Sealed Lead-Acid Battery Deep Cycle 727-0427 (12V100Ah) : Specification

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Sealed Lead-Acid Battery

Deep Cycle 727-0427(12V100Ah)

Specification
Cells Per Unit 6 Applications
Voltage Per Unit 12
Capacity 100.0Ah@10hr-rate to 1.80V per cell @250C Electric tools
Weight Approx 30.4kg Mobility
Max. Discharge Current 1200A (5 sec) Lawn mowers
Internal Resistance Approx 4.9mÙ Golf trolleys and golf cart
Portable apparatus, lights and
Discharge : -15 500C (5 1220F)
Operating Temp.Range Charge : 0 400C (32 1040F) instruments;
Storage : -15 400C (5 1040F) Electric toy s
Nominal Operating Temp. Range 25 30C (77 50F ) Emergency lighting
Fire and security alarms
Float charging Voltage 13.5 to 13.8 VDC/unit Average at 25 0C
Portable power
Recommended Maximum Charging 30.0A Wheelchairs
Current Limit
0
Medical equipments.
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25 C
s olar energy
S
The batteries can be stored for more than 6 months
Self Discharge at 25 0C . Self-discharge ratio less than 3% per month
0
at 25 C . Please charge batteries before using.
Terminal T11
A.B.S. (UL94-HB) , Flammability resistance of UL94-V0
Container Material can be available upon request.

Dimensions
Unit: mm Dimension: 330(L) 173(W) 212(H) 220(TH)
Terminal T11
20 [0.787]
M8 [0.315]

7 [0.276]
173 2
220 2
212 2

330 3

Constant Current Discharge Characteristics : A (25 0C ) Amps


F.V/Time 10min 15min 20min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h
1.85V/cell 146.4 123.2 107.7 77.5 61.5 49.9 31.0 24.2 19.6 15.9 13.9 11.3 9.4 5.31
1.80V/cell 187.1 148.9 127.3 91.4 71.6 55.9 33.9 26.0 20.9 17.1 14.9 12.0 10.0 5.36
1.75V/cell 205.6 162.6 136.9 94.9 74.3 58.5 35.1 26.5 21.4 17.5 15.3 12.2 10.1 5.41
1.70V/cell 224.1 173.6 143.9 98.8 77.2 60.4 36.5 27.2 22.0 18.0 15.6 12.4 10.2 5.51
1.65V/cell 241.8 184.6 152.8 104.2 79.2 62.4 37.5 28.4 22.7 18.5 16.0 12.6 10.4 5.58
1.60V/cell 262.5 197.4 162.8 110.0 82.5 64.6 38.8 29.3 23.4 19.1 16.3 12.7 10.5 5.61

Constant Power Discharge Characteristics : W (25 0C ) Watts


F.V/Time 10min 15min 20min 30min 45min 1h 2h 3h 4h 5h 6h 8h 10h 20h
1.85V/cell 273.2 232.3 205.2 148.8 119.0 96.9 60.4 47.2 38.4 31.3 27.4 22.4 18.7 10.6
1.80V/cell 344.4 276.5 238.8 173.5 137.3 107.9 65.6 50.6 40.8 33.5 29.3 23.7 19.8 10.7
1.75V/cell 373.8 299.1 254.8 179.3 141.8 112.5 67.8 51.4 41.6 34.3 30.1 24.1 20.0 10.8
1.70V/cell 401.7 316.9 266.3 185.8 147.0 115.7 70.3 52.7 42.6 35.1 30.7 24.5 20.2 11.0
1.65V/cell 430.4 334.8 281.5 195.2 150.2 119.2 72.1 54.8 44.0 36.0 31.3 24.8 20.6 11.1
1.60V/cell 459.4 353.8 296.8 204.0 155.1 122.5 74.1 56.2 45.1 37.0 31.9 25.0 20.8 11.2
Effect of Temperature on Long Term Float Life Self Discharge Characteristics
100
100C A
Testing condition
Discharging:current 0.17C (FV 1.7V/cell); 80

Remaining Capacity(%)
Charging:current 2.45V/cell,max. 0.25CA; 250C
Charging volume:125% of discharged capacity.
60
B
120
400C 300C
40
100
C
20
80
Capcity(%)

60 0
100% 50% 30% 0 2 4 6 8 10 12
DOD DOD DOD
40 Storage Time(Months)

20
No supplementary charge required
A (Carry out supplementary charge before use if 100% capacity is required.)
0
0 200 400 600 800 1000 1200 1400 1600 1800 Supplementary charge required before use.Optional charging way as below:
1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.
Number of Cycles B
2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.
3.Charged for 8~10hours at limted current 0.05CA .
Avoid this storage period unless regular Top charge.
C Supplementary charge may often fail to recover the full capacity

Cycle Charging Characteristics Discharge Characteristics


Charging Characteristics 0
Temperature 25C
Charge Charging Charged
Volume Current Voltage 13.0
% (A) (V/cell) Charge At 0.1C Amp initial charging current and 2.45V/Cell Constant
o
Voltage at 25C
120
Terminal Voltage(V)

12.0
Charged Volume
100 0.1C 2.5
11.0

2.4 Charge Voltage 0.1C 0.054C


80 0.08C (Constant 2.45v/cell) 0.214C
10.0
0.365C
60 0.06C 2.3
3.8C 2.6C 1.1C 0.646C
After 50% Discharge
9.0
0.04C 2.2
40 After 100% Discharge

Charging Current 8.0


20 0.02C 2.1 (initial at 0.1c Amp)

0C
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20
0 4 8 12 16 20 24 28
min H

Charging Time(hours) Discharge Time

Available Capacity Sub ject to Temperature

Battery Type -20 -10 0 5 10 20 25 30 40 45


AGM 46% 66% 76% 83% 90% 98% 100% 103% 107% 109%
6V&12V
Battery

Discharge Current VS. Discharge Voltage Maintenance & Cautions


Final Discharge
Voltage V/cell 1.80V 1.75V 1.60V Float Service:
Discharge A 0.2C 0.2C A 1.0C A 1.0C It is recommended to check battery/Float voltage each month.
Current (A)
Equalisation charge:

Equalisation charging is recommended once every 3 to 6 months using.


Charge the batteries at least once every six months, Discharge 100% rated capacity.
if they are stored at 25 0C .
Charge 2.35v/cell constant voltage, maximum 0.3CA 24hrs.
Charging Method: Cyclic Service:
Constant Voltage -0.2Cx2h+2.4~2.45V/Cellx24h,Max. Current 0.3CA
Temperature compensation for varying temperatures:
Constant Current -0.2Cx2h+0.1CAx 12h
Fast -0.2Cx2h+0.3CAx4.0h -Charge voltage -5mV/Cell/degC from 25degC norm.

The service life of your battery will be affected by:

-The number of discharge cycles, depth of discharge, ambient

temperature and charging voltage.