plate of the box. The moving part comes in the kit that converts the fixed version into a plug-in
version;
■ WITHDRAWABLE. These have a moving part and a fixed part, equipped with side runners to
Version
Fixed Plug-in Withdrawable
XT1 n n
XT2 n n n
XT3 n n
Plug-in circuit breaker
XT4 n n n
Installing at 50mm/1.97in
Installing at 70mm/2.76in
versions. When withdrawable versions are made, it is essential to order an accessory to apply
to the front of the circuit breaker in order to maintain the IP40 degree of protection over the
Conversion kit for turning a fixed entire isolation run. This accessory can be chosen from:
circuit breaker into the moving – front for lever operating mechanism (FLD); 3
part of a plug-in circuit breaker
– motor operator (MOE);
– direct or extended rotary handle operating mechanisms (RHD or RHE).
If no accessory is indicated, the front for lever operating mechanism (FLD) is automatically
included in the order.
■ Kit for converting the fixed part of plug-in versions into the fixed part of withdrawable
for XT2-XT4. RC Sel four-pole residual current devices for XT2 and XT4 can be converted from
the fixed version into the plug-in version using the special kit.
■ Kit for converting plug-in types into the withdrawable version for RC Sel residual current
devices for XT2-XT4. RC Sel four-pole residual current devices for XT2 and XT4 can be
converted from the plug-in version to the withdrawable version using the special kit, which
comprises a bellows to apply to the front of the residual current device so as to allow it and
the residual current part to be withdrawn when the panel door is closed. This kit can also
be assembled on fixed circuit breakers fitted with the front part for locks or the direct rotary
handle, thus adding to the range of uses for residual current devices.
In the plug-in to withdrawable conversion kit, there is also a 6-pin connector to be applied onto
the right side of the circuit breaker to facilitate disconnecting the auxiliary circuits connected to
Conversion kit for turning a fixed
part of plug-in version into the the residual current device.
fixed part of a withdrawable This kit contains also the shunt opening release of the residual current device dedicated to the
version withdrawable version, which is fitted with a connector for the fixed part and the moving part.
Plug-in version
+ + =
3
Withdrawable version
1st solution
+ + + =
2nd solution
+ + + + =
Fixed part Conversion kit for turning a Fixed Conversion kit for turning a Frontal Withdrawable
of plug-in fixed part of plug-in version circuit breaker fixed circuit breaker into the accessory(1) circuit breaker
into the fixed part of a moving part of a withdrawable
withdrawable version circuit breaker
(1)
Frontal accessory is mandatory. If not specified in the order, the FLD is supplied automatically
Connection terminals
Connection terminals allow the circuit breaker to be connected to the system in the way best
suited to the installation requirements. By and large, they consist of front terminals for connecting
cables or busbar directly from the front of the circuit breaker.
Where possible, the terminals have laser markings on the surface to indicate the tightening
torques for the correct isolation of cables and bars.
Fixed version
Standard SACE Tmax XT circuit breakers for UL and CSA are supplied with front terminals (F).
However, they can be fitted with the following types of terminal as accessories thanks to the
special kits:
■ extended front (EF);
■ extended spread front (ES);
■ front for copper/aluminum cables (FCCuAI), for XT3 and XT4 sizes;
■ front for copper cables (FCCu);
■ multicable for copper cable (MC);
■ for flexible busbar (FB);
■ rear oriented (R) 1).
For XT1 and XT3 sizes, the use of non-insulated busbar with Ue ≤ 480V involves the mandatory
assembly of terminal-covers HTC.
1)
IEC only
The adapter mimics the terminal zone of the fixed circuit breaker. This means that fixed parts can
also be equipped with the same terminal covers and phase separators as those used for fixed
circuit breakers.
H3 H1 H2
Installing at 50mm/1.97in
Installing at 70mm/2.76in
Front extended terminal - EF EF terminal with cable lug EF terminal with busbar
W Width F Fixed
H Hole height P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request
3 XT3 F-P 30/1.181 4/0.157 10.5/0.413 30/1.181 10.5/0.413 M8 8/70.8 M10 18/159.3 – – – – – S
XT4 F-P-W 30/1.181 10/0.394 10.5/0.413 30/1.181 10.5/0.413 M8 8/70.8 M10 18/159.3 – – – – – S
(1)
UL Listed
Front extended spread terminal ES terminal with cable ES terminal with busbar
- ES lug
FCCu terminal FCCu terminal with cable FCCu terminal with busbar
W Width F Fixed
H Hole heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request
Internal FCCuAl terminal for Internal FCCuAl terminal for FCCuAl internal terminal
copper/aluminum cables copper and aluminum cable with cable
with take-up of auxiliary
voltage
W Width F Fixed
H Hole heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request
Rear horizontal terminals (R) R terminal with horizontal busbar R terminal with vertical busbar
W Width F Fixed
H Hole heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request
W Width F Fixed
H Hole heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request
Phase barriers Phase barrier - medium [mm/in] 100/3.94 100/3.94 100/3.94 100/3.94
Phase barrier - high [mm/in] 200/7.87 200/7.87 200/7.87 200/7.87
Rear phase barrier for FP [mm/in] 90/3.54 90/3.54 90/3.54 90/3.54
(1)
IEC rear terminals only
the front;
■ extended (RHE): installed on the panel door. Allows the circuit breaker to be operated by
means of a rod which acts on a base installed on the front of the circuit breaker;
■ side, for lateral left (RHS-L) and lateral right (RHS-R). Allows operation from the side by means
of a shaft which acts on the base installed on the front of the circuit breaker.
A long handle grip (LH) which can be combined with the extended handle (RHE) and with the side
Direct rotary handle (RHD) Extended rotary handle (RHE) (LH) Long handle (RHS) Side rotary handle
– rotary handle on compartment door with normal standard handgrip (RHE_H, RHE_H LH)
or emergency handgrip (RHE_H_EM, RHE_H_EM LH); 3
– 60.5mm/2.38" and 170.5mm/6.71" rod (RHE_S). The minimum and maximum distances
between the fixing plate and the door are 60.5mm/2.38" and 170.5mm/6.71";
– base to fix to the circuit base (RHE_B).
