbus messaging to transfer
the status of 10 different items can be combined into a single transfer.

System Perform a system performance evaluation to be sure that the combination of all data
Evaluation transfers does not overload any service or device. An overload may result in lower
performance from a service or a complete failure of the data transfers.

Network Design Your network must either be designed to support the services you select or, if the
network is already in place, checked to verify that it can transport the required
services. Items to be checked include:
z networks, subnets (see p. 135) and addressing (see p. 133)
z bandwidth
z routers (see p. 142) and firewalls (see p. 154)
z RAS (see p. 148)

31006929.00 10/2005 169


Services Overview

3.2 I/O Scanning Service

At a Glance

Overview This section describes the I/O scanning service and how it is used to exchange data
between a central device and many remote devices.

What's in this This section contains the following topics:


Section?
Topic Page
I/O Scanning Service Description 171
I/O Scanner Operation 173
Repetition Rates 178
Some Common Fault Conditions 180
Response Times 181

170 31006929.00 10/2005


Services Overview

I/O Scanning Service Description

The I/O Scanning The I/O scanning service is a stand-alone communications task that exchanges
Service register data between one device running the service and many remote devices on
the network using Modbus TCP. The service requires only a simple configuration
operation in the I/O scanner device; no special programming is required in either the
I/O scanner device or the remote devices.
The remote device must be a Modbus TCP/IP server. Examples of remote devices
include:
z distributed I/O such as Advantys STB and Momentum
z intelligent devices such as Altivar drives and Sepam circuit monitors
z PLC devices such as Quantum and Premium
z Modbus serial devices such as Lt6 motor relays that are accessed through a
bridge
z any third-party device that is a Modbus TCP/IP server
The I/O scanner reads and writes data repetitively in a user-configurable period
ranging from 20 ms to 5 s. These read/write exchanges generate a load on the
network. For this reason, the I/O scanner is best suited for critical periodic
operations.
The I/O scanner is configured with a list of devices, data areas, and the rate at which
the register data exchange takes place. The scanner establishes a connection to the
remote device and exchanges data at the configured rate. The I/O scanner
maintains the connection to the remote device while handling any errors that occur.
For each remote device, a report is sent back to the application, indicating whether
the data is being transferred within the specified exchange rate.

I/O Scanner I/O scanner is an open system; you are not bound to any particular platform or to the
Characteristics same brand name. The I/O scanner system consists of two parts, the scanning
device and the remote device(s).
The scanning device has no control over the remote device. For example, if the
device fails, the I/O scanning device cannot issue its fallback state. The I/O scanning
device has the ability to issue what state its application value should have in the
case of lost communication to the remote device. There are no individual
configurable parameter screens available for the remote devices. You may be able
to do an initial write to the remote device to configure it, if this is supported by the
remote device. However, you need to disable that entry after the initial configuration
because you don’t want the write request to take place at every configured repetitive
rate.

31006929.00 10/2005 171


Services Overview

The I/O scanner device does not have any specific information about the remote
device other than its IP address. Due to this open system, you have no control over
the remote device’s response time. WIth other I/O systems, you are able to
determine the cyclic time at which the information is expected. With I/O scanner,
there is no set value as to when that register data exchange takes place; It may be
different for each remote device.
Some other characteristics of I/O scanner are:
z maximum transferable data block sizes of 100 words written and 125 words read
per entry
z maximum number of words read or written is 4,000
z multiple data blocks that can be exchanged with a single remote device
z a user-configurable repetitive data transfer rate (see p. 178) ranging from 1 ms to
5s
z fault reporting for each remote device
z a data exchange enable/disable for each remote device
Each entry in the I/O scanner configuration creates a new socket, including multiple
entries to the same remote device.

Remote Device z Modbus TCP/IP messaging support or Modbus serial slave if a serial-to-Ethernet
I/O Scanning bridge is used
Requirements z supports Modbus function codes 3 (read registers), 16 (write registers) and 23
(read/write registers), depending on data that is exchanged

Applications The I/O scanning service should be used when a central device needs to exchange
data (either read or write data) with a remote device at a fixed, reasonably fast rate.
Suitable applications include:
z fast repetitive communications
z applications that call for communication between one device and many remote
devices, where different data is exchanged with different remote devices
z applications that need to exchange data to more devices than is possible using
the existing COMM blocks
z automatic error handling
z controlling I/O devices
z devices that need to exchange the same data with many devices but that do not
support the global data service (see p. 202)
Because of the network and device load produced by its data exchanges, the I/O
scanning service should not be used for nonperiodic communications, event-
triggered actions, report generation, or event notification because of the network
and device load produced by its data exchanges. The Modbus messaging service
should be used in these situations.

172 31006929.00 10/2005


Services Overview

I/O Scanner Operation

Summary The I/O scanning service is implemented as a separate stand-alone


communications task in either an Ethernet communication module or in a CPU with
an embedded Ethernet port. After the service is configured, it receives a list of
devices to scan and memory zones where it can read and write in the remote
devices. It then begins to exchange data with each remote device. Each entry in the
I/O scanner configuration runs independently, even if multiple entries exchange data
with a single remote device.

2 3

1 a controller
2 an output device
3 a reading device

31006929.00 10/2005 173


Services Overview

Service Each independent information exchange is represented by a separate entry in the


Operation I/O scanner configuration table. The following flow chart illustrates how the I/O
scanner executes one information exchange.

PLC Run

An ARP is issued to receive the remote device


MAC address and open a TCP connection to the
remote device (SYN, SYN ACK, etc.)

Exchange N
N Read exchange?
is both read Write exchange?
and write?

Y Y
Y

Send Modbus FC23 Send Modbus FC3 Send Modbus FC16

Y Send FC3 in the first


FC23 not request then FC16
supported error? in the next request
1

Receive Modbus
response with data
Set Modbus health
bit to 1

Y
Time for next
exchange?
2

N End of CPU Y
Transfer data to
scan? CPU memory
3

174 31006929.00 10/2005


Services Overview

1 If the remote device does not support FC23, the I/O scanner uses FC3 and FC16 to
execute the data transfer. When this happens, the read operation is performed in the first
exchange and the write operation is performed in the next exchange. The total read/write
operation takes twice as long as the time required for the FC23 operation to execute.
2 The timing of this loop is affected by the repetition rate.
3 All I/O scanner entries exchange data with the CPU at the end of the scan.

Write Operations The I/O scanning service writes data from a memory zone in the I/O scanner device
to a memory zone in the remote device. Depending on the I/O scanner device, the
memory holding the values to be sent may be 16-bit registers (%MW or 4x) or blocks
of bits (%M or 0x). The data is always written to 16-bit registers in the remote
devices.

31006929.00 10/2005 175


Services Overview

Read Operations The I/O scanner device reads data from memory zones in the remote devices to
gather field device or input status. The remote devices always store this status data
in 16-bit registers. After the data is read, it can be stored in 16-bit registers (%MW
or 4x) or blocks of bits (%M or 0x) in the I/O scanner device’s memory.

Error Handling If there is a loss of communication with one or more remote devices, the I/O scanner
applies configured fallback values to the corresponding I/O scanner memory areas.
If a communication failure occurs, the I/O scanner does not control remote device
operation. These devices handle their own fallback states.

Enable/Disable Enable/disable allows you to start and stop the data exchange between a remote
device and the I/O scanner device. Four double-word registers are designated to the
128 entries in the I/O scanner configuration. Each I/O scanner entry is controlled by
a single bit. When a control bit is turned on, the data exchange is disabled and the
health bit is turned off after the time-out period expires. At this point, the TCP socket
to the remote device is closed.
This feature can be used to limit the number of concurrent sockets to a remote
device. For example, in a Modbus Ethernet-to-serial bridge, which supports a limited
number of concurrent TCP sockets, turning on the control bit that was turned off
opens a new socket and enables the I/O scanning exchange to resume. However,
the health bit remains off until the first data exchange with the remote device is
completed successfully.

176 31006929.00 10/2005


Services Overview

Health Bit The health bit indicates whether or not a data exchange has been successful. If a
Operation fault occurs but is resolved within the health time-out period, the bit stays on. The
health bit turns off if the data exchange is not complete/resolved successfully in the
health time-out period. The health timeout should be longer than the repetitive rate.
For a Quantum NOE Ethernet module, the health timeout must also be longer than
the CPU scan time, due to the link with the CPU scan cycles.

Diagnostic Word A diagnostic word is provided for each I/O scanner exchange. This word provides
Support additional diagnostic information on fault codes. Implementation is platform-specific.

TCP Socket The I/O scanner opens a single TCP socket for each configured data exchange. A
Usage device configured for multiple exchanges has multiple sockets. The I/O scanner
uses source TCP port numbers in the range of 3000 - 4000.

31006929.00 10/2005 177


Services Overview

Repetition Rates

Summary The repetition rate is the rate at which you configure the I/O scanning service to
exchange data.

Effective The effective repetition rate is the actual rate at which data is polled from the remote
Repetition Rates devices. This rate may differ from the configured repetition rate on different PLC
platforms and option modules. The effective rate is determined by the way the I/O
scanning service is installed. The effective repetition rate is limited by:
z the I/O scanning service timer
z remote device response times
z CPU scan time and data transfer time
A new request cannot be issued until after the remote device responds to the
previous request.

Repetition Rates/ Repetition rates are limited by the I/O scanner device. A Quantum NOE Ethernet
Internal Clocks communications module has a 17 ms clock rate. A Premium ETY Ethernet
communications module or a Unity CoPro CPU with an embedded Ethernet port
(Quantum or Premium) has a 10 ms clock rate. The clock rate limits the time
resolution in which an I/O scanner request is sent to a remote device.
When the configured repetition rate is 0 ms, the system sends requests as fast as
possible. In a Quantum NOE system, requests are sent after the data is transferred
at each end of scan (EOS). A Premium or Copro system sends requests as
frequently as a remote device can respond to the previous request.
When the repetition rate is configured for a value greater than 0 ms, the rate is
rounded up to a multiple of 10 ms on a Premium or a Unity Copro system or 17 ms
on a Quantum system. For example, a Premium system with a configured repetition
rate of 35 ms sends a request every 40 ms (providing the end device has finished
responding). A Quantum NOE system configured for a 25 ms repetition rate sends
requests either every 34 ms or once per PLC scan, whichever is greater.

178 31006929.00 10/2005


Services Overview

A Comparative The following chart compares effective repetition rates for Quantum, Premium, and
Example Unity CoPro systems over multiple scans:

Premium/ETY Unity CoPro or ETY


Quantum/NOE (running PL7 or Unity 1.0) (running Unity 2.0)
CPU NOE Remote Remote CPU CoPro Remote
CPU ETY
Device Device Device

Input Input Input


Time

EOS EOS EOS

CPU logic CPU logic

EOS EOS EOS

CPU Output
logic
EOS EOS

Output Output

z A Quantum PLC with an NOE Ethernet communications module exchanges data


with a remote device once per CPU scan. This limits the effective repetition rate
to a value greater than one PLC scan cycle.
z A Premium PLC with an ETY Ethernet communications module (in a PL7 or Unity
1.0 environment) exchanges data at the configured repetition rate (assuming that
the device can answer within this time period) and exchanges the data with the
CPU on each EOS cycle. The output cycle requires an additional CPU scan to
transfer the data to the ETY module.
z A Unity CoPro CPU with an embedded Ethernet port or a Premium CPU with an
ETY module in a Unity environment transfers data at the configured repetition
rate (assuming that the device is able to answer within this time period).

Note: Data values may be exchanged with the remote device multiple times per
CPU scan. The last value read from the remote device is sent to the CPU at the
next EOS, and the value written to the remote device is the value from the CPU at
the previous EOS.

31006929.00 10/2005 179


Services Overview

Some Common Fault Conditions

Condition Cause Response


A device is not The I/O scanner device issuing the ARP
found on the requests attempts to locate the remote
network. device. Requests are sent every 30 s.
Socket overload: This error is commonly If the remote device is unable to open the
a remote device seen on bridges with many TCP socket, the I/O scanner device attempts
refuses to accept entries in the I/O scanner to open a socket every second.
a TCP socket or in low-end devices that If the problem persists, you may be able to
connection. support a limited number correct it by using the enable/disable feature
of sockets. It occurs as an (see p. 176). To free up sockets, limit the
I/O scanner health bit number of I/O scanner data exchanges
goes off at random operating to the same IP address.
intervals.
A remote device If you are using pre-Unity When this failure occurs, the device sends
refuses FC23. 2.0 I/O scanner systems back a Modbus exception with an error code
or end devices that do not corresponding to function code not
send back the correct supported. The I/O scanner falls back to a
error code, the I/O combination of FC3 andFC16.
scanner fails. It continues
to send FC23 and
continues to fail.
A request or Normal TCP socket transmissions occur on
response packet the first retransmission by the I/O scanner
is lost, or the device; after three retransmissions, the
socket is socket is reset and a new ARP is issued.
corrupted and The loss of an Ethernet packet can switch off
unable to transfer the health bit unless there is sufficient time to
data. reissue the packet and receive an answer
before the health time-out period has
expired.
The retry time for a lost or corrupted packet
varies with different versions of the product.
Early versions retried at 800 ms, 600 ms,
1.5 s, and 3 s. Newer versions base their
retries on the previous response times, but in
a good system approximately 50 ms,
800 ms, and 1.5 s can be achieved.

180 31006929.00 10/2005


Services Overview

Response Times

The I/O scanner system response time depends on:


z the CPU scan time
z the time for the scanned device to respond to the request
z the activation time for the scanned device for a new input or output

I/O Scanner
Ethernet TCP/IP

Response time
Hub

Input Device

Output Device

The following chart illustrates the performance of a Quantum I/O scanner, round trip
from the field input to the CPU and back to the output.

Delay sending Delay in field


Delay in field device 1 rep rate
new requests device

New field Input available in End of CPU New request New request Response Start of next CPU
input communications scan sent at field back at PLC scan response
adapter device taken into CPI

Delay sending Delay in field


1 CPU scan 1 rep rate new requests device

New input New output End of CPU New request New request Output at I/O
available ready scan sent at field device
CPU communications
adapter

31006929.00 10/2005 181


Services Overview

For a configured repetition rate of 0 ms, the formula for the worst-case time is:
z total time = Tmod + 1 CPU scan + [if (T1 > 1 CPU scan) then (T1 + 1 CPU scan)
Else (1 CPU scan)] + 1 CPU scan + 0.3 ms * no Requests + Tmod
z T1 = 0.3 ms * number of requests + device response time
The following chart illustrates a Premium I/O scanner’s performance, round-trip from
the field input to the CPU and back to the output.

Delay in Field 1 Rep Rate Delay Sending Delay in Field


Device New Requests Device

New Field Input Available in New Request New Request Response Start of next CPU
Input Communications Sent at Field back at PLC Scan Response
Adapter Device taken into CPI

Possible 1 scan Delay Sending Delay in Field


1CPU Scan Delay 1 Rep Rate Device
New Requests

New Input New Output End of CPU Output in New Request New Request Output at I/O
Available Ready Scan ETY Module Sent at Field Device
CPU Communications
Adapter

For a repetition rate of 0 ms, the formula for the worst-case time is:
z total time = Tmod + T1 + 1 CPU scan + 1 CPU scan + 1 CPU scan (for ETY
only) + 0.3 ms *number of requests + Tmod
z T1 = 0.3 ms * number of requests + device response time
The following chart illustrates the typical I/O scanner response time from a field input
on a scanned device to a field output activated at another scanned device due to
PLC logic triggered from the first input. CPU scan time is ~50 ms. The scanned
device response time is ~10 ms.
PLC System Number of Device Scanned
1 16 32
Quantum or Premium with NOE/ETY (non-Unity) 110 ms 115 ms 125 ms
Quantum or Premium Unity CPU with embedded 100 ms 105 ms 115 ms
Ethernet port

182 31006929.00 10/2005


Services Overview

3.3 Modbus Messaging

At a Glance

Overview This section describes the Modbus messaging service. This service handles the
Modbus protocol and enables data transfers between network devices.

What's in this This section contains the following topics:


Section?
Topic Page
Modbus Messaging Service Description 184
Devices that Support Ethernet Modbus Services 189
Modbus Client Operations in Quantum Systems 190
Modbus Client Operations in Premium Systems 191
Modbus Client Operations in Momentum Systems 193
Modbus Server Operations in Quantum Systems 194
Modbus Server Operations in Premium Systems 197
Modbus Server Operations in Momentum Systems 199
Modbus Servers and Socket Limits 200
Modbus Messaging Retry Times and Time-outs 201

31006929.00 10/2005 183


Services Overview

Modbus Messaging Service Description

The Modbus The Modbus messaging service handles the transfer of data or commands between
Messaging two devices. One device is the client and the other is the server. The client initiates
Services the request and the server responds to the request. These services use the Modbus
protocol (or Modbus over TCP/IP in Ethernet applications) to support the data
transfer between devices.

1 SCADA and HMI data requests


2 PLC data transfer
3 device data gathering

Modbus Modbus has been the industrial communication standard since 1979. It is now
Communication combined with Ethernet TCP/IP to support Transparent Ready solutions.
Standard Modbus over TCP/IP is a completely open Ethernet protocol. The development of a
connection to Modbus TCP/IP requires no proprietary component or license
purchase. The protocol may be easily combined with any device that supports a
standard TCP/IP communication stack. Specifications can be obtained free of
charge from www.modbus.org.

184 31006929.00 10/2005


Services Overview

Modbus TCP The Modbus application layer is very simple and universally recognized. Thousands
Device of manufacturers are already implementing this protocol. Many have already
Implementation developed Modbus TCP/IP connections, and many products are currently available.
The simplicity of Modbus TCP/IP enables any small field device, such as an I/O
module, to communicate over Ethernet without a powerful microprocessor or a large
amount of internal memory.

Modbus The same application protocol is used for Modbus serial link, Modbus Plus, and
TCP/IP Modbus TCP. This interface routes messages from one network to another without
changing the protocol. Because Modbus is implemented above the TCP/IP layer,
you can also benefit from the IP routing, which enables devices located anywhere
in the world to communicate regardless of the distance between them.
Schneider offers an entire range of gateways for interconnecting a Modbus TCP/IP
network to already existing Modbus Plus or Modbus serial link networks. For further
details, consult a Schneider Electric regional sales office. The IANA institute has
assigned to Schneider port TCP 502, which is reserved for the Modbus protocol.

Modbus The transfer of information between a Modbus client and server is initiated when the
Messaging client sends a request to the server to transfer information, to execute a command,
Summary or to perform one of many other possible functions.
After the server receives the request, it executes the command or retrieves the
required data from its memory. The server then responds to the client by either
acknowledging that the command is complete or providing the requested data.
The system response time is limited by two main factors, the time required for the
client to send the request/receive the response and the ability of the server to
answer within a specific amount of time.

3
Modbus Server

1
Modbus Client

2 4

1 retrieved data
2 client request
3 server response
4 data retrieval
A device may implement a Modbus client service, a Modbus server service, or both,
depending on the requirements of the device. A client is able to initiate Modbus
messaging requests to one or more servers. The server responds to requests
received from one or more clients.

31006929.00 10/2005 185


Services Overview

A typical HMI or SCADA application implements a client service to initiate


communications with PLCs and other devices for information gathering. An I/O
device implements a server service so that other devices can read and write its I/O
values. Because the device does not need to initiate communications, it does not
implement a client service.
A PLC implements both client and server services so that it can initiate
communications to other PLCs and I/O devices and respond to requests from other
PLCs, SCADA, HMIs and other devices.

Client Client

Client Server Server

Server
Server

What a Modbus A device that implements the Modbus client service can initiate Modbus messaging
Client Service requests to another device that implements a Modbus server. These requests allow
Provides the client to retrieve data from or send commands to the remote device.

What a Modbus A device that implements the Modbus server service can respond to requests from
Server Service any Modbus client. The Modbus server service allows a device to make all its
Provides internal and I/O data available to remote devices for both reading and control.

186 31006929.00 10/2005


Services Overview

Modbus The Modbus protocol is a collection of function codes, where each code defines a
Function Codes specific action for the server to perform. The ability of a device to perform read and
write functions is determined by the Modbus function codes that are implemented by
the server.
The Modbus protocol is based on five memory areas inside the device.
Memory Area Description
0x or %M Memory bits or output bits
1x or %I Input bits
3x or %IW Input words
4x or %MW Memory words or output words
6x Extended memory area

In addition to the function codes for reading and writing data within these areas,
there are codes for statistics, programming, device identification, and exception
responses. The Modbus server can make data available based on the following
limits:
z Read: 125 words or registers
z Write: 100 words or registers

When to Use the A Modbus client should be used when data needs to be exchanged between two
Client devices at irregular or infrequent intervals such as when an event occurs. The client
allows a request to be triggered by the application code (in the case of a PLC or
SCADA) or by an internal timer (for a SCADA or an HMI). This allows you to initiate
communications only when required and provides a more efficient use of resources.
If the data must be exchanged at a short fixed rate, the I/O scanner service
(see p. 170) should be used instead (if that service is supported by the client).

31006929.00 10/2005 187


Services Overview

When to Use the The Modbus server is accessed by either a Modbus client or an I/O scanner service
Server and should be used to transfer plant information, commands, or other required data.
The Modbus server provides real-time data transfer or access to data reports that
are stored in its memory. The Modbus server answers any Modbus requests it
receives. No additional configuration is necessary.
Any device that needs to exchange plant status, commands or data with other
devices should implement a Modbus server. A device that implements the server
can respond to requests sent from Modbus clients and make its internal I/O and data
available to remote devices for reading and control. The device may be an I/O
module, a drive, a power meter, a circuit breaker, a motor starter, or a PLC.
I/O modules are good examples of devices that implement a Modbus server service.
As servers, input modules let other control devices read values from them, and
output modules let control devices write values to them.
A PLC system implements both client and server services. The client service
enables the PLC to communicate with other PLCs and I/O modules; the server
service enables it to respond to requests from other PLCs, SCADA, HMIs and other
devices. Devices that do not need to respond to data transfer requests should not
need to implement a server service.

188 31006929.00 10/2005


Services Overview

Devices that Support Ethernet Modbus Services

Device Modbus Client Modbus Server


Unity Pro Quantum 140CPU65150 X X
140CPU65160 X X
140NOE77101 X X
140NOE77111 X X
140NWM10000 X X
Unity Pro Premium TSXP571634M X X
TSXP572634M X X
TSXP573634M X X
TSXP574634M X X
TSXP575634M X X
TSXETY4103 X X
TSXETY110WS X X
TSXETY5103 X X
TSXWMY100 X X
TSX Micro TSXETZ410 X X
TSXETZ510 X X
Momentum 171CCC96020 X X
171CCC96030 X X
171CCC98020 X X
171CCC98030 X X
171ENT11001 - X
171ENT11002 - X
Twido 499TWD01100 X 1 X1
Advantys STB STBNIP2212 - X
Altivar ATV38/58 VW3A58310 - X
Power Logic EGX200 - X1
Gateways/Bridges
EGX400 - X1
ConneXium Cabling 174CEV30020 X1 X1
systems
174CEV20030 X1 X1
174CEV20040 X1 X1
1 Device receives and sends Modbus messages as a gateway.

31006929.00 10/2005 189


Services Overview

Modbus Client Operations in Quantum Systems

Limits With Concept or Proworx programming software, an application on a Quantum


system can initiate Modbus client communications using the following Modbus client
blocks:
z MSTR
z READ_REG
z WRITE_REG
z C_READ_REG
z C_WRITE_REG
The Quantum PLC reads and writes to the 4x or %MW data area only. Up to 16
concurrent Modbus client blocks can be triggered by an NOE Ethernet
communications module. If additional blocks are triggered, they are buffered until
one or more active blocks complete their operations.

Quantum A Quantum Modbus client operates as follows:


Modbus Client
Sequence Event
Operations
1 The application triggers the Modbus client block.
2 The request is immediately sent to the NOE Ethernet communications module.
3 The NOE module checks if a TCP socket is connected to the destination device.
4 If a TCP socket is not connected, the NOE initializes a TCP socket and connects
it to the destination device.
5 The NOE module sends the Modbus request.
6 The message travels across the network, and a network delay occurs.
7 The Modbus server receives the message.
8 The Modbus server responds to the request.
9 The message travels across the network, and a network delay occurs.
10 The NOE receives the response.
11 The next time the Modbus client block is reached in the code, the response is
gathered from the NOE module and any new data is made available to the user
application.
12 The NOE leaves the TCP socket open for future use.

Note: The NOE module keeps the TCP socket open until the other end closes it or the NOE
module reaches its TCP socket limit. If one of these events occurs, the NOE closes any
socket that has no outstanding requests on it.
Newer NOE modules can send multiple requests down a single TCP socket. Some older
NOE modules may support only a single TCP socket per request and close the TCP socket
after each exchange is completed.

190 31006929.00 10/2005


Services Overview

Modbus Client Operations in Premium Systems

Limits Using Unity Pro or PL7 programming software, an application on a Premium system
can initiate Modbus client communications using the following Modbus client blocks:
z WRITE_VAR
z READ_VAR
z SEND_REQ
z DATA_EXCH
The Premium PLC limits the number of Modbus client communication blocks that
can be triggered concurrently (based on CPU type). This limit applies to the total
number of Modbus client request blocks per CPU and includes blocks triggered for
the following messaging services:
z Modbus TCP/IP client
z Fipway
z Modbus serial
z Unitelway
z Ethway
If additional client blocks are triggered, an error message is returned to the
application program.
Modbus client requests are limited as follows:
Client: family of Ethernet Communications Number of Requests
processors Mechanism
Unity Pro v2.0 CoPro ETY module or embedded port* 80*
Unity level 2 P57-xx ETY module 32
Unity level 4 TSX574-xx ETY module 64
PL7 level 2 TSX572-xx ETY module 32
PL7 level 4 TSX574-xx ETY module 64
* When the Unity 2.0 CoPro uses an embedded port, it can send 80 requests, but it can accept
only eight replies per scan.

31006929.00 10/2005 191


Services Overview

Premium The Modbus client operates as follows:


Modbus Client
Sequence Event
Operations
1 The application triggers the Modbus client block.
2 The processor holds the request until the end of the current CPU scan.
3 The ETY module checks if a TCP socket is connected to the destination
device.
4 If a TCP socket is not connected, the ETY module initializes a TCP socket and
connects it to the destination device.
5 The ETY module sends the Modbus request.
6 The message travels across the network and a network delay occurs.
7 The Modbus server receives the message.
8 The Modbus server responds to the request.
9 The response travels across the network and a network delay occurs.
10 The ETY module receives the response.
11 The response is passed back to the CPU at the next phase (beginning of the
next CPU scan).
12 The next time the Modbus client block is reached in the code the response and
any new data is available to the user application.
13 The ETY leaves the TCP socket open for future use.

Note: The ETY module leaves the TCP socket open until the other end closes it or
the ETY module reaches its limit of TCP sockets. At that point, the ETY module
closes any socket that has no outstanding requests on it. The ETY module can
send multiple requests down a single socket.

192 31006929.00 10/2005


Services Overview

Modbus Client Operations in Momentum Systems

Limits Using Unity Pro, Concept or Proworx programming software, an application running
on a Momentum system can initiate Modbus client communications using the
following Modbus client blocks:
z MSTR
z READ_REG
z WRITE_REG
z C_READ_REG
z C_WRITE_REG
The Momentum PLC reads and writes to 4x or %MW data register areas only. Up to
16 concurrent Modbus client blocks can be triggered. If an additional block is
triggered, it returns an error code to the application.

Momentum A Momentum Modbus client operates as follows:


Modbus Client
Sequence Event
Operations
1 The application triggers a Modbus client block.
2 The processor holds the request until the end of the current CPU scan.
3 At the end of the current CPU scan, the Momentum PLC begins to open a
socket to the destination device and a SYN message is sent.
4 The Modbus server responds with a SYN ACK.
5 At the end of the next CPU scan, the Momentum PLC receives the SYN ACK
and opens the socket.
6 As soon as the socket is open, the Momentum sends the Modbus request.
7 The message travels across the network and a network delay occurs.
8 The Modbus server receives the message.
9 The Modbus server responds to the request.
10 The response travels across the network and a network delay occurs.
11 The Momentum receives the response.
12 At the end of the next CPU scan, the response is read into the Momentum
and the socket is closed.
13 The next time the Modbus client block is reached in the code, the response
and any new data is made available to the application.

31006929.00 10/2005 193


Services Overview

Modbus Server Operations in Quantum Systems

Quantum A Modbus server is implemented in either an NOE Ethernet communications module


Implementation or an Ethernet port embedded in the Quantum PLC. The data to be accessed by the
Modbus server is held in the PLC CPU memory. The interface between the NOE
module or the embedded port and the CPU defines the Modbus server operation.

Quantum The Modbus server for Quantum systems operates as follows:


Modbus Server
Sequence Event
Operation
1 A Modbus client establishes a TCP socket to the NOE module or the
embedded Ethernet port.
2 The Modbus client sends a request along the TCP socket.
3 The NOE module or the embedded Ethernet port receives the request and may
acknowledge it.
4 The request is placed in the queue inside the module to be passed to the CPU.
The CPU lets the NOE module/embedded Ethernet port access its memory at
the end of the next CPU scan.
5 In the case of the NOE module, the NOE passes the request from the queue
to the CPU in one of two possible ways:
z If the NOE requests a Modbus register read/write (FC3, FC16 or FC23), it
reads the PLC’s memory by using request type 1.
z If the NOE module requests any other Modbus function code, it passes the
entire request to the CPU for processing type 2.
In the case of the embedded Ethernet port, the request from the queue is
passed to the CPU.
6 The NOE module/embedded Ethernet port immediately receives an answer to
any request (except programming requests) sent to the CPU.
7 The NOE module/embedded Ethernet port sends the response back to the
Modbus client.
8 The TCP socket is left open.

z Path type 1 requests give the NOE module direct memory access.
z Path type 2 requests pass the entire Modbus message to the CPU.

194 31006929.00 10/2005


Services Overview

Depending on the system, the NOE module or the embedded port may respond to
a different number of requests at the end of each CPU scan.The following diagram
shows the five backplane paths between the NOE module and the CPU:

4 Backplane Type 1 Paths


(FC3,FC16 and FC23)

CPU NOE
Module

1 Backplane Type 2 Path


(All other FCs)

Concept/ Each time the NOE module is serviced (once per CPU scan), it sends one request
Proworx Modbus across each of the five paths. The type 1 backplane paths allow direct memory
Server Operation access to the CPU memory. The NOE module uses these paths to read/write 4x
registers directly on the CPU memory for Modbus FC3, FC16, and FC23.
The type 2 backplane path allows the Modbus message to be passed to the CPU.
The NOE uses this path to pass all other function code requests to the CPU; the
CPU handles the Modbus message. Function code examples include unlocated
variables (FC42), PLC programming software (FC125, FC43), and read/write 0x, 1x,
3x requests. The type 2 path is not used to answer requests for 4x registers (FC3,
FC16, and FC23).
The number of backplane paths limits the Modbus server performance. For
example, if 10 FC3 and 5 FC42 Modbus requests are queued inside the NOE
module, a total of 5 CPU scans is needed to compete the transfer. During the first 3
CPU scans, 10 FC3 (4 per CPU scan) and 3 FC42 (1 per CPU scan) requests are
transferred, but an additional 2 CPU scans are needed to transfer the remaining 2
FC42 requests.

31006929.00 10/2005 195


Services Overview

Unity Modbus In a Unity Modbus server system, path types and uses remain the same, but
Server performance is improved 2 to 4 times over the Concept system.
Performance)
8 Backplane Type 1 Paths
(FC3,FC16 and FC23)

CPU NOE
Module

4 Backplane Type 2 Path


(All other FCs)

The Unity 2.0 NOE/backplane supports:


z eight type 1 path requests served per CPU scan
z four type 2 path requests served per CPU scan (up to a limit of 20 requests)

Note: To see the improvement, you may need to adjust the SCADA package to
make sure enough requests are being sent to the PLC.

196 31006929.00 10/2005


Services Overview

Modbus Server Operations in Premium Systems

Premium Premium PLC systems implement a Modbus server in the PLC’s CPU. ETY cards
Implementation or embedded ports pass Modbus requests to the CPU for processing. The CPU
limits the number of Modbus requests that the server can answer per CPU scan.
This limit includes requests from:
z Modbus TCP/IP
z Fipway
z Modbus serial
z Unitelway
z Ethway

A Modbus busy exception occurs when the CPU receives more requests than it can
handle during a CPU scan. If this happens, an exception response is sent back to
the Modbus client that sent the request.
The following table shows the number of requests processed per CPU scan for
different Premium PLC systems.
PLC Ethernet Communications Responses
Mechanism per Scan
Pre-Unity v2.0 Unity Pro v2.0 CoPro ETY module* or embedded 20 (estimated)
port**
Unity level 2 P57-xx ETY module* 20
Unity level 4 TSX 574-xx ETY module* 20
PL7 level 2 TSX572-xx ETY module* 8
PL7 level 4 TSX574-xx ETY module* 16
Unity Pro v2.0 Unity CoPro embedded port** 16
ETY module* 20
Unity TSX P57304M ETY module* 12
* The ETY module is limited to 400 transactions/s for all modules.
** The embedded Ethernet port is limited to 500 transactions/s on the Unity CoPro systems.

31006929.00 10/2005 197


Services Overview

Premium The response process for Premium systems functions as follows:


Modbus Server
Sequence Event
Operation
1 The Modbus client establishes a TCP socket to the ETY module or embedded
Ethernet port.
2 The Modbus client sends a request along the TCP socket.
3 The ETY module or embedded Ethernet port receives the request and may
acknowledge it.
4 The request is placed in the ETY module/embedded Ethernet port queue.
5 At the beginning of the next CPU scan, the ETY module/embedded Ethernet
port passes requests to the CPU. At this time, all communication modules pass
requests to the CPU, including Fipway, Ethway, and SCP serial modules.
6 The CPU answers as many requests as possible (the limit is determined by the
CPU).
7 If more requests are received than can be answered, the CPU responds with
a Modbus busy exception to the ETY module/embedded Ethernet port, which
sends the exception response back to the clients.
8 The ETY module/embedded Ethernet port receives responses to all answered
requests and sends responses back to the clients.
9 The TCP socket is left open.

Premium The Premium response time is the time period between receiving a request and
Response Times starting the next CPU scan.

198 31006929.00 10/2005


Services Overview

Modbus Server Operations in Momentum Systems

Momentum The Momentum PLC implements a Modbus server as part of the main CPU. There
Implementation is no limit on the number of Modbus requests that can be answered by a Momentum
CPU.

Momentum The Modbus server for Momentum CPU operates as follows:


Modbus Server
Sequence Event
Operation
1 The Modbus client establishes a TCP socket to the Momentum CPU, which
may take several CPU scans.
2 On the first scan, a SYN is received and is sent back to the client at the end
of the scan.
3 The Modbus client sends a request along the TCP socket.
4 The CPU receives the request.
5 The request is answered at the end of the next CPU scan.

31006929.00 10/2005 199


Services Overview

Modbus Servers and Socket Limits

Simple Modbus
Servers
Product Response Time
Advantys 4.5 ms
ATV58 Drive 30 ms
Momentum ENT1100/02 1 ms (additional 4.5 ms to include I/O base)
Momentum ENT1101 5-9 ms

Note: The response times above do not include I/O reaction times.

Modbus Server
TCP Socket
Product TCP Socket Limit
Limits
Quantum NOE modules NOE77100/10 32
Quantum NOE modules NOE77101/11 64 (all Ethernet services combined)
Premium ETY410/510 32 (all Ethernet services combined)
Premium ETY4102/5102 64 (all Ethernet services combined)
Momentum CPU 12
Momentum ENT1100/02 4
Momentum ENT1101 4

200 31006929.00 10/2005


Services Overview

Modbus Messaging Retry Times and Time-outs

Modbus Client The Modbus client service supports retry times at the application layer (see p. 128).
The system also performs TCP retries to make sure that Modbus requests and
responses are being delivered. Modbus retry times and time-outs are device-
dependent:
Platform TCP Retry Times Modbus Client Time-outs
Quantum 5, 25, and 45 s 30 s, no retries
Premium 5, 25, and 45 s user-defined (in the communication block) with no
retries

Modbus Server The Modbus server service does not support retry times at the applications layer.
The system implements TCP retries to make sure Modbus requests and responses
are delivered. The retry times are device-dependent:
Platform TCP Retry Times
Unity 2.0 Quantum 50 ms, 800 ms and 1.5 s
Unity 2.0 Premium 50 ms, 800 ms and 1.5 s
Quantum 800 ms and 1.5 s
Premium 800 ms and 1.5 s

31006929.00 10/2005 201


Services Overview

3.4 Global Data Service

At a Glance

Overview The global data service supports the transfer of real-time information from a source
device to any other device on the network that subscribes to that information.

What's in this This section contains the following topics:


Section?
Topic Page
The Global Data Service 203
Global Data Considerations 207

202 31006929.00 10/2005


Services Overview

The Global Data Service

Summary The global data service on Ethernet provides the ability for one device to publish
real-time information to the network. Any device connected to the network can
choose to receive this information. Devices that need to exchange information are
arranged in distribution groups. Each device in a group can choose to publish a
block of data to the entire group and can select blocks of published data that it wants
to subscribe to (receive).

S S

P publisher
S subscribers

Global Data The global data service is implemented using the standard network data distribution
Standards service (NDDS). NDDS uses the real-time publish subscribe (RTPS) protocol as
defined by Real Time Innovations (RTI). This has been adopted as a standard by
the Object Management group (OMG), the same group responsible for the COBRA
standard. The global data service is responsible for the mechanics of distributing
data over an IP network by using multicast technology.
The combination of the above services distributes the global data using UDP/IP
multicasting technology.

31006929.00 10/2005 203


Services Overview

Publisher and The global data operation involves two types of participants with one or more
Subscriber publishers and one or more subscribers. A publisher is responsible for putting data
Operations on the network. The publisher takes a collection of local data and sends it to the
distribution group at a rate configured in the publisher device.
The distribution group is a logic group of subscribing devices, possibly spanning
across more than one network. You can make a subscribing device part of a
distribution group by assigning it a unique multicast IP address. This IP address is
a separate, additional IP address from the normal IP address used for Modbus, I/O
scanner, Web, etc. All devices within the distribution group use this unique multicast
IP address (see p. 138).
The subscriber receives a copy of all data published to the distribution group, selects
only the blocks of data that it subscribes to, and passes that data to the user
application.
Error handling must be done on the subscriber side because the publisher does not
send the data to individual subscribers. The publisher puts data on the network; it
has no control over the subscribers and does not receive feedback when a
subscriber receives data. The subscriber is responsible for monitoring the time
between receiving new data from each publisher. If the time between two
successive updates of data from an individual publisher is longer than the configured
health time-out, the service informs the user application on the subscriber device of
an error. The subscriber must perform error monitoring and take action if the data is
not received.
This is different from Modbus communications, where a command is sent to another
device to perform an action. In the case of Modbus, the device sending the
command must know if it is successful. With global data, the publisher just makes
the information available and leaves it to the subscriber to receive and act on the
information.
If for any reason a subscribing device does not receive a particular copy of newly
published data to which it subscribes, the device receives an update of that data in
the next publication cycle. The global data service publishes status information at a
fast regular rate, and the next subsequent publication provides the current status of
the subscription data, rather than a retry of the previous data.

204 31006929.00 10/2005


Services Overview

The following figure shows a distribution group comprising four devices (D1 through
D4). Two of these devices are publishers (D1 and D2) and three are subscribers
(D2, D3 and D4). Device 2 is both a publisher and a subscriber. The data flow
illustrates how devices 1, 2 and 3 all subscribe to data published by device 1 and
device 4 subscribes to data published by both devices 1 and 2.

Subscribe Subscribe

Publish

Publish Subscribe

Limits The global data service has the following communication limitations:
z A distribution group may contain up to 64 members; each device that is a member
can be a publisher, subscriber or both.
z The current restriction is that each Ethernet module can be a member of only one
group. Therefore, in order for a system to be a member of multiple groups, there
must be multiple Ethernet communications modules in that system.
z A publisher can publish a single block of data up to 512 words long.
z A subscriber can receive any number of published data blocks from the group,
although some PLCs restrict the total amount of data received by the service.

31006929.00 10/2005 205


Services Overview

When to Use Global data is used when a single device wants to make the information it contains
Global Data available to multiple devices within 10 ms to 30 s. This service is used for publishing
device data and plant status from one device to many others. Global data is not
recommended for issuing commands, because the publisher does not send the data
to an individual device and data transfer is not acknowledged.
The system is designed for a device to publish its status and for other devices to
react to that status. For example, a drive publishes its speed and all other drives in
the system adapt their speeds to match it.

Global Data The following devices implement global data with a maximum publishing of 512
Devices words and a maximum subscription of 2048 words:
z ETY4102/5102 and ETY4013/5103
z Premium and Quantum CoPro Ethernet port
z NOE77101/11

206 31006929.00 10/2005


Services Overview

Global Data Considerations

Multicast The global data service is implemented using multicast technology (see p. 138).
Technology Multicast is different from broadcast and unicast technologies. Broadcast sends
information from one device to all devices on the network. Unicast sends data from
one device to another. Multicast allows a device to send a single block (packet) of
data to a predefined distribution group (see p. 204).
Published data that is sent to a specific multicast IP address is forwarded by
switches and routers only to devices in the distribution group that subscribe to that
multicast IP address. Multicast filtering (see p. 139) restricts the data from going to
every device on the network and allows the distribution group to operate efficiently
on an Ethernet network without disturbing other devices on the network.

Distribution Group
IP multicast: 255 255 255 251

Data distribution

Intranet
Control

2.n stations

Data distribution

Distribution Group
IP multicast: 255 255 255 250

The global data service currently implements GMRP to set up multicast filtering.
GMRP is the protocol that the end device uses to notify switches and routers that it
wants to receive data from a particular multicast IP address. That IP address
belongs exclusively to a distribution group.

Application The publication of data is synchronized at the start of the CPU cycle after the
Synchronization configured publication rate has been reached. Subscribed data is recopied in the
application memory of the subscribing device at the end of the CPU cycle after the
data is received.

31006929.00 10/2005 207


Services Overview

Response Time Global data response time is measured from a status change in the publisher to the
time when the change is known in the subscriber:
publication time + 1 CPU scan on the publisher + publication time of the service +
network time + subscription time of the subscriber + 1 CPU scan on the subscriber
where publication time of the service and subscription time of the subscriber are
generally 1 to 2 ms each.

Note: ETY systems need to include one additional CPU scan on the subscriber.

The following diagram shows system start-up times for a Premium ETY Ethernet
communications module and a Unity Copro module. The response times for both
devices are measured with each device used as a subscriber and as a publisher.

3.50
3.00

2.50
Time (in ms)

2.00

1.50

1.00

0.50

0.00
16 32 64 128 256 512 1024
Length
ETY subscriber ETY publisher
Copro subscriber Copro publisher

The following diagram shows the maximum time required to reach a steady state
(measured in seconds).

70
60

50
Time (in s)

40

30

20

10

0
2 16 32 48 64
Number of Stations

208 31006929.00 10/2005


Services Overview

3.5 Faulty Device Replacement

At a Glance

Overview When the FDR service is supported in a field device, you can easily and reliably
replace the device if it fails. When the replacement device is installed, it is
automatically reconfigured with the operating parameters and IP address of the
failed device.

What's in this This section contains the following topics:


Section?
Topic Page
Faulty Device Replacement 210
Devices that Support the FDR Services 212

31006929.00 10/2005 209


Services Overview

Faulty Device Replacement

Summary The FDR service uses a central FDR server to store network parameters and the
operating parameters of devices on the network. If a device fails, the server
automatically configures the replacement device with the identical parameters as
the failed device. The FDR service removes the need for service personnel to keep
configuration records on hand and reduces the possibility of human error in entering
the new configuration.

TFTP Server
1
2

DHCP Server

TFTP Client DHCP Client


4

1 FDR server
2 server configuration
3 operating parameter file transferred to the FDR client
4 FDR client (replacement device)
5 rolename assignment

210 31006929.00 10/2005


Services Overview

FDR An FDR service comprises an FDR server and a client. The server is a passive
Components device; it simply stores all the parameters for the devices on the network. To
configure the server, create a list of the devices connected to the network (each
identified by a rolename) and their IP parameters. After the FDR service is enabled,
the server responds to requests from the FDR clients.
The FDR client is a network device that stores its parameters on the FDR server to
facilitate replacement of the device. Each client is assigned a rolename that uniquely
identifies it from other devices on the network. After the device is connected to the
network, it sends a copy of its operating parameters to the server. The actual
parameters depend on the type FDR client device, but they should always be
sufficient to enable a replacement device to be configured to operate exactly as the
original client. After the server has a copy of the parameters, the client periodically
checks to see that the server has a current set of parameters. An update is sent to
the server when there is a change in the client’s operating parameters. Depending
on the client’s implementation, this update may or may not be automatic.
If a client fails, the following occurs:
Sequence Event
1 Your service personnel must assign the same rolename to the replacement
device.
2 Your service personnel places the new device on the network.
3 The device automatically issues a request to the server for a set of IP
parameters that is used by a device with this rolename.
4 The device receives the IP parameters and then connects to the FDR server
and downloads a copy of its operating parameters.
5 After the parameters are downloaded, the device implements the parameters
and operation resumes.

The actual parameters may include a device consistency check to see that the
replacement device is of the same type as the original. Based on this check, the
client may choose to operate even if the replacement device is different from, but
still compatible with, the original device.

When to Use FDR FDR should be used for all devices that support this service on an automation
network. As Schneider Electric adds FDR support into more of its devices, plants
should be updated. At the present time, the service focuses on I/O devices, not on
PLC or HMI systems. In Hot Standby system, you are unable to use the FDR server.
Only one FDR server is permitted on a subnet (see p. 135). If you reach the limit for
FDR clients on a network, split the network and assign a new FDR server to the
newly established network.

31006929.00 10/2005 211


Services Overview

Devices that Support the FDR Services

Device FDR Client FDR Server


Quantum 140CPU65150 - X
140CPU65160 - X
140NOE77101 - X
140NOE77111 - X
Premium TSXP571634M - X
TSXP572634M - X
TSXP573634M - X
TSXP574634M - X
TSXP575634M - X
TSXETY4103 - X
TSXETY5103 - X
TSX Micro TSXETZ410 X -
TSXETZ510 X -
Momentum 171ENT11001 X -
Advantys STB STBNIP2212 X -
Altivar ATV38/58 VW3A58310 X -

212 31006929.00 10/2005


Services Overview

3.6 Time Synchronization

At a Glance

Overview This section describes the time synchronization service and how it distributes time
to devices on the network.

What's in this This section contains the following topics:


Section?
Topic Page
Time Synchronization Service 214
Time Synchronization Service Operation 216
Time Synchronization Applications 217
Schneider Devices Implementing Time Synchronization Service 221

31006929.00 10/2005 213


Services Overview

Time Synchronization Service

Time Synchroni- Time synchronization is a service that distributes and maintains an accurate time for
zation Summary devices on the network. Typically, the time is accurate to within 1 to 2 ms. After the
devices have been time-synchronized, this service can be used to:
z synchronize an action
z time-stamp the occurrence of events (sequence-of-events recording)
z manage the order of plant operations
Time synchronization is achieved by sending out periodic time updates to all the
devices configured for this service.

2 2

3
3

1 GPS satellite time


2 NTP time servers
3 local time

214 31006929.00 10/2005


Services Overview

Time Time synchronization uses SNTP to distribute the server time to all clients that
Synchronization implement this service. The central time server may run independently or be
connected to a GPS receiver, a DCF receiver, or a remote clock (using NTP). The
NTP service operates in Greenwich mean time and local time zones and is
administered by the clients. Several time servers can operate on the network to
provide redundancy in case the primary server goes out of service.
To maintain accurate time, clients request the time from the server at configured
intervals. Clients may make adjustments for network delays in the time transfer.
Once the client receives the time, an internal clock keeps track locally. At the next
configured update, the client requests the time from the server and synchronizes its
local clock. The client’s time accuracy is affected by the accuracy of the local clock,
the update period, and the accuracy of the time server.
Many devices can be used as a time server (e.g., a Windows or Linux PC with a
1 to 30-ms accuracy, a dedicated time server with better than 1 ms accuracy). The
time server maintains its time by using a local clock while receiving updates from a
remote source like a GPS or a DCF receiver.
During time synchronization, all the clients request the time from the time server.
Each client’s internal clock is synchronized with the time server time, allowing all
alarms and file-and-program-change time stamps across the plant to be recorded
using the same time source. Time synchronization allows you to track the order of
changes in the plant without the need to manually set the time in each device.

Sequence-of- Sequence-of-events recording allows the order of events across a plant or across
events multiple plants to be reconstructed or examined very accurately. This application is
Recording based on the accurate time-stamping of events at their source.

Action Action synchronization allows multiple devices across a plant to execute an


Synchronization operation at the same time. It can be useful for starting drives along a conveyor or
transferring products from one part of the plant to another.

31006929.00 10/2005 215


Services Overview

Time Synchronization Service Operation

Detailed Service The time synchronization service uses SNTP to distribute the time from the central
Operation server to all clients who request it at configured intervals. By time-stamping the
requests and responses at each point in the exchange, the clients can account for
delays caused by the network. Network loads and delays generally do not affect the
time signal accuracy. However, the delay is assumed to be uniform, so a delay that
occurs on the request packet, but not on the received packet, may cause the client
time to be inaccurate by a small amount.
After the client receives the time, its internal clock keeps time locally. At the next
configured update, the client requests the time from the server and synchronizes its
local clock again. The client’s time accuracy is affected by the accuracy of its local
clock and the update period. More frequent time updates result in less time drift and
therefore more accurate client time.
Service accuracy is also determined by the accuracy of the time server. A time
server can be from a Windows or a Linux PC to a dedicated time server with an
atomic clock. The time server maintains its time by using its local clock while
receiving updates from a remote source like a GPS or a DCF receiver. The internal
clock’s accuracy and the response time to NTP requests can affect the overall
system accuracy. A Windows PC acting as an NTP server typically restricts the
system accuracy to ~ +/-30 ms; a dedicated NTP server with a GPS receiver is
accurate to within less than 1 ms.
This service is better than earlier time synchronization systems because it requires
only a single connection. Earlier systems required each device to have a GPS or a
DCF receiver, resulting in higher costs and difficulty in placing antennas.
When a CPU acting as a client requests a time update, the Ethernet module obtains
this information from the server and updates the CPU’s internal clock. This internal
clock now functions as the local clock for the PLC until the next time update. This
clock can be accessed at any time inside the user logic by using a specific
elementary function block.

NTP
Server
Power Processor Ethernet
Supply Module
NTP Request
Internal Ethernet Network
Clock
(S)NTP
Client
NTP Response

Premium/Quantum

216 31006929.00 10/2005


Services Overview

Time Synchronization Applications

Functions that Time synchronization gives all devices on the network the identical time reference.
Use Time This service supports event time-stamping, alarms, and program or file changes
Synchronization across the plant, based on the same time.

