Xt3su3225dff000xxx Acc

Download as pdf or txt
Download as pdf or txt
You are on page 1of 57

Accessories

Versions and types

Tmax XT circuit breakers are available in the following versions:


■ FIXED. These have a current-interrupting part connected to the trip unit, to be installed on the

back plate of the box;


■ PLUG-IN. These have a moving part and a fixed part. The latter must be installed on the back

plate of the box. The moving part comes in the kit that converts the fixed version into a plug-in
version;
■ WITHDRAWABLE. These have a moving part and a fixed part, equipped with side runners to

3 Fixed circuit breaker


allow easy racking in/out of the moving part. The fixed part is installed on the back plate of
the box. The moving part comes in the kit that converts the fixed version into a withdrawable
version. To create the withdrawable circuit breaker, it’s necessary to order a front accessory to
maintain the IP40 degree of protection over the circuit breaker’s entire isolation run.
If the plug-in circuit breaker is fitted with electrical accessories, appropriate connectors for
insulating the corresponding auxiliary circuits must also be ordered. For the withdrawable version,
there are dedicated accessories fitted with connectors enabling automatic disconnection when
racking-out. (Consult the “Connectors for electrical accessories” section of this chapter).
Using the fixed version as a base, SACE Tmax XT circuit breakers can easily be converted into
plug-in and withdrawable versions with the appropriate conversion kits. The moving part can
always be obtained in the required version, fully pre-engineered in the factory, by ordering the
fixed circuit breaker and the conversion kit at the same time.

Version
Fixed Plug-in Withdrawable
XT1 n n
XT2 n n n
XT3 n n
Plug-in circuit breaker
XT4 n n n

Fixed part of plug-in and withdrawable versions


The fixed parts of the plug-in/withdrawable versions are available with extended front terminals
(EF). The fixed parts can be equipped with some of the same terminal, terminal-cover and phase
barrier kits used for the fixed circuit breakers, by using the proper adapter.
The fixed parts of a plug-in/withdrawable circuit breaker can be installed at a distance of
Withdrawable circuit breaker 50mm/1.97in from the back of the panel or at 70mm/2.76in as shown in the picture.

Installing at 50mm/1.97in
Installing at 70mm/2.76in

3/2 SACE Tmax XT UL/CSA | US Technical Catalog


Conversion kits
The following conversion kits can be obtained in order to create the different versions:
■ Kit for converting the fixed circuit breaker into the moving part of plug-in/withdrawable

versions. When withdrawable versions are made, it is essential to order an accessory to apply
to the front of the circuit breaker in order to maintain the IP40 degree of protection over the
Conversion kit for turning a fixed entire isolation run. This accessory can be chosen from:
circuit breaker into the moving – front for lever operating mechanism (FLD); 3
part of a plug-in circuit breaker
– motor operator (MOE);
– direct or extended rotary handle operating mechanisms (RHD or RHE).
If no accessory is indicated, the front for lever operating mechanism (FLD) is automatically
included in the order.
■ Kit for converting the fixed part of plug-in versions into the fixed part of withdrawable

versions. The kit comprises:


– a guide for turning the fixed part of the plug-in circuit breaker into the fixed part of the
withdrawable circuit breaker;
– a racking-out rotary handle that allows the moving part to be inserted and withdrawn. The
Conversion kit for turning a fixed
mechanism allows the circuit breaker to be set to the isolated position (with the power
circuit breaker into the moving
part of a withdrawable circuit and auxiliary circuits disconnected) with the compartment door closed, for operator safety.
breaker The rotary handle can only be inserted when the circuit breaker is open. Once it has been
removed or withdrawn, the circuit breaker can be set to the open/closed position;
– a flange for the compartment door, which replaces the one supplied with the fixed version of
the circuit breaker.
■ Kit for converting fixed type into the plug-in version for RC Sel residual current devices

for XT2-XT4. RC Sel four-pole residual current devices for XT2 and XT4 can be converted from
the fixed version into the plug-in version using the special kit.
■ Kit for converting plug-in types into the withdrawable version for RC Sel residual current

devices for XT2-XT4. RC Sel four-pole residual current devices for XT2 and XT4 can be
converted from the plug-in version to the withdrawable version using the special kit, which
comprises a bellows to apply to the front of the residual current device so as to allow it and
the residual current part to be withdrawn when the panel door is closed. This kit can also
be assembled on fixed circuit breakers fitted with the front part for locks or the direct rotary
handle, thus adding to the range of uses for residual current devices.
In the plug-in to withdrawable conversion kit, there is also a 6-pin connector to be applied onto
the right side of the circuit breaker to facilitate disconnecting the auxiliary circuits connected to
Conversion kit for turning a fixed
part of plug-in version into the the residual current device.
fixed part of a withdrawable This kit contains also the shunt opening release of the residual current device dedicated to the
version withdrawable version, which is fitted with a connector for the fixed part and the moving part.

US Technical Catalog | SACE Tmax XT UL/CSA 3/3


Accessories
Versions and types

Plug-in version

+ + =
3

Fixed part of Fixed Conversion kit for turning a fixed Plug-in


plug-in circuit breaker circuit breaker into the moving circuit breaker
part of a plug-in
circuit breaker

Withdrawable version

1st solution

+ + + =

Fixed part of Fixed Conversion kit for turning a Frontal Withdrawable


withdrawable circuit breaker fixed circuit breaker into the accessory(1) circuit breaker
moving part of a withdrawable
circuit breaker

2nd solution

+ + + + =

Fixed part Conversion kit for turning a Fixed Conversion kit for turning a Frontal Withdrawable
of plug-in fixed part of plug-in version circuit breaker fixed circuit breaker into the accessory(1) circuit breaker
into the fixed part of a moving part of a withdrawable
withdrawable version circuit breaker

(1)
Frontal accessory is mandatory. If not specified in the order, the FLD is supplied automatically

3/4 SACE Tmax XT UL/CSA | US Technical Catalog


Accessories
Mechanical accessories

UL Listed XT1 XT2 XT3 XT4


Terminals F - Front terminals n n n n n
EF - Extended front terminals n n n n n
ES - Extended spread terminals n n n n n
FCCu - Front for copper cables n n n n n
FCCuAl - Front for copper/aluminum cables n – – n n
FB - For flexible busbars – n n n n
MC - Multi cable for copper cable n n n n n 3
R - Rear oriented – n n n n
EF - Extended front for the fixed part n n n n n
HR/VR - Horizontal rear / Vertical rear for fixed part – n n n n
R for RC - Rear for residual current release – n – n –
Terminal covers LTC - Low terminal cover – n n n n
HTC - High terminal cover n n n n n
Phase barriers PB - 25mm/0.98in n n n n n
PB - 100mm/3.94in n n n n n
PB - 200mm/7.87in n n n n n
Flange handle operating mechanism MKC - Cable operated flange handles n n n n n
Rotary handle operating mechanism RHD - Direct rotary handle n n n n n
RHE - Extended rotary handle n n n n n
RHS - Side rotary handle (right and left sides) n n n n n
LH - Long "pistol" rotary handle (for RHE or RHS) n n n n n
RHL - Rotary handle/front lever lock, open n n n n n
RHL - Rotary handle/front lever lock, open/closed n n n n n
Front for operating lever mechanism FLD - Front for locks n – n – n
Locks on circuit breaker PLL - Padlock device, removable n n – n –
PLL - Padlock device, open n n n n n
PLL - Padlock device, open/closed n n n n n
KLC - Key lock, open n n n n n
KLC - Key lock, open/closed n n n n n
Mechanical interlock MIR - Mechanical interlock (HR and VR) n n n n n

Connection terminals
Connection terminals allow the circuit breaker to be connected to the system in the way best
suited to the installation requirements. By and large, they consist of front terminals for connecting
cables or busbar directly from the front of the circuit breaker.
Where possible, the terminals have laser markings on the surface to indicate the tightening
torques for the correct isolation of cables and bars.

Fixed version
Standard SACE Tmax XT circuit breakers for UL and CSA are supplied with front terminals (F).
However, they can be fitted with the following types of terminal as accessories thanks to the
special kits:
■ extended front (EF);
■ extended spread front (ES);
■ front for copper/aluminum cables (FCCuAI), for XT3 and XT4 sizes;
■ front for copper cables (FCCu);
■ multicable for copper cable (MC);
■ for flexible busbar (FB);
■ rear oriented (R) 1).

For XT1 and XT3 sizes, the use of non-insulated busbar with Ue ≤ 480V involves the mandatory
assembly of terminal-covers HTC.
1)
IEC only

US Technical Catalog | SACE Tmax XT UL/CSA 3/5


Accessories
Mechanical accessories

Plug-in and withdrawable versions


The fixed part of plug-in and withdrawable version circuit-breakers is normally supplied with
extended front terminals (EF) or horizontal/vertical rear terminals (HR/VR).
Horizontal/vertical rear terminals (HR/VR) are factory-mounted in the horizontal position. If
needed, the terminals can easily be field-rotated to the vertical position.
A fixed part with front terminals (EF) can be converted into a fixed part with rear terminals
(HR/VR) by ordering the appropriate terminal kit. The fixed parts can also be fitted with some
3 of the same types of terminal available on the fixed circuit breaker after an adapter has been
installed on the terminal zone of the fixed part itself. Consequently, the following types of
connection terminals are also acceptable for use with the fixed part:
■ extended spread front (ES);
■ for copper cables (FCCu);
■ multi-cable (MC).
■ for copper and aluminum cables (FCCuAl);
■ for flexibar (FB).

The adapter mimics the terminal zone of the fixed circuit breaker. This means that fixed parts can
also be equipped with the same terminal covers and phase separators as those used for fixed
circuit breakers.

H3 H1 H2

Installing at 50mm/1.97in
Installing at 70mm/2.76in

Fixed part adapter


Circuit breakers H1 H2 H3 fixed part
fixed part circuit breaker with two adapters
[mm/in] [mm/in] [mm/in]
XT1 146/5.75 134/5.28 181/7.13
XT2 153/6.02 134/5.28 188/7.40
Fixed part adapter
XT3 166/6.54 154/6.06 225/8.86
XT4 182/7.17 164/1.46 228/8.98

3/6 SACE Tmax XT UL/CSA | US Technical Catalog


Front terminals - F (1)
CB. Vers. Busbar dimensions Cable terminals Tightening H Terminal covers H Phase separators
[mm/in] [mm/in] [Nm/lb-in] [mm/in] [mm/in]
W min W max H Ø D min D max W Ø Cable or busbar 2/0.08 50/1.97 60/2.36 25/0.98 100/3.94 200/7.87
/Terminal
XT1 F 13/0.512 16/0.630 7.5/0.295 6.5/0.256 3.5/0.138 5/0.197 16/0.630 6.5/0.256 M6 6/53.1 – R – S R R
XT2 F 13/0.512 20/0.787 7.5/0.295 6.5/0.256 2.5/0.098 5/0.197 20/0.787 6.5/0.256 M6 6/53.1 – R – S R R
XT3 F 17/0.669 25/0.984 9.5/0.374 8.5/0.335 5/0.197 8/0.315 24/0.945 8.5/0.335 M8 8/70.8 – – R S R R
3
XT4 F 17/0.669 25/0.984 10/0.394 8.5/0.335 5/0.197 8/0.315 25/0.984 8.5/0.335 M8 8/70.8 – – R S R R
(1)
UL Listed

Front terminal - F F terminal with cable lug F terminal with busbar

Front extended terminals - EF (1)


CB Vers. Busbar dimensions Cable terminals Tightening H Terminal covers H Phase separators
[mm/in] [mm/in] [Nm/lb-in] [mm/in] [mm/in]
W D Ø W Ø Terminal Cable or busbar 2/0.08 50/1.97 60/2.36 25/0.98 100/3.94 200/7.87
/CB /Terminal
XT1 F 20/0.787 4/0.157 8.5/0.335 20/0.787 8.5/0.335 M6 6/53.1 M8 9/79.7 – R – – S R
XT2 F 20/0.787 4/0.157 8.5/0.335 20/0.787 8.5/0.335 M6 6/53.1 M8 9/79.7 – S – – S R
XT3 F 20/0.787 6/0.236 10/0.394 20/0.787 10/0.394 M8 8/70.8 M10 18/159.3 – – R – S R
XT4 F 20/0.787 10/0.394 10/0.394 20/0.787 10/0.394 M8 8/70.8 M10 18/159.3 – – S – S R
(1)
UL Listed

Front extended terminal - EF EF terminal with cable lug EF terminal with busbar

W Width F Fixed
H Hole height P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request

US Technical Catalog | SACE Tmax XT UL/CSA 3/7


Accessories
Mechanical accessories

Front extended spread terminals - ES (1)


CB Vers. Busbar dimensions MAX Cable terminals Tightening H Terminal covers H Phase separators
[mm/in] [mm/in] [Nm/lb-in] [mm/in] [mm/in]
W D Ø W Ø Terminal Cable or busbar 2/0.08 50/1.97 60/2.36 25/0.98 100/3.94 200/7.87
/CB /Terminal
XT1 F-P 25/0.984 4/0.157 8.5/0.335 25/0.984 8.5/0.335 M6 6/53.1 M8 9/79.7 – – – – – S
XT2 F-P-W 30/1.181 4/0.157 10.5/0.413 30/1.181 10.5/0.413 M6 6/53.1 M10 18/159.3 – – – – – S

3 XT3 F-P 30/1.181 4/0.157 10.5/0.413 30/1.181 10.5/0.413 M8 8/70.8 M10 18/159.3 – – – – – S
XT4 F-P-W 30/1.181 10/0.394 10.5/0.413 30/1.181 10.5/0.413 M8 8/70.8 M10 18/159.3 – – – – – S
(1)
UL Listed

Front extended spread terminal ES terminal with cable ES terminal with busbar
- ES lug

Terminals for copper cables - FCCu (2)


CB Type of Vers. Cable Inner dimensions Tightening L cable H Terminal covers H Phase separators
terminal [mm/in] [Nm/lb-in] stripping [mm/in] [mm/in]
AWG/kcmil mm2 Cable or busbar/Terminal [mm/in] 2/0.08 50/1.97 60/2.36 25/0.98 100/3.94 200/7.87
XT1 (3)
internal F-P 1x14…1/0 1x2.5…70 12x12/0.472x0.472 7/61.95 16/0.629 – R – S(1) R R
XT1 (4)
internal F-P 1x14…1/0 1x1.5…70 9,5x16/0.37x0.63 7/61.95 16/0.629 – R – S(1) R R
<50mm2 (1/10 AWG): 7/61.95
XT2 internal F-P-W 1x14…1/0 1x2.5…95 14x14/0.551x0.551 14/0.551 – R – S(1) R R
≥50mm2 (1/10 AWG): 8,5/75.23
XT3 internal F-P 1x10…250 1x6…185 18x18/0.709x0.709 14/123.91 20/0.787 – – R S(1) R R
XT4 internal F-P 1x10…250 1x6…185 18x18/0.709x0.709 14/123.91 16/0.787 – – R S(1) R R
XT4 internal F-P 1x14-1/0 1x2.5...50 1x2.5...50 – – – – – – – –
(1)
Phase separators are supplied as standard with the basic version of the circuit breaker; (2)
UL Listed; (3)
MCCB only application; (4)
MCCB/MCP application.