Using the rotary handle is an alternative to the motor operator and to all accessories of the front type.
The rotary handles can be locked by means of a vast range of key locks and padlocks (consult
the “Locks” section of this chapter).
The direct and extended rotary operating mechanisms allow early contacts to be used on
closing in order to supply the undervoltage release in advance of the circuit breaker's closing
(consult the “Early auxiliary contacts” section of this chapter).
IP54 Protection
A device that can be applied onto the transmitted rotary and lateral handle allowing IP54 degree of
protection(G.1.11) to be achieved.
IP54 protection
Locks
Padlocks or key locks prevent the circuit breaker from being closed and/or opened. They can be fitted:
■ directly on the front of the circuit breaker;
■ on the rotary handle operating mechanism;
pered with.
All locks that hold the circuit breaker in the open position ensure circuit isolation in accordance with the
IEC 60947-2 Standard. In the closed position, the locks do not prevent the mechanism from releasing
after a fault or remote control.
Fixed padlock in open/ Circuit breaker with Circuit breaker with fixed Circuit breaker with fixed
closed position removable padlock in open padlock in open position padlock in open/close
position position
Removable padlock
in open position
RHD with key lock RHE with key lock FLD with key lock
MOD with key lock MOE with key lock Withdrawable fixed part
with key lock/padlock
(1)
On the transmitted rotary handle (RHE), the lock is mounted on the base. The key lock is not available on the lateral handle (RHS).
(2)
Only for MOE and MOE-E.
(3)
Applied to the cover of the circuit breakers on a level with the regulator of the thermal element of thermal magnetic release TMD to prevent it from being tampered with.
(4)
This function can be totally inhibited by the customer when the handle is assembled by means of a simple operation that can be reversed if needed.
Moreover, if the door lock function is not disabled by the customer during the assembly phase, the door lock can be temporarily deactivated with a tool in exceptional cases,
so that the door can be opened without opening the circuit breaker .
(5)
Incompatible with electrical accessories mounted in the third pole.
+ =
current releases.
XT1-XT3
with standard flange
Service releases
Shunt opening release (SOR). Allows the circuit breaker to be opened by means of a non-
permanent electrical control. Release operation is ensured for voltages between 70% and 110%
Cabled SOR - UVR of the rated power supply voltage Un, in both alternating and direct current. The SOR is equipped
with a built-in limit contact to shut off the power supply in the open position with the relay tripped.
A remote controlled emergency opening command can be created by connecting an opening
button to the SOR.
Undervoltage release (UVR). Allows the circuit breaker to open when the release is subjected
to either a power failure or a voltage drop. Opening is ensured when the voltage is between 70%
and 35% of the rated power supply Un. After tripping, the circuit breaker can be closed again
Cabled SOR - UVR
if the voltage exceeds 85% of Un. When the undervoltage release is not energized, neither the
for withdrawable circuit breaker
circuit breaker nor the main contacts can be closed. A remote controlled emergency opening
command can be created by connecting an opening button to the UVR.
– for fixed/plug-in circuit breakers with cables from (1.5 mm2/14 AWG in section). 3
In circuit breakers:
■ three-pole: either one SOR or one UVR can be installed in the slot on the left of the operating
lever;
■ four-pole: two service releases can be installed at the same time by using the third and fourth
poles. If the circuit breaker is the withdrawable type, the connector for the fourth pole must be
ordered to be able to install an SOR or UVR in the fourth pole.
Auxiliary contacts
Contacts which allow information about the operating state of the circuit breaker to be routed
outside the circuit breaker. The following information is available:
■ open/closed: indication of the position of the circuit breaker power contacts (Q);
■ trip: signaling circuit breaker opening due to the current release tripping (owing to overload or
Changeover of auxiliary contacts Q (open/closed), SY (relay tripped) and S51 (trip unit tripping)
Normal sequence CB Open Q=12 SY=96 S51=06
CB Closed Q=14 SY=96 S51=06
Trip sequence CB Open Q=12 SY=96 S51=06
(trip caused by:
CB Closed Q=14 SY=96 S51=06
SOR, UVR, trip test)
CB Trips Q=12 SY=98 S51=06
CB Resets Q=12 SY=96 S51=06
Trip sequence CB Open Q=12 SY=96 S51=06
(trip caused by trip unit)
CB Closed Q=14 SY=96 S51=06
CB Trips Q=12 SY=98 S51=08
CB Resets Q=12 SY=96 S51=06
– for fixed/plug-in circuit breakers with cables from 0.5 up to 1.5 mm2 in section.
Auxiliary contacts are supplied for each circuit breaker in the SACE XT family in various
combinations, as shown in the table. The following items can be ordered to make installation even
more flexible:
■ a non-cabled auxiliary contact can create different signals (Q or SY) based on its position
2Q
2Q
3Q 1 SY
XT1 3Q 1 SY
on Left
on Left
3Q 3Q
1 SY 3Q 1 SY
XT3 3Q
on Left on Left
2 SY 2 SY
2Q 2Q
3Q 3Q
on Left on Left
XT2
XT4 1 S51 1 S51
or 1 Q or 1 Q
101
S75I
(racked-in)
S57I=104 S75I=102
104 102 142 144 Withdrawable circuit breaker with racked-in/racked-out contacts
101 141
S75I S75E
(racked-in) (racked-out)
S75I=102 S75I=102 S75I=104
S75E=144 S75E=142 S75E=142
Motor operators
Devices that allow circuit breaker opening and closing to be controlled:
■ in the remote mode, by means of electric controls;
■ locally, directly from the front, by means of special mechanisms.
Circuit breaker
Position for key lock status signal ON-OFF
(key lock is not supplied)
The direct action motor control is available for XT1 and XT3 and is supplied:
■ complete with 1m long cables;
■ with flange, to replace the standard one supplied with the circuit breaker;
■ with padlock device, only removable when the motor is in the open position. The padlock
routed outside;
■ (on request) the motor operator can be fitted with a key lock (consult the "Locks" section of
this chapter).
