3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 1 de 54

Cerrar SIS

Pantalla anterior

! """" #$

! " #$ %&% & ' "( #$ )&% & '

"%&' '%

Electronic Control Module (Generator Set) - Configure


SMCS - 4490-025

Function Keys and Navigation Keys


ReferenceFor a full explanation of the use of the Function keys (Enter, Escape) and the Navigation keys (Scroll Left,
Scroll Right, Scroll Up, Scroll Down) that are referenced in this section, see Systems Operation, "Electronic Control
Module (Generator Set)"

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 2 de 54

Illustration 1
(1) Display Screen

(2) Yellow Warning Lamp

(3) Red Shutdown Lamp

(4) Alarm Acknowledge/Silence key

(5) Lamp Test key

(6) Stop key

(7) Auto key

(8) Run key

(9) Escape key

(10) Enter key

(11) Scroll Right key

(12) Scroll Down key

(13) Scroll Up key

(14) Scroll Left key

(15) Engine Overview key

(16) AC Overview key

(9) Escape - Navigate up (backward) through the menu structure and also used to cancel out of data entry screens during
setpoint programming.

(10) Enter - Select a highlighted menu item

(11) Scroll Right - During numeric data entry, choose the digit to edit. During certain setpoint adjustments, select or
deselect a checkbox.

(12) Scroll Down - Move down through the main menu or navigate within a list in order to highlight one of the items.
Also used to decrement digits (0-9).

(13) Scroll Up - Move up through the main menu or navigate within a list in order to highlight one of the items. Also
used to increment digits (0-9)

(14) Scroll Left - During numeric data entry, choose the digit to edit. During certain setpoint adjustments, select or
deselect a checkbox.

Initial Setup
Information from the EMCP 3 is displayed on the Display Screen (1). Press the Scroll Up key or the Scroll Down key in
order to highlight the MAIN MENU options.

Press the Enter key in order to select one of the main menu options.

The keypad is also used in order to change the setpoints. Press the Enter key in order to change a setpoint. Press the

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 3 de 54

Scroll Up key or the Scroll Down key in order to increase or decrease the value. Press the Scroll Left key or the Scroll
Right key in order to change the digit that is to be adjusted.

Note: The EMCP 3 panel will power up to the MAIN MENU screen. If the EMCP 3 panel is already powered up, press
the Escape key in order to return to the main menu. Each press of the Escape key moves you back one level in the menu
structure,

Setpoints
Within each setpoint category there are one or more function blocks. Each of those function blocks may contain one or
more setpoints. Each of these setpoint categories and its corresponding function blocks are shown below.

Control

Automatic Start/Stop

Automatic Voltage Regulator (AVR) Desired Voltage Request

Generator Desired Engine Speed Request

Engine Monitor/Protect

Battery Voltage Monitor

Crank Attempt/Successful start Counter

Engine Coolant Temperature Monitor

Engine Oil Pressure Monitor

Engine Speed Monitor

Enhanced Engine Monitor

Service Maintenance Interval

Events

Diagnostics Configuration

Engine protection Events Configuration

Generator Protection Events Configuration

Other System Events Configuration

Custom Events

Event Output Function

Event System

Generator Monitor/Protect

Enhanced Generator Monitor

Generator AC Monitor

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 4 de 54

Generator AC Power Monitor

Generator Over Current

Generator Over/Under Frequency

Generator Over/Under Voltage

Generator Reverse Power

Input/Output (I/O)

Digital Inputs

Digital Outputs

Relay Outputs

Spare Analog Input

Network

Data Link - SCADA

Other

Digital Selectors

Reduced Power Mode

Menu Maps
The maps in this section are to be used as a guide when programming the EMCP 3. Maps are provided for all versions of
the controller.

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 5 de 54

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 6 de 54

Illustration 2

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 7 de 54

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 8 de 54

Illustration 3

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 9 de 54

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 10 de 54

Illustration 4

Programming the Display Preferences


The preferences affect the way data is viewed on the display screen. The configuration may need to be changed in order
to meet local requirements.

In order to program the display preferences, perform the following menu options.

1. Press the Escape key as many times as necessary in order to go back to the "MAIN MENU" display.

2. From the "MAIN MENU", press the Scroll Down key or the Scroll Up key in order to highlight the
"PREFERENCES" option. The following parameters can be changed or viewed:

CONTRAST

PRESSURE

TEMPERATURE

VOLUME

LANGUAGE

a. Press the Enter key in order to select PREFERENCES. CONTRAST will be highlighted.

b. Press the Enter key in order to select the contrast level. The contrast can be adjusted between 1 and 100,
with 1 being the least contrast and 100 being the greatest contrast. The display will show a status bar and a
number representing the current contrast level.

c. Use the Scroll Right key or the Scroll Left key in order to adjust the contrast to the desired level, and
then press the Enter key in order to save the new contrast setting.

d. Press the Scroll Down key in order to highlight PRESSURE, and then press the Enter key in order to
select the pressure function. The available options for pressure measurement are "kPa", "PSI", and
"BAR". The display will list all three options, with the current option highlighted.

e. Adjust the pressure to the desired measurement unit using the Scroll Right key or the Scroll Left key,
and then press the Enter key in order to save the pressure measurement unit.

f. Press the Scroll Down key in order to highlight TEMPERATURE and then press the Enter key in order
to select the temperature function. The available options for temperature measurement are "°C" or "°F".
The display will list both options, with the current option highlighted.

g. Adjust the temperature to the desired measurement scale using the Scroll Right key or the Scroll Left
key, and then press the Enter key in order to save the temperature measurement unit.

h. Press the Scroll Down key in order to highlight VOLUME and then press the Enter key in order to select
the volume function. The available options for volume measurement are "LITERS", "US GAL", or "IMP
GAL". The display will list all three options, with the current option highlighted.

i. Highlight the desired volume measurement unit using the Scroll Right key or the Scroll Left key, and
then press the Enter key in order to save the volume measurement unit.

j. Press the Scroll Down key in order to highlight LANGUAGE and then press the Enter key in order to
select the language function. Language does not display a value to the right. The display will show one or

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 11 de 54

two options. TECHNICIAN ENGLISH will always be shown and, if another language is available on the
flash file, that language will also be shown as an options.

k. Highlight the desired language that is to be used for display on the EMCP 3 using the Scroll Right key or
the Scroll Left key, and then press the Enter key (10) in order to save the desired language selection

l. Press the Escape key as required in order to step back up to the MAIN MENU.

Programming the Setpoints


The engine/generator setpoints affect the proper operation and serviceability of the engine, and the accuracy of
information shown on the display screen. The EMCP 3 setpoints are programmed at the factory.

The setpoints may require changing when the EMCP 3 is moved from one engine to another engine. The setpoints may
also require changing in order to satisfy the site requirements. The setpoints that are stored in the EMCP 3 must match
the specified setpoints of the particular generator set.

See the Setpoint tables following these procedures for a complete list of all the setpoint blocks. All of the setpoints listed
in the tables should be verified and reprogrammed if required.