FCCu terminal FCCu terminal with cable FCCu terminal with busbar

W Width F Fixed
H Hole heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request

3/8 SACE Tmax XT UL/CSA | US Technical Catalog


Terminals for copper cables - FCCuAl (1)
CB Type of Vers. Cable Tightening L H Terminal covers H Phase separators
terminal [Nm/lb-in] cable [mm/in] [mm/in]
AWG/kcmil mm 2 Terminal/CB Cable or busbar/Terminal stripping 2/0.08 50/1.97 60/2.36 25/0.98 100/3.94 200/7.87
[mm/in]
XT2 internal F-P 1x14…1/0 1x2.5…50 2.5/22.12 M6 ≤ 8mm (8 AWG):4.5/39.82
2
15,5/0.61 – – – S R R
> 8mm2 (8 AWG) 5.7/50.44
XT3 internal F-P 1x14…1/0 1x2.5…50 9/79.7 slot 5.6/50 15,5/0.61 – – – S R R
internal F-P 1x4…300 1x25…150 9/79.7 M6 22.6/200 20/0.787 – – – S R R 3
XT4 internal F-P 1x14…1/0 1x2.5…50 9/79.7 slot 5.6/50 15,5/0.61 – – – S R R
internal F-P 1x4…300 1x25…150 9/79.7 M6 22.6/200 20/0.787 – – – S R R
XT4 internal F-P 1x250...350 1x127...177 not app M6 25/221 24 – – – S R R
XT4 X internal F-P 1x14...1/0 1x2.5...50 9/79.7 M6 <8mm2 (8 AWG): 2.3/20.35 16 S R R
– – –
≥8mm2 (8 AWG): 5.6/49.56
(1)
UL Listed

Internal FCCuAl terminal for Internal FCCuAl terminal for FCCuAl internal terminal
copper/aluminum cables copper and aluminum cable with cable
with take-up of auxiliary
voltage

Terminals for flexible busbars - FB


CB Type of Vers. Busbar dimensions Busbar dimensions Tightening H Terminal covers H Separators
terminal MIN [mm/in] MAX [mm] [Nm/lb-in] [mm/in] [mm/in]
W D Nr W D Nr Cable or busbar/Terminal 2/0.08 50/1.97 60/2.36 25/0.98 100/3.94 200/7.87
XT1 internal F-P 10/0.394 0,8/0.031 2/0.078 10/0.394 0,8/0.031 9/0.354 7/61.95 – R – S(1) R R
XT2 internal F-P-W 10/0.394 0,8/0.031 2/0.078 10/0.394 0,8/0.031 9/0.354 7/61.95 – R – S(1) R R
XT3 internal F-P 16/0.629 0,8/0.031 2/0.078 16/0.629 0,8/0.031 10/0.394 14/123.91 – – R S(1) R R
XT4 internal F-P-W 16/0.629 0,8/0.031 2/0.078 16/0.629 0,8/0.031 10/0.394 14/123.91 – – R S(1) R R
(1)
Phase separators supplied as standard with basic version circuit breaker

Terminal for flexible busbars (FB) FB terminal with flexible


busbars

W Width F Fixed
H Hole heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request

US Technical Catalog | SACE Tmax XT UL/CSA 3/9


Accessories
Mechanical accessories

Multi-cable terminals - MC Cu (1)


CB Type of Vers. Cable Tightening L H Terminal covers H Phase separators
terminal [Nm/lb-in] cable stripping [mm/in] [mm/in]
AWG/kcmil mm 2 Terminal Cable or busbar [mm/in] 2/0.08 50/1.97 60/2.36 25/0.98 100/3.94 200/7.87
/CB /Terminal
XT1 external F-P 6x14…2 6x2.5…35 6/53.1 7/61.95 10, 20, 30 / 0.394, 0.787, 1.181 – S – – – –
XT2 external F-P-W 6x14…2 6x2.5…35 6/53.1 7/61.95 10, 20, 30 / 0.394, 0.787, 1.181 – S – – – –
XT3 external F-P 6x12…2 6x2.5…35 8/70.8 7/61.95 15, 30 / 0.591, 1.181 – – S – – –
3
XT4 external F-P 6x12…2 6x2.5…35 8/70.8 7/61.95 15, 30 / 0.591, 1.181 – – S – – –
Installation on loas side only
(1)
UL Listed

Multi-cable terminals (MC) Multi-cable terminals with cables

Rear horizontal terminals - R


CB Vers. Busbar dimensions MAX Tightening H Terminal covers H Separators
[mm] [Nm/lb-in] [mm] [mm]
W H D Ø Terminal/CB Cable or busbar/terminal 2/0.08 50/1.97 60/2.36 25/0.98 100/3.94 200/7.87
XT1 F 15/0.590 7.5/0.295 5/0.196 6.5/0.255 M5 5/44.2 M6 6/53.1 S – – – – –
XT2 F 20/0.787 9/0.354 4/0.157 8.5/0.335 M6 6/53.1 M8 8/70.8 S – – – – –
XT3 F 20/0.787 9/0.354 6/0.236 8.5/0.335 M8 8/70.8 M8 8/70.8 S – – – – –
XT4 F 20/0.787 9/0.354 6/0.236 8.5/0.335 M8 8/70.8 M8 8/70.8 S – – – – –

Rear horizontal terminals (R) R terminal with horizontal busbar R terminal with vertical busbar

W Width F Fixed
H Hole heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request

3/10 SACE Tmax XT UL/CSA | US Technical Catalog


Extended front terminals for fixed part - EF (1)
CB Vers. Busbar dimensions Cable terminals Tightening Phase separators
[mm/in] [mm/in] [Nm/lb-in] [mm/in]
W D Ø W Ø Terminal/ Cable or busbar 100/3.94 200/7.87
CB /Terminal
XT1 P 20/0.787 5/0.197 8.5/0.335 21/0.827 6.5/0.256 M6 6/53.1 M6 9/79.7 S R
XT2 P-W 20/0.787 5/0.197 8.5/0.335 21/0.827 6.5/0.256 M6 6/53.1 M6 9/79.7 S R
XT3 P 25/0.984 8/0.315 8.5/0.335 30/1.181 8.5/0.335 M6 8/70.8 M8 18/159.3 S R
3
XT4 P-W 25/0.984 8/0.315 8.5/0.335 30/1.181 8.5/0.335 M6 8/70.8 M8 18/159.3 S R
(1)
UL Listed

EF terminals for fixed part

Rear flat horizontal terminals for fixed part - HR


CB Vers. Busbar dimensions Cable terminals Tightening Rear Separators
[mm/in] [mm/in] [Nm/lb-in] [mm/in]
W D Ø W Ø Terminal/ Cable or busbar 90/3.543
CB /Terminal
XT1 P 20/0.787 4 8.5/0.335 20/0.787 8.5/0.335 6/53.1 9/79.7 R
XT2 P-W 20/0.787 4 8.5/0.335 20/0.787 8.5/0.335 6/53.1 9/79.7 R
XT3 P 25/0.984 6 8.5/0.335 25/0.984 8.5/0.335 8/70.8 9/79.7 R
XT4 P-W 25/0.984 10 8.5/0.335 25/0.984 8.5/0.335 8/70.8 9/79.7 R

HR terminals for fixed part

Rear flat vertical terminals for fixed part - VR


CB Vers. Busbar dimensions Cable terminals Tightening Rear Separators
[mm/in] [mm/in] [Nm/lb-in] [mm/in]
W D Ø W Ø Terminal/ Cable or busbar 90/3.543
CB /Terminal
XT1 P 20/0.787 4 8.5/0.335 20/0.787 8.5/0.335 6/53.1 9/79.7 R
XT2 P-W 20/0.787 4 8.5/0.335 20/0.787 8.5/0.335 6/53.1 9/79.7 R
XT3 P 25/0.984 6 8.5/0.335 25/0.984 8.5/0.335 8/70.8 9/79.7 R
XT4 P-W 25/0.984 10 8.5/0.335 25/0.984 8.5/0.335 8/70.8 9/79.7 R

VR terminals for fixed part

W Width F Fixed
H Hole heigth P Plug-in
D Depth W Withdrawable
Ø Diameter
S Standard
W
D R On Request

US Technical Catalog | SACE Tmax XT UL/CSA 3/11


Accessories
Mechanical accessories

Terminal covers and phase barriers


Terminal covers are applied to the circuit breaker to prevent accidental contact with live parts,
thereby providing protection against direct contacts. The high terminal covers are pre-punched
for knock-outs on the front to facilitate installing busbars and/or cables and ensuring correct
insulation.
The phase barrier partitions increase the insulation characteristics between the phases on a level
with the connections. They are mounted from the front, even when the circuit breaker has already
3 been installed, by inserting them into the corresponding slots.
Terminal covers
The table lists the various terminal covers and phase barriers available for each SACE Tmax
XT circuit breaker. The terminal covers/phase barriers that are able to ensure adequate circuit
breaker installation and correct insulation are listed in the “Connection terminals” section of this
chapter, alongside each terminal.

XT1 XT2 XT3 XT4


HTC - High terminal covers [mm/in] 50/1.97 50/1.97 60/2.36 60/2.36
LTC - Low terminal covers(1) [mm/in] 2/0.08 2/0.08 2/0.08 2/0.08
Phase barrier - low [mm/in] 25/0.98 25/0.98 25/0.98 25/0.98

Phase barriers Phase barrier - medium [mm/in] 100/3.94 100/3.94 100/3.94 100/3.94
Phase barrier - high [mm/in] 200/7.87 200/7.87 200/7.87 200/7.87
Rear phase barrier for FP [mm/in] 90/3.54 90/3.54 90/3.54 90/3.54
(1)
IEC rear terminals only

Rotary handle operating mechanism


This device allows the circuit breaker to be operated by means of a rotary handle, which makes
the circuit breaker easier to open and close.
Different types of handle are available:
■ direct (RHD): installed directly on the front of the circuit breaker. Allows it to be operated from

the front;
■ extended (RHE): installed on the panel door. Allows the circuit breaker to be operated by

means of a rod which acts on a base installed on the front of the circuit breaker;
■ side, for lateral left (RHS-L) and lateral right (RHS-R). Allows operation from the side by means

of a shaft which acts on the base installed on the front of the circuit breaker.
A long handle grip (LH) which can be combined with the extended handle (RHE) and with the side

Direct rotary handle (RHD) Extended rotary handle (RHE) (LH) Long handle (RHS) Side rotary handle

3/12 SACE Tmax XT UL/CSA | US Technical Catalog


All rotary handles are available in two versions:
■ standard: grey color;
■ emergency: red on a yellow background. Suitable for operating machine tools.

Rotary handles can be ordered:


■ by specifying one single sales code (for RHD, RHE, RHS L/R);
■ by indicating the following three devices (only for RHE):

– rotary handle on compartment door with normal standard handgrip (RHE_H, RHE_H LH)
or emergency handgrip (RHE_H_EM, RHE_H_EM LH); 3
– 60.5mm/2.38" and 170.5mm/6.71" rod (RHE_S). The minimum and maximum distances
between the fixing plate and the door are 60.5mm/2.38" and 170.5mm/6.71";
– base to fix to the circuit base (RHE_B).

Using the rotary handle is an alternative to the motor operator and to all accessories of the front type.
The rotary handles can be locked by means of a vast range of key locks and padlocks (consult
the “Locks” section of this chapter).
The direct and extended rotary operating mechanisms allow early contacts to be used on
closing in order to supply the undervoltage release in advance of the circuit breaker's closing
(consult the “Early auxiliary contacts” section of this chapter).

IP54 Protection
A device that can be applied onto the transmitted rotary and lateral handle allowing IP54 degree of
protection(G.1.11) to be achieved.

IP54 protection

Front for operating lever mechanism


This device can be installed on the front of the circuit breaker, allowing it to be locked with key
locks and padlocks.
The front for operating lever mechanism can only be installed on XT2 and XT4 three-pole and
four-pole circuit breakers. It can be fitted with a vast range of key locks and padlocks (see the
"Locks" section of this chapter).

Front for operating lever mechanism

US Technical Catalog | SACE Tmax XT UL/CSA 3/13


Accessories
Mechanical accessories

Locks
Padlocks or key locks prevent the circuit breaker from being closed and/or opened. They can be fitted:
■ directly on the front of the circuit breaker;
■ on the rotary handle operating mechanism;

Key lock ■ on the front for lever operating mechanism;


■ on the motor;
■ to the fixed and withdrawable part, to prevent the moving part from being inserted;
3 ■ on the front of the thermal magnetic trip unit, to prevent the thermal part adjustor from being tam-

pered with.
All locks that hold the circuit breaker in the open position ensure circuit isolation in accordance with the
IEC 60947-2 Standard. In the closed position, the locks do not prevent the mechanism from releasing
after a fault or remote control.

Fixed padlock in open position

Fixed padlock in open/ Circuit breaker with Circuit breaker with fixed Circuit breaker with fixed
closed position removable padlock in open padlock in open position padlock in open/close
position position

Removable padlock
in open position

RHD with key lock RHE with key lock FLD with key lock

Key lock/padlock for


withdrawable fixed part

MOD with key lock MOE with key lock Withdrawable fixed part
with key lock/padlock

3/14 SACE Tmax XT UL/CSA | US Technical Catalog


Type of lock Circuit- Optional/ Position of Type Removability
breaker Standard supply circuit breaker lock of lock of key
Circuit- PLL XT1…XT4 Optional OPEN / CLOSED padlocks max 3 padlocks Ø –
breaker Fixed padlock device 7mm stem (not supplied)
XT1…XT4 Optional OPEN padlocks max 3 padlocks Ø –
7mm stem (not supplied)
PLL XT1, XT3 Optional OPEN padlocks max 3 padlocks Ø –
Removable 7mm stem (not supplied)
padlock device
KLC XT1…XT4 Optional OPEN Ronis Same key OPEN 3
Key lock(5) (A, B, C, D type)
XT1…XT4 Optional OPEN Ronis OPEN
Different key
XT1…XT4 Optional OPEN Ronis OPEN / CLOSED
Same key
Rotary handle RHL XT1…XT4 Optional OPEN Ronis OPEN
(RHD/RHE/ Key lock(1) Same key
RHE-LH/ XT1…XT4 Optional OPEN Ronis OPEN
RHS) Different key
XT1…XT4 Optional OPEN / CLOSED Ronis OPEN / CLOSED
Different key
Padlock device XT1…XT4 Standard OPEN padlocks max 3 padlocks Ø –
6mm stem (not supplied)
Door lock(4) XT1…XT4 Standard DOOR LOCKED WHEN – –
CIRCUIT BREAKER CLOSED
Frontal for Padlock device XT2, XT4 Standard OPEN padlocks max 3 padlocks Ø –
operating 6mm stem (not supplied)
lever Door lock XT2, XT4 Standard DOOR LOCKED WHEN – –
(FLD) CIRCUIT BREAKER CLOSED
RHL XT2, XT4 Optional OPEN Ronis OPEN
Key lock(1) Same key
XT2, XT4 Optional OPEN Ronis OPEN
Different key
XT2, XT4 Optional OPEN / CLOSED Ronis OPEN / CLOSED
Different key
Motor Padlock device XT1…XT4 Standard OPEN padlocks max 3 padlocks Ø –
(MOD, MOE, 8mm stem (not supplied)
MOE-E) Key lock on motor XT1…XT4 Optional OPEN Ronis OPEN
MOL-D Different keys
MOL-S XT1…XT4 Optional OPEN Ronis OPEN
Same keys
Key lock against XT1…XT4 Optional MANUAL Ronis WITH LOCK
manual operation key INSERTED
MOL-M(2)
Fixed part of KLF-FP XT2, XT4 Optional Key WITHDRAWN / INSERTED Ronis key Different + –
withdrawable Key lock / padlock Padlock WITHDRAWN padlocks max 3 padlocks Ø
for fixed part of 6mm stem (not supplied)
withdrawable device XT2, XT4 Optional Key WITHDRAWN / INSERTED Ronis key Same + padlocks –
Padlock WITHDRAWN max 3 padlocks Ø 6mm
stem (not supplied)
XT2, XT4 Optional Key WITHDRAWN / INSERTED Giussani key Different + –
Padlock WITHDRAWN padlocks max 3 padlocks Ø
6mm stem (not supplied)
XT2, XT4 Optional Key WITHDRAWN / INSERTED Giussani key Same + –
Padlock WITHDRAWN padlocks max 3 padlocks Ø
6mm stem (not supplied)
Trip unit Lock of thermal XT1, XT3 Optional – – –
regulation (3)
XT2, XT4 Standard – – –

(1)
On the transmitted rotary handle (RHE), the lock is mounted on the base. The key lock is not available on the lateral handle (RHS).
(2)
Only for MOE and MOE-E.
(3)
Applied to the cover of the circuit breakers on a level with the regulator of the thermal element of thermal magnetic release TMD to prevent it from being tampered with.
(4)
This function can be totally inhibited by the customer when the handle is assembled by means of a simple operation that can be reversed if needed.
Moreover, if the door lock function is not disabled by the customer during the assembly phase, the door lock can be temporarily deactivated with a tool in exceptional cases,
so that the door can be opened without opening the circuit breaker .
(5)
Incompatible with electrical accessories mounted in the third pole.