PLC clocks synchronized

31006929.00 10/2005 217


Services Overview

Sequence-of- To time-stamp events, the PLC must be able to detect an event as it occurs at the
events I/O module. To do this, choose a module with minimal filtering and delay times. If
Recording possible, link the input module to an event task in the CPU (a feature supported on
higher-end CPUs). The field event is detected by the module and calls the event
task, interrupting the program and allowing the application code to time-stamp the
input.
If the CPU does not support the implementation of event tasks, the fast task should
be used. Configure the fast task to execute as frequently as possible. Unlike the
event task, the fast task interrupts the execution of the main program to check for
events. Fast task execution frequency should be configured so it does not heavily
impact the execution time of the main program. The I/O module that contains the
input event should be linked to the fast task; the fast task’s first actions should be to
check the I/O module for the input and to time-stamp that input if it represents a
recordable event.

1 comparison of event times across the plant to determine the order of events
2 local time-stamping of events

218 31006929.00 10/2005


Services Overview

Action The time synchronization service can synchronize the activation of events across
Synchronization one or more plants. Use the fast task to make sure that the current time is set equal
to the time at which the event is configured to occur. If the time is correct, then the
output should be activated. Accuracy is affected by the frequency of the fast task,
the length of execution of the fast task (since the output is not activated until the fast
task has completed), and the I/O activation time. The I/O module containing the
event output must be linked to the fast task.

1 synchronized actions across the plant

31006929.00 10/2005 219


Services Overview

Comparison with The main differences between the time synchronization service and a traditional
Traditional Event recorder system for sequence-of-events recording are cost and accuracy. A
Recording traditional implementation has an accuracy of 1 ms, but comes at a higher cost than
Systems a PLC system implementing the time synchronization service.
Any difference in accuracy is due to the I/O modules used. A traditional sequence-
of-event recording system uses dedicated I/O modules with special filtering
systems. The I/O module time-stamps the input as soon as it occurs and then begins
to filter it. If the input is determined to be noisy, the event is discarded from the
records.
The time synchronization service is based on normal PLC I/O modules where the
input is filtered inside the module before it is passed to the CPU as an event and
recorded by a time-stamp. This filter-before-recording method results in less
accuracy, but it reduces costs because no special I/O modules are required.
The cost advantage is based on the distribution of the time across an existing
Ethernet network. In a traditional system, a GPS or DCF receiver must be connected
directly to each I/O module. The cost of multiple receivers and the difficulty of
running antennas for these devices outside the plant (because GPS receivers
require a clear view of the sky) is much greater than the cost of a single receiver
attached to a central NTP time server. The Ethernet configuration requires only a
single outside antenna system and uses the plant’s existing Ethernet network.

220 31006929.00 10/2005


Services Overview

Schneider Devices Implementing Time Synchronization Service

Unity Module and Processor Predicted Typical Time Service Operation


Used
Ethernet Ethernet Clock Event Time Stamping2
Modules Modules with Synchronization1 Synchronization
Unity Processor
TSXETY5103 TSXP570244M +/-1 ms typical = =
TSXP571x4M +/-10 ms clock clock
TSXP572x4M maximum synchronization synchronization
TSXP573x4M precision precision
TSXP574x4M +/-1 ms typical + +
TSXP575x4M +/-5 ms fast task time I/O time
maximum +
I/O time
140NOE 77111 140CPU31110 +/-1 ms typical
140CPU43412U +/-10 ms
140CPU53414U maximum
140CPU65150 +/-1 ms typical
140CPU65160 +/-5 ms
140CPU67160 maximum
1 Time difference between field input and central server.
2
Assuming input connected to the interrupt module.

31006929.00 10/2005 221


Services Overview

3.7 Electronic Mail Notification Service

At a Glance

Overview This section describes the electronic mail notification service and how it provides
users with process data, production reports, alarms and event notifications.

What's in this This section contains the following topics:


Section?
Topic Page
Electronic Mail Notification Service 223
Electronic Mail Notification Service Operation 225
Devices that Support Email Notification 227

222 31006929.00 10/2005


Services Overview

Electronic Mail Notification Service

Summary The electronic mail notification service allows PLC applications to report conditions
monitored by the PLC by running an email client inside an Ethernet communication
module. The PLC can automatically and dynamically create short electronic mail
messages to alert specified users to:
z alarms
z events
z production reports
z maintenance reminders
z plant status updates
z other plant information
Recipients may be local or remote.
This service allows you to create predefined email headers (including recipients’
names, email addresses, and message subject) to be used with different email
bodies. Some devices let you include values dynamically obtained from the latest
information in the PLC application or machine state; other devices allow only
predefined messages. Multiple email messages can be created to describe different
events or alarms, including several system variables. This option can be change by
an authorized administrator.

Note: Because messages need to be processed through an email system, delays


may occur between the time the message is sent and the time it is received.
Therefore, this service should be used only for noncritical notification.

31006929.00 10/2005 223


Services Overview

An Application Many industrial facilities are connected to numerous pump houses in remote
Example locations that supply them with water. These locations contain pumps, valves, and
filters that require regular preventive maintenance based on the number of hours of
operation. Maintenance dates may change from month to month depending on the
utilization of the pumps, filters, or valves. Email notification to the maintenance crew
when those maintenance limits are reached eliminates the need to travel to a remote
pump house to check.
For example, one of the pump filters has been in service for 1000 hours over a
period of 3 months without being cleaned or replaced and now requires preventive
maintenance. Because the system has been configured to trigger a maintenance
request after every 1000 hours of operation, an alarm is sent out by the Ethernet
module to the email server to notify the maintenance crew to clean or replace the
filter in the pump house. After the email server has processed the message and sent
it to the company network, the maintenance crew receives the email notification. If
the email server is set up to send messages to pagers or mobile phones, an
additional notification could be sent to the maintenance crew using these media.

1 Email notification sent regarding pump run hours


2 multiple site report maintenance to contractor via email.

224 31006929.00 10/2005


Services Overview

Electronic Mail Notification Service Operation

Service The electronic mail notification service is implemented inside an Ethernet


Operation communication module that serves as an email client. When a preconfigured event
or alarm is triggered in the controller, the Ethernet module uses SMTP (over TCP
port number 25) to communicate with an email server. That server is connected to
the plant’s network or to the Internet, thereby allowing the email message to reach
its recipients. Email or SMS (short message service) messages may also be sent to
mobile phones if the client’s email server has the capability.

6
3
4

1 input event
2 email triggered
3 email sent to the mail server
4 Internet or email system
5 local mail server
6 email message displayed
Even though notifications are sent automatically after an event or alarm is triggered,
there may be a significant delay before the recipient gets the message. The
message is processed by an email server, sent through the Internet or company mail
system, processed again by an email delivery server, then accessed by the recipient
through his/her email account. A notification sent to a mobile phone is received only
when the phone is on and within the coverage area. Therefore, this service should
only be used for noncritical notifications, such as maintenance reminders or
production reports.

31006929.00 10/2005 225


Services Overview

Security An optional login password, which is authenticated by the SMTP mail server to verify
if the client is authorized to send emails, can protect each email message. To
establish password protection, you can use a subset of the SMTP service extension
for authentication (RFC 2554). This extension allows the client to authenticate prior
to sending messages. Also, the SASL (a method for adding authentication support
to connection-based protocols) includes a command for identifying and authenti-
cating a user to a server and for optionally negotiating protection of subsequent
protocol interactions. As a result of this negotiation, a security layer is inserted
between the protocol and the connection. When enabled, both the login and the
password are encrypted. To provide additional security, the site’s email installation
can change the TCP port number from the default setting of 25.

Additional The notification service only provides an email client in the Ethernet module. The
Service client sends electronic mail notifications. To enable recipients to receive these
Requirements messages, the site where the Ethernet module is installed must have an email
server, such as Lotus Notes, Microsoft Exchange, or Linux SendMail.The client
connects to the email server to distribute the mail to its recipients.

226 31006929.00 10/2005


Services Overview

Devices that Support Email Notification

Device Security Maximum Variables in Dynamic


Feature Number of Message Email Body
Headers Body Content
Premium TSXP571634M X 3 X X
(v3.1 or higher)
TSXP572634M X 3 X X
(v3.1 or higher)
TSXP573634M X 3 X X
(v3.1 or higher)
TSXP574634M X 3 X X
(v2.0 or higher)
TSXP575634M X 3 X X
(v2.0 or higher)
TSXETY4103 X 3 X X
(v3.1 or higher)
TSXETY5103 X 3 X X
(v3.1 or higher)
TSXWMY100 - 100 X -
Quantum 140CPU65150 X 3 X X
(v2.0 or higher)
140CPU65160 X 3 X X
(v2.0 or higher)
140NOE77101 X 3 X X
(v3.5 or higher)
140NOE77111 X 3 X X
(v3.5 or higher)
140NWM10000 - 100 X -

31006929.00 10/2005 227


Services Overview

3.8 Standard Web Server

At a Glance

Overview The section describes a service that uses a standard Web browser to diagnose and
configure Transparent Ready devices.

What's in this This section contains the following topics:


Section?
Topic Page
Web Server Services 229
Web Server Operation 231
Devices that Support Standard Web Server Services 234

228 31006929.00 10/2005


Services Overview

Web Server Services

Summary Embedded diagnostics are used to execute diagnostic and maintenance functions.
They can be run either locally or remotely through a simple Internet browser. This
service uses an embedded Web server and a real-time data server. All data is
presented in HTML format and can be accessed from any Internet browser. This
service is a convenient way to monitor the health of devices on the network and to
access operational and configuration information.
The embedded Web server is a real-time PLC data server. All the device, diagnostic,
and configuration data is viewed in HTML by using any Internet browser with a Java
virtual machine (JVM) to support the integrated Java code. No programming is
required at either the Transparent Ready device level or at the PC running the Web
browser.

31006929.00 10/2005 229


Services Overview

Web Service and Some automation devices allow remote configuration via Web pages. For example,
Web Pages Altivar drives provide access to current speed information and allow you to configure
acceleration rates through the Altivar drive’s Web pages. The Web client can then
access the Altivar drive’s Web pages.

PLC

Web client
Altivar drive

Another application is monitoring power usage in apartment buildings. If Power


Logic circuit monitors are installed at various circuit breakers throughout the
building, an administrator can remotely monitor the power usage of each tenant
simply by accessing the Power Logic circuit monitor’s Web page with a Web
browser. Eliminating the need to physically read each meter saves a vast amount of
time and resources.

1 remote access to the power meters over the building’s Ethernet network
2 office building configured for separate power metering for each tenant

230 31006929.00 10/2005


Services Overview

Web Server Operation

Summary When an HTTP client accesses the Web server, the application receives the request
and retrieves the required data from the device’s memory. The information is sent
back to the client in the form of a Web page. The Web server is a passive service; it
runs only when information is requested from it. The Web pages are in HTML format;
they are stored on the Web server along with other data source files such PDF, JPG,
etc. Some Web servers can display real-time data, but a JVM must be installed to
enable the client to display these Web pages.
When you try to access a Web page, the Web browser issues a request to the
server. After the server handles the request, it sends the HTML pages back to the
client. There are two types of Web pages:
z static pages, which may or may not contain real-time data. If you want to refresh
real-time data, the Web pages must be reloaded, which means another request
must be sent.
z dynamic pages, which do contain real-time data. These Web pages contain Java
applets that run on the client’s JVM, retrieve real-time data from the Web server,
and display data in the Web browser.
With static pages, such as those from an EGX Gateway or an NOE configuration
screen, the client needs to a refresh the page request to update the data. The Web
server accesses the HTML page, obtains the real-time data, updates the HTML file,
and then sends the information back to the destination. The client can request
updates as needed.
With dynamic pages, such as Ethernet statistics on a NOE module, the data updates
are provided by Java applets. The client requesting the data must have a JVM
running. When you access HTML files, the static portion of the HTML file is
downloaded along with the Java applets. The Java applets running inside the JVM
on the client issue a Modbus request for the device to obtain the real-time data.
1

2
3

1 an http server
2 a Web page
3 request for a Web page
4 current dynamic data values placed into the Web page
5 device memory

31006929.00 10/2005 231


Services Overview

Common Web The more common Web pages are:


Pages z rack viewers
z data editors
z Ethernet statistics displays
z device property displays
z menus
z device configuration screens
z device diagnostics displays

Rack Viewers A rack viewer is supported in Ethernet TCP/IP modules for the following platforms
and devices:
z TSX Micro
z Premium
z Quantum
z Momentum
z Advantys STB
z FactoryCast
A typical rack viewer Web page looks like this:

232 31006929.00 10/2005


Services Overview

Data Editors The data editor function can be used to create tables of animated variables for real-
time read/write access to lists of PLC data. The variables to be displayed can be
entered and displayed symbolically (S_Pump 234) or by their address (%MW99).
These variables support write access only if this option has been enabled using
FactoryCast configuration software. A second password must be entered and
verified when writing a value to a variable. You can create various animation tables
containing specific application variables to be monitored or modified and save them
in the Ethernet TCP/IP module.
The following illustration shows a data editor:

Ethernet statistics: Ethernet statistics include IP parameters, the number of


packets transmitted and received, and any errors at the Ethernet layer.
Device properties: Device properties display the current product version, the
operating system, and the firmware or kernel version.
Menu: Menus display lists of pages available from a device.
Device configuration: The device configuration shows the service configurations
on the device.
Device diagnostics: Device diagnostics are the diagnostics of the services on that
device.

31006929.00 10/2005 233


Services Overview

Devices that Support Standard Web Server Services

Product Reference
Quantum Processor 140CPU65150
140CPU65160
Modules 140NOE771001
140NOE 77111
140NWM10000
Premium Processor TSXP572623M
TSXP572823M
TSXP573623M
TSXP574823M
TSXP571634M
TSXP572634M
TSXP573634M
TSXP574634M
TSXP575634M
Module TSXETZ4103
TSXETY110WS
TSXETY5103
TSXWMY100
TSX Micro Modules TSXETZ410
TSXETZ510
Momentum M1E processors 171CCC96020
171CCC96030
171 CCC 980 20
171 CCC 980 30
Modules 170 ENT 110 01
170 ENT 110 02
Advantys STB STBNIP2212
Altivar ATV 38/58 VW3 A58310
Power Logic Gateway EGX200
EGX400

234 31006929.00 10/2005


Services Overview

3.9 FactoryCast Web Server

At a Glance

Overview The section describes how to use the FactoryCast Web server to control and
monitor plant operations.

What's in this This section contains the following topics:


Section?
Topic Page
FactoryCast Web Server 236
FactoryCast Web Server Operation 238
Devices that Support FactoryCast Web Server Services 240

31006929.00 10/2005 235


Services Overview

FactoryCast Web Server

Summary A FactoryCast Web server is an extension of the standard Web server that provides
plant diagnostics and control through customized Web pages. The following
functions are available:
z management of device and plant alarms with partial or global acknowledgment
(ready-to-use pages for the alarm viewer function)
z graphical plant diagnostics (customized user-generated graphical views using
the graphic data editor function)
z graphical plant control via user-generated animated Web pages that are stored
in the FactoryCast module
The customized Web pages are transferred to the module using FactoryCast
configuration software.

Hosting and FactoryCast Web modules have a memory area that hosts user-generated Web
Displaying User pages. These Web pages may be created with standard HTML editing tools such as
Web Pages Microsoft FrontPage and Macromedia Dreamweaver. Java applets linked to PLC
variables can enhance these pages by providing graphical representations of plant
status. These animated objects are provided in the graphic data editor supplied with
FactoryCast.
The Web pages can be used to:
z display and modify variables in real time
z create hyperlinks to other external Web servers
The graphic data editor lets you create graphical screens for:
z display, monitoring, and diagnostics
z generation of real-time production reports
z maintenance manuals
z operator guides

Configuration The MS Windows-based configuration software for FactoryCast Web servers is


Software for supplied on CD-ROM with every FactoryCast module. Use the software to configure
FactoryCast Web and administer the Web server embedded in these modules. It allows you to:
Servers z access security management
z define user names and passwords for accessing Web pages
z define access to variables authorized for modification
z save/restore an entire Website
z transfer Web pages created locally to and from the FactoryCast module

236 31006929.00 10/2005


Services Overview

FactoryCast Web Your ability to configure plant diagnostics makes important information readily
Server Uses available and lays it out in a format you choose. You can create Web pages that
contain manuals, operating procedures, and useful reference material such as CAD
drawings.
If the files become too large, you can store them on separate Web servers and store
only the links to those files on the FactoryCast device. The illustration shows how a
FactoryCast web server accesses documents:

1 a FactoryCast module where links to a central Web server are stored


2 the central Web server where documents are stored
3 a Web client can access the desired documents through the FactoryCast module

31006929.00 10/2005 237


Services Overview

FactoryCast Web Server Operation

Alarm Viewer The alarm viewer is a ready-to-use alarming system comprising a password-
protected alarm page (viewable in a Web browser) and function blocks inside the
device (used to add alarms to the alarm system). The diagnostics buffer in the
device is the source of the alarms on the Web page. This system can be used:
z to process device alarms (display, acknowledgment, and deletion) that can be
managed automatically by the system
z by the user application employing diagnostic elementary function blocks (EFBs)
The alarm viewer is a Web page that contains the following information for each
alarm:
z its state
z the type of associated EFB
z its geographical area
z the dates and times of the occurrence/removal of a fault

Graphic Data The graphical data editor can be used to create customized screens showing
Editor animated plant data. These views are created in a Web-based tool (accessed from
the FactoryCast device) using a library of graphic objects. The objects may be
customized for color, PLC variables to display, labels, etc. The following graphic
objects are provided:
z analog and digital indicators
z horizontal and vertical bar charts
z boxes for displaying messages and entering values
z push button boxes
z functions for displaying trends
After the screens are created, they can be stored in the FactoryCast device for future
use or to be reused in customized Web pages.

238 31006929.00 10/2005


Services Overview

The following illustration shows some of the objects that can be used to develop a
graphical screen:

A completed graphical screen might look something like this:

31006929.00 10/2005 239


Services Overview

Devices that Support FactoryCast Web Server Services

Device
Quantum 140NOE77111
140NWM10000
Premium TSXETY110WS
TSXETY5103
TSXWMY100
Micro TSXETZ510

240 31006929.00 10/2005


Services Overview

3.10 FactoryCast HMI Web Server

At a Glance

Overview The section describes the FactoryCast HMI Web service and how to use it for real-
time plant diagnostics and control.

What's in this This section contains the following topics:


Section?
Topic Page
FactoryCast HMI Web Services 242
Devices that Support The FactoryCast HMI Web Service 247

31006929.00 10/2005 241


Services Overview

FactoryCast HMI Web Services

Summary The FactoryCast HMI Web server extends the FactoryCast functions (see p. 236) by
executing the following HMI Web features:
z real-time HMI database management (specific to the module and independent of
the PLC processor)
z arithmetic and logical calculations for preprocessing data on the HMI
z transmission of electronic messages triggered by a specific process event (by
email)
z connection to the SQL server and the MySQL and Oracle relational databases to
archive tracking or logging data
FactoryCast HMI is an active Web server that executes HMI functions integrated in
a PLC module. The active Web server eliminates the need for communication via
polling to update the HMI/SCADA database.
The FactoryCast HMI software configures the services on the module. You need
only to configure the parameters for each service; no actual programming is
required. The software provides a simulation mode to test the application without a
FactoryCast HMI module or a physical connection to a PLC, thereby simplifying
debugging.

242 31006929.00 10/2005


Services Overview

FactoryCast HMI Although other Ethernet devices with an embedded Web server can provide real-
Web Service time data, they are unable to provide historical information or initiate Web services
Operation unless a client is connected. The FactoryCast HMI devices have an integrated JVM.
A FactoryCast HMI device can provide historical trending information and initiate
other Web services such as database logging and email.
The following illustration shows the FactoryCast HMI Web service data flow:

Rational database Thin client IPC

Ethernet TCP/IP

Premium Web server

Architecture FactoryCast HMI Web servers can be integrated into:


z installations that require flexible and cost-effective HMI solutions
z hybrid architectures that supplement conventional SCADA systems
z architectures where direct links are required between automation systems and
information management levels (IT links)

31006929.00 10/2005 243


Services Overview

Flexible Web HMI FactoryCast HMI devices replace conventional HMI or SCADA solutions for
Solution architectures that require a flexible multi-station HMI. A FactoryCast HMI device
provides a temporary remote control function over Internet or company networks.
Typical architectures may consist of:
z several PLCs networked on an Ethernet network with FactoryCast HMI Web
server modules
z one or more clients with a thin client interface equipped with a simple Web
browser
z a relational database in which FactoryCast HMI can archive data directly from the
automation system
FactoryCast HMI modules read PLC data and execute HMI services (email,
interpreted calculations, connections to relational databases, updating Web pages)
at source in the PLC, without affecting the PLC program or the CPU scan time.
This solution provides:
z a reliable HMI application executed at source in a PLC
z an integrated multi-station interface and remote access that is easy and cost-
effective to set up (thin-client terminal)
z an HMI application that is easy to maintain because it resides in a single location
on the server
z preventive maintenance notification via email
z data archiving directly from the data source

Hybrid FactoryCast HMI supplements conventional SCADA systems. SCADA Vijeo Look or
Architectures Monitor Pro software provides a means of centralizing information in order to
perform global supervision from a central site.
Combining a FactoryCast HMI solution and a conventional SCADA solution
enables:
z simplification of the SCADA application by locating some of the SCADA
processing at the source level
z increased availability to trace data due to the direct connection between
FactoryCast HMI modules and relational databases
z powerful ready-to-use remote diagnostics

244 31006929.00 10/2005


Services Overview

Direct Links and In hybrid architectures, FactoryCast HMI eliminates the need for intermediate
Information devices (gateways), which are expensive to install and maintain. It establishes a
Management direct link between the automation levels and the global information management
Levels levels (MES, ERP, etc.). The PLC archives information directly from the automation
system in relational databases, allowing a collaborative automation system to share
data in real time. This solution results in:
z simplified architectures
z lower installation, development, and maintenance costs
z increased data reliability (because the data is collected at source)
z greater availability of data archiving

The HMI Tag With an internal architecture similar to that of an HMI/SCADA system, FactoryCast
Database HMI modules manage their own variable database in real time, independent of the
PLC program. This variable database executes various functions, including internal
processing, archiving, alarm, and email. Variables in this real-time database are
updated by the automation system’s data acquisition service. This service becomes
operational once the following parameters have been set in the FactoryCast HMI
software:
z direct import of PLC variable/symbol databases (without duplicate entries)
z definition of the acquisition frequency (the period at which this variable is
updated)

Note: A FactoryCast HMI application running in a configured Premium


FactoryCast HMI module can also access the remote PLC variables in the
architecture via a transparent network (X-Way/Uni-TE transparent protocols).

Web Service FactoryCast HMI Web services have:


Characteristics z a maximum of 1000 I/O variables from PLCs per application
z a maximum of 100 internal variables per application
z a minimum acquisition frequency of 500 ms

31006929.00 10/2005 245


Services Overview

Connections to The FactoryCast HMI module can be connected directly to the following remote
Relational relational databases:
Databases z SQL server
z MySQL
z Oracle
This connection enables all internal or process data to be archived so that it can be
logged and traced. The data can be archived (written) periodically and/or for a
specific event. These variables can be from PLCs (I/O bits, internal bits, internal
words, and registers) or local to the module.
The FactoryCast HMI roll-over function checks the size of tables by managing the
maximum number of records. It is a circular data-archiving function that
automatically deletes the oldest data. The roll-over function can be accessed by
setting parameters in the FactoryCast HMI software.

Database Database characteristics are as follows:


Characteristics z number of databases that can be connected: 3
z number of tables that can be written per database: 10 (maximum)
z number of columns per table: 50 (maximum)
z type of database supported: Oracle, SQL Server and MySQL
z automatic table creation: The FactoryCast HMI server automatically creates a
table in the database

Calculation The FactoryCast HMI server can perform various arithmetic and logical operations
Functions on a combination of variables from the HMI database independent of the PLC
processor. Some of these calculations include scaling, formatting, and logic
processing for event triggering.
The calculation function comprises a set of spreadsheets with the formulae defined
in cells. The spreadsheets are interpreted and processed by the server. The result
of each formula is associated with a new internal variable. A user-defined trigger
initiates the processing of each spreadsheet.

246 31006929.00 10/2005


Services Overview

Devices that Support The FactoryCast HMI Web Service

Device
Quantum 140NWM10000
Premium TSXWMY100

31006929.00 10/2005 247


Services Overview

3.11 Other Services

At a Glance

Overview This section describes other support services available with some Transparent
Ready devices. These services are implementations of standard IT infrastructure
services that may be used for system maintenance and monitoring.

What's in this This section contains the following topics:


Section?
Topic Page
FTP Service 249
SNMP Service 250
TFTP Service 252
Telnet Service 253
Quantum Device Support for Other Services 255
Other Services Supported by Premium Devices 257
Other Services Supported by TSX Micro Devices 259
Other Services Supported by Momentum Devices 260
Other Services Supported by Advantys STB Devices 261
Other Services Supported by Power Logic Gateways/Bridges 262
Other Services Supported by ConneXium Cabling Systems 263

248 31006929.00 10/2005


Services Overview

FTP Service

FTP Service FTP is a client-server protocol used by many systems to transfer files between
Summary devices. Many devices, including Transparent Ready devices, implement FTP to
transfer information to load new firmware, custom Web pages, etc.
FTP transports and exchanges all information using TCP. By default, FTP uses TCP
port number 20 for data transport and TCP port number 21 for control. The client
initiates an FTP connection by connecting to the control port on the server. The
server responds by connecting the data port back to the client. After the connections
are made, file transfer can take place.
In Transparent Ready devices, FTP may be used for different purposes depending
on the device. For example, only firmware and custom Web pages are accessible
on Transparent Ready CPUs through the FTP server. CPU program files cannot be
accessed.
1

4
5
2

Client Server
3

1 an FTP client PC
2 an Ethernet switch
3 a PLC with FTP server connections
4 a PLC program with no path to the FTP server
5 HTML Web page files

FTP Security The client must provide a username and password in order to read or write files on
the server. However, the transmission of this authentication information is done in
simple text; therefore it can be obtained by inspecting the content of the messages
between the client and the server.
The transmission of files over or outside of a network is a major concern when
firewalls are implemented to control access and information flow. Therefore unless
the FTP port is open in the firewall, this type of communication is blocked. For
information on how to open ports on firewalls, refer to the firewall documentation
(see p. 154) or contact your company’s IT department.

31006929.00 10/2005 249


Services Overview

SNMP Service

Summary With the SNMP service, you can monitor the status of the network and the devices
connected to it. This service supports the management of many diverse network
devices using a single system. It consists of the network management system, the
SNMP protocol, and the SNMP agent in each network device.

SNMP agents
SNMP manager

The SNMP protocol is used to exchange network management information between


the network manager or management system (such as HP Openview, IBM Netview,
etc.) and the SNMP agents.

250 31006929.00 10/2005


Services Overview

SNMP Service The information available in a device is listed in a data structure called a
Operation management information base (MIB). A MIB contains data definitions of the
attributes for each of the network-managed objects so that the management system
can gather and combine information from multiple devices. The SNMP service
monitors the state of the network, modifies device configurations, and generates
alarms based on device failures.
Many standard MIBs have been developed (MIB-II, Switch MIB, etc.). Devices
implement these MIBs to provide standard information to any network management
system. Depending on the device complexity, manufacturers may choose to
implement private MIBs that provide additional information specific to their device.
The SNMP protocol transports and exchanges all information using UDP. UDP’s
small and simple packet size reduces the network load. However, extensive
monitoring can cause increased network load.

SNMP Security Since the introduction of SNMP, protecting network management information has
become an increasingly important issue. In SNMPv1, requests and replies are sent
in clear text, exposing variables to hackers. MIB writers discovered that some data
type definitions required more precision. SNMPv2 addressed these issues by
improving the authentication of the message source, protecting these messages
from disclosure, and placing access controls on the MIB database. However, some
security aspects still remained vulnerable. SNMPv3 framework augments the
original SNMPv1 and v2 specifications with additional security and administration
capabilities.

31006929.00 10/2005 251


Services Overview

TFTP Service

TFTP Service TFTP is a simple client/server protocol that may be used instead of FTP to transfer
Summary files. It uses UDP port number 69 and is implemented on top of the UDP transport
layer. With TFTP most of the features of a regular FTP are removed. It can perform
only read and write operations from/to a remote server; it cannot list directories, and
it has no provisions for user authentication or security. TFTP can be implemented in
simple devices.
During a TFTP connection, files are transferred between the client and the server.
The recipient of the file issues a confirmation that the file was received without
errors.The protocol does not permit retransmission of only part of a file that contains
an error; the entire file must be retransmitted. This can represent a delay in the
transmission time. However, the probability of errors in the file due to transmission
or transmission loss is not very high.
As with the FTP service in Transparent Ready devices (see p. 249), TFTP uses are
device-dependent. For example, on a Modbus serial-to-Modbus Ethernet bridge, the
firmware is transferred using TFTP, but the device configuration file cannot be. To
establish a connection with the server, a client (such as WSFTP or Windows TFTP
client) is required.

252 31006929.00 10/2005


Services Overview

Telnet Service

Telnet Service The Telnet protocol provides an interactive, text-based communications session or
Summary user interface between a client and a host. Telnet interfaces can be used for tasks
such as device configuration, diagnostics, and file interchange.
The Telnet protocol runs over the TCP transport layer using port 23. A Telnet
session can generate unexpected amounts of network overhead, because each
keystroke may be sent as a separate TCP packet.
Here are examples of a configuration screen and a diagnostics screen for the
ConneXium Ethernet Switch (499NES27100):

System Parameter 148.218.112.101

Schneider Automation Ethernet Switch 10/100 Mbps

IP Address : [148.218.112.101]
Subnet Mask : [255.255.255.0]
Default Gateway : [0.0.0.0 ]
VLAN ID (0=all) : [0 ]

IP Configuration : <LOCAL>

MAC Address : 00:79:63:00:02:77


System Name : Switch_Role_Name

Note:

Set IP-Configuration <LOCAL> to use manual settings.


APPLY changes the stare if the objects immediately and
saves the state to Non Volatile Memory.

MAIN MENU APPLY

Enter Agent IP address in decimal dot format (e.g., 148.218.19.69)

31006929.00 10/2005 253


Services Overview

Port Configuration/Statistics 148.218.112.101

Schneider Automation Ethernet Switch 10/100 Mbps


Port: 01 Port Name: [ ]
State: <Enable > Set Speed: <autonegotiate
Link: Up Actual Speed: 100MFDX Type: 10/100 TP

Port Statistics

Transmitted Packets: 277234


Received Packets: 1231027
Received Bytes: 154371683
Received Broadcasts: 917923
Received Multicasts: 183637
Received Fragments: 0
Detected CRCErrors: 0
Detected Collisions: 0

MAIN MENU APPLY REFRESH

Type in port number and press enter

Telnet Security The Telnet protocol implements a username and password that the client must use
to gain access to the Telnet session. In some cases the Telnet servers implement
different usernames/passwords for access to different device configuration options.
However, the transmission of this authentication information is done in simple text,
and therefore it can be obtained by inspecting the content of the message.

254 31006929.00 10/2005


Services Overview

Quantum Device Support for Other Services

SNMP
Device SNMP(v1) SNMP(v2) SNMP(v3) MIB-II TFprivate-MIB
140CPU65150 X - - X X
140CPU65160 X - - X X
140NOE77101 X - - X X
140NOE77111 X - - X X
140NWM10000 X - - X X

FTP
Device Firmware Web Files Security FDR Support
140CPU65150 X X X X
140CPU65160 X X X X
140NOE77101 X X X X
140NOE77111 X X X X
140NWM10000 X X X -

TFTP
Device FDR Support
140CPU65150 X
140CPU65160 X
140NOE77101 X
140NOE77111 X
140NWM10000 X

31006929.00 10/2005 255


Services Overview

Telnet
Device Configuration Diagnostics1 Security Levels of Security

140CPU65150 - X X X2
140CPU65160 - X X X2
140NOE77101 - X X X2
140NOE77111 - X X X2
140NWM10000 - X X X2
1
For factory use only
2
multiple passwords

256 31006929.00 10/2005


Services Overview

Other Services Supported by Premium Devices

SNMP
Device SNMP(v1) SNMP(v2) SNMP(v3) MIB-II TFprivate-MIB
TSXP571634M X - - X X
TSXP572634M X - - X X
TSXP573634M X - - X X
TSXP574634M X - - X X
TSXP575634M X - - X X
TSXETY4103 X - - X X
TSXETY110WS X - - X X
TSXETY5103 X - - X X
TSXWMY100 X - - X X

FTP
Device Firmware Web Files Security FDR Support
TSXP571634M X X X X
TSXP572634M X X X X
TSXP573634M X X X X
TSXP574634M X X X X
TSXP575634M X X X X
TSXETY4103 X X X X
TSXETY110WS X X X -
TSXETY5103 X X X X
TSXWMY100 X X X -

31006929.00 10/2005 257


Services Overview

TFTP
Device FDR Support
TSXP571634M X
TSXP572634M X
TSXP573634M X
TSXP574634M X
TSXP575634M X
TSXETY4103 X
TSXETY110WS X
TSXETY5103 X
TSXWMY100 X

Telnet
Device Configuration Diagnostics1 Security Levels of Security

TSXP571634M - X X X2
TSXP572634M - X X X2
TSXP573634M - X X X2
TSXP574634M - X X X2
TSXP575634M - X X X2
TSXETY4103 - X X X2
TSXETY110WS - X X X2
TSXETY5103 - X X X2
TSXWMY100 - X X X2
1
For factory use only
2 multiple passwords

258 31006929.00 10/2005


Services Overview

Other Services Supported by TSX Micro Devices

FTP
Device Firmware Web Files Security FDR Support
TSXETZ410 X X X X
TSXETZ510 X X X X

31006929.00 10/2005 259


Services Overview

Other Services Supported by Momentum Devices

SNMP
Device MIB-II TFprivate-MIB
170ENT11001 X X

FTP
Device Configuration Web Files Security
170ENT11001 X X X

Telnet
Device Configuration Diagnostics Security
171CCC96020 - X X
171CCC96030 - X X
171CCC98020 - X X
171CCC98030 - X X
170ENT11001 X X X

260 31006929.00 10/2005


Services Overview

Other Services Supported by Advantys STB Devices

SNMP
Device SNMP(v1) SNMP(v2) SNMP(v3) MIB-II TFprivate-MIB
STBNIP2212 X - - X X

FTP
Device Configuration Web Files Security
STBNIP2212 X X X

31006929.00 10/2005 261


Services Overview

Other Services Supported by Power Logic Gateways/Bridges

SNMP
Device SNMP(v1) SNMP(v2) SNMP(v3) MIB-II TFprivate-MIB
EGX 200 X - - X -
EGX 400 X - - X -

FTP
Device Configuration Web Files Security
EGX 200 - X X
EGX 400 X X X

262 31006929.00 10/2005


Services Overview

Other Services Supported by ConneXium Cabling Systems

SNMP
Device SNMP(v1) SNMP(v2) SNMP(v3) MIB-II TFprivate-MIB
499NES17100 X - - X X
499NOS17100 X - - X X
174CEV30020 X - - X -
174CEV20030 X - - X -
174CEV20040 X - - X -

FTP
Device Configuration Web Files Security
174CEV20040 X X X

TFTP
Device Configuration FDR Support
499NES17100 - -
174CEV30020 X X
174CEV20030 X X

Telnet
Device Configuration Diagnostics Security
174CEV30020 X X X
174CEV20030 X X X

31006929.00 10/2005 263


Services Overview

3.12 OPC Factory Server

At a Glance

Overview This section describes OFS (OPC Factory Server) and provides examples of how to
implement these servers in Transparent Ready systems.

What's in this This section contains the following topics:


Section?
Topic Page
OPC Factory Server 265
OFS Services 269
OFS Performance 272
Runtime Architecture for Unity/OFS/SCADA: a Simple Example 275
Build-time/Runtime Architecture for Unity/OFS/SCADA Systems that Are Not 277
Frequently Modified
Build-time/Runtime Architecture for Unity/OFS/SCADA Systems that Require 279
Frequent Modification
Build-time/Runtime Architecture for a System with Multiple SCADA 281
Connections

264 31006929.00 10/2005


Services Overview

OPC Factory Server

Summary OPC data access is used to move real-time data from PLCs, DCSs, and other
control devices to display clients such as HMI panels. The OPC specification defines
a standard set of objects, interfaces, and methods for interoperability in process
control and manufacturing automation applications. The specification was originally
based on Microsoft’s OLE component object model and distributed component
object model technologies.
OPC factory server (OFS) is a multi-controller data server that can deliver data to
OPC clients and can communicate with Compact, Micro, Momentum, Premium,
Quantum, TSX Series 7, and TSX S1000 PLCs. OFS provides the client applications
with a group of services (called methods) for accessing control system variables.
OFS is a PLC data access OPC server that is compliant with OPC 1.0A and OPC
2.0; it functions with any OPC-compliant client and with two types of OPC-compliant
software:
z supervisory software: the OFS assumes the role of a driver by ensuring
communication with all Transparent Ready devices
z custom supervisory software: using either the OLE automation interface or the
OLE custom interface
The following illustration shows an OFS interface:
Pump
Client Server
OLE

OLE

OLE

Gate

PLC 3: Micro
PLC 1: Quantum PLC 2: Premium

OFS provides the interface between Schneider Electric PLCs and one or more client
applications in which some of the device data values are viewed and/or modified.

31006929.00 10/2005 265


Services Overview

OFS Capabilities OFS supports:


z multiple devices
z multiple communication protocols
z multiple clients
z access to devices and variables by address or by symbol
z access to the server in local or remote mode
z a notification mechanism that enables values to be sent to the client only when
these values change state
z automatic determination of the size of network requests depending on the device
type
z service availability via both the OLE automation and OLE custom interfaces
z compatibility with OPC Data Access standards, both version 1.0A and 2.0

Data Exchange OFS supports two modes for exchanging data with the PLC:
Modes z default classic (polling) mode
z push data mode, where data is sent at the initiative of the PLC
Push data is recommended when changes of state are infrequent.

OFS Services OFS offers the following services:


z reading and writing of variables in one or more PLCs present on one or more
different networks
z a user-friendly configuration tool that explains the parameters needed for the
server to function efficiently
z a tool enabling parameters to be modified online to maximize utilization flexibility
z the ability to use a list of symbols for the PLC application
z a browser interface that provides a graphical understanding of the accessible
devices and their associated symbols
z a list of specific device-dependent items that enables functions such as status,
start/stop of the PLC, and alarm supervision to be executed

266 31006929.00 10/2005


Services Overview

Communication OFS operates with the Quantum, Premium, Micro, Momentum, Compact, Series 7,
with the PLC and S1000 PLC ranges on the following networks:
z Modbus Serial (RTU)
z TCP IP (IP or X-Way addressing)
z Modbus Plus
z Uni-Telway
z Fipway
z Ethway
z ISAway
z PCIway
z USB
OFS is compatible with the Nano on a Uni-Telway network, with these restrictions:
z read operations only
z access to a single word or x bits within 16 consecutive bits
The following table outlines OFS 3.1 compatibility with devices in the Schneider
Electric SA range and the different networks:
Network Premium Micro Series 7 Series 1000
Ethway TSXETY110 (Ethway) TSXETH107 ETH030
TSXETH200
TCP/IP TSXETY110 (TCP/IP) TSXETZ410
TSXETY410 (TCP/IP) TSXETZ510
Built-in channel
TSXETY510 (TCP/IP)
Uni-Telway Built-in channel Built-in channel TSX SCM22
TSXFPP20 TSX FPP20
Fipway TSXFPP20 PCMCIA TSXP7455
TSXFPP20 TSXFPP20
ISAway ISA Bus
PCIway PCI Bus
Modbus TSXSCP11 TSXSCM22 JB cards
Modbus Plus TSXMBP100 TSXMBP100
USB Built-in channel

31006929.00 10/2005 267


Services Overview

Quantum Momentum Compact


TCP/IP 140NOE771 171CCC96030
Built-in channel 171CCC98030
Modbus Built-in channel 171CCC760 Built-in channel
171CCC780
Modbus PLus Built-in channel Built-in channel
USB Built-in channel

Definition of OFS services are all based on the concept of a group of items. An item is a variable
Group of Items of any PLC that can be accessed either by their address or by their symbol. OFS
groups are characterized as follows:
z Several groups may be defined.
z A group may involve several devices. Each item in a group may have a different
device address.
z A group involves various communication devices and media. Each item may refer
to a different communication driver. If a device can be accessed via several
communication media, it is possible to mix variables addressed via different
media within one group.
z The items comprising a group may be different. It is possible to mix all types of
objects managed by the OFS, for example, mixing words, double words, and
floating points in one group.
z All the items in the same group have the same update rate and deadbanding
percentage.

268 31006929.00 10/2005


Services Overview

OFS Services

Synchronous Synchronous services are used to:


Services z partially or completely read and write a group of items
z periodically scan variables (read polling) that must be handled by the client
application
The term synchronous means that the client application that calls a read or write
service is blocked for the time it takes to obtain a result. The instruction that follows
a synchronous read or write call in the code of the client application is executed only
after all the communication requests corresponding to that call have been
processed. During a synchronous read operation, OFS does not guarantee that all
the variables in a group will be accessed in the same CPU scan if the group is
transcribed on several communication requests. An OFS mechanism ascertains the
number of requests necessary to access the whole of a group of items (for
synchronous groups only).
The conditions that permit the items in a group to be consistent with one another
(read or written in the same CPU scan) are described in the OPC Factory Server
manual.

OPC
OFS.EXE

Application Code Interfaces OPC Server

OPC Group
OPC read/write Sync
OPC Item
Synchronous

Writing data
OPC Item
Update
OPC Item
Back to
Application Code

Data R/W Request

Client Application is blocked during DEVICES


the time the server gets data.

31006929.00 10/2005 269


Services Overview

Asynchronous In asynchronous mode, a request for any asynchronous operation receives an


Services immediate response. The operation requested has either been refused (incorrect
code response) or is underway (correct code response); it has not been completed.
The completion and the outcome of the operation is announced via the notification
mechanism. This mechanism must be activated before starting an asynchronous
operation.
Read, Write, Refresh, and Cancel operations are used to partially or completely read
and write a group of items. The client application must periodically scan the
evolution of variables (read polling). The client application is not blocked during the
time it takes to obtain the data. The activated notification mechanism then
announces the results to the client.
Synchronization with the PLC is the same as the process outlined for synchronous
services.

OPC Client
OFS.EXE
Application Code Interface OPC Server
Asynchronous READ/WRITE
OPC read/write
Event Data Ready

Back to
Application
Code Callback proc

Data available
Wait Data
Update Data

Back to
Application Data R/W
Code Request

DEVICE

Notification OFS performs read polling and notification of changes in variable values. The client
Service application needs a wake-up function programmed into it. The OFS should call the
wake-up when the values of items in periodically examined groups change.
The wake-up function must be unique in the client application. It receives all the
notifications from the OFS, then it redistributes them to the processing functions
specific to each periodically scanned group.

270 31006929.00 10/2005


Services Overview

Note: For ready-to-run supervisory software, the wake-up function should be pre-
programmed. If this is not the case, do not use the notification mechanism.
The OPC standard OnDataChange sets the name of this wake-up function. The OFS notifies
by group, not by individual items. For a given group, the OFS sends the client application
wake-up function a list of items whose value has changed. In the case of a table type item,
the OFS transmits the whole table even if only a subset of the elements has changed values.

Note: In the wake-up function, processes that take up a significant amount of CPU time (e.g.,
an overly complex display) should not be performed. These kinds of processes can adversely
affect the Operating System's performance.

The following issues relate to the notification service:


z Assigning a scanning period (rate) to a group enables you to scan the PLC
variables at different periods. For example, you can display the PLC time every
second and the temperature every minute.
z Allocate deadband to a group so that notifications are filtered when group
variable values change. Notification occurs if variables change by more than a
certain percentage of their previous value after the group scanning period. For
example, the client application is informed only if temperature changes by more
than 10%.

OPC
OFS.EXE
Application Interfaces OPC Server
Enable
Active Groups
and Items
Event Data
Back to
Application
Code Call-back
Data Available Cache
Update

Back to
Application R/W
Code Data Requests

DEVICE

Note: Deadbanding is applied only to floating-point or integer variables so that you can
control (or limit) the flow of notifications sent to the client application and thereby avoid
overloading the system.

31006929.00 10/2005 271


Services Overview

OFS Performance

Summary The following discussion describes the static characteristics of OFS and defines
some rules for generating and optimizing network requests. The purpose for these
rules is to minimize the number of requests as much as possible.

Maximum Size of The table that follows specifies the maximum number of data bytes that can be
a Request compacted into a single request. Any data items accessed in the same request are
from the same PLC cycle and so are consistent in size. The byte sizes given in the
table can be used to calculate the number of items of the same type that can be read
or written in a PLC communication request. A word takes up 2 bytes, a double word
4 bytes, and a floating-point word 4 bytes.
Count 8 bits per byte except when you are reading with a PL7 PLC on an XWAY
network, in which case each byte contains only 4 bits.
For example, on a PL7 PLC running on XIP, 248%MB, 62%MD,124%MW, or
992%M can be read in one request, and 244%MB, 61%MD, 122%MW or 1960%M
can be written in 1 request.
The following table lists the number of data bytes that can be compacted in one
Unity Pro device request:
Communication Medium Read Write
XIP 249 235
XIP Built-in channel 256 242
TCP/IP 1022 1008
PCIway 224 210
USB 1022 1008
USB X-Way (USBX) 1020 1006
Fipway 123 109
Uni-Telway 241 227
Ethway 249 235
Modbus Plus 250 236
Modbus RTU 249 235

272 31006929.00 10/2005


Services Overview

Use of Groups Dividing items into different groups can have an effect on the construction of network
requests. For each device, the items are separated into independent sets if
necessary. However, the sets are not determined by the groups themselves, but by
the Group Min update rate.

Group 1 Net Manager


XWAY

Group 2 Global Data Net Manager


Cache Modbus

Group n

Group Manager Var Manager


Client X

The groups do not influence the generation of network requests. Declaring items in
two different groups with the same update rate generates the same number of
requests as declaring items in a single group.
Requests are generated in batches made up of items belonging to groups with the
same period. They are not generated within a group.

Optimizing Each set of items is optimized individually corresponding to a device and a


Requests frequency. Optimization algorithms act in two stages:
z compacting: grouping items of the same type (with similar or consecutive
addresses) in tables. For writing, grouping is performed only if the items are
strictly consecutive. Obtain a list of elements from the original items to send to the
PLC to read or write. On Series 7 PLCs, compacting is not performed on unitary
bits; for bit tables, it is performed only if the number of bits is a multiple of 8.
z concatenating: constructing requests by optimizing the possibilities of the
protocol. Certain protocols let you define access to different types of objects in
the same request. OFS automatically adjusts the size of requests to the
maximum that is admissible.
Unity devices use both compacting and concatenating for optimization.
The located and unlocated variables in the Modbus read request generator provide
a mixing technique (read block offset length). The read request generator can mix
any variable type in the same request; one variable equals one 6-byte identifier. The
NOE module can send only 1 request per CPU scan for unlocated variables and 4
requests per CPU scan for registers.

31006929.00 10/2005 273


Services Overview

For example, sending 1 Boolean, 2 floating-point integers, and a structure with 5


integers would equal or exceed 1 request:
%MW2, %MW3, %MW40, %mX5, %MX8 => 1 request with 3 elements
(MW2 ... 3, MW40, MWX5 ... 8)

Dynamic The dynamic performance of OFS can be measured against several characteristics:
Performance z configuration response time
z read/write response time
z volume of data exchanged
z sensitivity to errors
It can also be measured along 2 lines:
z OFS communication with devices
z OFS communication with OPC clients
In certain cases, you must configure different OFS parameters to obtain better
performance; for example, if devices are accessed via different types of networks
and a lower-performance network is used somewhere on the network path. One of
the server adjustment parameters that influences performance for OFS
communication with devices is the multichannel feature.
Refer to the OPC Factory Server manual for more information about the diagnostic
window, which holds the server and communication status.

Multichannel Most of the communication protocols used by OFS are half-duplex; after sending 1
Feature request, the server waits for the answer before sending the next request. (The
exception is XWAY for Unity or PL7 PLCs.) With half-duplex networks, the only way
to speed up the communication is to open more than 1 channel between the sender
and the receiver. You can open between 1 and 16 channels for each device, and
you can configure that number either statically with the OFS configuration tool or
dynamically with the specific #MaxChannel.
The value that gives optimal performance depends on the PLC being accessed (i.e.,
the number of requests it can process per cycle) and the communication card being
used (most notably on Concept PLCs). To obtain this data, refer to the PLC and
communication card documentation.

Note: The multi-channel function is not significant for Unity Pro or PL7 PLCs that
use an XWAY (full-duplex) network and with serial Modbus drivers (single-channel
only) on any PLC types.

On half-duplex networks a parameter can be used to send several requests to a


device simultaneously; the higher the value, the better the performance for
communication with the device.

274 31006929.00 10/2005


Services Overview

Runtime Architecture for Unity/OFS/SCADA: a Simple Example

Sample The following runtime example is for simple architectures where the PLC application
Architecture does not need on-line modifications.

SCADA

XVM files
Symbols for OFS

OFS

VijeoLook is the best choice for this type of architecture. Only one PC is used to run
both the SCADA and OFS software. The maximum number of PLCs on a system
like this is five.

Runtime System On Ethernet TCP/IP only, you can locate the XVM symbols file on another PC
Options instead of the one that runs the SCADA and OFS. This option lets you centralize the
resources on one PC that can be easily backed up. This implementation may be
necessary when the system is integrated in larger architecture.

31006929.00 10/2005 275


Services Overview

Key System z The runtime system needs the Unity Pro XVM symbols file to be compatible with
Characteristics OFS. The symbols file is exported in Build mode by Unity Pro and must be copied
on the PC that is used to run the system. A symbols file is needed for each PLC
application.
z The SCADA + OFS + XVM files system runs on one PC.
z OFS accesses the data in the PLC in real time. Any discrepancies between the
running application and the local symbols file on the PC initiates signature
checking. In accordance with QoS for OFS, the communication stops or switches
to a bad quality service. You need to manually update the PC with the correct
symbols file in order to have consistency between the symbols file and the
application running in the PLC.

Product
Versions
Product Version Comments
Unity Pro M, L, XL 2.0
VijeoLook 2.6 includes the correct version of OFS

276 31006929.00 10/2005


Services Overview

Build-time/Runtime Architecture for Unity/OFS/SCADA Systems that Are Not


Frequently Modified

Sample The following example of a build-time/runtime system supports architectures that:


Architecture z do not require frequent modifications of the application
z have a low constraint on synchronization between the SCADA and the running
application during modifications
The synchronization between the Unity Pro database and OFS is managed
manually; there is static exchange of the symbols file.

SCADA
XVM files Unity Pro
Symbols for OFS
OFS

Synchronization by
static exchange

With VijeoLook as the SCADA, a maximum of 5 PLCs can be supported. For larger
configurations, use Monitor Pro. One PC is used to run both the SCADA and OFS
software. Another PC is used to run Unity Pro on the PLC applications.

Build-time/ On Ethernet TCP/IP only, you may locate the XVM symbols file on a different PC
Runtime Option than the one that runs the SCADA and OFS. This option lets you centralize the
resources on one PC that can be easily backed up. This implementation may be
necessary when the system is integrated in a larger architecture.

