Distance Protection: of Transmission Line
Distance Protection: of Transmission Line
3 of Transmission Line
Syllabus
Introduction to Distance Protection, Types ofDistance Relay, Impedance, Reactance, MHO Relay,
Performance of Distance Relay During Normal Load andPower Swing, Efectof Arc Resistance on
Reach of Distance Relays, Comparison of Distance Relays, Distance Protection of Transmission
line, Reasons for Inaccuracy of Distance Relay Reach, Three Step Protection, Trip contact
configuration, 3 - step protection of double end fed lines.
Contents
3.1 Drawbacks ofOvercurrent Protection....... . . Summer-18, Marks3
3.2 Introduction to Distance Relays
3.3 Impedance Relay Summer-13,15,18,
... Winter-16,20, Marks 7
3.4 Reactance Relay Summer-13,14,15,17,18,
Winter-14,16,17,18,20, . . * Marks 7
. . . Winter-19,20, Marks 4
3.9 Classification of Distance Relays
3.10 Setting of Distance Relays
3.11 Distance Protection of Transmission Lines
3.12 Reasons for Inaccuracy of Distance Relay Reach
. . ... Winter-15,16, Marks 7
3.13 Three Stepped Distance Protection of Transmission Line
Summer-17,
(3 1)
Distance Protection of Trensmissin
3-2 Line Switchgeer end Protection
Switchge8 and Protection 3-3 Diatance Protection of
GTU:Summer-18 Transmiesion iLIne
Protection
Overcurrent
3.1 Drawbacks of
reach of the over
h e main drawback of
overcurrent protection is that the
overcurrent Fault Fa is
in Line
factors which are, under
relay depends on hwo the type of fault variable
inpadarnc
carrent varies
according to Fault consideration vkiatbia
1. Ihe magnitude of
for a particular type of fault. curren Zi2in1AB,IAB|
2The changes in the
s o u r c e impedance For Zin2 AB 1<AB causing under reach
causi
protecting the section of the 1
Consider a source E with
constant impedance Zin
current of the relay.
This value is designed for the fault 1 Correspcnds to Zit
AB. Let 1 is the pick up B tor the fault L-L-G I in3in1
the relay reaches upto point For Zin3
line to ground (L-L-G). Thus
to LG (Line to Ground)
then the current changes
the and Distance
the fault varies from L-LG
where the distance is less than AB. This is
AB under ABgA8| causing over reach from relay
relay reach changes to point Bj the reach of the relay changes to point B,. Sue Fig. 3.1.2 Reach of overcurrent relay varies with source impadance
reach. Similariy for a three phase fault,
that the distance AB is more than AB. This is over reach. Thus the reach of the rolaay Review Questions
which is undesirable. This is shown in the Fig. 3.11
changes with the type of the fault 1. Discuss the drarwbacks of overcurrent relays in detail.
Line 2. Explain superiority of distance protection for the protection of tramsmissiot line.
under ype of
Consideration fault changing GTU: Summer-18, Marks 3
B B2 for constant
$ource
impedance 3.2 Introduction to Distance Relays
Fault
Constant In the relays discussed uptil now, the operation of the relays is dependent on the
in Faut
AB< JAB For L-G fault magnitude of the current or voltage of the circuit to be protected. in distance relays, the
Curent
Under reach
operation is dependent on the ratio of the voltage and current, which is expressed
Designed reach of interms of an impedance. Hence basically distance relays are called impedance relays.
L-L-G fault
AB AB The impedance is nothing but an electrical measure of distance along a transmission
Over reach line. The relay operates when the ratio V/I ie. impedance is less than a predetermined
Distance value. As the ratio VI affects the performance of these relays, the relays are also called
from relay
For three phase ratio relays. Dependent on the ratio of V and I there are three types of distance relays
fauit
which are,
Fig. 3.1.1 Reach of overcurrent
relay varies with of fault
type . lmpedance relay which is based on measurement of impedance Z
Now consider that the 2. Reactance relay which is based on measurement of reactance X.
relay reach is designed for the current Io with urce
impedance Zin1 for a particular type of fault. This sou 3, Admittance or Mho relay which is based on measurement of component of
gives the reach of the relay to
point B. If source impedance changes to Zi2 Such that u admittance Y.