US Technical Catalog | SACE Tmax XT UL/CSA 3/15


Accessories
Mechanical accessories

Rear mechanical interlock


Support designed for rear installation of two circuit breakers that, through connections, prevents
the two installed breakers from closing simultaneously.
The circuit breakers in the Tmax XT family are interlocked two-by-two (IO-OI-OO) by means of a
chassis and special plates. Interlocked circuit breakers can be of a fixed, plug-in or withdrawable
version. Both circuit breakers and molded case switch disconnectors in the three-pole and four-
pole versions can be interlocked.
3 Acceptable combinations are:
Interlock

XT1 XT2 XT3 XT4


XT1 n n n n
XT2 n n n
XT3 n n
XT4 n n n

The following equipment must be ordered to make the rear interlock:


■ a vertical or horizontal chassis;
■ a plate for each circuit breaker to be interlocked.

+ =

Interlock - Chassis Two Plates Interlock

Bracket for fixing on DIN rail


Support designed to be installed on the back of the circuit breakers to simplify assembly on
standardized DIN EN 50022 rail.
The following can be installed on DIN EN 50022 rail:
■ all Tmax XT circuit breakers in the fixed three-pole or four-pole versions;
■ XT1, XT3 circuit breakers equipped with RC Sel 200; RC Inst, RC Sel for XT1 and XT3 residual

current releases.

Bracket for fixing on DIN rail

3/16 SACE Tmax XT UL/CSA | US Technical Catalog


Flanges
A flange is a plastic plate that acts as an interface between the circuit breaker and the hole in
the panel door. All the Tmax XT series flanges are newly designed and do not require screws for
installation. Flanges are applied:
■ around the front part of the fixed/plug-in circuit breaker;
■ around the operating lever for all fixed/plug-in/circuit breakers;
■ around the MOD or MOE motor operator;
■ around the front for FLD locks; 3
■ around the direct rotary handle operating mechanism;
■ around the extended rotary handle operating mechanism;
■ around the RC Inst, RC Sel for XT1 and XT3, RC Sel for TX2 and TX4 residual current release.

XT1-XT3
with standard flange

XT2-XT4 XT1-XT4 Rotary handle MOE MOD


with standard flange with operating lever with flange with flange align flush left
flange under MOD

US Technical Catalog | SACE Tmax XT UL/CSA 3/17


Accessories
Electrical accessories

Tmax XT UL/CSA electrical accessories UL Listed XT1 XT2 XT3 XT4


Shunt opening release SOR / SOR-C (uncabled and cabled) n n n n n
Undervoltage release UVR / UVR-C (uncabled and cabled) n n n n n
Time-delay device for undervoltage release UVD – n n n n
Cabled auxiliary contacts, 1m 1 Q 1 SY 24V DC n n n n n
3 Q 1 SY 24V DC n – n n n
Q: signaling contact open/closed
1 S51 24V DC n – n – n
SY: trip position signaling contact 1 Q 1 SY 250V AC/DC n n n n n
3 2 Q 2 SY 1 S51 250V AC/DC n – n – n
S51: signaling contact due to trip unit 3 Q 2 SY 250V AC/DC n – n – n
tripping or interaction
3 Q 1 SY 250V AC/DC n – n n n
1 S51 250V AC/DC n – n – n
3 Q on left 250V AC/DC n n n n n
2 Q 1 SY 250V AC/DC n n n n n
1 Q 1 SY 400V AC n – n – n
2 Q 400V AC n – n – n
Uncabled auxiliary contacts 24V DC n n n n n
S51 24V DC n – n – n
250V AC/DC n n n n n
S51 250V AC/DC n – n – n
Auxiliary position contacts AUP - Inserted (24V and 250V) n n n n n
AUP - Withdrawn (24V and 250V) n – n – n
Early auxiliary contacts in the rotary handle AUE - 2 contacts closed n n n n n
AUE - 2 contacts open n n n n n
Motor operators MOD n n – n –
MOE n – n – n
MOE-E – – n – n
Residual current devices RC Inst – n – n –
RC Sel 200 – n – – –
RC Sel for XT1 XT3 – n – n –
RC Sel for XT2 XT4 – – n – n
RC B Type n – – n –
Ekip electronic trip unit accessories Ekip Display – – n – n
Ekip LED Meter – – n – n
Ekip Com – – n – n
HMI030 interface on the front of the switchboard – – n – n

Service releases
Shunt opening release (SOR). Allows the circuit breaker to be opened by means of a non-
permanent electrical control. Release operation is ensured for voltages between 70% and 110%
Cabled SOR - UVR of the rated power supply voltage Un, in both alternating and direct current. The SOR is equipped
with a built-in limit contact to shut off the power supply in the open position with the relay tripped.
A remote controlled emergency opening command can be created by connecting an opening
button to the SOR.

Undervoltage release (UVR). Allows the circuit breaker to open when the release is subjected
to either a power failure or a voltage drop. Opening is ensured when the voltage is between 70%
and 35% of the rated power supply Un. After tripping, the circuit breaker can be closed again
Cabled SOR - UVR
if the voltage exceeds 85% of Un. When the undervoltage release is not energized, neither the
for withdrawable circuit breaker
circuit breaker nor the main contacts can be closed. A remote controlled emergency opening
command can be created by connecting an opening button to the UVR.

Uncabled SOR - UVR

3/18 SACE Tmax XT UL/CSA | US Technical Catalog


None of the service releases in the Tmax XT series requires screws for installation. They are
extremely easy to fit. Just use slight pressure to snap the release into the appropriate place. All
service releases are available in two versions:
■ cabled (AWG20 cable section - 0.5mm 2):

– for fixed/plug-in circuit breakers with 1m long cables;


– for withdrawable circuit breakers with fixed part and moving part connector;
■ not cabled:

– for fixed/plug-in circuit breakers with cables from (1.5 mm2/14 AWG in section). 3

In circuit breakers:
■ three-pole: either one SOR or one UVR can be installed in the slot on the left of the operating
lever;
■ four-pole: two service releases can be installed at the same time by using the third and fourth

poles. If the circuit breaker is the withdrawable type, the connector for the fourth pole must be
ordered to be able to install an SOR or UVR in the fourth pole.

SOR SOR SOR


UVR UVR UVR

SOR Electrical specifications


Version Max power absorbed on inrush
AC [VA] DC [W]
12V DC 50
24-30V AC/DC 50 50
48-60V AC/DC 60 60
110...127V AC-110...125V DC 50 50
220...240V AC-220...250V DC 50 50
380-440V AC 55
480-525V AC 55

UVR Electrical specifications


Version Power absorbed during normal operation
AC [VA] DC [W]
24-30V AC/DC 1.5 1.5
48V AC/DC 1 1
60V AC/DC 1 1
110...127V AC-110...125V DC 2 2
220...240V AC-220...250V DC 2.5 2.5
380-440V AC 3
480-525V AC 4

US Technical Catalog | SACE Tmax XT UL/CSA 3/19


Accessories
Electrical accessories

Time delay device for undervoltage release (UVD)


The undervoltage release (UVD) can be combined with an external electronic power supply time
delay. This allows the circuit breaker opening to be delayed with preset and adjustable timing if
the power supply voltage of the release either drops or fails, thus preventing untimely tripping
caused by temporary faults. The time delay must be used with the undervoltage release (UVR) of
the corresponding voltage.
A remote control positive safety opening command can be created by connecting an opening
3 pushbutton to the UVR combined with the UVD.

Time delay device for UVD - Electrical specifications


undervoltage release
24...30V AC/DC
48...60V AC/DC
Power supply Voltage [V]
110...125V AC/DC
220...250V AC/DC
Settable delay [s] 0.25 - 0.5 - 0.75 - 1 - 1.25 - 2 - 2.5 - 3
Opening time tolerance ±15%

Auxiliary contacts
Contacts which allow information about the operating state of the circuit breaker to be routed
outside the circuit breaker. The following information is available:
■ open/closed: indication of the position of the circuit breaker power contacts (Q);
■ trip: signaling circuit breaker opening due to the current release tripping (owing to overload or

short-circuit), opening or undervoltage releases, emergency opening pushbutton of the motor


operator, or use of the test button (SY);
■ trip unit tripping: indicates that one of the protection functions of the electronic or thermal

magnetic trip unit has tripped (S51).

Changeover of auxiliary contacts Q (open/closed), SY (relay tripped) and S51 (trip unit tripping)
Normal sequence CB Open Q=12 SY=96 S51=06
CB Closed Q=14 SY=96 S51=06
Trip sequence CB Open Q=12 SY=96 S51=06
(trip caused by:
CB Closed Q=14 SY=96 S51=06
SOR, UVR, trip test)
CB Trips Q=12 SY=98 S51=06
CB Resets Q=12 SY=96 S51=06
Trip sequence CB Open Q=12 SY=96 S51=06
(trip caused by trip unit)
CB Closed Q=14 SY=96 S51=06
CB Trips Q=12 SY=98 S51=08
CB Resets Q=12 SY=96 S51=06

3/20 SACE Tmax XT UL/CSA | US Technical Catalog


3
Cabled auxiliary contact Uncabled auxiliary contact Cabled auxiliary contact for
withdrawable circuit breaker

24V DC and 250V AC/DC auxiliary contacts


250V AC/DC and 24VAC/ DC auxiliary contacts are installed without the need for screws. They
are extremely easy to fit. Simply use slight pressure to snap the auxiliaries into the appropriate
place. The following versions of auxiliary contacts are available:
■ cabled (AWG20 cable section - 0.5mm 2):

– for fixed/plug-in circuit breakers with 1m long cables;


– for withdrawable circuit breakers with fixed part and moving part connector;
■ heavy duty cabled (AWG20 cable section - 0.5mm 2):

– for applications requiring cable capacity to 600V;


– for fixed/plug-in circuit breakers with 1m long cables;
– for withdrawable circuit breakers with fixed part and moving part connector;
■ not cabled:

– for fixed/plug-in circuit breakers with cables from 0.5 up to 1.5 mm2 in section.
Auxiliary contacts are supplied for each circuit breaker in the SACE XT family in various
combinations, as shown in the table. The following items can be ordered to make installation even
more flexible:
■ a non-cabled auxiliary contact can create different signals (Q or SY) based on its position

within the circuit breaker;


■ a non-cabled S51 auxiliary contact, which can be used for XT2 or XT4 circuit breakers;
■ a cabled auxiliary contact, with non numbered cables. By changing the placement in the circuit

breaker, it’s possible to obtain different signals (Q or SY).


This version is available with standard cables and with a heavy duty (600V) cable option.

US Technical Catalog | SACE Tmax XT UL/CSA 3/21


Accessories
Electrical accessories

Combinations of cabled auxiliary contacts with XT1 XT2 XT3 XT4


numbered cables 3/4p 3/4p 3/4p 3/4p
1 Q + 1 SY 24V DC (1)
F-P F-P-W F-P F-P-W
3 Q + 1 SY 24V DC – F-P-W F-P F-P-W
1 S51 24V DC – F-P-W – F-P-W
1 Q + 1 SY 250V AC/DC (1)
F-P F-P-W F-P F-P-W
2 Q + 2 SY + 1 S51 250V AC/DC – F-P-W – F-P-W
3 3 Q + 2 SY 250V AC/DC – F-P-W – F-P-W
3 Q 1 SY 250V AC/DC – F-P-W F-P F-P-W
1 S51 250V AC/DC – F-P-W – F-P-W
3 Q on left 250V AC/DC F-P F-P F-P F-P
2 Q + 1 SY 250V AC/DC F-P F-P F-P F-P
F = Fixed, P = Plug-in, W = Withdrawable
(1)
Available in standard and HD versions

Auxiliary contacts 24V DC - 250V AC/DC


Circuit breaker 3p Circuit breaker 4p

2Q
2Q

3Q 1 SY
XT1 3Q 1 SY
on Left
on Left

3Q 3Q

1 SY 3Q 1 SY
XT3 3Q
on Left on Left

2 SY 2 SY

2Q 2Q
3Q 3Q
on Left on Left
XT2
XT4 1 S51 1 S51
or 1 Q or 1 Q

3/22 SACE Tmax XT UL/CSA | US Technical Catalog


AUX 250V AC/DC - Electrical specifications
Power supply Voltage Class of use (G2.16) Operating current [A]
[V] AC DC
110 AC/DC DC-12 – 0.5
DC-13 and DC-14 – 0.05
125 AC AC-12, AC-13, AC-14 6 –
AC-15 5 –
250 AC/DC AC-12 and DC-12 6 0.3 3
AC-13 and DC-13 6 0.03
AC-14 and DC-14 5 0.03
AC-15 4 –

AUX 24V DC - Electrical specifications


Power supply Voltage Operating current [A]
[V] DC
5 DC 0.01
24 DC 0.1

400V AC auxiliary contacts


400V AC auxiliary contacts are only available for XT2 and XT4 circuit breakers in the following
versions:
■ cabled (AWG17 cable section -1mm 2):

– for fixed/plug-in circuit breakers with 1m long cables;


– for withdrawable circuit breakers with fixed part and moving part connector.
Cabled auxiliary contact
The 400V auxiliary contacts take up the whole right-hand slot of the circuit breaker.

Combinations XT1 XT2 XT3 XT4


3/4p 3/4p 3/4p 3/4p
1 Q + 1 SY 400V – F-P-W – F-P-W
2 Q 400V – F-P-W – F-P-W
F = Fixed, P = Plug-in, W = Withdrawable

Cabled auxiliary contact for


Auxiliary contacts 400V AC
withdrawable circuit breaker
Circuit breaker 3p Circuit breaker 4p

AUX 400V AUX 400V


XT2
XT4

US Technical Catalog | SACE Tmax XT UL/CSA 3/23


Accessories
Electrical accessories

AUX 400V AC - Electrical specifications


Power supply Voltage [V] Class of use (G2.16) Operating current [A]
AC DC
125 DC DC-13 and DC-12 – 0.5
250 AC/DC AC-13 and AC-14 12 –
DC-12 and DC-13 – 0.3
400 AC AC-13 and AC-14 3 –
3

Auxiliary position contacts - AUP


These contacts allow information about the position of the circuit breaker relative to the fixed
part of plug-in or withdrawable versions to be routed outside the circuit breaker itself.
Two types of position contact (AUP) are available, at 250V AC/DC and 24V AC/DC:
■ racked-in contact for all plug-in and withdrawable SACE Tmax XT circuit breakers, to be

positioned in the fixed part;


■ racked-out contact for all withdrawable SACE Tmax XT2 and XT4 circuit breakers, to be

installed in the side part of the withdrawable version.


Auxiliary position
contact For further details about the electrical specifications of the contacts, consult the “24V DC and
250V AC contacts” section of this chapter.

Circuit breaker N° racked-in contact N° racked-out contact


XT1 3/4 poles 4 –
3 poles 2
XT2 2
4 poles 4
XT3 3/4 poles 4 –
XT4 3/4 poles 4 2

Plug-in circuit breaker with racked-in contact


104 102

101
S75I
(racked-in)
S57I=104 S75I=102

104 102 142 144 Withdrawable circuit breaker with racked-in/racked-out contacts

101 141
S75I S75E
(racked-in) (racked-out)
S75I=102 S75I=102 S75I=104
S75E=144 S75E=142 S75E=142

3/24 SACE Tmax XT UL/CSA | US Technical Catalog


Early make/break auxiliary contacts - AUE
Early contacts in relation to closing (early/make): allow the undervoltage release to be supplied
before the main contacts close, in accordance with the IEC 60204-1, VDE 0113 Standards.
Early contacts in relation to opening (early/break): allow any electronic devices connected to the
system that could be damaged owing to overvoltages generated by the circuit breaker opening
operation to be disconnected in advance.
The early opening/closing auxiliary contacts can be installed inside the direct and extended rotary
handle operating mechanisms for all the SACE Tmax XT circuit breakers (max two contacts @ 3
Early auxiliary contacts in the handle
400V):
– in the cabled version with 1m long cables (AWG20 cable sections);
– a dedicated code is available in the withdrawable version which includes the connector for the
moving part and fixed part.
For further details about the electrical specifications of the contacts, consult the “400V DC
contacts” section of this chapter.