Operating principles:
■ a selector on the front of the MOD is used for selecting the operating mode:
– AUTO: when the selector is in this position, circuit breaker closing can only take place
remotely by means of an electric impulse, whereas opening is allowed both remotely and
from the front of the motor;
– MANUAL: when the selector is in this position, the circuit breaker can only be opened/
closed from the front of the motor by means of the corresponding lever housed in a slot
3 made in the motor itself;
■ operation of the motor operator via remote control is also ensured by permanent electrical
opening/closing impulses;
■ the resetting modes shown in the diagrams below depend on the reset wiring diagram chosen
by the customer (consult the reset wiring diagrams in the “Electric diagrams”) chapter.
Close I: ON Close I: ON
SOR / UVR / SA SOR / UVR / SA
release tripping release tripping
move the move the OFF ON
Close O: OFF lever to lever to Close O: OFF pushbutton pushbutton
Reset Close remotely remotely
Move the lever OFF pushbutton
to Reset remotely
AUTO-MANUAL-LOCKED selector
Stored energy motor operators
(MOE) Circuit breaker status signal ON-OFF
Slot for padlock device
The MOE or MOE-E stored energy motor operator is available for XT2 and XT4 and is supplied:
■ complete with 1m long cables;
■ complete with connector for the fixed part and moving part of withdrawable devices. If the
motor operator is used with fixed or plug-in circuit breakers, the connector can be easily
removed;
■ with flange, to use instead of the standard one supplied with the circuit breaker;
■ with padlock device, only removable when the motor is in the open position. The padlock
this chapter);
■ (on request) the motor operator can be equipped with a lock to safeguard against manual
Operating principles: 3
■ a selector on the front of the MOE, is used for selecting the operating mode:
– AUTO: when the selector is in this position, the pushbuttons on the front of the motor are
locked. Circuit breaker closing can only take place remotely by means of an electric impulse,
whereas opening is allowed both remotely and from the front of the motor;
– MANUAL: the circuit breaker can only be opened/closed from the front of the motor using
the appropriate pushbuttons;
– LOCKED: when the selector is in this position, the circuit breaker is in the open position.
The padlock device can be withdrawn and the motor locked in the open position;
■ operation of the motor operator via remote control is also ensured by permanent electrical
opening/closing impulses. Once an opening command has been given, the next closing
command (permanent) is taken over by the motor operator once opening has been completed.
Likewise, an opening command is taken over once the previous closing operation has been
completed;
■ the resetting modes shown in the diagrams below depend on the reset wiring diagram chosen
by the customer (consult the reset wiring diagrams in the “Electric diagrams" chapter).
If the electronic trip unit (Ekip LSI, Ekip LSIG or Ekip E-LSIG) with Ekip Com module is used,
motor operator MOE-E can be used instead of motor operator MOE.
MOE-E allows the digital signals from the monitoring system to be used by means of the release
and Ekip Com contacts and to be converted into power signals for operating the motor operator.
All the features described above for the MOE motor operator are also valid for the MOE-E version.
Changeover of auxiliary contacts Q (open/closed), SY (relay-tripped) and S51 (trip unit tripping)
Circuit breaker with MOE (MANUAL Mode)
Normal sequence CB Closed Q=14 SY=96 S51=06
By pressing the Red pushbutton, the CB trips Q=12 SY=98 S51=06
Charging the springs, CB opens Q=12 SY=96 S51=06
By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
Trip sequence CB Closed Q=14 SY=96 S51=06
3 (trip caused by:
CB trips Q=12 SY=98 S51=06
- SOR,
- UVR, Charging the springs, CB opens Q=12 SY=96 S51=06
- trip test) By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
Trip sequence CB Closed Q=14 SY=96 S51=06
(trip caused by
CB trips Q=12 SY=98 S51=08
trip unit)
Charging the springs, CB opens Q=12 SY=96 S51=06
By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
Circuit breaker with MOE (AUTO Mode)
Normal sequence CB Closed Q=14 SY=96 S51=06
By pressing the Opening pushbutton remotely, Q=12 SY=98 S51=06
the CB opens
By pressing the Closing pushbutton remotely, Q=14 SY=96 S51=06
the CB Closes
Trip sequence CB Closed Q=14 SY=96 S51=06
(trip caused by: CB trips Q=12 SY=98 S51=06
- SOR,
- UVR, By pressing the Opening pushbutton remotely, Q=12 SY=96 S51=06
- trip test) the CB opens
By pressing the Closing pushbutton remotely, Q=14 SY=96 S51=06
the CB Closes
Trip sequence CB Closed Q=14 SY=96 S51=06
(trip caused by
CB trips Q=12 SY=98 S51=08
trip unit)
By pressing the Opening pushbutton remotely, Q=12 SY=96 S51=06
the CB opens
By pressing the Closing pushbutton remotely, Q=14 SY=96 S51=06
the CB Closes
Plug and socket adapters installed on the rear of the circuit breaker and in the fixed part
Only for the plug-in versions of Tmax XT2 and XT4 circuit breakers can the auxiliary circuits be
automatically disconnected. This is accomplished by an adapter installed on the rear of the circuit
breaker and in the fixed part of the plug-in version.
The 12-PIN connector can only be used with accessories that function at a voltage not exceeding
250V AC/DC. Cables are connected to/disconnected from the connector quickly and easily with
no special tools required. Wiring is to be carried out by the customer.
Plug and socket
adapter in the fixed part
The table shows all the residual current devices that can be used with the Tmax XT family of
circuit breakers:
cated opening solenoid (supplied with the residual current release and also available as a spare
part) which must be housed in the corresponding slot in the third pole left of the operating lever;
■ do not need an auxiliary supply; they are powered directly from the mains;
■ can be supplied either from above or below;
■ functionality is ensured even with a single phase plus neutral or just two live phases and in the
presence of pulsating unidirectional currents with direct components (minimum auxiliary voltage
PHASE-NEUTRAL 85 Vrms);
■ all possible connection combinations are permitted, as long as the neutral connection to the first
pole on the left in the four-pole version is ensured.