Zin2 <
Zinl then the relay each distance whose performance is based on the measurement of
changes upto point Bj causing under reach. If in short, a relay is one
of relay and the point
admittance of ine between the location
such
that Zin3 Zin! then the source
impedance changes to Lin3 impedance, reactance or
C.T Conerally the spring effect is negiected as its effect is dominant at low currents which
generally do not occur in practice. So with Kg = 0,
Fault
i mpedanic
ralay
K v- KP -Kg .. (3.3.2)
knowledge
an up-thrust for
TECHNICAL PUBLICA TIONS
TECHNICAL PUBLICATIONS an yp-thnist for k
Distance Profection of iransmission Line S w i t c h g e a ra n d P r o t e c t i o n
3-7
3-6 ance Protection of Transmission Line
Switchgear and Protection
a diagram called R-X diagram. The diagram is shown in a plane having X-axis as torque
region
R (resistance) while the Y-axis as X (reactance). This plane is called R-X plane. The
impedance Z can be expressed as,
+R
flow is in
one torque shaded a
+X bias, the ircle representing impedance characteristics on R-X diagram shifts. The radius
of circle remains same as V/I but its centre gets shifted from origin. This is shown in the
Line of
maximumm Fig. 3.3.6. By controlling current bias, shift of the circle can be adjusted as per the
Operating torque requirement.
region
Review Questions
Impedance 1. Explain an impedance relay showing its characteristics on R-X diagram
characteristics
90 GTU Summer-13,15,18,Winter-16.20, Marks
2. Derive the torque equation of impedance relay from unicersal torque equation.
+R . How directional feature is provided to impedance relay ? Expiain twith the help of
characteristics.
an
up-thrust for knowledge
*SSIOn Li
Switchgear and Protection
Line Switchgsar and Protection
3-11
Hstancs Proection f 7
is so designed that the maximum torque angle is 90
The directional elernent
K K cos (-1) i.e. K- K2 Zcos (-)
3.4.1 Construction
Adding capacitor, the
torque angle
reactance relay can be of
induction cup type, It i is adjusted as 90,
The structure used for the K K2 Z cos (6-90
coil, polarizing coil and a restraining coil. The scO
polestructure. t has operating
for the reactance relay is
shown in the Fig. 3.4.1. schematic 1.e.
K K2 Z sin
arrangement of coils Z sin 0
Polarizing coil
Consider an impedance triangle shown in the Fig. 3.4.2.
Z sin 6 = X = Reactance
Restraining
coil
Z cos 0 = R = Resistance
X Constant
Fig. 3.4.2
Thus the relay operates on the reactance only. The constant X means a straight line
Operating parallel to X-axis on R-X diagram. For the operation of the relay, the reactance seen by
CC
the relay should be smaller than the reactance for which the relay is designed.
3
3.4.3 Operating Characteristics
The operating characteristics
Fig. 3.4.1 Schematic arrangement of reactance relay of such relay is a straight line
The current I flows from Characteristics
pole 1, through iron core stacking to lower pole 3. The parallel to the X-a>xis i.e R-axis on
-ve torque
winding on pole 4 is fed from voltage V. The operating torque is region
interactiorn of fluxes due to the produced by R-X diagram. All the impedance
windings carrying current coils i.e. interaction of fluxes vectors have their tips lying on
produced by poles 1, 2 and 3. While the restraining
interaction of fhuxes due to the torque is developed due to the straight line
representing +ve torque
Z sine= X =
poles 1, 3 and 4. Hence the operating torque constant reactance. The resistance region
proportional to the square of the current () while the R
+R
the product of V and I (VI). The desired maximum restraining torque proporio
to
is component of the impedance has
no effect on the operation of the
help of RC circuit, shown in the Fig. 3.4.1.
torque angle is obtained wit
relay. It responds only to the
3.4.2 Torque Equation reactance component of the -X
an
up-thrust for knowledgA
Switchgear and Protection
3-12 Distance Protection of Trensmission
Switchgear and Protection
3-13
is located or it has taken place in the adjoining Distance Protection of Transmissie
place in the section where relay
to use a directional relay type of the used with basic impedan section
edance relay the operating torque is obtained by Vand
It is not possible even under normal load conditions
relay n
I element while
because in thai case the relay will operate straining torque is obtained by a voltage element. Thus the
an
at or near unity p.f. conditions.