Motor operators
Devices that allow circuit breaker opening and closing to be controlled:
■ in the remote mode, by means of electric controls;
■ locally, directly from the front, by means of special mechanisms.

MOD direct action motor operator

Circuit breaker
Position for key lock status signal ON-OFF
(key lock is not supplied)

Slot for padlock device

Slot for the operating lever


Direct action motor operator (MOD) AUTO-MANUAL selector

Lever case: under the cover


there is the thermal magnetic
trip unit rotary switch for setting
thermal protection
Test pushbutton

The direct action motor control is available for XT1 and XT3 and is supplied:
■ complete with 1m long cables;
■ with flange, to replace the standard one supplied with the circuit breaker;
■ with padlock device, only removable when the motor is in the open position. The padlock

device accepts up to three 8mm/0.31in padlocks;


■ auxiliary contacts (AU-MO) which allow the motor control mode (manual or auto) signal to be

routed outside;
■ (on request) the motor operator can be fitted with a key lock (consult the "Locks" section of

this chapter).

US Technical Catalog | SACE Tmax XT UL/CSA 3/25


Accessories
Electrical accessories

Operating principles:
■ a selector on the front of the MOD is used for selecting the operating mode:

– AUTO: when the selector is in this position, circuit breaker closing can only take place
remotely by means of an electric impulse, whereas opening is allowed both remotely and
from the front of the motor;
– MANUAL: when the selector is in this position, the circuit breaker can only be opened/
closed from the front of the motor by means of the corresponding lever housed in a slot
3 made in the motor itself;
■ operation of the motor operator via remote control is also ensured by permanent electrical

opening/closing impulses;
■ the resetting modes shown in the diagrams below depend on the reset wiring diagram chosen

by the customer (consult the reset wiring diagrams in the “Electric diagrams”) chapter.

Operating mode: Manual Operating mode: Auto

Close I: ON Close I: ON
SOR / UVR / SA SOR / UVR / SA
release tripping release tripping
move the move the OFF ON
Close O: OFF lever to lever to Close O: OFF pushbutton pushbutton
Reset Close remotely remotely
Move the lever OFF pushbutton
to Reset remotely

Reset O: OFF Reset O: OFF

Stored energy motor operators - MOE and MOE-E

Lever to recharge the springs


Transparent lock (optional installation)
Spring status signal: of the AUTO-MANUAL selector
charged springs/discharged springs (always supplied).

AUTO-MANUAL-LOCKED selector
Stored energy motor operators
(MOE) Circuit breaker status signal ON-OFF
Slot for padlock device

Opening pushbutton Closing pushbutton

The MOE or MOE-E stored energy motor operator is available for XT2 and XT4 and is supplied:
■ complete with 1m long cables;
■ complete with connector for the fixed part and moving part of withdrawable devices. If the

motor operator is used with fixed or plug-in circuit breakers, the connector can be easily
removed;
■ with flange, to use instead of the standard one supplied with the circuit breaker;
■ with padlock device, only removable when the motor is in the open position. The padlock

device accepts up to three 8mm/0.31in padlocks;


■ with lock of the AUTO-MANUAL selector;

3/26 SACE Tmax XT UL/CSA | US Technical Catalog


■ with auxiliary contacts (AUX-MO) that allow the motor’s control mode (manual or remote) signal
to be routed outside;
■ (on request) the motor operator can be fitted with a key lock (consult the "Locks" section in

this chapter);
■ (on request) the motor operator can be equipped with a lock to safeguard against manual

operation MOL-M (consult the "Locks" section in this chapter).

Operating principles: 3
■ a selector on the front of the MOE, is used for selecting the operating mode:

– AUTO: when the selector is in this position, the pushbuttons on the front of the motor are
locked. Circuit breaker closing can only take place remotely by means of an electric impulse,
whereas opening is allowed both remotely and from the front of the motor;
– MANUAL: the circuit breaker can only be opened/closed from the front of the motor using
the appropriate pushbuttons;
– LOCKED: when the selector is in this position, the circuit breaker is in the open position.
The padlock device can be withdrawn and the motor locked in the open position;
■ operation of the motor operator via remote control is also ensured by permanent electrical

opening/closing impulses. Once an opening command has been given, the next closing
command (permanent) is taken over by the motor operator once opening has been completed.
Likewise, an opening command is taken over once the previous closing operation has been
completed;
■ the resetting modes shown in the diagrams below depend on the reset wiring diagram chosen

by the customer (consult the reset wiring diagrams in the “Electric diagrams" chapter).
If the electronic trip unit (Ekip LSI, Ekip LSIG or Ekip E-LSIG) with Ekip Com module is used,
motor operator MOE-E can be used instead of motor operator MOE.
MOE-E allows the digital signals from the monitoring system to be used by means of the release
and Ekip Com contacts and to be converted into power signals for operating the motor operator.
All the features described above for the MOE motor operator are also valid for the MOE-E version.

Operating mode: Manual Operating mode: Auto

I: ON discharged springs I: ON discharged springs


OFF
SOR / UVR / SA pushbutton SOR / UVR / SA
release tripping on the release tripping
motor ON
OFF ON
pushbutton
O: OFF discharged springs on the
O: OFF discharged springs pushbutton pushbutton
remotely remotely
recharge motor OFF pushbutton
the springs remotely

O: OFF charged springs O: OFF charged springs

US Technical Catalog | SACE Tmax XT UL/CSA 3/27


Accessories
Electrical accessories

Changeover of auxiliary contacts Q (open/closed), SY (relay-tripped) and S51 (trip unit tripping)
Circuit breaker with MOE (MANUAL Mode)
Normal sequence CB Closed Q=14 SY=96 S51=06
By pressing the Red pushbutton, the CB trips Q=12 SY=98 S51=06
Charging the springs, CB opens Q=12 SY=96 S51=06
By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
Trip sequence CB Closed Q=14 SY=96 S51=06
3 (trip caused by:
CB trips Q=12 SY=98 S51=06
- SOR,
- UVR, Charging the springs, CB opens Q=12 SY=96 S51=06
- trip test) By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
Trip sequence CB Closed Q=14 SY=96 S51=06
(trip caused by
CB trips Q=12 SY=98 S51=08
trip unit)
Charging the springs, CB opens Q=12 SY=96 S51=06
By pressing the Green pushbutton, the CB Closes Q=14 SY=96 S51=06
Circuit breaker with MOE (AUTO Mode)
Normal sequence CB Closed Q=14 SY=96 S51=06
By pressing the Opening pushbutton remotely, Q=12 SY=98 S51=06
the CB opens
By pressing the Closing pushbutton remotely, Q=14 SY=96 S51=06
the CB Closes
Trip sequence CB Closed Q=14 SY=96 S51=06
(trip caused by: CB trips Q=12 SY=98 S51=06
- SOR,
- UVR, By pressing the Opening pushbutton remotely, Q=12 SY=96 S51=06
- trip test) the CB opens
By pressing the Closing pushbutton remotely, Q=14 SY=96 S51=06
the CB Closes
Trip sequence CB Closed Q=14 SY=96 S51=06
(trip caused by
CB trips Q=12 SY=98 S51=08
trip unit)
By pressing the Opening pushbutton remotely, Q=12 SY=96 S51=06
the CB opens
By pressing the Closing pushbutton remotely, Q=14 SY=96 S51=06
the CB Closes

Electrical specifications MOD MOE and MOE-E


Rated voltage, Un [V] – 24 DC – 24 DC
[V] – 48…60 DC – 48…60 DC
[V] 110…125 AC 110…125 DC 110…125 AC 110…125 DC
[V] 220…250 AC 220…250 DC 220…250 AC 220…250 DC
[V] 380...440 AC – 380...440 AC –
[V] 480...525 AC – 480...525 AC –
Operating Voltage [% Un] MIN=85% Un; MAX=110% Un
Power absorbed on inrush Ps [VA - W] ≤ 500 ≤ 500 ≤ 300 ≤ 300
Power absorbed in Pc service [VA - W] ≤ 300 ≤ 300 ≤ 150 ≤ 150
Operating frequency [Hz] 50..60 50..60
Duration (1) CL → OP [s] < 0.1 < 1.5
OP → CL [s] < 0.1 < 0.1
TR → OP [s] < 0.1 <3
Mechanical life [N° operations] 25000 25000
Minimum duration of electrical [ms] ≥ 150 ≥ 150
opening and closing command
(1)
Total time, from transmission of impulse to opening/closing of circuit breaker

3/28 SACE Tmax XT UL/CSA | US Technical Catalog


Connectors for electrical accessories
Plug-in circuit breaker
In the plug-in version of SACE Tmax XT circuit breakers, the auxiliary circuits can be disconnected
by means of two different types of adapter:
■ plug and socket adapter to be fixed on the bottom of the panel: for XT1, XT2, XT3, XT4;
■ plug and socket adapter installed on the rear of the circuit breaker and in the fixed part of plug-

in devices: for XT2, XT4. 3

Plug and socket adapters on the panel


To make it easier to connect/disconnect auxiliary circuits, wired electrical accessories can be
Plug and socket adapters connected to one or more plug and socket connectors to be installed on the back of the panel.
on the back of the panel 3, 6, 9 and 15-PIN connectors are available. The cables connect/disconnect to and from the
connector quickly and easily without any special tools.
Consider the number of cables each electrical accessory requires when calculating the number of
connectors needed.

Accessory Number of cables


SOR, UVR, External Neutral 2
1 AUX 3
AUE 4
MOE-E 5
Placked and socket adapter Ekip Com 6
placed on the back moving part
MOE (with AUX-MO), MOD (with AUX-MO) 7

Plug and socket adapters installed on the rear of the circuit breaker and in the fixed part
Only for the plug-in versions of Tmax XT2 and XT4 circuit breakers can the auxiliary circuits be
automatically disconnected. This is accomplished by an adapter installed on the rear of the circuit
breaker and in the fixed part of the plug-in version.
The 12-PIN connector can only be used with accessories that function at a voltage not exceeding
250V AC/DC. Cables are connected to/disconnected from the connector quickly and easily with
no special tools required. Wiring is to be carried out by the customer.
Plug and socket
adapter in the fixed part

Withdrawable circuit breaker


When withdrawable circuit breakers are used, the codes of the electrical accessories specifically
designed for this version must be ordered. These dedicated codes contain the wired electrical
accessory with connector for both the moving and the fixed parts to be inserted in the side of the
fixed part. If the MOE motor operator is ordered, connectors for the fixed part and moving part
are always supplied since there is no dedicated code for the withdrawable version.
Electrical accessory connectors for withdrawable circuit breakers must all be installed in housings on the
right-hand side of their fixed part. This type of connection allows for automatic disconnection of auxiliary
Cabling of withdrawable version circuits when the circuit breaker is withdrawn from the fixed part. If the customer wants to wire the fixed
part in advance of the moving part, mounting connectors for the fixed part can be ordered as spare parts.

US Technical Catalog | SACE Tmax XT UL/CSA 3/29


Accessories
Electrical accessories

Residual current releases


Both circuit breakers and switch-disconnectors are pre-engineered for assembly combined with
residual current releases.
Residual current circuit breakers, derived from the circuit breaker, are known as "mixed". In
addition to protecting against circuit breakers' typical overloads and short circuits, they also
protect people against ground fault currents. This, in turn, protects against direct and indirect
contact and the risk of fire.
3 Residual current circuit breakers, derived from the switch-disconnector, known as "pures". They
only provide residual current protection and not the protections typical of circuit breakers. “Pures”
are only sensitive to ground fault current and are generally used as main switches in small panels
for distribution to end users.
Using “pure” and “mixed” residual current circuit breakers allows for continuous monitoring of
the installation's insulation status. It ensures effective protection against the risk of fire, explosion
and, in the case of detecting fault at IΔn<30mA devices, also protects people against indirect
and direct contacts, incorporating compulsory measures established by the accident prevention
standards and regulations.
The residual current releases comply with the following Standards:
■ IEC 60947-2 annex B;
■ IEC 61000: for protection against unwarranted tripping.

The table shows all the residual current devices that can be used with the Tmax XT family of
circuit breakers:

XT1 XT2 XT3 XT4


3p 4p 3p 4p 3p 4p 3p 4p
RC Inst F F F F
RC Sel XT1-XT3 F F F F
RC Sel 200 F
Rc Sel XT2-XT4 F-P-W F-P-W
RC B type F
F = Fixed, P = Plug-in, W = Withdrawable

All Tmax XT residual current devices:


■ feature microprocessor technology and act directly on the circuit breaker by means of a dedi-

cated opening solenoid (supplied with the residual current release and also available as a spare
part) which must be housed in the corresponding slot in the third pole left of the operating lever;
■ do not need an auxiliary supply; they are powered directly from the mains;
■ can be supplied either from above or below;
■ functionality is ensured even with a single phase plus neutral or just two live phases and in the

presence of pulsating unidirectional currents with direct components (minimum auxiliary voltage
PHASE-NEUTRAL 85 Vrms);
■ all possible connection combinations are permitted, as long as the neutral connection to the first
pole on the left in the four-pole version is ensured.

3/30 SACE Tmax XT UL/CSA | US Technical Catalog


RC Sel 200 residual current releases (type A) XT1
Thanks to its low height, the RC Sel 200 residual current release can be installed in 200mm
modules. Its special shape also reduces the installation's footprint if two or more units are to be
installed side by side.

Power-on LED
Current setting
Alarm and pre-alarm
signal LED
Time of non-trip setting
Magnetic indicator of
residual current trip Test pushbutton

Disconnection device for


insulation test

RC Inst residual current releases for XT1 and XT3

Power-on LED

Current setting

Magnetic indicator for


residual current trip

Test pushbutton

Disconnection device
for the insulation test

US Technical Catalog | SACE Tmax XT UL/CSA 3/31


Accessories
Electrical accessories

RC Sel residual current releases (type A) for XT1 and XT3

3 Power-on LED

Alarm and pre-alarm Current setting


signal LED
Time of non-trip setting
Magnetic indicator of
residual current trip
Test pushbutton

Disconnection device
for insulation test

With RC Inst and RC Sel residual current release for XT1 - XT3, available only in Fixed version, it
is possible to have rear terminal connection, by ordering RC Rear terminals 4p kits.

Current setting

Power-on LED

Alarm and pre-alarm Test pushbutton


signal LED

Magnetic indicator of Disconnection device for


residual current trip insulation test

Time of non-trip setting

3/32 SACE Tmax XT UL/CSA | US Technical Catalog


RC Sel residual current releases (type A) for XT2 and XT4
The fixed version of the RC Sel residual current release can easily be converted:
■ into the plug-in type:

– by ordering the kit for converting the residual current release from the fixed to the plug-in version;
■ into the withdrawable type:

– by ordering the kit for converting the residual current release from the plug-in to the
withdrawable version. This kit contains the shunt opening release of the withdrawable
residual current device to replace the one supplied with the fixed version. The shunt opening 3
release of the withdrawable residual current device contains connectors for both the moving
and fixed parts. The 160A frame with residual current withdrawable breaker can be used up
to a maximum current of 135A; the 250A frame can be used up to 210A.
With the RC Sel residual current release for XT2-XT4, it is possible to use the same terminals for the
fixed circuit breaker and for the fixed parts of plug-in and withdrawable circuit breakers.

RC B Type residual current release (type B) for XT3

Current setting

Power-on LED
Test pushbutton
LED signaling alarm
and pre-alarm

Setting fault frequencies


Magnetic indicator of
residual current device trip

Setting non-tripping times

The RC B Type residual current release, to be used in conjunction with the XT3 circuit breaker,
has the following features:
■ it complies with type B operation, which guarantees sensitivity to residual fault currents with

alternating, pulsating alternating and direct current components (IEC 60947-1, IEC 60947-2
Annex B, IEC 60755);
■ the maximum frequency band of the residual fault current can be selected (3 steps: 400

- 700 - 1000Hz). The residual current device can therefore be adapted to suit various
industrial installation requirements according to the prospective fault frequencies generated
on the load side of the release. Typical installations that may require different frequency
thresholds from the standard ones (50 - 60Hz) are welding systems for the automobile
industry (1000Hz), the textile industry (700Hz), airports and three-phase drives (400Hz)
■ UL Listed.