The first setpoint block to program is the Automatic Start/Stop Block. The Automatic Start/Stop Block is part of the
Control Category. In order program the Automatic Start/Stop Setpoints, perform the following:

1. Press the Escape key as required in order to step back to the MAIN MENU.

2. From the MAIN MENU, press the Scroll Down key until CONFIGURE is highlighted and then press the Enter
key in order to select the menu.

3. Press the Scroll Down key until SETPOINTS is highlighted, and then press the Enter key in order to select the
menu.

4. Press the Scroll Down key in order to scroll through the setpoint options until CONTROL is highlighted, and
then press the Enter key in order to select the menu. The AUTOMATIC START / STOP menu is highlighted.

5. Press the Enter Key in order to select the AUTOMATIC START / STOP menu and then use the Scroll Down
key and the Scroll Up key in order to highlight the next setpoint that is to be programmed.

6. Press the Enter key in order to select the setpoint and then press the Enter key a second time in order to highlight
the current configuration of the selected setpoint.

7. Use the Scroll Down key and the Scroll Up key in order to change the current configuration to the desired
setting, and then use the Enter key in order to the save the new setting.

8. Repeat steps 5 through 7 in order to program all of the Automatic Start/Stop setpoints.

9. After all of the Automatic Start/Stop Setpoints are programmed as required, then press the Escape key in order to
back up to the CONTROL menu.

10. The next block of setpoints that is to be programmed is the Automatic Voltage Regulator (AVR) Request block.
Press the Scroll Down key in order to scroll through the setpoint options until AVR DESIRED VOLTAGE is
highlighted, and then press the Enter key in order to select the menu.

11. Repeat steps 5 through 7 in order to program all of the AVR Request setpoints.

12. Continue programming the remaining function blocks in the "CONTROL" menu.

13. Press the Escape key twice in order to back up to the SETPOINTS menu.

14. Press the Scroll Down key in order to scroll through the setpoint options until ENGINE MONITOR/PROTECT

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 12 de 54

is highlighted.

15. Press the Enter key in order to select the ENGINE MONITOR/PROTECT menu and then program all of the
function blocks in this menu.

16. Continue to program the remaining setpoints until each setpoint in every setpoint category has been checked and
programmed as required.

Setpoint Tables
All of the available setpoints on the EMCP 3 are listed in the following tables. Refer to these tables while programming
the setpoints.

Control

Automatic Start/Stop

The Automatic Start/Stop block receives starting and stopping requests from various sources (local, remote, internal),
arbitrates between them and then cranks or shuts down the engine in an orderly fashion.

Table 1

Setpoints - Automatic Start/Stop (1)

Min Max Factory


Setpoint Units
Value Value Default Description
Name

Engine start fault


Fault protection time delay prevents shut down
protection activation 0 300 sec 30
during start up from low oil pressure etc.
delay time

Amount of time the EMCP 3 energizes (cranks) the


Crank Duration 5 300 sec 7
starting motor

Amount of time the EMCP 3 deenergizes the starting


Crank Cycle Rest
5 300 sec 7 motor between crank cycles
Interval

Engine Purge Cycle


0 20 sec 0
Time

Maximum Number Number of crank/rest cycles that the EMCP 3 uses to


1 20 n/a 3
of Crank Cycles declare that a overcrank fault exists

Cooldown Duration min. 180 sec Amount of time the EMCP 3 allows the engine to run
0 30
after a normal shutdown is initiated

Amount of time the EMCP 3 activates start aid


Start Aid Activation sec.
0 240 0 control output. Set to 10 seconds if the EUI with
Time
prelube option is installed.

Crank Alert sec. Amount of time the EMCP activates crank alert
0 60 0
Activation Time output.

Crank Terminate 1000 rpm Engine speed setting used in order to disengage the
100 400
RPM starting motor during engine cranking

Engine Fuel Type Setpoint allows for selection of "Diesel" or "Natural


Setpoint Value List 0
Configuration Gas"

Fuel Shutoff Type of fuel system solenoid used on the generator

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 13 de 54

Solenoid Type set. Select "Energized to run" (ETR) or "Energized to


Setpoint Value List 0
Configuration Shut Off" (ETS).

Engine Type
Setpoint Value List 0 Select mechanical or electronic
Configuration

Engine Controller
J1939 Data Link Setpoint allows for selection of "No Data Link",
Setpoint Value List 1
Support "Basic Data Link", or "Enhanced Data" Link.
Configuration

Engine Cool Down


Setpoint allows for selection of engine speed during
Speed Setpoint Value List 0
cooldown. Select rated or idle.
Configuration

Setpoint configures whether the EMCP3 determines


its operating state on its own, or whether it receives it
Engine Operating
over the data link from the engine ECM. Set to
State Input Setpoint Value List 0
"CAN Input" for common engine interface engines
Configuration
and set to "Hard Wired "for non-common engine
interface EUI engines and non-EUI engines.

Engine Idle
Operation Enable Setpoint Value List 0
Status Engine

Fuel Priming
Feature Enable Setpoint Value List 0
Status
(1) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

AVR Desired Voltage Request

The AVR Desired Voltage Request block generates a data link request over the J1939 data link in order to request a
desired output voltage from the CDVR.

Table 2

Setpoints - AVR Desired Voltage Request (2)

Min Max
Setpoint Units Factory
Value Value Description
Name Default

The Maximum Generator Output voltage Bias


Maximum
Percent is the maximum value above and below the
Generator Voltage
0 100 % 5 Nominal Voltage that the EMCP 3 will send a
Output Bias
request for when adjusting the voltage from the
Percentage
control screen

The Generator Nominal Output Voltage is the


Generator Nominal 50000
100 V 100 desired output voltage of the generator set. This
Output Voltage
value is set to match the generator rated voltage.
(2) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Maximum Generator Output Voltage Bias Percent

The following settings will only apply if there is a CDVR installed on the generator.

Note: It is possible to set the "MAXIMUM GEN OUTPUT VOLTAGE BIAS PERCENT" from 0 to 100% but the

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 14 de 54

CDVR will only allow the voltage to change by a maximum of 15%.

1. From the MAIN MENU, press the Scroll Down key or the Scroll Up key in order to highlight the CONFIGURE
menu, and then press the Enter key in order to select the menu. "SECURITY" will be highlighted.

2. Press the Scroll Down key in order to highlight the SETPOINTS menu, and then press the Enter key in order to
select the menu. AUTOMATIC START/STOP will be highlighted.

3. Press the Scroll Down key in order to highlight the AVR DESIRED VOLTAGE menu, and then press the Enter
key in order to select the menu. MAXIMUM GEN OUTPUT VOLTAGE BIAS PERCENT will be displayed.

4. Press the Enter key in order to select the AVR DESIRED VOLTAGE menu and then press the Enter key a
second time in order to select the MAXIMUM GEN OUTPUT VOLTAGE BIAS PERCENT function and in
order to display the current voltage bias percent.

Note: The voltage bias percent setpoint will determine the amount of voltage change for each key press on the
voltage control screen. A higher value will result in a larger change in voltage per key press. A lower value will
result in a smaller change in voltage per key press.