31006929.00 10/2005 277


Services Overview

Key System z The runtime system needs the Unity Pro XVM symbols file to be compatible with
Characteristics OFS. The symbols file is exported in Build mode by Unity Pro and must be copied
on the PC that is used to run the system. A symbols file is needed for each PLC
application.
z The SCADA + OFS + XVM files system runs on one PC.
z Unity Pro runs on a separate PC for application modifications. This PC is not
necessarily connected to the network permanently; it may be connected only for
on-line modification or XVM file copying to the OFS system.
z OFS accesses the data in the PLC in real time. Any discrepancies between the
running application and the local symbols file on the PC initiates signature
checking. In accordance with QoS for OFS, the communication stops or switches
to a bad quality service. You must manually update the PC with the correct
symbols file in order to have consistency between the symbols file and the
application running in the PLC.
The update can be triggered by the SCADA application through a specific command
mode of OFS. The application does not stop. Only the OFS communication is
interrupted during the symbols file update.

Product
Versions
Product Version Comments
Unity Pro M, L, XL v2.0
VijeoLook v2.6 includes the correct version of OFS
MonitorPro v7.2 without access to the structured variables

278 31006929.00 10/2005


Services Overview

Build-time/Runtime Architecture for Unity/OFS/SCADA Systems that Require


Frequent Modification

Sample The following example of build-time/runtime system supports architectures that


Architecture require:
z frequent application modifications
z a higher level of service for synchronization between the SCADA and a running
application during modifications
Synchronization is managed through dynamic exchanges between OFS and Unity
Pro XL. No manual operation is necessary to update the symbols file for OFS.

Unity Pro XL SCADA


SCADA
server STU files on Unity Pro
a PC server
OFS OFS

Synchronization by
dynamic exchange STANDBY

Unity PLCs

One PC is used for the SCADA, OFS and Unity Pro XL in server mode. Another PC
is used to run Unity Pro for application modifications, and a third PC is required to
achieve redundancy for Monitor Pro. The PC server for the STU application files
enables consistency to access from either the OFS / Unity Pro XL system and the
Unity Pro to the same application.

31006929.00 10/2005 279


Services Overview

Build-time/ The architecture described above is recommended for a (normal/standby)


Runtime Options redundancy system for Monitor Pro.
In architectures that do not require redundancy, the STU application file can be
located on the PC where the OFS/SCADA and the Unity Pro XL system are running.

Key System z Unity Pro XL is necessary for the operating modes of OFS; it is the only package
Characteristics able to run the server mode that is mandatory for the dynamic symbol update.
Unity Pro XL must be installed. OFS launches Unity Pro XL and opens the
application in background mode.
z The SCADA + OFS + Unity Pro XL system runs on one PC.
z Unity Pro runs on a separate PC for application modifications. This PC does not
need to be connected to the network permanently, only for on-line modifications.
z When a PC server is used for the STU application files, OFS and Unity Pro use
the same application for the modifications and synchronization.
z OFS accesses the data in the PLC in real time. It detects any discrepancies
between the running application and the local symbols file on the PC (signature
checking). In accordance with the OFS QoS, communication stops or switches to
a bad quality service.
z OFS/Unity Pro XL updates the symbols by accessing the STU file. Depending on
the OFS settings, this update can be automatic or triggered by the SCADA
application by a specific command mode in OFS. The application does not stop.
Only the OFS communication is interrupted during the symbol file update.
z When Unity Pro handles on-line modifications, the STU application file handles
the synchronization of OFS/Unity Pro XL with the right version of the application.

Product
Versions
Product Version Comments
Unity Pro M, L, XL v2.0 for the application modifications
VijeoLook v2.6 includes the correct version of OFS
MonitorPro v7.2 without access to the structured variables

280 31006929.00 10/2005


Services Overview

Build-time/Runtime Architecture for a System with Multiple SCADA Connections

Sample The following example of a build-time/runtime system supports architectures that


Architecture require:
z frequent application modifications
z a higher level of service for synchronization between the SCADA and the running
application during modifications
This architecture also supports multiple SCADA connected on one centralized OFS.
The synchronization is managed through dynamic exchanges between OFS and
Unity Pro XL. Manual operation is not needed to update the symbols file for OFS.

PC server with STU


application files

SCADA Unity Pro


Unity Pro Unity Pro

OFS

Synchronization by
dynamic exchange

One PC is used to run both OFS and Unity Pro XL in server mode. One or several
PCs are dedicated for the SCADA. Another PC is used to run Unity Pro for
application modification. The PC server for the STU application files provides the
consistency needed so that all the stations running Unity Pro can access the same,
up-to-date application information.

31006929.00 10/2005 281


Services Overview

System Option The STU application file can be located on the same PC where the OFS/SCADA and
Unity Pro XL system run.

Key System z Unity Pro XL is needed for the OFS operating modes. This is the only architecture
Characteristics that lets you run in server mode, which is mandatory for the dynamic update of
the symbols. Unity Pro XL must be installed. OFS launches Unity Pro XL and
opens the application in background mode.
z The OFS + Unity Pro XL system runs on one PC.
z The SCADA is executed on a dedicated PC and communicates with OFS
(DCOM) for real-time access to the PLC.
z Unity Pro runs on a separate PC for application modifications. This PC does not
need to be connected to the network permanently, but only for on-line
modification.
z The PC server for the STU application files provides consistency so that all the
OFS and Unity Pro stations use the same application data for the modifications
and synchronization.
z OFS accesses the data from the PLC in real time. It detects any discrepancies
between the running application and the local symbol file on the PC (signature
checking). In accordance with the OFS QoS, the communication stops or
switches to a bad quality service.
z OFS/Unity Pro XL updates the symbols by accessing the STU file. Depending on
the OFS settings, this update can be automatic or triggered by the SCADA
application through a specific command mode in OFS. The application does not
stop. Only the OFS communication is interrupted during the symbol file update.
z Any on-line modifications from Unity Pro imply saving the STU application file so
that OFS / Unity Pro XL is synchronized with the right version of the application.

Product
Versions
Product Version Comments
Unity Pro M, L, XL 2.0 for the application modifications
Unity Pro XL v2.0 for the PC server mode
VijeoLook v2.6 includes the correct version of OFS
Monitor Pro v7.2 without access to the structured variables

282 31006929.00 10/2005


Services Overview

3.13 SCADA/HMI

At A Glance

Overview This section describes the operation and design of a SCADA or HMI system. It
focuses on the use of the Modbus TCP/IP communications protocol between the
SCADA system and the end devices. The information is not specific to a particular
SCADA system or HMI package; the concepts described apply to most packages on
the market, but terms and techniques may vary between packages.

What's in this This section contains the following topics:


Section?
Topic Page
SCADA/HMI 284
I/O Server to Field Device Communications 286
SCADA Communications to Field Devices: Socket and Request Usage 290
I/O Server and Display Client Communications 294
Schneider Product Implementation Details 295

31006929.00 10/2005 283


Services Overview

SCADA/HMI

SCADA/HMI SCADA and HMI systems are represented by two models: standalone and client/
Models server.

Standalone The standalone SCADA/HMI model uses the same computer or terminal to poll and
Model display data from devices in the field. Each additional display terminal polls its own
data from the field devices. This illustration shows an HMI and a PC with SCADA
polling a PLC for data.

Switch

HMI (polling)

SCADA (polling)

Client/Server The client/server model uses a separate I/O server and display clients. The I/O
Model server polls data from the field devices and the clients display the data. Each client
obtains the data from the I/O server, not the field devices. The I/O server combines
all the requests from the display devices and gathers the required data from the field
devices to the SCADA system. As a result, the load on the network and the field
devices is lower, and the system response time improves. In some systems, the I/O
server can be the same physical device as the display device.

Note: Multiple I/O servers can be used to enable redundancy.

284 31006929.00 10/2005


Services Overview

This illustration shows that the requests from the SCADA client are being obtained
from the PLCs by the I/O server.
SCADA clients PLCs

Switch Switch
I/O server

A SCADA system may include other servers such as trending, alarms, etc. These
servers are not included in the description here because they use the I/O server to
communicate with the field devices.
The data used by the SCADA system are called tags. Tags can be used for display,
trending, alarming, reporting, etc.

Communications There are two stages of communications in the SCADA-to-device path:


in the SCADA z between the display client and the I/O server
System z between the I/O server and the PLC (or standalone system)
You may use multiple I/O servers to enable redundancy.

31006929.00 10/2005 285


Services Overview

I/O Server to Field Device Communications

Summary The way a SCADA system gathers data from the field device can greatly affect
network and device loads and overall system response times. Communications
between the I/O server and the field devices can follow several common models.
Most SCADA systems use a combination of:
z data exception reports from field devices
z I/O server polling for field status, based on user-configured groups and time
periods
z I/O server exception writes in response to operator commands
z I/O server time-based read/writes for tags used in application code

Exception Exception reporting is the most efficient but least common method for transferring
Reporting data between a field device and the SCADA system. The field device needs to be
aware of the tags the SCADA system is using and needs to monitor these tags for
changes in the field device. When a value in a tag changes, the field device writes
the new value to the SCADA. For this method to work, the field devices needs to be
able to initiate communications with the SCADA system (through a Modbus
messaging client) and SCADA system must be able to receive the data transfer
(through a Modbus messaging server).Exception reporting is used for reporting the
status of field devices for display, trending, and alarms.
Exception reporting is efficient because the same unchanged values are not
transferred over and over again (as they are in a polled system). This exception
reporting system allows the device to close the TCP socket when data values are
unchanged, thereby freeing up the TCP socket for other uses and reducing the
device load.

Exception SCADA systems normally poll data from field devices to monitor the status of each
Reporting device. The SCADA can detect and notify you of a communications failure. If the
Problems SCADA system is not polling the field device (as in an exception report system), it
cannot detect or report a communications failure. To enable the SCADA system to
detect a communications failure, it must either:
z expect write commands from the field device every n seconds
z poll the field device occasionally to check if it is on-line
An additional problem is that a write response from the field device can be lost or a
value can change while the SCADA system is unable to receive the message. In this
case, the SCADA system displays the old value but does not display a
communications error. To correct this, the field device periodically transfers the tag
value.

286 31006929.00 10/2005


Services Overview

Field Device It is not practical for a field device to individually monitor a great number of variables
Monitoring to determine if an exception report is required. Most systems use a checksum on a
group of variables. A backup write should always be implemented because the
checksum can fail. For example, multiple variables may change in a way that makes
the checksum stay the same. The field device can reduce device and network loads
by applying hysteresis to the variables and sending an exception report only when
a variable changes by a predetermined amount.

Variation on If you use a SCADA system that does not implement a Modbus messaging server
Exception or a field device that does not implement a Modbus messaging client, the SCADA
Reporting system polls only the checksum or a single bit to indicate that one or more tags in a
block of data has changed. When a change is detected, the SCADA polls the entire
data set to obtain the new values. This system is not normally supported natively
within the SCADA system. You must code it using some form of user logic within the
SCADA system.
To poll for field status, the SCADA package reads data from each field device.
Normally the SCADA package determines how the data is polled based on either:
z user-defined groups
z SCADA-created groups
If you set up the groups, you must take into account:
z how variables are grouped and their corresponding addresses in the field devices
z how often the groups are polled compared to the rate at which they are answered
z when the groups are polled: continually or as required
z how the polling of groups is linked
The groups of variables should be set up so they are polled at a rate no faster than
that which the field device can answer. To calculate this rate, consult the system
performance evaluation section (see p. 332). Remember to take into account all
other devices, including other SCADA systems, that are communicating with the
field device.
When creating groups, try to group tags so that the polling of the groups can be
turned on and off. The variables are polled only when they are required. You may
code this behavior or use an automatic feature of the SCADA system. In either case,
the alarm variables need to be placed into one group and trending variables into one
or more groups separate from the display variables. The group containing the
display variables needs to be polled only when the tags are active on a screen.

31006929.00 10/2005 287


Services Overview

When SCADA systems use an OPC server to read data from a field device, each
I/O server may create separate groups (even though each I/O server is polling the
same variables). The SCADA system may try to add/remove variables from the
groups on the OPC server. This process is inefficient because of time delays.The
preferred alternative is for the SCADA system to create a larger number of groups
with fewer variables in each group and enable/disable the groups or variables within
the groups. However, OPC servers vary in their abilities to enable/disable variables
and groups or add remove variables from a group. OPC servers may or may not be
able to block data for requests when the data is in multiple groups.
When the timing is set up for the polling of groups, make sure that the polling does
not overload the field devices. The most common method used to poll data is to set
a polling period that each group uses to read data. If this period is set to 1000, the
group tries to poll all the data every 1000 ms. A problem can occur when multiple
groups are set at the same polling rate. When the 1000 ms time expires, the SCADA
system tries to read several blocks of data from the field devices, causing spikes in
the network and field device loads. After these requests are answered, the field
device waits passively until the next time it is polled. Depending on the field device,
this overload may cause communication failure or delays.
If the device is able to buffer requests and answer them over time and if the total
average load is less than the device capabilities, then the only problem is the small
delay in answering the request.
Time SCADA Device
Requests
100 ms

Responses

Doing
Nothing

500 ms etc.
Requests

To avoid this type of communications overload, set the polling periods of the groups
to unique values. These values should be chosen so that the polling of multiple
groups does not occur too often (e.g., 500 ms, 700 ms, 900 ms). A better solution is
to link the polling of the groups. Link the polling so that one group has to finish before
another group can be polled. This solution prevents:

288 31006929.00 10/2005


Services Overview

z an overload of requests that are waiting to be answered by the field devices


resulting in communications failure
z a queue of requests forming in the SCADA system or field device
Some SCADA systems automatically link the polling of groups. Others require you
to manually implement this function.

Blocking For reading or writing the same type of data (the same Modbus function code), the
SCADA system may try to combine multiple tags into a single data transfer for
efficiency. This is not normally done for write commands, except when you are
writing tables of data.
The way a SCADA system combines values into a single read is known as blocking.
Blocking can improve the efficiency of the overall system communications.

For blocking to be most efficient, the variables in the field device should be located
so that all the data required by the SCADA system is together in the Modbus
memory area. When defining groups that the SCADA system polls, arrange the
variables inside the field device so that all variables within a group are adjacent to
each other. Even if you are not arranging the groups to be polled, arrange the
variables used for alarms and trending so they are adjacent to each other. Items that
are trended at the same rate should be grouped, and alarms should be grouped.
An exception to the data-blocking rule is unlocated variables. Both the Unity and
Concept software allow variables in the field device to exist without physical
addresses. A specific Modbus messaging function code can read/write these
variables. The variables cannot be located next to each other, but the SCADA
system can read/write them as efficiently as a block of located variables. However,
some devices are able to answer requests for located variables faster or more often
than for unlocated ones.

31006929.00 10/2005 289


Services Overview

SCADA Communications to Field Devices: Socket and Request Usage

Summary You need to consider several factors to determine how your SCADA system may
transfer data to a field device:
z how the data groups are structured
z when another section attempts to read the data groups
z TCP sockets and how they are used
z the number of Modbus messaging requests that can be sent down each socket
z the types of requests used
A SCADA system can open one or more TCP sockets to a device. It can send
Modbus messaging requests on each of these sockets. Depending on how the
SCADA system is designed, it may allow you to control the number of sockets to be
opened and how the requests can be sent, or it may only perform as designed with
no customizing possible.
Typical SCADA systems use a combination of 3 methods, with several sockets in
use and one or more requests on each socket. Commonly one or more sockets are
set up for reading and writing data. A request queue can form in both the end device
and the SCADA system.

290 31006929.00 10/2005


Services Overview

One Request at a The efficiency of the SCADA system in sending requests and processing responses
Time has a large impact on the system response time. Here is an example of a single
socket that supports one request at a time:

Only one request answered at a


time

15 requests Unused capacity for 15


unable to be additional answers
sent

The SCADA system only opens a single socket to the field device and is able to send
only a single request. It waits until this request is answered before the next request
is sent. This prevents overload in the end device by limiting the system to only one
request at a time in the end device. It also severely affects system response time.
For example, if the SCADA system has 10 requests to send to the end device, the
end device takes 100 ms to answer each request and an additional 50 ms to send
the new request. The overall time to answer all requests is 1.5 s.

31006929.00 10/2005 291


Services Overview

Multiple Here is an example of a single socket that supports multiple requests, in this case
Requests on a 10:
Single Socket

10 requests answered
in parallel

8 requests unable Unused capacity for 6


to be sent additional answers

The SCADA system opens a single socket to the field device but is able to send 10
requests to the end device without waiting for an answer. The end device can start
answering all 10 requests without delay. This system provides a faster response
time, but can also overload an end device if the device cannot handle 10 requests
at once. Even if the device can handle the 10 requests, it may not be able to handle
more than one request at a time on a single TCP socket. This is common in older
devices or devices that do not use the Modbus TCP transaction ID. The response
time of the system is 150 ms, instead of 1.5 s as in the previous example.

292 31006929.00 10/2005


Services Overview

Multiple Sockets Here is an example of a SCADA system that uses 10 separate sockets to send
Sending One requests to the field device but only sends a single request down each socket. This
Request at a system handles devices support only a single request per socket.
Time

10 requests answered
in parallel

16 sockets established

This system avoids problems with devices that are unable to handle multiple
requests on the same socket, but the end device may still become overloaded due
to the total number of requests. The system response time is 150 ms.

31006929.00 10/2005 293


Services Overview

I/O Server and Display Client Communications

Client communications between an I/O server and a display are commonly based
on one or more of the following:
z proprietary systems and protocols
z OPC client/server communications
z MS Windows communications
Because most SCADA-to-SCADA communications rely on some form of MS
Windows networking service (Com/DCom, machine names, etc.), this service must
be installed on the network. However, by installing this type of service, the network
becomes loaded down with additional MS Windows traffic and is susceptible to
overloads by MS Windows and other traffic.
SCADA-to-SCADA communications should be separated from the normal device
communications network whenever possible. You can do this by installing separate
Ethernet cards into the SCADA PCs and running a separate Ethernet network for
SCADA-to-SCADA communications.

294 31006929.00 10/2005


Services Overview

Schneider Product Implementation Details

VijeoLook VijeoLook uses the Schneider OPC server for communications (see p. 265).
Implementation

Monitor Pro Monitor Pro supports the I/O server/multiple clients model. When using the Modbus
Implementation TCP/IP communications system, Monitor Pro implements user-defined groups,
allowing you to configure the tags to be read in each group. You can trigger the
reading and writing of each group via a user-defined tag. It can be a time-based tag
for reads or a customized tag. For writes, the tag is automatically set whenever an
item in the group is changed and only that item is written. For reads, the entire group
is read. Groups can be sequenced by preventing the control tag for one group from
being triggered before the completion flag is set for the previous group.
Monitor Pro uses a TCP socket for reads, a separate socket for writes, and another
separate socket for exception reads. Each socket allows a single Modbus
messaging request to be outstanding on the device at a time.
You can create an additional instance of the Modbus communications task and
spread the variables to be read between the two tasks. Because additional requests
can be sent to the field device at the same time, system performance is faster.
Monitor Pro creates a queue inside itself for any communications requests that are
triggered but cannot be sent to the PLC because of outstanding requests on a
socket. These requests go into the Modbus TCP/IP task mailbox. The mailbox can
eventually overflow and cause communications to cease.

31006929.00 10/2005 295


Services Overview

3.14 Redundancy

At a Glance

Overview This section covers service redundancy from a system perspective. Total system
redundancy is affected by the network, the devices, and the service redundancies.

What's in this This section contains the following topics:


Section?
Topic Page
Network Redundancy and Communication Services 297
Redundancy within a SCADA System 301
SCADA in a Quantum Hot-Standby System 304
Hot Standby Swap and Ethernet Services 311

296 31006929.00 10/2005


Services Overview

Network Redundancy and Communication Services

Summary Redundancy allows the network to continue to carry data in the event of the failure
of a network component or cable. When a failure occurs, some amount of time
elapses before the failure is realized and corrected by the network components. This
correction may or may not occur before other systems notice the problem.
Data being carried across the network may or may not be lost during the failure. If
data is lost, it must be retransmitted.
If the network can recover before the time-out time for a service and if no data is lost
during the break/recovery, the services are not affected. If the network cannot
recover before the service time-out time, the service abandons the individual
request. The service may or may not retry the transfer (depending on the service),
but you will experience some delay in the information transfer. If the service
implements retries, you do not notice an application error because the service is
able to pass the data sent before the application error.
If the network cannot recover before the retry/time-out times, the service registers
an error to the application. You need to decide if the application can tolerate service
time-outs and errors or if the network should recover before a service time-out or
error occurs. Be aware of the service time-outs and retry times before selecting a
network redundancy strategy. A faster network recovery time is generally more
expensive and it may not be needed in your application.

Multiple Ethernet Multiple Ethernet interfaces in a device are resilient when one of the Ethernet
Interfaces in a interfaces fails or when the attached network fails. However, they also require the
Device communications to and from the device to be managed so all other devices can
communicate to the active interface. If two Ethernet interfaces are installed in a
device, there are two methods for handling communications: two linked interfaces
or two independent interfaces.

31006929.00 10/2005 297


Services Overview

Linked Interfaces Two linked interfaces share the same IP address, and they appear to be a single
Ethernet interface to the rest of the devices on the network. The two interfaces
automatically monitor their ability to communicate with the rest of the system and
decide which one is available to the device and the outside network. Enabling this
solution requires no extra work.
Linked interfaces are commonly found in PC systems. They are similar to Modbus
Plus redundant ports in that you do not need to act to benefit from the two interfaces.
The interfaces monitor themselves and decide which interface to present to the
outside network and to the device (so they see only one interface). Several Ethernet
cards for PCs provide this functionality and their use is recommended.

2
1

1 Interface 1 provides a single presentation to the SCADA and the PLC; it monitors the
health of interface 2 to be sure that interface 2 can take over if it should fail.
2 Device 2 monitors the status of interface 1 and shares the same IP address as interface 1.
It does not present information to the SCADA and PLC unless interface 1 fails.

298 31006929.00 10/2005


Services Overview

Independent Each interface has a different IP address; only one interface is active at a time. This
Interfaces method of implementing multiple interfaces normally requires that you monitor the
health of the interfaces within their application and decide which interface should be
active. For example, with a SCADA package that has two unlinked Ethernet cards
installed in a PC, the system monitors both interfaces and chooses one. Another
example is that of two ETY modules in a Premium PLC. All Schneider Automation
devices use this method.
You need to monitor the health of each interface and decide how to handle
communications so that exchanges are not duplicated. Monitoring can reduce
network traffic and load on other devices, but controlling communications in this way
may not always be possible. If both interfaces need to be active (for global data, for
instance), both interfaces process exchanges and pass the results to the device/
application; the application must decide which information to use. Here is a Premium
PLC with two Ethernet ETY communications modules:

2
1

1 Interface 1 has its own IP address and appears as an independent device on the network
2 Interface 2 also has its own IP address and appears as an independent device on the
network
In systems like the one shown above, you may be unable to control how
communications are issued from each device because you cannot control which
interface is used. This is a common problem for PCs configured with two Ethernet
cards. The PC chooses a card to send data to based on the network on which the
card is connected (as defined by the IP address and the subnet mask). The PC
attempts to send requests through the card connected directly to the destination
network. If a PC is configured with two Ethernet interfaces that have different IP
addresses on the same network, the PC does not know which card to use. As a
result, communications are erratic and can fail.

31006929.00 10/2005 299


Services Overview

To avoid this problem, configure each Ethernet card for a separate network address
range and manually control communications by addressing the communications to
one network or the other. Unfortunately, the two Ethernet cards using different IP
networks (even if they are connected to the same physical network) cause problems
communicating with remote devices. The devices may not be able to communicate
on both networks at the same time. Two complete networks must be constructed,
and all the devices must be connected to both networks. You must determine which
network is active through network management.
The following illustration shows a PC with two Ethernet cards going to the same
switch and a PLC with two ETY modules connected to the switch.

1 A decision block inside the SCADA or PC program


2 Network B
3 Network A
Two independent networks supply a high level of redundancy, but a decision block
must be included in the SCADA or PC program to determine which network to use
at any given time.

300 31006929.00 10/2005


Services Overview

Redundancy within a SCADA System

Summary Multiple levels of redundancy are available within a SCADA system. For plant
communications, the SCADA system should operate so that only the primary I/O
server exchanges data with the field devices. This provides the following benefits:
z greatly reduced communications load on the field devices, resulting in faster
response times for the entire system
z reduced network traffic at the interdevice level of the plant.
z more efficient network traffic as the SCADA server-to-client traffic can be
optimized (to transfer all data to a client instead of the client gathering information
from each field device); traffic can be separated onto another network instead of
the plant control network
The following illustration shows three redundant SCADA systems polling the PLC:
1

Primary I/O server 2


Display clients

Back-up I/O server

I/O server 1 3
Display clients

I/O server 2

1 Two separate SCADA systems, both polling the PLC


2 Two display clients polling a primary I/O server. The back-up I/O server only monitors the
health of the connections to the PLC
3 Two display clients polling an I/O server, where the I/O server does not know that there is
redundant back-up. It continues to poll all data from the PLC.

31006929.00 10/2005 301


Services Overview

SCADA SCADA system planners need to consider redundancy from communications to


Communication redundant devices. For a redundant device to communicate, the SCADA system
to a Redundant must be able to exchange the same data with what it considers to be two devices.
Device For example, a Quantum PLC system that contains two NOE modules allows the
SCADA system to exchange data with the PLC CPU using either NOE module. If
one module fails (or the network attached to this module fails), communications
continue using the other NOE module.
The SCADA system may be able to automatically manage communications to
redundant devices or you may need to manage communications manually. For
automatic management within the SCADA, you need only to enable the service and
configure the SCADA system to recognize that the two devices are the same. If this
support is not native to the SCADA, you must perform additional configuration and
programming to make the system communicate to the devices on both interfaces.
The most common problem is that the SCADA system is configured to communicate
to the Ethernet interface of the end device, not to the end device itself. The SCADA
system should view a Quantum PLC with two NOE modules (e.g., IP address
192.168.1.10 and 192.168.1.11) as two separate devices, even though the SCADA
requests are exchanged with the same CPU.
The following illustration shows a SCADA system communicating to a PLC with two
Ethernet interfaces. The SCADA assumes that there are two PLCs, and it must
decide the one with which it will communicate.

3
1

1 Data for both exchanges comes from the same variables in the PLC.
2 The PLC has two interface modules.
3 Two sets of data are exchanged.
The SCADA system needs to be able to retrieve the values it needs to display from
one device or the other without affecting the final display of data. If the path to one
device is unavailable, use the path to the alternate device or backup until the original
path is available.

302 31006929.00 10/2005


Services Overview

SCADA Back-up A back-up device configured in a SCADA system is beneficial only when the system
Watchdogs can reliably change over to the backup device if the primary device fails. The back-
up device must be continually monitored to make sure it is operational; data from the
back-up device needs to be read periodically so that the SCADA knows the health
of the back-up at all times. Monitoring helps by:
z alarming a back-up failure while the primary is in use so the failure can be
corrected before the back-up is required
z allowing the SCADA system to check the status of the backup before deciding to
switch over
If the primary fails and the SCADA system switches to a failed standby, it may cause
confusion among personnel, as well as waste time and stop your application.

31006929.00 10/2005 303


Services Overview

SCADA in a Quantum Hot-Standby System

Summary Hot standby systems were traditionally implemented to control critical remote I/O in
industrial automation environments. As SCADA systems continue to develop and
play a more important role in plant operation, the role of a hot standby system has
changed. A hot standby system may be required to provide redundant operation of
control networks and SCADA communications. New hot standby control rules need
to be defined.

Traditional Hot In a traditional industrial automation system, the single goal of a hot standby PLC
Standby System was to control the plant via physically connected I/O:
1 2

3
1 The primary CPU
2 The standby CPU
3 Racks of remote I/O modules
Hot standby provides redundant control of a plant via physical I/O. The system
changes from the primary CPU to a standby CPU if the primary unit is unable to
control the physical I/O. This can occur due to the failure of the primary system’s:
z power supply
z CPU
z RIO adapter
z RIO link
A traditional hot standby system does not switch control from the primary to standby
for any of the following reasons:
z failure of Modbus Plus or Ethernet links
z inability of the primary system to communicate to a remote device via a network
link (other than I/O via the RIO network)
These restrictions present problems for a system that relies on SCADA system
communications or plant control via network communications. In the event of a
communications failure of the primary PLC, the system does not automatically
switch over to the standby unit to re-establish communications, even if each PLC is
capable of controlling the I/O.

304 31006929.00 10/2005


Services Overview

Communication- In a communication-centric system, the integrity of the communications between the


centric Systems hot standby system and a device in the plant system may be important enough to
justify a hot standby changeover. In this type of system, the standard Quantum hot
standby operation must be modified so that the communications to the remote
device are monitored and a changeover is forced if communications fail.

Note: You may implement a hot standby system for communications purposes only. Such a
system is not required to control physical plant I/O. A dummy I/O rack must be configured,
and the RIO network needs to be physically installed to allow the hot standby system to
operate.

The following illustration shows a redundant SCADA system with hot standby PLCs.
1

3 4

5
1 SCADA monitoring a critical process controlled by the PLC
2 Critical intelligent devices controlled via Ethernet by the PLC
3 The primary CPU
4 The standby CPU
5 Racks of remote I/O modules
The original industrial automation priorities of the hot standby system, which provide
redundancy for the remote I/O, remain the same. In addition, you can assign equal
(or even greater) hot standby priority to the plant’s communication link.
Although the Quantum hot standby system was originally designed principally for
I/O control, full user control of the changeover capability is provided. You can
customize the operation so that communications failures at the plant level trigger a
primary-standby changeover. You can program your system to switch control if the
current primary CPU loses communications with the SCADA platforms or with the
critical Ethernet devices, even if there are no communication problems between the
CPU and the remote I/O.

31006929.00 10/2005 305


Services Overview

Rules for a The following questions must be answered to enable a communications based
Communication- HSBY system to be implemented:
centric Hot z What communication links must be monitored?
Standby System In the event of a failure, should the links cause a changeover of the hot standby
PLCs?
z What defines a communication failure (time-outs, retries, etc.)?
z Will redundant Ethernet interfaces be implemented?
If so, how will they be addressed?
z How will the health of the communications network on the Standby PLC be
monitored to be sure that a changeover improves communications?

Basic Redundant To achieve basic communications redundancy for a minimum investment in extra
System hardware and time, the system should have:
z a single network connection to each PLC in the hot standby system
z network connections monitored using the module diagnostics functions

Basic Changeover can be set up to occur if the primary CPU cannot locate a SCADA
Redundancy platform or if the connection between the CPU and the Ethernet switch fails.
System However, hot standby PLCs cannot detect a communications failure due to a break
Limitations in the network beyond their local connection.
1
2

3 4

1 SCADA monitoring a critical process controlled by the PLC


2 Ethernet switch
3 The primary CPU
4 The standby CPU
5 Racks of remote I/O modules
The failure of a single critical device beyond the local connections can cause the
failure of the entire communications system as shown in the illustration above.

306 31006929.00 10/2005


Services Overview

Fully Redundant A fully redundant system must be implemented when the specification calls for no
System single point of failure for the control system, including communications.

1 Redundant SCADA system with dual linked Ethernet interfaces


2 Switch-based network with spanning tree
3 ConneXium redundant ring network
4 Hot standby PLC system with dual independent Ethernet interfaces
A fully redundant system typically uses the following:
z additional network hardware installed for redundant network paths
z each PLC in the hot standby system connected to a separate network path
z each PLC connected to the network at multiple points using multiple network
cards in the PLC (for a network or network card failure that does not trigger a
changeover)
z communications paths monitored by watchdogs for communications integrity
along the entire path to the end devices
z other devices (such as the SCADA system) connected to the network at multiple
points using multiple network cards
z optionally, a complete second physical network
z each connection point (switch or a hub) for a device (e.g., PLC, SCADA system,
etc.) powered from a separate power supply so that the failure of a single power
supply does not disconnect the device from the network

Fully Redundant Fully redundant systems have the following limitations:


System z increased cost of components
Limitations z the need to modify systems outside of the hot standby PLC
z system complexity

31006929.00 10/2005 307


Services Overview

Network The status of the local Ethernet communications module can be monitored by the
Monitoring via PLC program using the MSTR or MBP_MSTR block to read local statistics. These
Module Status blocks provide information on the health of the module and of the Ethernet link from
the module to the first hub or switch.
Word 3 of the returned data is defined as the board status.
Bit # Definition
15...12 Module type
11 (Reserved)
10 0 = half duplex 1 = full duplex
9 0 = not configured 1 = configured
8 0 = PLC not running 1 = PLC/NOE running
7 0 = Link LED off 1 = = Link LED on
6 0 = Appl LED off 1 = Appl LED on
5 0 = twisted pair 1 = fiber
4 0 = 10 Mbit 1 = 100 Mbit
3...0 (Reserved)

Bit 7 (Link LED on) can be monitored to determine the status of the connection from
the module to the local hub or switch. If the Ethernet module is faulty, an error is
returned by the Read Local Statistics command.

Note: The Read Local Statistics command monitors only the local connection. It
does not ensure that the full network required to communicate to a remote device
(such as additional hubs or switches that are used to connect to the other device)
is intact. It does not check the operation of the remote device. Device monitoring
by watchdogs is a more reliable way to determine the health of communications to
a remote device.

308 31006929.00 10/2005


Services Overview

Device To completely monitor the operation of a remote device and the connection to it, a
Monitoring via watchdog should be implemented. To implement a watchdog from a SCADA system
Watchdogs to a PLC, send a single write register from the SCADA system to a register in the
PLC. The PLC increments this register, the SCADA reads the new value back,
increments the value again, and writes the value. The cycle runs constantly.
The watchdog monitors the operations of the full network link between the two
devices and the operations of the PLC and the SCADA systems. It informs both
devices of a device or network failure. A simpler watchdog can be implemented by
having the PLC read a value from a remote device or by reading a value that
changes in a known way (such as a counter) from the remote device. These two
methods check the network link, but do not enable the remote device to know the
PLC status.

Note: When implementing watchdogs via a register that is incremented, be sure to


account for the situation when the register rolls over (e.g., from 32767 to 0).

Standby Unit When implementing a hot standby system where communication links are
Monitoring monitored and where a failed link may trigger a changeover, you need to know the
status of the standby link. All nonoperational links should be monitored (back-up
links on primary and all links on the standby PLC) to detect and correct link failure
before the link is needed.
The standby link status should also be known so the PLC can determine if the
changeover re-establishes communications. If communications are not re-
established, the changeover will not improve plant control redundancy. Also, a
changeover can affect other devices.
The standby communication links in the primary PLC are monitored in the same way
as the primary link. They can be monitored with a Read Local Statistics
command or with a full watchdog. A full watchdog for the standby PLC is different
from a watchdog on the primary PLC because the standby PLC is not always
processing code.
Use the reverse transfer registers of the hot standby system to transfer the register
written by the SCADA system to the primary PLC and increment the register there.
Then transfer the register either back to the SCADA system using the primary PLC’s
communication links or back to the standby PLC using the hot standby link where
the SCADA system reads the result. Current Quantum hot standby systems allow a
small amount of code to be executed in the standby PLC. The code can be used to
execute the Read Local Statistics command and place the results in the
reverse transfer registers for transfer to the primary PLC.

31006929.00 10/2005 309


Services Overview

PLC IP In a Quantum hot standby system, the IP address of the Ethernet modules in the
Addresses standby rack is automatically set to the IP address of the Ethernet module in the
primary rack plus one. For example, if the NOE module in primary rack is address
192.168.1.10 then the NOE in the standby rack is 192.168.1.11. When the system
performs a changeover, the IP addresses of the Ethernet modules also swap. This
simplifies communication programming for other devices since they can always
communicate to a single IP address. This feature is available with the exec version
2.0 or greater of the NOE 77100/10 modules.

Manual Hot The PLC code in a Quantum PLC can initiate a hot standby system changeover with
Standby PLC the Hot Standby control word. To cause a change from primary to standby, the
Changeovers primary PLC sets the bit to indicate that it is offline. After changeover, the new
primary PLC can be used to set the original PLC back online. Since there is already
a primary PLC running in the system, the original primary PLC comes back on line
as the standby PLC.

Note: Manually setting the primary PLC offline to force a changeover works only if
the standby unit is available and able to go online. Make sure the PLC code checks
this using the hot standby status word before a change is initiated by the PLC code.
Failure to do so may result in both PLCs going offline.

Common Hunting is the term used for a problem in a hot standby system implemented with
Problem multiple communications paths. It describes a situation where one device (e.g., the
(Hunting) SCADA system) is attempting to communicate using one communications link (e.g.,
to the Standby PLC) to determine if that link is the correct one. The primary PLC
waits for a good SCADA system communications watchdog. Since neither system
is able to receive a valid communications watchdog, each attempts a new path. If
both systems swap at the same time, they only continue to swap and never establish
communications on the same link.
To avoid hunting:
z monitor all the active communications links for watchdogs, including the links in
the Standby PLC.
z establish a clear system master such as the primary PLC. If the primary PLC sees
communications to the SCADA system on both primary PLC links and standby
PLC links, it does not change over. It waits for the SCADA system to establish
communications on the correct link (in this case a link to the primary PLC).
z set different amounts of time for the SCADA system and the PLC to try a
communications link. If the PLC is the system master, it should wait and monitor
its current link for the amount of time required for the SCADA system to attempt
communications on all the possible links. Only after this time should the PLC
switch to another communications link.

310 31006929.00 10/2005


Services Overview

Hot Standby Swap and Ethernet Services

Services The following services are available in a hot standby system:


Available
Service Description
Modbus Client Running in both primary and standby. Only the first section of PLC
application is running in the standby to trigger Modbus client requests.
Modbus Server Running in both primary and standby. Requests to the standby PLC are
processed by the standby CPU; Modbus write data may be overwritten
by the hot standby data transfer.
I/O Scanner Running in primary, stopped in standby
Global Data Running in primary; standby may send some maintenance messages at
start-up but does not publish or subscribe to data
FTP/TFTP Running in both primary and standby
SNMP Running in both primary and standby
SMTP Running in both primary and standby; e-mail messages in the standby
can be triggered only in first section of PLC application (the only section
running)
NTP Running in both primary and standby; primary Ethernet communications
module sets the clock in the primary CPU, standby Ethernet
communications module sets the clock in the standby CPU. The NTP
clock is not transferred between primary and standby CPUs.
Web (Embedded Running in both primary and standby as independent services
and FactoryCast)

Services not The faulty device replacement service (see p. 210) is not available because the
Available DHCP server is not available.

Changeover If there is a changeover from the primary to the standby PLC, the IP swapping
Operation function automatically assigns the IP address of the Ethernet communications
module in the primary PLC to the Ethernet communications module in the standby
PLC. The changeover is transparent to other network devices. After closing the
current client/server and I/O scanner connections on Ethernet using a reset, each
Ethernet communications module sends a UDP changeover message to the
Ethernet communications module in the other PLC. The Ethernet communications
module that sent the message waits for the response from the other Ethernet
communications module or for a time-out of approximately 500 ms. As soon as the
message is received or after the time-out, the IP address changes over.

31006929.00 10/2005 311


Services Overview

During the changeover any Modbus messaging communications currently in


progress (either client or server) are aborted and must be resent. Any MSTR or read/
write blocks in the PLC application must be retriggered, and any remote requests
(e.g., SCADA) must be resent by the remote device.
I/O scanning needs to re-establish the MAC address (using ARP requests) and
socket connections to each remote device before data transfers resume. The time
required depends on the time it takes the remote device to respond to the new
socket-open request.

Note: Each line in the I/O scanner is an independent entry; each begins data
transfers at different times. The IO scanner needs only the MAC address and
socket for the device listed on a line before it starts communicating with the device.
As a result, the I/O scanner starts to communicate with each device when each is
ready, rather than waiting for all devices to be ready.

For global data service, the standby NOE leaves the global data group and the new
primary joins the group and starts publishing. The time required for this is dependent
on the implementation of multicast filtering (see p. 139) and the number of devices
in the group (global data start-up times).
All other services force clients to disconnect (either by reset or time-out). Services
are restarted on both the primary and standby Ethernet communications modules.
As a result, services are unavailable for a short amount of time, but overall system
operation is not affected. For example, the NTP service restarts, but the CPU clock
remains accurate for the time required to restart the service. A Telnet session is
disconnected, and you must reconnect.
The most recent versions of distributed I/O on Ethernet TCP/IP have a function for
maintaining the status of the outputs when there is a break in communications (such
as a hot standby changeover). Devices controlled by distributed I/O continue to
operate during the changeover.

TCP Socket In all cases, the TCP source sockets used on the new module and the old module
Numbers should be different. Different sockets prevent confusion between the old and new
connections to the remote device.

312 31006929.00 10/2005


Services Overview

3.15 Gateway/Bridge Systems

At a Glance

Overview This section describes gateway and bridge systems.

What's in this This section contains the following topics:


Section?
Topic Page
Gateway and Bridge Overview 314
Gateway and Bridge Operation 318

31006929.00 10/2005 313


Services Overview

Gateway and Bridge Overview

Summary A gateway allows devices on one network to communicate with devices on a


separate network by converting the protocol on one side to the protocol on the other.
Gateways (also known as bridges) are used in an Ethernet system to convert from
one type of network to another (e.g., coaxial Ethernet to twisted pair, token ring to
Ethernet).
The following illustration shows protocol A on one side and B on the other with a
message going from one side to the other.

Gateway

Conversion of protocol A
to protocol B

Network A Network B

Operation Gateways can be grouped into 3 different types, based on how devices are enabled
on the 2 connected networks to communicate, as follows:
z gateway without protocol conversion
z gateway with protocol conversion
z gateway using shared memory (read and write)

314 31006929.00 10/2005


Services Overview

Gateway without A gateway without protocol conversion is able to take a message from the source
Application network and pass the same message onto the destination network without
Protocol modifying the application protocol. The gateway waits for a response, then passes
Conversion this response back to the source network. This type of gateway is the most efficient
and powerful implementation because no limits are put on the protocol. However,
this gateway is possible only if both the source and destination networks use the
same application-layer protocol. Schneider’s Modbus Ethernet-to-Modbus serial
and Modbus Ethernet-to-Modbus Plus gateways are examples of this gateway type.

Note: A minor modification of the application message is made in conversion from


Modbus Ethernet to Modbus Plus or Modbus serial; a bridge index and transaction
ID are included in a Modbus Ethernet packet, but these are not present at the
applications layer for Modbus Plus or Modbus serial. On Modbus Plus, the bridge
index is part of the addressing used by the lower layers. On Modbus serial, the
index is not required. A transaction ID is not required on either system.

This type of gateway receives the packet containing the application layer message
and removes the lower layers before passing the message to the destination
network. Because the actual message is not interpreted, the total system response
time can be lower, and you can use functions supported by both networks.

Gateway
Network A Network B
Layer 7 Application

Layer 6 Presentation

Layer 5 Session

Layer 4 Transport

Layer 3 Network

Layer 2 Data Link

Layer 1 Physical

31006929.00 10/2005 315


Services Overview

Gateway with A gateway with protocol conversion takes a message from the source network, and
Application converts it to the appropriate destination message format, and sends it to the
Protocol destination network. The gateway then waits for a response and converts the
Conversion response before sending it back to the source network. The gateway actually reads
the application message from the source network, but refers to an internal table to
find the message to be sent onto the destination network.
This conversion is required when the source and destination networks do not use
the same application layer protocol. Gateways that use this system include those
that connect Modbus networks to networks from other vendors. Because the
message from the source network must be received and interpreted before an
outgoing message is sent, this type of gateway is slower than a gateway that does
not do application protocol conversion.
The rules for protocol conversion are based on rules defined by the gateway
designer; only messages identified by the designer can be converted. Messages
defined after the gateway is designed are not converted. You cannot normally
modify the mapping of messages from one network to the other. This type of
gateway is only able to map a simple message for which there is an equivalent on
both networks. Messages with no equivalent on the other network cannot be
mapped. As a result, it is not possible to program over this type of gateway.
Gateway
Network A Network B
Request Mapped request

Mapped Response
response
read = read A

write = write A

connect = N/A

program = N/A
Mapping

316 31006929.00 10/2005


Services Overview

Gateways Using Some gateways can present a shared memory area to devices on both networks.
Shared Memory Devices on both networks can read or write data from this memory area and can
share data although no message is actually passed from one network to the other.
A device on the source network can write data to the shared memory area, and a
device on the destination network can then read the data from that memory area.
A gateway of this type never actually passes a message from the source network to
the destination network. No programming is required, and no complex messages
are transferred. Only data using the memory types presented in the shared memory
area can be transferred. For example, if only words are supported, the transfer of
individual bits is not supported.
This gateway decouples the two networks. Because it does not wait for a response
from the destination network before it responds to the request, this gateway can
respond very quickly with data from its shared memory area. Although this gateway
appears to be very fast, the actual response time is slow because all data must be
handled twice, once into shared memory and once out to the other network. These
two tasks are not synchronized, so system response time is slow and inconsistent.

Gateway

Network A Network B

Internal register area

31006929.00 10/2005 317


Services Overview

Gateway and Bridge Operation

Queues If devices on the source network are sending requests to the gateway faster than
they can be processed on the destination network, a message queue forms inside
the gateway. Depending on the actual gateway, the queue may have a fixed
maximum length. Once the queue is full, the gateway either crashes or returns a
new message request with an error response.
Consider the response time of the destination network and the effect of a timeout as
it pertains to the queues inside the gateway of the destination network. To help
prevent a queue from growing to unreasonable lengths, requesting devices should
not send a retry of a message before the gateway has processed the message; they
must wait until either a response or error message is received before sending the
retry. Devices must keep track of the number of messages sent to the gateway for
which they have not received answers; this number needs to be kept low.
The queue affects the system response time. If a source device sends a command
to the destination network device, the command must wait in the queue until all
pending messages are sent before it can be processed. This can create slow system
response times.

318 31006929.00 10/2005


Services Overview

The best response times are achieved when the queue is never empty and never
longer than 1 or 2 messages.

1 2
3

1 request pending
2 response
3 response to client
4 all requests move up in the queue
5 a new request is placed at the end of the queue

Gateway Sockets A gateway enables a large number of devices on one network to communicate with
a large number of devices on another network. When a large number of devices
connects to an Ethernet network gateway, a large number of TCP sockets must be
opened. For low-cost gateways, the number of sockets is limited by the low
processing power and low memory of the components chosen. Once the number of
sockets is exceeded, no additional devices can connect to the gateway. Problems
can be caused when:
z the requesting devices choose communications services that require a TCP
socket for every device they communicate with
z services hold a socket open after communications have finished
Examples of these are the I/O scanner service and the Modbus client service on
older devices. To reduce the number of sockets held open on a gateway, use the
enable/disable function in the I/O scanner or Modbus client requests.

31006929.00 10/2005 319


Services Overview

Gateway When a gateway sends a message onto the destination network, that message
Timeouts follows the timeout and retry timings of that network. However, the requesting device
has sent a message to the gateway that is following the timeout and retry times of
the source network.
If the total time for the timeout and retries on the destination network is longer than
the timeout of the source network, the source network resends the request.
Duplicate messages are placed in the queue. When Modbus TCP/IP is the source
network, there is no application layer retry; as long as the gateway acknowledges
the TCP packet, there is no retry on the source network. However, you may
manually resend the same message.
If the first message in the queue is sent to a disconnected device, that message
times out and is retried. All other messages in the queue are delayed and possibly
timed out by the requesting device. If these messages do time out, the requesting
device may resend the message, causing multiple messages in the queue. When
the initial message is answered by the gateway, it is discarded by the requesting
device, because this message has already been timed out.
To avoid this situation, the timeout for any messages sent from the source network
needs to be set greater than:
timeout x the number of retires on destination network x the maximum number of
requests expected in the queue
Avoid having this number become too long. Set the number of retries on the
destination network to a low value and do not send request to devices that are
known to be unavailable. If a device is normally polled every 5 s but has returned 2
errors in a row, check that device only once every 30 seconds to see if it is able to
respond again.

Response Times Response times for Schneider Gateway systems are shown in Appendix A (see
p. 387).

Common Common problems with gateway systems include:


Problems z overloaded gateways caused by source network devices sending requests faster
than they can be processed on the destination network
z communications errors to one or all destination devices when a single-destination
device is removed; caused by time-outs that affect how quickly communications
are processed on the destination network and produce overloads
z timed-out requests from the source device before the message is processed on
the destination network; caused by setting incorrect time-out values or by a failure
to consider the effect of message queuing in the gateway
z inability to connect to the gateway because all the socket connections are in use

320 31006929.00 10/2005


Services Overview

3.16 Supported Services per Device

Ethernet Services and the Transparent Ready Devices that Support Them

Quantum The following table lists the Ethernet services supported by the Quantum CPUs with
Devices embedded Ethernet ports and by the Quantum Ethernet communications modules:
Service 140CPU65150 140CPU65160 140NOE77101 140NOE77111 140NWM10000
I/O Scanner X X X X -
Modbus Server X X X X X
Modbus Client X X X X X
Global Data X X X X -
FDR Server X X X X -
FDR Client - - - - -
BootP Client X X X X X
Time Synchronization - - - X -
E-mail Notification X X X X X
Web/Embedded Diagnostics X X X X X
FactoryCast Web Server - - - X X
FactoryCast HMI Web Server - - - - X
SNMP X X X X X
FTP Server X X X X X
TFTP Server X X X X -
Telnet Server X1 X1 X1 X1 X1
1
For factory diagnostic purposes only.

31006929.00 10/2005 321


Services Overview

Premium CPUs The following table lists the Ethernet services supported by the Premium CPUs with
embedded Ethernet ports:
Service TSXP571634M TSXP572634M TSXP573634M TSXP574634M TSXP575634M
I/O Scanner X X X X X
Modbus Server X X X X X
Modbus Client X X X X X
Global Data X X X X X
FDR Server X X X X X
FDR Client - - - - -
BootP Client X X X X X
Time Synchronization - - - - -
E-mail Notification X X X X X
Web/Embedded Diagnostics X X X X X
FactoryCast Web Server - - - - -
SNMP X X X X X
FTP Server X X X X X
TFTP Server X X X X X
Telnet Server X 1 X1 X1 X1 X1
1
For factory diagnostic purposes only.

322 31006929.00 10/2005


Services Overview

Premium The following table lists the Ethernet services supported by the Premium Ethernet
Ethernet communications modules:
Communications
Service TSXETY4103 TSXETY110WS TSXETY5103 TSXWMY100
Modules
I/O Scanner X - X -
Modbus Server X X X X
Modbus Client X X X X
Global Data X - X -
FDR Server X - X -
FDR Client - - - -
BootP Client X X X X
Time Synchronization - - X -
E-mail Notification X - X X
Web/Embedded X X X X
Diagnostics
FactoryCast Web Server - X X X
FactoryCast HMI Web - - - X
Server
SNMP X X X X
FTP Server X X X X
TFTP Server X - X -
Telnet Server X 1 X2 X2 X1
1
For factory diagnostic purposes only.

31006929.00 10/2005 323


Services Overview

TSX Micro The following table lists the Ethernet services supported by the TSX Micro Ethernet
Ethernet communications modules:
Communications
Service TSXETZ410 TSXETZ510
Modules
I/O Scanner - -
Modbus Server X X
Modbus Client X X
Global Data - -
FDR Server - -
FDR Client X X
BootP Client X X
Time Synchronization - -
E-mail Notification - -
Web/Embedded Diagnostics X X
FactoryCast Web Server - X
SNMP X X
FTP Server X X
TFTP Server - -
Telnet Server X 1 X1
1
For factory diagnostic purposes only.