US Technical Catalog | SACE Tmax XT UL/CSA 3/33


Accessories
Electrical accessories

Electrical characteristic Residual current devices


RC Sel 200mm RC Inst RC Sel RC Sel RC B Type
XT1 XT1-XT3 XT1-XT3 XT2-XT4 XT3
Primary power supply Voltage [V] 85…690 85…690 85…690 85…690 110…500
Operating frequency [Hz] 45…66 45…66 45…66 45…66 45…66
Fault frequency [Hz] 50-60 50-60 50-60 50-60 400-700-1000
Test operating range [V] 85…500 85…500 85…500 85…690 110…500
XT1 up to 160 up to 160 XT1 up to 160 XT2 (2)
3 Rated operating current [A] up to 160
XT3 up to 250 up to 250 XT3 up to 250 XT4(2)
up to 225

0.03-0.05-0.1-0.3 0.03-0.1-0.3 0.03-0.05-0.1-0.3 0.03-0.05-0.1-0.3 0.03-0.05-0.1


Adjustable trip thresholds [A]
0.5-1-3-5-10 0.5-1-3 0.5-1-3-5-10 0.5-1-3-5-10 0.3-0.5-1
Selective type S n – n n n
instantaneous instantaneous instantaneous instantaneous
Adjustable NON-trip time settings [s]
0.1-0.2-0.3- instantaneous 0.1-0.2-0.3- 0.1-0.2-0.3- 0-0.1-0.2-0.3-
at 2xIΔn
0.5-1-2-3 0.5-1-2-3 0.5-1-2-3 0.5-1-2-3
Power input <10 W at 500V AC <8 W at 500V AC <10 W at 500V AC <5 W at 500V AC <10 W at 500V AC
Trip Coil with switch contact for trip signal n n n n n
Input for remote controlled opening command n – n n n
NO contact for pre-alarm signal n – n n n
NO contact for alarm signal n – n n n
Prealarm indication from 25% IΔn.
n – n n n
Steady yellow LED light
Alarm timing indication at 75% IΔn.
n – n n n
Flashing yellow LED light (1)
Type A for pulsating alternating current,
n n n n n
Type AC for alternating current
Type B for pulsating current and direct current – – – – n
(1)
indication of alarm timing at 90% IΔn for 30mA
(2)
plug-in and withdrawable version: the 160 frame can be used with a max In = 135A
the 250 frame can be used with a max In = 210A

SACE RCQ020/A panel type residual current release (type A)


Tmax circuit breakers can also be used in conjunction with RCQ020 panel type residual current
relays with separate toroid to be installed on the line conductors ("/A" letter show the necessity to
have on auxiliary power supply).
Thanks to its wide range of settings, the panel relay is suitable for:
■ applications where the installation conditions are particularly restrictive, such as circuit

breakers already installed or limited space in the circuit breaker compartment;


■ creating a residual current protection system coordinated at various distribution levels, from the
Toroid main switchboard to the end user;
■ where residual current protection with low sensitivity is required, e.g. in partial (current) or total

(time) selective chains;


■ highly sensitive applications (physiological sensitivity) for protecting people against direct

contacts.
Thanks to the 115-230...415V external auxiliary power supply, the RCQ020 panel-type residual
current device is able to detect current leakage from 30mA to 30A and to act with a trip time that
can be adjusted from instantaneous to delayed by 5s. The opening mechanism is the indirect
action type and acts on the circuit breaker release mechanism by means of the shunt opening or
undervoltage release of the circuit breaker itself.
The opening command to the circuit breaker (Trip delay) can be temporarily inhibited, and the
circuit breaker can be opened by remote control by means of the RCQ020 device.
The following equipment must be requested when ordering:
■ the RCQ020 device;
■ an opening coil (SOR) or an undervoltage release (UVR) of the circuit breaker to be housed in

the corresponding slot in the left pole of the circuit breaker itself;
■ a closed toroid with a diameter from 60mm to 185mm that can be used for cables and

busbars.
3/34 SACE Tmax XT UL/CSA | US Technical Catalog
Signals available:
■ LED to indicate the residual current device's status (supplied or not supplied). RCQ02 is

equipped with a positive safety function that commands automatic circuit breaker opening in
the absence of auxiliary voltage;
■ LED for signaling faults;
■ LED for signaling tripping of the residual current device;
■ pre-alarm/alarm/trip electrical signals.

LED signaling the


status of the residual
Protection threshold current device
from 30mA at 30A

Trip time adjustable Dip-switch to set the


from instantaneous to 5s signaling status

Test pushbutton Reset pushbutton

RCQ020/A residual current release


Power supply Voltage AC [V] 115-230...415
Operating frequency [Hz] 45÷66Hz
@115V AC 500mA for 50ms
Inrush current @230V AC 150mA for 50ms
@415V AC 100mA for 50ms
Power input at full rate 2 [VA] / 2 [W]
Trip threshold adjustment IΔn [A] 0.03-0.05-0.1-0.3-0.5-1-3-5-10-30
No trip time adjustment [s] instantaneous 0.1-0.2-0.3-0.5-0.7-1-2-3-5
Pre-alarm threshold x IΔn 25%
A type for pulsing alternate current n
Signals
Device powered visual signaling n
Visual signaling of device not functioning/ not
n
configured
Visual signaling of residual current protection n
Electrical alarm/pre-alarm signal n
Electric trip signal n
Controls
Remotely controlled opening command n
Remotely controlled reset command n
Operating range of closed transformers
In max = 250A
Ø 60 [mm] toroidal transformer [A]
Use 0.03..30A
In max = 400A
Ø 110 [mm] toroidal transformer [A]
Use 0.03..30A
In max = 800A
Ø 185 [mm] toroidal transformer [A]
Use 0.1..30A
By means of 4 shielded or twisted conductors.
Connection to toroidal transformer
Maximum tolerated length: 15m
Dimensions W x H x D [mm] 96 x 96 x 77
Drilling for assembly on door [mm] 92 x 92
Standard IEC 60947-2 annex M

US Technical Catalog | SACE Tmax XT UL/CSA 3/35


Accessories
Accessories for electronic trip units

Accessories for electronic trip units


Ekip Display Ekip LED Meter External neutral
Distribution protection
Ekip LS/I – – –
Ekip LSI n n n
Ekip LSIG n n n
Motor protection
3 Ekip M-LIU – – –
Ekip I – – –
Energy measurement
Ekip E-LSIG n n n

Ekip Display
This unit can be installed on the front of the solid state trip unit to show current values, alarms
and protection/communication parameter programming.

Display

Power-on LED

Fixing device

Slot for lead seal


Ekip TT or Ekip T&P
connector Display pushbutton

Main features:
■ installation: Ekip Display can easily be installed on the front of the Ekip LSI, Ekip LSIG and Ekip

E-LSIG electronic trip units. It is connected by means of the test connector on the front of the
trip unit. Installation is simple and reliable thanks to a specially designed mechanism. It also
provides a practical way of fastening the accessories to the circuit breaker in order to prevent
undesired access to the dip-switches. Installation can be carried out under any conditions, even
with the door closed and the electronic trip unit already on and functioning;
■ functions: Ekip Display has four buttons for browsing through the menus. It functions in the

self-supply mode starting from a current of I>0.2xIn circulating through at least one phase.
Backlighting is activated in the presence of higher loads, making displayed information more
legible. Backlighting comes on in self-supply for a current I>0.4xIn and is always on when there
is electronic trip unit auxiliary power supply.
Ekip Display:
– shows the current, voltage, power and energy values;
– shows the settings of the protection functions in Amperes or in In;
– shows the protection that caused the release to trip and the fault current (only when there is
24V external voltage or the Ekip TT unit);
– allows the trip thresholds of the trip unit to be programmed and the communication
parameters to be set on bus system;
■ compatibility: Ekip Display can be fitted even when front accessories, such as the motor,

direct and transmitted rotary handles etc. are already installed. It's possible to use Ekip TT
or Ekip T&P without removing Ekip Display. It's not possible to use Ekip Displaywith the
withdrawable version of circuit breaker.

3/36 SACE Tmax XT UL/CSA | US Technical Catalog


Ekip LED Meter
The Ekip LED Meter can be applied to the front of the electronic trip unit. It displays the current
values and alarms.

L, S, I, G protection LED

Power-on LED
3
Ekip TT or Ekip Fixing device
T&P connector

Slot for lead seal


LED signaling the % of
current for each phase Timing LED

Main features:
■ installation: Ekip LED Meter can be easily installed on the front of Ekip LSI, Ekip LSIG and

Ekip E-LSIG electronic trip units. It is connected by means of the test connector on the front
of the release. Installation is simple and reliable thanks to a specially designed mechanism. It
also provides a practical way of fastening accessories to the circuit breaker in order to prevent
undesired access to dip-switches. Installation can be carried out under any conditions, even
with the door closed and the electronic trip unit already on and functioning;
■ functions: Ekip LED Meter provides an accurate indication of the value of the current

circulating in the trip unit. It does this by means of Its. Its different colors allow the normal
operation, prealarm and alarm states of the circuit breaker to be recognized at a glance. It
functions in self-supply mode from a current of I>0.2xIn circulating through at least one phase
or when electronic trip unit’s auxiliary power is available;
■ compatibility: the Ekip LED Meter can also be fitted with front accessories, such as the motor,

direct and transmitted rotary handles. Ekip TT or Ekip T&P can be used without removing Ekip
LED Meter. Ekip LED Meter cannot be used when the breaker is in the withdrawable version.

Current sensor for external neutral


The current sensor for external neutral is applied to the uninterrupted neutral conductor. It allows
neutral current for all protection functions to be read.
Main features:
■ installation: the external neutral current sensor is available for XT2 and XT4 three-pole circuit

breakers in the fixed/plug-in and withdrawable version equipped with an Ekip LSI or an Ekip
LSIG electronic trip unit. The sensor must be connected to the release with the specific
connector, which must be ordered separately.

Connection accessories
Devices that allow the electronic trip unit to be connected to external plant units or components.
These connectors are available for the circuit breakers in fixed, plug-in and withdrawable versions.

Name of connector Trip Units


External neutral connector Ekip LSI – Ekip LSIG – Ekip E-LSIG
Connector for 24V DC auxiliary power supply Ekip LSI – Ekip LSIG – Ekip E-LSIG

The connector for the auxiliary power supply is inserted inside the right-hand slot of the circuit
breaker, and occupies the space of two due auxiliary contacts. To check compatibility with the
Connector for 24V
auxiliary contacts, consult the compatibility tables in this chapter.

US Technical Catalog | SACE Tmax XT UL/CSA 3/37


Accessories
Communication devices and systems

HMI030 interface on the front of the switchboard


HMI030 is an interface on the front of the switchboard and is usable with protection trip units
fitted with Ekip Com.

LED signaling the % of current for each phase

3 Alarm LED

Display

Display pushbutton

Main features:
■ installation: HMI030 can be fitted into the hole in the door using the automatic click-in

method. In situations where mechanical stress is particularly intense, it can also be installed
by using the special clips supplied. It must be connected directly to the Ekip LSI, Ekip LSIG
or Ekip E-LSIG protection trip unit with Ekip Com via the serial communication line. HMI030
requires a 24V DC power supply;
■ functions: HMI030 consists of a graphic display and 4 buttons for browsing through the

menus. This accessory allows you to view:


– the measurements taken by the release to which it is connected;
– the alarms/events of the release.
Thanks to its high level of accuracy, the same as that of the trip unit protection, the device is a
valid substitute for conventional instruments without any additional current transformers.
■ communication: HMI030 is provided with two communication lines. Either one can be used.

– Modbus
– Local Bus.
Connecting Ekip LSI, Ekip LSIG or Ekip E-LSIG to the Local Bus allows the Modbus line to be
connected to a different communication network.
Consult the "Electrical diagrams" chapter for further details about wiring.

3/38 SACE Tmax XT UL/CSA | US Technical Catalog


Ekip Com
Ekip Com allows the MOE-E motor operator to be controlled, determines the
ON/OFF/TRIP state of the circuit breaker and connects the electronic trip unit to a Modbus
communication line.
Ekip Com is available in two versions: one for fixed/plug-in circuit breakers and one, complete
with connectors for both the fixed and moving parts, for withdrawable circuit breakers.
Main characteristics:
■ installation: the Ekip Com module is inserted into the special area in the right-hand pole of the 3
circuit breaker and can be fastened without screws or tools.
To connect with the trip unit, a special cable that is fitted with a cable guide is used to ensure
an easy and safe installation. The Modbus line is connected by means of a terminal box, to
which a 24V DC auxiliary power supply must be connected. The connection of the Modbus line
is made by means of the terminal box to which a 24V DC auxiliary power supply must also be
connected. The auxiliary power activates both the module and the protection trip unit;
■ functions: the Ekip Com module allows for remote reading of the circuit breaker’s status. In

combination with an MOE-E motor operator, it can open/close the circuit breaker remotely.
Combined with a trip unit fitted with a communication device (Ekip LSI, Ekip LSIG or Ekip
E-LSIG), the Ekip Com module allows the trip unit’s connection to a Modbus network. This
allows protections to be programmed, measurements to be taken and alarms to be sent when
it’s connected to a control and/or monitoring system. Connected to the HMI030 interface,
these data can be displayed directly on the front of the switchboard.
For further details on the communication systems which can be made by means of the Ekip Com
module, refer to the “Communication systems” section in the “Ranges” chapter.

Ekip Com
Circuit breaker 3p Circuit breaker 4p

Ekip Com Ekip Com


XT2
XT4

US Technical Catalog | SACE Tmax XT UL/CSA 3/39


Accessories
Communication devices and systems

Ekip Connect
Installation and diagnosis software for ABB SACE products with Modbus RTU communication.
The software can be used during the commissioning stage, or for troubleshooting in an up and
running communication network.

Ekip Connect automatically scans the RS-485 bus, detects all the connected devices and checks
their configuration, all possible addresses, parity and baud rate combinations. A simple click over
SCAN will highlight:
■ devices that fail to respond;
■ configuration errors;
■ incorrect addresses and parity;
■ any wiring errors (with the SACE electronic trip unit);

achieving a complete diagnosis of the communication network.


This user-friendly software makes installing the Modbus communication network very easy.
Ekip Connect can be downloaded free of charge from the BOL (http://bol.it.abb.com) or ABB
(www.abb.com) websites.

3/40 SACE Tmax XT UL/CSA | US Technical Catalog


Accessories
Test and configuration accessories

Ekip T&P
Ekip T&P is a kit used to monitor, configure and test electronic protection trip units.
The kit includes:
■ Ekip T&P unit;
■ Ekip TT unit;
■ Adapters for Emax and Tmax trip units;
■ USB cable for connecting the Ekip T&P unit to the electronic trip unit;
■ CD for installing Ekip Connect and the Ekip T&P driver. 3
The Ekip T&P unit is connected on one side to the USB port of a PC and on the other, by means
Ekip T&P
of a cable provided, to the protection trip unit of the SACE Tmax XT series.
The Ekip T&P unit allows automatic, manual and trip tests of the device it is connected to. These
functions are managed by means of the Ekip T&P Interface which can only be activated directly
by the Ekip Connect when the Ekip T&P is present and connected to the PC.

Ekip TT
The Ekip TT accessory is supplied with a special connector to facilitate connection between the
electronic trip unit and the Ekip TT unit. The kit also includes an adapter that allows the Ekip TT
unit to be used with the current Tmax breakers.
Ekip TT is a device which allows:
■ verification that the electronic trip unit's opening solenoid and the circuit breaker's trip

mechanism (trip test) are functioning properly;


■ testing the LEDs on the electronic trip unit it's connected to;
■ supplying auxiliary power to show the most recent protection interruption in the event of an
Ekip TT
intervention by the electronic unit. Simply linking Ekip TT to the electronic trip unit (or to the
Ekip display or Ekip LED Meter), illuminates the LED light on the most recently interrupted
protection.
Its reduced dimension makes it pocket sized.