5. Press the Scroll Down key or the Scroll Up key in order to decrement or increment the highlighted digit to the
desired value and then press the Scroll Right key or the Scroll Left key in order to highlight the next character
that is to be entered.

6. Continue this process until the desired current voltage bias percent has been entered and then press the Enter key
in order to save the new value.

Generator Desired Engine Speed Request

The Generator Desired Engine Speed Request block generates a data link request over the J1939 data link in order to
request a desired generator frequency from a generator.

Table 3

Setpoints - Generator Desired Engine Speed Request (27)

Min Max
Setpoint Units Factory
Value Value Description
Name Default

The Maximum Engine Speed Range is the maximum


Maximum
rpm value above and below the Nominal Engine Speed
Engine Speed 0 2000 100
that the EMCP 3 will send a request for when
Range
adjusting the speed from the control screen

Generator
This value is set to match the generator rated
Nominal Output 40 500 Hz 50
frequency
Frequency
( 27 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Engine Monitor/Protect

Battery Voltage Monitor

The Battery Voltage Monitor block measures the battery supply voltage to the EMCP 3. The EMCP 3 will have the
ability to monitor the battery supply voltage based on the "+BATT" and "−BATT".

Table 4

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 15 de 54

Setpoints - Battery Voltage Monitor (3)

Setpoint Min Max Units Factory Description


Name Value Value Default

High Battery Voltage Warning Event Threshold VDC


12 50 29.4

High Battery Voltage Warning Event


0 240 sec 30
Notification Delay Time

High Battery Voltage Shutdown Event Threshold VDC


12 50 30.0

High Battery Voltage Shutdown Event


0 240 sec 30
Notification Delay Time

Low Battery Voltage Warning Event Threshold VDC


0.0 25.0 23.4

Low Battery Voltage Warning Event


0 240 sec 30
Notification Delay Time

Low Battery Charging System Voltage Warning VDC


0 30 26
Event Threshold

Low Battery Charging System Voltage Warning


0 240 sec 30
Event Notification Delay Time

Low Cranking Voltage Warning Event VDC


0.0 30.0 0.0
Threshold

Low Cranking Voltage Warning Event


0 240 sec 2
Notification Delay Time
(3) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Crank Attempt/Successful Start Counter

The Crank Attempt/Successful Start Counter block tracks the number of times the engine has been cranked and the
number of times the engine has been successfully started.

Table 5

Setpoints - Crank Attempt / Successful Start Counter (31)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Customer Security Password Password level required in order


Level to Reset Crank/Start 0 4 n/a 3 to reset the Crank/Start Counters
Counters
( 31 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Engine Coolant Temperature Monitor

The Engine Coolant Temperature Monitor block converts a raw sensor value into coolant temperature and, when
configured as a sensor, detects sensor diagnostics.

Table 6

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 16 de 54

Setpoints - Engine Coolant Temperature Monitor (10)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Select "Sensor" or "Data Link". Set


Engine Coolant Temperature
Setpoint Value List 0 to Sensor for MUI Engines or set to
Sensor Configuration
Data Link for EUI engines.

High Engine Coolant


49 °C 120 °C deg.
Temperature Warning Event 100 °C
(120 °F) (248 °F)
Threshold (212 °F)

High Engine Coolant


Temperature Warning Event 0 30 sec. 15
Notification Delay Time

High Engine Coolant


49 °C 120 °C deg.
Temperature Shutdown Event 120 °C
(120 °F) (248 °F)
Threshold (248 °F)

High Engine Coolant


Temperature Shutdown Event 0 30 sec. 15
Notification Delay Time

Low Engine Coolant


0 °C 36 °C
Temperature Warning Event 21 °C (70
( 32°F) (99 °F)
Threshold °F)

Low Engine Coolant


Temperature Warning Event 0 30 sec. 10
Notification Delay Time

Coolant Temperature Sensor N/A


1 5 1
Map Selection Number
( 10 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Engine Oil Pressure Monitor

The Engine Oil Pressure Monitor block converts a raw sensor value into oil pressure and, when configured as a sensor,
detects sensor diagnostics.

Table 7

Setpoints - Engine Oil Pressure Monitor (11)

Min
Setpoint Max Units Factory
Value Description
Name Value Default

Select "Sensor" or "Data Link". Set to Sensor


Engine Oil Pressure
Setpoint Value List 0 for MUI Engines or set to Data Link for EUI
Sensor Configuration
engines.

Low Engine Oil


34 kPa 690 kPa kPa
Pressure Warning Event 160 kPa
(5 psi) (100
Threshold (23 psi)
psi)

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 17 de 54

Low Idle Low Engine


34 kPa 690 kPa kPa
Oil Pressure Warning 160 kPa
(5 psi) (100
Event Threshold (23 psi)
psi)

Low Engine Oil


Pressure Warning Event sec.
0 30 10
Notification Delay Time

Low Engine Oil


34 kPa 690 kPa kPa
Pressure Shutdown 34 kPa (5
(5 psi) (100
Event Threshold psi)
psi)

Low Idle Low Engine


34 kPa 690 kPa kPa
Oil Pressure Shutdown 160 kPa
(5 psi) (100
Event Threshold (23 psi)
psi)

Low Engine Oil


Pressure Shutdown sec.
0 30 10
Event Notification
Delay Time

When the engine speed is below this setpoint,


the Low Idle setpoint is used. Set to 800 RPM
Low Engine Oil RPM
400 1800 1350 for engines rated at 1000 or 1200 RPM. Set to
Pressure Step Speed
1200 RPM for engines rated at 1500 or 1800
RPM.

Oil Pressure Sensor


N/A
Map Selection Number 1 5 1

( 11 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Engine Speed Monitor

The Engine Speed Monitor block determines the engine speed, in rpm, from the Magnetic Pickup (MPU) input pins and
detects diagnostics on the MPU. The MPU used for these determinations will be an independent MPU to be used by the
EMCP 3 only.

Note: All Engine Speed Monitor setpoints require a "LEVEL 3" password. Engine Speed Monitor setpoints may also be
changed with Caterpillar Electronic Technician software without a password.

Table 8

Setpoints - Engine Speed Monitor (12)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Flywheel Teeth 95 350 N/A 95

Engine Over Speed Shutdown Threshold Set to 118% of rated


400 4330 rpm 400
speed

Engine Under Speed Warning Event Set to 86% of rated


400 4330 rpm 4330
Threshold speed

0.0 20.0 sec. 2.0


Engine Under Speed Warning Event

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 18 de 54

Notification Delay Time

Engine Under Speed Shutdown Event Set to 82% of rated


400 4330 rpm 4330
Threshold speed

Engine Under Speed Shutdown Event


0.0 20.0 sec. 2.0
Notification Delay Time

Engine Speed Sensor Configuration Setpoint Value List 0


( 12 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Enhanced Engine Monitor

The "Enhanced Engine Monitor" block provides a method to access the engine cylinder temperature parameters from the
primary data link for use in configuration logic.

Note: Standard Caterpillar product does not utilize this group of setpoints.

