RDOL Power and Control Wiring Drawing

The document provides a diagram and description of a power supply circuit. It includes a control supply receiving 230V input that is fed through fuses and resistors to terminals. The circuit also includes terminals connected to a contactor coil that is used to open and close the circuit based on input signals. Resistors are used to regulate voltage levels throughout the circuit.

Uploaded by

Prachi Dongre
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9K views2 pages

RDOL Power and Control Wiring Drawing

The document provides a diagram and description of a power supply circuit. It includes a control supply receiving 230V input that is fed through fuses and resistors to terminals. The circuit also includes terminals connected to a contactor coil that is used to open and close the circuit based on input signals. Resistors are used to regulate voltage levels throughout the circuit.

Uploaded by

Prachi Dongre
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

0 1 2 3 4 5 6 7 8 9

Power Supply
R R1
Y Y1
B B1
N N1
1 3 5 12 11
-Q1
11 14
/2.2

/2.7

I> I> I>


2 4 6
1 3 5 1 3 5
C31 C32
2 4 6 2 4 6
-X1 1 2 3
U V W
M
3~
PE
RDOL Scheme
SFC Environmental Technologies Pvt. Ltd.
21st Floor, The Ambience Court, Hi-tech Busines Park, Plot No. 2, Sector 19D,
Vashi, Navi Mumbai-400705. INDIA.
Page 1 /2
0 1 2 3 4 5 6 7 8 9
1 2 Control Supply
230V-L
11
3 4 Q1
230V-N /1.0 14
-F1
31
R2
/2.2 34
41
R5
/2.5 44
11
R1
/2.1 12 14
/2.8
STOP
TB 1
X 1
-X3 1 -X3 1
11 -X2 2
OPEN TRQ
TB 1 TB 1 SW FEDD. TB 1 TB 1
14
11 1 11 11 1 11 1 11 12
LPBS 11 11 11 LPBS 11 PLC 11
PLC 11
1 2
SS1 R5 R2
OPEN
R3
CLOSE
R4
CLOSE TRQ R5 OPEN OPEN CLOSE CLOSE CLOSE OPEN
FEDD. FEED. SW FEDD. /2.5
14 /2.5 2 /2.2 14 14 /2.3 4 14 /2.4 4 14 11 14 14 14 4 14 14
X 2
TB 2 TB 2
12 -X2 3 -X2 3 -X3 2 -X3 2
Q1 TB 2
/1.0 11
12 12

Open Feedback

Close Feedback
C2 C1

Auto Feedback

Trip Feedback
/2.7 11 /2.7 11
11 11
R3 R4
14 14
A1 A1
A1 A1 x1 A1 x1 A1 x1 A1 x1
C1 C2
R1 R2 L1 R3 L2 R4 L3 R5 L4 A2 A2
A2 A2 x2 A2 x2 A2 x2 A2 x2 21 21 21 21
R1 R2 R3 R4
/2.1 24 /2.2 24 /2.3 24 /2.4 24
12 11 /2.7 12 11 /2.7
14 11 14 /2.2 1 4 /2.3 1 4 /2.4 1 2 /2.2
12 11 /2.7 21 24 /2.9 11 14 /2.7 11 14 /2.7 12 11 /2.6
21 24 /2.8 31 34 /2.7 21 24 /2.9 21 24 /2.9 41 44 /2.7
-X4 1 2 3 4 5
Digital Input To PLC Panel

Valve Trip

Indication
Valve Trip
Auto/Manual

Valve Open
Indication

Indication

Indication
Valve Close
Valve Open

Valve Close
Mode

Trip
Torque S/W

Torque S/W Trip

CLOSE Contactor
OPEN Contactor
Note:
1. Selection of MPCB (Qxx) and Contactor (Cxx) shall be as per Type-2 co-ordination.
2. Control supply MCB (Fxx) selection shall be done as per current requirement of contactor coil.
RDOL Scheme
SFC Environmental Technologies Pvt. Ltd.
21st Floor, The Ambience Court, Hi-tech Busines Park, Plot No. 2, Sector 19D,
Vashi, Navi Mumbai-400705. INDIA.
Page 2 /2