324 31006929.00 10/2005


Services Overview

Momentum M1E The following table lists the Ethernet services supported by the Momentum M1E
Processors CPU modules:
Service 171CCC96020 171CCC96030 171CCC98020 171CCC98030
I/O Scanner X X X X
Modbus Server X X X X
Modbus Client X X X X
Global Data - - - -
FDR Server - - - -
FDR Client - - - -
BootP Client X X X X
Time Synchronization - - - -
E-mail Notification - - - -
Web/Embedded X X X X
Diagnostics
FactoryCast Web - - - -
Server
SNMP - - - -
FTP Server - - - -
TFTP Server - - - -

31006929.00 10/2005 325


Services Overview

Momentum The following table lists the Ethernet services supported by the Momentum Ethernet
Ethernet communications modules:
Communications
Service 170ENT11001 170ENT11002
Modules
I/O Scanner - -
Modbus Server X X
Modbus Client - -
Global Data - -
FDR Server - -
FDR Client X -
BootP Client X X
Time Synchronization - -
E-mail Notification - -
Web/Embedded Diagnostics X -
FactoryCast Web Server - -
SNMP X -
FTP Server X -
TFTP Server - -
Telnet Server X 1 -
1
For factory diagnostic purposes only.

326 31006929.00 10/2005


Services Overview

Twido Devices The following table lists the Ethernet services supported by a Twido CPU and a
Twido Ethernet communications modules:
Service TwidoPort 499TWD01100
I/O Scanner -
Modbus Server X1
Modbus Client X1
Global Data -
FDR Server -
FDR Client -
BootP Client X
Time Synchronization -
E-mail Notification -
Web/Embedded Diagnostics -
FactoryCast Web Server -
SNMP -
FTP Server X
TFTP Server -
Telnet Server X
1
Device receives and sends Modbus messages as a gateway.

31006929.00 10/2005 327


Services Overview

Advantys STB The following table lists the Ethernet service supported by an Advantys STB
Distributed I/O standard Ethernet network interface module (NIM):
Service STBNIP2212
I/O Scanner -
Modbus Server X
Modbus Client -
Global Data -
FDR Server -
FDR Client X
BootP Client X
Time Synchronization -
E-mail Notification -
Web/Embedded Diagnostics X
FactoryCast Web Server -
SNMP X
FTP Server X
TFTP Server -
Telnet Server -
1
Device can be scanned by the I/O scanner as it implements the Modbus server.

328 31006929.00 10/2005


Services Overview

Altivar ATV 38/58 The following table lists the Ethernet service supported by the VW3A58310 card in
Variable Speed the Altivar ATV 38/58 variable speed drive:
Drive
Service VW3A58310
I/O Scanner -
Modbus Server X
Modbus Client -
Global Data -
FDR Server -
FDR Client X
BootP Client X
Time Synchronization -
E-mail Notification -
Web/Embedded Diagnostics X
FactoryCast Web Server -
SNMP -
FTP Server -
TFTP Server -
Telnet Server -

31006929.00 10/2005 329


Services Overview

Power Logic The following table lists the Ethernet services supported by the Power Logic EXG
Gateways/ gateways:
Bridges
Service EGX200 EGX400
I/O Scanner - -
Modbus Server X1 X1
Modbus Client - -
Global Data - -
FDR Server - -
FDR Client - -
BootP Client X X
Time Synchronization - -
E-mail Notification - -
Web/Embedded Diagnostics X X
FactoryCast Web Server - -
SNMP X X
FTP Server X X
TFTP Server - -
Telnet Server X X
1
Device receives and sends Modbus messages as a gateway.

330 31006929.00 10/2005


Services Overview

ConneXium The following table lists the Ethernet services supported by the ConneXium NES/
Cabling Systems NOS managed switches and the CEV gateways:
Service 499NES17100 499NOS17100 174CEV30020 174CEV20030 174CEV20040
I/O Scanner - - - - -
Modbus Server - - X1 X1 X1
Modbus Client - - X1 X1 X1
Global Data X2 X2 - - -

FDR Server - - - - -
FDR Client - - - - -
BootP Client X X X X X
Time Synchronization - - - - -
E-mail Notification - - - - -
Web/Embedded Diagnostics X X - - X
FactoryCast Web Server - - - - -
SNMP X X X X X
FTP Server X X - - X
TFTP Server - - X X -
Telnet Server X X X 3
X 3 -
1 Device receives and sends Modbus messages as a gateway
2
Multicast filter support for global data.
3
For factory diagnostic purposes only.

31006929.00 10/2005 331


Services Overview

3.17 System Performance Evaluation

At a Glance

Overview This section describes how to obtain the system response times for each of the
chosen communications within your plant. It also describes the checks that should
be done on the devices and the network so that the overall message load on a
device does not exceed its abilities and so that the overall network load does not
cause communication delays.

What's in this This section contains the following topics:


Section?
Topic Page
System Communications 333
Modbus Messaging Response Times 334
Modbus Server Response Times 335
Modbus Messaging Client Response Times 339
I/O Scanner Systems 343
Total Load on Devices 345
System Performance Solutions 346
Gateway Response Times 352

332 31006929.00 10/2005


Services Overview

System Communications

Summary The performance of Ethernet architecture is linked to the hardware and the
application services used and to the parameters set for these services.

Hardware z network bandwidth


Considerations z resources of module or CPU with Ethernet
z embedded processor resources (PLC, PC or other CPUs)

Application z Modbus (or Uni-TE) industrial messaging handling service


Services z global data service, data scanning between PLC
z I/O scanning service, data scanning of distributed I/O
z others (Web access, TCP open communication)
It may be difficult to determine the correct size of an architecture because most of
these parameters are linked.
Response time is determined using the graphs in Appendices A through D, showing
the response times for sample systems or formula-based calculations that can be
used to calculate the response time for any system.

31006929.00 10/2005 333


Services Overview

Modbus Messaging Response Times

The Modbus messaging service involves the following components in a data


transfer:
z Modbus client
z network transfer
z Modbus server
These components are the same for all Modbus messaging systems. To determine
the response time of a Modbus system, the timing for each of the above items needs
to be calculated. Each component can be calculated separately, and the total
response time determined.

334 31006929.00 10/2005


Services Overview

Modbus Server Response Times

Summary Two methods can be used to determine the Modbus server response time:
z measured response times; for general times for all devices (e.g., PLCs) and as
the actual value for simple devices (e.g., a VSD, an I/O block
z calculation based on system operation; for more complex devices like Quantum
or Premium PLC systems
The measured response times for various Schneider Modbus server devices are
described in an appendix (see p. 417). These response times were measured under
controlled conditions and may vary from results obtained in the field. These graphs
are valid only if the overall limits of device communications are not exceeded.
The Modbus server response times for the following devices are not fixed and need
to be calculated:
z Premium PLC system
z Momentum PLC system
z Quantum PLC system

Premium PLC The PLC system response time for all received Modbus messaging requests is
System equal to one CPU scan time. All Modbus messaging requests received during the
CPU scan are answered before the start of the next scan. If the total number of
Modbus messaging requests received by the CPU in a single scan is greater than
the limit for that type of CPU, all additional requests are answered at the end of the
same scan. However, all additional requests receive the Modbus exception
response Server Busy, instead of the actual data requested.

Time Client Server


Syn

Syn Ack

Request
Scan start
Answer

Request

Request
Scan start
Response

31006929.00 10/2005 335


Services Overview

Momentum PLC The response time of a Momentum PLC system for all received Modbus messaging
System requests is one CPU scan time. All Modbus messaging requests received during the
CPU scan are answered at the end of that current CPU scan. The PLC takes several
CPU scans to answer an initial request; a TCP socket needs to be established,
which takes several CPU scans.

Time Client Server


Syn

Syn Ack Scan

Request (Initial requests take two CPU scans)

Response Scan

Request (Additional requests take one CPU scan)

Response Scan

Request Scan

Response Scan

Quantum PLC The response time of the Quantum PLC system is dependant on the number of
System requests being processed.
The system answers requests using three independent methods:
z direct access to the CPU memory by the NOE modules
z passing of requests to the CPU from the NOE modules
z direct access using an embedded Ethernet port on the CPU

Each method allows the PLC system to answer a specified number of requests per
CPU scan. All requests arriving at the Ethernet module are placed in the queue for
that module; each Ethernet port has its own queue. At the end of the CPU scan, the
requests from the top of the queue are answered. Any unanswered requests remain
in the queue and are answered in the order they are received. New requests placed
in the queue can take one or more scans to move to the top of the queue.

336 31006929.00 10/2005


Services Overview

If no requests are currently in the queue, the response time for a new request
arriving at the PLC system is between 0 ms and one CPU scan, depending on when
during the CPU scan the request arrives.

Time Client Server


Syn

Scan
Syn Ack

Request

Scan
Response

Request
Scan
Response

Scan
Response

If requests are in the queue when a new request arrives, the new request is placed
at the end of the queue. The new request is answered when it moves to the top of
the queue. The response time can be calculated as the number of requests in the
queue divided by the number of requests that can be answered per CPU scan
multiplied by the CPU scan time.

Note: Each method has its own queue. Decide in which queue the new request is
placed, and perform the calculations based on the number of requests in the
queue.

Several milliseconds should be added to the above times to accommodate any


overhead. This is much less than the CPU scan time and does not significantly affect
the overall result.

Response Times
for Devices
Product Best Average Worst Case
Case
Premium 1-2 ms 0.5 * CPU 1 CPU scan
scan

31006929.00 10/2005 337


Services Overview

Product Best Average Worst Case


Case
Momentum 1-2 ms 0.5 * CPU 1 CPU scan or 2 CPU scans if
scan initial request opens a TCP socket.
Client device must be able to
complete socket opening within 1
CPU scan for this to be accurate.
Quantum NOE or embedded port 1-2 ms 0.5 * CPU 1 CPU scan
— no overload in number of scan
requests, therefore no requests in
the queue
Quantum NOE read/write register - - Number of requests in queue / 8 *
with overloaded requests 1 CPU scan
Quantum NOE non-read/write - - Number of requests in queue / 4 *
register with overloaded requests 1 CPU scan
Quantum embedded Ethernet port - - Number of requests in queue / 16 *
with overloaded requests 1 CPU scan

Communication
Limits for
Product Number of Number of TCP Multiple Requests
Modbus Requests Sockets per Socket
Messaging
Quantum — NOE read/ 8/ CPU scan per 64 per NOE yes
write 4x register NOE module module
Quantum — NOE non 4x 4/ CPU scan per 64 per NOE yes
register NOE module1 module

Quantum Embedded 16/ CPU scan 64 yes


Ethernet Port
Premium TSXP571xx 4/ CPU scan - yes
Premium TSXP572xx 8/ CPU scan - yes
Premium TSXP573xx 12/ CPU scan - yes
Premium TSXP574xx 16/ CPU scan - yes
Premium TSXP575xx 16/ CPU scan - yes
Advantys - 4 yes
ENT V1 - 4 -
ENT V2 - 4 -
Momentum unlimited 16 no
1
20 / CPU scan max for all NOEs and embedded ports.

338 31006929.00 10/2005


Services Overview

Modbus Messaging Client Response Times

Summary The Modbus messaging client response time is part of the total Modbus messaging
system response time. There are two methods for determining the Modbus client
response times:
z considering the entire Modbus messaging system (client and server) as one unit
z calculating the system component times separately
In the first case, the total system response time from client request to server
response is measured. The second provides more specific results for a particular
system than the total time graphs used in method one.
The measured response times for several of Schneider’s Modbus client systems
based on various server response times are described in an appendix (see p. 421).
These response times were measured under controlled conditions and may vary
from results obtained in the field. The graphs in this appendix are valid only when
the overall limits of device communications are not exceeded on the client or the
server.
The following devices may require the calculation of the Modbus messaging client
time as it is not fixed:
z Quantum PLC system
z Premium PLC system
z Momentum PLC system
z SCADA system
z OFS server

31006929.00 10/2005 339


Services Overview

Quantum PLC For a Quantum system, the Modbus messaging request is sent immediately when
System the function inside the user logic is triggered. When the response is received from
the Modbus server, that response is processed in the user logic memory the next
time the calling function is processed. This is normally during the CPU scan
immediately after the PLC system has received the message.

Time CPU NOE

Scan Start

Request Block triggered Request Sent

Response

Scan

Request Block response

If this is the only request being sent or there are no prior requests in the queue, the
response time is:
response time = server response time + 1 CPU scan
If the maximum number of Modbus client requests exceeds the limits of the system,
the additional Modbus messaging requests are placed in a queue. Each time the
requesting function is evaluated by the CPU, a check is made to see if the number
of requests waiting on a response from the server is less than the maximum
supported for the system. If this is true, the next request from the queue is sent to
the server. The Modbus client response time is:
response time = number of requests in the queue x (Modbus server response
time for each request + 1 CPU scan) + Modbus server response time to the new
request + 1 CPU scan

340 31006929.00 10/2005


Services Overview

Premium PLC For a Premium system, the Modbus messaging request is sent at the end of the CPU
System scan current after the function inside the user logic is triggered. When the response
is received from the Modbus server, that response is processed in the user logic
memory the next time the calling function is processed. This is normally during the
CPU scan immediately after the PLC system has received the message.

Time CPU ETY

Scan

Request block
triggered

Request sent to ETY Request sent to server

Response

Scan

Request block processed

For a Premium system the response time is:


response time = 1 CPU scan + server response time + 1 CPU scan
If the maximum number of Modbus client requests is exceeded, additional Modbus
messaging requests are rejected and not sent; an error is generated in the user
logic.

Momentum PLC For a Momentum system each Modbus messaging request requires that a TCP
System socket be opened before the request can be sent. The Modbus TCP socket is closed
at the completion of each request. A Modbus client request response time is:
response time = 1 CPU scan (to send the open socket request) + server response
time to the open socket + 1 CPU scan (to send the request) + Modbus server
response time + 1 CPU scan (to receive the response back into the user logic)
If the maximum number of Modbus client requests is exceeded, additional Modbus
messaging requests are rejected and not sent; an error is generated in the user
logic.

31006929.00 10/2005 341


Services Overview

Modbus Client
Communication
Product Number of TCP Socket Usage Multiple
Limits
Requests Requests per
Socket
Quantum NOE 16 One per remote device yes
Quantum embedded Ethernet port 64 One per remote device yes
Premium TSXP571xx 16 One per remote device yes
Premium TSXP572xx 32 One per remote device yes
Premium TSXP573xx 48 One per remote device yes
Premium TSXP574xx 64 One per remote device yes
Premium TSXP575xx 80 One per remote device yes
Momentum 16 One per Modbus no
messaging request

342 31006929.00 10/2005


Services Overview

I/O Scanner Systems

Overview The I/O scanner system operates differently in the Quantum and the Premium (see
p. 170) PLC systems. Calculation of the system response time for either system
depends on several factors and results in a complicated formula. The formula is
provided for reference, but you should refer to the graphs in the appendix for most
systems (see p. 389). These graphs provide the I/O scanner system response times
from:
z field input to the PLC memory
z PLC memory to a field output
z field input to the PLC through a decision and back to a field output

Note: For the following calculations, the I/O scanner repetition rate must be set to
0 ms.
Tnet is 0.05 ms at 10 MB and 0.005 ms at 100 MB. For more accurate results, the
actual network transfer time can be calculated using the number of bytes sent, the
network traffic, the network speed, and the switch latency.
Tios is the number of entries in the I/O scanner table x 0.3 ms.

Response Time For a Quantum NOE system, the response time from a field input to the information
Formulae: Field in the PLC is given by the following two formulae:
Input to PLC time max = Tmod + Tios + Tnet + 2 CPU scans
Memory
time average = Tmod + (Tios x 0.5) + Tnet + 1.5 CPU scans
For a Premium PLC system or a Quantum embedded Ethernet port system, the
response time from a field input to the information in the PLC is given by the
following two formulae:
time max = Tmod + Tios + Tnet + 1 CPU scan
time average = Tmod + (Tios x 0.5) + Tnet + 0.5 CPU scans

31006929.00 10/2005 343


Services Overview

Response Time For a Quantum PLC, the response time from a field input to a decision in a field
Formulae: Field output is:
Input to Decision time max = Tmod + Tios + Tnet + 3 CPU scans + Tios + Tnet + Tmod
to Field Output
time average = Tmod + (Tios x 0.5) + Tnet + 2.5 CPU scans + (Tios x 0.5) + Tnet
+ Tmod
For a Premium PLC, the response time from a field input to a decision in a field
output is:
time max = Tmod + Tios + Tnet + 3 CPU scans + Tios + Tnet + Tmod

Response Time For a Quantum PLC, the response time from a decision to a field output is:
Formulae: time max = 1 CPU scan + Tios + Tnet + Tmod
Decision to Field
Output time average = 0.5 CPU scans + Tios + Tnet + Tmod
For a Premium PLC, the response time from a decision to a field output is:
time max = 2 CPU scans + Tios + Tnet + Tmod
time average = 1 CPU scan + Tios + Tnet + Tmod

344 31006929.00 10/2005


Services Overview

Total Load on Devices

Summary Be sure that the total number of Ethernet messages being sent to and from the
device does not exceed the following limits:
Processing Capacity Premium Ethernet TCP/IP Quantum Ethernet TCP/IP
of Ethernet
Connections
TSXETY110 TSXETY4103 TSXP575xx 140NOE771** 140CPU65150
TSXETY210 TSXETY5103 140NWM10000(5) 140CPU65160
TSXETY110WS TSXWMY100(5) 140CPU67160
TSXP571xx
TSXP572xx
TSXP573xx
TSXP574xx
Message 60 450 500 350 350
Transactions/s
Scanning I/O Polling - 2000 2000 2000 2000
Transactions/s
Global Data 800 800 800 800
Subscription
Transactions/s

31006929.00 10/2005 345


Services Overview

System Performance Solutions

Summary Here are several situations, presented as problems and answers, that may help
when evaluating your own system’s performance.

Problem 1 Problem: A single SCADA polling a Quantum PLC with an NOE module sends 15
separate requests to read blocks of Modbus 4x registers. All these requests are sent
simultaneously.
How long does it take to complete all transactions when the CPU scan time is
50 ms?
Answer: The NOE module can service 8 Modbus TCP requests per PLC cycle; 15
requests take 15/8 = 2 PLC cycles. All the requests are answered in 100 ms.

Problem 2 Problem: A Premium PLC is reading data from a field device and writing the data to
another field device.The input field device has a response time of 80 ms and has
already processed the input to its memory. The output field device has a response
time of 30 ms, and the CPU scan time is 70 ms.
What is the response time (i.e., from when the PLC reads the field input to when the
new field output turns on)?
Answer: If the Premium PLC triggers a read request at the start of the CPU scan,
there is a delay of one CPU scan (70 ms) before the request is sent. The field device
answers after 80 ms. The response is read back into the PLC the next time the read
function is called, and this can take up to one CPU scan (70 ms). The Premium
triggers a write function during the same CPU scan and sends the response at the
end of the scan (70 ms). The field device receives the response and sets the output
(30 ms). The total time is:
70 ms + 80 ms + 70 ms + 70 ms + 30 ms = 320 ms

Problem 3 Given: A SCADA system is polling a Quantum PLC running Unity Pro software. The
Quantum CPU scan time is 140 ms. The SCADA system is polling the following
items every second:
z 250 registers for trending
z 750 bits for alarms
z 30 registers for a current screen being displayed
z 20 bits for a current screen being displayed
z 1 bit write to start a motor in response to a user command on the current screen

346 31006929.00 10/2005


Services Overview

In order to calculate the number of requests, you can either look at the configuration
and determine the number of requests being sent or you can estimate the number
of requests. In this case, the number of requests has been provided for you. Note
that not all registers are in congestive order, so the number of requests is more than
the ideal amount.
z 3 requests for trending every second
z 6 requests for alarms every second
z 8 requests for registers being displayed on the screen every second
z 4 requests for bits being displayed on the screen every second
The variables are located according to the following diagram:

Problem: Determine the response time of the SCADA system in each of the
following cases.
Case One: SCADA opens one socket and only sends one request at a time.
Answer: In this scenario, the SCADA only sends a new request when a response is
received from the previous request. This results in the formation of a queue in the
SCADA. The PLC has only one request to answer at the end of each CPU scan in
which a response to the request is guaranteed at the end of each CPU scan.
In this case, there will be 21 requests in the queue. The SCADA sends the first
request to the PLC; the PLC sends a response back in 140 ms, after which the
SCADA sends the next request in the queue to the PLC. Therefore, the PLC takes
2.94 seconds to answer all 21 requests. SCADA system response time is 2.94
seconds.
Case Two: SCADA opens one socket, but sends multiple requests to the PLC at the
same time.

31006929.00 10/2005 347


Services Overview

Answer: In this case, the PLC has multiple requests to answer at the same time,
which may exceed its ability. This results in the PLC taking multiple CPU scans to
answer all requests. The SCADA sends all 21 requests to the PLC and forms two
queues in the PLC, one for 0x and one for 4x. From the information above, you can
see that the PLC has 11 requests in the 4x register and 10 requests in the 0x queue.
The NOE can process 8 4x requests and 4 other requests per CPU scan. In this
scenario, it takes 2 CPU scans (280 ms) to answer the 4x and 3 CPU scans
(420 ms) for 0x requests, which is much faster than the first case.
If the user sends a write command to the PLC to start the motor, there are several
possibilities:
z Case 1a: The SCADA may interrupt the polling and send the request right away
(after the current request is finished); the motor starts two CPU scans later, one
CPU scan to finish the current request and another to process the request to start
the motor.
z Case 1b: The SCADA may place the request at the end of the queue; it takes up
to 2.94 seconds before the write request is sent. The motor starts one CPU scan
after this time.
z Case 2: The request is sent and is queued at the end of the other ox requests in
the NOE module. This is processed on the third CPU scan; the delay is 3 CPU
scans (420 ms).
For more information, Modbus Server Operations in Quantum Systems, p. 194

Problem 4 Problem: A Quantum PLC is reading data from a Premium PLC. Thee Quantum’s
scan time is 50 ms, and the Premium’s scan time is 70 ms.
What is the response time of the system to read a block of 50 Modbus 4x registers?
Answer: For Quantum-to-Premium communications, there are two methods: using
the graphs in the appendix or calculating from the system operation. The one block
of 50 Modbus registers can be read in a single Modbus request. Look for a single
Modbus messaging request to a device with a response time of 70 ms. 70 ms is
used because this is the scan time of the Premium PLC; a Premium PLC is able to
answer requests within one CPU scan.
The Quantum PLC triggers a read request, which is immediately sent to the
Premium PLC. The Premium answers this within one CPU scan time (70 ms). The
Quantum receives this response and brings it into the PLC application the next time
the request block is processed, causing a delay of 1 CPU scan (50 ms). The total
time from when the block is triggered to when the response is available is 120 ms.

348 31006929.00 10/2005


Services Overview

Problem 5 Problem: What is the response time for a Quantum PLC with a scan time of 50 ms
to read 10 4x registers from each of 25 remote power meters that each has a
response time of 100 ms?
Quantum PLC with 25 power meters having a single block of 10 registers in each
power meter.

Answer: The Quantum can send only 16 messaging requests at a time from a single
NOE module. There are two methods for evaluating: using a graph from the
appendix or performing system evaluation.
If 25 requests are triggered, 16 are sent immediately. The meters answer after
100 ms and the responses are taken into the PLC application the next time the
request block is processed. This causes a delay of 1 CPU scan (50 ms). After
150 ms the PLC has the answers to 16 requests inside the PLC application. The
remaining 9 blocks are sent. The meters answer (100 ms), and the PLC reads the
data in next scan (50 ms). The additional time is 150 ms. The total system response
time is 300 ms.

Note: You can calculate a slightly lower time if the actual timing of the other
devices’ response and the CPU’s scan is taken into account. The response should
arrive part way through a CPU scan, so you can calculate just the remaining CPU
scan time before the response is processed into the application. This method is not
recommended because the worst case should always be assumed. You have no
control over the synchronization of the two devices.

31006929.00 10/2005 349


Services Overview

Problem 6 Problem: A 140CPU65150 Quantum I/O scanner (with an embedded Ethernet port)
on a PLC with a CPU scan time of 20 ms is polling five Momentum, Advantys and a
third-party I/O devices (15 devices in all). The response time of the third-party device
is 100 ms.
What are the response times for each device type to read an input, act on it in PLC
code, and write a responding output to the same device?
Determine how the response time changes if the CPU scan time increases to
100 ms.
Determine how the response time changes if the CPU scan time is 10 ms but the
configured repetition rate is 50 ms.
Answer: For the Momentum I/O the response time of the field device is minimal. The
Momentum was used for the I/O scanner performance graphs in the appendix (see
p. 389). The graph to evaluate the system response time is chosen on the I/O
scanner processor being used and type of system (field input to field output). For 16
devices and a 20 ms CPU scan time, the system response time (from field input to
field output) is 49 ms.
For Advantys devices, the response time needs to be calculated using the system
formulae to take into account the field device delays.

350 31006929.00 10/2005


Services Overview

Problem 7 Problem: A Momentum I/O device is being polled by:


z a Quantum I/O scanner reading three separate blocks of data
z a Premium PLC reading a block of data using a Modbus messaging request
If a SCADA wishes to access the Momentum is it able to read data? How can the
system be changed so the SCADA is able to read data?
Answer: The Momentum I/O device can open only four TCP sockets
simultaneously. The I/O scanner from the Quantum holds the TCP sockets open
(the I/O scanner always hold the sockets open); the Premium PLC opens a single
socket when the Modbus read request is triggered. A total of four sockets is open on
the Momentum. The socket being used by the Premium could be closed after the
transaction if the Momentum requests that it be closed, but the Momentum is not
designed to do this. Because the maximum number of sockets open, the open-
socket request from the SCADA is rejected.
To enable the SCADA system to open a socket, one of the other sockets must be
closed. This cannot be done on the Premium, but the Quantum I/O scanner can
close one if its sockets. It does this by disabling the line in the I/O scanner, causing
the data transfer to stop but enabling the Premium to communicate. When the I/O
scanner data is required, the line can be re-enabled again. The problem with this
solution is that there is no coordination between the SCADA and the Quantum on
which system is attempting to use the socket. This can lead to communication errors
or retries if both devices attempt to read data at the same time.

31006929.00 10/2005 351


Services Overview

Gateway Response Times

Summary The response time for a gateway system can be calculated in one of two ways:
z Gateway with or without protocol conversion; actual calculation including
response time of devices on the destination network and queues inside the
gateway.
z Gateway using shared memory; For simple response time, just the time to read
the internal memory can be used. For a full system response for data in a
destination device through the gateway and to a device on the source network,
the reading of data into the gateway (often based on a timer) must be included.
The simplest way to calculate response time is to consider a single message to read
data. The following actions must occur:
z A device on the source network must send out a request to read the data; the
delay is dependant on the requesting device.
z The gateway receives the request; the delay from the time the requesting device
sends the request to the time the gateway receives the request is dependent on
the source network. For an Ethernet network, the delay is normally 0.05 ms. For
a Modbus Plus network, the delay may be up to one token rotation time, the time
which it takes the token (message packet) to rotate around the ring and return to
the sending device. (Refer to the Modbus Plus User’s Guide for more
information.)
z The gateway passes the request to the destination network; this is the gateway
delay (see p. 387). If there is a queue, this time can be significant. Gateway delay
is common if the two networks connected by the gateway have very different
response times.
z The request is received by the destination device; the delay is based on the ability
of the destination network to transfer the message. For Modbus Plus, this is one
token rotation time. For serial networks it depends on the speed of the network.
z The request is processed by the destination device; this is dependent on the
actual device.
z An answer is sent back to the gateway; the delay is based on the ability of the
destination network to transfer the message. For Modbus Plus it is one token
rotation time; for serial networks it depends on the speed of the network.
z The gateway passes the response back to the source network; this is the
gateway delay (see p. 387). If there is a queue, this time can be significant. This
is common if the two networks connected by the gateway have very different
response times.
z The response is received by the requesting device; the delay from the time the
requesting device sends the request to the time the gateway receives the request
is dependent on the source network. For an Ethernet network, the delay is
normally 0.05 ms. For a Modbus Plus network, the delay may be up to one token
rotation time.

352 31006929.00 10/2005


Services Overview

In steps that have a delay, the system response time is the total of all the delays.
The delay for transferring the request and the response across the network may be
different. For example, a serial network takes much longer to transfer a response
including 100 registers of data than it does to transfer the request itself contains no
actual data.
Two items complicate the calculation of the system response time:
z a queue of messages in the gateway due to time-outs or multiple queries
z the time-out of a message on the destination network, this is applicable in a
network that must hold all future messages until the current message has timed
out (e.g., Modbus serial line).
To improve the system response time, limit the number of requests being sent
through the gateway by limiting the number of devices connected to each gateway.

Calculation of The serial line response time is determined by the number of bits sent and the serial
Serial Line line speed. Refer to the Modbus protocol specification for the exact number of bits
Transmission per Modbus message. For the actual network transmission time, use:
Time (the number of bits in the message/8) x (1/baud rate)
For a Modbus read request at 9600 baud, the time is about 5 ms. A response is
about 100 ms for 100 registers of data.

Calculation of The system response time is determined by the number of requests sent through the
the Number of bridge; the more requests sent, the slower the overall response time for all devices.
Supported To determine the number of devices on a system, first determine the total number
Devices per of Modbus requests to gather all the data. The best response time the system can
Bridge give is:
number of requests x (time to transmit the request on the serial line + response
time of the serial device + time to transmit the response on the serial line +
~50 ms)
The average response time for a serial device is 200 ms, but may vary from
50 to 500 ms. The time to transmit the request/response depends on the speed of
the network and the Modbus RTU/ASCII setting.
z RTU is much faster because fewer bytes are transferred.
z An average Modbus read request at 9600 baud is ~ 5 ms
z A maximum response is ~ 100 ms
The total best-case system response would therefore be:
5 ms (request) + 200 ms (serial device response) + 100 ms (response) + 50 ms
= ~350 ms/request
For 8 Modbus devices with 2 requests each, the best-case response time to get data
from the system is 16 x 350 ms = 5.6 s.

31006929.00 10/2005 353


Services Overview

This is too long for most system users to wait for a response, so the number of
devices per bridge needs to be reduced.
However, with a faster serial device response time, calculating the total best-case
bridge response would use the formula:
-5 ms (request) + 50 ms (serial device response) + 20 ms (response) + 50 ms =
~125ms/request
For 8 Modbus devices with 2 requests each, the best-case response time would
then be an acceptable 16 x 125 ms = 2.0 s.

Calculation of If the time-out of a request is included, calculating the worst-case bridge response
the Ethernet time gives the required value for the Ethernet timeout field:
Timeout Ethernet time-out = timeout of a serial line request x number of serial line
retries x number of requests sent to the bridge
If this time-out calculation is not used, and the value in the field is too slow, the failure
of one or more serial devices can cause Ethernet requests to other serial devices to
time-out due to the delay caused by the incorrect value.

354 31006929.00 10/2005


Troubleshooting

4
At a Glance

Introduction This chapter describes general troubleshooting steps and provides methods for
identifying problems. It also provides tables that help you identify and resolve
problems.

What's in this This chapter contains the following sections:


Chapter?
Section Topic Page
4.1 About Troubleshooting 356
4.2 Network Troubleshooting 359
4.3 Services Troubleshooting 368
4.4 SCADA/HMI System Slow Response Time Troubleshooting 379
4.5 Bridge Troubleshooting 380
4.6 Lost Packet Troubleshooting 381

31006929.00 10/2005 355


Troubleshooting

4.1 About Troubleshooting

At a Glance

Introduction This section introduces troubleshooting for Transparent Ready networks.

What's in this This section contains the following topics:


Section?
Topic Page
Introduction to Troubleshooting 357
General Problem Identification 358

356 31006929.00 10/2005


Troubleshooting

Introduction to Troubleshooting

Overview The troubleshooting tables in this section cover the issues you are most likely to
encounter with a Transparent Ready network. Owing to the complexity of network
design, it is impossible to account for every type or problem that can occur.
Here are some questions to ask yourself that cover the most common problems
encountered:
z Is the device powered up?
z Are cables properly connected?
z Is the IP address correct?

To avoid redundancy, this manual explains the issues above in the network tables
(see p. 359) and not for every service (Modbus, I/O scanner, etc.) to which they can
potentially apply.
This manual is not able to anticipate defects and lockups for all devices on the
market, so there are few instances in which Schneider recommends a power recycle
for a network device. To achieve quick resolution, you can cycle the power on a
suspect device, but you should first evaluate whether the cycle interferes with plant
operations. Cycling the power may temporarily restore communications to the
device, but it will not identify or correct the problem.

31006929.00 10/2005 357


Troubleshooting

General Problem Identification

Before You Gather as much information as you can about the characteristics, symptoms, and
Begin behavior of an issue before you attempt to troubleshoot. Problems that initially seem
to be network issues can turn out to be application issues, mismanaged end
devices, or facility-related.
Ask these basic questions when you start to troubleshoot:
z Are symptoms regular or intermittent?
z How widespread is the problem? Does it affect one device, several devices, or all
devices? Are the affected devices located in the same area of the site?
z Are symptoms related to one or all applications/services? What other
applications/services run at the same time?
z When was the first occurrence of the problem?
z Do occurrences coincide with irregular or non-standard network activities that
would not initially seem to cause problems?
z Have you changed network hardware or software components recently? Have
you added end devices to the network recently?
z Could maintenance work (moving, cleaning, cable management, electrical work,
etc.) affect network operations?
Keep the answers in mind when you use the troubleshooting tables.

Problem
Identification
Topic Description Examples
Network issues Problems with: z No light link Ethernet on device.
z physical connections of devices z Cannot ping device.
z logical addresses z Cannot contact device.
z transmission of Ethernet packets to and from
devices
Services Problems with one or more Transparent Ready z Modbus communications failure, but web
services. A ping command can find the device pages are OK.
and get a response, but other communications z I/O scanner failure, but programming is OK.
to the device may fail.
SCADA system Specific information on performance SCADA system is slow to report field device
improvement for SCADA systems. status or execute commands.
Ethernet-to-serial Specific information on troubleshooting Bridge operation is slow or communications to
bridges communications through Ethernet-to-serial all devices are intermittent after a single device
bridges. failure.
Ethernet packet Specific information on capturing and analyzing
capture tool Ethernet packets for detailed troubleshooting.

358 31006929.00 10/2005


Troubleshooting

4.2 Network Troubleshooting

At a Glance

Introduction This section describes network troubleshooting, mostly for layer 1 (the physical
layer) and layer 2 (IP problems) of the TCP stack.

What's in this This section contains the following topics:


Section?
Topic Page
Introduction to Network Troubleshooting 360
Connection Troubleshooting 362
Intermittent Connection Troubleshooting 364
Slow Connection Troubleshooting 365
Remote Access Troubleshooting 366

31006929.00 10/2005 359


Troubleshooting

Introduction to Network Troubleshooting

Problem Types The most common network problems on Transparent Ready systems are:
z physical
z logical
z traffic congestion
The intelligent switches and high-speed network interface cards in modern networks
create complex network configurations and operations. In such an environment,
problems can be hard to isolate.
Intermittent problems are the hardest to troubleshoot. It is a lot easier to tell when
you've solved a constant problem than one that comes and goes.
The ability to troubleshoot a problem is often a function of the investigator's
comprehension of the physical and logical network design. (The quality of on-hand
documentation can also be a factor.)

Physical Physical connection problems are generally the easiest of the three common types
Connections to troubleshoot. Making sure the network cable is plugged in is only the beginning of
the investigation of the network's physical connectivity. Cable testers and hardware
performance indicators (often just lights on network devices) help you identify and
isolate physical connection issues.
More complex physical connection problems can be related to:
cables Did you implement the correct cable type and quality?
Did you account for cable interference issues (noise and ground)?
Is the implementation of straight and crossover cables appropriate?
Are the settings and configurations appropriate for duplex (transmission
speed) communications?
interference wireless connections
common interference

360 31006929.00 10/2005


Troubleshooting

Logical To troubleshoot more complex logical connections, one must first have an
Connections understanding of physical connections and network components.
Generally, logical connection troubleshooting requires some expertise with specific
software utilities and applications, although you can fix some problems with
standard DOS commands that work with most off-the-shelf operating systems.
Poor network administration is often the cause of logical connection problems. If you
don't restart the system before you fully test recent administration changes, end
users can have problems much later, especially when they try to connect specific
applications or programs after a system restart. Administration changes that are
likely to cause logical connection issues include:
z critical application changes or server operating system changes (DHCP servers,
DNS servers, mail servers, etc.)
z changes to logins, policies, scripting, and authentication
z security changes (firewall rules, port/services, and encryption settings)
z network hardware functionality changes (multicast filtering, default gateway
routing, configuration)

Traffic A high volume of network traffic can cause problems that are difficult to isolate and
Congestion solve. Software utilities such as network sniffers and protocol analyzers help you
troubleshoot congestion issues. (In most cases, you should be trained for these
specific tools.) Unfortunately, the tools often indicate only general problems like
broadcast errors.
In large switched networks, it is more difficult to isolate and analyze congestion
without the aid of hardware probes and vendor-specific software tools. A quick
understanding of the magnitude and scale of an issue can guide your attempts to
find and fix the problem quickly and efficiently.
If the issue creates non-critical problems for only a few users, you might choose a
troubleshooting method that does not require a complete network outage. In a case
of widespread communications problems, you may need to physically segment the
network to help you quickly isolate the problem.

31006929.00 10/2005 361


Troubleshooting

Connection Troubleshooting

Problem Topic Cause and Actions


Physical cables Use the proper physical cable connections from the end device to
check (see note) the wall, patch panel, hub, or switch. Also check for cable defects,
lacerations, and causes of interference (like electrical noise).
Replace questionable patch cables.
Check device link lights, if available. Typically, lights are green
when operational, amber during an error, and unlit when no
physical connection is detected by the hardware. (See the
hardware user guide for details)
Check for duplex mode lights, if available, on device, for speed
settings (10 mb, 100 mb, auto, etc.). Refer to Physical Layout
chapter (see p. 29).
Make sure that crossover cables have been used between network
devices (hub-to-hub, switch-to-switch, etc.) where required. Check
the device documentation for straight or crossover cable
requirements.
Cable lengths should not exceed Ethernet specifications.
Test the backbone wire integrity with a testing device and re-
terminate wiring at the patch panel if suspect after completing
logical checks.
NIC Make sure the traditional or PCMCIA network card is properly
seated in the machine. Swap the NIC card for another to test card
performance.
network Check:
hardware z hubs, switches, routers, and other network devices for power
z port link lights for proper activity (typically solid or blinking
green)
z uplink cable connectivity for stacked devices
For a suspect hub port or switch port, substitute an identical port
after you have completed logical checks.

362 31006929.00 10/2005


Troubleshooting

Problem Topic Cause and Actions


Logical OS At a DOS prompt, type ping to check the basic level of network
check connectivity for replies or timeouts.
At DOS prompt, type ipconfig to see if the device receives an IP
address and associated IP.
Check the operating system network configuration. For example:
z Is the hardware card operational?
z Are the TCP/IP protocols properly bound to NIC?

Check the IP address configuration:


z For static addressing, is the IP address and subnet mask typed
correctly?
z Is the default gateway address (if required) correct for source
and end devices?
If you encounter trouble while connecting to remote networks, type
trace route at a DOS prompt to check network routing hops for
failing points. If you discover a timeout at a router hop, discuss and
validate the problem with the person that is responsible for that
router.
For wireless connections, check the validity of these configuration
settings:
z SSID
z channel
z type (a, b, g)
z encryption key

NIC Check the duplex (speed) settings (autonegotiate, 10 mb, 100 mb,
etc.). If possible, match the duplex settings on the end device with
that of its network port.
Make sure the network interface drivers and adapter settings have
been properly installed on the end device. Update or reload the
NIC software drivers from the manufacturer.
network Enable the ports to which your hubs and switches are connected.
hardware
Check the switch configuration for (optional) VLANs.
applications Check for proxy or firewall settings that can block ports or protocols
between source and destination devices.
For client/server applications, check that the server (other
destination device) is properly operating on network. Check to see
if other clients have the same problem to determine if the issue is
with an individual client or if it is a system-wide problem.
Note: Specific tools are available to perform automatic testing of a cable.
These tools test for correct cable type selection, pin connection, etc. For details on brands
and models, see p. 29.

31006929.00 10/2005 363


Troubleshooting

Intermittent Connection Troubleshooting

Problem Topic Cause and Actions


Physical cables z Check for loose connections, especially if there is a dongle
check (see note) with PCMCIA between NIC and RJ45 cable connections.
z Check cables for defects.
z Check the patch panel connections and grounding.
z Check cable integrity with a cable testing device after
completing necessary logical checks.
NIC With wireless connections, check the signal strength and refresh
the signal or eliminate interference between an end device and a
wireless access point.
Logical OS/ At DOS prompt, use the ping command to check the basic level of
check applications network connectivity for replies or timeouts.
If you encounter trouble while connecting to remote networks,
type trace route at the DOS prompt to check network routing hops
for failing points.
Scan the OS for virus or memory resources issues.
network Check hubs, switches, or routers (if applicable) for network traffic
hardware congestion or possible network broadcast storms. If available,
monitor the error logs on the network hardware.
NIC For wireless connections, use the network configuration to check
the signal strength on the end device.
Note: Specific tools are available to perform automatic testing of a cable.
These tools test for correct cable type selection, pin connection, etc. For details on brands
and models, see p. 29.

364 31006929.00 10/2005


Troubleshooting

Slow Connection Troubleshooting

Problem Topic Cause and Actions


Physical cable Check cable integrity and conformance to proper cabling
check (see note) requirements (category 3, 5, etc.).
If an entire network in a large switched environment is still affected
significantly after you check all logical connections, disconnect
entire network segments at the central backbone location and
monitor the traffic until it is normal. In this manner, you can pinpoint
the specific site, building, closet, switch, port, cubicle, end device, or
cable that is problematic.
network Check the hub, switch, or router link lights for network traffic issues.
hardware Under normal circumstances, these indication lights are solid. See
the device vendor documentation for interpreting blink patterns.
Check the maximum number of repeaters (hubs) within a network
segment.
Check for loops in the Ethernet network that can be caused by:
z a ConneXium ring without a redundancy manager configured
z incorrect spanning tree setups
z a loop created by incorrect cabling among switches

Logical OS Scan the OS for virus or memory resource issues.


applications Check applications for multiple instances of overloaded system
resources.
Establish whether the problem is system-wide by examining other
network devices.
network Check hub, switch, or router (if applicable) for:
hardware z network traffic congestion
z a possible network broadcast storm
z large bandwidth usage (large downloads, streaming audio/
video, etc.)
A network traffic analyzer (sniffer) can help.
Note: Specific tools are available to perform automatic testing of a cable.
These tools test for correct cable type selection, pin connection, etc. For details on brands
and models, see p. 29.

31006929.00 10/2005 365


Troubleshooting

Remote Access Troubleshooting

Problem Topic Cause and actions


Physical cables Check for proper physical cable connections from the end device to
check the wall, patch panel, hub, or switch. Also check for cable defects,
lacerations, and causes of interference (like electrical noise).
Replace questionable patch cables with new ones (RJ-11 for dial-
up).
With dial-up connections, check the dial tone at the RJ-11 jack with
a standard analog phone.
NIC Make sure the traditional or PCMCIA network card is properly
seated in the machine. Test the card's performance by swapping
one NIC for another.
network Check the hub, switch, router, wireless access point, RAS server,
hardware and other network hardware for power and port link lights for proper
activity (typically solid or blinking green).)
Check uplink cable connectivity for stacked devices. For a suspect
hub port or switch port, substitute an identical port after you have
completed logical checks. (See the vendor's documentation for
device-specific information.
Logical OS When working remotely (at an unfamiliar hotel, conference center,
check customer site, etc.), verify with your network administrator that your
access method is supported and allowed through the remote site's
network.
When using a VPN or dial-up connection over an existing Internet
connection, verify the performance of the connection by using the
Internet browser before you attempt to troubleshoot the client or
server.
When using a dial-up connection, make sure the appropriate dial-up
network configuration is installed and configured.
At the DOS prompt, use the ping command to check for the basic
level of network connectivity for replies or timeouts. For security
reasons, ICMP ping requests are sometimes blocked. Discuss this
issue with the network administrator.
At the DOS prompt, use the ipconfig command to see if a device
receives an IP address and associated IP parameters.
Check the operating system network configuration. For example:
z Is the hardware card operational?
z Are the TCP/IP protocols properly bound to NIC?

366 31006929.00 10/2005


Troubleshooting

Problem Topic Cause and actions


Check the IP address configuration:
z For static addressing, is the IP address and subnet mask typed
correctly?
z If required, is the default gateway address correct for source and
end devices?
If you encounter trouble while connecting to remote networks, type
trace route at the DOS prompt to check network routing hops for
failing points. If you discover a timeout at a router hop, discuss and
validate the problem with the person who is responsible for that
router.
application For specific VPN client software, make sure you have basic Internet
access before you establish the VPN tunnel. Configure the VPN with
appropriate authentication options. (See the local IT network
administrator.)
Make sure that (optional) firewall software that runs on end devices
does not filter connectivity for specific applications or protocols.
network Check the remote access server or VPN configuration (and VPN
hardware logs) for:
z event information
z connection attempt

If the network uses an independent authentication server, make


sure the end user accounts have been created correctly and check
system logs for authentication attempts. The local system
administrator can help you with this.

31006929.00 10/2005 367


Troubleshooting

4.3 Services Troubleshooting

At a Glance

Introduction This section describes common problems and actions for correcting a
communications error on Transparent Ready services. Troubleshooting of this
nature is simpler for some devices than for others, because diagnostic information
is provided by different devices. The complexity of the troubleshooting also varies
between Schneider products and third-party devices. A device's indicator lights and
the information provided by its diagnostic or programming software can aid with
troubleshooting.
In some cases, you can use a network packet capture tool (see p. 383). This tool
can accurately diagnose the problem on a service and indicate a single corrective
action. It can take awhile to set up the tool, so you may want to attempt an intuitive
solution (swapping a suspect device or modifying a service configuration) before
attempting to perform analysis with the packet capture tool.

What's in this This section contains the following topics:


Section?
Topic Page
Services Troubleshooting 369
Modbus Messaging and I/O Scanner Troubleshooting 370
SNMP Troubleshooting 372
Telnet and FTP Troubleshooting 373
Faulty Device Replacement/BootP Troubleshooting 374
SMTP Troubleshooting 376
Time Synchronization (NTP) Troubleshooting Table 377
Web Troubleshooting Table 378

368 31006929.00 10/2005


Troubleshooting

Services Troubleshooting

Problem Topic Cause and actions


Service all services failed You can ping a network device, but no other device
failed services function (see p. 359).
Modbus messaging Modbus messaging does not function. For example:
z communications from PLC to remote devices
z communications from most SCADA systems to a
PLC or device
I/O scanner I/O scanner service fails, as indicated by error bits that
are on in the I/O scanner service.
network management A network management system is unable to read or
(SNMP) write values to the end device. For example, a network
management system can discover a device, but can not
read information about the device.
global data The global data service fails, as indicated by health bits
that are off in the global data service.
Telnet/FTP Telnet is unable to connect to the device, for example
you can not configure a bridge device with Telnet.
FTP is unable to connect or transfer files to the device,
for example you can not download Web pages with an
FTP client.
faulty device A device is unable to obtain an appropriate IP address
replacement/BootP or parameters through BootP or FDR, indicated when
the device continually issues BootP requests. (The
LEDs indicate this error.) Otherwise, the device goes to
the default IP address.
Web You can not access Web pages, or some Web page
functions do not work correctly. For example, you can
see Web pages, but live data from a device is replaced
with an error message or blank space.
NTP (time stamping) A device is unable to obtain the time from the NTP
server (or the time is not accurate).
SMTP (e-mail) A device is unable to send an e-mail message.

31006929.00 10/2005 369


Troubleshooting

Modbus Messaging and I/O Scanner Troubleshooting

General Errors
Topic Problem Solution
Service response This is usually caused by:
is too slow (no z overloaded client or server
error generated) (see p. 345) causes slow response
z TCP socket problem or packet loss (see p. 382)

Timeout error The error response from the client identifies timeout
(data is not errors, usually caused by:
transferred) z slow response from the server (see p. 335)
z a lost packet on the network (see p. 382)
z socket error (see p. 335)

TCP socket error An error on the TCP socket that carries the Modbus Solve this problem by correcting the TCP
(data is not message. The TCP socket is aborted or closed socket error, which can be:
transferred) before data transfer. Some devices report an error z a lost packet on the network (see
code, but most report a timeout or general error p. 382)
message. In the absence of a reported error, you z a sequence or ack number problem that
can discover this event only with a packet capture is caused by a problem with the TCP
program. implementation of either end device
(see p. 382)

Client Errors
Topic Issue
Incorrect An entry for the server IP/MAC address combination must be in the ARP cache of the device that sends
MAC the client request. The client device usually generates this entry, but it can be incorrect, usually when:
address z a failed device is replaced with a device with a different MAC address for the same IP address
z two devices swap IP addresses and create different IP/MAC combinations for each device
z a client device saves its ARP table to flash memory, but does not refresh the table after a subsequent
power-up
Client An overloaded client system is not able to send requests. This is most true for systems in which the user
overload controls the trigger request time (as in a PLC system). This issue is not common where the system (like
SCADA or HMI) schedules requests.
Candidates for overload are:
z the device's Modbus system
z a limit on the number of TCP sockets the device can have open (A new socket may need be opened
for the transmission of a new Modbus request.)
This error is normally indicated by an error message or a long delay before the request transmission.

370 31006929.00 10/2005


Troubleshooting

Server Errors
Topic Problem
Function All network servers do not support all function codes. A server that receives an unsupported function code
code will usually respond to the client with an error message.
Error indication:
z client reports the error
z user finds the error by inspecting the network packet for either the absence of a response or a Modbus
exception response
Examples of newer Modbus function codes that can cause this error:
z FC23 read/write registers (Quantum and Premium I/O scanners use FC23 when read and write data
are listed on the same line)
z Ethernet statistics or identification
Solution: Choose a supported function code to correct the error.
Request A socket connection to the server can not be established because of:
not z controlled access
accepted z a firewall
z the number of available server sockets is exceeded

Register If a request is sent to a nonexistent register area or to a range of registers that contain nonexistent registers,
area not the server can either respond with an error code (as the Modbus specification expects) or discard the
supported request. This error is detected through:
z the Modbus error response report
z examination of the documentation on the supported registers
The common cause of this error is when SCADA or administration personnel try to read multiple blocks or
registers in a single request from a server that implements specific registers with gaps of unsupported
registers between them.
Pipeline Servers should support pipeline requests, but you should not necessarily implement pipeline requests at
requests every opportunity. For more information, see gateway (see p. 313) and Modbus messaging (see p. 183).
Pipeline requests occur when a new request is sent over a single socket before the previous request has
been answered. If the server cannot process a pipeline request, it will:
z respond with an error code: the error code is likely to be request not supported or server busy (especially
if the server is a serial-to-Ethernet bridge)
z discard the request: without a response
z crash
You can only identify this problem through:
z knowledge of the device operation
z packet inspection with an Ethernet packet capture tool
A subsequent problem arises when a device sends multiple Modbus requests in a single Ethernet packet,
which the Modbus specification does not permit. This can cause the same problems as above, but more
likely scenarios include a request discard or a device crash.
Incorrect If a Modbus request returns an incorrect response (either incorrect data or data of the wrong type or size)
response the client/server may be incorrectly using the Modbus transaction IDs. Transaction IDs in the Modbus TCP
(not serial) specification support pipeline requests, although all devices do not implement them. This
returns incorrect data, making the device non-compliant with the Modbus TCP/IP specification. Inspect the
request and response with an Ethernet packet capture device to detect this problem.