Table 9

Setpoints - Enhanced Engine Monitor (31)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Engine Cylinder Temperature Select "Installed" or "Not


Setpoint Value List 0
Sensor Installation Status installed"

Number of Engine Cylinders 1 20 n/a 1


( 31 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Service Maintenance Interval

The Service Maintenance Interval block annunciates a need for engine service based on engine hours or duration since
the last service, whichever occurs first.

Table 10

Setpoints - Service Maintenance Interval (31)

Setpoint Min Max Units Factory Description


Name Value Value Default

hours
Service Maintenance Interval Hours 0 2000 500 hours

Service Maintenance Interval Days 0 365 days 180

Customer Password Security Level to Reset


0 4 N/A 3
Service Maintenance Interval
( 31 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

EVENTS

Table 11

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 19 de 54

Description of Event Response Selections

Active Only Only displays event in the event log (no history on the event)

Warning Event logged, amber warning status LED

Audible Alert Activates relay output configured as "horn control"

Soft Shutdown Shutdown event allows cooldown cycle

Hard Shutdown Shutdown event skips cooldown cycle for fast engine shutdown

Breaker 1 Trip Activates relay output configured as "breaker 1 trip"

Breaker 2 Trip Activates relay output configured as "breaker 2 trip"

FTP Suppress the event until the engine is running and the fault protection timer has expired

Diagnostics Configuration

Warning and/or shutdown events should not be disabled. If warning or shutdown


events are disabled, the user may not be aware of conditions that could cause damage
to the engine, generator, or electrical loads. If warning or shutdown events are
disabled, make sure that there is another control that is set up that can diagnose the
event, and if necessary, will shut the engine down.

The "Diagnostics Configuration" block is used in order to configure the desired response for any diagnostic that is
generated by the genset control.

The Diagnostics Configuration block is subdivided into four subcategories as follows: Pressures, Temperatures, Levels
and Others. Each of the Diagnostics Configuration subcategories is shown in it's own table.

Note: Table 12 lists the available options for each setpoint in the "PRESSURES" category. The options that are available
for each setpoint are designated by an "X" in the option column.

Table 12

"PRESSURE" Setpoints - Diagnostics Configuration (15)

Loss Breaker Breaker


Audible Soft Hard Active
Setpoint Warning of FPT
Shutdown Shutdown Only
Name Utility Trip #1 Trip #2
Alert

Air Filter
Differential
Pressure Sensor
X X X X X X
Diagnostic
Response
Configuration

Engine Oil
Pressure Sensor
Diagnostic X X X X X X
Response
Configuration

Fire Extinguisher

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 20 de 54

Pressure Sensor
Diagnostic
X X X X X X
Response
Configuration

Fuel Filter
Differential
Pressure Sensor
X X X X X X
Diagnostic
Response
Configuration

Engine Oil Filter


Differential
Pressure Sensor
X X X X X X
Diagnostic
Response
Configuration

Starting Air
Pressure Sensor
Diagnostic X X X X X X
Response
Configuration
( 15 ) Each setpoint in the Diagnostics Configuration block is used in order to program a system response to the associated Suspect
Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.

Note: Table 13 lists the available options for each setpoint in the "TEMPERATURE" category. The options that are
available for each setpoint are designated by an "X" in the option column.

Table 13

"TEMPERATURE" Setpoints - Diagnostics Configuration (15)

Loss Breaker Breaker


Audible Soft Hard Active
Setpoint Warning of FPT
Shutdown Shutdown Only
Name Utility Trip #1 Trip #2
Alert

Ambient Air
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration

Engine Coolant
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration

Engine Oil
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration

Exhaust
Temperature
Sensor

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 21 de 54

Diagnostic
Response X X X X X X
Configuration

Right Exhaust
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration

Left Exhaust
Temperature
Sensor
X X X X X X
Diagnostic
Response
Configuration

Generator
Bearing #1
Temperature
Sensor X X X X X X
Diagnostic
Response
Configuration
( 15 ) Each setpoint in the Diagnostics Configuration block is used in order to program a system response to the associated Suspect
Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.

Note: Table 14 lists the available options for each setpoint in the "LEVEL" category. The options that are available for
each setpoint are designated by an "X" in the option column.

Table 14

"LEVEL" Setpoints - Diagnostics Configuration (15)

Loss Breaker Breaker


Audible Soft Hard Active
Setpoint Warning of FPT
Shutdown Shutdown Only
Name Utility Trip #1 Trip #2
Alert

Engine Coolant
Level Sensor
Diagnostic X X X X X X
Response
Configuration

Engine Oil Level


Sensor
Diagnostic X X X X X X
Response
Configuration

Fuel Level
Sensor
Diagnostic X X X X X X
Response
Configuration

External Tank
Fuel Level
Sensor X X X X X X
Diagnostic
Response

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 22 de 54

Configuration
( 15 ) Each setpoint in the Diagnostics Configuration block is used in order to program a system response to the associated Suspect
Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.

Note: Table 15 lists the available options for each setpoint in the "OTHER" setpoints category. The options that are
available for each setpoint are designated by an "X" in the option column.

Table 15

"OTHER" Setpoints - Diagnostics Configuration (15)

Loss Breaker Breaker


Audible Soft Hard Active
Setpoint Warning of FPT
Shutdown Shutdown Only
Name Utility Trip #1 Trip #2
Alert

Accessory Data
Link Diagnostic
X X X X X X
Response
Configuration

Digital Output
#1 Diagnostic
X X X X X X
Response
Configuration

Digital Output
#2 Diagnostic
X X X X X X
Response
Configuration

Engine Speed
Sensor
Diagnostic X X (16) X X
Response
Configuration

Generator
Output Sensing
System
X X X X X X
Diagnostic
Response
Configuration

Primary Data
Link Diagnostic
X X X X X X
Response
Configuration

SCADA Data
Link Diagnostic
X X X X X X X
Response
Configuration
( 15 ) Each setpoint in the Diagnostics Configuration block is used in order to program a system response to the associated Suspect
Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.
( 16 ) Setpoint Is not adjustable

Engine Protection Events Configuration

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 23 de 54

Warning and/or shutdown events should not be disabled. If warning or shutdown


events are disabled, the user may not be aware of conditions that could cause damage
to the engine, generator, or electrical loads. If warning or shutdown events are
disabled, make sure that there is another control that is set up that can diagnose the
event, and if necessary, will shut the engine down.

The Engine Protection Events Configuration block is used in order to configure the desired response for any engine
protection event generated by the genset control.

The Engine Protection events Configuration block is subdivided into 4 categories as follows: Pressures, Temperatures,
Levels and Others. Each of the Diagnostics Configuration subcategories is shown in it's own table.

Note: Table 16 lists the available options for each "PRESSURE" setpoint. The options that are available for each setpoint
are designated by an "X" in the option column.