Ekip T&P functions Ekip TT functions


Trip Protection Parameter Protection Communication Thermal Trip LED Latest trip
test function reading parameter parameter memory test test detection
test programming programming enabling/
disabling
Distribution protection
Ekip LS/I n n n – – n n n n
Ekip LSI n n n n n n n n n
Ekip LSIG n n n n n n n n n
Ekip E-LSIG n n n n n – n n n
Motor protection
Ekip M-LIU n n n – – – n n n
Ekip I n n n – – – n n n

US Technical Catalog | SACE Tmax XT UL/CSA 3/41


Accessories
Automatic network-generator transfer unit ATS021-ATS022

The ATS (Automatic Transfer Switch) is the network-generator transfer unit used in installations
where switching the main power line to an emergency one is required, in order to ensure power
supply to the loads in the case of anomalies in the main line.
The unit is able to manage the entire transfer procedure automatically, and prepares the
commands for carrying out the procedure manually as well.
In the case of an anomaly in the main line voltage, in accordance with the parameters set by the
user, the opening of the circuit breaker of the main line, the starting of the generator set (when
3 ATS021 provided) and the closing of the emergency line are performed. In the same way, in the case of
the main line returning, the procedure of reverse transfer is controlled automatically.
The new generation of ATS (ATS021 and ATS022) offers the most advanced and complete
solutions to ensure service continuity. The ATS021 and ATS022 can both be used with all the
circuit breakers in the SACE Tmax XT family and with the switch-disconnectors.
ATS021 and ATS022 devices have been designed to operate on self-supply. The ATS022 unit
also prepares the connection for auxiliary power supply, allowing additional functions to be used.
ATS021 and ATS022 devices control both of the the power supply lines and analyze:
■ phase unbalance;
■ frequency unbalance;
■ phase loss.

Apart from its standard control functions, the ATS022 unit makes it possible to:
■ select the priority line;
ATS022
■ controlling a third circuit breaker;
■ incorporate it into a monitoring system with Modbus communication (auxiliary power supply is

needed);
■ read/set parameters and show measurements and alarms on a graphic display.

Typical applications include: power supply to UPS (Uninterrupted Power Supply) units, operating
rooms and primary hospital services, emergency power supply for civil buildings, airports, hotels,
data banks and telecommunication systems, power supply of industrial lines for continuous
processes.
For correct configuration, each circuit breaker connected to the ATS021 or ATS022 must be fitted
with the following accessories:
■ mechanical interlock;
■ motorized control of opening and closing;
■ key lock against purely manual operation for the motor operator;
■ contact for signaling the status (open/closed) and contact for tripped;
■ contact for racked-in (in the case of a withdrawable version circuit breaker).

3/42 SACE Tmax XT UL/CSA | US Technical Catalog


Accessories
Test and configuration accessories

ATS021 ATS022
General
Auxiliary Power Supply Not Required Not Required
(24-110V DC is required only for Modbus
dialog and 16 2/3 Hz system)
Rated Voltage, Un [VAC] Max 480 Max 480
Frequency [Hz] 50, 60 16 2/3, 50, 60, 400
Dimensions (HxLxD) [mm] 96x144x170 96x144x170
3
Type of installation Door mounting Door mounting
DIN-rail mounting DIN-rail mounting
Operating Mode Auto/Manual Auto/Manual
Features
Monitoring of the Normal and Emergency lines n n
Controlling CBs of the Normal and Emergency lines n n
Generator set startup n n
Generator set shutdown with adjustable delay n n
Bus-tie – n
No-priority Line – n
Modbus RS485 – n
Display – n
Ambient conditions
Operating temperature -20…+60 °C -20…+60 °C
Humidity 5% - 90% without condensation 5% - 90% without condensation
Align flush left thresholds
Minimum voltage -30%…-5%Un -30%…-5%Un
Maximum voltage +5%…+30%Un +5%…+30%Un
Fixed frequency thresholds -10%…+10%fn -10%…+10%fn
Test
Test Mode n n
Compliance with standards
Electronic equipment for use in power installations EN-IEC 50178 EN-IEC 50178
Electromagnetic compatibility EN 50081-2 EN 50081-2
EN 50082-2 EN 50082-2
Environmental conditions IEC 68-2-1 IEC 68-2-1
IEC 68-2-2 IEC 68-2-2
IEC 68-2-3 IEC 68-2-3

US Technical Catalog | SACE Tmax XT UL/CSA 3/43


Accessories
Compatibility of accessories

3p
Check whether the different devices are compatible/incompatible with each other when ordering
accessories. The following table provides a simple check between:
■ mechanical accessories, accessories for electronic trip units and motors;
■ internal electrical accessories.

To better understand the abbreviations used to identify the accessories, refer to the “Symbols”
paragraph in chapter 8, “Glossary”.

Three-pole circuit breaker Example of reading the compatibility tables


Fixed/plug-in circuit breaker compatibility XT1-XT3
SOR UVR 3Q SOR UVR .....
3p 3p 3p 4p 4p
SOR 3p ✔ ✔
4p 3p UVR 3p
1 2 3 4

5

6

3Q sx 3p ✔ ✔
SOR 4p ✔ ✔ ✔ ✔
UVR 4p ✔ ✔ ✔ ✔
.....

The UVR positioned in the slot of the 3rd pole(1) is:


– incompatible with the SOR positioned in the 3rd pole(2);
– incompatible with the UVR positioned in the 3rd pole(3);
– incompatible with the 3Q contacts on the left in the 3rd pole(4);
Four-pole circuit breaker
– compatible with the SOR positioned in the slot of the 4th pole(5);
– compatible with the UVR positioned in the slot of the 4th pole(6).
– ....

Compatibility of mechanical accessories


RHD RHE RHS FLD PLL KLC KLC KLC MOD/ Ekip Ekip SOR/ 1Q+ 2Q+ 3Q+
on on on on MOE/ Display LED UVR/ 1 SY 1 SY 1 SY
CB CB RHX FLD MOE-E Meter 3 Form
C/Q L 3p
RHD ✔ ✔ ✔ ✔ ✔ ✔ ✔
RHE ✔ ✔ ✔ ✔ ✔ ✔ ✔
RHS ✔ ✔ ✔ ✔ ✔ ✔
FLD ✔ ✔ ✔ ✔ ✔ ✔ ✔
PLL on CB ✔ ✔ ✔ ✔ ✔ ✔
KLC on CB ✔ ✔ ✔ ✔ ✔
KLC on RHX ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
KLC on FLD ✔ ✔ ✔ ✔ ✔ ✔ ✔
MOD/MOE/MOE-E ✔ ✔ ✔ ✔ ✔ (1)
✔ (2)

Ekip Display ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Ekip LED Meter ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SOR/PS-SOR/UVR/3 Form C/Q L ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
1 Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
2/Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (1)
✔ ✔ ✔
3 Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (2)
✔ ✔ ✔

✔ Compatibility (1)
Not valid for XT1 (2)
Not valid for XT3

3/44 SACE Tmax XT UL/CSA | US Technical Catalog


Compatibility of electrical accessories
Fixed/plug-in circuit breaker compatibility XT1-XT3
SOR UVR SA 3QL SA SOR UVR 3QL 1Q+ 2Q+ 3Q+ KLC MOD
3p 3p 3p 3p 3p 4p 4p 4p 1 SY 1 SY 1 SY on CB
SOR 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔
UVR 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔
3 Q L 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔
SA 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔
3
SOR 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
UVR 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
3 Q L 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
1 Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
2 Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (1)

3 Q + 1 SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
KLC on CB ✔ ✔ ✔ ✔ ✔ ✔
MOD ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (1)

✔ Compatibility (1)
Not valid for XT1

Fixed/plug-in circuit breaker compatibility XT2-XT4


SOR UVR 3Q sx SA AUE SOR UVR 3Q sx S51 1Q 2Q 3Q 3Q 2Q 400V 400V 24V Ekip KLC
3p 3p 3p internal 4p 4p 4p 1SY 1SY SY 2SY 2SY 2Q 1Q Com on CB
3p 1S51 1SY
SOR 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
UVR 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
3Q sx 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SA ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
AUE internal 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SOR 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
UVR 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
3Q sx 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
S51 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
1Q 1SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
2Q 1SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
3Q 1SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
3Q 2SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
2Q 2SY 1S51 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
400V 2Q ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
400V 1Q 1SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
24V ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Ekip Com ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
KLC on CB ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
✔ Compatibility

US Technical Catalog | SACE Tmax XT UL/CSA 3/45


Accessories
Compatibility of accessories

Withdrawable circuit breaker compatibility XT2-XT4


S51 1Q 3Q 3Q 2Q 400V 400V Ekip 24V NE MOE MOE-E AUX- AUE SOR UVR SA SOR UVR
1SY 1SY 2SY 2SY 2Q 1Q Com MOE 3p 3p 4p 4p
S51 1SY
S51 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
1Q 1SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
3Q 1SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔

3 3Q 2SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
2Q 2SY S51 ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
400V 2Q ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
400V 1Q 1SY ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
Ekip Com ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
24V ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
NE ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
MOE ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔(1) ✔ ✔ ✔ ✔ ✔
MOE-E ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔(1) ✔ ✔ ✔ ✔ ✔
AUX-MOE ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ (1)
✔ (1)
✔ ✔ ✔
AUE ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SOR 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
UVR 3p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SA ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
SOR 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
UVR 4p ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔
✔ Compatibility AUX-MOE always supplied with MOE and MOE-E
(1)

3/46 SACE Tmax XT UL/CSA | US Technical Catalog


Ordering information for XT1, XT2, XT3, XT4 UL/CSA
Accessories

Fixed parts, conversion kits and accessories for fixed parts


Fixed part of plug-in (P)
XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
Kit P FP EF KXT1PFPEF-3 KXT1PFPEF-4 KXT2PFPEF-3 KXT2PFPEF-4 KXT3PFPEF-3 KXT3PFPEF-4 KXT4PFPEF-3 KXT4PFPEF-4
Kit P FP HR/VR (1) KXT1EPFPHR-3 KXT1EPFPHR-4 KXT2EPFPHR-3 KXT2EPFPHR-4 KXT3EPFPHR-3 KXT3EPFPHR-4 KXT4EPFPHR-3 KXT4EPFPHR-4
Fixed part of
(1)
IEC rated only. Terminals are factory-mounted in the horizontal position (HR).
plug-in

Fixed part of withdrawable (W)


XT2 XT4
Type 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number
Kit W FP EF KXT2WFPEF-3 KXT2WFPEF-4 KXT4WFPEF-3 KXT4WFPEF-4
Fixed part of Kit W FP HR/VR (1) KXT2EWFPHR-3 KXT2EWFPHR-4 KXT4EWFPHR-3 KXT4EWFPHR-4
withdrawable (1)
IEC rated only. Terminals are factory-mounted in the horizontal position (HR).

Terminals for the fixed parts (1)


XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
EF-Front extended
7 terminals
KXT1EEFFP-3 KXT1EEFFP-4 KXT2EEFFP-3 KXT2EEFFP-4 KXT3EEFFP-3 KXT3EEFFP-4 KXT3EEFFP-3 KXT3EEFFP-4
R-Rear terminals
KXT1ERFP-3 KXT1ERFP-4 KXT2ERFP-3 KXT2ERFP-4 KXTEERFP-3 KXTEERFP-4 KXTEERFP-3 KXTEERFP-4
HR/VR
EF terminals PS - Rear phase
for fixed part separators KXTAEPB90-3 KXTAEPB90-4 KXTAEPB90-3 KXTAEPB90-4 KXTAEPB90-3 KXTAEPB90-4 KXTAEPB90-3 KXTAEPB90-4
90mm/3.54in
(1)
IEC rated only.

Conversion kit of the circuit breaker from fixed into moving part of plug-in
XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
P MP kit KXT1PMP-3 KXT1PMP-4 KXT2PMP-3 KXT2PMP-4 KXT3PMP-3 – KXT4PMP-3 KXT4PMP-4
Conversion kit

Conversion kit of the circuit breaker from fixed into moving part of withdrawable
XT2 XT4
Type 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number
W MP kit KXT2WMP-3 KXT2WMP-4 KXT4WMP-3 KXT4WMP-4

7/18 SACE Tmax XT UL/CSA | US Technical Catalog


Conversion kit of the fixed part from plug-in to withdrawable
XT2 XT4
Catalog number Catalog number
Conversion kit FP P>W kit KXT2FPPtoFPW KXT4FPPtoFPW
for turning a fixed
circuit breaker into
the moving part
of a withdrawable Adapter for mounting the terminals of the fixed circuit breaker on the fixed part
circuit breaker XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
ADP adapter for fixed
parts KXT1ADP-3 KXT1ADP-4 KXT2ADP-3 KXT2ADP-4 KXT3EADP-3 KXT3EADP-4 KXT4ADP-3 KXT4ADP-4
Fixed part (2 pieces)
adapter Note: when using ADP with ES/MC terminals, also order “Kit F Front Terminals”

Conversion kit of RC Sel from fixed to plug-in (1)


XT2 XT4
Type 4P 4P
Catalog number Catalog number
P MP RC Sel 4P kit KXT2EPMPRC-4 KXT4EPMPRC-4
(1)
IEC rated only.

7
Conversion
kit for turning Conversion kit of RC Sel from plug-in to withdrawable (1)
a fixed circuit XT2 XT4
breaker into the Type 4P 4P
moving part of Catalog number Catalog number
a plug-in circuit W MP RC Sel 4P kit KXT2WFPEF-4 KXT4EWMPRC-4
breaker (1)
IEC rated only.

Key lock for fixed part of withdrawable (1)


XT2, XT4
Catalog number
KL-D key lock FP, different keys KXTCEKLDFPW
KL-S key lock FP, same keys N.20005 KXTCEKLSFPW
Key lock/padlock
(1)
IEC rated only.
for fixed part

Ronis key lock for fixed part of withdrawable (1)


XT2, XT4
Catalog number
KL-D Ronis FP key lock, different keys KXTCEKLDRonFPW
KL-S Ronis FP key lock, same type A keys KXTCEKLSRonFPW
(1)
IEC rated only.
Ronis key lock/
padlock for
fixed part

US Technical Catalog | SACE Tmax XT UL/CSA 7/19


Ordering information for XT1, XT2, XT3, XT4 UL/CSA
Accessories

Service releases
Shunt opening trip - SOR
XT1, XT2, XT3, XT4 XT2, XT4
Type Fixed/plug-in Withdrawable
Uncabled version Catalog number Catalog number
SOR 12V DC KXTASORA –
SOR uncabled SOR 24-30V AC/DC KXTASORB –
SOR 48-60V AC/DC KXTASORC –
SOR 110-127V AC/110-125V DC KXTASORD –
SOR 220-240V AC/220-250V DC KXTASORE –
SOR 380-440V AC KXTASORF –
SOR 480-525V AC KXTASORG –
Cabled version Catalog number Catalog number
SOR-C 12V DC KXTASORCFPA KXTCSORCWA
SOR cabled SOR-C 24-30V AC/DC KXTASORCFPB KXTCSORCWB
SOR-C 48-60V AC/DC KXTASORCFPC KXTCSORCWC
SOR-C 110-127V AC/110-125V DC KXTASORCFPD KXTCSORCWD
SOR-C 220-240V AC/220-250V DC KXTASORCFPE KXTCSORCWE
SOR-C 380-440V AC KXTASORCFPF KXTCSORCWF
SOR-C 480-525V AC KXTASORCFPG KXTCSORCWG

SOR for withdrawable

7
Undervoltage release-UVR
XT1, XT2, XT3, XT4 XT2, XT4
Type Fixed/plug-in Withdrawable
Uncabled version Catalog number Catalog number
UVR 24-30V AC/DC KXTAUVR1 –
UVR uncabled UVR 48V AC/DC KXTAUVR2 –
UVR 60V AC/DC KXTAUVR3 –
UVR 110-127V AC/110-125V DC KXTAUVR4 –
UVR 220-240V AC/220-250V DC KXTAUVR5 –
UVR 380-440V AC KXTAUVR6 –
UVR 480-525V AC KXTAUVR7 –
Cabled version Catalog number Catalog number
UVR-C 24-30V AC/DC KXTAUVRCFP1 KXTCUVRCW1
UVR-C 48V AC/DC KXTAUVRCFP2 KXTCUVRCW2
UVR cabled
UVR-C 60V AC/DC KXTAUVRCFP3 KXTCUVRCW3
UVR-C 110-127V AC/110-125V DC KXTAUVRCFP4 KXTCUVRCW4
UVR-C 220-240V AC/220-250V DC KXTAUVRCFP5 KXTCUVRCW5
UVR-C 380-440V AC KXTAUVRCFP6 KXTCUVRCW6
UVR-C 480-525V AC KXTAUVRCFP7 KXTCUVRCW7

UVR for withdrawable

Delay device for undervoltage release - UVD (1)


XT1, XT2, XT3, XT4
Type Fixed/plug-in
Uncabled version Catalog number
UVD 24-30V AC/DC KT3UVD8
UVD 48-60V AC/DC KT3UVD7
UVD 110-125V AC/DC KT3UVD4
Time delay device for UVD 220-250V AC/DC KT3UVD2
(1)
IEC rated only.
undervoltage release

7/20 SACE Tmax XT UL/CSA | US Technical Catalog


Connectors
Fourth pole connectors for withdrawable (1)
XT2, XT4
Type Catalog number
Connector 4th Pole SOR/PS-SOR KXTCE3PINCONSOR
Connector 4th Pole UVR KXTCE3PINCONUVR
(1)
IEC rated only.

