Test Report Dt. 29th Sep. 2013

The document is a test report from Durga Switchgears for two 500 KVA transformers and a high voltage vacuum circuit breaker at an ESI Hospital in Chennai, India. It summarizes the results of oil filtration and breakdown voltage tests on the transformers, which showed improvements after filtration. Acidity levels were also within normal limits. Inspections and operational tests found the circuit breaker to be functioning properly.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views10 pages

Test Report Dt. 29th Sep. 2013

The document is a test report from Durga Switchgears for two 500 KVA transformers and a high voltage vacuum circuit breaker at an ESI Hospital in Chennai, India. It summarizes the results of oil filtration and breakdown voltage tests on the transformers, which showed improvements after filtration. Acidity levels were also within normal limits. Inspections and operational tests found the circuit breaker to be functioning properly.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 10

TRANSFORMER

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 1


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : [email protected]

DATE OF TEST: 29TH SEP. 2013


TRANSFORMER NO. 1 --- OIL TEST REPORT
NAME OF THE CONSUMER : M/S. ESI HOSPITAL,
K.K.NAGAR, CHENNAI – 600 078.

Make : Electric Transformer & Equipment Co. Ltd.,


Rating : 500 KVA
Phase : 3 Phases
Serial number : 8119
Voltage Primary voltage : 11000 VOLTS
Seconday Voltage : 433 VOLTS
Current HV current : 26.23 AMPS
LV current : 666.7 AMPS
Oil quantity : 600 Liters
Year of manufacturing : 1976
BREAK DOWN VOLTAGE TEST RESULT (TEST GAP 2.5 MM)
Before Oil Filtration
Top sample : Oil withstood 30 KV level.
Bottom sample : Oil withstood 29 KV level.

After Oil Filtration


Top sample : Oil withstood 40 KV for One Minute
Oil Flashed at 55KV.
Bottom sample : Oil withstood 40 KV for One Minute.
Oil Flashed at 56KV
Oil filtration carried out on &
Break down voltage tested on : 29.09.2013

Oil filtration Due & Break


Down voltage test due on : 29.09.2014

Acidity test result : 0.19 mg OF KOH PER GRAM

Tested as per For Durga Switchgears

        IS: 335: 1972 Authorized signatory


TIN 33251085384 DURGA SWITCHGEARS
CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 2


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : [email protected]

DATE OF TEST: 29TH SEP. 2013


TRANSFORMER NO. 2 --- OIL TEST REPORT
NAME OF THE CONSUMER : M/S. ESI HOSPITAL,
K.K.NAGAR, CHENNAI – 600 078.

Make : Electric Transformer & Equipment Co. Ltd.,


Rating : 500 KVA
Phase : 3 Phases
Serial number : 8118
Voltage Primary voltage : 11000 VOLTS
Seconday Voltage : 433 VOLTS
Current HV current : 26.23 AMPS
LV current : 666.7 AMPS
Oil quantity : 600 Liters
Year of manufacturing : 1976
BREAK DOWN VOLTAGE TEST RESULT (TEST GAP 2.5 MM)
Before Oil Filtration
Top sample : Oil withstood 30 KV level.
Bottom sample : Oil withstood 27 KV level.

After Oil Filtration


Top sample : Oil withstood 40 KV for One Minute
Oil Flashed at 56 KV.
Bottom sample : Oil withstood 40 KV for One Minute.
Oil Flashed at 56 KV
Oil filtration carried out on &
Break down voltage tested on : 29.09.2013

Oil filtration Due & Break


Down voltage test due on : 29.09.2014

Acidity test result : 0.18 mg OF KOH PER GRAM

Tested as per For Durga Switchgears


        IS: 335: 1972 Authorized signatory
HT VACUUM CIRCUIT BREAKER

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 3a


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : [email protected]

DATE OF TEST: 29TH SEP. 2013


TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
TO
M/S. ESI HOSPITAL, Breaker Sl. No. 03922112009
K.K.NAGAR, CHENNAI – 600 078.
Breaker Make System Control
Type Sysvac /1280025
Rating 630 Amps
Uv 11KV
Title Transformer No. 1
S.NO. DESCRIPTION TYPE OF CHECK CHECKED REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Opening ELECTRICAL FOR


PERFORMANCE OK

4 CONTACT PENETRATION FOR VISUAL (Moving contact FOR ABNORMALITY OK


VCB mechanism only)

VCB CLOSED VCB OPEN


5 INSULATION RESISTANCE CONDITION CONDITION
R-E > 200 M Ω R I/C – R O/G
Y-E > 200 M Ω > 200 M Ω
B-E > 200 M Ω Y I/C – Y O/
R-Y > 200 M Ω > 200 M Ω
Y-B > 200 M Ω B I/C – B O/G
B-R > 200 M Ω > 200 M Ω

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS
8/5, JOHN VASU STREET, Mobile : 9884320732 Page 3b
MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : [email protected]

DATE OF TEST: 29TH SEP. 2013


TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
TO
M/S. ESI HOSPITAL, Breaker Sl. No. 03922112009
K.K.NAGAR, CHENNAI – 600 078.
Breaker Make System Control
Type Sysvac /1280025
Rating 630 Amps
Uv 11KV
Title Transformer No. 1

2) Contact Resistance Test:-

Phase Ref DC Current DC Volts Across Resistance


Applied Terminal
R-Phase 100 Amps 4.60mv 46 Micro Ohms
Y-Phase 100 Amps 4.40 mv 44 Micro Ohms
B-Phase 100 Amps 4.50 mv 45 Micro Ohms