Power-on LED
Current setting
Alarm and pre-alarm
signal LED
Time of non-trip setting
Magnetic indicator of
residual current trip Test pushbutton
Power-on LED
Current setting
Test pushbutton
Disconnection device
for the insulation test
3 Power-on LED
Disconnection device
for insulation test
With RC Inst and RC Sel residual current release for XT1 - XT3, available only in Fixed version, it
is possible to have rear terminal connection, by ordering RC Rear terminals 4p kits.
Current setting
Power-on LED
– by ordering the kit for converting the residual current release from the fixed to the plug-in version;
■ into the withdrawable type:
– by ordering the kit for converting the residual current release from the plug-in to the
withdrawable version. This kit contains the shunt opening release of the withdrawable
residual current device to replace the one supplied with the fixed version. The shunt opening 3
release of the withdrawable residual current device contains connectors for both the moving
and fixed parts. The 160A frame with residual current withdrawable breaker can be used up
to a maximum current of 135A; the 250A frame can be used up to 210A.
With the RC Sel residual current release for XT2-XT4, it is possible to use the same terminals for the
fixed circuit breaker and for the fixed parts of plug-in and withdrawable circuit breakers.
Current setting
Power-on LED
Test pushbutton
LED signaling alarm
and pre-alarm
The RC B Type residual current release, to be used in conjunction with the XT3 circuit breaker,
has the following features:
■ it complies with type B operation, which guarantees sensitivity to residual fault currents with
alternating, pulsating alternating and direct current components (IEC 60947-1, IEC 60947-2
Annex B, IEC 60755);
■ the maximum frequency band of the residual fault current can be selected (3 steps: 400
- 700 - 1000Hz). The residual current device can therefore be adapted to suit various
industrial installation requirements according to the prospective fault frequencies generated
on the load side of the release. Typical installations that may require different frequency
thresholds from the standard ones (50 - 60Hz) are welding systems for the automobile
industry (1000Hz), the textile industry (700Hz), airports and three-phase drives (400Hz)
■ UL Listed.
contacts.
Thanks to the 115-230...415V external auxiliary power supply, the RCQ020 panel-type residual
current device is able to detect current leakage from 30mA to 30A and to act with a trip time that
can be adjusted from instantaneous to delayed by 5s. The opening mechanism is the indirect
action type and acts on the circuit breaker release mechanism by means of the shunt opening or
undervoltage release of the circuit breaker itself.
The opening command to the circuit breaker (Trip delay) can be temporarily inhibited, and the
circuit breaker can be opened by remote control by means of the RCQ020 device.
The following equipment must be requested when ordering:
■ the RCQ020 device;
■ an opening coil (SOR) or an undervoltage release (UVR) of the circuit breaker to be housed in
the corresponding slot in the left pole of the circuit breaker itself;
■ a closed toroid with a diameter from 60mm to 185mm that can be used for cables and
busbars.
3/34 SACE Tmax XT UL/CSA | US Technical Catalog
Signals available:
■ LED to indicate the residual current device's status (supplied or not supplied). RCQ02 is
equipped with a positive safety function that commands automatic circuit breaker opening in
the absence of auxiliary voltage;
■ LED for signaling faults;
■ LED for signaling tripping of the residual current device;
■ pre-alarm/alarm/trip electrical signals.
Ekip Display
This unit can be installed on the front of the solid state trip unit to show current values, alarms
and protection/communication parameter programming.
Display
Power-on LED
Fixing device
Main features:
■ installation: Ekip Display can easily be installed on the front of the Ekip LSI, Ekip LSIG and Ekip
E-LSIG electronic trip units. It is connected by means of the test connector on the front of the
trip unit. Installation is simple and reliable thanks to a specially designed mechanism. It also
provides a practical way of fastening the accessories to the circuit breaker in order to prevent
undesired access to the dip-switches. Installation can be carried out under any conditions, even
with the door closed and the electronic trip unit already on and functioning;
■ functions: Ekip Display has four buttons for browsing through the menus. It functions in the
self-supply mode starting from a current of I>0.2xIn circulating through at least one phase.
Backlighting is activated in the presence of higher loads, making displayed information more
legible. Backlighting comes on in self-supply for a current I>0.4xIn and is always on when there
is electronic trip unit auxiliary power supply.
Ekip Display:
– shows the current, voltage, power and energy values;
– shows the settings of the protection functions in Amperes or in In;
– shows the protection that caused the release to trip and the fault current (only when there is
24V external voltage or the Ekip TT unit);
– allows the trip thresholds of the trip unit to be programmed and the communication
parameters to be set on bus system;
■ compatibility: Ekip Display can be fitted even when front accessories, such as the motor,
direct and transmitted rotary handles etc. are already installed. It's possible to use Ekip TT
or Ekip T&P without removing Ekip Display. It's not possible to use Ekip Displaywith the
withdrawable version of circuit breaker.
L, S, I, G protection LED
Power-on LED
3
Ekip TT or Ekip Fixing device
T&P connector
Main features:
■ installation: Ekip LED Meter can be easily installed on the front of Ekip LSI, Ekip LSIG and
Ekip E-LSIG electronic trip units. It is connected by means of the test connector on the front
of the release. Installation is simple and reliable thanks to a specially designed mechanism. It
also provides a practical way of fastening accessories to the circuit breaker in order to prevent
undesired access to dip-switches. Installation can be carried out under any conditions, even
with the door closed and the electronic trip unit already on and functioning;
■ functions: Ekip LED Meter provides an accurate indication of the value of the current
circulating in the trip unit. It does this by means of Its. Its different colors allow the normal
operation, prealarm and alarm states of the circuit breaker to be recognized at a glance. It
functions in self-supply mode from a current of I>0.2xIn circulating through at least one phase
or when electronic trip unit’s auxiliary power is available;
■ compatibility: the Ekip LED Meter can also be fitted with front accessories, such as the motor,
direct and transmitted rotary handles. Ekip TT or Ekip T&P can be used without removing Ekip
LED Meter. Ekip LED Meter cannot be used when the breaker is in the withdrawable version.
breakers in the fixed/plug-in and withdrawable version equipped with an Ekip LSI or an Ekip
LSIG electronic trip unit. The sensor must be connected to the release with the specific
connector, which must be ordered separately.