The reactance relay with direcse restrained directional relay. admittance relay is
system is operating
or admittance relay.
ctional voltage
a
feature is called mho relay r anerating torque is produced by the interaction of the
fluxes due to the windings
h y the poles 1, 2 and 3. While the
restraining
Review Questions
raction of the fluxes due to the
windings
carried
toTque is
produced by the
by the poles 1, 3 and 4.
1. Explain a reactance reiay showing its characteristics on R-X diagram. ThrG the restraining torque is
proportional to the square of the voltage (V ) while the
GTU: Summer-13.14,15.17,18, Winter-14,16,17,18,20, Marks erating torque is
opera roportional to the
product of voltage and current (V). The torque
is adjusted using series tuning circuit.
2. Derive the torqe equation of reactance relay from universal torque equation. angle
B.5.2 Torque Equation
3.5 Mho Relay or Admittance Relay
GTU: Suamer-13,15,17,19,Winter-14,16,17,18.20 The operating torque is proportional to VI while
restraining torque is proportional to
V2. Hence net torque is given by,
Inthe impedance relay a separate unit is required to make it directional while the
same unit cannot be used to make a reactance relay with directional feature. The mho T K VI cos (-) -
K V -Kg
relay is made inherently directional by adding a voltage winding called polarizing
where Ka Control spring effect
winding. This relay works on the measurement of admittance Y 2 6. This relay is also
called angie impedance relay. Generally control spring effect is neglected (K3 =0).
3.5.1 Construction And at balance net torque is also zero.
This relay aiso uses an induction cup type structure. It also has an operating coil, 0 K VI cos (-T) -K2 V
polarizing coil and restraining coil. The schematic arrangement of all the coils is shown K VI cos (-t) =
K, V
in the Fig. 3.5.1.
K cos (-t) =
K2 v2
yiT
i.e. K cos (-t) -
K22
Polarizin9
coll
z- cos - )
Series tuning 2
Operating
COi
And
lhis is the
equation of a circle having diameter K,/K, passing through origin.
this constant
K/K2 is the ohmic setting of this relay.
3.5.3 Operating Characteristics
this relay is a circle passing
s Seen from the torque equation, the characteristics of
through origin with diameter as K/K2
Let Z - Ohmic setting of relay Diarmeter
Restraining coll
Then the ratio ON/OA represents the line protected by mho relay.
ON
OA
100= % of line protected by mho relay x 100 =
80 %
-X
While the ratio OM/OA represents the line protected by impedance reiay.
Fig. 3.5.2 Operating characteristics of mho relay
+X Characteristics of
operate for the fauits occurring in the section AB Scale: 1:1 unit
only and not for the faults occurring in reactance relay
the section AC. This shows that this
relay is inherently directional without any
addiional directional unit required.
The
angle be
t can
adjusted to be 45, 60, 75° and so on. This angle is maximum
torque angle. The setting of 45° is used for high voltage (33 or 11 kV) distribution lines,
the setting of 60° is used for 66 or 132 kV lines Characteristics of
while the setting of 75° is used for
275 and 400 kV lines. mho relay
protected
relay, the maximum portion of the line that can e an impedance relay
x 100 85 %
by impedance relay
1: Unt
Crerecerice
- o f ine potectei
resistance and
unatfectd by the presene of
the arc
hence Characderisics
of mho raay
0 o s amirehEre alons
h g shrt cirst aurs ating n impedarnce of 15
the line that can be
the lone. Foved ir eac toe of distance relay the marimum portion of
BA-5
06 28 and
The circe with O as a centre and OA as the radius represents the haracteristics o asestes
p e a c e relay. Tis is shonn in the Fig. 3.5.4
reatance relay.
-X
The cincde dram wih OA as a diameter represents the characteristics of mho relay
Fig. 35.4
arcng fault is 15 i 0 which is represented as OD. The line
Theimpedane of an
parail to OA draa irom point D. cuting the mho arde at point F and cutting ad henæ
by the presenoe af the arc eissme
ven
The reactance relay is unaffected
pedane irde at point E wah the arC present the % line protectad by the reatane elay is
0
3M neiy
pedance reiay 2 Reactasce reiay
= 5.5
Line protected by impedane re.a
anyuhere along
fault ocurs with an inmpedance of 1.5 +j0 Q Write a note on offset mho relay.
dtstance rebay the maximum portion of the line
that can be protected. 1.