Socket plug connector on the panel (1)


XT1, XT2, XT3, XT4
Type Catalog number
Socket-plug connector with 3 PINS KXTAE3PINCON
Socket-plug connector with 6 PINS KXTAE6PINCON
Socket-plug Socket-plug connector with 9 PINS KXTAE9PINCON
panel connector Socket-plug connector with 15 PINS KXTAE15PINCON
(1)
IEC rated only.

Fixed part socket-plug connector(1)


XT2, XT4
Type Catalog number
Socket-plug connector of moving part - 12 PINS KXTCE12PINMPCON
Socket-plug connector of fixed part - 12 PINS
(1)
IEC rated only.
KXTCE12PINFPCON 7
Fixed part socket-
plug connector

Electrical signals
Auxillary contacts - AUX
XT1 XT3 XT2, XT4
Type Fixed/plug-in Fixed/plug-in Fixed/plug-in Withdrawable
Uncabled version Catalog number Catalog number Catalog number Catalog number
AUX 250V KXTAAUX –
AUX uncabled AUX 24V DC KXTAAUXD –
AUX S51 250V – – KXTCAXS51 –
AUX S51 24V DC – – KXTCAXDS51 –
Cabled version
AUX-C 3Q 250V Left KXT1AXC3QL KXT3AXC3QL KXTCAXC3QL –
AUX-C 1Q + 1 SY 250V KXTAAXCQSYFP KXTCAXCQSYW
AUX-C 2Q + 1 SY 250V KXTAAXC2QSYFP –
AUX cabled AUX-C 3Q + 1 SY 250V – KXTDAXC3QSYFP KXTCAXC3QSYW
AUX-C 3Q + 2 SY 250V – – KXTCAXC3Q2SYFP KXTCAXC3Q2SYW
AUX-C 2Q + 2 SY + 1S51 250V – – KXTCAXC2Q2SYS51FP KXTCAXC2Q2SYS51W
AUX-S51 250V – – KXTCAXCS51FP KXTCAXCS51W
AUX-C 1Q + 1SY 24V DC KXTAAXCDQSYFP KXTCAXCDQSYW
AUX-C 3Q + 1SY 24V DC – KXTDAXCD3QSYFP KXTCAXCD3QSYW
AUX for
AUX-S51-C 24V DC – – KXTCAXDS51FP KXTCAXDS51W
withdrawable
AUX-C 1Q + 1SY 400V AC – – KXTCAXC4QSYFP KXTCAXC4QSYW
AUC-C 2Q 400V AC – – KXTCAXC42QFP KXTCAXC42QW

US Technical Catalog | SACE Tmax XT UL/CSA 7/21


Ordering information for XT1, XT2, XT3, XT4 UL/CSA
Accessories

Auxillary position contacts - AUP


XT1, XT3 XT2, XT4
Cabled version Catalog number Catalog number
AUP-I - Four racked-in contacts 250V for plug-in circuit breaker KXTAAUP250IN
AUP-I - Four racked-in contacts 24V DC for plug-in circuit breaker KXTAAUP24IN
AUP - Auxiliary AUP-R - Two racked-out contacts 250V for withdrawable breaker --- KXTCAUP250W
position contacts AUP-R - Two racked-out contacts 24V DC for withdrawable breaker --- KXTCAUP24W

Early auxillary contacts - AUE


XT1,XT2,XT3, XT4 XT2, XT4
Type Fixed/plug-in Withdrawable
Cabled version Catalog number Catalog number
AUE - Two contacts in the rotary handle RHx (closed) KXTAAUECLFP KXTCAUECLW
AUE - Two contacts in the rotary handle RHx (open) KXTDAUEOPFP KXTCAUEOPW
AUE - Early
auxiliary contacts

Motor operators
Motor operators with direct action - MOD
XT1, XT3
Catalog number
MOD 24V DC KXTBMOD24
MOD 48-60V DC KXTBMOD48-60
MOD 110-125V AC/DC KXTBMOD110-125
7 MOD 220-250V AC/DC KXTBMOD220-250
Motor operator MOD 380-440V AC KXTBMOD280-440
MOD 480-525V AC KXTBMOD480-525

Stored energy motor operator - MOE


XT2, XT4
Catalog number
MOE 24V DC KXTCMOE24
MOE 48-60V DC KXTCMOE48-60
MOE 110-125V AC/DC KXTCMOE110-125
MOE - Motor MOE 220-250V AC/DC KXTCMOE220-250
operator MOE 380-440V AC KXTCMOE380-440
MOE 480-525V AC KXTCMOE480-525

Electronic stored energy motor operator - MOE-E (1)


XT2, XT4
Catalog number
MOE-E 24V DC KXTCEMOEE24
MOE-E 48-60V DC KXTCEMOEE48-60
MOE-E 110-125V AC/DC KXTCEMOEE110-125
MOE-E 220-250V AC/DC KXTCEMOEE220-250
MOE-E 380-440V AC KXTCEMOEE380-440
MOE-E 480-525V AC KXTCEMOEE480-525
(1)
IEC rated only.

7/22 SACE Tmax XT UL/CSA | US Technical Catalog


Rotary handle operating mechanisms
Rotary handle operating mechanism
XT1, XT3 XT2, XT4
Type Fixed/plug-in Fixed/plug-in Withdrawable
Catalog number Catalog number Catalog number
RHD Standard Direct Handle KXTBRHDSTFP KXTCRHDSTFP KXTCRHDSTW
RHD Emergency Direct Handle KXTBRHDEMFP KXTCRHDEMFP KXTCRHDEMW
RHE Standard Extended Handle KXTBRHESTFP KXTCRHESTFP KXTCRHESTW
RHE Emergency Extended Handle KXTBRHEEMFP KXTCRHEEMFP KXTCRHEEMW
RHE Standard Extended Handle with Padlock (1) KXTBRHESTFPPLK KXTCRHESTFPPLK KXTCRHESTWPLK
Direct rotary handle RHE Emergency Extended Handle with Padlock (1) KXTBRHEEMFPPLK KXTCRHEEMFPPLK KXTCRHEEMWPLK
RHS-L Standard Left Side Handle KXTBRHSLSTFP KXTCRHSLSTFP –
RHS-L Emergency Left Side Handle KXTBRHSLEMFP KXTCRHSLEMFP –
RHS-R Standard Right Side Handle KXTBRHSRSTFP KXTCRHSRSTFP –
RHS-R Emergency Right Side Handle KXTBRHSREMFP KXTCRHSREMFP –
Extended handle spare parts
RHE_B Base for Extended Handle KXTBRHEBFP KXTCRHEBFP KXTCRHEBW
RHE_B Base for Extended Handle with Padlock (1) KXTBRHEBFPPLK KXTCRHEBFPPLK KXTCRHEBWPLK
RHE_S 500mm Shaft (2) KXTARHES500
RHE_H Standard Extended Handle KXTARHEHST
RHE_H Emergency Extended Handle KXTARHEHEM
LH Standard Large Handle, NEMA 1 KXTALHNDLST
LH Emergency Large Handle, NEMA 1 KXTALHNDLEM
Extended rotary handle Standard Pistol Handle with reset function, 65mm, NEMA, 3R,12 OHB65J10B
Emergency Pistol Handle with reset function, 65mm, NEMA, 3R,12 (1) OHY65J10B
Standard Pistol Handle with reset function, 65mm, NEMA, 4,4X (1) OHB65L10B 7
Emergency Pistol Handle with reset function, 65mm, NEMA, 4,4X (1) OHY65L10B
Standard Pistol Handle with reset function, 125mm, NEMA, 3R,12 OHB125J10B
Emergency Pistol Handle with reset function, 125mm, NEMA, 3R,12 (1) OHY125J10B
Standard Pistol Handle with reset function, 125mm, NEMA, 4,4X (1) OHB125L10B
Emergency Pistol Handle with reset function, 125mm, NEMA, 4,4X (1) OHY125L10B
148mm Pistol Handle Shaft (3) OXP10X148
225mm Pistol Handle Shaft (3) OXP10X225
500mm Pistol Handle Shaft (3) OXP10X500
(1)
Consult ABB for availability
(2)
Shaft for use with handles beginning with KXT.
(3)
Shafts for use with handles beginning with OH.

IP54 protection for transmitted rotary handle (1)


XT1, XT2, XT3, XT4
Type Fixed/plug-in
Catalog number
IP54 protection for transmitted handle -RHE KXTAERHEIP54
(1)
IEC rated only.

IP54 Flange handle (1)


XT1 XT3 XT2 XT4
Type Catalog number Catalog number Catalog number Catalog number
Flange Handle + Mechanism + 4ft Cable (NEMA 1,3R, 12, 4) KXT1N12FLHDL4 KXT3N12FLHDL4 KXT2N12FLHDL4 KXT4N12FLHDL4
Flange Handle + Mechanism + 6ft Cable (NEMA 1,3R, 12, 4) KXT1N12FLHDL6 KXT3N12FLHDL6 KXT2N12FLHDL6 KXT4N12FLHDL6
Flange Handle + Mechanism + 10ft Cable (NEMA 1,3R, 12, 4) KXT1N12FLHDL10 KXT3N12FLHDL10 KXT2N12FLHDL10 KXT4N12FLHDL10
Flange Handle + Mechanism + 4ft Cable (NEMA 1,3R, 12, 4, 4X) KXT1N4FLHDL4 KXT3N4FLHDL4 KXT2N4FLHDL4 KXT4N4FLHDL4
Flange Handle + Mechanism + 6ft Cable (NEMA 1,3R, 12, 4, 4X) KXT1N4FLHDL6 KXT3N4FLHDL6 KXT2N4FLHDL6 KXT4N4FLHDL6
Flange Handle + Mechanism + 10ft Cable (NEMA 1,3R, 12, 4, 4X) KXT1N4FLHDL10 KXT3N4FLHDL10 KXT2N4FLHDL10 KXT4N4FLHDL10
Flange handle spare parts
Flange handle only (NEMA 1,3R,12,4) KXTAN12FLHDL
Flange handle only (NEMA 1, 3R, 12, 4, 4X) KXTAN4XFLHDL
Flange handle hardware KXTAFLHDLHW
Flange mounting hardware KXTBFLMTHW KXTCFLMTHW
(1)
Consult ABB for availability

US Technical Catalog | SACE Tmax XT UL/CSA 7/23


Ordering information for XT1, XT2, XT3, XT4 UL/CSA
Accessories

Locks
Padlock on the circuit breaker
XT1, XT3 XT2, XT4
Type Catalog number Catalog number
PLL removable lock with padlocks in open position KXTBPLLREM –
PLL fixed lock with padlocks in open position KXTBPLLOP KXTCPLLOP
PLL fixed lock with padlocks in open/closed position KXTBPLLOPCL KXTCPLLOPCL

Fixed padlock Key lock on the circuit breaker


XT1 XT3 XT2,XT4
Type Catalog number Catalog number Catalog number
KLC Ronis key lock open, different keys, removable in open position KXT1KLCCBDIF KXT3KLCCBDIF KXTCKLCCBDIF
KLC Ronis key lock open, same type A keys, removable in open position KXT1KLCCBA KXT3KLCCBA KXTCKLCCBA
KLC Ronis key lock open, same type B keys, removable in open position KXT1KLCCBB KXT3KLCCBB KXTCKLCCBB
KLC Ronis key lock open, same type C keys, removable in open position KXT1KLCCBC KXT3KLCCBC KXTCKLCCBC
KLC Ronis key lock open, same type D keys, removable in open position KXT1KLCCBD KXT3KLCCBD KXTCKLCCBD
KLC Ronis key lock open/closed, different keys, removable in both positions KXT1KLCCBOPCL KXT3KLCCBOPCL KXTCKLCCBOPCL
Key lock on the circuit
breaker
Key lock on the rotary handle/Key lock on the front for locks
XT1,XT3 XT2,XT4
Type Catalog number Catalog number
RHL Ronis key lock open, different keys, RHx KXTARHLDIF
RHL Ronis key lock open, same Type A keys, RHx KXTARHLA
7 RHL Ronis key lock open, same Type B keys, RHx KXTARHLB
RHL Ronis key lock open, same Type C keys, RHx KXTARHLC
RHL Ronis key lock open, same Type D keys, RHx KXTARHLD
RHL Ronis key lock open/closed, different keys, RHx KXTARHLOPCL
Key lock on the handle RHL Ronis key lock open/closed, different keys, FLD – KXTCRHLFLD

Key lock on the motor(1)


XT1,XT3 XT2,XT4
Type Catalog number Catalog number
MOL-D Ronis key lock open, different keys KXTBEMOLDIF KXTCEMOLDIF
MOL-S Ronis key lock open, same type A keys KXTBEMOLA KXTCEMOLA
MOL-S Ronis key lock open, same type B keys KXTBEMOLB KXTCEMOLB
MOL-S Ronis key lock open, same type C keys KXTBEMOLC KXTCEMOLC
Key lock on the motor MOL-S Ronis key lock open, same type D keys KXTBEMOLD KXTCEMOLD
MOL-M Key lock against manual operation – KXTCEMOLMO
(1)
IEC rated only.

Front for operating lever mechanism


XT2,XT4
Type Fixed/plug-in Withdrawable
Catalog number Catalog number
FLD front for operating lever mechnism KXTCFLDFP KXTCFLDW
Front for operating lever
mechanism Mechanical interlock
XT1 XT2 XT3 XT4
Type Fixed Plug-in Fixed Plug-in/ Fixed Plug-in Fixed Plug-in/
withdrawable withdrawable
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
Chassis MIR-H KXTAMIRHR
Chassis MIR-V KXTAMIRVR
Plate KXT1MIRPLF KXT1MIRPLP KXT2MIRPLF KXT2MIRPLPW KXT3MIRPLF KXT3MIRPLP KXT4MIRPLF KXT4MIRPLPW

Interlock

Sealable lock of thermal setting (1)


XT1,XT2,XT3,XT4
Type Catalog number
Lock on thermal setting for TMA or MA trip unit KXTAEAASEALREL
(1)
IEC rated only.

7/24 SACE Tmax XT UL/CSA | US Technical Catalog


Residual current devices
Residual current device (1)
XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
RC Sel Low 220mm – KXT1ERCSEL200-4 – – – – – –
RC Inst KXT1ERCINST-3 KXT1ERCINST-4 – – KXT3ERCINST-3 KXT3ERCINST-4 – –
RC Sel KXT1ERCSEL-3 KXT1ERCSEL-4 – KXT2ERCSEL-4 KXT3ERCSEL-3 KXT3ERCSEL-4 – KXT4ERCSEL-4
RC B Type – – – – – KXT3ERCB-4 – –
(1)
IEC rated only.

RC Inst / RC Sel

Panel type residual current delay(1)


XT1, XT2, XT3, XT4
Type Catalog number
RCQ020/A 115-230V AC KXTAERCQ230
RCQ020/A 415V AC KXTAERCQ415
Toroid closed Ø60mm KXTTET0R60
Toroid closed Ø110mm KXTTET0R110
Toroid closed Ø185mm KXTTET0R185
(1)
IEC rated only.