Connection accessories
Devices that allow the electronic trip unit to be connected to external plant units or components.
These connectors are available for the circuit breakers in fixed, plug-in and withdrawable versions.
The connector for the auxiliary power supply is inserted inside the right-hand slot of the circuit
breaker, and occupies the space of two due auxiliary contacts. To check compatibility with the
Connector for 24V
auxiliary contacts, consult the compatibility tables in this chapter.
3 Alarm LED
Display
Display pushbutton
Main features:
■ installation: HMI030 can be fitted into the hole in the door using the automatic click-in
method. In situations where mechanical stress is particularly intense, it can also be installed
by using the special clips supplied. It must be connected directly to the Ekip LSI, Ekip LSIG
or Ekip E-LSIG protection trip unit with Ekip Com via the serial communication line. HMI030
requires a 24V DC power supply;
■ functions: HMI030 consists of a graphic display and 4 buttons for browsing through the
– Modbus
– Local Bus.
Connecting Ekip LSI, Ekip LSIG or Ekip E-LSIG to the Local Bus allows the Modbus line to be
connected to a different communication network.
Consult the "Electrical diagrams" chapter for further details about wiring.
combination with an MOE-E motor operator, it can open/close the circuit breaker remotely.
Combined with a trip unit fitted with a communication device (Ekip LSI, Ekip LSIG or Ekip
E-LSIG), the Ekip Com module allows the trip unit’s connection to a Modbus network. This
allows protections to be programmed, measurements to be taken and alarms to be sent when
it’s connected to a control and/or monitoring system. Connected to the HMI030 interface,
these data can be displayed directly on the front of the switchboard.
For further details on the communication systems which can be made by means of the Ekip Com
module, refer to the “Communication systems” section in the “Ranges” chapter.
Ekip Com
Circuit breaker 3p Circuit breaker 4p
Ekip Connect
Installation and diagnosis software for ABB SACE products with Modbus RTU communication.
The software can be used during the commissioning stage, or for troubleshooting in an up and
running communication network.
Ekip Connect automatically scans the RS-485 bus, detects all the connected devices and checks
their configuration, all possible addresses, parity and baud rate combinations. A simple click over
SCAN will highlight:
■ devices that fail to respond;
■ configuration errors;
■ incorrect addresses and parity;
■ any wiring errors (with the SACE electronic trip unit);
Ekip T&P
Ekip T&P is a kit used to monitor, configure and test electronic protection trip units.
The kit includes:
■ Ekip T&P unit;
■ Ekip TT unit;
■ Adapters for Emax and Tmax trip units;
■ USB cable for connecting the Ekip T&P unit to the electronic trip unit;
■ CD for installing Ekip Connect and the Ekip T&P driver. 3
The Ekip T&P unit is connected on one side to the USB port of a PC and on the other, by means
Ekip T&P
of a cable provided, to the protection trip unit of the SACE Tmax XT series.
The Ekip T&P unit allows automatic, manual and trip tests of the device it is connected to. These
functions are managed by means of the Ekip T&P Interface which can only be activated directly
by the Ekip Connect when the Ekip T&P is present and connected to the PC.
Ekip TT
The Ekip TT accessory is supplied with a special connector to facilitate connection between the
electronic trip unit and the Ekip TT unit. The kit also includes an adapter that allows the Ekip TT
unit to be used with the current Tmax breakers.
Ekip TT is a device which allows:
■ verification that the electronic trip unit's opening solenoid and the circuit breaker's trip
The ATS (Automatic Transfer Switch) is the network-generator transfer unit used in installations
where switching the main power line to an emergency one is required, in order to ensure power
supply to the loads in the case of anomalies in the main line.
The unit is able to manage the entire transfer procedure automatically, and prepares the
commands for carrying out the procedure manually as well.
In the case of an anomaly in the main line voltage, in accordance with the parameters set by the
user, the opening of the circuit breaker of the main line, the starting of the generator set (when
3 ATS021 provided) and the closing of the emergency line are performed. In the same way, in the case of
the main line returning, the procedure of reverse transfer is controlled automatically.
The new generation of ATS (ATS021 and ATS022) offers the most advanced and complete
solutions to ensure service continuity. The ATS021 and ATS022 can both be used with all the
circuit breakers in the SACE Tmax XT family and with the switch-disconnectors.
ATS021 and ATS022 devices have been designed to operate on self-supply. The ATS022 unit
also prepares the connection for auxiliary power supply, allowing additional functions to be used.
ATS021 and ATS022 devices control both of the the power supply lines and analyze:
■ phase unbalance;
■ frequency unbalance;
■ phase loss.
Apart from its standard control functions, the ATS022 unit makes it possible to:
■ select the priority line;
ATS022
■ controlling a third circuit breaker;
■ incorporate it into a monitoring system with Modbus communication (auxiliary power supply is
needed);
■ read/set parameters and show measurements and alarms on a graphic display.
Typical applications include: power supply to UPS (Uninterrupted Power Supply) units, operating
rooms and primary hospital services, emergency power supply for civil buildings, airports, hotels,
data banks and telecommunication systems, power supply of industrial lines for continuous
processes.
For correct configuration, each circuit breaker connected to the ATS021 or ATS022 must be fitted
with the following accessories:
■ mechanical interlock;
■ motorized control of opening and closing;
■ key lock against purely manual operation for the motor operator;
■ contact for signaling the status (open/closed) and contact for tripped;
■ contact for racked-in (in the case of a withdrawable version circuit breaker).