GTU Witer-20. Marks 3
(Ans.: 82 %, 100 % and 85
3.7Effect of Arc Resistance on tance Relays
Relay
GTU: Winter-20 GTU: Sumner-19, Wioter-19 20
3.6 Offset Mho tuuslts like flashover across the line insulator or
a circde passing through the origin. It Can
The faults between the phases
For a mho relay, the haracteristics is not
arc oduces an
introduces resistance Rarc into a fault
arc
produces an
behind the busbar. For this an offset is Such an loop. Hence the
faults and faults lying arc
3.7.1
1Z> Z- nZ| PF Actual impedance upto faut point.
nZ Arcing
The offset mho characteristics are shown Resistance of arc fault. fault
R
Rarce
in the Fig. 3.6.1.
Due to the added arc resistance, the relay Plane impedance
Practically 10 % offset is a typical Offsst If this relay
measures the mpedance Z +R
value of the offset used. For viewed the than set
closeup impedance by relay is more
Fig. 3.7.1 Effect of Rae On impedance
faults, V 0 and for the offset mho relay value Z then the relay fails to operate. Hence relay
Fig. 3.6.1 Offset mho characteristics
when V 0 the condition becomes the relay will under reach and hence will able to protect only a portion of the zone.
11 10 nll. As n< 1, this condition gets satisfied and relay of the distance by which the relay
faults. This is main operates for the closeupP The percentage under reach is defined as the ratio
advantage of the offset mho
relay. under reaches to the reach setting of the relay.
The main applications of offset mho relay Line fault
are, The effect of Rarc on R-X diagram is shown charactenistics
i) Operation for closeup faults. in the
Fig. 3.7.2
Restrain FR Rare
ii) Bushbar zone backup
protection. PQ-Z Setting of relay Radius of circle. Trip R
ii) Carrier blocking protection schemes.
PF Z Impedance up to fault.
iv) Blocking of power
swing. FR
Practically in typical protection scheme,
a
Rarc then PR =
PF + FR =
Z +Rarc
normal mho three units are used. The first two units is more than the Fig. 3.7.2
relays while the third unit is offset are
he arc resistance Rae
mho relay. R, then the total impedance realised by the will fail to
and the relay
the PQ which is the circle radius
De more than
operate.
TECHNICAL PUBLICATIONS up-thrust for
knowtledge
an
up-thrust for knowledge TECHNICAL PUBLICA
TIONS- an
Distance Protection of Transmission Line
S W C g
Distance Protection o
3- 20
Switchgear and Protection
8.8 Effect of
Power wing on Distar ce Relays
ansmission Line
both impedance and mho Fig. 3.8.2. 3.8.2 Power swing characteristics
relay will fail to operate Reactance Fig.
but reactance relay will continue
to operate. Ep t h e n the locus of power swing on R-X diagram is a family ofcircles with
In
general, due R2 Eo
affected
to arc
resistance,relay mho is Mho /R +R
most, impedance relay is affected characteristics 1s a
Parameter and & as variable. For n 1, the power swing
=
electrical centre.
Review Question Fig. 3.7.5 If the
the characteristic zone of the relay long enough,
power swing locus remains in
for which the
1.
Explain the effect of arc resistance the
then the Operates.
relay The operation of the relay depends
on the period
on
performance of plane impedance, reactance and Mho POwer
swing
relays curve influences the relay charactes
GTU Summer-19, Winter-19,20, Marks 4
knowledge
TECHNICAL PUBLICATIONS an up-thrust for
an
up-thrust for knowledge TECHNICAL
PUBLICATIONS
Distance Protection of Transmission Line Switcngeara n d P r d roteu 3- 23
Switchgear and Protection 3-22 Distanca Protedcion of
discuss the construction and
Trensmission ing
occupied by the relay characteristics on the R-X diagram Let us peration of these
Thus the larger the area
types of distance
of relay by the power swing and more are thhe relays.
more are the chances of infiuenang Definite Distance Type impedance
chances of its maloperation. 3.9.1
hence it is least
ion
construction of this relay can be balanced beam
The mho has the least area occupied on the R-X diagram,
relay
The
type or induction
infuenced by the power swing. The impedance relay
has more area occupied on the R-X eam type construction of definite distance dise type. The
balanced
Restraining Operating
R From Coil coil
P.T. I from C.T.