Table 16

"PRESSURE" Setpoints - Engine Protection Events Configuration (17)

Loss
Soft Hard Breaker Breaker Active
Setpoint Warning Audible of FPT
Shutdown Shutdown Trip #1 Trip #2 Only
Name Alert Utility

High Air Filter


Differential
Pressure
X X X X
Warning Event
Response
Configuration

High Air Filter


Differential
Pressure
X X X X X
Shutdown Event
Response
Configuration

Low Air Filter


Differential
Pressure
X X X X X
Warning Event
Response
Configuration

Low Air Filter


Differential
Pressure
X X X X X X
Shutdown Event
Response
Configuration

High Gas
Pressure
Warning Event X X X X
Response
Configuration

High Gas

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 24 de 54

Pressure
Shutdown Event
X X X X X
Response
Configuration

Low Gas
Pressure
Warning Event X X X X
Response
Configuration

Low Gas
Pressure
Shutdown Event X X X X X
Response
Configuration

Low Engine Oil


Pressure
Warning Event X X X X X
Response
Configuration

Low Engine Oil


Pressure
Shutdown Event X X X X X X
Response
Configuration

High Fuel Filter


Differential
Pressure
x x x X
Warning Event
Response
Configuration

High Fuel Filter


Differential
Pressure
X X X X X
Shutdown Event
Response
Configuration

Low Fuel Filter


Differential
Pressure
X X X X X
Warning Event
Response
Configuration

Low Fuel Filter


Differential
Pressure
X X X X X X
Shutdown Event
Response
Configuration

High Engine Oil


Filter
Differential
Pressure X X X X
Warning Event
Response
Configuration

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 25 de 54

High Engine Oil


Filter
Differential
Pressure X X X X X
Shutdown Event
Response
Configuration

Low Engine Oil


Filter
Differential
Pressure X X X X X
Warning Event
Response
Configuration

Low Engine Oil


Filter
Differential
Pressure X X X X X X
Shutdown Event
Response
Configuration

High Starting
Air Pressure
Warning Event X X X X
Response
Configuration

High Starting
Air Pressure
Shutdown Event X X X X X
Response
Configuration

Low Starting
Air Pressure
Warning Event X X X X X
Response
Configuration

Low Starting
Air Pressure
Shutdown Event X X X X X X
Response
Configuration
( 17 ) Each setpoint in the Engine Protection Events Configuration block is used in order to program a system response to the
associated Suspect Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.

Table 17 lists the available options for each "TEMPERATURE" setpoint. The options that are available for each setpoint
are designated by an "X" in the option column.

Table 17

"TEMPERATURE" Setpoints - Engine Protection Events Configuration (17)

Loss
Soft Hard Breaker Breaker Active
Setpoint Warning Audible of FPT
Shutdown Shutdown Trip #1 Trip #2 Only
Name Alert Utility

High Engine

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 26 de 54

Coolant
Temperature
Warning Event
X X X X X
Response
Configuration

High Engine
Coolant
Temperature
Shutdown X X X X X X
Event Response
Configuration

Low Engine
Coolant
Temperature
Warning Event X X X X X
Response
Configuration

High Engine
Oil
Temperature
Warning Event X X X X X
Response
Configuration

High Engine
Oil
Temperature
Shutdown X X X X X X
Event Response
Configuration

Low Engine Oil


Temperature
Warning Event
X X X X X
Response
Configuration

Low Engine Oil


Temperature
Shutdown
X X X X X X
Event Response
Configuration

High Exhaust
Temperature
Warning Event
X X X X X
Response
Configuration

High Exhaust
Temperature
Shutdown X X X X X X
Event Response
Configuration

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 27 de 54

Low Exhaust
Temperature
Warning Event
X X X X X
Response
Configuration

Low Exhaust
Temperature
Shutdown
X X X X X X
Event Response
Configuration

High Right
Exhaust
Temperature
Warning Event X X X X X
Response
Configuration

High Right
Exhaust
Temperature
Shutdown X X X X X X
Event Response
Configuration

Low Right
Exhaust
Temperature
Warning Event X X X X X
Response
Configuration

Low Right
Exhaust
Temperature
Shutdown X X X X X X
Event Response
Configuration

High Left
Exhaust
Temperature
Warning Event X X X X X
Response
Configuration

High Left
Exhaust
Temperature
Shutdown X X X X X X
Event Response
Configuration

Low Left

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 28 de 54

Exhaust
Temperature
Warning Event
X X X X X
Response
Configuration

Low Left
Exhaust
Temperature
Shutdown X X X X X X
Event Response
Configuration

( 17 ) Each setpoint in the Engine Protection Events Configuration block is used in order to program a system response to the
associated Suspect Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.

Table 18 lists the available options for each "LEVEL" setpoint. The options that are available for each setpoint are
designated by an "X" in the option column.

Table 18

"LEVEL" Setpoints - Engine Protection Events Configuration (17)

Loss
Soft Hard Breaker Breaker Active
Setpoint Warning Audible of FPT
Shutdown Shutdown Trip #1 Trip #2 Only
Name Alert Utility

High Engine
Coolant Level
Warning Event
X X X X
Response
Configuration

High Engine
Coolant Level
Shutdown
X X X X X
Event Response
Configuration

Low Engine
Coolant Level
Warning Event
X X X X
Response
Configuration

Low Engine
Coolant Level
Shutdown
X X X X X
Event Response
Configuration

High Engine
Oil Level
Warning Event
X X X X
Response
Configuration

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 29 de 54

High Engine
Oil Level
Shutdown
X X X X X
Event Response
Configuration

Low Engine Oil


Level Warning
Event Response X X X X
Configuration

Low Engine Oil


Level
Shutdown
X X X X X
Event Response
Configuration

High Fuel Level


Warning Event
Response X X X X
Configuration

High Fuel Level


Shutdown
Event Response X X X X X
Configuration

Low Fuel Level


Warning Event
Response X X X X
Configuration

Low Fuel Level


Shutdown
Event Response X X X X X
Configuration

External Tank
High Fuel Level
Warning Event
X X X X
Response
Configuration

External Tank
High Fuel Level
Shutdown
X X X X X
Event Response
Configuration

External Tank
Low Fuel Level
Warning Event
X X X X
Response
Configuration

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 30 de 54

External Tank
Low Fuel Level
Shutdown
X X X X X
Event Response
Configuration

( 17 ) Each setpoint in the Engine Protection Events Configuration block is used in order to program a system response to the
associated Suspect Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.

Table 19 lists the available options for each of the "OTHER" setpoints. The options that are available for each setpoint
are designated by an "X" in the option column.

Table 19

"OTHER" Setpoints - Engine Protection Events Configuration (17)

Loss
Soft Hard Breaker Breaker Active
Setpoint Warning Audible of FPT
Shutdown Shutdown Trip #1 Trip #2 Only
Name Alert Utility

Air Damper
Closed Event
Response X X X
Configuration

Emergency
Stop Shutdown
Event Response X X (16) X X
Configuration

Engine Failure
to Start
Shutdown
X X (16) X X
Event Response
Configuration

Unexpected
Engine
Shutdown
X X (16) X X
Event Response
Configuration

Engine Over
Speed
Shutdown
X X (16) X X
Event Response
Configuration

Engine Under
Speed Warning
Event Response X X X X X
Configuration

Engine Under
Speed
Shutdown

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 31 de 54

Event Response
Configuration X X X X X X

Fuel Tank Leak


Event Response
X X X X X X
Configuration

Service
Maintenance
Interval
Warning Event X X
Response
Configuration

( 17 ) Each setpoint in the Engine Protection Events Configuration block is used in order to program a system response to the
associated Suspect Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.
( 16 ) Setpoint Is not adjustable

Generator Protection Events Configuration

Warning and/or shutdown events should not be disabled. If warning or shutdown


events are disabled, the user may not be aware of conditions that could cause damage
to the engine, generator, or electrical loads. If warning or shutdown events are
disabled, make sure that there is another control that is set up that can diagnose the
event, and if necessary, will shut the engine down.