ATS021 ATS022
General
Auxiliary Power Supply Not Required Not Required
(24-110V DC is required only for Modbus
dialog and 16 2/3 Hz system)
Rated Voltage, Un [VAC] Max 480 Max 480
Frequency [Hz] 50, 60 16 2/3, 50, 60, 400
Dimensions (HxLxD) [mm] 96x144x170 96x144x170
3
Type of installation Door mounting Door mounting
DIN-rail mounting DIN-rail mounting
Operating Mode Auto/Manual Auto/Manual
Features
Monitoring of the Normal and Emergency lines n n
Controlling CBs of the Normal and Emergency lines n n
Generator set startup n n
Generator set shutdown with adjustable delay n n
Bus-tie – n
No-priority Line – n
Modbus RS485 – n
Display – n
Ambient conditions
Operating temperature -20…+60 °C -20…+60 °C
Humidity 5% - 90% without condensation 5% - 90% without condensation
Align flush left thresholds
Minimum voltage -30%…-5%Un -30%…-5%Un
Maximum voltage +5%…+30%Un +5%…+30%Un
Fixed frequency thresholds -10%…+10%fn -10%…+10%fn
Test
Test Mode n n
Compliance with standards
Electronic equipment for use in power installations EN-IEC 50178 EN-IEC 50178
Electromagnetic compatibility EN 50081-2 EN 50081-2
EN 50082-2 EN 50082-2
Environmental conditions IEC 68-2-1 IEC 68-2-1
IEC 68-2-2 IEC 68-2-2
IEC 68-2-3 IEC 68-2-3
3p
Check whether the different devices are compatible/incompatible with each other when ordering
accessories. The following table provides a simple check between:
■ mechanical accessories, accessories for electronic trip units and motors;
■ internal electrical accessories.
To better understand the abbreviations used to identify the accessories, refer to the “Symbols”
paragraph in chapter 8, “Glossary”.
3Q sx 3p ✔ ✔
SOR 4p ✔ ✔ ✔ ✔
UVR 4p ✔ ✔ ✔ ✔
.....
Ekip Display ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Ekip LED Meter ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SOR/PS-SOR/UVR/3 Form C/Q L ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
1 Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
2/Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (1)
✔ ✔ ✔
3 Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (2)
✔ ✔ ✔
✔ Compatibility (1)
Not valid for XT1 (2)
Not valid for XT3
3 Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
KLC on CB ✔ ✔ ✔ ✔ ✔ ✔
MOD ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (1)
✔ Compatibility (1)
Not valid for XT1
3 3Q 2SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
2Q 2SY S51 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
400V 2Q ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
400V 1Q 1SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Ekip Com ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
24V ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
NE ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
MOE ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔(1) ✔ ✔ ✔ ✔ ✔
MOE-E ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔(1) ✔ ✔ ✔ ✔ ✔
AUX-MOE ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (1)
✔ (1)
✔ ✔ ✔
AUE ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SOR 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
UVR 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SA ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SOR 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
UVR 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
✔ Compatibility AUX-MOE always supplied with MOE and MOE-E
(1)
Conversion kit of the circuit breaker from fixed into moving part of plug-in
XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
P MP kit KXT1PMP-3 KXT1PMP-4 KXT2PMP-3 KXT2PMP-4 KXT3PMP-3 – KXT4PMP-3 KXT4PMP-4
Conversion kit
Conversion kit of the circuit breaker from fixed into moving part of withdrawable
XT2 XT4
Type 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number
W MP kit KXT2WMP-3 KXT2WMP-4 KXT4WMP-3 KXT4WMP-4
7
Conversion
kit for turning Conversion kit of RC Sel from plug-in to withdrawable (1)
a fixed circuit XT2 XT4
breaker into the Type 4P 4P
moving part of Catalog number Catalog number
a plug-in circuit W MP RC Sel 4P kit KXT2WFPEF-4 KXT4EWMPRC-4
breaker (1)
IEC rated only.
Service releases
Shunt opening trip - SOR
XT1, XT2, XT3, XT4 XT2, XT4
Type Fixed/plug-in Withdrawable
Uncabled version Catalog number Catalog number
