Sealed Lead-Acid Battery Deep Cycle 727-0427 (12V100Ah) : Specification
Sealed Lead-Acid Battery Deep Cycle 727-0427 (12V100Ah) : Specification
Sealed Lead-Acid Battery Deep Cycle 727-0427 (12V100Ah) : Specification
Specification
Cells Per Unit 6 Applications
Voltage Per Unit 12
Capacity 100.0Ah@10hr-rate to 1.80V per cell @250C Electric tools
Weight Approx 30.4kg Mobility
Max. Discharge Current 1200A (5 sec) Lawn mowers
Internal Resistance Approx 4.9mÙ Golf trolleys and golf cart
Portable apparatus, lights and
Discharge : -15 500C (5 1220F)
Operating Temp.Range Charge : 0 400C (32 1040F) instruments;
Storage : -15 400C (5 1040F) Electric toy s
Nominal Operating Temp. Range 25 30C (77 50F ) Emergency lighting
Fire and security alarms
Float charging Voltage 13.5 to 13.8 VDC/unit Average at 25 0C
Portable power
Recommended Maximum Charging 30.0A Wheelchairs
Current Limit
0
Medical equipments.
Equalization and Cycle Service 14.4 to 15.0 VDC/unit Average at 25 C
s olar energy
S
The batteries can be stored for more than 6 months
Self Discharge at 25 0C . Self-discharge ratio less than 3% per month
0
at 25 C . Please charge batteries before using.
Terminal T11
A.B.S. (UL94-HB) , Flammability resistance of UL94-V0
Container Material can be available upon request.
Dimensions
Unit: mm Dimension: 330(L) 173(W) 212(H) 220(TH)
Terminal T11
20 [0.787]
M8 [0.315]
7 [0.276]
173 2
220 2
212 2
330 3
Remaining Capacity(%)
Charging:current 2.45V/cell,max. 0.25CA; 250C
Charging volume:125% of discharged capacity.
60
B
120
400C 300C
40
100
C
20
80
Capcity(%)
60 0
100% 50% 30% 0 2 4 6 8 10 12
DOD DOD DOD
40 Storage Time(Months)
20
No supplementary charge required
A (Carry out supplementary charge before use if 100% capacity is required.)
0
0 200 400 600 800 1000 1200 1400 1600 1800 Supplementary charge required before use.Optional charging way as below:
1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.
Number of Cycles B
2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.
3.Charged for 8~10hours at limted current 0.05CA .
Avoid this storage period unless regular Top charge.
C Supplementary charge may often fail to recover the full capacity
12.0
Charged Volume
100 0.1C 2.5
11.0
0C
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20
0 4 8 12 16 20 24 28
min H