31006929.00 10/2005 371


Troubleshooting

SNMP Troubleshooting

Device
Discovery
Topic Issue
A device A known network device can not be discovered by an SNMP management
cannot be system, usually because the device does not support SNMP or because a
discovered. firewall blocks SNMP traffic.
Check the network device with a ping request from a DOS prompt. If the ping
is successful, the error is probably in the network management package. An
unsuccessful ping indicates a likely problem with the device itself (see p. 359).

Data Access
Topic Issue
A device can be z incorrect community strings: the read string must be correct to
discovered, but read data and the write string must be correct to write data
cannot be accessed z different versions of SNMP (V1, V2, V3): for details on versions,
to read data. refer to SNMP sections of networking (see p. 250).

372 31006929.00 10/2005


Troubleshooting

Telnet and FTP Troubleshooting

These tables describe troubleshooting for Telnet (p. 253) and FTP (p. 264) issues

Device Access
Topic Problem Solution
Cannot A firewall is a An error message on the client side can sometimes detect
access common access this problem, but in a more ideal situation:
device. restriction. z The user is already aware of the firewall.
z The user examines the packets with an Ethernet packet
capture tool to verify proper transmission of the socket
open request, but a socket is not established because no
response is received.

Incorrect Login
or Restricted
Topic Issue
Access
Cannot log in to the An incorrect username or password is usually the cause of this
device or cannot problem. The user interface can detect this problem and display an
perform the desired error message. In the absence of a user interface, the problem can
action. be hard to distinguish from the previous error (above).
Cannot perform the This problem is common when the current username does not
desired function. provide access to the desired action (for example, an attempt to write
a file is made with a read-only login).
The user interface can detect this problem and display an error
message. In the absence of a user interface, the problem can be hard
to distinguish from the previous error (above).

31006929.00 10/2005 373


Troubleshooting

Faulty Device Replacement/BootP Troubleshooting

These tables describe troubleshooting for faulty device replacement (see p. 209)
and BootP (see p. 137).

Address
Assignment
Topic Problem Solution
No response z The server does not list the device by either rolename If you are not familiar with the network,
from the server or MAC address. This usually happens when you add a use an Ethernet packet capture tool to
to a request for replacement device (with a new MAC address) without detect the problem.
an IP address updating the server table.
z A firewall or router prevents the client from reaching the
server. Set up the server as a DHCP relay agent to
correct the problem.
When the client does not obtain an IP address, it either
reports an error code or goes to the default IP address
(or both).
Slow response A server can respond slowly when: You can distinguish slow server
from the server z overloaded, for example, many devices powered up at responses from the errors above only
causing a the same time with a packet capture tool. Use an
timeout on the z client and server are powered on at the same time Ethernet packet capture tool to detect
client (generally, client devices boot up faster and can send a the problem
request to the server before the server is operational)
When there is a slow server response, the client does not
get an IP address. It either reports an error code or goes to
the default IP address (or both).
Server sends Multiple DHCP/BootP servers connected to the same You can distinguish this problem from
negative network can create multiple responses to the same the errors above only with a packet
response, request. One server response can offer the correct capture tool. Use an Ethernet packet
preventing the address while another server response reports that no capture tool.
device from address is available. The negative response can cause the This is seen as the client not obtaining
obtaining an IP client to go to an error state or assume a fallback address. an IP address. (The client device may
address report an error code or go to the default
IP address.)

374 31006929.00 10/2005


Troubleshooting

Configuration
File
Topic Problem
IP address obtained but no A firewall in front of the FDR server may allow the DHCP
configuration file for an FDR request (for an IP address) but block the FTP/TFPT request
system for the configuration file.
When a PC used as an FDR server, the file server can be on
a different (unreachable) machine.

31006929.00 10/2005 375


Troubleshooting

SMTP Troubleshooting

These tables describe troubleshooting for SMTP issues (see p. 372).

Cannot Connect
to Server
Topic Problem Solution
Firewall Check that firewall allows SMTP traffic.
Password i Password incorrect Check that the server uses the same password
scheme as the client.
Check that the passwords are correct.

Cannot Send
Messages
Topic Issue
Server failure Check server connection error counter.

Messages Slow
to Arrive
Issue Solution
Server Send e-mail from PC client to confirm that it is a server delay and not a client delay.
delays If server delay is confirmed, consult the IT staff.

376 31006929.00 10/2005


Troubleshooting

Time Synchronization (NTP) Troubleshooting Table

These tables describe troubleshooting for time synchronization (see p. 213).

Cannot Obtain
Time From
Topic Issue
Server
Time exchange The server might implement SNTP broadcasts. Schneider devices
format is incorrect support only NTP/SNTP request responses (not broadcasts).
You can find this problem through the examination of device
configurations.
Cannot obtain time The server might be behind a firewall.
from the server

Time Obtained Is
Not Accurate
Topic Problem Solution
Server time is The server time is not accurate,
inaccurate or especially if the network uses a PC
unstable (instead of a dedicated server) as an
NTP server. Windows PCs are the most
likely to create this problem, whereas a
Linux PC or dedicated time server can
solve it.
Network delays Non-uniform network loads can cause To solve this problem, move the
cause time large delays in either the request or server closer to the network
inaccuracies response message because NTP client device through:
algorithms that calculate accurate times z the elimination of routers and
assume uniform network delays. switches between the server
You can find this problem through the and client
examination of network loads or by z the implementation of a
using an Ethernet packet capture tool to separate network (possibly a
capture request and response packets. VLAN) for the NTP system
Some devices also list delays on a
diagnostics page.

31006929.00 10/2005 377


Troubleshooting

Web Troubleshooting Table

Cannot Access
Static Pages
Topic Problem Solution
Firewalls Make sure you have the appropriate
security access for all devices that
you try to reach. Also, the firewall
should be configured to allow access
to your HTTP request.
Proxy server A proxy server can allow access to
only the appropriate Web pages
through filtering. Make sure the proxy
server does not filter out the Web
page you want to reach.

Cannot Access
Dynamic Data
Topic Issue
Java version If you can see the Web pages but not the dynamic data (like Ethernet
statistics), the Java applet may not be compatible with your JVM.
A gray Java box or an error in the status bar at the bottom of the Web
browser window indicate this problem.
firewall A firewall can also block the particular application protocol (like Modbus
TCP and Uni-TE (502)) so you can not see live data. For example, a Web
page that can not display real-time data indicates that protocol 502 is
blocked.
If this is the case, you see either:
z question marks in the data fields, or
z an error indicating that the Modbus device can not be reached

browser security You can not download Java applets if you chose high security settings in
setting your Internet options. In this case, a security error in the status bar at the
bottom of the Web browser window indicates this problem.
access control on Check the Schneider device to make sure your IP is listed as a
Modbus designated IP for communications with the device.
If this is the case, you see either:
z question marks in the data fields, or
z an error indicating that the Modbus device can not be reached

378 31006929.00 10/2005


Troubleshooting

4.4 SCADA/HMI System Slow Response Time


Troubleshooting

Slow Response Time (SCADA/HMI) Troubleshooting

Problem Topic Suggestions


Category
Determine Determine if the Send a device operation command and measure the interval between the command
the cause of delay is on write transmission and the device reaction. Determine:
the delay traffic or read traffic z Is the delay in data writing or response reading?
z Is there a difference between digital and analog data reading and writing?
Note: Determine the device reaction from physical observation of the actual device,
not from the status display on the SCADA/HMI system.
Determine if the With a separate PC tool, send a single request to the server and measure the
delay is SCADA- response time. Separate read and write requests should be sent for each data type
based or server- the SCADA system reads.
based z A fast response from the PC and a slow response from the SCADA indicates a
problem in SCADA communications. SCADA responses might be slowed down
by either the SCADA system or by a SCADA request queue inside the server.
(Other requests, such as PC requests are not held up in this queue).
z A slow response from the PC indicates an overloaded server, so you reduce the
load on the server (see p. 290).
Slow SCADA is slow but Examine the response time of a SCADA request on the server with an Ethernet
response PC test tool is fast packet capture tool. To do this, check one of each request type (read, write, digital,
caused by (check server analog) that the SCADA uses.
SCADA response time for When doing this measurement, you may see that after you send the request to be
SCADA requests) measured the server will send back some responses to earlier requests. It is
important to wait for the response to the specific request you sent before calculating
the response time.
To identify a specific request/response pair, either the Modbus transaction ID or
another unique feature of the request must be used (for example, the number of
requested registers).
If the observed response time is slow, then a queue of SCADA requests in the server
can cause a long delay. To improve the response:
z Reduce the number of requests sent to the server. (see p. 290)
z Start an additional queue for data access and send requests on that path. This
works because the PC is able to get a fast response, showing that the server is
not overloaded. To do this, force the SCADA to open extra TCP sockets and split
the requests between the sockets.
SCADA is slow but A queue in the SCADA system itself causes this delay. This can happen when the
PC is fast and there SCADA sends only a single request at a time to the server. This usually happens in
is no delay on systems for which only a single TCP socket to the server exists.
SCADA requests in The SCADA section (see p. 283) gives information for opening more sockets or
the server device sending more requests down a single socket elsewhere in this document.

31006929.00 10/2005 379


Troubleshooting

4.5 Bridge Troubleshooting

Bridge Troubleshooting

Problem Topic Suggestions


Category
Slow response slow There are too many devices on the serial line side of the
or response bridge.
communication socket Most bridges can only implement a limited number of Ethernet
failure rejected sockets. This number is usually less than the number of
devices connected to the serial line side. Therefore, if one
socket is used per serial device, the number of available
bridge sockets will be inadequate.
To solve this, reduce the number of devices on the serial line
or select the Modbus client device that can send requests to
multiple serial devices over a single socket. For an I/O
scanner system that scans devices over a bridge, either
implement the enable/disable feature or change to the
Modbus client communication blocks instead of the I/O
scanner.
The client may report this error. Otherwise, you must either
ascertain the number of sockets in use (through analysis of
the communications) or use an Ethernet packet capture tool to
see the socket rejection.
Intermittent additional Timeouts on the Ethernet side are not long enough. (They are
communication devices fail less than the total timeouts on the serial side.) Refer to
s failures after one gateway section (see p. 313) for more information.
fails
intermittent Timeouts on the Ethernet side are too close to the time
errors required for gathering serial line data. Refer to gateway
section (see p. 313) for more information.

380 31006929.00 10/2005


Troubleshooting

4.6 Lost Packet Troubleshooting

At a Glance

Introduction This section describes troubleshooting for lost data packets.

What's in this This section contains the following topics:


Section?
Topic Page
Lost Packet Troubleshooting 382
Using a Packet Capture Tool 383
Packet Capture Troubleshooting 384

31006929.00 10/2005 381


Troubleshooting

Lost Packet Troubleshooting

Problem Topic Cause and Actions


Category
General effect of a A lost packet causes an error on a TCP socket. Normally, the
lost packet socket recovers from the error, avoiding notice in the application
layer (for example, Modbus or I/O scanner). However, an error
occurs in the application layer when the time to recover is longer
than the application layer timeout.
detecting There are two ways to detect lost packets:
lost packets z sent/received packet counter: Use this method when you can
verify that one packet is sent for each one received (for
example, a system that only has Modbus client/server
traffic). Counters are also suited for detecting large numbers
of lost packets.
z Ethernet packet capture tool: Use this method to see the TCP
sequence and acknowledgment numbers to identify lost
packets. Packet captures should use the timestamp feature
to correlate the time of packet loss with the alarm time on a
SCADA system or time of a problem in the plant.
Responding packet lost You see this error when a packet appears on one side of a
to packet in a switch or switch but not the other. This requires the simultaneous
loss network implementation of two packet capture tools.
device To resolve this, check the switch load. Network devices discard
some packets when the switch is overloaded. Electrical noise
can also cause packet corruption, forcing a packet to be
discarded.
packet loss If a packet loss causes an application error:
causes an z extend the application timeout to allow for the recovery of
application TCP layer
error z modify the devices for faster TCP layer recovery (requires a
firmware change)
z reduce the number of packets lost

Sample ways to reduce the number of lost packets:


z reduce network traffic
z eliminate half-duplex links
z reduce electrical noise

These changes only reduce packet loss. They do not eliminate


the problem.

382 31006929.00 10/2005


Troubleshooting

Using a Packet Capture Tool

Overview In an ideal system, all devices would detect and report the exact cause of network
errors, but this is not always possible. A device can be unable to detect or report an
error.
If the device indicates only a general error (instead of a specific error), you can use
an Ethernet packet capture tool to monitor the Ethernet packets and determine the
specific error and its cause. This allows you to determine the actual error and layer
(IP/TCP or application) on which the error occurs so you can take corrective action.
We do not recommend packet capture tools for general plant maintenance, but they
are well-suited for diagnosing intermittent problems or problems that occur during
device installation.
These tools capture network packets and display them on the screen. The tools also
save the packets in a file that you can analyze later.

Tool Types Ethernet packet capture tool types:


z physical layer: These expensive tools capture physical signals on the wire and
logical data on the upper layer.
z hand-held: These tools analyze only layers 2, 3, and 4. They are not quite as
expensive as physical layer tools, and are rugged enough for field use.
z PC-based: These tools use a PC's Ethernet card to capture network data for
analysis in a software program. Owing to wide fluctuations in price (from freeware
to more than USD$20,000), the degree of automatic analysis and customer
support services for these tools significantly vary. These tools analyze only layers
2, 3, and 4.

Tool Capabilities Ethernet packet capture tools can detect or determine:


z overall network traffic load: Which devices contribute to congestion? What is the
nature of the traffic? (VoIP? Windows broadcast? I/O scanner traffic?)
z broadcast traffic and its causes
z a list of devices to which a specific device transmits and the communication
protocol it uses
z details of communications between devices: protocols, function codes, the
addresses and values of transferred/requested data
z a device's application layer response time
z packet loss or multiple TCP retries
z communications to and from a device that suffers from TCP socket errors
(rejected connections, lost packets, etc.)
All Ethernet packet capture tools can analyze all of these items, but better tools do
analysis automatically and report errors on the alarm screen.

31006929.00 10/2005 383


Troubleshooting

Packet Capture Troubleshooting

Problem Topic Suggestions


Category
Packets only packets The package does not operate in promiscuous mode. Enable
from the to or from the this mode to allow the computer to capture all data seen on the
required host PC are Ethernet cable connected to the computer.
device are captured by For most tools, you can set this as a general option within the tool
not seen the tool for all captures or set it when the capture starts. You need a
special Ethernet card driver to enable this setting. Most tools
include Ethernet card drivers, but all cards don't always function
on all systems.
packets from When a packet arrives at a switch, the switch sends the packet
the device out on only the port that is ultimately connected to the destination
being device. As a result, a packet capture tool connected to a spare
analyzed are port on the switch will not see the packet. To allow the packet
not captured, capture tool to see the packet, do one of the following:
but z Replace the switch with a hub: In this case you'll see traffic to
broadcast and from all devices connected to the hub.
packets are z Insert a hub between the device in question and the switch:
The packet capture tool is then connected to the hub, in which
case you'll see only packets to and from the device in
question.
z Enable port mirroring: This configures the switch to forward a
copy of all packets sent or received on a port to a different
port to which the packet capture tool is connected. (Port
mirroring is not supported by all switches.)
z Configure the switch to operate as a hub: Some switches
support this feature as a disable learning option. In this case,
the switch no longer determines the data destination and
sends all data to all ports.
Note: These solutions result in data transmission to Ethernet
ports that do not normally receive data when the network is not
under analysis. This can result in increased traffic on the network
(among other undesirable results).

384 31006929.00 10/2005


Troubleshooting

Problem Topic Suggestions


Category
Finding the capturing For errors that occur every few minutes or hours, a capture setup
error data for may have to run for several hours. This creates many thousands
packets intermittent of packets in the file that has to be analyzed during error
within a errors investigation.
capture causes files Because such a large file consumes hundreds of MB of disk
of excessive space, it is impractical to run an analyzer for 24-hour periods.
size Therefore, an error may not necessarily occur when the analyzer
happens to be running. To avoid this, the packet capture tool can
be set to limit the duration of data collection or the number of
packets in the capture file. At the predefined limit, the file closes
and the tool starts a new file. After the configured number of files
have been created, the tool either stops recording or begins to
overwrite the files in order in which they were created.
Each such file is time-stamped when the tool closes it. Using a
SCADA system or other plant system to record error times (for
example, plant stoppage or and unavailable device), you can
open the correct file to find packets that were exchanged at the
time of the error. The tool marks each packet with the exact time
so you can find specific packets at the time of the error. Note that
packets showing the problem are usually seen just before
SCADA reports the error because of timeout and reporting
delays.
filter the Use data filtering to find the packets you want to investigate.
captured Filter packets with one of two methods:
data (to just z during the capture stage: Filtering during capture can discard
the required packets that are needed for analysis later. If that happens,
packets) you have to do another capture.
z in the stored data: This is the suggested method. Filter
according to address (IP or MAC) and protocol (destination
socket number). Then filter the visible data to a single TCP
socket based on source socket number.

31006929.00 10/2005 385


Troubleshooting

386 31006929.00 10/2005


Appendices

What's in this The appendix contains the following chapters:


Appendix? Chapter Chapter Name Page
A I/O Scanning Response Times 389
B Modbus Server Throughput Capacity 417
C Modbus Client Response Times 421
D Gateway Response Time and Timeout Measurements 461
E Standards and Other Considerations for Industrial Ethernet 495
Networks
F Earthing (Grounding) Procedures 517

31006929.00 10/2005 387


Appendices

388 31006929.00 10/2005


I/O Scanning Response Times

A
At a Glance

Overview This appendix illustrates some I/O scanner response times for Premium and
Quantum systems that use industrial Ethernet.

What's in this This chapter contains the following sections:


Chapter?
Section Topic Page
A.1 Premium PLC I/O Scanner Response Times 390
A.2 Quantum PLC I/O Scanner Response Times 403

31006929.00 10/2005 389


I/O Scanner Performance

A.1 Premium PLC I/O Scanner Response Times

At a Glance

Overview The system response time curves illustrated in this section are based on
measurements made on Premium PLCs that are scanning Momentum
170 ENT 110 00 devices. Momentum was used because it provides the shortest
response times for Ethernet applications (approximately 5 to 8 ms). Three different
types of response time scenarios are presented.

What's in this This section contains the following topics:


Section?
Topic Page
Premium I/O Scanner Response Times: Remote Input to Remote Output 391
Premium I/O Scanner Response Times: Remote Input to a Local Output 395
Premium I/O Scanner Response Times: PLC Memory to Remote Output 399

390 31006929.00 10/2005


I/O Scanner Performance

Premium I/O Scanner Response Times: Remote Input to Remote Output

Measurement The set of curves below illustrates Premium PLC response times when a signal is
Setup sent from a remote input module through the PLC to a remote output module:

Response Time

The signal is:


z triggered by a Momentum input module with a response time of ~2 ms
z scanned into the Premium PLC at a repetition rate of 0 ms (see p. 178)
z copied to another internal variable within the PLC
z written to a Momentum output module with a response time of ~2 ms
Results are plotted for 1, 8, 16 and 32 devices.

31006929.00 10/2005 391


I/O Scanner Performance

TSXP575634M The TSXP575634M CPU used for the following measurements is at version 2.0, with
CPU with its embedded Ethernet port at version 2.0.
Embedded
Ethernet Port
Time (ms)

32 devices

1 ... 16 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 8 devices are within 1 ms
of each other. The response times for 16 devices increase by 2 to 3 ms. For 32
devices, response times are approximately 11 to 14 ms longer.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Scanned Device
Output (ms)
TSXP575634M (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
Embedded Ethernet Port (v2.0) Scan Scan Scan Scan Scan
1 device 25 45 106 205 406
8 devices 26 46 107 206 407
16 devices 28 48 108 207 409
32 devices 39 61 120 224 421

392 31006929.00 10/2005


I/O Scanner Performance

TSXP575634M The TSXP575634M CPU used for the following measurements is at version 2.0, and
CPU with a the TSXETY5103 Ethernet communications module is at version 3.1.
TSXETY5103
Module Time (ms)

32 devices

1 ... 16 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 8 devices are within 1 ms
of each other. The response times for 16 devices increase by 2 to 3 ms. For 32
devices, response times are approximately 12 to 16 ms longer.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Scanned Device
Output (ms)
TSXP575634 (v2.0) + ETY 10 ms 20 ms 50 ms 100 ms 200 ms
5103 (v3.1) Scan Scan Scan Scan Scan
1 device 24 44 104 204 405
8 devices 25 45 105 205 406
16 devices 28 47 107 206 408
32 devices 40 60 118 218 417

31006929.00 10/2005 393


I/O Scanner Performance

TSXP57304M The TSXP57304M CPU used for the following measurements is at version 2.0, and
CPU with a the TSXETY5103 Ethernet communications module is at version 3.1.
TSXETY5103
Module
Time (ms)

32 devices

16 devices

1 ... 8 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 8 devices are within 2 ms
of each other. The response times for 16 devices increase by 3 to 4 ms. For 32
devices, response times are approximately 10 to 16 ms longer.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Scanned Device
Output (ms)
TSXP57304M (v2.0) + ETY 10 ms 20 ms 50 ms 100 ms 200 ms
5103 (v3.1) Scan Scan Scan Scan Scan
1 device 25 44 105 206 406
8 devices 27 47 107 208 408
16 devices 31 52 112 213 413
32 devices 41 601 118 219 419

394 31006929.00 10/2005


I/O Scanner Performance

Premium I/O Scanner Response Times: Remote Input to a Local Output

Measurement The set of curves below illustrates Quantum PLC response times when a signal is
Setup sent from a remote input module to a Premium output module in the PLC:

Response Time

The signal is:


z triggered by a Momentum input module with a response time of ~2 ms
z scanned into the Premium PLC at a repetition rate of 0 ms (see p. 178)
z copied to another internal variable within the PLC
z written to a local Premium output module
Results are plotted for 1, 8, 16 and 32 devices.

31006929.00 10/2005 395


I/O Scanner Performance

TSXP575634M The TSXP575634M CPU used for the following measurements is at version 2.0, with
CPU with its embedded Ethernet port at version 2.0.
Embedded
Ethernet Port
Time (ms)

32 devices

1 ... 16 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 16 devices are within 1 ms
of each other. The response times for 32 devices are 9 to 10 ms longer initially; as
scan time increases, the difference in response times becomes smaller.
The table below shows the data used to generate the graph represented above.
Number of Devices to Scan Time from Scanned Device Input to Local Output
(ms)
TSXP575634M (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
Embedded Ethernet Port (v2.0) Scan Scan Scan Scan Scan
1 device 23 42 102 201 402
8 devices 23 42 102 201 402
16 devices 24 43 103 202 403
32 devices 33 52 110 208 405

396 31006929.00 10/2005


I/O Scanner Performance

TSXP575634M The TSXP575634M CPU used for the following measurements is at version 2.0, and
CPU with a the TSXETY5103 Ethernet communications module is at version 3.1.
TSXETY5103
Module Time (ms)

32 devices

1 ... 16 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 16 devices are within 3 ms
of each other. The response times for 32 devices are 6 to 9 ms longer initially; as
scan time increases, the difference in response times becomes smaller.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Local Output (ms)
TSXP575634M (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
ETY5103 (v3.1) Scan Scan Scan Scan Scan
1 device 21 41 101 200 400
8 devices 22 42 102 201 401
16 devices 24 43 103 202 402
32 devices 30 49 107 207 406

31006929.00 10/2005 397


I/O Scanner Performance

TSXP57304M The TSXP57304M CPU used for the following measurements is at version 2.0, and
CPU with a the TSXETY5103 Ethernet communications module is at version 3.1.
TSXETY5103
Module
Time (ms)

32 devices

1 ... 16 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 16 devices are identical or
within 1 ms of each other. The response times for 32 devices are 6 ms longer
initially; as scan time increases, the difference in response times decreases slowly.
The table below shows the data used to generate the graph represented above.
Number of Devices to Scan Time from Scanned Device Input to Local Output (ms)
TSXP57304M (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
ETY5103 (v3.1) Scan Scan Scan Scan Scan
1 device 24 43 103 204 404
8 devices 24 43 103 204 404
16 devices 24 43 103 204 404
32 devices 32 51 108 209 409

398 31006929.00 10/2005


I/O Scanner Performance

Premium I/O Scanner Response Times: PLC Memory to Remote Output

Measurement The set of curves below illustrates Quantum PLC response times when a signal is
Setup sent from the PLC to a remote output module:

Response Time

The signal is written to a Momentum output module with a response time of ~2 ms.
Results are plotted for 1, 8, 16 and 32 devices.

31006929.00 10/2005 399


I/O Scanner Performance

TSXP575634M The TSXP575634M CPU used for the following measurements is at version 2.0, with
CPU with its embedded Ethernet port at version 2.0.
Embedded
Ethernet Port

32 devices
Time (ms)

1 ... 16 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 16 devices are within 1 to
2 ms of each other. The response times for 32 devices are 2 to 4 ms longer initially;
as scan time increases, the difference in response times becomes larger.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from PLC Memory to Scanned Device Output
(ms)
TSXP575634M (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
Embedded Ethernet Port (v2.0) Scan Scan Scan Scan Scan
1 device 12 23 54 104 204
8 devices 13 23 55 105 205
16 devices 14 25 55 105 206
32 devices6 16 29 60 116 216

400 31006929.00 10/2005


I/O Scanner Performance

TSXP575634M The TSXP575634M CPU used for the following measurements is at version 2.0, and
CPU with a the TSXETY5103 Ethernet communications module is at version 3.1.
TSXETY5103
Module Time (ms)

32 devices

1 ... 16 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 16 devices are within 1 to
4 ms of each other. The response times for 32 devices are 6 to 9 ms longer.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from PLC Memory to Scanned Device Output (ms)
TSXP575634M (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
ETY5103 (v3.1) Scan Scan Scan Scan Scan
1 device 13 23 53 104 205
8 devices 13 23 53 104 205
16 devices 14 24 54 104 206
32 devices6 20 31 61 111 211

31006929.00 10/2005 401


I/O Scanner Performance

TSXP57304M The TSXP57304M CPU used for the following measurements is at version 2.0, and
CPU with a the TSXETY5103 Ethernet communications module is at version 3.1.
TSXETY5103
Module
Time (ms)

32 devices

1 ... 16 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 16 devices are identical.
The response times for 32 devices are 8 ms longer initially; as scan time increases,
the difference in response times becomes smaller.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from PLC Memory to Scanned Device Output (ms)
TSXP57304M (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
ETY5103 (v3.1) Scan Scan Scan Scan Scan
1 device 11 21 52 102 202
8 devices 13 24 54 104 204
16 devices 17 29 59 109 209
32 devices6 19 30 60 110 210

402 31006929.00 10/2005


I/O Scanner Performance

A.2 Quantum PLC I/O Scanner Response Times

At a Glance

Overview The system response time curves illustrated in this section are based on
measurements made on Quantum PLCs that are scanning Momentum
170 ENT 110 00 devices. Momentum was used because it provides the shortest
response times for Ethernet applications (approximately 5 to 8 ms). Three different
types of response time scenarios are presented.

What's in this This section contains the following topics:


Section?
Topic Page
Quantum I/O Scanner Response Tmes: Remote Input to Remote Output 404
Quantum I/O Scanner Response Tmes: Remote Input to Local Output 408
Quantum I/O Scanner Response Times: Local Input to Remote Output 412

31006929.00 10/2005 403


I/O Scanner Performance

Quantum I/O Scanner Response Tmes: Remote Input to Remote Output

Measurement The set of curves below illustrates Quantum PLC response times when a signal is
Setup sent from a remote input module through the PLC to a remote output module:

Response Time

The signal is:


z triggered by a Momentum input module with a response time of ~2 ms
z scanned into the Quantum PLC at a repetition rate of 0 ms (see p. 178)
z copied to another internal variable within the PLC
z written to a Momentum output module with a response time of ~2 ms
Results are plotted for 1, 8, 16 and 32 devices.

404 31006929.00 10/2005


I/O Scanner Performance

140CPU65150 The 140CPU65150 used for the following measurements is at version 2.0, with an
with Embedded embedded Ethernet port at version 3.1.
Ethernet Port

16 devices
32 devices
Time (ms)

1 ... 8 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 8 devices are within 1 to
3 ms of each other. The response times for 16 devices are 2 to 4 ms longer initially;
as scan time increases, the difference in response times becomes larger (e.g.,
11 ms at a 200 ms scan rate). The response times for 32 devices are 13 to 17 ms
longer initially; as scan time increases, the difference in response times becomes
larger (e.g., 34 ms more at a 200 ms scan).
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Scanned Device
Output (ms)
140CPU65150 (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
Embedded Ethernet Port (v3.1) Scan Scan Scan Scan Scan
1 device 25 46 112 220 409
8 devices 26 47 113 222 412
16 devices 28 49 115 223 423
32 devices 42 62 129 241 443

31006929.00 10/2005 405


I/O Scanner Performance

140CPU65150 The 140CPU65150 used for the following measurements is at version 2.0, and the
with 140NOE771x1 Ethernet communications module is at version 3.5.
140NOE771x1
Module
Time (ms)

PLC Scan Time (ms)

The curves above show that response times remain within 5 to 7 ms of each other
whether 1, 8, 16 or 32 devices are used.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Scanned Device
Output (ms)
140CPU65150 (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
NOE771x1 (v3.5) Scan Scan Scan Scan Scan
1 device 35 61 153 302 602
8 devices 36 62 154 303 603
16 devices 38 64 155 305 606
32 devices 40 66 157 307 609

406 31006929.00 10/2005


I/O Scanner Performance

140CPU43412A The 140CPU43412A used for the following measurements is at version 2.0, and the
with an 140NOE771x1 Ethernet communications module is at version 3.5.
140NOE771x1
Module Time (ms)

PLC Scan Time (ms)

The curves above show that response times remain within 5 to 6 ms of each other
whether 1, 8, 16 or 32 devices are used.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Scanned Device
Output (ms)
140CPU43412A (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
NOE771x1 (v3.5) Scan Scan Scan Scan Scan
1 device 41 73 179 358 665
8 devices 42 75 180 360 666
16 devices 44 77 182 361 668
32 devices 46 79 185 364 671

31006929.00 10/2005 407


I/O Scanner Performance

Quantum I/O Scanner Response Tmes: Remote Input to Local Output

Measurement The curves below illustrate the Quantum PLC response times when a signal is sent
Setup from a remote input module to a local output module in the PLC:

Response Time

The signal is:


z triggered by a Momentum input module with a response time of ~2 ms
z scanned into the Quantum PLC at a repetition rate of 0 ms (see p. 178)
z copied to another internal variable within the PLC
z written to a local Quantum output module
Results are plotted for 1, 8, 16 and 32 devices.

408 31006929.00 10/2005


I/O Scanner Performance

140CPU65150 The 140CPU65150 used for the following measurements is at version 2.0, with an
with Embedded embedded Ethernet port at version 3.1.
Ethernet Port

32 devices

1 ... 16 devices

The lower curve shows that the response times for 1 to 16 devices remain within
2 ms of each other regardless of the PLC scan time. The upper curve shows that the
response times for 32 devices are 7 to 8 ms greater.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Local Output (ms)
140CPU65150 (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
Embedded Ethernet Port (v3.1) Scan Scan Scan Scan Scan
1 device 22 41 102 202 402
8 devices 23 42 103 204 403
16 devices 24 43 104 204 404
32 devices 31 49 110 211 410

31006929.00 10/2005 409


I/O Scanner Performance

140CPU65150 The 140CPU65150 used for the following measurements is at version 2.0, with a
with 140NOE771x1 Ethernet communications module at version 3.5.
140NOE771x1
Module
Time (ms)

PLC Scan Time (ms)

The curves above show that the response times for all devices remain are the same
for 1, 8, 16 and 32 devices.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Local Output (ms)
140CPU65150 (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
NOE771x1 (v3.5) Scan Scan Scan Scan Scan
1 device 31 56 145 292 590
8 devices 31 56 145 292 590
16 devices 31 56 145 292 590
32 devices 31 56 145 292 590

410 31006929.00 10/2005


I/O Scanner Performance

140CPU43412A The 140CPU43412A used for the following measurements is at version 2.0, with a
with 140NOE771x1 Ethernet communications module at version 3.5.
140NOE771x1
Module Time (ms)

PLC Scan Time (ms)

The curves above show that the response times for all devices remain are the same
for 1, 8, 16 and 32 devices.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Local Output (ms)
140CPU43412A (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
NOE771x1 (v3.5) Scan Scan Scan Scan Scan
1 device 35 64 168 334 634
8 devices 35 64 168 334 634
16 devices 35 64 168 334 634
32 devices 35 64 168 334 634

31006929.00 10/2005 411


I/O Scanner Performance

Quantum I/O Scanner Response Times: Local Input to Remote Output

Measurement The curves below illustrate the Quantum PLC response times for a when a signal is
Setup sent from the local PLC to a remote output module:

Response Time

The signal is:


z triggered by a local Quantum input module
z scanned into the Quantum PLC at a repetition rate of 0 ms (see p. 178)
z copied to another internal variable within the PLC
z written to a remote Momentum output module with a response time of ~2 ms
Results are plotted for 1, 8, 16 and 32 devices.

412 31006929.00 10/2005


I/O Scanner Performance

140CPU65150 The 140CPU65150 used for the following measurements is at version 2.0, with its
with Embedded embedded Ethernet port at version 3.1.
Ethernet Port

16 devices
32 devices
Time (ms)

1 ... 8 devices

PLC Scan Time (ms)

The bottom curve shows that the response times for 1 to 8 devices are almost the
same, differing by only 2 ms at a 200 ms scan time. The response times for 16
devices are 1 ms longer initially; as scan time increases, the difference in response
times increases to 10 to 12 ms at a 200 ms scan rate. The response times for 32
devices are 7 to 8 ms longer initially; as scan time increases, the difference in
response times becomes larger (e.g., 14 to 16 ms more at a 200 ms scan).
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Local Output (ms)
140CPU65150 (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
Embedded Ethernet Port (v3.1) Scan Scan Scan Scan Scan
1 device 13 25 60 118 207
8 devices 13 25 60 118 209
16 devices 14 26 61 119 219
32 devices 21 33 69 130 233

31006929.00 10/2005 413


I/O Scanner Performance

140CPU65150 The 140CPU65150 used for the following measurements is at version 2.0, with a
with 140NOE771x1 Ethernet communications module at version 3.5.
140NOE771x1
Ethernet Module

32 devices

16 devices
Time (ms)

1 ... 8 devices

PLC Scan Time (ms)

The curves above show that the response times for all devices remain within 5 to
7 ms of each other for 1, 8, 16 and 32 devices.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Local Output (ms)
140CPU65150 (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
NOE771x1 (v3.5) Scan Scan Scan Scan Scan
1 device 14 25 58 110 212
8 devices 15 26 59 111 213
16 devices 17 28 60 113 216
32 devices 19 30 62 115 219

414 31006929.00 10/2005


I/O Scanner Performance

140CPU43412A The 140CPU43412A used for the following measurements is at version 2.0, with a
with 140NOE771x1 Ethernet communications module at version 3.5.
140NOE771x1
Ethernet Module

32 devices

16 devices
Time (ms)

1 ... 8 devices

PLC Scan Time (ms)

The curves above show that the response times for all devices remain within 5 to
6 ms of each other for 1, 8, 16 and 32 devices.
The table below shows the data points used to generate the graph represented
above.
Number of Devices to Scan Time from Scanned Device Input to Local Output (ms)
140CPU43412A (v2.0) + 10 ms 20 ms 50 ms 100 ms 200 ms
NOE771x1 (v3.5) Scan Scan Scan Scan Scan
1 device 16 29 61 124 231
8 devices 17 31 62 126 232
16 devices 19 33 64 127 234
32 devices 21 35 67 130 237

31006929.00 10/2005 415


I/O Scanner Performance

416 31006929.00 10/2005


Modbus Server Throughput
Capacity
B
At a Glance

Overview This appendix illustrates Modbus server throughput for Premium and Quantum
systems that use industrial Ethernet.

What's in this This chapter contains the following topics:


Chapter?
Topic Page
Quantum Modbus Server Throughput Capacity: Unity v2.0 418
Premium Modbus Server Throughput Capacity: Unity v2.0 420

31006929.00 10/2005 417


Modbus Server Performance

Quantum Modbus Server Throughput Capacity: Unity v2.0

Performance The following chart shows the number of Modbus read-register requests that may
Measurements be answered by Quantum CPUs in 1 s. (A read-register request is a Modbus
function code 3 command.) The minimum time to respond to a single Modbus
request is one PLC scan cycle. The throughput capacity of five PLCs is measured:
z a 140CPU65150 with a 140NOE77101Ethernet communications module
z a 140CPU65150 with a 140NOE77111 Ethernet communications module
z a 140CPU43412A with a 140NOE77101Ethernet communications module
z a 140CPU43412A with a 140NOE77111Ethernet communications module
z a 140CPU65150 with an embedded Ethernet port
Number of Modbus Transactions/s

Scan Time (ms)

The four bottom curves (all with equal values and hence appearing as one line)
show throughput for the four CPUs that use NOE modules. The upper curve shows
throughput for the CPU with an embedded Ethernet port. As scan times increase,
the difference in throughput capacity (the number of Modbus transactions/
messages) between the CPUs with NOE modules and the CPU with the Embedded
Ethernet port decreases.

418 31006929.00 10/2005


Modbus Server Performance

The table below shows the data points used to generate the graph represented
above.
Scan TIme 65150 65150 + 65150 + 43412A + 43412A+
(ms) (Embedded Port) NOE77101 NOE77111 NOE77101 NOE77111
Number of Modbus Transactions/s
10 400 100 100 100 100
20 400 100 100 100 100
50 320 120 120 120 120
100 160 80 80 80 80
200 80 40 40 40 40

31006929.00 10/2005 419


Modbus Server Performance

Premium Modbus Server Throughput Capacity: Unity v2.0

Performance The following chart shows the number of Modbus read-register requests that may
Measurements be answered by Quantum CPUs in 1 s. (A read-register request is a Modbus
function code 3 command.) The minimum time to respond to a single Modbus
request is one PLC scan cycle. The throughput capacity of three PLCs is measured:
z a TSXP575634M CPU with a TSX ETY5103 Ethernet communications module
z a TSXP575634M CPU with an embedded Ethernet port
z a TSXP57304M CPU with a TSX ETY5103 Ethernet communications module

P5
75
ET 6 3 4
Y5 a n d
10
3
Number of Modbus Transactions/s

P
(em 5756
b 3
P
an 5730 po edde 4
dE 4 rt) d
TY
51
03

Scan Time (ms)

The table below shows the data points used to generate the graph represented
above.
Scan Time (ms) P575634M P575634M + ETY5103 P57304M + ETY5103
(Embedded Port)
Number of Modbus Transactions/s
10 400 400 300
20 300 400 300
50 320 400 160
100 160 200 120
200 80 100 60

420 31006929.00 10/2005


Modbus Client Response Times

C
At a Glance

Overview This appendix illustrates some Modbus client response times for Premium and
Quantum systems that use industrial Ethernet.

What's in this This chapter contains the following topics:


Chapter?
Topic Page
Modbus Client Response Times: Premium TSXP575634M 422
Modbus Client Response Times: Premium TSXP57304M 429
Modbus Client Response Times: Quantum 140 CPU65150 with an Embedded 436
Ethernet Port
Modbus Client Response Times: Quantum 140 CPU65150 with a 140 441
NOE77101 Ethernet Communications Module
Modbus Client Response Times: Quantum 140 CPU65150 with a 140 446
NOE77111 Ethernet Communications Module
Modbus Client Response Times: Quantum 140 CPU43412A with a 140 451
NOE77101 Ethernet Communications Module
Modbus Client Response Times: Quantum 140 CPU43412A with a 140 456
NOE77111 Ethernet Communications Module

31006929.00 10/2005 421


Modbus Client Performance

Modbus Client Response Times: Premium TSXP575634M

Test Setup The following charts show Premium CPU response times where a client request
block is triggered in PLC logic by reading data from a Modbus server. The graphs
represent the number of CPU cycles required for the PLC to complete all triggered
Modbus client requests. In all cases, the CPU is a Premium TSXP575634M with an
TSXETY5103 Ethernet communications module (exec v3.10). The CPU logic scan
times vary.
Modbus client response times are tracked with respect to six Modbus server
response times:
z < 1 ms
z 10 ms
z 20 ms
z 50 ms
z 70 ms
z 100 ms

422 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 200 ms

CPU Cycles

100 ms 50 ms
70 ms
50 ms 20 ms 10 ms
1 ms

Requests Sent

A sampling of results in the chart follows:


Number of Requests Server Response Time CPU Cycles Needed To Complete
1 ... 7 <1 ... 100 ms 2 cycles
8 70 ... 100 ms 3 cycles
10 50 ms 3 cycles
29 100 ms 4 cycles
33 70 ms 4 cycles
100 ms 5 cycles
38 50 ms 4 cycles
70 ms 5 cycles
100 ms 6 cycles
41 20 ms 3 cycles
42 100 ms 7 cycles
46 50 ms 5 cycles
70 ms 6 cycles
48 10 ms 3 cycles
55 50 ms 6 cycles
70 ms 7 cycles
100 ms 10 cycles
60 100 ms 11 cycles

31006929.00 10/2005 423


Modbus Client Performance

at a CPU Scan
Time of 100 ms

100 ms
70 ms
CPU Cycles

50 ms
20 ms

100 ms 70 ms
50 ms 10 ms 1 ms

Communications Completed
A sampling of results in the chart follows:
Number of Requests Server Response Time CPU Cycles Needed To Complete
1 ... 4 <1 ... 100 ms 2 cycles
5 100 ms 3 cycles
7 20 ... 70 ms 3 cycles
16 100 ms 4 cycles
18 10 ms 3 cycles
22 70 ms 4 cycles
24 100 ms 5 cycles
29 50 ms 4 cycles
70 ms 5 cycles
31 100 ms 6 cycles
33 <1 ms 3 cycles
70 ms 6 cycles
100 ms 7 cycles
34 100 ms 8 cycles
38 50 ms 6 cycles
39 70 ms 8 cycles
100 ms 9 cycles

424 31006929.00 10/2005


Modbus Client Performance

Number of Requests Server Response Time CPU Cycles Needed To Complete


47 20 ms 4 cycles
50 ms 8 cycles
70 ms 10 cycles
100 ms 12 cycles
60 20 ms 5 cycles
50 ms 10 cycles
70 ms 14 cycles
100 ms 18 cycles

at a CPU Scan
Time of 50 ms
CPU Cycles

70 ms
100 ms
50 ms

20 ms

10 ms
10 ms
<1 ms
20 ms

Communications Completed

A sampling of results in the chart follows:


Number of Requests Server Response Time CPU Cycles Needed To Complete
1 ... 2 <1 ... 50 ms 2 cycles
70 ... 100 ms 3 cycles
3 50 ms 3 cycles
100 ms 4 cycles
7 10 ... 20 ms 3 cycles
50 ms 4 cycles
70 ... 100 ms 5 cycles
8 100 ms 6 cycles

31006929.00 10/2005 425


Modbus Client Performance

Number of Requests Server Response Time CPU Cycles Needed To Complete


15 10 ms 4 cycles
20 ... 70 ms 5 cycles
26 50 ... 70 ms 6 cycles
100 ms 7 cycles
31 70 ms 8 cycles
100 ms 11 cycles
37 50 ms 9 cycles
70 ms 13 cycles
100 ms 16 cycles
39 <1 ms 4 cycles
100 ms 17 cycles
50 10 ... 20 ms 6 cycles
50 ms 13 cycles
70 ms 20 cycles
100 ms 26 cycles
60 <1 ms 5 cycles
10 ms 7 cycles
20 ms 8 cycles
50 ms 18 cycles
70 ms 25 cycles
100 ms 35 cycles

426 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 10 ms
CPU Cycles

100 ms

70 ms

50 ms

20 ms

10 ms

<1 ms

Communications Completed

A sampling of results in the chart follows:


Number of Requests Server Response Time CPU Cycles Needed To Complete
1 <1 ... 10 ms 3 cycles
20 ms 5 cycles
50 ... 70 ms 7 cycles
100 ms 8 cycles
3 <1 ms 5 cycles
10 ms 4 cycles
20 ms 6 cycles
50 ms 10 cycles
70 ms 12 cycles
100 ms 13 cycles
10 <1 ms 6 cycles
10 ms 7 cycles
20 ms 18 cycles
70 ... 100 ms 22 ms

31006929.00 10/2005 427


Modbus Client Performance

Number of Requests Server Response Time CPU Cycles Needed To Complete


16 10 ms 8 cycles
20 ms 18 cycles
50 ms 22 cycles
70 ms 27 cycles
100 ms 22 cycles
21 <1 ms 8 cycles
10 ... 20 ms 19 cycles
50 ms 22 cycles
70 ms 27 cycles
100 ms 31 cycles
33 <1 ms 11 cycles
10 ms 19 cycles
20 ms 24 cycles
50 ms 25 cycles
70 ms 44 cycles
100 ms 54 cycles
39 <1 ms 4 cycles
100 ms 17 cycles
45 <1 ms 14 cycles
10 ms 21 cycles
50 ms 58 cycles
70 ms 76 cycles
100 ms 101 cycles
60 <1 ms 16 cycles
10 ms 21 cycles
20 ms 35 cycles
50 ms 89 cycles
70 ms 119 cycles
100 ms 163 cycles

428 31006929.00 10/2005


Modbus Client Performance

Modbus Client Response Times: Premium TSXP57304M

Test Setup The following charts show Premium CPU response times where the client request
block is triggered in PLC logic by reading data from a Modbus server. The graphs
represent the number of CPU cycles required for the PLC to complete all triggered
Modbus client requests. In all cases, the PLC is a Premium TSXP57304M with an
ETY5103 Ethernet communications module (exec v3.10). The CPU logic scan times
vary.
Modbus client response times are tracked with respect to six Modbus server
response times:
z < 1 ms
z 10 ms
z 20 ms
z 50 ms
z 70 ms
z 100 ms

at a CPU Scan
Time of 200 ms
CPU Cycles

50 ms 20 ms
100 ms 70 ms

100 ms 50 ms 70 ms 10 ms
20 ms

Communications Completed

A sampling of results in the chart follows:


Number of Requests Server Response Time CPU Cycles Needed To Complete
1 ... 4 <1 ... 100 ms 2 cycles
5 100 ms 3 cycles
9 50 ms 3 cycles
14 70 ms 3 cycles

31006929.00 10/2005 429


Modbus Client Performance

Number of Requests Server Response Time CPU Cycles Needed To Complete


20 100 ms 4 cycles
23 20 ms 3 cycles
70 ms 4 cycles
100 ms 5 cycles
28 50 ms 4 cycles
70 ms 5 cycles
100 ms 6 cycles
36 10 ms 3 cycles
20 ms 4 cycles
50 ms 5 cycles
70 ms 7 cycles
100 ms 9 cycles
43 20 ms 5 cycles
50 ms 7 cycles
70 ms 9 cycles
100 ms 13 cycles
48 50 ms 10 cycles
70 ms 13 cycles
100 ms 18 cycles

430 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 100 ms

CPU Cycles

70 ms
50 ms

100 ms
20 ms

100 ms 70 ms
50 ms
10 ms
20 ms

Communications Completed

A sampling of results in the chart follows:


Number of Requests Server Response Time CPU Cycles Needed To Complete
1 <1 ... 50 ms 2 cycles
70 ... 100 ms 3 cycles
2 ... 4 <1 ... 100 ms 2 cycles
5 100 ms 3 cycles
6 50 ... 70 ms 3 cycles
15 20 ... 50 ms 3 cycles
70 ms 3 cycles
100 ms 5 cycles
18 20 ms 4 cycles
50 ms 3 cycles
70 ms 4 cycles
24 50 ms 5 cycles
70 ms 3 cycles
100 ms 5 cycles

31006929.00 10/2005 431


Modbus Client Performance

Number of Requests Server Response Time CPU Cycles Needed To Complete


32 10 ms 3 cycles
20 ms 5 cycles
50 ms 8 cycles
70 ms 9 cycles
100 ms 13 cycles
48 10 ms 4 cycles
20 ms 8 cycles
50 ms 18 cycles
70 ms 24 cycles
100 ms 34 cycles

at a CPU Scan
Time of 50 ms
CPU Cycles

70 ms
50 ms

20 ms
100 ms
10 ms

Communications Completed

A sampling of results in the chart follows:


Number of Requests Server Response Time CPU Cycles Needed To Complete
1 <1 ... 20 ms 2 cycles
50 ms 3 cycles
70 ms 4 cycles
100 ms 6 cycles
2 70 ms 3 cycles
100 ms 4 cycles

432 31006929.00 10/2005


Modbus Client Performance

Number of Requests Server Response Time CPU Cycles Needed To Complete


4 50 ms 4 cycles
8 20 ms 3 cycles
70 ms 5 cycles
100 ms 6 cycles
15 10 ms 3 cycles
20 ms 4 cycles
50 ms 7 cycles
70 ms 6 cycles
100 ms 8 cycles
22 <1 ms 3 cycles
20 ms 6 cycles
50 ms 9 cycles
70 ms 10 cycles
100 ms 14 cycles
35 10 ... 20 ms 7 cycles
50 ms 17 cycles
70 ms 22 cycles
100 ms 31 cycles
48 20 ms 10 cycles
50 ms 37 cycles
70 ms 51 cycles
100 ms 73 cycles

31006929.00 10/2005 433


Modbus Client Performance

at a CPU Scan
Time of 10 ms

CPU Cycles

70 ms
50 ms

100 ms
70 ms 20 ms 10 ms
50 ms

Communications Completed

A sampling of results in the chart follows:


Number of Requests Server Response Time CPU Cycles Needed To Complete
1 <1 ... 10 ms 2 cycles
20 ms 4 cycles
50 ms 5 cycles
70 ms 3 cycles
100 ms 5 cycles
2 10 ms 3 cycles
3 <1 ms 3 cycles
70 ms 4 cycles
100 ms 6 cycles
11 <1 ms 4 cycles
10 ms 5 cycles
20 ms 6 cycles
50 ms 15 cycles
70 ms 12 cycles
100 ms 22 cycles

434 31006929.00 10/2005


Modbus Client Performance

Number of Requests Server Response Time CPU Cycles Needed To Complete


18 <1 ms 5 cycles
10 ms 6 cycles
20 ms 13 cycles
50 ms 16 cycles
70 ms 22 cycles
100 ms 28 cycles
22 <1 ms 6 cycles
10 ms 7 cycles
20 ms 18 cycles
50 ms 27 cycles
70 ms 35 cycles
100 ms 50 cycles
39 <1 ms 9 cycles
10 ms 12 cycles
20 ms 33 cycles
50 ms 81 cycles
70 ms 109 cycles
100 ms 159 cycles
48 <1 ms 10 cycles
20 ms 16 cycles
20 ms 64 cycles
50 ms 159 cycles
70 ms 220 cycles
100 ms 314 cycles