The Generator Protection Events Configuration block is used in order to configure the desired response for any engine
protection event generated by the genset control.

Note: Table 20 lists the available options for each setpoint number. The options that are available for each setpoint are
designated by an "X" in the option column.

Table 20

Setpoints - Generator Protection Events Configuration (18)

Loss
Soft Hard Breaker Breaker Active
Setpoint Warning Audible of FPT
Shutdown Shutdown Trip #1 Trip #2 Only
Name Alert Utility

Earth Fault
Event Response X X X X X X
Configuration

High Generator
Winding #1
Temperature
X X X X X
Warning Event
Response
Configuration

High Generator
Winding #1 X X X X X X
Temperature

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 32 de 54

Shutdown
Event Response
Configuration

High Generator
Winding #2
Temperature
X X X X X
Warning Event
Response
Configuration

High Generator
Winding #2
Temperature
X X X X X X
Shutdown
Event Response
Configuration

High Generator
Winding #3
Temperature
X X X X X
Warning Event
Response
Configuration

High Generator
Winding #3
Temperature
X X X X X X
Shutdown
Event Response
Configuration

High Generator
Bearing #1
Temperature
X X X X X
Warning Event
Response
Configuration

High Generator
Bearing #1
Temperature
X X X X X X
Shutdown
Event Response
Configuration

Low Generator
Bearing #1
Temperature
X X X X X
Warning Event
Response
Configuration

Low Generator
Bearing #1
Temperature
X X X X X X
Shutdown
Event Response
Configuration

Generator Over
Current (Amp)
Warning Event X X X X
Response
Configuration

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 33 de 54

Generator Over
Current (Amp)
Shutdown X X X X X
Event Response
Configuration

Generator Over
Frequency
Warning Event X X X X
Response
Configuration

Generator Over
Frequency
Shutdown X X X X X
Event Response
Configuration

Generator
Under
Frequency
X X X X X
Warning Event
Response
Configuration

Generator
Under
Frequency
X X X X X X
Shutdown
Event Response
Configuration

Generator
Reverse Power
Warning Event X X X X
Response
Configuration

Generator
Reverse Power
Shutdown X X X X X
Event Response
Configuration

Generator Over
Voltage
Warning Event X X X X
Response
Configuration

Generator Over
Voltage
Shutdown X X X X X
Event Response
Configuration

Generator
Under Voltage
Warning Event X X X X X
Response
Configuration

Generator
Under Voltage X X X X X X
Shutdown

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 34 de 54

Event Response
Configuration
( 18 ) Each setpoint in the "Generator Protection Events Configuration" block is used in order to program a system response to the
associated Suspect Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.

Other System Events Configuration

Warning and/or shutdown events should not be disabled. If warning or shutdown


events are disabled, the user may not be aware of conditions that could cause damage
to the engine, generator, or electrical loads. If warning or shutdown events are
disabled, make sure that there is another control that is set up that can diagnose the
event, and if necessary, will shut the engine down.

The "Other System Events Configuration" block is used in order to configure the desired response for any engine
protection event generated by the genset control.

Note: Table 21 lists the available options for each setpoint number. The options that are available for each setpoint are
designated by an "X" in the option column.

Table 21

Setpoints - Other System Events Configuration (19)

Loss
Soft Hard Breaker Breaker Active
Setpoint Warning Audible of FPT
Shutdown Shutdown Trip #1 Trip #2 Only
Name Alert Utility

High Ambient
Air Temperature
Warning Event X X X X X
Response
Configuration

High Ambient
Air Temperature
Shutdown Event X X X X X X
Response
Configuration

Low Ambient
Air Temperature
Warning Event X X X X
Response
Configuration

Low Ambient
Air Temperature
Shutdown Event X X X X X
Response
Configuration

Automatic
Transfer Switch
in Normal X X X
Position Event
Response

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 35 de 54

Configuration

Automatic
Transfer Switch
in Emergency
X X X
Position Event
Response
Configuration

Battery Charger
Failure
Diagnostic X X X
Response
Configuration

High Battery
Voltage
Warning Event X X X X
Response
Configuration

High Battery
Voltage
Shutdown Event X X X X X
Response
Configuration

Low Battery
Voltage
Warning Event X X X X X
Response
Configuration

Low Battery
Charging
System Voltage
X X X X X
Warning Event
Response
Configuration

Generator
Breaker Failure
to Open Event X X X X X
Response
Configuration

Generator
Breaker Failure
to Close Event X X x X X
Response
Configuration

Generator
Breaker Open
X X X
Event Response
Configuration

Generator
Breaker Closed
X X X
Event Response
Configuration

Utility Breaker
Failure to Open X X X X X
Event Response

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 36 de 54

Configuration

Utility Breaker
Failure to Close
X X X X X
Event Response
Configuration

Utility Breaker
Open Event
X X X
Response
Configuration

Utility Breaker
Closed Event
X X X
Response
Configuration

Emergency
Shutdown
Override Mode
X (16) X
Active Warning
Event Response
Configuration

Engine in
Cooldown
X X X
Event Response
Configuration

Engine Speed-
Generator
Output
Frequency
X X X X
Mismatch
Warning Event
Response
Configuration

Custom Event
#1 High
Warning Event X X X X X
Response
Configuration

Custom Event
#1 High
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#1 Low
Warning Event X X X X X
Response
Configuration

Custom Event
#1 Low
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#1 Event X X X X X X X X X
Response

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 37 de 54

Configuration

Custom Event
#2 High
Warning Event X X X X x
Response
Configuration

Custom Event
#2 High
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#2 Low
Warning Event X X X X X
Response
Configuration

Custom Event
#2 Low
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#2 Event
X X X X X X X X X
Response
Configuration

Custom Event
#3 High
Warning Event X X X X X
Response
Configuration

Custom Event
#3 High
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#3 Low
Warning Event X X X X X
Response
Configuration

Custom Event
#3 Low
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#3 Event
X X X X X X X X X
Response
Configuration

Custom Event
#4 High
Warning Event X X X X X
Response
Configuration

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 38 de 54

Custom Event
#4 High
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#4 Low
Warning Event X X X X X
Response
Configuration

Custom Event
#4 Low
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#4 Event
X X X X X X X X X
Response
Configuration

Custom Event
#5 High
Warning Event X X X X X
Response
Configuration

Custom Event
#5 High
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#5 Low
Warning Event X X X X X
Response
Configuration

Custom Event
#5 Low
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#5 Event
X X X X X X X X X
Response
Configuration