Mho relay Fig. 3.9.1 Definite distance type impedance relay
Moderate area
OCCupied by impedance
Impedance relay consists of a balanced beam pivoted at the central point C. The beam carries the
It
relay (more than mho but
less than reactance relay) armatures of the two electromagnets. The two electromagnets are energized by a current
from C.T. and voltage from P.T., which are located in the circuit to be
Fig. 3.8.3 Effect of power swing on distance relays The protected.
voltage coil acts as restraining coil while the current coil acts as operating coil. The
In general, the mho relay is least affected, the impedance relay is moderately affected beam also carries the moving contacts which can bridge the two fixed contacts of a trip
and the reactance relay is severely affected by the power swing. circuit when the relay operates.
Review Questions Operation: The torque produced by voltage coil is proportional to square of the
voltage (K V) while the torque produced by current coil is proportional to the square
1.Explain with the help of suitable diagrams, the effects of power swing on the performance of ot
(K2 1). Under normal operating conditions, the torque produced by
mho, impedance and reactance relays.
the current
GTU: Summer-19, Winter-19,20, Marks 4 vOltage coil is more than the
torque produced by the curent coil Thus restraining
2 Explain the phenomenon of power swing Orque is more than the operating torque and hence the relay is inoperative. On the
GTU : Summer-18, Marks3 increases. Thus the
e of any tault, the voltage of system decreases and current
3.9 Classification of Distance Relays wnich is impedance also decreases. It falls below preset its value. Ihe forque
-Fixed contacts
requirement.
The Fig. 3.9.2
Characteristics
shows the characteristics of the definite
From
distance type impedance relay. The C.T.
Y-axis represents time for operaion
while the X-axis Tepresents distance inducion tyoa
Overcurrent r9iay
which 15 measured interms of X iouctopn
aisc
impedance between fault position and Distance
the point where relay is installed. Fig. 3.9.2 Characteristics of definite distance
For the entire length AB of the line, impedance relay
the time of operation remains constant, irrespective of distance. But if fault occurs in the
of line which is not protected,
section
shown in the
the operating time becomes suddenly infinite as
Fig. 3.9.3 Distance time impedance relay
Fig. 3.9.2. Towards end of the protected zone, the curve rises gradually.
It consists of an induction
Its advantages are, type overcurrent relay unit which is a curent drven
1.
element. The spindle which is carrying the disc of the element is cornected to a second
Superior to the time graded overcurrent relay. This second spindle carries
2. Number of feeders in series which can be protected is unlimited as the relay timt
spindle with the help of spiral spring coupling
can bridge the trip contacts
when
moving
which
is constant.
Otacts which is nothing but a bridging piece is held in this posthon
elay operates. The trip contacts are normally open and spindle This electromagriet s
The one limitation of these relays is the absence of back up
protection.
a n armature held
against the pole face of an electromagnet.
energized by the voltage of the circuit to be protected.
3.9.2) Distance Time Impedance Relay peration: Under normal conditions, the force
exerted by voltage restraining magnet
Thus the trip contacts
his relay adjusts overcurrent induction element.
automatically, its time or
operation corresponding to the
e of n a n that produced by an
the fault from the distan emain open and the
relay. relay is inoperative. disc 1s
lhe speed or the
disc starts rotating.
Operating time Z Distance E the fault occurs, the induction ettect. Hence the time wheh
neglecting the spring
h n a l to the operating current, varies inversely
With currernt. As
the
disc requires to turn through the given angle
ne
TECHNICAL PUBLICATIONSan up-thrust for knowleadge
PUBLICATIONS an
up-thrust for knowledge
TECHNICAL
Distance Protection or Trensmission Ling S w i t c h g o a ra n d P r o t o c t i o n
3-27
3-226
-
tance Protection of
Switohgear and Proteotion Tra
dransmiasion Line
a force
on
armature so as ull iit away
to pull Review Questions
Z for 75 % reach of
must tall within the Maximum
secondary positive sequence impedance relay torque line
This value of the
distance relays is achieved.
the setting of
setting. This is how,
seguence impedance
seen
by the distance rel
What is the secondary positioe
Example 3.10.1 with 600/5 star connected CTs nd
50 mile, 138 kV ransmission lime provided
fer a
Assume the impedance of tranSmission
line as 0.8 /mile
138000/115 star coimiected P.Ts.
on the positive phase
sequence impedan.