31006929.00 10/2005 435


Modbus Client Performance

Modbus Client Response Times: Quantum 140 CPU65150 with an Embedded


Ethernet Port

Test Setup The following charts show Quantum PLC response times where the client request
block is triggered in PLC logic by reading data from a Modbus server. The graphs
represent the number of CPU cycles required for the PLC to complete all triggered
Modbus client requests. In all cases, the PLC is a Quantum 140 CPU65150 with an
embedded Ethernet port. The CPU logic scan times vary.
Modbus client response times are tracked with respect to six Modbus server
response times:
z < 1 ms
z 10 ms
z 20 ms
z 50 ms
z 70 ms
z 100 ms

436 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 200 ms

100 ms

70 ms
CPU Cycles

50 ms

10 ms

100 ms
50 ms

70 ms

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
200 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 1
2 1 1 1 1 1 2
3 1 1 1 1 2 2
4 1 1 1 2 2 3
5 2 2 2 2 3 3
6 2 2 2 2 3 4
7 2 2 2 3 3 4
8 2 2 2 3 4 5
9 3 3 3 3 4 5
10 3 3 3 4 5 6
11 3 3 3 4 5 6
12 3 4 3 4 5 7
13 4 4 4 4 6 7
14 4 4 4 5 6 8
15 4 4 4 5 6 8
16 4 5 4 6 7 9
17 5 5 5 6 7 9

31006929.00 10/2005 437


Modbus Client Performance

at a CPU Scan
Time of 100 ms

CPU Cycles

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
100 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 1
2 1 2 2 1 2 2
3 1 2 2 2 3 3
4 1 2 2 2 4 4
5 2 2 2 3 4 5
6 2 3 3 3 5 6
7 2 3 3 4 6 7
8 2 4 3 5 6 8
9 3 4 3 5 7 9
10 3 4 4 6 8 10
11 3 4 4 6 8 10
12 3 5 4 6 9 11
13 4 5 4 7 10 12
14 4 5 5 8 10 13
15 4 5 5 9 12 14
16 4 6 6 9 12 15
17 5 6 6 10 12 16

438 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 50 ms

CPU Cycles

Communications Completed
The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
50 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 2 1 1 2 2
2 1 3 2 2 3 4
3 1 4 2 3 4 6
4 1 4 3 4 6 8
5 2 5 3 5 7 10
6 2 5 4 6 8 12
7 2 5 4 7 9 13
8 2 6 4 8 11 15
9 3 6 5 9 12 17
10 3 6 5 10 13 19
11 3 6 6 11 15 21
12 3 7 6 12 16 23
13 4 7 7 13 17 24
14 4 7 7 13 18 26
15 4 8 9 15 22 30
16 4 8 10 17 22 30
17 5 8 10 17 22 32

31006929.00 10/2005 439


Modbus Client Performance

at a CPU Scan
Time of 10 ms

CPU Cycles

70 ms
50 ms

20 ms
100 ms
10 ms

Communications Completed
The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
10 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 2 2 3 5 5 8
2 2 3 4 10 11 17
3 2 4 6 15 18 26
4 2 4 8 19 24 35
5 3 5 10 24 31 44
6 3 6 12 28 37 54
7 3 7 14 33 43 63
8 3 8 15 37 50 72
9 4 9 17 42 56 81
10 4 10 19 47 63 90
11 4 11 21 51 69 100
12 4 12 23 56 76 109
13 5 13 25 60 82 118
14 5 14 48 65 88 127
15 5 17 48 80 106 144
16 6 17 48 80 106 146
17 6 17 48 80 108 155

440 31006929.00 10/2005


Modbus Client Performance

Modbus Client Response Times: Quantum 140 CPU65150 with a 140 NOE77101
Ethernet Communications Module

Test Setup The following charts show Quantum PLC response times where the client request
block is triggered in PLC logic by reading data from a Modbus server. The graphs
represent the number of CPU cycles required for the PLC to complete all triggered
Modbus client requests. In all cases, the PLC is a Quantum 140 CPU65150 with a
140 NOE77101 Ethernet communications module. The CPU logic scan times vary.
Modbus client response times are tracked with respect to six Modbus server
response times:
z < 1 ms
z 10 ms
z 20 ms
z 50 ms
z 70 ms
z 100 ms

31006929.00 10/2005 441


Modbus Client Performance

at a CPU Scan
Time of 200 ms

100 ms
CPU Cycles

100 ms 20 ms
50 ms
70 ms
100 ms 10 ms
20 ms
<1 ms
70 ms 50 ms 20 ms

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
200 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 2
2 1 1 1 1 2 2
3 1 1 1 2 2 2
4 1 1 1 2 2 3
5 1 2 2 2 3 3
6 1 2 2 2 3 3
7 1 2 2 2 3 4
8 1 2 2 2 3 4
9 1 2 2 3 4 5
10 1 2 2 3 4 5
11 1 2 2 3 4 6
12 1 2 2 3 5 6
13 1 2 3 3 5 7
14 1 2 3 4 5 7
15 1 2 3 4 6 8
16 1 2 3 4 6 8
17 2 3 3 5 6 8

442 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 100 ms
CPU Cycles

Communications Completed
The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
100 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 2
2 1 1 1 1 2 2
3 1 1 1 2 3 4
4 1 1 2 2 3 4
5 1 1 2 4 4 5
6 1 2 3 4 4 6
7 1 2 3 4 5 7
8 1 2 3 4 5 8
9 1 2 3 5 6 9
10 1 2 4 5 7 10
11 1 2 4 6 8 11
12 2 3 4 6 9 12
13 2 3 4 7 9 13
14 2 3 4 7 10 13
15 2 3 4 7 10 14
16 2 3 4 8 11 15
17 2 3 4 8 11 16

31006929.00 10/2005 443


Modbus Client Performance

at a CPU Scan
Time of 50 ms

CPU Cycles

Communications Completed
The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
50 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 2 2
2 1 1 1 2 3 4
3 1 1 2 4 5 7
4 1 1 3 5 6 8
5 1 2 4 6 7 9
6 2 2 4 6 8 11
7 2 3 4 7 9 12
8 2 3 4 8 10 14
9 2 4 5 9 11 16
10 2 4 6 9 13 19
11 2 4 6 10 14 20
12 3 5 6 11 15 21
13 3 5 6 12 16 23
14 3 5 6 13 17 25
15 3 5 6 14 19 27
16 3 5 6 15 20 29
17 3 5 7 16 21 31

444 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 10 ms

CPU Cycles

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
10 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 6 4 4 5 6 8
2 6 4 5 7 9 14
3 6 5 6 14 19 26
4 6 5 8 18 19 29
5 6 5 9 22 25 35
6 7 6 15 25 31 43
7 7 7 20 28 35 51
8 8 8 20 30 41 58
9 8 11 21 35 47 67
10 10 12 21 38 51 76
11 11 14 22 43 58 82
12 11 15 22 46 63 94
13 12 16 23 51 67 99
14 13 17 24 56 73 109
15 14 20 24 59 81 117
16 14 22 25 64 89 124
17 14 23 28 67 96 134

31006929.00 10/2005 445


Modbus Client Performance

Modbus Client Response Times: Quantum 140 CPU65150 with a 140 NOE77111
Ethernet Communications Module

Test Setup The following charts show Quantum PLC response times where the client request
block is triggered in PLC logic by reading data from a Modbus server. The graphs
represent the number of CPU cycles required for the PLC to complete all triggered
Modbus client requests. In all cases, the PLC is a Quantum 140 CPU65150 with a
140 NOE77111 Ethernet communications module. The CPU logic scan times vary.
Modbus client response times are tracked with respect to six Modbus server
response times:
z < 1 ms
z 10 ms
z 20 ms
z 50 ms
z 70 ms
z 100 ms

446 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 200 ms

70 ms
CPU Cycles

100 ms
50 ms

100 ms 70 ms 20 ms
50 ms
20 ms 10 ms
50 ms
100 ms

10 ms
70 ms 20 ms <1 ms

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
200 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 1
2 1 1 1 1 1 2
3 1 1 1 2 2 2
4 1 1 2 2 2 2
5 1 1 2 2 3 3
6 1 2 2 2 3 3
7 1 2 2 2 3 4
8 1 2 2 2 3 4
9 1 2 2 3 4 5
10 1 2 2 3 4 5
11 1 2 2 3 4 6
12 1 2 3 3 5 6
13 1 2 3 4 5 7
14 1 2 3 4 5 7
15 1 2 3 4 6 8
16 1 2 3 4 6 8
17 2 2 3 5 6 8

31006929.00 10/2005 447


Modbus Client Performance

at a CPU Scan
Time of 100 ms

CPU Cycles

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
100 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 2
2 1 1 1 1 2 2
3 1 1 1 2 3 4
4 1 1 2 4 3 4
5 1 1 2 4 4 5
6 1 2 3 4 4 6
7 1 2 3 4 5 7
8 1 2 4 4 6 8
9 1 2 4 5 6 9
10 1 2 4 5 7 10
11 2 3 4 6 8 11
12 2 3 4 6 8 12
13 2 3 4 7 9 13
14 2 3 4 7 10 13
15 2 3 4 7 10 14
16 2 3 4 8 11 15
17 2 3 4 8 12 16

448 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 50 ms

CPU Cycles

Communications Completed

The table below shows the data points used to generate the graph represented
above.
PLC Scan (ms) Server Response Time (ms)
50 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 2 2
2 1 1 1 2 3 4
3 1 1 2 4 6 7
4 2 2 3 5 6 7
5 2 2 4 5 7 9
6 2 2 4 6 8 11
7 2 3 4 7 9 13
8 2 3 5 8 10 14
9 2 3 5 8 11 16
10 2 4 6 9 13 19
11 3 4 6 10 14 20
12 3 4 6 11 15 21
13 3 5 6 12 16 23
14 3 5 6 13 18 25
15 3 5 6 14 19 27
16 3 5 6 15 20 29
17 3 5 7 16 22 31

31006929.00 10/2005 449


Modbus Client Performance

at a CPU Scan
Time of 10 ms

CPU Cycles

Communications Completed

The table below shows the data points used to generate the graph represented
above.
PLC Scan (ms) Server Response Time (ms)
10 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 6 4 4 5 5 8
2 6 5 5 8 10 15
3 7 5 6 16 18 28
4 7 5 6 18 19 29
5 7 6 7 21 25 36
6 7 6 19 26 30 43
7 7 7 21 28 35 51
8 7 7 21 30 41 58
9 8 12 21 34 46 66
10 9 12 21 38 51 74
11 9 14 22 42 57 82
12 10 14 22 46 63 91
13 11 16 23 50 69 99
14 12 17 24 55 75 108
15 13 19 24 59 81 117
16 13 22 26 64 88 126
17 14 23 28 68 95 136

450 31006929.00 10/2005


Modbus Client Performance

Modbus Client Response Times: Quantum 140 CPU43412A with a 140 NOE77101
Ethernet Communications Module

Test Setup The following charts show Modbus client response times where the client request
block is triggered in PLC logic by reading data from a Modbus server. The graphs
represent the number of CPU cycles required for the PLC to complete all triggered
Modbus client requests. In all cases, the PLC is a Quantum 140 CPU43412A with a
140 NOE77101 Ethernet communications module. The CPU logic scan times vary.
Modbus client response times are tracked with respect to six Modbus server
response times:
z < 1 ms
z 10 ms
z 20 ms
z 50 ms
z 70 ms
z 100 ms

31006929.00 10/2005 451


Modbus Client Performance

at a CPU Scan
Time of 200 ms 9
8
7
6
CPU Cycles

5
4
3
2
1

0 5 10 15 20
Communications Completed
The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
200 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 1
2 1 1 1 1 1 1
3 1 1 1 1 1 1
4 1 1 1 1 2 2
5 1 1 1 2 2 2
6 1 1 1 2 2 3
7 1 1 1 2 3 3
8 1 1 1 2 3 4
9 1 1 1 2 3 4
10 1 1 1 3 4 5
11 1 1 1 3 4 5
12 1 1 2 3 4 5
13 1 1 2 3 4 6
14 1 1 2 4 5 6
15 1 1 2 4 5 7
16 1 1 2 4 5 7
17 2 2 2 4 6 8

452 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 100 ms 16

14

12

10
CPU Cycles

0 5 10 15 20
Communications Completed
The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
100 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 1
2 1 1 1 1 1 2
3 1 1 1 2 2 3
4 1 1 2 2 3 4
5 1 1 2 2 3 4
6 1 1 2 3 3 5
7 1 1 2 3 4 6
8 1 1 2 4 4 6
9 1 1 2 4 5 7
10 1 1 2 4 6 8
11 1 1 2 5 6 9
12 1 1 2 5 7 10
13 1 2 2 6 7 10
14 1 2 3 6 8 11
15 1 3 3 6 8 12
16 1 3 3 7 9 13
17 2 3 3 7 9 14

31006929.00 10/2005 453


Modbus Client Performance

at a CPU Scan
Time of 50 ms 30

25

20
CPU Cycles

15

10

0 5 10 15 20
Communications Completed
The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
50 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 2 2
2 1 1 1 2 3 3
3 1 1 2 5 4 6
4 1 1 4 6 6 7
5 1 2 5 6 7 8
6 1 2 5 6 9 10
7 2 5 5 6 11 12
8 2 5 5 7 13 13
9 2 5 6 8 14 15
10 2 5 6 9 16 16
11 2 5 6 10 17 18
12 2 5 6 10 18 20
13 2 5 6 11 19 22
14 3 5 6 12 21 23
15 3 5 6 13 23 25
16 3 5 6 14 24 27
17 3 5 6 15 26 28

454 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 10 ms
CPU Cycles

100 ms
70 ms

50 ms

20 ms
100 ms
10 ms
50 ms

20 ms <1 ms
70 ms

Communications Completed
The table below shows the data points used to generate the graph represented
above.
PLC Scan (ms) Server Response Time (ms)
10 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 3 4 4 4 4 5
2 4 4 5 7 8 10
3 5 7 6 18 18 22
4 6 8 8 18 19 25
5 6 8 10 19 20 29
6 7 9 12 19 24 35
7 8 17 18 23 28 41
8 8 18 18 26 33 48
9 9 19 21 30 38 55
10 9 19 21 33 43 63
11 10 19 21 36 47 69
12 10 20 21 40 53 76
13 11 21 23 43 58 83
14 13 23 24 47 63 91
15 13 24 25 51 68 99
16 14 24 25 55 74 106
17 14 24 25 59 79 115

31006929.00 10/2005 455


Modbus Client Performance

Modbus Client Response Times: Quantum 140 CPU43412A with a 140 NOE77111
Ethernet Communications Module

Test Setup The following charts show Modbus client response times where the client request
block is triggered in PLC logic by reading data from a Modbus server. The graphs
represent the number of CPU cycles required for the PLC to complete all triggered
Modbus client requests. In all cases, the PLC is a Quantum 140 CPU43412A with a
140 NOE77111 Ethernet communications module. The CPU logic scan times vary.
Modbus client response times are tracked with respect to six Modbus server
response times:
z < 1 ms
z 10 ms
z 20 ms
z 50 ms
z 70 ms
z 100 ms

456 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 200 ms 9
8

6
CPU Cycles

3
2

0 5 10 15 20
Communications Completed

The table below shows the data points used to generate the graph represented
above.
PLC Scan (ms) Server Response Time (ms)
200 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 1
2 1 1 1 1 1 1
3 1 1 1 1 1 1
4 1 1 1 1 2 2
5 1 1 1 1 2 2
6 1 1 1 2 2 3
7 1 1 1 2 2 3
8 1 1 1 2 3 4
9 1 1 1 2 3 4
10 1 1 1 2 4 5
11 1 1 2 3 4 5
12 1 1 2 3 4 5
13 1 1 2 3 4 6
14 1 1 2 3 5 6
15 1 1 2 4 5 6
16 1 1 2 4 5 7
17 2 2 2 4 6 8

31006929.00 10/2005 457


Modbus Client Performance

at a CPU Scan
Time of 100 ms

CPU Cycles

70 ms
100 ms

50 ms

20 ms
70 ms 50 ms 10 ms
20 ms
100 ms
20 ms 10 ms <1 ms <1 ms
50 ms

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
100 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 1 1
2 1 1 1 1 1 2
3 1 1 1 1 2 3
4 1 1 1 2 2 3
5 1 1 1 2 3 4
6 1 1 2 3 3 5
7 1 1 2 3 4 6
8 1 1 2 3 4 6
9 1 1 2 4 5 7
10 1 1 2 4 6 8
11 1 1 2 4 6 9
12 1 2 2 5 7 9
13 1 2 2 6 7 10
14 1 2 2 6 8 11
15 1 3 3 6 9 12
16 1 3 3 6 9 13
17 2 3 3 7 9 14

458 31006929.00 10/2005


Modbus Client Performance

at a CPU Scan
Time of 50 ms

100 ms
CPU Cycles

70 ms

50 ms
20 ms
100 ms
20 ms 10 ms
70 ms <1 ms
20 ms
50 ms

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
50 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 1 1 1 1 2 2
2 1 1 1 2 3 3
3 1 1 3 4 4 5
4 1 1 3 5 6 7
5 1 2 4 6 7 8
6 2 2 5 6 8 9
7 2 3 5 6 10 12
8 2 3 5 6 12 13
9 2 4 5 8 14 15
10 2 5 6 9 16 17
11 3 5 6 10 17 18
12 3 5 6 10 19 20
13 3 5 6 11 19 22
14 3 5 6 12 21 24
15 3 5 6 13 23 25
16 3 5 6 13 24 27
17 3 5 6 15 25 28

31006929.00 10/2005 459


Modbus Client Performance

at a CPU Scan
Time of 10 ms

CPU Cycles

100 ms 70 ms

50 ms

20 ms
10 ms
<1 ms

Communications Completed

The table below shows the data points used to generate the graph above.
PLC Scan (ms) Server Response Time (ms)
10 <1 10 20 50 70 100
Requests Sent PLC Cycles to Receive Response
1 4 4 4 4 5 6
2 4 4 5 7 8 10
3 4 7 6 18 18 20
4 5 8 8 18 19 26
5 6 8 10 19 20 30
6 6 11 12 19 24 34
7 7 16 18 21 28 41
8 7 18 18 26 31 46
9 8 19 20 30 39 55
10 9 19 21 33 42 64
11 9 20 21 34 46 69
12 10 20 21 39 52 76
13 10 21 22 42 57 83
14 11 23 24 47 63 91
15 11 24 24 51 68 96
16 12 24 25 55 74 106
17 13 24 26 57 79 115

460 31006929.00 10/2005


Gateway Response Time and
Timeout Measurements
D
At a Glance

Overview This appendix illustrates some performance measurements for devices with various
response times when they communicate on a network through an EGX200,
EGX400, or 174CEV30020 serial gateway. Separate measurements are given for
devices that communicate successfully and for the same devices when a single
request failure is experienced.

What's in this This chapter contains the following sections:


Chapter?
Section Topic Page
D.1 EGX200 Gateway Serial Server Response Time and Timeout 462
Measurements
D.2 EGX400 Gateway Serial Server Response Time and Timeout 473
Measurements
D.3 174CEV30020 Gateway Serial Server Response Time and 484
Timeout Measurements

31006929.00 10/2005 461


Gateway Performance

D.1 EGX200 Gateway Serial Server Response Time


and Timeout Measurements

At a Glance

Overview The performance of serial devices with response times of 50 ms, 100 ms, 200 ms,
and 500 ms are measured as they communicate across a network through an
EGX200 Modbus-to-Ethernet gateway. Network speeds of 9600 baud and 19 200
baud are considered. Measurements are taken for both successful communications
and for situations where a single request failure is experienced followed by a
successful retry.

What's in this This section contains the following topics:


Section?
Topic Page
EGX200 Serial Server Response Times 463
EGX200 Serial Server Response Measurements with One Request Timeout 468

462 31006929.00 10/2005


Gateway Performance

EGX200 Serial Server Response Times

Test Setup The following charts track the time it takes to get responses from a certain number
of requests sent to devices connected on the serial side of the EGX200 gateway.
The performance is based on network baud rates of both 9600 and 19 200 and on
the amount of data (i.e., the number of registers) requested. The following legend
describes the baud rate and number of requests sent, as tracked in all four of the
charts that follow:
Curve Number of Requests Baud Rate
1 16 9600
2 19 200
3 8 9600
4 19 200
5 1 9600
6 19 200

31006929.00 10/2005 463


Gateway Performance

Serial Devices
with 50 ms
Response Time
Time (ms)

2
3
4

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 50
EGX200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 250.8333333 694.1666667 1200.833333 244.1666667 640.83333333 1094.166667 187.5
16 300.8333333 1094.166667 2000.833333 269.1666667 840.8333333 1494.166667 187.5
32 354.1666667 1520.833333 2854.166667 295.8333333 1054.1666667 1920.833333 187.5
64 460.8333333 2374.166667 4560.833333 349.1666667 1480.833333 2774.166667 187.5
100 580.8333333 3334.166667 6480.833333 409.1666667 1960.833333 3734.166667 187.5

464 31006929.00 10/2005


Gateway Performance

Serial Devices
with 100 ms
Response Time

1
Time (ms)

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 100
EGX200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 300.8333333 1094.166667 2000.833333 294.1666667 1040.833333 1894.166667 187.5
16 350.8333333 1494.166667 2800.833333 319.1666667 1240.833333 2294.166667 187.5
32 404.1666667 1920.833333 3654.166667 345.8333333 1454.166667 2720.833333 187.5
64 510.8333333 2774.166667 5360.833333 399.166667 1880.833333 3574.166667 187.5
100 630.8333333 3734.166667 7280.833333 459.166667 2360.833333 4534.166667 187.5

31006929.00 10/2005 465


Gateway Performance

Serial Devices
with 200 ms
Response Time

1
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 200
EGX200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 400.8333333 1894.166667 3600.833333 394.1666667 1840.833333 3494.166667 187.5
16 450.8333333 2294.166667 4400.833333 419.1666667 2040.833333 3894.166667 187.5
32 504.1666667 2720.833333 5254.166667 445.8333333 2254.166667 4320.833333 187.5
64 610.8333333 3574.166667 6960.833333 499.1666667 2680.833333 5174.166667 187.5
100 730.8333333 4534.166667 8880.833333 559.1666667 3160.833333 6134.166667 187.5

466 31006929.00 10/2005


Gateway Performance

Serial Devices
with 500 ms
Response Time

2
Time (ms)

3
4

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 500
EGX200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 700.8333333 4294.16667 8400.833333 694.1666667 4240.833333 8294.166667 187.5
16 750.8333333 4694.16667 9200.833333 719.1666667 4440.833333 8694.166667 187.5
32 804.1666667 5120.83333 10054.16667 745.8333333 4654.166667 9120.833333 187.5
64 910.8333333 5974.16667 11760.83333 799.1666667 5080.833333 9974.166667 187.5
100 1030.833333 6934.16667 13680.83333 859.1666667 5560.833333 10934.16667 187.5

31006929.00 10/2005 467


Gateway Performance

EGX200 Serial Server Response Measurements with One Request Timeout

Test Setup The following charts show the time it takes to get responses from a certain number
of requests sent to devices connected on the serial side of the EGX200 gateway
when the system experiences a failure of one communications request (e.g., a
disconnected serial device). The failure results in a 1000 ms timeout of the initial
request followed by one retry of the request.

Note: One request failure increases the response times for all requests.

The performance is based on network baud rates of both 9600 and 19 200 and on
the amount of data (i.e., the number of registers) requested. The following legend
describes the baud rate and number of requests sent, as tracked in all four of the
charts that follow:
Curve Number of Requests Baud Rate
1 16 9600
2 19 200
3 8 9600
4 19 200
5 1 9600
6 19 200

468 31006929.00 10/2005


Gateway Performance

Serial Devices
with 50 ms
Response Time

2
3
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 50 Timeout
EGX200 Time to Complete All Requests 1000 ms
1 Retry
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2200.83 2644.163333 3150.83 2194.17 2590.836667 3044.17 187.5
16 2200.83 2994.163333 3900.83 2194.17 2765.836667 3419.17 187.5
32 2200.83 3367.496667 4700.83 2194.17 2952.50333 3819.17 187.5
64 2200.83 4114.163333 6300.83 2194.17 3325.836667 4619.17 187.5
100 2200.83 4954.163333 8100.83 2194.17 3745.83667 5519.17 187.5

31006929.00 10/2005 469


Gateway Performance

Serial Devices
with 100 ms
Response Time

2
3
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 100 Timeout
EGX200 Time to Complete All Requests 1000 ms
1 Retry
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2200.83 2994.163333 3900.83 2194.17 2940.836667 3794.17 187.5
16 2200.83 3344.163333 4650.83 2194.17 3115.836667 4169.17 187.5
32 2200.83 3717.496667 5450.83 2194.17 3302.50333 4569.17 187.5
64 2200.83 4464.163333 7050.83 2194.17 3675.836667 5369.17 187.5
100 2200.83 5304.163333 8850.83 2194.17 4095.836667 6269.17 187.5

470 31006929.00 10/2005


Gateway Performance

Serial Devices
with 200 ms
Response Time

1
Time (ms)

3
4

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 200 Timeout
EGX200 Time to Complete All Requests 1000 ms
1 Retry
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2200.83 3694.163333 5400.83 2194.17 3640.836667 5294.17 187.5
16 2200.83 4044.163333 6150.83 2194.17 3815.836667 5669.17 187.5
32 2200.83 4417.496667 6950.83 2194.17 4002.50333 6069.17 187.5
64 2200.83 5164.163333 8550.83 2194.17 4375.836667 6869.17 187.5
100 2200.83 6004.163333 10350.83 2194.17 4795.83667 7769.17 187.5

31006929.00 10/2005 471


Gateway Performance

Serial Devices
with 500 ms
Response Time
1
2

3
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 500 Timeout
EGX200 Time to Complete All Requests 1000 ms
1 Retry
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2200.83 5794.163333 9900.83 2194.17 5740.836667 9794.17 187.5
16 2200.83 6114.163333 10650.83 2194.17 5915.836667 10169.17 187.5
32 2200.83 6517.496667 11450.83 2194.17 6102.50333 10569.17 187.5
64 2200.83 7264.163333 13050.83 2194.17 6475.836667 11369.17 187.5
100 2200.83 8104.163333 14850.83 2194.17 6895.83667 12269.17 187.5

472 31006929.00 10/2005


Gateway Performance

D.2 EGX400 Gateway Serial Server Response Time


and Timeout Measurements

At a Glance

Overview The performance of serial devices with response times of 50 ms, 100 ms, 200 ms,
and 500 ms are measured as they communicate across a network through an
EGX400 Modbus-to-Ethernet gateway. Network speeds of 9600 baud and 19 200
baud are considered. Measurements are taken for both successful communications
and for situations where a single request failure is experienced followed by a
successful retry.

What's in this This section contains the following topics:


Section?
Topic Page
EGX400 Gateway Serial Server Response Times 474
EGX400 Serial Server Response Measurements with One Request Timeout 479

31006929.00 10/2005 473


Gateway Performance

EGX400 Gateway Serial Server Response Times

Test Setup The following charts track the time it takes to get responses from a certain number
of requests sent to devices connected on the serial side of the EGX400 gateway.
The performance is based on network baud rates of both 9600 and 19 200 and on
the amount of data (i.e., the number of registers) requested. The following legend
describes the baud rate and number of requests sent, as tracked in all four of the
charts that follow:
Curve Number of Requests Baud Rate
1 16 9600
2 19 200
3 8 9600
4 19 200
5 1 9600
6 19 200

474 31006929.00 10/2005


Gateway Performance

Serial Devices
with 50 ms
Response Time

1
Time (ms)

2
3

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 50
EGX200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 235.3333333 678.6666667 1185.333333 228.6666667 625.33333333 1078.666667 172
16 285.3333333 1078.666667 1985.333333 253.6666667 825.3333333 1478.666667 172
32 338.6666667 1505.333333 2838.666667 280.3333333 1038.6666667 1905.333333 172
64 445.3333333 2358.666667 4545.333333 333.6666667 1465.333333 2758.666667 172
100 565.3333333 3318.666667 6465.333333 393.6666667 1945.333333 3718.666667 172

31006929.00 10/2005 475


Gateway Performance

Serial Devices
with 100 ms
Response Time

1
Time (ms)

3
4

5
6

Number of Registers
The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 100
EGX200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 285.3333333 1078.666667 1985.333333 278.6666667 1025.3333333 1878.666667 172
16 335.3333333 1478.666667 2785.333333 303.6666667 1225.3333333 2278.666667 172
32 388.6666667 1905.333333 3638.666667 330.3333333 1438.6666667 2705.333333 172
64 495.3333333 2758.666667 5345.333333 383.6666667 1865.333333 3558.666667 172
100 615.3333333 3718.666667 7265.333333 443.6666667 2345.333333 4518.666667 172

476 31006929.00 10/2005


Gateway Performance

Serial Devices
with 200 ms
Response Time

2
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 200
EGX200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 385.3333333 1878.666667 3585.333333 378.666667 1825.3333333 3478.666667 172
16 435.3333333 2278.666667 4385.333333 403.666667 2025.3333333 3878.666667 172
32 488.6666667 2705.333333 5238.666667 430.333333 2238.6666667 4305.333333 172
64 595.3333333 3558.666667 6945.333333 483.666667 2665.3333333 5158.666667 172
100 715.3333333 4518.666667 8865.333333 543.666667 3145.3333333 6118.666667 172

31006929.00 10/2005 477


Gateway Performance

Serial Devices
with 500 ms
Response Time

2
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 500
EGX200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 685.3333333 4278.666667 8385.333333 678.6666667 4225.333333 8278.666667 172
16 735.3333333 4678.666667 9185.333333 703.6666667 4425.333333 8678.666667 172
32 788.6666667 5105.333333 10038.66667 730.3333333 4638.666667 9105.333333 172
64 895.3333333 5958.666667 11745.33333 783.6666667 5065.333333 9958.666667 172
100 1015.333333 6918.666667 13665.33333 843.6666667 5545.333333 10918.66667 172

478 31006929.00 10/2005


Gateway Performance

EGX400 Serial Server Response Measurements with One Request Timeout

Test Setup The following charts show the time it takes to get responses from a certain number
of requests sent to devices connected on the serial side of the EGX400 gateway
when the system experiences a failure of one communications request (e.g., a
disconnected serial device). The failure results in a 1000 ms timeout of the initial
request followed by one retry of the request.

Note: One request failure increases the response times for all requests.

The performance is based on network baud rates of both 9600 and 19 200 and on
the amount of data (i.e., the number of registers) requested. The following legend
describes the baud rate and number of requests sent, as tracked in all four of the
charts that follow:
Curve Number of Requests Baud Rate
1 16 9600
2 19 200
3 8 9600
4 19 200
5 1 9600
6 19 200

31006929.00 10/2005 479


Gateway Performance

Serial Devices
with 50 ms
Response Time

2
3
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 50 Timeout
EGX400 Time to Complete All Requests 1000 ms
1 Retry
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2185.33 2628.663333 3135.33 2178.67 2575.336667 3028.167 172
16 2185.33 2978.663333 3885.33 2178.67 2750.336667 3403.167 172
32 2185.33 3351.996667 4685.33 2178.67 2937.003333 3803.67 172
64 2185.33 4098.663333 6285.33 2178.67 3310.336667 4603.67 172
100 2185.33 4938.663333 8085.33 2178.67 3730.336667 5503.67 172

480 31006929.00 10/2005


Gateway Performance

Serial Devices
with 100 ms
Response Time

2
Time (ms)

3
4

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 100 Timeout
EGX400 Time to Complete All Requests 1000 ms
1 Retry
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2185.33 2978.663333 3885.33 2178.67 2925.336667 3778.67 172
16 2185.33 3328.663333 4635.33 2178.67 3100.336667 4153.67 172
32 2185.33 3701.996667 5435.33 2178.67 3287.003333 4553.67 172
64 2185.33 4448.663333 7035.33 2178.67 3660.336667 5353.67 172
100 2185.33 5288.663333 8835.33 2178.67 4080.336667 6253.67 172

31006929.00 10/2005 481


Gateway Performance

Serial Devices
with 200 ms
Response Time

1
2

3
Time (ms)

Number of Registers
The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 200 Timeout
EGX400 Time to Complete All Requests 1000 ms
1 Retry
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2185.33 3678.663333 5385.33 2178.67 3625.336667 5278.67 172
16 2185.33 4028.663333 6135.33 2178.67 3800.336667 5653.67 172
32 2185.33 4401.996667 6935.33 2178.67 3987.003333 6053.67 172
64 2185.33 5148.663333 8535.33 2178.67 4360.336667 6853.67 172
100 2185.33 5988.663333 10335.33 2178.67 4780.336667 7753.67 172

482 31006929.00 10/2005


Gateway Performance

Serial Devices
with 500 ms
Response Time

1
2
Time (ms)

3
4

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 500 Timeout
EGX400 Time to Complete All Requests 1000 ms
1 Retry
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2185.33 5778.663333 9885.33 2178.67 5725.336667 9778.67 172
16 2185.33 6128.663333 10635.33 2178.67 5900.336667 10153.67 172
32 2185.33 6501.996667 11435.33 2178.67 6087.003333 10553.67 172
64 2185.33 7248.663333 13035.33 2178.67 6460.336667 11353.67 172
100 2185.33 8088.663333 14835.33 2178.67 6880.336667 12253.67 172

31006929.00 10/2005 483


Gateway Performance

D.3 174CEV30020 Gateway Serial Server Response


Time and Timeout Measurements

At a Glance

Overview The performance of serial devices with response times of 50 ms, 100 ms, 200 ms,
and 500 ms are measured as they communicate across a network through a
174CEV30020 Modbus-to-Ethernet gateway. Network speeds of 9600 baud and
19 200 baud are considered. Measurements are taken for both successful
communications and for situations where a single request failure is experienced
followed by a successful retry.

What's in this This section contains the following topics:


Section?
Topic Page
174CEV30020 Gateway Serial Server Response Times 485
174CEV30020 Serial Server Response Measurements with One Request 490
Timeout

484 31006929.00 10/2005


Gateway Performance

174CEV30020 Gateway Serial Server Response Times

Test Setup The following charts track the time it takes to get responses from a certain number
of requests sent to devices connected on the serial side of the 174CEV30020
gateway. The performance is based on network baud rates of both 9600 and 19 200
and on the amount of data (i.e., the number of registers) requested. The following
legend describes the baud rate and number of requests sent, as tracked in all four
of the charts that follow:
Curve Number of Requests Baud Rate
1 16 9600
2 19 200
3 8 9600
4 19 200
5 1 9600
6 19 200

31006929.00 10/2005 485


Gateway Performance

Serial Devices
with 50 ms
Response Time

1
Time (ms)

2
3

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 50
CEV300200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 201.3333333 644.6666667 1151.833333 194.6666667 591.8333333 1044.166667 138
16 251.3333333 1044.666667 1951.833333 219.6666667 791.8333333 1444.166667 138
32 304.6666667 1471.333333 2804.166667 246.3333333 1004.166667 1871.833333 138
64 411.3333333 2324.666667 4511.833333 299.6666667 1431.833333 2724.166667 138
100 531.3333333 3284.666667 6431.833333 359.6666667 1911.833333 3684.166667 138

486 31006929.00 10/2005


Gateway Performance

Serial Devices
with 100 ms
Response Time

1
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 100
CEV300200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 251.33333 1044.66667 1951.333333 244.66667 991.333333 1844.666667 138
16 301.33333 1444.6667 2751.333333 269.66667 1191.33333 2244.666667 138
32 354.66667 1871.33333 3604.666667 296.33333 1404.66667 2671.333333 138
64 461.33333 2724.66667 5311.333333 349.66667 1831.33333 3524.666667 138
100 581.33333 3684.66667 7231.333333 409.66667 2311.33333 4484.666667 138

31006929.00 10/2005 487


Gateway Performance

Serial Devices
with 200 ms
Response Time

1
Time (ms)

5
6

Number of Registers
The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 200
CEV300200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 351.33333 1844.66667 3551.333333 344.66667 1791.333333 3444.666667 138
16 401.33333 2244.66667 4351.333333 369.66667 1991.33333 3844.666667 138
32 454.66667 2671.33333 5204.666667 396.33333 2204.66667 4271.333333 138
64 561.33333 3524.66667 6911.333333 449.66667 2631.33333 5124.666667 138
100 681.33333 4484.66667 8831.333333 509.66667 3111.33333 6084.666667 138

488 31006929.00 10/2005


Gateway Performance

Serial Devices
with 500 ms
Response Time

2
Time (ms)

3
4

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 500
CEV300200 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 651.33333 4244.66667 8351.333333 644.66667 4191.333333 8244.666667 138
16 701.33333 4644.66667 9151.333333 669.66667 4391.33333 8644.666667 138
32 754.66667 5071.33333 10004.66667 696.33333 4604.66667 9071.333333 138
64 861.33333 5924.66667 11711.33333 749.66667 5031.33333 9924.666667 138
100 981.33333 6884.66667 13631.33333 809.66667 5511.33333 10884.66667 138

31006929.00 10/2005 489


Gateway Performance

174CEV30020 Serial Server Response Measurements with One Request Timeout

Test Setup The following charts show the time it takes to get responses from a certain number
of requests sent to devices connected on the serial side of the 174CEV30020
gateway when the system experiences a failure of one communications request
(e.g., a disconnected serial device). The failure results in a 1000 ms timeout of the
initial request followed by one retry of the request.

Note: One request failure increases the response times for all requests.

The performance is based on network baud rates of both 9600 and 19 200 and on
the amount of data (i.e., the number of registers) requested. The following legend
describes the baud rate and number of requests sent, as tracked in all four of the
charts that follow:
Curve Number of Requests Baud Rate
1 16 9600
2 19 200
3 8 9600
4 19 200
5 1 9600
6 19 200

490 31006929.00 10/2005


Gateway Performance

Serial Devices
with 50 ms
Response Time

1
Time (ms)

2
3
4

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 50
CEV30020 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2151.33 2594.663333 3101.33 2144.67 2541.336667 2994.67 138
16 2151.33 2944.663333 3851.33 2144.67 2716.336667 3369.167 138
32 2151.33 3317.333333 4651.33 2144.67 2903.166667 3769.67 138
64 2151.33 4064.996667 6251.33 2144.67 3276.336667 4569.67 138
100 2151.33 4904.663333 8051.33 2144.67 3696.336667 5469.67 138

31006929.00 10/2005 491


Gateway Performance

Serial Devices
with 100 ms
Response Time

2
3
Time (ms)

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 100
CEV30020 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2151.33 2944.663333 3851.33 2144.67 2891.336667 3744.67 138
16 2151.33 3294.663333 4601.33 2144.67 3066.336667 4119.67 138
32 2151.33 3667.333333 5401.33 2144.67 3253.003333 4519.67 138
64 2151.33 4414.996667 7001.33 2144.67 3626.336667 5319.67 138
100 2151.33 5254.663333 8801.33 2144.67 4046.336667 6219.67 138

492 31006929.00 10/2005


Gateway Performance

Serial Devices
with 200 ms
Response Time

2
Time (ms)

3
4

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 200
CEV30020 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2151.33 3644.663333 5351.33 2144.67 3591.336667 5244.67 138
16 2151.33 3994.663333 6101.33 2144.67 3766.336667 5619.67 138
32 2151.33 4367.333333 6901.33 2144.67 3953.003333 6019.67 138
64 2151.33 5114.996667 8501.33 2144.67 4326.336667 6819.67 138
100 2151.33 5954.663333 10301.33 2144.67 4746.336667 7719.67 138

31006929.00 10/2005 493


Gateway Performance

Serial Devices
with 500 ms
Response Time

1
2
Time (ms)

3
4

5
6

Number of Registers

The table below shows the data points used to generate the graph above.
Device Serial Server Response TIme = 200
CEV30020 Time to Complete All Requests
Baud Rate 9600 19200
Number of 1 Request 8 Requests 16 Requests 1 Request 8 Requests 16 Requests Bridge
Registers Time
1 2151.33 5744.663333 9851.33 2144.67 5691.336667 9744.67 138
16 2151.33 6094.663333 10601.33 2144.67 5866.336667 10119.67 138
32 2151.33 6467.333333 11401.33 2144.67 6053.003333 10519.67 138
64 2151.33 7214.996667 13001.33 2144.67 6426.336667 11319.67 138
100 2151.33 8054.663333 14801.33 2144.67 6846.336667 12219.67 138

494 31006929.00 10/2005


Standards and Other
Considerations for Industrial
Ethernet Networks E
At a Glance

Overview This appendix provides additional material in support of the standards and planning
information presented in Chapter 2 (see p. 29).

What's in this This chapter contains the following topics:


Chapter?
Topic Page
Standards and Organizations 496
Electromagnetic Compatibility 506
Copper Connector Standards Activities 510
Conforming to Standards 511
Transparent Ready Industrial Ethernet Conformance 514

31006929.00 10/2005 495


Standards and Considerations

Standards and Organizations

Standards Several standards organizations develop generic cabling requirements. The


Organizations Electronics Industries Alliance (EIA) and the Telecommunications Industry
Association (TIA) develop and approve the LAN cable standards. Other groups
develop network standards that affect cabling specifications.
Standards Organization WebSite Description Area of Influence
EIA www.eia.org An association of seven electronics industry U.S. and Canada
sectors and groups, including the TIA,
CEMA, ECA, EIG, GEIA, JEDEC, and EIF.
TIA www.tiaonline.org An association of mostly U.S. and Canadian U.S. and Canada
companies that provides communications
and information technology products,
materials, systems, distribution services,
and professional services.
IEC (International www.iec.ch International standards and conformity Worldwide
Electrotechnical assessment body for all fields of electro
Committee) technology.
ISO (International www.iso.org Worldwide federation of national standards Worldwide
Standards Organization) institutes from 146 countries. Cabling
standards is a very small part of the ISO's
total responsibilities.
CENELEC (Comité www.cenelec.org Develops electro technical standards for the Europe
Européen de Normalisation European Market/European Economic Area.
Electrotechnique) Many CENELEC cabling standards mirror
ISO cabling standards with minor
differences.
Canadian Standards www.csa.ca An association that works internationally to Canada
Association (CSA) set standards for products and services
through tests, certification, inspection for
safety and performance, including EMC and
IEC testing.
IEEE 802.3 (International www.ieee.org A working group that develops standards for Worldwide
Electrical and Electronics CSMA/CD (Ethernet) based LANs, including
Engineers) 1000Base-T and 100Base-T.

496 31006929.00 10/2005


Standards and Considerations

Standards Organization WebSite Description Area of Influence


ANSI www.ansi.org Facilitates development of the American Worldwide
National Standards. ANSI is the sole U.S.
representative and dues-paying member of
the two major non-treaty international
standards organizations, ISO and IEC (via
the U.S. National Committee (USNC)).
Through ANSI, the U.S. has immediate
access to the ISO and IEC standards
development processes.
Internet Engineering Task www.ietf.org IETF is a large open international community Worldwide
Force (IETF) of network designers, operators, vendors,
and researchers concerned with the
evolution of the Internet architecture and the
smooth operation of the Internet. It is the
organization taking care of the Internet suite
of protocols (TCP/IP)
Internet Assigned Numbers www.iana.org Dedicated to preserving the central Worldwide
Authority coordinating functions of the global Internet:
protocol number assignment, domain name
assignment.

Other industrial Ethernet organizations provide recommendations and support these


standards organizations, but they do not define standards.

Internet Suite of The IETF is an IT organization that takes care of the TCP/IP suite. This organization
TCP/IP manages the evolution of protocols such as TCP, IP, UDP, SNMP, HTTP, and FTP.
Standards
Requirements for Internet Hosts RFC 1122 IETF Network Working Group, R. Branden,
Communication Layers Ed., RFC-1122 (STD-0003), October 1989

Modbus
Industrial
Modbus Application Protocol Specification Modbus-IDA - Version 1.1a, June 2004 IEC
Application
PAS
Protocol
Standard

31006929.00 10/2005 497


Standards and Considerations

TIA/EIA-568-A TIA/EIA-568-A is one of the first cabling standards. It was developed jointly by TIA
Standard and EIA to define the wiring system for voice and data networks as a structured,
hierarchical star-topology network in which high-speed (fiber optic) cables feed
slower peripheral networks. The standard was incorporated into TIA/EIA-568-B in
2000.
Standard Focus Description
TIA/EIA-568-A-1995 Commercial building Defines a standard for building cable systems for
telecommunications commercial buildings that support data networks,
Wiring standards voice, and video. It also defines technical and
performance criteria for cabling.
TIA/EIA-568-A (1998-1999) Updates A1 outlines propagation delay and delay skew
parameters. A2 specifies miscellaneous changes. A3
defines requirements for bundled and hybrid cables.A4
defines NEXT and return loss requirements for patch
cables. A5 defines performance requirements for
Enhanced Category 5 (CAT5e).
TIA/EIA-568-B.1-2000 Commercial building Incorporates previous updates into a new release and
telecommunications specifies Category 5e cable as preferred due to its
Wiring standards performance. Several addenda specify technical
information for 100 Ω twisted-pair cable, shielded
twisted-pair cable, and optical fiber cable.
ANSI/TIA/EIA-568-B.2 100 Ω twisted-pair cabling
standard
ANSI/TIA/EIA-568-B.3 Optical fiber standard
TIA/EIA-569-A-1995 Commercial building standard Specifies how to build pathways and spaces for
for telecommunications telecommunication media.
pathways and spaces
TIA/EIA-606-1994 Building infrastructure Defines design guidelines for managing a
administration standard telecommunications infrastructure.
TIA/EIA-607-1995 Grounding and bonding Defines grounding and equipotential bonding
requirements requirements for telecommunications cabling and
equipment.
ANSI/EIA/TIA-570-A Residential
telecommunications cabling
standard

498 31006929.00 10/2005


Standards and Considerations

The TIA/EIA standards define a structured cabling system that is designed and built
in multiple blocks. The blocks are integrated into a hierarchical network to create a
unified communication system. LANs represent blocks with lower-performance
requirements while backbone network blocks, which require high-performance fiber
optic cable, perform the work of connecting the blocks to each other in a star-
topology. The standard also specifies the requirements for fiber-optic (single and
multimode), STP, and UTP cable.
In general, the TIA/EIA 568 wiring standard provides:
z specifications for a generic telecommunications wiring system for commercial
buildings
z specifications for media, network topology, termination and connection
(grounding) points, and administration of wiring systems
z support for environments that use several different products and vendors
z information about planning and installing a telecommunications network for
buildings

ISO/IEC IS 11801 The ISO/IEC 11081 and EN 50173 standards define the structure and configuration
and EN 50173 of cabling systems for office buildings and campuses. They are almost identical in
Standards scope and content, have the same terminology, and provide the same technical
information. This generic cabling system is application-independent and consists of
an open system of cabling components that are easy to implement. The cabling
system described in the standard supports a range of services including voice, data,
image, and video.
This table summarizes updates to the ISO/IEC-11801 standard.
Standard Description
ISO/IEC-11801:1995 Generic customer Based on the TIA/EIA-568
premises cabling cabling standard; defines a
telecommunications cabling
system for office buildings and
campuses.
ISO/IEC-11801:2000 Generic customer Released in 2000; updates
premises cabling, 2nd earlier standard based on new
Edition releases of the TIA/EIA-568
standard.
Administration, ISO/IEC 14763-1
documentation, records
Planning and Installation ISO/IEC 14763-2
practices
Testing of optical fibre ISO/IEC 14763-3
cabling
Testing of copper cabling IEC 61935-1

31006929.00 10/2005 499


Standards and Considerations

This table summarizes the EN 50173 and related standards.


European Standards Documents Reference
Building Design Phase
Application of Equipotential Bonding and Earthing in EN 50310
Buildings with Information Technology Equipment
Coding Design Phase
Information technology - Generic cabling systems EN 50173 (and/or EN 50098-1 or -2):
Planning Design Phase
Specification and Quality Assurance EN 50174-1
Installation planning and practices inside buildings EN 50174-2
Installation planning and practices outside buildings EN 50174-3
Testing of Installed Cabling EN 50346
Application of Equipotential Bonding and Earthing in EN 50310
Buildings with Information Technology Equipment
Implementation Planning Phase
Specification and Quality Assurance EN 50174-1
Installation planning and practices inside buildings EN 50174-2
Installation planning and practices outside buildings EN 50174-3
Testing of Installed Cabling EN 50346
Application of Equipotential Bonding and Earthing in EN 50310
Buildings with Information Technology Equipment
Testing of Installed Cabling EN 50346
Operation Phase
Specification and Quality Assurance EN 50174 Part 1

The ISO/IEC-11801:2000 standard specifies cabling systems for commercial


properties which may include one or more buildings on a campus. The standard
defines the requirements for both copper and fiber optic cables. Although the
standard's focus is office buildings, the principles of the standard are applicable to
other types of installations.

500 31006929.00 10/2005


Standards and Considerations

In general, the ISO/IEC-11801 standard provides:


z the structure and minimum configuration for a generic cabling system
z performance requirements for individual cable links
z conformance requirements and verification procedures
z requirements of an installation
The standard does not cover specifications for cables used to connect application-
specific equipment to a cabling system. Standard guidelines relate to performance
and length of cables only as these have the most significant impact on transmission
quality. Safety and EMC are also not covered in the standard. Related information
in the ISO/IEC 11801 standard, however, may be useful in understanding
regulations encountered in other standards documents.For a cabling installation to
conform to the IEC11801 standard, the configuration must connect the following
subsystems to create a generic cabling structure:
z Campus backbone - uses a campus distributor.
z Building backbone - uses a building distributor for each building.
z Horizontal cabling - uses floor distributors.

Electromagnetic The main EMC standards organizations are:


Compatibility z IEC - International Electrotechnical Commission (Geneva)
Standards z CENELEC - European Committee for Electrotechnical Standardization
(Brussels)
There are two major international standards for electromagnetic emission and
immunity:
z IEC 61000-6-2: 1999 Electromagnetic compatibility (EMC) - Part 6-2: Generic
standards - Immunity for industrial environments
z IEC 61000-6-4: 1997 Electromagnetic compatibility (EMC) - Part 6: Generic
Standards - Section 4: Emission standard for industrial environments.
The following table lists standards and publications that describe the requirements
related to electromagnetic compatibility (see p. 506).

31006929.00 10/2005 501


Standards and Considerations

The following IEC publications table gives the equivalent European standards
documents in brackets below each appropriate publication reference.
IEC Publications Description
General
IEC 1000-1-1 (1992) Application and interpretation of fundamental
differences and terms.
Environment
IEC 1000-2-1 (1990) Electromagnetic environment for conducted low-
frequency (LF) interference and the transmission
of signals over public supply networks.
IEC 1000-2-2 (1990) Compatibility levels for conducted low-frequency
(LF) interference and the transmission of signals
over low-voltage public supply networks.
IEC 1000-2-3 (1992) Radiated phenomena and conducted
phenomena at frequencies other than mains
frequencies.
IEC 1000-2-4 (1994) Compatibility levels in industrial installations for
conducted low-frequency interference.
IEC 1000-2-5 (1995) Classification of electromagnetic environments.
Limits
552-2 IEC 1000-3-2 Limits for rated harmonic current < 16 A per
(1995) [EN 61000- phase emitted by appliances.
3-2 (1995)
552-3 IEC 1000-3-3 Limitation of voltage fluctuations and flicker in
(1994) [EN 61000- low-voltage systems for equipment having a
3-3 (1995)] rated current equal to or less than 16 A.
IEC 1000-3-5 Limitation of voltage fluctuations and flicker in
(1994) low-voltage systems for equipment having a
rated current greater than 16 A.
Installation Requirements
IEC 1000-5-1 General considerations
IEC 1000-5-2 Earthing and Wiring
IEC 1000-5-3 External Influences

IEC 1000-4 The IEC 1000-4 (previously known as IEC-801) standard establishes a common
Standard reference for evaluating the performance of industrial-process measurement and
control instrumentation when exposed to electric or electromagnetic interference.