Custom Event
#6 High
Warning Event X X X X X
Response
Configuration

Custom Event
#6 High
Shutdown Event X X X X X X
Response
Configuration

Custom Event

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 39 de 54

#6 Low
Warning Event
X X X X X
Response
Configuration

Custom Event
#6 Low
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#6 Event
X X X X X X X X X
Response
Configuration

Custom Event
#7 High
Warning Event X X X X X
Response
Configuration

Custom Event
#7 High
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#7 Low
Warning Event X X X X X
Response
Configuration

Custom Event
#7 Low
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#7 Event
X X X X X X X X X
Response
Configuration

Custom Event
#8 High
Warning Event X X X X X
Response
Configuration

Custom Event
#8 High
Shutdown Event X X X X X X
Response
Configuration

Custom Event
#8 Low
Warning Event X X X X X
Response
Configuration

Custom Event
#8 Low

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 40 de 54

Shutdown Event
Response X X X X X X
Configuration

Custom Event
#8 Event
X X X X X X X X X
Response
Configuration

High Fire
Extinguisher
Pressure
X X X X
Warning Event
Response
Configuration

High Fire
Extinguisher
Pressure
X X X X X
Shutdown Event
Response
Configuration

Low Fire
Extinguisher
Pressure
X X X X X
Warning Event
Response
Configuration

Low Fire
Extinguisher
Pressure
X X X X X X
Shutdown Event
Response
Configuration

Generator
Control Not in
Automatic
X X X
Warning Event
Response
Configuration

Loss of Utility
Event Response X X X
Configuration

Utility to
Generator
Transfer Failure
X X X X
Warning Event
Response
Configuration

Utility to
Generator
Transfer Failure
X X X X
Shutdown Event
Response
Configuration

Generator to
Utility Transfer X X X X
Failure Warning

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 41 de 54

Event Response
Configuration
( 19 ) Each setpoint in the "Other System Events Configuration" block is used in order to program a system response to the associated
Suspect Parameter Number/Failure Mode Identifier (SPN/FMI) for any internal source.
( 16 ) Setpoint Is not adjustable

Event Input Functions

The Event Input Function block allows the user of the genset to define selected inputs to cause user-defined events to
become active.

Table 22

Setpoints - Event Input Functions (13)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Custom Event #NN Active State Settings for custom


N/A N/A N/A High
Configuration events #1- #8

Custom Event #NN Event Settings for custom


0 250 sec. 0
Notification Delay Time events #1- #8

Custom Event #NN Suspect Settings for custom


N/A N/A N/A 107
Parameter Number events #1- #8

Custom Event #NN Failure Mode Settings for custom


0 20 N/A 15
Identifier events #1- #8
( 13 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Event Output Functions

The Event Output function block provides a method to access the active status of an event for use in configuration logic

Table 23

Setpoints - Event Output Functions (14)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Event Output Function #NN Settings for event output


N/A N/A N/A Disabled
Trigger Condition functions #1- #30

Event Output Function #NN Settings for event output


N/A N/A N/A 100
Suspect Parameter Number functions #1- #30
( 14 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Event System

Event System block provides a method to log system events to non-volatile memory. The Event System block also
manages the status of the events in order to provide overall status outputs to the system.

Table 24

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 42 de 54

Setpoints - Event System (20)

Setpoint Min Max Units Factory Description


Name Value Value Default

Event Warning Condition Response Auto


Setpoint Value List 1
Reset Enable Status

Event Audible Alert Response Auto Reset


Setpoint Value List 1
Enable Status

Event Loss of Utility Response Auto Reset


Setpoint Value List 1
Enable Status

Event Breaker #1 Trip Response Auto Reset


Setpoint Value List 1
Enable Status

Event Breaker #2 Trip Response Auto Reset


Setpoint Value List 1
Enable Status
( 20 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Generator Monitor/Protect

Enhanced Generator Monitor

The Enhanced Generator Monitor block provides a method to access the generator monitored parameters from the
Accessory Data Link for use in configuration logic. The following generator values will be monitored:

Front bearing temperature

Rear bearing temperature

Winding #1 temperature

Winding #2 temperature

Winding #3 temperature

Table 25

Setpoints - Enhanced Generator Monitor (31)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Generator Winding Set to "Installed" when a temperature


Temperature Sensor Setpoint Value List module is installed on the accessory
Installation Status data link

Number of Generator
Bearing Temperature Sensors Setpoint Value List

( 31 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Generator AC Monitor

The Generator AC Monitor block measures the AC voltage and current output by the generator. The following generator
values will be monitored:

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 43 de 54

True RMS line - line voltages

Average line - line voltage

True RMS line - neutral voltages (for star/wye configurations)

Average line-neutral voltage (for star/wye configurations)

True RMS phase currents

Average phase current

Generator output frequency

Table 26

Setpoints - Generator AC Monitor (21)

Min Max
Setpoint Units Factory
Value Value Description
Name Default

Configurations can be:


"Star/Wye",
Generator Connection "Delta/3 Wire"
Setpoint Value List 0
Configuration "Delta/4 Wire"
"Single Phase 2 Wire"
"Single Phase 3 Wire"

For direct sensing, leave at default value. For


Generator Potential
50000 an application requiring a potential
Transformer Primary 1 V 1
transformer, set to transformer primary
Winding Rating
winding value.

For direct sensing, leave at default value. For


Generator Potential
an application requiring a potential
Transformer Secondary 1 240 V 1
transformer, set to transformer secondary
Winding Rating
winding value

Generator Current
Set to current transformer primary winding
Transformer Primary 1 7000 A 75
value
Winding Rating

Generator Current
Transformer Secondary 1 5 A 5 Can only be set to 1 or 5
Winding Rating

Number of Generator N/A


0 200 4
Poles

Generator Rated
Setpoint Value List 0
Frequency

Generator Rated Voltage 50000


100 V 100

50000
Generator Rated Power 1 kW 1

Generator Rated 50000 kVA


1 1
Apparent Power
( 21 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 44 de 54

Generator AC Power Monitor

The Generator AC Power Monitor Block measures all generator power quantities following generator values will be
monitored:

Per phase kW (for star/wye configurations)

Total kW

Total kW hours imported

Total kW hours exported

Percent kW output

Per phase kVAr (for star/wye confutations)

Total kVAr

Total kVAr hours imported

Total kVAr hours imported

Percent kVAr output

Per phase kVA (for star/wye confutations)

Total kVA

Percent kVA output

Per phase genset output Power Factor with lead/lag indication (for star/wye confutations)

Average output Power Factor with lead/lag indication

Note: Per phase quantities (kW, kVAr, KVA, and Power Factor) will be monitored for 3-phase, 4-wire star-connected
configurations)

Table 27

Setpoints - Generator AC Power Monitor (31)

Setpoint Min Max Units Factory Description


Name Value Value Default

Customer Password Security Level to Reset


0 3 N/A 3
Generator Energy Meters
( 31 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Generator Over Current

The generator overcurrent block detects an overcurrent condition that persists for a duration that is a function of the
overcurrent level or a condition that exceeds a threshold for a programmed duration.