SOR 12V DC KXTASORA –
SOR uncabled SOR 24-30V AC/DC KXTASORB –
SOR 48-60V AC/DC KXTASORC –
SOR 110-127V AC/110-125V DC KXTASORD –
SOR 220-240V AC/220-250V DC KXTASORE –
SOR 380-440V AC KXTASORF –
SOR 480-525V AC KXTASORG –
Cabled version Catalog number Catalog number
SOR-C 12V DC KXTASORCFPA KXTCSORCWA
SOR cabled SOR-C 24-30V AC/DC KXTASORCFPB KXTCSORCWB
SOR-C 48-60V AC/DC KXTASORCFPC KXTCSORCWC
SOR-C 110-127V AC/110-125V DC KXTASORCFPD KXTCSORCWD
SOR-C 220-240V AC/220-250V DC KXTASORCFPE KXTCSORCWE
SOR-C 380-440V AC KXTASORCFPF KXTCSORCWF
SOR-C 480-525V AC KXTASORCFPG KXTCSORCWG
7
Undervoltage release-UVR
XT1, XT2, XT3, XT4 XT2, XT4
Type Fixed/plug-in Withdrawable
Uncabled version Catalog number Catalog number
UVR 24-30V AC/DC KXTAUVR1 –
UVR uncabled UVR 48V AC/DC KXTAUVR2 –
UVR 60V AC/DC KXTAUVR3 –
UVR 110-127V AC/110-125V DC KXTAUVR4 –
UVR 220-240V AC/220-250V DC KXTAUVR5 –
UVR 380-440V AC KXTAUVR6 –
UVR 480-525V AC KXTAUVR7 –
Cabled version Catalog number Catalog number
UVR-C 24-30V AC/DC KXTAUVRCFP1 KXTCUVRCW1
UVR-C 48V AC/DC KXTAUVRCFP2 KXTCUVRCW2
UVR cabled
UVR-C 60V AC/DC KXTAUVRCFP3 KXTCUVRCW3
UVR-C 110-127V AC/110-125V DC KXTAUVRCFP4 KXTCUVRCW4
UVR-C 220-240V AC/220-250V DC KXTAUVRCFP5 KXTCUVRCW5
UVR-C 380-440V AC KXTAUVRCFP6 KXTCUVRCW6
UVR-C 480-525V AC KXTAUVRCFP7 KXTCUVRCW7
Electrical signals
Auxillary contacts - AUX
XT1 XT3 XT2, XT4
Type Fixed/plug-in Fixed/plug-in Fixed/plug-in Withdrawable
Uncabled version Catalog number Catalog number Catalog number Catalog number
AUX 250V KXTAAUX –
AUX uncabled AUX 24V DC KXTAAUXD –
AUX S51 250V – – KXTCAXS51 –
AUX S51 24V DC – – KXTCAXDS51 –
Cabled version
AUX-C 3Q 250V Left KXT1AXC3QL KXT3AXC3QL KXTCAXC3QL –
AUX-C 1Q + 1 SY 250V KXTAAXCQSYFP KXTCAXCQSYW
AUX-C 2Q + 1 SY 250V KXTAAXC2QSYFP –
AUX cabled AUX-C 3Q + 1 SY 250V – KXTDAXC3QSYFP KXTCAXC3QSYW
AUX-C 3Q + 2 SY 250V – – KXTCAXC3Q2SYFP KXTCAXC3Q2SYW
AUX-C 2Q + 2 SY + 1S51 250V – – KXTCAXC2Q2SYS51FP KXTCAXC2Q2SYS51W
AUX-S51 250V – – KXTCAXCS51FP KXTCAXCS51W
AUX-C 1Q + 1SY 24V DC KXTAAXCDQSYFP KXTCAXCDQSYW
AUX-C 3Q + 1SY 24V DC – KXTDAXCD3QSYFP KXTCAXCD3QSYW
AUX for
AUX-S51-C 24V DC – – KXTCAXDS51FP KXTCAXDS51W
withdrawable
AUX-C 1Q + 1SY 400V AC – – KXTCAXC4QSYFP KXTCAXC4QSYW
AUC-C 2Q 400V AC – – KXTCAXC42QFP KXTCAXC42QW
Motor operators
Motor operators with direct action - MOD
XT1, XT3
Catalog number
MOD 24V DC KXTBMOD24
MOD 48-60V DC KXTBMOD48-60
MOD 110-125V AC/DC KXTBMOD110-125
7 MOD 220-250V AC/DC KXTBMOD220-250
Motor operator MOD 380-440V AC KXTBMOD280-440
MOD 480-525V AC KXTBMOD480-525
Locks
Padlock on the circuit breaker
XT1, XT3 XT2, XT4
Type Catalog number Catalog number
PLL removable lock with padlocks in open position KXTBPLLREM –
PLL fixed lock with padlocks in open position KXTBPLLOP KXTCPLLOP
PLL fixed lock with padlocks in open/closed position KXTBPLLOPCL KXTCPLLOPCL
Interlock
RC Inst / RC Sel
7
Installation
Bracket for mounting onto DIN rail
XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P
Catalog Catalog Catalog Catalog Catalog Catalog Catalog Catalog
number number number number number number number number
(1)
Kit DIN50022 KXT1EDIN-3 KXT1EDIN-4 KXTCEDINPL KXT3EDIN-3 KXT3EDIN-4 KXTCEDINPL
Kit DIN50022 UL – – KXT2DIN-3 KXT2DIN-4 – – KXT4DIN-3 KXT4DIN-4
Kit DIN50022 XT1 + RC Low 220mm (1) – KXT1EDINRCSELPL – – – – – –
Kit DIN50022 XT1 + RC Sel/RC Inst (1) KXT1EDINRCPL – – – – – –
DIN guide Kit DIN50022 XT3 + RC Sel/RC Inst (1) – – – – KXT3EDINRCPL – –
(1)
IEC rated only.
Terminal cover
Sealable screw
Phase barriers
7 XT1, XT3 XT2, XT4
Type 4 pcs 6 pcs 4 pcs 6 pcs
Catalog number Catalog number Catalog number Catalog number
PB Height 25mm/0.98in KXTBPB25-3 KXTBPB25-4 KXTCPB25-3 KXTCPB25-4
PB Height 100mm/3.94in KXTBPB100-3 KXTBPB100-4 KXTCPB100-3 KXTCPB100-4
PB Height 200mm/7.87in KXTBPB200-3 KXTBPB200-4 KXTCPB200-3 KXTCPB200-4
Phase barriers
XT3 XT4
Type 3pcs 4pcs 6pcs 8pcs 3pcs 4pcs 6pcs 8pcs
Front Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
extended F Front terminals KXT3F-3PC KXT3F-4PC KXT3F-6PC KXT3F-8PC KXT4F-3PC KXT4F-4PC KXT4F-6PC KXT4F-8PC
spread F Front terminals for MCP – – – – – – – –
terminal - ES EF Extended front terminals KXT3EF-3PC KXT3EF-4PC KXT3EF-6PC KXT3EF-8PC KXT4EF-3PC KXT4EF-4PC KXT4EF-6PC KXT4EF-8PC