502 31006929.00 10/2005


Standards and Considerations

The standard considers only those types of interference caused by sources external
to the equipment. The standard describes interference susceptibility tests that
demonstrate the capability of equipment to function correctly in its working
environment. You determine the type of tests to run based on the types of
interference to which your equipment is exposed when installed, taking into
consideration the electrical circuit (that is, the way the circuit and shields are tied to
earth ground), the quality of the shielding, and the environment.
The IEC 1000-4 standard is divided into six sections.
Test and Measurement Techniques
801-1 IEC 1000-4-1 (1992-12) Overview of immunity tests.
[EN 61000-4 (1994-08)]
801-2 IEC 1000-4-2 (1995-01) Testing of immunity to electrostatic discharges.
[EN 61000-4-2]
801-3 IEC 1000-4-3 (1995-02) Testing of immunity to radiated radio frequency
[ENV 50140 (1993)] electromagnetic fields.
801-4 IEC 1000-4-4 (1995-01) Testing of immunity to high-speed burst
[EN 61000-4-4] transients.
801-5 IEC 1000-4-5 (1995-02) Testing of immunity to impulse waves.
[EN 61000-4-5]
pr IEC 1000-4-6 [ENV Immunity to conducted interference induced by
50141 (1993)] radio frequency fields.
IEC 1000-4-7 (1991-07) Guidance on measurement of harmonics and
[EN 61000-4-7 (1993-03)] interharmonics and measuring apparatus
applicable to power supply systems and devices
connected to them.
IEC 1000-4-8 (1993-06) Testing of immunity to mains-frequency magnetic
[EN 61000-4-8 (1993-09)] fields.
IEC 1000-4-9 (1993-06) Testing of immunity to impulsive magnetic fields.
[EN 61000-4-9 (1993-09)]
IEC 1000-4-10 (1993-06) Testing of immunity to damped oscillating
[EN 61000-4-10 (1993-09)] magnetic fields.
IEC 1000-4-11 (1994-06) Testing of immunity to voltage dips, brief power
[EN 61000-4-11 (1994-09] failures and voltage variations.
pr IEC 1000-4-12 Testing of immunity to damped oscillating waves.

Automation
Equipment
Programmable controllers part 2: Equipment IEC 61131-2
standards
requirements and tests

31006929.00 10/2005 503


Standards and Considerations

TIA/EIA 568 The TIA/EIA-568-A standard is one of the first cabling standards, developed jointly
Standards by TIA and EIA. The TIA/EIA-568-A standard defined the wiring system for voice and
data networks: a structured, hierarchical star-topology network in which high-speed
(fiber optic) cables feed slower peripheral networks. The standard was incorporated
into TIA/EIA-568-B in 2000.
This table summarizes updates to the TIA/EIA-568 standard.
Standard Description
TIA/EIA-568-A-1995 Commercial Building Defines a standard for building cable
Telecommunications Wiring systems for commercial buildings that
Standards support data networks, voice, and
video. It also defines technical and
performance criteria for cabling.
TIA/EIA-568-A Updates A1 outlines propagation delay and
(1998-1999) delay skew parameters.
A2 specifies miscellaneous changes.
A3 defines requirements for bundled
and hybrid cables.
A4 defines NEXT and return loss
requirements for patch cables.
A5 defines performance requirements
for enhanced CAT5e).
TIA/EIA-568-B.1- Commercial Building Incorporates previous updates into a
2000 Telecommunications Wiring new release and specifies Category 5e
Standard cable as preferred due to its
performance. Several addenda specify
technical information for 100-ohm
twisted-pair cable, shielded twisted-
pair cable, and optical fiber cable.
TIA/EIA-569-A-1995 Commercial Building Specifies how to build pathways and
Standard for spaces for telecommunication media.
Telecommunications
Pathways and Spaces
TIA/EIA-606-1994 Building Infrastructure Defines design guidelines for
Administration Standard managing a telecommunications
infrastructure.
TIA/EIA-607-1995 Grounding and Bonding Defines grounding and equipotential
Requirements bonding requirements for
telecommunications cabling and
equipment.

504 31006929.00 10/2005


Standards and Considerations

The TIA/EIA standards define a structured cabling system that is designed and built
in multiple blocks. The blocks are integrated into a hierarchical network to create a
unified communication system. LANs represent blocks with lower-performance
requirements, while backbone network blocks, which require high-performance fiber
optic cable, perform the work of connecting the blocks to each other in a star-
topology. The standard also specifies the requirements for fiber optic cable (single
and multimode), STP, and UTP cable. In general, the TIA/EIA 568 wiring standard
provides:
z specifications for a generic telecommunications wiring system for commercial
buildings
z specifications for media, network topology, termination and connection
(grounding) points, and administration of wiring systems
z support for environments that use several different products and vendors
z information about planning and installing a telecommunications network for
commercial buildings

31006929.00 10/2005 505


Standards and Considerations

Electromagnetic Compatibility

Introduction EMI can be an interfering electromagnetic noise, unwanted signal, or change in the
propagation medium that can impair the performance of devices and equipment or
of an entire system. It is one of the main causes of malfunction for communication
networks in industrial environments. EMI can impact industrial applications in
different ways, ranging from acceptable influence to damaged system components.
During the installation process, you need to recognize EMI conditions and follow
procedures that support electromagnetic capability and a safe environment.
This following discussion provides basic information about the types and sources of
EMI and proposes solutions that can reduce EMI in environments where industrial
machines and communication networks must coexist. Also included are the
explanations of terminology and classifications.

Definitions EMC is the ability of a device, equipment, or system to function satisfactorily in its
electromagnetic environment without introducing intolerable disturbances to that
environment or to other equipment. It requires that the interference emission level of
equipment or devices in a system be low enough not to interfere with other
equipment or devices located in the same electromagnetic environment. Because
network wiring and equipment can be susceptible to and emit EMI, it also requires
that the immunity level of equipment and devices be such that they are not disturbing
and not being disturbed by other equipment in the environment.
EMI is any electromagnetic phenomenon capable of impairing the performance of a
device, equipment, or system. It certain cases, the interference can be significant
enough to damage the equipment beyond repair. In communication networks,
unwanted EMI is simply an unwanted electrical signal that is added to the useful
signal. This unwanted signal is sourced by conductions in conductors and by
radiation in the air.

Disturbance or The terms EMI and disturbance mean essentially the same thing. A disturbance can
Interference be caused by an electromagnetic phenomenon such as electrical voltage, electrical
current, and electrical or magnetic fields. It has a broad amplitude and frequency
range over varying amounts of time. It results in the reduced ability of susceptible
equipment to function.

Electromagnetic Electromagnetic influence occurs each time a disturbance is transferred from an


Influence interference source through one or more coupling mechanisms to susceptible
equipment. An interference source can be any device or equipment component that
emits an electromagnetic disturbance such as electrical wiring, cables and
communication devices, regulators and relays, and electric motors.
Susceptible equipment is any device or equipment component(s) that is capable of
being influenced by EMI. Susceptible equipment has a low immunity level to EMI.

506 31006929.00 10/2005


Standards and Considerations

Coupling Coupling is the spreading of EMI from its source to other susceptible equipment or
Mechanisms devices. There are five types of coupling mechanisms.
Coupling Mechanisms Description
Galvanic Coupling through a common circuit
Inductive Coupling through a magnetic field
Capacitive Coupling through an electric field.; also called electrostatic
coupling.
Radiation influence Coupling through an electromagnetic field
Wave Influence Coupling through an electromagnetic field.

Interference can be transferred in a conductive (guided energy) form such as along


a wire or through air (unguided/radiated energy). Interferences are normally found
together as line-guided and radiated interference. In general, the same physical
laws of energy transfer in electromagnetic fields apply to coupling interference.
The installation of an Ethernet for industrial application requires that you understand
electromagnetic interference, coupling mechanisms, contributing influences, and
proper preventive measures before you begin to install. Some of the ways you can
decrease EMI and increase EMC in your installation are described in this chapter.

Ways to Depending on the type of coupling interference, you can use various methods to
Decrease EMI decrease or neutralize EMI. The following table shows methods appropriate for each
type of coupling.
Methods Galvanic Inductive Capacitive Radiation Wave
Coupling Coupling Coupling Influence Influence
Grounding X - - - -
Electrical Isolation X - - - -
Balancing Circuits - X X X -
Transposition of Outgoing/ - X X X -
Return Lines
Placement of Wires - X X X -
Placement of Devices - X X X -
Shielding - X X X -
Filtering X X X X X
Cable Selection X - X X X
Wire Layout X X X X X

Note: The two most efficient methods for decreasing EMI are shielding and wire
layout. Both methods are described in this chapter.

31006929.00 10/2005 507


Standards and Considerations

Make sure you take the appropriate measures to


z reduce the transmission of electromagnetic disturbance from interference
sources
z limit the spread of any electromagnetic disturbance

Types of There are two main types of electromagnetic interference:


Electromagnetic z low-frequency (LF)
Interference z high-frequency (HF)
LF interference is encountered chiefly in conducted form, such as conduction in
cables. It often has a long duration over several dozen milliseconds and in some
cases may be continuous (harmonic). The conducted energy can be high and can
result in the malfunction or even destruction of connected devices. The frequency
range is <1 - 5 Hz.
HF interference is encountered chiefly in radiated form, such as electrostatic
discharges in the air. The radiated energy is generally low and results in the
malfunction of nearby equipment and devices. HF interference pulses with a pulse
rise time of less than 10 ns. It can occur continuously, for example, in rectifiers and
clocks. The frequency range is >30 MHz.
HF type interference may also encountered in conducted form as transient current
or voltage. A transient is a temporary oscillation in a circuit that occurs as the result
of a sudden change of voltage or load. For example, it could be caused by a lightning
strike or an electrical fault. Electrostatic discharges disturbances can also be
conducted along conductors and easily injected into other conductors by radiation.

508 31006929.00 10/2005


Standards and Considerations

LF and HF The following table provides an overview of the sources of LF interference


Interference
Type Possible Sources Effects of EMI
Harmonic inverters, choppers malfunction of connected devices
Interference bridge rectifiers, electrolysis, welding machines, etc. potential destruction of
arc furnaces connected devices
induction ovens
electronic starters
electronic speed controllers for DC motors
frequency converters for induction and synchronous motors
domestic appliances such as televisions, gas discharge
lamps, and fluorescent tubes
Low voltage mains voltage fluctuation, brief power failures, voltage dip, surge malfunction of connected
interference voltages devices, such as high-speed
frequency variations relay dropout during voltage dips
waveform harmonics, transients, carrier currents loss of power
phases, unbalanced potential destruction of electronic
power short circuits, overloads (effects on voltage) hardware

The following table provides an overview of the sources of HF interference


Type Sources Effects of EMI
transients lightning malfunction of nearby equipment
faults to earth
commutation failures in inductive circuits (contractor coils,
solenoid valves, etc.
Electrostatic between a person and an object malfunction of nearby equipment
discharge between electrostatically charged objects potential destruction of
For example, exchange of electrons between the body and equipment
fabric as a person walks across a carpet or of clothes worn
by an operator sitting on a chair.

The following table summarizes ways you can reduce EMI for LF versus HF
disturbances
Preventive Measures for LF Phenomena Preventive Measures for HF Phenomena
Protective systems Equipotential bonding of exposed conductive parts (interconnections)
Filtering Careful cable routing
Appropriate cable lengths Selection of quality cables
Proper connections for HF conditions
Cable shielding
Protective systems are most important. Installation practices are most important

31006929.00 10/2005 509


Standards and Considerations

Copper Connector Standards Activities

Current The IEC Subcommittee SC 48B is responsible for standardization of electronic


Activities connectors based on the requirements of IEC committees such as ISO/IEC JTC 1
SC 25 (standards for office and similar environments) and its Industrial Premises
Cabling Task Group. These groups work together with the Subcommittee SC65C
(Digital Communication) and are called the SC65C/JWG10 joint working group.
The SC65C/JWG10 working group's mission is to define the wiring and cabling of
an Ethernet in industrial environments. It is important to note that standards defining
the specifications for connectors already exist. The usage of these connectors in
industrial Ethernet applications still needs to be standardized.Several networking
organizations (Modbus-IDA, IAONA, PNO, ODVA) have made recommendations
related to the type of copper connectors to use within different industrial
environments. At the time of this writing, these are only recommendations and not
standards.

Light Duty For light-duty industrial environments, the market has accepted the use of RJ45
Industrial connectors, in accordance with the IEC 60603-7 standard. Some organizations
Connector have proposed the use of protective housings for the RJ45 (discussed by the IEC
Recommen- 61076-3-106).This topic is under heavy discussion due to the fact that there are
dations multiple sealed RJ45 non-compatible models. The housings cover a variety of
different mating dimensions (round or rectangular), locking mechanisms (screw,
bayonet, locking lever, push/pull) and other special features. The different variants
are not mateable.

Heavy Duty For heavy duty environments, the choice seems to be the circular connector M12,
Industrial already defined by the IEC61076-2-101 standard.The type of M12 connector to use
Connector is still under discussion due to the preference for 4 pins in Europe and the
Recommen- preference for 8 pins in the US. The 4-pin connectors are more prevalent in Europe
dations which corresponds to the European practice of employing a 2-pair cable in Ethernet
service, instead of the 4-pair cable specified by TIA, the US-based telecommuni-
cations standards body.

510 31006929.00 10/2005


Standards and Considerations

Conforming to Standards

Introduction At this time, there is no international standard for planning and installing an industrial
Ethernet network. There are recommendations from industrial Ethernet
organizations and ongoing activities that have resulted in the creation of a draft for
such a standard. Plans are to publish this standard as ISO/IEC 24702 by the end of
2006.

ISO/IEC 24702 Because the forthcoming ISO/IEC 24702 is based on the ISO/IEC 11801 standard,
and ISO/IEC these existing standards can be used as references until ISO/IEC 24702 is
11801 published.
The ISO/IEC 11801 standard includes the following information:
Topic Chapter Description
(Clause)
Structure of the 5 Describes the functional elements of a generic cabling
generic cabling system (campus distributor, building distributor, transition
system point, etc.) and how they are connected together.
Implementation 6 Specifies a cabling design that, when properly installed,
conforms to the requirements of the International
Standard. This section also defines maximum lengths.
Permanent link 7 Defines the permanent link and channel performance
and channel requirements of installed generic cabling systems. The
specifications section defines the:
z Performance specifications of cabling for individual
permanent links and channels
z Performance specifications for two different media
types (balanced cables and optical fiber)
z Permanent channels and links and their
classifications (5 classes, class D being an application
of up to 100 MHz)
z Performance specifications for the link/channel based
on the application (performance around impedance,
return loss, attenuation, etc.)
Cable 8 Provides the requirements for cable used in horizontal
requirements and backbone cabling subsystems.
Connecting 9 Provides guidelines and requirements for connecting
hardware hardware used in generic cabling systems.
requirements
Shielding practices 10 Provides basic information about shielding.
Administration 11 Explains the identification, recording and documentation
of a generic cabling system.

31006929.00 10/2005 511


Standards and Considerations

The final ISO/IEC 24702 standard will borrow the following chapters from standard
ISO/IEC 11801:
z Chapter 7 - Link and Channel transmission classes for balanced cabling and fiber
optic.
z Chapters 7, 8 and 9 - Component transmission performance for balanced cabling
and fiber optic.
It will also add the following information based on industry requirements:
z A modification to the cabling structure specifications in the ISO/IEC 11801
Chapter 5.
z Environmental classification. (There is some limited information included in the
ISO/IEC 11801 Chapter 10.)
z Suitable components
z Potential new concepts

ISO/IEC 11801 The ISO/IEC 11801 standard defines conformance for cabling installations as
Conformance for follows: For a cabling installation to conform to this International Standard the
Cabling following applies:
Installations a The configuration shall conform to the requirements outlined in clause 5.
b The interfaces to the cabling shall conform to the requirements of clause 9.
c The entire system shall be composed of links that meet the necessary level of
performance specified in clause 7. This shall be achieved by installing
components which meet the requirements of clauses 8 and 9, according to the
design parameters of clause 6, or by a system design and implementation
ensuring that the prescribed performance class of clause 7, and the reliability
requirements of clause 9, are met.
d System administration shall meet the requirements of clause 11.
e Local regulations concerning safety and EMC shall be met.

512 31006929.00 10/2005


Standards and Considerations

The ISO/IEC 11801 standard further states:


The link performance specified in clause 7 is in accordance with clause 6
(installation). The link performance is met when components specified in clauses
8 and 9 are installed in a workmanlike manner and in accordance with supplier's
and designer's instructions, over distances not exceeding those specified in
clause 6. It is not required to test the transmission characteristics of the link in that
case. Conformance testing to the specifications of clause 7 should be used in the
following cases:
z a. the design of links with lengths exceeding those specified in clause 6
z b. the design of links using components different from those described in
clauses 8 and 9
z c. the evaluation of installed cabling to determine its capacity to support a
certain group of applications
z d. performance verification, as required, of an installed system designed in
accordance with clauses 6, 8 and 9

31006929.00 10/2005 513


Standards and Considerations

Transparent Ready Industrial Ethernet Conformance

Application Application classes are defined by the ISO/IEC 11801 standard. Each application
Classes has a frequency range, and every application range has a recommended cable
category. This table shows each of the classes and their associated application and
cable category.
Class Application Class includes Permanent Link ANSI/TIA/EIA-568 Category
and Channel
A Speech band and low-frequency applications specified up to -
Copper cabling permanent links and channels 100 kHz
Supporting Class A applications are referred
to as Class A permanent links and Class A
channels, respectively
B Includes medium bit rate data applications specified up to -
Copper cabling permanent links and channels 1 MHz
supporting Class B applications are referred to
as Class B permanent links and Class B
channels, respectively
C Includes high bit rate data applications specified up to Category 3
Copper cabling permanent links and channels 16 MHz
Supporting Class C applications are referred
to as Class C permanent links and Class C
channels, respectively.
D Includes very high bit rate data applications specified up to Category 5 (No longer recognized by
Copper cabling permanent links and channels 100 MHz TIA/EIA)
Supporting Class D applications are referred Category 5e (Recommended as the
to as Class D permanent links and Class D minimum for all future installations
channels, respectively by: TIA/EIA, IEEE, Active Equipment
Manufacturers.
Optical Includes high and very high bit rate data specified to support -
Class applications applications
Optical fibre permanent links and channels specified at 10 MHz
Supporting Optical Class applications are and above.
referred to as Optical Class permanent links
and Optical Class channels, respectively

514 31006929.00 10/2005


Standards and Considerations

Maximum This table shows the maximum channel lengths by cable category and class as
Channel Lengths defined by the ISO/IEC 11801 standard.
Media Class A Class B Class C Class D Class E Class F Optical
CAT 3 2 km 200 m 100 m - - - -
CAT 4 3 km 260 m 150 m - - - -
CAT 5e 3 km 260 m 160 m - - - -
CAT 6 - - - - 100 m 100 m -
CAT 7 3 km 290 m 180 m 120 m - - -
150 ohm 3 km 400 m 250 m 150 m - - -
- - - - - - -
Cable - - - - - - -
62.5/125 and 50/ - - - - - - 2 km
125 mm
Optical Fiber - - - - - - -
Singlemode - - - - - - 3 km

The class D link performance limits are listed in Annex A of EN 50173:2002 and ISO/
IEC 11801:2002. The measurement limits are described in prEN 50346:2001.

31006929.00 10/2005 515


Standards and Considerations

516 31006929.00 10/2005


Earthing (Grounding) Procedures

F
At a Glance

Overview This appendix describes procedures for earthing (grounding).

What's in this This chapter contains the following topics:


Chapter?
Topic Page
Well-made Earthing (Ground) Connections 518
Making an Earthing Connection 519
Cable Shielding Connection Options 525
Copper Ethernet Testing Procedures 527
Performance Parameters 528
Definitions of Performance Parameters 530

31006929.00 10/2005 517


Earthing (Grounding) Procedures

Well-made Earthing (Ground) Connections

Introduction When you connect metal structures and equipment to an earthing system, the
quality of the earthing connections is critical in protecting your equipment and
achieving EMC. Earth connections use conductive straps, bars, bolts and cable
fasteners to interconnect the metal components of machines, equipment, cabinets,
cables shields, and other conductive objects to your earthing system.

Type and Length When choosing the type of connection, frame earth connections must be as short
of Connections and wide as possible in every case.

Note: Make sure that connections are properly made and that all exposed metal
components are properly grounded. A well-made connection has the LF and HF
conductive properties you require and promotes a long service life for your
equipment.

518 31006929.00 10/2005


Earthing (Grounding) Procedures

Making an Earthing Connection

Introduction You can make two types of earthing connection:


z between two metal surfaces
z between shielded cable and a metal surface

Making a Make sure that earth plane plates are not coated with paint or any other type of
Connection insulating covering. These materials prevent direct contact with other metal surfaces
Between Two in an earthing system:
Metal Surfaces

31006929.00 10/2005 519


Earthing (Grounding) Procedures

Follow these steps to make an EMC-compliant connection between two metal


surfaces.
Step Action Comments
1 Select appropriately Here is a braided strap connection:
conductive connection
materials for optimum
contact.
Use braided straps or bolts to
connect metal surfaces.
A metal plate or bar is less
preferable but may be used in
the absence of a braided
strap. Do not use green/
yellow wire conductors.

Here is a bolt, nut, and washer connection:

2 Prepare the surface for metal This includes the surfaces between any two continuous connections
connections at all contact that are placed in contact, such as two flat metal sheets or bars
points. Remove any paint or
insulating coatings from the
surface of metal contact
points.
3 Attach connection surfaces Make sure the connection between contact surfaces is tight by using a
using braided straps or nuts, nut and bolt system with a washer.
bolts and washers.

520 31006929.00 10/2005


Earthing (Grounding) Procedures

Step Action Comments


4 Make sure all metal Recheck your connections to make sure they create a local earthing
components are system that attaches to the earthing main conductor for your building
interconnected and attached (see p. 99).
to an earthing system.

5 Apply a coating of paint or Maintain the connection over time.


grease on nuts and bolts at
each contact point to protect
against corrosion.

Connection z Paint, locking compounds and Teflon tape act as insulating materials and prevent
Notes clean contact between metal surfaces at connection points. If a cabinet or metal
surface, including the bottom plate, has been painted, remove the paint before
making a connection. After the connection is made, you may paint the connection
materials to prevent corrosion.
z Make sure all exposed metal components and units that are fitted in a cabinet are
bolted directly onto the earth plane plate.

31006929.00 10/2005 521


Earthing (Grounding) Procedures

Making a Because Ethernet operates at frequencies higher than 10 MHz, you must ground
Connection cable shielding at both ends to obtain maximum EMC effectiveness. If your site does
Between Cable not have equipotential bonding, you can make a connection to one end only and still
Shielding and provide acceptable, but not as effective, operation. Follow these steps to create a
Metal Surfaces quality connection between a cable shielding and a metal surface.
Step Action Comments
1 Select the appropriate cable for a Schneider Electric strongly recommends that you use STP cable, at
Transparent Ready installation. least CAT5, for any Transparent Ready installation. Schneider
Electric also recommends that you use shielded connectors on
cables, devices, and switches.
2 Install an earth bus bar or plane Make sure there is no insulating covering or paint on the surface to
connected to a chassis to which which plan to attach the cable. Do not use soldered cable lugs or
you will attach the cable tinned leading-out wires to connect cable shielding. If possible, plan to
shielding. You can also attach connect the cable shield to an earth bus bar or at the point of entry to
cable shielding at entry points to a cabinet.
cabinets.

In all cases, make sure you have allowed for a strong metal-to-metal
contact that surrounds the cable 360 degrees.
3 Check the cable to make sure If the cable is damaged or the cable shielding is cut, replace the entire
you have an uninterrupted cable length of cable.
shield from end to end.

522 31006929.00 10/2005


Earthing (Grounding) Procedures

Step Action Comments


4 Remove the outer plastic jacket An excellent metal-to-metal contact must exist between the mesh
to expose the internal cable cable shielding and the metal bus bar or earth plane. Expose the cable
sheath. shield so that it has a 360-degree contact surface to make a good
ground connection.

5 Attach the cable shield. If Make sure the connection at the end of the cable shielding provides a
possible, connect the cable shield metal-to-metal bond that circles the sheath a full 360 degrees. You
to an earth bus bar or at the point can use metal cable clips to fasten mesh shielding and get complete
of entry of a cabinet. Wherever 360-degree contact.
possible, ground both ends of a
cable by attaching them properly
to an earth plane.

Check that no paint or insulating coating exists between contact


surfaces.

31006929.00 10/2005 523


Earthing (Grounding) Procedures

Connection z Avoid using poor connections from the cable sheath to a metal earth bus bar or
Notes plane.
z Remove any insulating plastic tape between the cable shielding layer and the
sheath.
z Avoid using long cable shielding lengths. Shielding loses its effectiveness if the
cable is too long. To optimize the effectiveness of shielding, provide a large
number of intermediate connections to the earthing frame.
This diagram shows a cable with multiple connections to the earthing frame.

524 31006929.00 10/2005


Earthing (Grounding) Procedures

Cable Shielding Connection Options

Two Ways to There are two ways you can ground a cable shield:
Ground a Cable z create earthing connections at both ends of the cable
Shield z create earthing connections at only one end of the cable
The use of shielded cable without earthing connections is not recommended.
Without a n earthing connection, the shielding is ineffective against magnetic
fields and both HF and LF disturbances. Any possible contact with the cable
shield creates a potential safety issue because of the potential difference
between the shielding and the ground.

CAUTION
Exposure to low voltage.
When grounding a cable shield at only one end, there is a potential difference
between the shielding and the ground connection of the unearthed end.
z Avoid contact.

Failure to follow this instruction can result in injury or equipment damage.

31006929.00 10/2005 525


Earthing (Grounding) Procedures

Advantages and The following table describes the advantages and risks associated with these two
Disadvantages earthing methods. Use this information to help you decide what is the best earthing
connection choice for your installation.
Ground Connection Advantages Restrictions
Method
Earthing connection Extremely effective against external LF and HF Ground-fault current can be induced in
on both ends of the disturbances high-frequency signals with high
cable Very good shielding effectiveness against interference-field strength for long cables
resonance frequency on the cable (>50 m).

No potential difference between cable and


ground
Enables common laying of cables that feed
different class signals.
Very good suppression of HF disturbances
Earthing connection Average shielding effectiveness Ineffective against external disturbances
on only one end of the caused by high-frequency electric fields
cable Enables protection of isolated lines against low- Shielding can cause resonance due to the
frequency electric fields antenna effect. This means the
Enables buzz (low-frequency disturbance) to disturbance is greater than when shielding
be avoided is present

Shielded Cable One of the risks of earthing cable shields at both ends is the creation of ground
Ground Loops loops. Ground loops occur when current circulates through the shield due to the
different potential between the extreme ends of the shield. If this happens, you need
to achieve the same potential at both ends. If you are working with an existing
installation, consider laying a binding conductor in parallel to the network cable. For
very long distances, use fiber optic cable.

526 31006929.00 10/2005


Earthing (Grounding) Procedures

Copper Ethernet Testing Procedures

Introduction The following discussion describes verification of installations, such as wiring and
proper lengths, and references specifications for the testing of performance defined
in Chapter 7 of ISO/IEC 11801.

Copper Make sure to test copper wiring for:


Installation z correct pin termination at each end
Testing z continuity to the remote end
z short circuits between any two or more conductors
z crossed pairs
z split pairs
z reversed pairs
z shorted pairs
z other miswiring

Copper The ISO/IEC 11801 standard requires that you test both channel and permanent
Performance links as follows:
Testing z The performance of the channel is specified at and between interfaces to the
channel
z The performance of a permanent link is specified at and between interfaces to the
link
The ISO/IEC 11801 also states:
The link performance is met when components specified in clauses 8 and 9 (of
the ISO/IEC 11801) are installed in a workmanlike manner and in accordance
with supplier's and designer's instructions, over distances not exceeding those
specified in clause 6 (of the ISO/IEC 11801).

31006929.00 10/2005 527


Earthing (Grounding) Procedures

Performance Parameters

Introduction Vendors of components and cables are required by the ISO/IEC 11801 standard to
publish performance parameters for their products. The standard states that
vendors of cables and components are required to present parameters for the
different components of a permanent link or channel (whose specifications are
defined in chapters 8 and 9 of the ISO/IEC 11801). The performance parameters
specified by the ISO/IEC 11801 apply to permanent links and channels with shielded
or unshielded cable elements (i.e., with or without an overall shield, unless explicitly
stated otherwise). STP and UTP are also referred to as balanced cabling.
Performance parameters are defined for 5 application classes. For example, class
D applications are related to class D permanent links and channels, which are
specified up to 100 MHz.

Specification The following table lists all parameters proposed and/or required for testing and their
Parameters and associated standards. The most important standards for industrial Ethernet
Related networks are in the last two columns.
Standards
Standard ISO/IEC 11801-2000 TIA/EIA 568B ISO/IEC 11801-2000+ Addendum to TIA/EIA 568-B
Status Approved Approved Draft Draft
Class or CI. C: 16 MHz CAT 3:16 MHz CI. C 16 MHz CAT 3: 16 MHz
Category CI. D: 100 MHz CAT 5e: 100 MHz CI. D: 100 MHz CAT 5e: 100 MHz
frequency range CI. E: 250 MHz CAT 6: 250 MHz
CI. F: 600 MHz
Wire Map x x x x
Length x x
Propagation x x x x
delay
Delay skew x x x x
Insertion loss x x x x
attenuation
PP NEXT loss x x x x
PS NEXT loss x x x x
PP ACR x
PS ACR x
PP ELFEXT x x x x
PS ELFEXT x x x x
Return Loss x x x x
DC resistance x x

528 31006929.00 10/2005


Earthing (Grounding) Procedures

List of The following parameters are required in the testing and performance measuring of
Parameters balanced cabling permanent links and channels:
z nominal impedance (see p. 530)
z return loss (see p. 530)
z attenuation (see p. 530)
z pair-to-pair NEXT loss (see p. 531)
z power sum NEXT (see p. 532)
z pair-to-pair ACR (see p. 532)
z power sum ACR (see p. 532)
z pair-to-pair ELFEXT (see p. 532)
z power sum ELFEXT (see p. 532)
z DC loop resistance (see p. 533)
z propagation delay (see p. 533)
z delay scew (see p. 533)
z longitudinal-to-differential conversion loss (see p. 533)
z transfer impedance of shield

31006929.00 10/2005 529


Earthing (Grounding) Procedures

Definitions of Performance Parameters

Introduction The following discussion describes each of the specification parameters defined in
the ISO/IEC 11801.

Nominal Impedance is a measure of the degree a component resists the flow of energy from
Impedance a given source. The impedance of a cable is important in determining the load
placed on the source and the efficiency of the signal transmission. A simple way to
define nominal impedance is to measurer a component that does not reflect energy
back to the transmitting source. When a transmitting system sees the nominal
impedance as its load, all the energy that it transmits is absorbed by the receiving
end. If it does not see the nominal impedance, part of the energy bounces back. In
an ideal system, all the transmitted energy is absorbed by the receiving end.
Impedance is measured in Ohms (Ω).

Return Loss Return loss is a measure of the reflected energy caused by impedance that
mismatches in the cabling system (impedance consistency). If the system that
transmits energy does not detect an impedance equal to the nominal impedance,
then there will be reflected energy (that is, the receiving end bounces back some
energy). In such cases, there is an echo of the transmitted signal. Return loss is
measured in decibels or as a percentage of signal strength.

Attenuation Attenuation is the loss of signal strength as it travels along the cable. It is measured
(Insertion Loss) in decibels (dB). A low attenuation number is good—the lower the attenuation value,
the stronger the signal. Attenuation depends on the cable length and the frequency.
Attenuation increases as the cable length increases. It also increases as the
frequency increases, and it is further affected by wire gauge. Thicker cables have
less attenuation than thinner cables. Problems with attenuation are usually related
to the use of thin cables, bad terminations, or long cables. Attenuation also
increases with temperature.

530 31006929.00 10/2005


Earthing (Grounding) Procedures

Pair-to-pair Near- Near-end crosstalk (NEXT) is the coupling of a signal from one pair (the disturbing
end Crosstalk pair) to another pair (the disturbed) measured at the end where the signal is injected
Loss (the near end). NEXT represents how much of the transmitted signal in the
disturbing pair gets electromagnetically coupled in the disturbed pair. It is measured
in the disturbed pair at the transmitting end. NEXT is measured in dB. A high NEXT
value is good because it indicates high attenuation from one pair to another. NEXT
varies with the frequency. It needs to be measured within a range of frequencies.
The figure below is an example of NEXT and attenuation values

Transmission signal affected by attenuation

Transmit Disturbing pair

Receive Disturbed pair

smaller number =
more crosstalk NEXT value due to transmitting pair larger number =
less crosstalk

Signal in response pair affected by attenuation

larger number =
more attenuation Attenuation value smaller number =
less attenuation

The illustration shows two Ethernet pairs, transmit and receive. When the
transmitting pair is energized it generates crosstalk to the receiving pair. At the near
end, the signal in the receiving pair is the lowest and therefore more susceptible to
the NEXT influence. As the value of NEXT increases, the value of attenuation also
increases.
Twisted pair cables were developed to avoid crosstalk and allow opposing fields to
cancel each other. The more twists there are, the better the cancellation and the
higher the frequency supported by the cable. Often, the NEXT of a permanent link
or channel decreases (indicating increased crosstalk) due to poor installation
termination of cables. To connect the cable to a device, you must untwist the cable
to access the wires. Untwisted wires increase crosstalk. You can minimize crosstalk
by retaining the cable pair twists as much as possible when you terminate the cable
and connect it to hardware.

31006929.00 10/2005 531


Earthing (Grounding) Procedures

Power Sum Power Sum NEXT is the sum of all pair combinations for crosstalk measured at the
NEXT (PSNEXT) Near End to the transmitter, and simulates all four pairs being operated
simultaneously. It is the addition of the NEXT effects of three disturbing pairs in the
fourth pair considered in the Near End. This parameter is intended for systems in
which more than two pairs are used. PSNEXT varies with the frequency, and
therefore, you need to measure it within a range of frequencies.

Pair-to-pair The attenuation of crosstalk ratio (ACR) is the difference between the NEXT and the
Attenuation of attenuation in the pair under test. The formula is)
Crosstalk Ratio ACR = NEXT - Attenuation
(ACR)
At the near end, the NEXT is the strongest (smallest NEXT value) and the
attenuation is the strongest (which means the largest attenuation and the lowest
signal level). ACR is nearly analogous to the definition of signal-to-noise ratio. (ACR
excludes the effect of external noise that may impact the signal transmission.

Power Sum ACR Power sum ACR (PSAR) is a mathematical calculation that simulates all four pairs
(PSACR) being operated simultaneously. The formula is:
PSACR = PSNEXT - Attenuation
Because PSACR is a measured signal to noise ratio, a larger number (more signal
and less noise) is more desirable than a smaller number (more noise and less
signal).

Far-end Far-end crosstalk (FEXT) is similar to the NEXT. Even though the disturbing pair
Crosstalk sends the signal from the local end, it is measured in the disturbed pair at the far
end. The signal in the disturbing pair is weaker at the far end due to attenuation.
Because the FEXT value is related to the attenuation of the cable, it is typically
measured to obtain the ELFEXT, but not reported.

Pair-to-pair Equal-level far-end crosstalk (ELFEXT) is a mathematical calculation that is


Equal-level Far- obtained by subtracting the attenuation of the disturbing pair from FEXT. This pair
end Crosstalk induces in an adjacent pair. The formula is:
ELFEXT = FEXT - Attenuation

Power Sum Power sum ELFEXT (PSELFEXT) is the sum of the values of the individual ELFEXT
ELFEXT effects on each pair by the other 3 pairs. It is similar to the calculation used for
(PSELFEXT) PSNEXT. The calculation used to measure ELFEXT removes the impact of
attenuation on FEXT.

532 31006929.00 10/2005


Earthing (Grounding) Procedures

DC Loop DC loop resistance is the total resistance through two conductors looped at one end
Resistance of the link. It is usually a function of the conductor diameter and varies only with
distance. This measurement is sometimes done so that gross misconnections do
not add significant resistance to the link.

Propagation Propagation delay is a measure of the time required for a signal to propagate from
Delay one end of the circuit to the other. Delay is measured in nanoseconds (ns). It is the
principle reason for a length limitation on LAN cabling. In many networking
applications, such as those employing CSMA/CD, there is a maximum delay that
can be supported without losing control of communications.

Delay Skew Propagation delay skew is the difference between the propagation delay on the
fastest and slowest pairs in a UTP cable or cabling system.

Longitudinal-to- Twisted-pair cable signal transmission assumes that the signals on each wire
differential relative to earth ground are balanced. This means that anywhere along the length of
Conversion Loss the cable, the signal on one wire of a twisted pair, measured relative to earth ground,
(Balance) is exactly equal in amplitude, but exactly opposite in phase to the signal on the other
wire of the same twisted pair.
If this ideal were true, there would be no RF signal emitted from the pair (no EMI/
RFI), and coupling inside the link would be reduced. The normal NEXT is the result
of the coupling of a differential signal applied to one pair showing up as a differential
mode signal at the receive input. Other coupling mechanisms, that occur when the
signal is not applied in a purely differential manner, include the differential mode to
common mode coupling, common mode to differential mode coupling, and common
mode to common mode coupling. These coupling mechanisms can be significant
sources of excess NEXT. Therefore, this parameter defines how well the signal
applied by the tester is balanced as it enters the link.

31006929.00 10/2005 533


Earthing (Grounding) Procedures

Parameter The following table lists the specification parameters and their Class D values for
Values for CAT5 network links and channels.
Cable from ISO/
Parameter Permanent Link Permanent Channel
IEC 11801
Class D Channel D
Frequency (it is presented 100 MHz 100 MHz
at 100MHz, but needs to
measure over the 1-
100MHz range)
Maximum Attenuation 20.6 dB 24 dB
Minimum NEXT 29.3 dB 27.1 dB
Minimum Power-sum 26.3 dB 24.1 dB
NEXT
Minimum ACR 8.7 dB 3.1 dB
Minimum Power-sum ACR 5.7 dB 0.1 dB
Minimum ELFEXT 19.6 dB 17.0 dB
Minimum Power-sum 17.0 dB 14.4 dB
ELFEXT
Minimum Return loss 17 dB 17 dB
Maximum Propagation 489.6 ns 547.6 ns
delay
Maximum Delay skew 43 ns 50 ns
Minimum Longitudinal to The measurement of these values The measurement of these
differential conversion loss on installed systems is not yet values on installed systems
well established. It is sufficient to is not yet well established.
verify the values by design. It is sufficient to verify the
values by design.

Parameter Permanent Link Class D


Maximum Loop resistance 40 Ω

534 31006929.00 10/2005


Glossary

100BaseT4 100 Mb/s Ethernet running on four pairs of category 3, 4, or 5 unshielded twisted-
pair cable.

10Base-F 10 Mb/s Ethernet running on optical fiber. 10BASE-F is a point-to-point network


medium—e.g., hub/switch device-to-station.

10Base-T 10 Mb/s Ethernet running on unshielded twisted-pair cable. 10BASE-T is a point-to-


point network medium—e.g., hub/switch device-to-station.

10Base2 10 Mb/s Ethernet running on thin coax network cable.

10Base5 10 Mb/s Ethernet running on thick wire network cable.

802 IEEE specifications for local area networks (LANs) and metropolitan area networks
(MANs).

802.1 IEEE specifications for general management and internetwork operations such as
bridging.

802.2 IEEE specifications that sets standards at the logical link control sub-layer of the
data link layer.

802.3 CSMA/CD (Ethernet) standards that apply at the physical layer and the MAC sub-
layer.

802.4 IEEE specifications for token passing bus standards.

31006929.00 10/2005 535


Glossary

802.5 IEEE specifications for token ring standards.

802.6 IEEE specifications for metropolitan area network (MAN) standards. IEEE 802
standards become ANSI standards and usually are accepted as international
standards.

ack number A sender transmits a message in this acknowlegment code to say that a message
was received without errors.

ARP (address resolution protocol) The ARP cache consists of a table with matched
hardware and IP addresses.

ATM asynchronous transfer mode A technology for high-speed transfer of voice, video
and data over a network.

AUI (attachment unit interface) A 15-pin shielded, twisted pair Ethernet cable used to
connect network devices and a medium attachment unit (such as a transceiver).

auto-negotiation/ The ability of a device (at the MAC sub-layer) to identify the speed (10 or 100 Mb/s)
auto-sensing and the duplex or half mode of a connection and to adjust it, according to clause 28
of the IEEE 802.3u standard.

backbone The main cable of the network.

bandwidth The range of frequencies that a line transmission can carry. The capacity of a digital
channel is measured in bits per second (bit/s).

baseband LAN A local area network that uses a single carrier frequency over a single channel.
Ethernet uses baseband transmission.

bit/s Bits per second, unit of transmission speed.

BNC (Bayonet Neill Concelman) Standard connector used to link 10Base2 thin coaxial
cable to a transceiver.

536 31006929.00 10/2005


Glossary

BootP (bootstrap protocol) A TCP/IP network protocol that offers network nodes request
configuration information from a BOOTP server node.

BRI (basic rate interface) Of the two levels of service within ISDN, the one intended for
residential and small business use. Consists of two 64 Kips B-channels and one
16 kbps D-channel for a total of up to 128 kbps of service.

bridge A networking device that connects two LANs and forwards or filters data packets
between them, based on their destination addresses. Bridges operate at the data
link level (or MAC layer) of the OSI reference model, and they are transparent to
protocols and to higher level devices like routers.
Bridges connect networks that use dissimilar protocols and that operate at the data
link level or layer 2 of the OSI model. They are often described as media-access
control level (MAC layer) bridges. They do not carry out any interpretation of the
information they carry. When two LANs are successfully bridged together, they
become one effective LAN. Various load-balancing techniques have been
developed to combat the problems of bandwidth limitation and the failure of any
element on the network. Bridges are increasingly used to control network traffic so
that the rest of the network is not involved. This boosts network performance and is
also useful for security purposes.

bridge/router A device that can provide the functions of a bridge, a router or both concurrently. A
bridge/router can route one or more protocols, such as TCP/IP and/or XNS, and
bridge all other traffic.

broadcast A message that is sent out to all devices on the network.

broadcast A collection of devices that receive a broadcast sent on an Ethernet network. The
domain broadcast domain ends at a router positioned in the network. If any device in a
broadcast domain broadcasts information, that information is received by all devices
in the same domain; it is not be received by devices connected through a router

Brouter A device that routes specific protocols, such as TCP/IP and IPX, and bridges other
protocols, thereby combining the functions of both routers and bridges.

bus A LAN topology in which all the nodes are connected to a single cable. All nodes are
considered equal and receive all transmissions on the medium.

CBN (common bonding network) The interconnected metallic components that comprise
an earthing system in a building. Also known as an integrated ground plane.

31006929.00 10/2005 537


Glossary

CENELEC European Committee for Electrotechnical Standardization in Brussels

channel The end-to-end data path between two nodes. All cabling from one active device to
another.

checksum A redundancy check that typically adds up bytes to detect errors in a message.

CIDR (classless interdomain routing) Also known as classless addressing or supernetting.


A flexible method to allocate IP addresses less wastefully.

circuit switching Maintaining a switch only while the sender and recipient are communicating.

circuit-switched A network that establishes a physical circuit temporarily until it receives a disconnect
network signal.

classless See CIDR.


addressing

coaxial cable An electrical cable with a solid wire conductor at its center surrounded by insulating
materials and an outer metal screen conductor with an axis of curvature coinciding
with the inner conductor.

collision The result of two network nodes transmitting on the same line at the same time. The
transmitted data are not usable, so the stations must send again. A delay
mechanism employed by both stations reduces the chances of another collision.

collision A signal indicating that other stations are contending with the local station's
detection transmission. The signal is sent by the physical layer to the data link layer on an
Ethernet/IEEE 802.3 node. With Ethernet, each device can detect collisions and try
to send the signal again. CSMA/CD is based on this principle.

communication A dedicated, standalone system that manages communications activities for other
server computers.

concentrator A device that serves as a wiring hub in star-topology network.

ConneXium Schneider family of Ethernet devices and solutions.

CRC (cyclical redundancy check) A way of checking for errors in a message by doing
mathematical calculations on the number of bits in the message, the results of which
are sent along with the data to the recipient. The recipient repeats the calculation on
the received data. If there are any discrepancies in the two calculations, the recipient
requests a retransmission from the originator.

538 31006929.00 10/2005


Glossary

crosstalk Noise passed between communications cables or device elements. Near-end


crosstalk is measured close to where the noise is introduced. Far-end crosstalk is
introduced at one end and measured at the other.

CSMA/CD (carrier sense multiple access with collision detection) An Ethernet and IEEE 802.3
media access method. All network devices contend equally for access to transmit.
If a device detects another device's signal while it is transmitting, it aborts
transmission and retries after a random period of time.

CSU/DSU The channel service unit/data service unit prevents electrical interference while it
transmits/receives signals to/from the WAN.T

cut-through Technique for examining incoming packets whereby an Ethernet switch looks only
at the first few bytes of a packet before forwarding or filtering it. This process is faster
than looking at the whole packet, but it also allows some bad packets to be
forwarded.

data link A logical connection between two nodes on the same circuit.

data link layer Layer 2 of the seven-layer OSI reference model for communication between
computers on networks. This layer defines protocols for data packets and how they
are transmitted to and from each network device. It is a medium-independent, link-
level communications facility on top of the physical layer, and is divided into two sub-
layers—medium-access control (MAC) and logical-link control (LLC).

datagram A means of sending data in which parts of the message are sent in a random order
and the recipient machine reassembles the parts in the correct order.

DCF A system of precision time signals sent from a transmitter near Frankfurt, Germany;
used for time synchronization.

DCOM distributed component object model An extension of COM (Component Object


Model) mode; DCOM mode is used for two remote machines to communicate with
one another. It replaces inter-process communication protocols with network
protocols. This is a Microsoft Windows standard.

DHCP (dynamic host configuration protocol) Communications protocol that assigns IP


addresses to devices on the network, based on BootP.

31006929.00 10/2005 539


Glossary

distributed A system in which each station or node in the network performs its own processing
processing and manages some of its data while the network facilitates communications
between the stations.

DNS server/ (domain name server/service) A service that translates a domain name into an IP
service address, the unique identifier of a device on the network.

DO (device outlet)

dongle A short network cable that connects a PCMCIA adapter to a network cable.

drop cable A cable that allows connection and access to the trunk cable in a network.a.k.a.
attachment unit interface (AUI) cable or transceiver cable.

DSL (digital subscriber line) A high-speed Internet connection using normal telephone
wires.

DVMRP (distance vector multicast routing protocol) A routing protocol used to support
multicast that uses distance, as measured in routing hops, to determine a packet’s
optimal path.

EGP (exterior gateway protocol) Exchanges routing information, specifically routing


tables, between two hosts on a network.

EMI (electromagnetic interference) Occurs when a device’s operation is disrupted or


degraded by the field of another nearby device.

encapsulation Wrapping a data set in a protocol header, for example, Ethernet data wrapped in a
specific Ethernet header before network transit.
Also, a method of bridging dissimilar networks where the entire frame from one
network is simply enclosed in the header used by the link-layer protocol of the other
network.

EOS (Ethernet over SONET/SDH) Transfers Ethernet signals in SONET/SDH.

ERP (enterprise resource planning) A software system for businesses that manages
planning, manufacturing and sales; also can include finances and human resources
modules.

540 31006929.00 10/2005


Glossary

Ethernet A 10 or 100 Mb/s, CSMA/CD baseband LAN that may run over thin coax, thick coax,
twisted pair or fiber optic cable. The IEEE standard 802.3 defines the rules for
configuring an Ethernet network.

fault tolerance A network’s ability to deter a failure on one part of the network from disrupting other
network services. It increases network integrity and uptime.
Examples include redundant power supplies on transceivers, hubs and switches;
simple or doubled-redundant optical or copper ring-topologies.

FDDI (fiber-distributed data interface) ANSI standard for using fiber optics to transmit data
at up to 100 Mb/s over a network.
Originally specified for fiber lines, FDDI standards can also be used on short lengths
of twisted-pair cable (a.k.a. CDDI).

FDR (faulty device replacement)

fiber optic cable A transmission medium composed of two glass optical (or plastic) fibers that
transmits digital signals in the form of modulated light pulses from a laser or LED.
Features a thin filament of glass, typically 125 to 140 μm in overall diameter
Because of its high bandwidth and high immunity to interference, fiber optic cable is
used in long-haul or noisy applications.

file server A computer that stores data for network users and provides network access to that
data.

filtering With respect to Ethernet, a process whereby a switch or bridge reads the contents
of a packet and, if it finds that the packet does not need to be forwarded, drops it.
The filtering rate is the rate at which a device can receive packets and drop them
without any loss of incoming packets or processing delay.

firewall A router or workstation with multiple network interfaces that controls and limits
specific protocols, types of traffic within each protocol, types of services and the
direction of information flow.

firmware The operating system (OS) of a device

FOIRL (fiber optic inter-repeater link) Signaling methodology based on the IEEE 802.3 fiber
optic specification.

31006929.00 10/2005 541


Glossary

forwarding Process whereby an Ethernet switch or bridge reads the contents of a packet and
passes the packet on to the appropriate attached segment. The forwarding rate is
the time that it takes the device to execute all of the steps.

fragment With respect to Ethernet, a piece of a larger packet that has been broken down into
smaller units.

fragmentation Breaking a packet into smaller units when transmitting over a network medium that
cannot support the original size of the packet.

frame A group of bits sent over a link that contains its own control information, such as
address and error detection. The size and composition of the frame varies by
protocol. The terms frame and packet tend to used synonymously, although in strict
OSI terms a frame is made at layer 2 and a packet at layer 3 or above.

frame relay A protocol using packet-switching to connect devices on a WAN.

framing Dividing data for transmission into groups of bits and adding a header and a check
sequence to each group.

FTP (file transfer protocol) A TCP/IP protocol for file transfer.

FTP (foil twisted pair) Cabling with two conductors wound around each other to lessen
crosstalk and a foil casing for added protection.

full duplex The ability of a device or line to transmit data independently and simultaneously in
both directions.

gateway A combination of hardware and software that interconnects otherwise incompatible


networks or networking devices. Gateways include packet assembler/disassembler
(pads) and protocol converters. Gateways operate at layers 5, 6 and 7—the session,
presentation and application layers, respectively—of the OSI model.

GMRP (GARP multicast registration protocol) A system allowing multi-cast of data; end
stations receive data sent to the multicast group for which they are registered.

Gopher a network protocol for document search and retrieval which goes for information and
uses a web of menu items like the holes of gophers to do so

542 31006929.00 10/2005


Glossary

GPS (global positioning system) A system of satellites and receiving devices used to
calculate position on Earth.

half duplex Data transmission that can occur in two directions over a single line, but in only one
direction at a time.

hardware See network address.


address

head-end A central point or hub in broadband networks that receives signals on one set
frequency band and retransmits them on another. Every transmission from one
workstation to another in a broadband network must go through the head-end. It
enables a network to send and receive on the same cable.

header The control information added to the beginning of a transmitted message. It contains
essential information such as the packet or block address, source, destination,
message number, length and routing instructions.