Solution: The distance relay setting depends which operation of a given
and the fault Iocation beyond R
between the position of relay distance is called reach of th
or the corresponding
relay unit stops. The impedance
relay. to secondary value, Modiffed
For converting primary impedance impedanc
ratio V1, C.T. ratio characteristics
Ze 2 P.I.V_C.T.
ratio I P.T. ratio Directional
characteristics
C.I rati0
ZP.T. ratio Fig. 3.11.1 Modified directional impedance relay characteristics
to reach 75 % length.
Secondary positive sequence impedance
= 0.75xZsec 0.75 x 4 - 3 To trip
Circuit
Review Question
Curre
1. Write a note on setting of distance relays. coil
90
Normal line current Positive torque region
I =
section
-
Impedance of healthy
Z +R
be protected, then the directional impedance relay can be used. As directional unit
3.12 Reasons for Inaccuracy of Distance Relay Reach
permits tripping only in one direction, the section AB wil be protected but relay will GTU: Wimter-15,16
not operate for any fault positions between section AC.
Practicallyit is impossible to obtain the exact 100 % reach for distance relay. There
Whether the relay is directional or nondirectional, if its setting is such that tor c Various reasons due to which the reach can not be exact 100 % and there is always
impedance less than Z defined upto point B, the relay should operate then for any fault reach. The operation of the distance
dt amount of uncertainty about the practical
failure of distance relay
positions to the right of point B like point Y the relay will not operate.
cy Deyond the set point distance is called over reach while
wIthin the set distance is called under reach. These reasons are,
The characteristics of the directional distance scheme discussed above can be shown Due to arc
Presence of arc resistance causes under reach of the relay.
R-X
diagram. It is shown in the Fig. 3.11.3. The various sections of the
on
line are the relay is more than the
actual impedance of
represented by straight lines on the R-X diagram. (See Fig. 3.11.3 on next page) t h e impedance seen by outside the
to the point of fault. This may shift point of operation
n e up
For fault at X ZË < Z hence point X is in the operating region and relay will trip. o present operating point causing the under reach.
for any over reach of the relay.
wave causes
fault position along line AB, relay will trip as the entire section AB is in tne 2 The
PEsence of d.c. offset in the fault current
the relay is high.
This
protected zone. For fault at Y, it can be seen that the impedance Z > Due presence of d.c. offset,
the current seen by
Z hence point ie e value. Thus the relay
than its actual
outside the circle hence in the negative
torque region and relay remains ed ne impedance seen by the relay
inoperative tends to over reach.
TECHNICAL up-thrust for knowledge
PUBLICATIONS an up-thnust for knowiedge TECHNICAL PUBLICATIONS an
e t h g a a rB n dF r o l e c t i o n
3-333
3-32 Distarnco Frotectorn
DiS
Of Tranemission Line Diatsnce Prote tior of
100 % oof
line section Trarismisslon Line
3
Covers
der consideratio
The step
T h e iransent response Capacitive Voitage
of
Transtormer (CVT) also tlhe cause
n(BC) (B)
and 50o % of next line section
(CD). Further time (AB), 00 % of next line
the selectivity. Generally delay is
nds is used provided for the
delay of 0.8 seconds
section
over readh of the distance relay. to
mai
3 for the
of line impedance is another
reason of inaccuracy.Th
iracy. This step
3.13.1 s the high speed 3 stepped distance step 3.
4. The ermor in the calculation the conditions. The Fig. protection of trarnsnission ines
is because the line parameters vary
with atmospheric
transformers (C.T.s and P.T.s) used
The errors in the ratios of instrument s
50 % Saye
another major reason Stage 3 of CO 15 % to 80 %
calculated from the A&
Practically inshead of measurement of line parameters, they are
data obtained. This causes errors in line parameter values, causing inaccuracy in
ihe reach of the relay.