ES Extended spread terminals KXT3ES-3PC KXT3ES-4PC KXT3ES-6PC KXT3ES-8PC KXT4ES-3PC KXT4ES-4PC KXT4ES-6PC KXT4ES-8PC
FC CuAl Terminals for CuAl cables 100A, 14-1/0 AWG, KXT3CUAL1-3PC KXT3CUAL1-4PC KXT3CUAL1-6PC KXT3CUAL1-8PC KXT4CUAL1-3PC KXT4CUAL1-4PC KXT4CUAL1-6PC KXT4CUAL1-8PC
1x2.5…50mm 2 (4)
FC CuAl Terminals for CuAl cables w/control tap 100A, KXT3CUAL1C-3PC KXT3CUAL1C-4PC – – KXT4CUAL1C-3PC KXT4CUAL1C-4PC – –
14-1/0 AWG, 1x2.5…50mm 2 (4)
FC CuAl Terminals for CuAl cables 110A, 14-1/0 AWG, 1x2.5… – – – – – – – –
50mm (2)(4)
FC CuAl Terminals for CuAl cables 225A, 4 AWG-300 KXT3CUAL2-3PC KXT3CUAL2-4PC KXT3CUAL2-6PC KXT3CUAL2-8PC KXT4CUAL2-3PC KXT4CUAL2-4PC KXT4CUAL2-6PC KXT4CUAL2-8PC
kcmil, 1x35…150mm (2)(4)
FC CuAl Terminals for CuAl cables w/control tap 225A, 4 KXT3CUAL2C-3PC KXT3CUAL2C-4PC – – KXT4CUAL2C-3PC KXT4CUAL2C-4PC – –
AWG-300 kcmil, 1x35…150mm (2)(4)
FC CuAl Terminals for CuAl cables 250A, 250-350 kcmil, – – – – KXT4CUAL3-3PC KXT4CUAL3-4PC KXT4CUAL3-6PC KXT4CUAL3-8PC
1x120…185mm (2)(4)
Multi-cable FC Cu Terminals for Cu cables 125A, 14-1/0 AWG,
terminals 1x2.5…50mm 2 – – – – – – – –
(MC) FC Cu Terminals for Cu cables MCP, 14-1/0 AWG,
1x1.5…50mm 2 – – – – – – – –
FC Cu Terminals for Cu cables 125A, 14-1/0 AWG, – – – – – – – –
1x2.5…95mm 2
FC Cu Terminals for Cu cables 250A, 10-250 AWG, KXT3CU-3PC KXT3CU-4PC KXT3CU-6PC KXT3CU-8PC KXT4CU-3PC KXT4CU-4PC KXT4CU-6PC KXT4CU-8PC
1x6…185mm 2
FC Cu Terminals for Cu cables, XT4X to 150A, 14-1/0 AWG, – – – – KXT4XCU-3PC KXT4XCU-4PC – –
1x2.5…50mm 2 (3)
MC Multi cable terminals for Cu cables, 6x14-2 AWG, – – – – – – – –
6x2.5…35mm 2
MC Multi cable terminals for Cu cables, 6x12-2 AWG, KXT3MC-3PC KXT3MC-4PC KXT3MC-6PC KXT3MC-8PC KXT4MC-3PC KXT4MC-4PC KXT4MC-6PC KXT4MC-8PC
6x2.5…35mm 2
R Rear adjustable terminals (1) KXT3ER-3PC KXT3ER-4PC KXT3ER-6PC KXT3ER-8PC KXT4ER-3PC KXT4ER-4PC KXT4ER-6PC KXT4ER-8PC
R-RC Rear terminals for residual current (1) – KXT3ERRC-4PC – – – – – –
FB Flexibar Terminals (1) KXT3EFB-3PC KXT3EFB-4PC KXT3EFB-6PC KXT3EFB-8PC KXT4EFB-3PC KXT4EFB-4PC KXT4EFB-6PC KXT4EFB-8PC
(1)
IEC rated only.
(2)
Consult ABB for availability.
(3)
For use with the XT4 X version up to 150A only. Note: XT4 X from 175-250A uses the standard 250A CU lug.
(4)
Not available for XT4 X up to 150A.
7 Connection kits
XT2, XT4
Type Fixed/plug-in Withdrawable
Catalog number Catalog number
24V DC auxillary voltage kit for electronic trip units (1) KXTCECAUXFP KXTCECAUXW
External neutral connection kit KXTCECNEFP KXTCECNEW
(1)
IEC rated only.
Spare parts
Spare parts
ATS021
XT1 XT2 XT3 XT4 XT2 XT4
Fixed/plug-in Withdrawable
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
SA RC Sel/RC Inst - opening solenoid for the residual
KXT1ESARCFP KXT2ESARCFP KXT3ESARCFP KXT4ESARCFP KXT2ESARCW KXT4ESARCW
current device (1)
SA RC B Type - opening solenoid for the residual
– – KXT3ESARCFPB – – –
current device (1)
AUX-C - Loose cabled auxillary contact 250V AC (2) KXTAAUXCFP KXTCEAUXCW
AUX-C - Loose cabled auxillary contact 24V DC (2) KXTAAUXCDFP KXTCEAUXCDW
AUX-C - Loose cabled auxillary contact 250V AC
KXTAAUXCFPHD KXTCAUXCWHD
600V (2)
AUX-C - Loose cabled auxillary contact 24V DC
KXTAAUXCDFPHD KXTCAUXCDWHD
600V (2)
(1)
IEC rated only.
(2)
Un-numbered cables. 7
Connectors for fixed part/moving part of withdrawable circuit breakers (1)
XT2, XT4
Catalog number
1 connector for with 2 pins for SOR/UVR up to 400V KXTCE2PINCONSOUV
1 connector with 3 pins for AUX up to 400V KXTCE3PINCONAUX
(1)
IEC rated only.
Fixed part of
withdrawable
Flanges for the compartment door (1)
XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
Small "optional"
flange for circuit KXTAEFLASMFP
breaker
Large "standard"
flange for circuit KXT1EFLAFP-3 KXT1EFLAFP-4 KXT2EFLAFP-3 KXT2EFLAFP-4 KXT3EFLAFP-3 KXT3EFLAFP-4 KXT4EFLAFP-3 KXT4EFLAFP-4
breaker
Flange Flange for MOD KXTBEFLAMOD – – KXTBEFLAMOD – –
Flange for MOE/
– – KXTCEFLAMOEFP – – KXTCEFLAMOEFP
MOE-E/FLD
Flange for direct
KXTAEFLARHDFP
handle RHD
Flange for residual
current RC Sel/ KXT1EFLARCFP-3 KXT1EFLARCFP-4 – – KXT3EFLARCFP-3 KXT3EFLARCFP-4 – –
RC Inst
Flange for residual
– – – KXT2EFLARCFP-4 – – – KXT4EFLARCFP-4
current RC Sel
(1)
IEC rated only.