HMI (human-machine interface) The screen of a device, the design of which makes its
use intuitive to the user.

host Generally a node on a network that can be used interactively, i.e., logged into, like
a computer.

host table A list of TCP/IP hosts on the network and their IP addresses.

HSBY (hot standby system) This system is based on two identically configured
programmable logic controllers linked to each other and to the same remote I/O
network; If one controller fails, the other assumes control of the I/O system.

HTML (hypertext markup language) The code used to write web pages.

HTTP (hyper text transfer protocol) Protocol used to transmit files on the World Wide Web.

hub The center of a star topology network or cabling system. A multi-node network
topology that has a central multiplexer with many nodes feeding into and through it.
The other nodes do not usually interconnect directly. LAN hubs are becoming
increasingly popular with the growth of twisted pair and fiber optics and with the
need for LAN management.

31006929.00 10/2005 543


Glossary

hysteresis Until a plus or minus threshold around the value of a variable is exceeded, a signal
to notify other systems of a change of state is suppressed.

I/O (input/output) The transfer of date to and from a computer.

ICMP (Internet control message protocol) This extension of the IP protocol is used to test
a connection on the Internet with the ping command. It supports data packets with
error, control and information messages.

IEC International Electrotechnical Commission in Geneva

IEEE 802.3 An Institute of Electrical and Electronic Engineers standard that defines the CSMA/
CD media-access method and the physical and data link layer specifications of a
local area network. Among others, it includes 10BASE2, 10Base5, 10Base-FL and
10Base-T Ethernet implementations.

IGMP Internet group management protocol This is the Internet standard for multicasting
that allows a host to subscribe to a particular multicast group.

IGMP snooping Allows a switch to snoop, or listen in on, messages between a router and hosts.

inter-networking General term used to describe the industry composed of products and technologies
used to link networks together.

Interbus An open communication standard that offers a high-speed network for the
connection of I/O modules, sensors, actuators, and control devices to
programmable logic controllers or large computer systems

Internet A series of interconnected local, regional, national and international networks, linked
using TCP/IP. Internet links many government, university and research sites. It
provides E-mail, remote login and file transfer services.

IP address The 32-bit address associated with a workstation in connection with TCP/IP Internet.

IP rating (internal protection rating) Describes the degree of protection for the internal circuitry
of the sensors.

ISDN (integrated services digital network) A set of standards for digital transmission over
copper telephone wires

544 31006929.00 10/2005


Glossary

ISO layered The International Standards Organization sets standards for computers and
model communications. Its open systems interconnection (OSI) reference model specifies
how dissimilar computing devices such as NICs, bridges and routers exchange data
over a network. The model consists of 7 layers. From lowest to highest, they are:
physical, data link, network, transport, session, presentation and application. Each
layer performs services for the layer above it.

ISP (Internet service provider)

jabber Network error caused by an interface card placing corrupted data on the network.
Also, an error condition caused by an Ethernet node transmitting longer packets
than allowed.

JVM (Java virtual machine) Executes compiled Java code; sits on top of the operating
system.

LAN (local area network) A data communications system consisting of a group of


interconnected computers, sharing applications, data and peripherals. The
geographical area is usually a building or group of buildings.

LAN Dividing local area network bandwidth into multiple independent LANs to improve
segmentation performance.

latency With respect to Ethernet, the delay incurred by a switching or bridging device
between receiving the frame and forwarding the frame.

layer With respect to networks, the software protocol levels that comprise the network’s
architecture, where each layer performs functions for the layer(s) above it.

line speed The maximum rate at which data can be transmitted reliably over a line using given
hardware, expressed in bit/s.

link Physical connection between two nodes in a network. It can consist of a data
communication circuit or a direct channel (cable) connection.

31006929.00 10/2005 545


Glossary

LLC (logical link control or link layer control) A data link protocol based HDLC, developed
for LANs by the IEEE 802 Committee and common to all LAN standards for data link
transmission (the upper part of ISO layer 2).

LNI (local network interconnect) A port multiplier or concentrator that supports multiple
active devices or communications controllers, either stand-alone or attached to
standard Ethernet cable.

logical link A temporary connection between source and destination nodes, or between two
processes on the same node.

loss Also referred to as signal loss. The attenuation or degradation of a signal during
transmission.

LS (low smoke) A cable’s ability to avoid giving off toxic smoke in case of fire.

MAC (media access control) Generic term for the way in which workstations gain access
to transmission media. Most widely used in reference to LANs.

MAC address The media access control address of a device, which is burned into a DNI card and
is added near the beginning of the packet.

MAN (metropolitan area network) A network that spans a geographical area greater than
a local area network but less than a wide area network. IEEE 802.6 specifies the
protocols and cabling for a MAN. However, they could be superseded by ATM.

masquerading When a user appears to the system as another user. Can be used for malicious
purposes. IP masquerading allows only the connection at the firewall or router to be
seen on the Internet in order to hide a protected IP address space.

MAU (medium attachment unit) A device used to convert signals from one Ethernet
medium to another. A transceiver is a MAU.

MES (manufacturing execution system) A computerized system that aids in managing


data and communications for production flow.

546 31006929.00 10/2005


Glossary

MIB (management information base) A database of network parameters used by Simple


Network Management Protocol (SNMP) and Common Management Information
Protocol (CMIP) to monitor and change network device settings. It provides logical
naming for all information resources on the network that pertain to network
management.

MICE (mechanical, ingress, climatic, environmental) An international standardization effort


by a collaborative group of experts from IEC TC65, TIA TR-42.9, and CENELEC
TC215 WG1 to establish environmental standards for industrial Ethernet.

MII (media-independent interface) IEEE 802.3u standard for fast Ethernet. MII is the fast
Ethernet equivalent of AUI in 10 Mb/s Ethernet—it allows different types of fast
Ethernet media to connect to a fast Ethernet device via a common interface.

MMF (multi -mode fiber) A cable that passes light instead of electronic pulses. It supports
point-to-point connections only, over a maximum length is 2 km. It has been
classified as the best type of cable to use between buildings.

MPLS multiprotocol label switching Integrates information on Layer 2 into Layer 3, thereby
allowing routing of traffic around system problems.

MSTR A function block used for programming.

MT-RJ A new standard connector for optical cables.

MTU (maximum transmission unit) The largest size packet a network can transmit,
measured in bytes. The size is set by the network administrator and can be different
for each network. Larger packets are divided before they are sent, but this slows
transmission speed.

multi-port A repeater, either stand-alone or connected to standard Ethernet cable, that


repeater interconnects up to 8 thin-wire Ethernet segments.

multicast A message sent out to multiple devices on the network by a host.


A special form of broadcast where copies of the packet are delivered to only a
subset of all possible destinations.

name server Software that runs on network hosts charged with translating text-based names into
numeric IP addresses.

31006929.00 10/2005 547


Glossary

Nano Small range PLC platform from Schneider

network An interconnected system of computers that can communicate with each other and
share files, data and resources.

network address Every node on a network has at least one address associated with it, including at
least a fixed hardware address assigned by the device's manufacturer. Most nodes
also have protocol-specific addresses assigned by a network manager.

network Administrative services for managing a network, including configuring and tuning,
management maintaining network operation, monitoring network performance, and diagnosing
network problems.

NFS (network file system) A protocol for file sharing among UNIX hosts.

NIC (network interface card) An adapter card inserted into a computer that contains the
necessary software and electronics to enable the station to communicate over the
network.

NMS (network management system) A manager, within SNTP, that can query and get
responses from agents and set variables in them.

node Any intelligent device connected to the network, including terminal servers, host
computers and devices such as printers and terminals that connect directly to the
network. A node can be thought of as any device that has a hardware address.

NTP (network time protocol) A protocol in TCP used to synchronize time on devices
across a network; uses signals from atomic and radio clocks.

OEM (original equipment manufacturer) Buys computers in bulk, customizes them for a
certain application and resells them under its own name.

OLE (object linking and embedding) Microsoft software system that lets WIndows
applications move and share information.

OPC Specification for process control and manufacturing automation; defines standards
for objects, methods and interfaces.

548 31006929.00 10/2005


Glossary

OSI (open systems interconnect/interconnection) A structure for internetworking


heterogeneous computers for distributed application processing according to
international standards.

OSI reference A 7-layer network architecture model of data communication protocols developed by
model ISO and CCITT. Each layer specifies particular network functions such as
addressing, flow control, error control, encapsulation and reliable message transfer.

OSPF (open shortest path first) A link-state routing protocol in which every switching node
(router) passes a full map of network connections, used to calculate the best next
hop, from one router to the next.

packet A series of bits containing data and control information, formatted for transmission
from one node to another. It includes a header with a start frame, the source and
destination addresses, control data, the message itself, and a trailer with error
control data (called the frame check sequence).

packet-switched A network in which data is transmitted in packet units. The packets can be routed
network individually over the best available network connection and reassembled as a
complete message at the destination.

PCMCIA (Personal Computer Memory Card International Associates) Developers of a


standard for a device card to add memory, use for a modem/fax or use as a portable
disk drive.

physical address An address identifying a single node.

physical control Layer 1 in the system network architecture model.


layer

physical layer Layer 1 (the bottom layer) of the OSI reference model is implemented by the
physical channel. It governs hardware connections and byte-stream encoding for
transmission. It is the only layer that involves a physical transfer of information
between network nodes. The physical layer insulates layer 2 (the data link layer)
from medium-dependent physical characteristics such as baseband, broadband or
fiber optic transmission. Layer 1 defines the protocols that govern transmission
media and signals.

31006929.00 10/2005 549


Glossary

physical media Any physical means for transferring signals between OSI systems. Considered
outside the OSI Model, and sometimes referred to as Layer 0, or the bottom of the
OSI Reference Model.

ping (packet Internet groper) To test the network by trying to reach a destination with an
ICMP echo request and waiting for a reply, type ping.exe at the command line.

point-to-point A circuit connecting two nodes only, or a configuration requiring a separate physical
connection between each pair of nodes.

port The physical connector on a device enabling the connection to be made.

port multiplier A concentrator that connects multiple devices to a network.

PPP (point-to-point protocol) A protocol that provides router-to-router and host-to-


network connections over both synchronous and asynchronous circuits. The
successor to SLIP.

PRI (primary rate interface) Of the two levels of service within ISDN, the one intended for
larger enterprises. Consists of 23 B-channels and one 16 kbps D-channel in the U.S.
or 30 B-channels and one D-channel in Europe.

print server A dedicated computer that manages printers and print requests from other nodes on
the network.

protocol Any standard method of communicating over a network.

QoS (quality of service) A performance specification for measuring and improving the
transmission quality and service availability of a communications system.

rapid spanning (RSTP) An enhancement of spanning tree protocol that cuts convergence time; it
tree reduces reconfiguration time and therefore restores service faster. See spanning
tree.

550 31006929.00 10/2005


Glossary

RARP (reverse address resolution protocol) A protocol used to convert a hardware


interface address into a protocol address.

RAS (remote access server/service) A server that offers remote access to a Local area
Network (LAN), most commonly by use of a telephone line.

redundancy The duplication of critical components in order to increase reliability.

remote access Access to network resources not located on the same physical Ethernet, where the
physical Ethernet refers to an entire site network topology.

remote control Form of remote access where a device dialing in assumes control of another
network node; all keystrokes on the remote are translated into keystrokes on the
network node. Used primarily with IPX protocol.

remote node Form of remote access where the device dialing in acts as a peer on the target
network. Used with both IP and IPX protocols.

repeater A network device that connects one Ethernet segment to another within the same
local area network. The repeater transmits signals both ways between the
segments. It amplifies the electrical signals, regenerates the header of each packet,
extends packet fragments and performs auto-segmentation and auto-reconnection
on ports with continuous collisions.

ring A network topology in which the nodes are connected in a closed loop. Data move
from node to node around the loop, always in the same direction.

RIO adapter Remote Input/Output CRP (communications processor to the remote devices)

RIO link Network communications across the remote input/output devices

RIP routing information protocol A distance vector protocol that uses distance in number
of routing hops to calculate the best next path for a data packet.

RJ connector A registered jack connector type used with twisted pair UTP/STP, e.g., RJ45.

RMON (remote monitoring) A subset of SNMP. MIB II allows flexible and comprehensive
monitoring and management capabilities by addressing up to 10 different groups of
information.

RMON MIB (remote monitor management information base) The nine (Ethernet) levels of
network management statistics reporting.

31006929.00 10/2005 551


Glossary

router Device capable of filtering/forwarding packets based on data link layer information.
Whereas a bridge or switch may read only MAC layer addresses to filter, a router
can read data such as IP addresses and route accordingly.
Unlike bridges, routers operate at level 3 (the network layer) of the OSI model. Also
unlike bridges, routers are protocol specific, acting on routing information carried by
the communications protocol in the network layer. Bridges pass layer 2 (data link)
packets directly onto the next segment of a LAN, whereas a router can use
information about the network topology and so can choose the best route for a
layer 3 packet. Because routers operate at level 3, they are independent of the
physical layer and so can be used to link a number of different network types. They
have to be able to exchange information between themselves so that they know the
conditions on the network; which links are active and which nodes are available.

router hop The route between one router and the next; all data packets specify the number of
hops after which the packet will be dropped and an error message sent to the data
source.

routing The process of delivering a message across a network or networks via the most
appropriate path. While simple in principle, routing uses a specialized, complex
science, influenced by a plethora of factors. The more networks are joined together,
the more esoteric it is set to become.

routing bridge MAC layer bridge that uses network layer methods to determine a network's
topology.

routing protocol Protocol that implements a specific routing algorithm.

routing table Table stored in a router or some other internetworking device that keeps track of
routes (and, in some cased, metrics associated with those routes) to particular
network destinations.

routing update Message sent from a router to indicate network accessibility and associated cost
information. Routing updates are typically sent at regular intervals and after a
change in network topology.

RTPS (real-time publish-subscribe) Enables the transfer of data and the transfer of state
over unreliable protocols like UDP/IP.

SASL (simple authentication and security layer) Used to identify and authenticate a user
to a server; can also protect further transmissions by inserting a security layer.

552 31006929.00 10/2005


Glossary

SCADA (supervisory control and data acquisition) Software that, interfacing with a
programmable logic controller, gathers and analyzes information used to monitor
and control commercial equipment

ScTP (screened twisted pair) Cabling with two conductors wound around each other to
lessen crosstalk, a braided shield like STP, and an extra outer braid for added
protection.

SDH (synchronous digital highway) Signal standard in digital transmission.

segment With respect to Ethernet, an electrically continuous piece of the bus. Segments can
be joined together using repeaters or bridges.

segment delay The amount of time it takes a signal to propagate from one end of the segment to
the distant end.

segmentation With respect to Ethernet, splitting an overloaded ring into two or more separate
rings, linked by a bridge/router or multipurpose hub.

server A computer that provides resources to be shared on the network, such as files (file
server) or terminals (terminal server).

session A connection to a network service.

shared Ethernet Ethernet configuration in which a number of segments are bound together in a single
collision domain. Hubs produce this type of configuration, where only one node can
transmit at a time.

signal loss See loss

SLIP (serial-line Internet protocol) A protocol for running TCP/IP over serial lines.

smart wiring hub A network concentrator that allows multiple media to be supported and managed
from a central location. When supporting structured wiring systems, smart hubs
provide port management.

SMF (single-mode fiber) A fiber with a small core diameter (approximately 3 μm) and a
cladding with a refractive index very close to that of the core. It transmits light rays
that enter at a narrow angle over very wide bandwidth. SMF has a relatively narrow
diameter through which only one mode propagates. It carries higher bandwidth than
MMF, but requires a light source with a narrow spectral width.

SMS (short message service) Text messages of up to 160 characters that can be sent to
a wireless device.

31006929.00 10/2005 553


Glossary

SMTP (simple mail transfer protocol) Internet standard used to send and receive email
messages.

SNA (systems network architecture) IBM's layered protocols for mainframe


communications.

SNMP (simple network management protocol) A 3-part protocol comprising: structure of


management information (SMI), management information base (MIB) and the
protocol itself. The SMI and MIB define and store the set of managed entities; SNMP
itself conveys information to and from these entities. The public domain standard is
based on the operational experience of TCP/IP Internet works within DARPA/
NSFnet.
A TCP/IP host running an SNMP application to query other nodes for network-
related statistics and error conditions. The other hosts, which provide SNMP agents,
respond to these queries and allow a single host to gather network statistics from
many other network nodes.

SNP (sub-network protocol) A TCP/IP protocol residing in the sub-network layer below IP.
It provides data transfer through the local sub-net. In some systems, an adapter
module must be inserted between IP and the SNP to reconcile their dissimilar
interfaces.

SNTP (simple network time protocol) A simplified version of NTP, used to synchronize the
clocks of computer systems.

SOAP (simple object access code)

socket A unique identifier, made up of an IP address and a port number, for an end-point of
communication in a system/application.

SONET (synchronous optical network) Signal standard in digital transmission.

spanning tree (STP) A technique that detects loops in a network and logically blocks the redundant
paths, ensuring that only one route exists between any two LANs; used in an IEEE
802.1d bridged network. See rapid spanning tree.

spanning tree An algorithm used by bridges to create a logical topology that connects all network
algorithm segments and to ensure that only one path exists between any two stations.

spoofing A security attack in which an intruder sends a message using the stolen/hacked IP
address of an identified host on the network in order to gain unauthorized access.

SQL (structured query language) Used to query (request data from) a relational
database.

554 31006929.00 10/2005


Glossary

SSID (service set identifier) A sequence of 32 letters or numbers in the packet header that
uniquely identifies a wireless LAN.

star topology A network where each workstation is connected to a central hub through a dedicated
point-to-point connection.

store and Technique for examining incoming packets on an Ethernet switch or bridge whereby
forward the whole packet is read before forwarding or filtering takes place. Store and forward
is a slightly slower process than cut-through, but it ensures that all bad or misaligned
packets are eliminated from the network by the switching device.

STP (shielded twisted-pair) Common transmission medium that consists of a receive


(RX) and a transmit (TX) wire twisted together to reduce crosstalk. The shield is a
braided outer sheath.

STU application Project file extension for Unity Pro software application
file

subnet A interconnected, but separate, portion of a network that shares a network address
with other portions of the network. Used for security and performance.

supernetting See CIDR.

switch A multiport Ethernet device designed to increase network performance by allowing


only essential traffic on the attached individual Ethernet segments. Packets are
filtered or forwarded based upon their source and destination addresses.

switched An Ethernet hub with integrated MAC-layer bridging or switching capability that
Ethernet provides each port with 10 Mb/s of bandwidth.Separate transmissions can occur on
each port of the switching hub. The switch filters traffic based on destination MAC
address.

switched virtual A logical network consisting of several different LAN emulation domains controlled
LAN through and intelligent network management application.

switching hubs Hubs that use intelligent Ethernet switching technology to interconnect multiple
Ethernet LANs and higher-speed LANs such as FDDI.

SYN (synchronize) A packet type used by TCP to synchronize sequence numbers on two
computers beginning a new connection.

SYN ACK A message that acknowledges the synchronize message from the client and opens
the socket from the server back to the client.

31006929.00 10/2005 555


Glossary

synchronous The client application that calls a read or write service is blocked from further
services requests for the time it takes to obtain a result from the original request.

T-connector A T-shaped device with two female connectors and one male BNC connector.

tap connector Physical hardware that allows connection of a device, or new section of cable, to a
trunk cable.

TCP/IP (transmission control protocol/Internet protocol) A set of protocols developed by the


U.S. Defense Department's Advanced Research Projects Agency (ARPA) during
the early 1970s. Its intent was to develop ways to connect different kinds of networks
and computers. TCP/IP does not have the functionality that OSI provides.
TCP/IP is a transport and Internet working protocol—i.e., the de facto networking
standard. It is commonly used over X.25 and Ethernet wiring and is viewed as one
of the few protocols available that is able to offer a true migration path towards OSI.
TCP/IP is able to operate in most environments. TCP/IP operates at Layers Three
and Four of the OSI model (Network and Transport respectively).
TCP and IP are the standard network protocols in UNIX environments. They are
almost always implemented and used together.

Telnet A terminal emulation program used to remotely control servers.

terminal server A concentrator that facilitates communication between hosts and terminals.

terminator A special connector used on both ends of a standard Ethernet or thin-wire Ethernet
segment. It provides the cable with 50 Ω of termination resistance.

TFTP (trivial file transfer protocol) On computers that run TCP/IP networking software,
TFTP is used to quickly send files across the network with fewer security features
than FTP.

thick wire Half-inch diameter coaxial cable.

thin wire Coaxial cable similar to that used for television/video hookups.

time-out An interrupt signal sent by a device that has not received the input it has waited a
given time for.

556 31006929.00 10/2005


Glossary

token-ring A computer network in which a bit pattern called a token is passed around a circular
topology, or ring, of computers, in order to prevent collision of data between two
computers trying to send messages at the same time.

topology The arrangement of the nodes and connecting hardware that comprises the
network. Types include ring, bus, star and tree.

TP (twisted-pair) Cable consisting of two 18 to 24 AWG solid or stranded copper


conductors, each coated in an insulating material, that are twisted together. The
twisting provides a measure of protection from electromagnetic and radio-frequency
interference.

trace route TraceRT is a route tracing tool used to measure the number of router hops, or
routes, between systems to help locate problems; Type tracert.exe at the command
prompt.

transceiver A network device capable of both transmitting and receiving messages. It serves as
the interface between a user device and a network, so that it may actively convert
signals between the network and the local node.

transceiver cable Cable that attaches a device either to a standard or thin coax Ethernet segment.

Transparent Schneider solutions for optimizing electrical distribution, industrial control and
Ready services automation performance.

twisted-pair Inexpensive, multiple-conductor cable comprising one or more pairs of 18 to


cable 24 AWG copper strands. The strands are twisted to improve protection against
electromagnetic and radio frequency interference. The cable, which may be either
shielded or unshielded, is used in low-speed communications, as telephone cable.
It is used only in base-band networks because of its narrow bandwidth.

UDP (universal datagram protocol) A transport layer protocol for datagrams, used
primarily for broadcasting. Also responsible for port addresses.

UL approval Tested and approved by Underwriters Laboratories, Inc.

UL cable In conjunction with several manufacturers, UL has developed a data transmissions


certification performance level marking program. This approval is printed on a cable as shown
below:

31006929.00 10/2005 557


Glossary

Level I - performance is intended for basic communications and power-limited circuit


cable.
Level II - performance requirements are similar to those for Type 3 cable (multi-pair
communications cable) of the IBM Cabling System Technical Interface Specification
(GA27-3773-1). These requirements apply to both shielded cable with two-to-25-
pair conductors.
Level III - data cable complies with the transmission requirements in the EIA/TIA
Wiring Standard for Horizontal Unshielded Twisted Pair (UTP) Cable and with the
requirements for Category 3 in the proposed EIA/TIA 568A Standard. These
requirements apply to both shielded and unshielded cables. Level IV Level IV cable
complies with the requirements in the proposed National Electrical Manufacturer's
Association (NEMA) Standard for Low-Loss Premises Telecommunications Cable.
Level IV - requirements are similar to Category 4 requirements of the proposed EIA/
TIA 568A Standard. These requirements apply to both shielded and unshielded
cable constructions. Level V Level V cable complies with the requirements in the
proposed NEMA Standard for Low-Loss Extended-Frequency Premises
Telecommunications Cable. Level V requirements are similar to Category 5
requirements of the EIA/TIA 568A Standard. These requirements apply to both
shielded and unshielded cable constructions.

UMAS protocol unified messaging application protocol Brings together all messaging media in a
single interface.

Uni-TE An application layer communication protocol; This service enables read and write
access to variable, program transfers, management of device operating modes, link
and device diagnostics and transmission of unsolicited data.

UTP (unshielded twisted pair) One or more cable pairs surrounded by insulation. UTP is
commonly used as telephone wire.

VijeoLook PC Base HMI (Human Machine Interface) software from Schneider S.D.

VPN (virtual private network ) A network that connects private networks with remote sites
using a third party service provider.

VSD (variable speed drive)

558 31006929.00 10/2005


Glossary

WAN (wide area network) A network using common carrier transmission services for
transmission of data over a large geographical area.

WEP (wired equivalent privacy) A security protocol for wireless LANs that encrypts data
transmitted over radio waves.

workgroup Configuration in which a number of users are connected to an Ethernet network via
switching a switch. Switching allows each user to get greater throughput than would be
available through a hub.

X-Way The addressing mechanism (at the network layer) for the Uni-TE protocol; It enables
several Ethway, Ethernet TCP/IP and/or Fipway networks or segments to be
interconnected. On TCP/IP Ethernet, X-Way and IP addressing are used in
conjunction.

XVM symbols file File extension of exported variables from Unity Pro used by OFS

31006929.00 10/2005 559


Glossary

560 31006929.00 10/2005


Index
B
AC
Numerics attenuation of crosstalk ratio
ISO/IEC 11801 performance
100Base-TX standard parameter, 532
for twisted-pair Ethernet systems, 83

A B
back-up watchdog
access server
in a SCADA system, 303
in an Ethernet WAN, 68
balance
ACR ISO/IEC 11801 performance
attenuation crosstalk ratio, 532
parameter, 533
actual earth, 98 blocking
address in SCADA communication, 289
administered IP multicasting, 138
BootP
for IP multicasting, 138 troubleshooting, 374
non-permanent IP multicasting, 138 BRI
permanent IP multicasting, 138
ISDN options, 65
address range, 134, 135 bridge
administered permanent IP multicast in an Ethernet system, 63
address, 138
troubleshooting, 380
administration broadcast domains
cabling, 114 in an Ethernet system, 60
alarm viewer
building backbone, 38
in a FactoryCast Web server, 238 bus topology, 46
application layer
in the TCP/IP model, 128
application synchronization C
for global data, 207
cabinet distributor, 45
asynchronous services
cabinets
in an OPC factory server operation, 270
creating equipotential bonding for, 101
attenuation
cable
ISO/IEC 11801 performance
construction for Ethernet, 113
parameter, 530

31006929.00 10/2005 561


Index

cable crimper CAT 1


for building Ethernet copper unshielded 1 Mb/s twisted-pair copper
cables, 111, 113 cable, 81
cable cutter CAT 2
for building Ethernet copper unshielded 4 Mb/s twisted-pair copper
cables, 111, 113 cable, 81
cable labeling CAT 3
standards, 114 16 Mb/s twisted-pair copper cable, 81
cable routing CAT 4
between buildings, 107 20 Mb/s twisted-pair copper cable, 81
between cabinets, 107 CAT 5
cable run recommendation, 104 100 Mb/s twisted-pair copper cable, 82
cable shielding CAT 5E
connecting to a metal surface, 522 enhanced CAT 5 350 MHz twisted-pair
cable stripper copper cable, 82
for building Ethernet copper CAT 6
cables, 111, 113 400 MHz twisted-pair copper cable, 82
cables, components CAT 7
labeling, 114 500-700 MHz twisted-pair copper
cabling cable, 82
100Base-FX fiber optic specifications, 89 changeover
10Base-FL fiber optic specifications, 89 in a Quantum hot standby system, 310
administration, 114 UDP message in a Quantum hot standby
commercial installations, 115 system, 311
component testing, 115 channel, 121
documentation, 115 circuit switching
fiber optic, 85 in an Ethernet system, 65
fiber optic standards, 85 client
fiber optic technical description, 85 in a faulty device replacement
fiber optic types, 86, 88 operation, 211
fiber optic vs. copper, 88 client communication
labels, 116 between an I/O server and a SCADA
test data, 116 display, 294
cabling planning standards, 34 climate protection requirements
cabling shield humidity, 75
how to ground, 525 operating temperature, 74
cabling subsystems, 38 storage temperature, 74
cabling system UV exposure, 75
elements, 38 collision domains
caching in an Ethernet system, 59
in a multicast application, 138 collision management, 59
calculation functions combining data transfers, 169
in a FactoryCast HMI Web server commercial installations
operation, 246 cabling, 115
campus backbone, 38

562 31006929.00 10/2005


Index

common bonding network, 99 data


company level communication, 159 lost packets, 381
Transparent Ready services, 160 packet capture, 383, 384
compatibility troubleshooting, 381
of services, 169 data transfer communication
component testing Transparent Ready services, 161
cabling, 115 data transfers
configuration services, 169 combining, 169
configuration software DC loop resistance
for a FactoryCast Web server, 236 ISO/IEC 11801 performance parameter,
conformance recommendations 533
for installing Ethernet copper cable, 118 decimal notation, 133
connecting a PLC to the Internet, 146, 151 degree of protection
connectors ingress protection requirements, 77
fiber optic, 93 delay scew
fiber optic LC, 93 ISO/IEC 11801 performance
fiber optic MT/RJ, 93 parameter, 533
fiber optic SC, 93 designing a network, 169
fiber optic ST, 93 device support
M12, 92 for a FactoryCast HMI Web server, 247
M12 pinouts, 92 for a FactoryCast Web server, 240
RJ45, 90 for a Web server, 234
RJ45 pinouts, 91 for electronic mail notification, 227
shielded RJ45, 91 for faulty device replacement, 212
copper cable for global data, 206
for Ethernet systems, 81 for Modbus messaging services, 189
copper cables for the file transfer protocol,
tools for building, 111, 113 255, 257, 259, 260, 261, 262, 263
crimper for the simple network management
for building Ethernet copper protocol, 255, 257, 260, 261, 262, 263
cables, 111, 113 for the Telnet service, 256, 258, 260, 263
crossover copper cable for the trivial file transfer
color code, 110 protocol, 255, 258, 263
pinout, 109 services for Advantys STB, 328
crush requirements, 73 services for Altivar ATV 38/58 variable
CSU/DSU hardware speed drives, 329
in an Ethernet WAN, 69 services for ConneXium cabling
cutter systems, 331
for building Ethernet copper services for Momentum Ethernet
cables, 111, 113 communication modules, 326
services for Momentum M1E
processors, 325
D services for Power Logic gateways, 330
daisy chain topology, 48 services for Premium CPUs, 322

31006929.00 10/2005 563


Index

services for Premium Ethernet electronic mail notification, 223


modules, 323 device support, 227
services for Quantum, 321 operation, 225
services for TSX Micro communication optional password protection, 226
modules, 324 service selection, 164
services for Twido, 327 elements of a Transparent Ready system, 26
diagnostic services, 168 ELFEXT
diagnostic word equal-level far-end crosstalk, 532
for I/O scanning, 177 embedded diagnostics
dial-up service selection, 164
for remote control of a PC, 146 EMC sensitivity
dial-up services signal classification, 102
in an Ethernet system, 67 EMI prevention
disable I/O scanning, 176 earthing methods, 97
distribution group equipotential bonding, 97
in a global data operation, 204 installation measures, 97
documentation methods, 97
cabling, 115 enable I/O scanning, 176
DSP-4000 certification tool equal-level far-end crosstalk
for copper cable installations and ISO/IEC 11801 performance parameter,
performance, 123 532
dual ring topology, 50 equipotential bonding
dynamic pages creating an earthing system for a
in a Web server operation, 231 building, 100
defined, 98
local equipment, 101
E standard, 99
earth plane, 99 to combat EMI in Ethernet networks, 97
earthing error handling
to combat EMI in Ethernet networks, 97 for I/O scanning, 176
earthing conductors, 98 in a global data operation, 204
earthing connection Ethernet
for cable shielding, 522 architectural considerations, 333
procedure, 520 in industrial applications, 19
earthing connections industrial, 18
recommendations, 518 packet capture tool, 383
earthing main conductor, 98 Ethernet bus topology, 52
earthing ring bus, 99 Ethernet cable construction, 113
earthing system components, 98 Ethernet daisy chain topology, 53
effective repetition rates Ethernet frames, 58
for I/O scanning, 178 Ethernet II
electromagnetic emission standards, 79 in the Transparent Ready model, 130
Ethernet ring topology, 54
Ethernet standards
IEEE 802.3, 34
ISO/IEC 8802-3, 34

564 31006929.00 10/2005


Index

Ethernet star topology, 53 FEXT


Ethernet systems far-end crosstalk, 532
broadcast domains, 60 fiber optic, 85
collision domains, 59 cabling types, 86
LAN technologies, 58 technical description, 85
VLANs, 60 field distributor, 45
wireless IP, 61 field level communication, 159
evaluating a system, 169 Transparent Ready services, 162
exception reporting file distribution
in SCADA communication, 286 in a multicast application, 138
file transfer protocol
Advantys STB device support, 261
F ConneXium device support, 263
FactoryCast Micro device support, 259
service selection, 164 Momentum device support, 260
FactoryCast HMI Web server service Power Logic device support, 262
architecture, 243 Premium device support, 257
calculation functions, 246 Quantum device support, 255
connected to a relational database, 246 file transfer protocol service, 249
device support, 247 firewall, 154
HMI tag database, 245 advanced, 154
hybrid architectures, 244 setup, 154
information management levels, 245 with Modbus filtering, 154
operation, 243 flexing requirements, 73
FactoryCast Web server service frames
alarm viewer, 238 in an Ethernet system, 58
configuration software, 236 FTP
device support, 240 file transfer protocol, 165
graphical data editor, 238 troubleshooting, 373
hosting, 236 function codes
far-end crosstalk Modbus, 187
ISO/IEC 11801 performance
parameter, 532
fast Ethernet, 58 G
fault conditions GARP multicast registration protocol, 139
for the Transparent Ready I/O scanning gateway
service, 180 in an Ethernet system, 63
faulty device replacement, 374 message queue, 318
device support, 212 response times, 352
service selection, 163 using shared memory, 317
when to use the service, 211 with application protocol conversion, 316
faulty device replacement client, 211 without application protocol
faulty device replacement server, 211 conversion, 315
FDR gateway delay, 352
faulty device replacement, 163 gateway socket, 319
gateway timeout, 320

31006929.00 10/2005 565


Index

gigabit Ethernet, 58 HMI


global data client/server model, 284
application synchronization, 207 standalone model, 284
device support, 206 troubleshooting, 379
limits, 205 HMI tag database
response times, 208 in a FactoryCast HMI Web server
service selection, 163 operation, 245
standards, 203 horizontal cabling, 38
using multicast technology, 207 hot standby
when to use the service, 206 in a communication-centric system, 305
global data service SCADA implementations, 304
error handling, 204 hub
GMRP, 139 in an Ethernet system, 62
graphical data editor humidity range requirements, 75
in a FactoryCast Web server, 238 hunting
ground connection to determine if a SCADA communication
for cable shielding, 522 path is correct, 310
procedure, 520
ground connections
recommendations, 518 I
ground loops, 526 I/O scanner
group management response time formulae, 343
over an Ethernet system, 139 troubleshooting, 370
group membership I/O scanning
in an IP multicast system, 139 common fault conditions, 180
group of items diagnostic word, 177
in an OPC factory server operation, 268 disable, 176
enable, 176
error handling, 176
H health bit, 177
health bit operation, 174
for I/O scanning, 177 read operations, 176
heavy industrial environment remote device requirements, 172
crush requirements, 73 repetition rates, 178
degree of ingress protection, 78 response times, 181
flexing requirements, 73 service selection, 163
humidity range, 75 TCP socket usage, 177
M12 circular connectors, 92 when to use, 172
operating temperature range, 74 write operations, 175
recommended levels of pollution, 76 I/O scanning characteristics, 172
shock requirements, 72 IEC 1000-4 standard
storage temperature range, 74 for electric and electromagnetic
tensile strength requirements, 73 interference, 79
UV exposure requirements, 75 IEEE 802.3
vibration requirements, 72 Ethernet standard, 34
in the Transparent Ready model, 130

566 31006929.00 10/2005


Index

IGMP, 139 IP code


IGMP snooping, 139 for degree of ingress protection, 77
immunity standards, 79 ISDN
impedance in an Ethernet system, 65
ISO/IEC 11801 performance ISDN terminal adapter
parameter, 530 in an Ethernet WAN, 69
independent interfaces ISO/IEC 11801 performance parameters
on an Ethernet network, 299 attenuation of crosstalk ratio, 532
industrial applications DC loop resistance, 533
for Ethernet, 19 equal-level far-end crosstalk, 532
industrial Ethernet far-end crosstalk, 532
defined, 18 insertion loss, 530
how it differs from commercial longitudinal-to-differential conversion
Ethernet, 19 loss, 533
industrial site backbone, 44 near-end crosstalk loss, 531
industrial site distributor, 44 nominal impedance, 530
information management levels power sum attenuation of crosstalk
in a FactoryCast HMI Web server ratio, 532
operation, 245 power sum equal-level far-end cross
ingress protection requirements talk, 532
degree of protection, 77 power sum near-end crosstalk loss, 532
pollution levels, 76 propagation delay, 533
installation measures propagation delay scew, 533
to combat EMI in Ethernet networks, 97 return loss, 530
installation standards, 34 ISO/IEC 11801 standard
intermittent connections copper cable testing definitions, 527
in an Ethernet system, 364 for planning and installing copper cable,
internal clocks 511
for I/O scanning repetition rates, 178 ISO/IEC 8802-3
international standards Ethernet standard, 34
for industrial Ethernet, 31
Internet connection to a PLC
for remote system access, 146, 151 L
Internet group management protocol, 139 labeling
Internet group management protocol cables, components, 114
snooping, 139 labels
Internet suite of protocols, 131 cabling, 116
internetwork layer LAN technologies
in the TCP/IP model, 129 for Ethernet systems, 58
of the Transparent Ready model, 130 leased line
inter-PLC level communication, 159 in an Ethernet system, 65
IP address and classes, 133
IP address classes, 134
IP address defined, 133
IP address management
in a Quantum hot standby system, 310

31006929.00 10/2005 567


Index

light industrial environment mesh topology, 51, 55


crush requirements, 73 MIB
degree of ingress protection, 78 for network management, 140
flexing requirements, 73 MICE, 32
humidity range, 75 Modbus
operating temperature range, 74 function codes, 187
recommended levels of pollution, 76 Modbus client, 186, 187
RJ45 copper connectors, 90 limits in a Momentum system, 193
shock requirements, 72 limits in a Premium system, 191
storage temperature range, 74 limits in a Quantum system, 190
tensile strength requirements, 73 operations in a Momentum system, 193
UV exposure requirements, 75 operations in a Premium system, 192
vibration requirements, 72 operations in a Quantum system, 190
linked interfaces retry times, 201
on an Ethernet network, 298 time-outs, 201
load limits Modbus communication standard, 184
for Ethernet messages, 345 Modbus messaging, 185
logical check client communication limits, 342
operating system, 363 client limits in a Momentum system, 193
logical connections client limits in a Premium system, 191
troubleshooting an Ethernet system, 361 client limits in a Quantum system, 190
longitudinal-to-differential conversion loss client operations in a Momentum
ISO/IEC 11801 performance system, 193
parameter, 533 client operations in a Premium
loop resistance system, 192
ISO/IEC 11801 performance client operations in a Quantum
parameter, 533 system, 190
client response times in a Momentum
system, 341
M client response times in a Premium
MAC address, 139 system, 341
machine distributor, 45 client response times in a Quantum
machines system, 340
creating equipotential bonding for, 101 client retry times, 201
MBP_MSTR block client services, 186, 187
to monitor Ethernet communications in a client time-outs, 201
Quantum system, 308 device support, 189
mechanical ratings Modbus TCP device
for environmental parameters and implementation, 185
requirements, 32 response time, 334
mechanical requirements server communication limits, 338
crush, 73 server operations in a Momentum
flexing, 73 system, 199
shock, 72 server operations in a Premium
tensile strength, 73 system, 198
vibration, 72

568 31006929.00 10/2005


Index

server operations in a Quantum N


system, 194
near-end crosstalk loss
server operations with Concept, 195
ISO/IEC 11801 performance
server operations with Proworx, 195
parameter, 531
server response times in a Premium
network access
system, 198
from a remote station, 146
server retry times, 201
network congestion
server services, 186, 188
in an Ethernet system, 60
server TCP socket limits, 200
network design, 169
service selection, 163
network interface layer
simple servers, 200
in the TCP/IP model, 129
troubleshooting, 370
network management
Unity server performance, 196
for an Ethernet system, 140
Modbus server, 186, 188
NIC
operations in a Momentum system, 199
operating system, 363
operations in a Premium system, 198
noise immunity standards, 79
operations in a Quantum system, 194
nominal impedance
operations with Concept, 195
ISO/IEC 11801 performance
operations with Proworx, 195
parameter, 530
performance in Unity, 196
nonpermanent IP multicast address, 138
response times in a Momentum
notification service
system, 336
in an OPC factory server operation, 270
response times in a Premium
NTP
system, 198, 335
troubleshooting, 377
response times in a Quantum
system, 336
retry times, 201
TCP socket limits, 200
O
Modbus servers, 200 OMNIscanner 2 certification tool
modem for copper cable installations and
in an Ethernet WAN, 69 performance, 123
Monitor Pro OPC factory server
implementation of the SCADA client/ asynchronous services, 270
server model, 295 build-time/runtime option, 277
MSTR block compacting items of the same type, 273
to monitor Ethernet communications in a concatenating requests, 273
Quantum system, 308 notification service, 270
multicast applications optimizing requests, 273
on an Ethernet system, 138 runtime architecture, 275
multicast technology services, 266
for global data, 207 size of requests, 272
synchronous services, 269
with multiple SCADA connections, 281
open standards
in Ethernet for automation, 126

31006929.00 10/2005 569


Index

operating system point-to-point link


logical check, 363 in an Ethernet system, 65
NIC, 363 point-to-point VPN, 150
operating temperature range pollution levels
requirements, 74 ingress protection requirements, 76
OSI model, 127 power sum attenuation of crosstalk ratio
ISO/IEC 11801 performance
parameter, 532
P power sum equal-level far-end crosstalk
packet capture ISO/IEC 11801 performance
tools, 383 parameter, 532
troubleshooting, 384 power sum near-end crosstalk loss
packet switching ISO/IEC 11801 performance
in an Ethernet system, 66 parameter, 532
packets PRI
lost, 382 ISDN options, 65
troubleshooting, 382 private MIB
pair-to-pair attenuation of crosstalk ratio for network management, 140, 358
ISO/IEC 11801 performance problem identification
parameter, 532 in an Ethernet system, 360
pair-to-pair equal-level far-end crosstalk propagation delay
ISO/IEC 11801 performance ISO/IEC 11801 performance
parameter, 532 parameter, 533
pair-to-pair near-end crosstalk loss propagation delay scew
ISO/IEC 11801 performance ISO/IEC 11801 performance
parameter, 531 parameter, 533
parameters PSACR
for copper cable testing, 528 power sum attenuation crosstalk
password, 153 ratio, 532
performance parameters PSELFEXT
for Ethernet copper cable, 528 power sumequal-level far-end cross
performance standards, 34 talk, 532
performance testing publisher
a copper installation, 527 in a global data operation, 204
permanent IP multicast address, 138 push media
permanent link, 119 in a multicast application, 138
physical connections
troubleshooting an Ethernet system, 360
pinout Q
RJ45 connector for twisted-pair Ethernet Quantum hot standby
systems, 84 in a communication-centric system, 305
pinouts SCADA implementations, 304
for an RJ45 copper connector, 91 queue
M12 circular connectors, 92 for messaging through a gateway, 318
plant data transfer services, 166
plant distributor, 44

570 31006929.00 10/2005


Index

R return loss
ISO/IEC 11801 performance
rack viewer
parameter, 530
in a Web server operation, 232
ring topology, 49
RAS systems, 148
RJ45 connector
read operations
color code for wires, 84
for I/O scanning, 176
pinouts, 84
recycle power
RJ45 copper connectors, 90
when troubleshooting an Ethernet
RM12 circular connectors, 92
system, 357
router
redundancy
in an Ethernet system, 63
and network communication
in an Ethernet WAN, 68
services, 297
routing
redundancy levels
using IP addressing, 142
in a SCADA system, 301
routing cables between buildings, 107
redundant system
routing cables between cabinets, 107
for Quantum, 306
running cables, 104
fully implemented for Quantum, 307
limitations in a Quantum system, 306
relational database connection S
to a FactoryCast HMI Web server, 246
SCADA
remote access
back-up watchdog, 303
to an Ethernet system, 144
blocking technique for efficient
via dial-up, 146
communication, 289
remote access server
client/server model, 284
layout, 148
communication to a redundant
remote access to an Ethernet system
device, 302
troubleshooting, 366
exception reporting, 286
remote access VPN, 150
for a Quantum hot standby system, 304
remote configuration
stages of communication, 285
using a Web server, 230
standalone model, 284
remote data transfer services
troubleshooting, 379
for plant data, 167
watchdog-to-Quantum PLC
remote device
implementation, 309
I/O scanning requirements, 172
SCADA communication
repeater
on a single socket that supports multiple
in an Ethernet system, 62
requests, 292
response time
on a single socket that supports one
for a gateway, 352
request at a time, 291
Premium I/O scanning performance, 182
on multiple sockets that support one
Quantum I/O scanning performance, 181
request at a time, 293
response times
SCADA-to-SCADA communication, 294
for global data, 208
scheduled distribution
Modbus server service summary, 337
in a multicast application, 138

31006929.00 10/2005 571


Index

security Momentum Ethernet communication


access control list, 154 device support, 326
access points, 155 Momentum M1E device support, 325
firewall, 154 OPC factory server, 265
firewall setup, 154 Power Logic gateway device
for an Ethernet system, 153 support, 330
password, 153 Premium CPU device support, 322
physical access, 153 Premium Ethernet communication
PLC access control, 155 device support, 323
policy, 153 Quantum device support, 321
port, 155 simple network management
VPN, 156 protocol, 250
WEP, 156 Telnet, 253
wireless, 155 time synchronization, 164
selection standards, 34 trivial file transfer protocol, 252
self-healing ring topology, 56 troubleshooting, 368, 369
sensitivity TSX Micro communication device
in EMC performance, 102 support, 324
server Twido device support, 327
in a faulty device replacement used for applications, 160
operation, 211 used for company level
service compatibility, 169 communication, 160
services used for field devices, 160
Advantys STB device support, 328 used for supervision systems and
Altivar ATV 38/58 variable speed drive PLCs, 160
device support, 329 Web server, 229
available for a Quantum hot standby Web/FactoryCast, 164
system, 311 shielded RJ45 copper connectors, 91
ConneXium cabling system device shielded twisted pair cable
support, 331 characteristics, 82
electronic mail notification, 164, 223 shock requirements, 72
embedded diagnostics, 164 signal classification, 102
FactoryCast HMI Web server, 242 simple network management protocol
FactoryCast Web server, 236 Advantys STB device support, 261
faulty device replacement, 163, 210 ConneXium device support, 263
file transfer protocol, 249 Momentum device support, 260
for field level communication, 162 operation, 251
for inter-PLC level communication, 161 Power Logic device support, 262
for synchronizing applications, 161 Premium device support, 257
global data, 163, 203 Quantum device support, 255
I/O scanning, 163, 171 slow connections
Modbus messaging, 163, 184 on an Ethernet system, 365
SMTP
for electronic mail notification, 225
troubleshooting, 376

572 31006929.00 10/2005


Index

SNMP system evaluation, 169


for network management, 140
for network management stations, 160
simple network management T
protocol, 165 TCP
troubleshooting, 372 in the Transparent Ready model, 132
standards TCP socket limits
cable labeling, 114 for Modbus server services, 200
fiber optic cabling, 85 TCP socket numbers
for cable planning, 34 in a Quantum hot standby system, 312
for Ethernet performance, 34 TCP socket usage
for installing an Ethernet system, 34 for I/O scanning, 177
for selection of Ethernet equipment, 34 TCP/IP
international, 31 in the Transparent Ready model, 131
structured cabling, 34 TCP/IP model
standby monitoring based on OSI, 128
using SCADA in a Quantum hot standby Telnet, 165
system, 309 ConneXium device support, 263
star topology, 47 Momentum device support, 260
static pages Premium device support, 258
in a Web server operation, 231 Quantum device support, 256
storage temperature range requirements, 74 troubleshooting, 373
straight copper cable Telnet service, 253
color code, 109 tensile strength requirements, 73
pinout, 108 test data
strategy cabling, 116
for Transparent Ready, 20 testing
stripper a copper installation, 527
for building Ethernet copper TFTP
cables, 111, 113 trivial file transfer protocol, 165
structured cabling standards, 34, 135 time synchronization
subscriber service selection, 164
in a global data operation, 204 troubleshooting, 377
switch tools
in an Ethernet system, 62 for building Ethernet copper
in an Ethernet WAN, 68 cables, 111, 113
switched networks
and collision management, 59
switched virtual circuits
in an Ethernet system, 67
synchronizing applications
Transparent Ready services, 161
synchronous services
in an OPC factory server operation, 269
system elements
of Transparent Ready, 26

31006929.00 10/2005 573


Index

topologies logical connections in an Ethernet


bus, 46 system, 361
daisy chain, 48 lost packets, 381, 382
dual ring, 50 NTP, 377
Ethernet bus, 52 packet capture, 384
Ethernet daisy chain, 53 physical connections in an Ethernet
Ethernet ring, 54 system, 360
Ethernet star, 53 physical connections on an Ethernet
mesh, 51, 55 network, 362
ring, 49 SCADA, 379
self-healing ring, 56 services, 368
star, 47 slow connections on an Ethernet
traffic congestion system, 365
on an Ethernet system, 361 slow response, 379
transceiver SMTP, 376
in an Ethernet system, 63 SNMP, 372
transfer services Telnet, 373
for plant data, 166 time synchronization, 377
Transparent Ready traffic congestion in an Ethernet
defined, 18 system, 361
strategy, 20 Transparent Ready services, 369
system elements, 26 Web, 378
Transparent Ready model twisted pair
based on OSI, 130 Ethernet copper cable, 81
transparent remote communication, 159
transport layer
in the TCP/IP model, 128 U
of the Transparent Ready model, 132 UDP
trivial file transfer protocol, 252 in the Transparent Ready model, 132
ConneXium device support, 263 UDP protocol
Premium device support, 258 for IP multicasting, 138
Quantum device unshielded twisted pair cable
support, 255, 358, 374, 370 characteristics, 82
troubleshooting UV exposure requirements, 75
an Ethernet system, 357
bridge, 380
Ethernet remote access, 366 V
FTP, 373 vibration requirements, 72
HMI, 379 VijeoLook
intermittent connections in an Ethernet implementation of the OPC server, 295
system, 364 virtual circuits
in an Ethernet system, 67
virtual private network
for remote system access, 150
VLAN end-stations
in an Ethernet system, 60

574 31006929.00 10/2005


Index

VPN
security, 156
VPN remote access, 150

W
wake-up function
in an OPC factory server operation, 270
WAN devices
access servers, 68
CSU/DSU hardware, 69
ISDN terminal adapters, 69
modems, 69
routers, 68
switches, 68
watchdog
back-up for a SCADA system, 303
to monitor remote communications in a
Quantum system, 309
Web
troubleshooting, 378
Web server service
device support, 234
dynamic pages, 231
operation, 231
remote configuration support, 230
static pages, 231
Web/FactoryCast
service selection, 164
WEP
security, 156
wireless communications
in an Ethernet system, 61
wiring recommendations, 103
write operations
for I/O scanning, 175

31006929.00 10/2005 575


Index

576 31006929.00 10/2005