3) Breaker Timing Test:-

Ref Closing Time in Opening Time in


milli secs. milli secs
R-Phase 132 80
Y-Phase 133 79
B-Phase 135 81

Test kit Details: Relay Test Kit IR Value Tester (1000V) Tong Tester
MAKE : ANANDHA JOTHI MAKE : CIE MAKE : VARTECH
Serial No: 01410 Serial No. :36308-6/11/PD Serial No.: 09060043630

Timer Kit
Make : ANANDHA JOTHI
SerialNo. : 11005

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 4a


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : [email protected]
DATE OF TEST: 29TH SEP. 2013
TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
TO
M/S. ESI HOSPITAL, Breaker Sl. No. 03923112009
K.K.NAGAR, CHENNAI – 600 078.
Breaker Make System Control
Type Sysvac /1280025
Rating 630 Amps
Uv 11KV
Title Transformer No. 2
S.NO. DESCRIPTION TYPE OF CHECK CHECKED REMARKS

1 PHYSICAL INSPECTION VISUAL FOR DAMAGE OK

2 INSTALLATION/CONNECTION VISUAL/MECHANICAL FOR OK


CORRECTNESS
3 OPERATIONS
a) Manual Spring charging MECHANICAL CORRECTNESS OK
Closing / Tripping

b) Normal Closing/Tripping MECHANICAL CORRECTNESS OK

FOR
c) Tripping through RELAY ELECTRICAL PERFORMANCE OK

d) Spring Charging Motor ELECTRICAL FOR OK


PERFORMANCE

e) Opening ELECTRICAL FOR


PERFORMANCE OK

4 CONTACT PENETRATION FOR VISUAL (Moving contact FOR ABNORMALITY OK


VCB mechanism only)

VCB CLOSED VCB OPEN


5 INSULATION RESISTANCE CONDITION CONDITION
R-E > 200 M Ω R I/C – R O/G
Y-E > 200 M Ω > 200 M Ω
B-E > 200 M Ω Y I/C – Y O/
R-Y > 200 M Ω > 200 M Ω
Y-B > 200 M Ω B I/C – B O/G
B-R > 200 M Ω > 200 M Ω

TIN 33251085384 DURGA SWITCHGEARS


CST 872774/08-01-08 (Servicing, Repairing and testing of all kinds of LT/HT Circuit
AREA CODE 0 5 5 Breakers, Protective relays, Transformers and High pot Test)
EA 2616 A-GRADE CONTRACTORS

8/5, JOHN VASU STREET, Mobile : 9884320732 Page 4b


MADHAVARAM MILK COLONY Office : 044 – 25550453
CHENNAI – 600 051. Mail : [email protected]

DATE OF TEST: 29TH SEP. 2013


TEST REPORT FOR HT VACUUM CIRCUIT BREAKER
TO
M/S. ESI HOSPITAL, Breaker Sl. No. 03923112009
K.K.NAGAR, CHENNAI – 600 078.
Breaker Make System Control
Type Sysvac /1280025
Rating 630 Amps
Uv 11KV
2) Contact Resistance Test:- Title Transformer No. 2

Phase Ref DC Current DC Volts Across Resistance


Applied Terminal
R-Phase 100 Amps 4.30 mv 43 Micro Ohms
Y-Phase 100 Amps 4.40mv 44 Micro Ohms
B-Phase 100 Amps 4.50 mv 45 Micro Ohms

3) Breaker Timing Test:-

Ref Closing Time in Opening Time in


milli secs. milli secs
R-Phase 125 79
Y-Phase 127 78
B-Phase 126 79

Test kit Details: Relay Test Kit IR Value Tester (1000V) Tong Tester
MAKE : ANANDHA JOTHI MAKE : CIE MAKE : VARTECH
Serial No: 01410 Serial No. :36308-6/11/PD Serial No.: 09060043630

Timer Kit
Make : ANANDHA JOTHI
SerialNo. : 11005
EA 2616– Durga Switchgears Page 5
Client: M/S. ESI HOSPITAL, K.K.NAGAR, CHENNAI – 600 078
EARTH RESISTANCE TEST REPORT

Date of Test : 29th Sep. 2013

S.NO TEST REPORT


DURGA SWITCHGEARS
DESCRIPTION FOR
LOCATION
Individual Combined
Resistance
EA 2616 -- A Grade Electrical Contractors Resistance
INDEX in Ohms in Ohms
1. Transformer Neutral EarthTRANSFORMER
-1 Outdoor Area
OIL 1.98 0.40
2. Transformer Neutral Earth -2 2.04
3.
S NO
HT Panel Body Earth -1
DESCRIPTION PAGE
2.89
NO.0.40
0.40
&
1 500kva Transformer - 1 1a – 1b
2 500kva Transformer - 2 2a – 2e
HT VACUUM CIRCUIT BREAKERS
3 3a – 3e
4 4a
AT
5 5a
6 6a – 6b
7 7a – 7b
M/S ESI Hospital,

KK Nagar, Chennai – 600 078.

On

29th Sep. 2013

TESTED WITH WACO Make Digital Earth Tester


Sl. No. : 50388
Remarks: - Test results are satisfactory.
PRECOMMISSIONING – RELAY TESTING – HIPOT TEST – TRANSFORMER OIL FILTRATION- TRANSFORER/HT/LT BREAKER REPAIRING
NO. 8/5, JOHN VASU STREET, MADHAVARAM MILK COLONY, CHENNAI – 600 051.
Job carried out by : DURGA SWITCHGEARS
EA 2616 A-Grade Electrical Contractors
No. 8/5, John Vasu Street,
Madhavaram Milk Colony,
Chennai – 600 051