7
Installation
Bracket for mounting onto DIN rail
XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P
Catalog Catalog Catalog Catalog Catalog Catalog Catalog Catalog
number number number number number number number number
(1)
Kit DIN50022 KXT1EDIN-3 KXT1EDIN-4 KXTCEDINPL KXT3EDIN-3 KXT3EDIN-4 KXTCEDINPL
Kit DIN50022 UL – – KXT2DIN-3 KXT2DIN-4 – – KXT4DIN-3 KXT4DIN-4
Kit DIN50022 XT1 + RC Low 220mm (1) – KXT1EDINRCSELPL – – – – – –
Kit DIN50022 XT1 + RC Sel/RC Inst (1) KXT1EDINRCPL – – – – – –
DIN guide Kit DIN50022 XT3 + RC Sel/RC Inst (1) – – – – KXT3EDINRCPL – –
(1)
IEC rated only.

US Technical Catalog | SACE Tmax XT UL/CSA 7/25


Ordering information for XT1, XT2, XT3, XT4 UL/CSA
Accessories

Terminals, terminal covers and phase barriers


Insulating terminal covers
XT1 XT2 XT3 XT4
Type 3p 4p 3p 4p 3p 4p 3p 4p
Catalog Catalog Catalog Catalog Catalog Catalog Catalog Catalog
number number number number number number number number
LTC low terminal covers(1) KXT1LTC-3 KXT1LTC-4 KXT2LTC-3 KXT2LTC-4 KXT3LTC-3 KXT3LTC-4 KXT4LTC-3 KXT4LTC-4
HTC high terminal covers KXT1HTC-3 KXT1HTC-4 KXT2HTC-3 KXT2HTC-4 KXT3HTC-3 KXT3HTC-4 KXT4HTC-3 KXT4HTC-4
(1)
Rear terminals, IEC only.

Terminal cover

Sealable screws for terminal covers (1)


XT1 XT2 XT3 XT4
Type Catalog number
Kit with two sealable screws KXTAESSEAL
(1)
IEC rated only.

Sealable screw

Phase barriers
7 XT1, XT3 XT2, XT4
Type 4 pcs 6 pcs 4 pcs 6 pcs
Catalog number Catalog number Catalog number Catalog number
PB Height 25mm/0.98in KXTBPB25-3 KXTBPB25-4 KXTCPB25-3 KXTCPB25-4
PB Height 100mm/3.94in KXTBPB100-3 KXTBPB100-4 KXTCPB100-3 KXTCPB100-4
PB Height 200mm/7.87in KXTBPB200-3 KXTBPB200-4 KXTCPB200-3 KXTCPB200-4

Phase barriers

7/26 SACE Tmax XT UL/CSA | US Technical Catalog


Terminals
XT1 XT2
Type 3pcs 4pcs 6pcs 8pcs 3pcs 4pcs 6pcs 8pcs
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
F Front terminals KXT1F-3PC KXT1F-4PC KXT1F-6PC KXT1F-8PC KXT2F-3PC KXT2F-4PC KXT2F-6PC KXT2F-8PC
F Front terminals for MCP KXT1F3PCMCP – KXT1F6PCMCP – – – – –
EF Extended front terminals KXT1EF-3PC KXT1EF-4PC KXT1EF-6PC KXT1EF-8PC KXT2EF-3PC KXT2EF-4PC KXT2EF-6PC KXT2EF-8PC
EF terminal ES Extended spread terminals KXT1ES-3PC KXT1ES-4PC KXT1ES-6PC KXT1ES-8PC KXT2ES-3PC KXT2ES-4PC KXT2ES-6PC KXT2ES-8PC
FC CuAl Terminals for CuAl cables 100A, 14-1/0 AWG, – – – – – – – –
1x2.5…50mm (2)(4)
FC CuAl Terminals for CuAl cables w/control tap 100A, 14-1/0 – – – – – – – –
AWG, 1x2.5…50mm (2)(4)
FC CuAl Terminals for CuAl cables 110A, 14-1/0 AWG, – – – – KXT2CUAL1-3PC KXT2CUAL1-4PC KXT2CUAL1-6PC KXT2CUAL1-8PC
1x2.5…50mm (2)(4)
FCCu FC CuAl Terminals for CuAl cables 225A, 4 AWG-300 kcmil,
terminal 1x35…150mm (2)(4) – – – – – – – –
FC CuAl Terminals for CuAl cables w/control tap 225A, – – – – – – – –
4 AWG-300 kcmil, 1x35…150mm (2)(4)
FC CuAl Terminals for CuAl cables 250A, 250-350 kcmil, – – – – – – – –
1x120…185mm (2)(4)
FC Cu Terminals for Cu cables 125A, 14-1/0 AWG, 1x2.5… KXT1CU-3PC KXT1CU-4PC KXT1CU-6PC KXT1CU-8PC – – – –
50mm 2
FC Cu Terminals for Cu cables MCP, 14-1/0 AWG, 1x1.5… KXT1CUMCP-3PC KXT1CUMCP-4PC KXT1CUMCP-6PC KXT1CUMCP-8PC – – – –
50mm 2
FC Cu Terminals for Cu cables 125A, 14-1/0 AWG, 1x2.5… – – --- – KXT2CU-3PC KXT2CU-4PC KXT2CU-6PC KXT2CU-8PC
95mm 2
FC Cu Terminals for Cu cables 10-250 AWG, 1x6…185mm 2 – – – – – – – –
FC Cu Terminals for Cu cables, XT4X to 150A, 14-1/0 AWG,
1x2.5…50mm 2 (3) – – – – – – – – 7
MC Multi cable terminals for Cu cables, 6x14-2 AWG, KXT1MC-3PC KXT1MC-4PC KXT1MC-6PC KXT1MC-8PC KXT2MC-3PC KXT2MC-4PC KXT2MC-6PC KXT2MC-8PC
6x2.5…35mm 2
MC Multi cable terminals for Cu cables, 6x12-2 AWG, – – – – – – – –
6x2.5…35mm 2
R Rear adjustable terminals (1) KXT1ER-3PC KXT1ER-4PC KXT1ER-6PC KXT1ER-8PC KXT2ER-3PC KXT2ER-4PC KXT2ER-6PC KXT2ER-8PC
R-RC Rear terminals for residual current (1) – KXT1ERRC-4PC – – – – – –
FB Flexibar Terminals (1) KXT1EFB-3PC KXT1EFB-4PC KXT1EFB-6PC KXT1EFB-8PC KXT2EFB-3PC KXT2EFB-4PC KXT2EFB-6PC KXT2EFB-8PC

XT3 XT4
Type 3pcs 4pcs 6pcs 8pcs 3pcs 4pcs 6pcs 8pcs
Front Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
extended F Front terminals KXT3F-3PC KXT3F-4PC KXT3F-6PC KXT3F-8PC KXT4F-3PC KXT4F-4PC KXT4F-6PC KXT4F-8PC
spread F Front terminals for MCP – – – – – – – –
terminal - ES EF Extended front terminals KXT3EF-3PC KXT3EF-4PC KXT3EF-6PC KXT3EF-8PC KXT4EF-3PC KXT4EF-4PC KXT4EF-6PC KXT4EF-8PC
ES Extended spread terminals KXT3ES-3PC KXT3ES-4PC KXT3ES-6PC KXT3ES-8PC KXT4ES-3PC KXT4ES-4PC KXT4ES-6PC KXT4ES-8PC
FC CuAl Terminals for CuAl cables 100A, 14-1/0 AWG, KXT3CUAL1-3PC KXT3CUAL1-4PC KXT3CUAL1-6PC KXT3CUAL1-8PC KXT4CUAL1-3PC KXT4CUAL1-4PC KXT4CUAL1-6PC KXT4CUAL1-8PC
1x2.5…50mm 2 (4)
FC CuAl Terminals for CuAl cables w/control tap 100A, KXT3CUAL1C-3PC KXT3CUAL1C-4PC – – KXT4CUAL1C-3PC KXT4CUAL1C-4PC – –
14-1/0 AWG, 1x2.5…50mm 2 (4)
FC CuAl Terminals for CuAl cables 110A, 14-1/0 AWG, 1x2.5… – – – – – – – –
50mm (2)(4)
FC CuAl Terminals for CuAl cables 225A, 4 AWG-300 KXT3CUAL2-3PC KXT3CUAL2-4PC KXT3CUAL2-6PC KXT3CUAL2-8PC KXT4CUAL2-3PC KXT4CUAL2-4PC KXT4CUAL2-6PC KXT4CUAL2-8PC
kcmil, 1x35…150mm (2)(4)
FC CuAl Terminals for CuAl cables w/control tap 225A, 4 KXT3CUAL2C-3PC KXT3CUAL2C-4PC – – KXT4CUAL2C-3PC KXT4CUAL2C-4PC – –
AWG-300 kcmil, 1x35…150mm (2)(4)
FC CuAl Terminals for CuAl cables 250A, 250-350 kcmil, – – – – KXT4CUAL3-3PC KXT4CUAL3-4PC KXT4CUAL3-6PC KXT4CUAL3-8PC
1x120…185mm (2)(4)
Multi-cable FC Cu Terminals for Cu cables 125A, 14-1/0 AWG,
terminals 1x2.5…50mm 2 – – – – – – – –
(MC) FC Cu Terminals for Cu cables MCP, 14-1/0 AWG,
1x1.5…50mm 2 – – – – – – – –
FC Cu Terminals for Cu cables 125A, 14-1/0 AWG, – – – – – – – –
1x2.5…95mm 2
FC Cu Terminals for Cu cables 250A, 10-250 AWG, KXT3CU-3PC KXT3CU-4PC KXT3CU-6PC KXT3CU-8PC KXT4CU-3PC KXT4CU-4PC KXT4CU-6PC KXT4CU-8PC
1x6…185mm 2
FC Cu Terminals for Cu cables, XT4X to 150A, 14-1/0 AWG, – – – – KXT4XCU-3PC KXT4XCU-4PC – –
1x2.5…50mm 2 (3)
MC Multi cable terminals for Cu cables, 6x14-2 AWG, – – – – – – – –
6x2.5…35mm 2
MC Multi cable terminals for Cu cables, 6x12-2 AWG, KXT3MC-3PC KXT3MC-4PC KXT3MC-6PC KXT3MC-8PC KXT4MC-3PC KXT4MC-4PC KXT4MC-6PC KXT4MC-8PC
6x2.5…35mm 2
R Rear adjustable terminals (1) KXT3ER-3PC KXT3ER-4PC KXT3ER-6PC KXT3ER-8PC KXT4ER-3PC KXT4ER-4PC KXT4ER-6PC KXT4ER-8PC
R-RC Rear terminals for residual current (1) – KXT3ERRC-4PC – – – – – –
FB Flexibar Terminals (1) KXT3EFB-3PC KXT3EFB-4PC KXT3EFB-6PC KXT3EFB-8PC KXT4EFB-3PC KXT4EFB-4PC KXT4EFB-6PC KXT4EFB-8PC
(1)
IEC rated only.
(2)
Consult ABB for availability.
(3)
For use with the XT4 X version up to 150A only. Note: XT4 X from 175-250A uses the standard 250A CU lug.
(4)
Not available for XT4 X up to 150A.

US Technical Catalog | SACE Tmax XT UL/CSA 7/27


Ordering information for XT1, XT2, XT3, XT4 UL/CSA
Accessories

Accessories for electronic trip units


General electronic trip unit accessories (1)
XT2 XT4
Type Fixed/plug-in Withdrawable Fixed/plug-in Withdrawable
Catalog number Catalog number Catalog number Catalog number
Ekip Display
Ekip Display KXTCEDISP
Ekip LED Meter KXTCELED
Ekip Comm KXTCECOMFP KXTCECOMW KXTCECOMFP KXTCECOMW
HMI030 interface on front of panel HMI030
PR212/CI contactor control unit – – 1SDA050708R1
(1)
IEC rated only.

Ekip LED Meter Current sensor for external neutral (1)


XT2 XT4
Type Catalog number Catalog number
CT external neutral of 10A KXT2ECT10
CT external neutral of 25A KXT2ECT25
CT external neutral of 40A KXT4ECT40
CT external neutral of 63A KXT2ECT63 KXT4ECT63
CT external neutral of 100A KXT2ECT100 KXT4ECT100
CT external neutral of 160A KXT2ECT160 KXT4ECT160
CT external neutral of 250A KXT4ECT250
(1)
IEC rated only.

7 Connection kits
XT2, XT4
Type Fixed/plug-in Withdrawable
Catalog number Catalog number
24V DC auxillary voltage kit for electronic trip units (1) KXTCECAUXFP KXTCECAUXW
External neutral connection kit KXTCECNEFP KXTCECNEW
(1)
IEC rated only.

Test and configuration units (1)


XT2, XT4
Type Catalog number
Ekip TT - Trip test unit ZEAEKPTT
Ekip T&P unit Ekip T&P - Programming and test unit EKIP
(1)
IEC rated only.

7/28 SACE Tmax XT UL/CSA | US Technical Catalog


Automatic transfer devices
ATS021-ATS022 Automatic transfer devices (1)
XT1, XT2, XT3, XT4
Catalog number
ATS021 ATS021
ATS022 ATS022
(1)
IEC rated only.

Spare parts
Spare parts
ATS021
XT1 XT2 XT3 XT4 XT2 XT4
Fixed/plug-in Withdrawable
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
SA RC Sel/RC Inst - opening solenoid for the residual
KXT1ESARCFP KXT2ESARCFP KXT3ESARCFP KXT4ESARCFP KXT2ESARCW KXT4ESARCW
current device (1)
SA RC B Type - opening solenoid for the residual
– – KXT3ESARCFPB – – –
current device (1)
AUX-C - Loose cabled auxillary contact 250V AC (2) KXTAAUXCFP KXTCEAUXCW
AUX-C - Loose cabled auxillary contact 24V DC (2) KXTAAUXCDFP KXTCEAUXCDW
AUX-C - Loose cabled auxillary contact 250V AC
KXTAAUXCFPHD KXTCAUXCWHD
600V (2)
AUX-C - Loose cabled auxillary contact 24V DC
KXTAAUXCDFPHD KXTCAUXCDWHD
600V (2)
(1)
IEC rated only.
(2)
Un-numbered cables. 7
Connectors for fixed part/moving part of withdrawable circuit breakers (1)
XT2, XT4
Catalog number
1 connector for with 2 pins for SOR/UVR up to 400V KXTCE2PINCONSOUV
1 connector with 3 pins for AUX up to 400V KXTCE3PINCONAUX
(1)
IEC rated only.

Fixed part of
withdrawable
Flanges for the compartment door (1)
XT1 XT2 XT3 XT4
Type 3P 4P 3P 4P 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number Catalog number
Small "optional"
flange for circuit KXTAEFLASMFP
breaker
Large "standard"
flange for circuit KXT1EFLAFP-3 KXT1EFLAFP-4 KXT2EFLAFP-3 KXT2EFLAFP-4 KXT3EFLAFP-3 KXT3EFLAFP-4 KXT4EFLAFP-3 KXT4EFLAFP-4
breaker
Flange Flange for MOD KXTBEFLAMOD – – KXTBEFLAMOD – –
Flange for MOE/
– – KXTCEFLAMOEFP – – KXTCEFLAMOEFP
MOE-E/FLD
Flange for direct
KXTAEFLARHDFP
handle RHD
Flange for residual
current RC Sel/ KXT1EFLARCFP-3 KXT1EFLARCFP-4 – – KXT3EFLARCFP-3 KXT3EFLARCFP-4 – –
RC Inst
Flange for residual
– – – KXT2EFLARCFP-4 – – – KXT4EFLARCFP-4
current RC Sel
(1)
IEC rated only.

Flanges for the compartment door for withdrawable versions (1)


XT2 XT4
Type 3P 4P 3P 4P
Catalog number Catalog number Catalog number Catalog number
Small "optional" flange for circuit breaker – – – –
Large "standard" flange for circuit breaker – – – –
Flange for MOD – – – –
Flange for MOE/MOE-E/FLD KXTCEFLAMOEW
Flange for direct handle RHD KXTCEFLARHDW
Flange for residual current RC Sel/RC Inst – – – –
Flange for residual current RC Sel – KXT2EFLARCW-4 – KXT4EFLARCW-4
(1)
IEC rated only.

US Technical Catalog | SACE Tmax XT UL/CSA 7/29