Stage 2
Hage 2
Revicw Questions 50 % AB + 50 %h of
Stage 1 of BC
2. Discuss the reusons for inacCuracy of distance relay reach.
GTU: Winter-15, Marks7 0.2
Erriain the reasons for under and over reacit of distance realys. GTU:Winter-16, Marks 7 Stage
AB+BC+50%of
- 75 % 75
CO
3.13 Three Stepped Distance Protection of Transmission Line
A
of AB of BC
GTU: Summer-17,Winter-17,16,19 Fig. 3.13.1 High speed transmission line protection
Practicaly in some cases it is necessary to operate the relay very fast, in about 20 ms,
The impedance relays are used tor sucn protection hence inpedance for step 1 is
to rapidly discorunect the faults. Such relays are called high speed distance relays 0.75 to 0.8 ZAB), the impedance for step 2 is Z2 =(ZAB +0.5 Zgc) while the
The high speed protection of transmission line uses the combination of: npedance for step 3 is Z3 ZAB + ZBc +0.5 ZcD. An additional distance measuring
impe
1) Deinite impedance relay elements used to operate instantaneously when fault unit is installed whose reach is beyond the reach of step 3 which detects the fauit
occurs within the nearest 75 % or more of the section controlled. This unit is called fault detector
instantly. a (FpD) or starter unit.
2) A short definite time lag is introduced to cover the faults in the remaining sections
and for the backup protection on the following section. 3.13.1 Trip Contact Configuration
This protection practically uses three steps using three definite impedance elements The Fig. 3.13.2 shows the trip contact configuration representing three stepped
on each phase. protection scheme.
Step 1: t is set so as to operate within first 75 % to 80 % of the transmission line When there is a fault Fauit detector
section. within the reach setting of
Step 2: It is set to operate for remaining 25 % and 50 % of the next line section. it detects t
Step 3: It is set to operate for faults beyond the 50 % of the next line section. instantaneously and t Trip
Circuit
initiates the timer. FD has supply
The protection provided in step 1 is instantaneous and no intentional time delay is
provided. Normally Open (NO)
contacts, which get closed 2 Timer
For the seiectivity with step 1, intentional time delay is for the step 2
some
provided when it detects the fault.
Generaily delay of 0.4 seconds is provided. Z0.8 2AB
The timer gives two Trip col
Operating time of step 2 - Operating time of step 1 + Intentional time delay of circuit breaker
ZZAB0.5 Zc
outputs. One output is ZZa 2ac05co
time delay
Practically intentional
breaker and travel time of the
is selected based on operating time of cireuit after a time delay of Ti
contact configuration
over
relay. and other is after Fig. 3.13.2 Trip
output a
GTU: Summer-17,
energized through series combination of Z3 and T2. Winter-17,18,19, Marks 4
Questions and Answers
Protection for Doubly Fed Lines 3.14 Short
3.13.2 Three Stepped State the use of distance relays.
The three stepped protection can be provided to the line which are fed from both the Q.1
ends. When the fault ocurs on such a line, then the fault power fows from both the Ans. Distance relays are generaliy used tor primary and backup protection for
and distribution lines.
transmission
sources. Hence the protection scheme including circuit breakers and three stepped
Name the important distance relays.
protection is required at both the ends. Q,2
The Fig. 3.13.3 shows three stepped protection for doubly fed line. The line AB is the 1. Impedance relay 2. Reactance relay 3. Mho relay
Ans.
line under consideration. State the principle of operation of impedance relay.
Q.3
2 Ans. The impedance relay works based on the ratio of voltage V and current I of the
60 % ircuit to be protected. When the fault occurs in the protected zone then the voltage
20 % ofAB 20 %1 drops and current increases. Hence the ratio V/l i.e. impedance reduces to very small
value. When the impedance reduces than its predetermined value then the relay trips
and opens the circuit breaker.
Source Source
Q.4 Why impedance relay is called voltage restrained relay ?
Ans. In an impedance relay there are two elements. One produces a torque
proportional to current while other produces a torque proportional to voltage. The
torque produced by the current element is used as an operating torque while the
d
step 2 which gets protection after Z, ZaR + 50 % ZAE for tne
=
Z3 ZAB +ZAE +50 % ZEF on other side ZcD on one side while of the impedance seen and trips if
which gets Wnich is sensitive to the reactive part
interval l2. protection after delayed the react value is called
a reactance
maloperation.
-Y6
Operating Q.13 System impedance ratio is defined as
torque
region
characteristic a) Zs/ZL b) ZL/Zs c) Zsurge/Z d) Z/Zsurge Ans.: a
GTU: Summes-17, Mark 1
+ve
torque
12
region Q.14 The reach of first step of 3 stepped distance is set at
b) 80 85 %, c) 150 %, d) 60 % Ans.: b
+R a) 100 % of the line section,
GTU Summer-17,Mark 1
2 Z
ve torque Characteristics
region
+ve torque
region
Zsine X =
+R