Table 28

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 45 de 54

Setpoints - Generator Over Current (23)

Min Max
Setpoint Units Factory
Value Value Description
Name Default

Generator Definite Time Over


Threshold for the Over Current
Current (Amp) Warning Event 80 130 % 100
Warning
Percentage Threshold

Generator Inverse Time Over Time multiplier setpoint (TM) used in


N/A
Current (Amp) Shutdown Event 0.05 10.00 0.27 equation shown in Illustration 5
Time Multiplier

If current is above this setpoint value


Generator Definite Time Over
for the specified time (setpoint #4)
Current (Amp) Shutdown Event 100 300 % 125
there will be an overcurrent shutdown.
Percentage Threshold

Generator Definite Time Over


Current (Amp) Shutdown Event 0.1 20.0 sec. 10 Time delay for setpoint #3
Notification Delay Time
( 23 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Illustration 5 g01239796

Generator Over / Under Frequency

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 46 de 54

The Generator Over/Under Frequency block detects bus frequency above or below programmable thresholds for a
programmable duration and activates an alarm.

Table 29

Setpoints - Generator Over / Under Frequency (24)

Setpoint Min Max Units Factory Description


Name Value Value Default

Generator Over Frequency Warning Event


80 120 % 105
Percentage Threshold

Generator Over Frequency Warning Event


0 120 sec. 10
Notification Delay Time

Generator Over Frequency Shutdown Event


80.0 120 % 110
Percentage Threshold

Generator Over Frequency Shutdown Event


0 120 sec. 2
Notification Delay Time

Generator Under Frequency Warning Event


80.0 120.0 % 95.0
Percentage Threshold

Generator Under Frequency Warning Event


0 120 sec. 10
Notification Delay Time

Generator Under Frequency Shutdown Event


80.0 120.0 % 90.0
Percentage Threshold

Generator Under Frequency Shutdown Event


0 120 sec. 4
Notification Delay Time
( 24 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Generator Over / Under voltage

The Generator Over/Under Voltage block detects generator output voltage above or below programmable thresholds for
a programmable duration and activates an alarm.

Table 30

Setpoints - Generator Over / Under Voltage (25)

Setpoint Min Max Units Factory Description


Name Value Value Default

Generator Over Voltage Warning Event


100 125 % 105
Percentage Threshold

Generator Over Voltage Warning Event


0 120 sec. 10
Notification Delay Time

Generator Over Voltage Shutdown Event


100 125 % 110
Percentage Threshold

Generator Over Voltage Shutdown Event


0 120 sec. 2
Notification Delay Time

Generator Under Voltage Warning Event


60 100 % 95
Percentage Threshold

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 47 de 54

Generator Under Voltage Warning Event


0 120 sec. 10
Notification Delay Time

Generator Under Voltage Shutdown Event


60 100 % 90
Threshold

Generator Under Voltage Shutdown Event


0 120 sec. 4
Notification Delay Time
( 25 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Generator Reverse Power

The Generator Reverse Power block detects a reverse power condition that persists for a duration above a programmed
level.

Table 31

Setpoints - Generator Reverse Power (26)

Setpoint Min Max Units Factory Description


Name Value Value Default

Generator Reverse Power Warning Event


1 20 % 5
Percentage Threshold

Generator Reverse Power Warning Event


0 30 sec. 10
Notification Delay Time

Generator Reverse Power Shutdown Event


1 20 % 10
Percentage Threshold

Generator Reverse Power Shutdown Event


0 30 sec. 10
Notification Delay Time
( 26 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Discrete Input/Output (I/O)

Digital Inputs

The Digital Input block is used in order to relay on/off information such as switch closures to the EMCP 3.

Note: There are eight digital inputs on "EMCP 3.2" and "EMCP 3.3". There are six digital inputs on "EMCP 3.1."

Table 32

Setpoints - Digital Inputs (5)

Min Max
Setpoint Units Factory
Value Value Description
Name Default

Active Active N/A Active Activating the E-STOP input will cause the generator set
E-STOP
Low High High to stop immediately.

Setpoint allows for starting and stopping the genset from


REMOTE Active Active N/A Active a remote location.
INITIATE Low High Low If input is active and the engine mode switch is in
"AUTO", the engine will attempt to start and run. Once

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 48 de 54

the input becomes inactive, the engine will enter into


cooldown (if programmed) and then STOP.

Digital #3 (6) Active Active N/A Active


Low High Low

Digital #4 (6) Active Active N/A Active


Low High Low

Digital #5 (6) Active Active N/A Active


Low High Low
The inputs can be set to any of the values listed in Table
33
Digital #6 (6) Active Active N/A Active
Low High Low

Digital #7 (6) Active Active N/A Active


Low High Low

Digital #8 (6) Active Active N/A Active


Low High Low
(5) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.
(6) The "Digital Inputs" parameter can only be set to "Active High" or "Active Low" in order to initiate a High Warning, Low
Warning, High Shutdown. Low Shutdown, or Status.

Table 33

Available Digital Inputs

Pressures
Air Filter Differential Pressure Other
Engine Oil Pressure Air Damper Closed
Fire Extinguisher Pressure ATS in Normal Position
Fuel Filter Differential Pressure ATS in Emergency Position
Engine Oil Filter Differential Pressure Battery Charger Failure
Battery Charging System Voltage
Starting Air Pressure Battery Voltage
Gas Pressure Fuel Leak
Custom Event
Temperatures Earth Fault
Ambient Air Temperature Earth Leakage
Engine Coolant Temperature Engine Inlet Manifold Charge Combustion
Engine Oil Temperature
Exhaust Temperature EPS Supplying Load
Generator Rear Bearing Temperature Generator Circuit Breaker Closed
Right Exhaust Temperature Generator Circuit Breaker Open
Left Exhaust Temperature Generator Frequency
Generator Winding #1 Temperature Generator Voltage
Generator Winding #2 Temperature Generator Current
Generator Winding #3 Temperature Generator Power
Loss of Utility
Levels Utility Breaker Closed
Engine Coolant Level Utility Breaker Open
Engine Oil Level Utility to Generator Transfer Failure
Fuel Level Generator to Utility Transfer Failure
External Tank Fuel Level

Table 34

Custom Event Setpoint Value for Event Input Functions cVue Block

Setpoint

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 49 de 54

Block Instance# Value Description

1 701 Custom Event (Instance #1 only)

2 702 Custom Event (Instance #2 only)

3 703 Custom Event (Instance #3 only)

4 704 Custom Event (Instance #4 only)

5 705 Custom Event (Instance #5 only)

6 706 Custom Event (Instance #6 only)

7 707 Custom Event (Instance #7 only)

8 708 Custom Event (Instance #8 only)

Digital Outputs

The Digital Output block is used in order to relay on/off information from the EMCP 3 for purposes such as operating
relays, solenoids and indicator lamps.

There are two digital outputs on "EMCP 3.3". There is one digital output on "EMCP 3.2". There are no digital outputs on
"EMCP 3.1"

Table 35

Setpoints - Digital Outputs (7)

Setpoint Min Value Max Value Units Factory Default Description


Name

Digital Output #1 Active State


Low High N/A Low
Configuration

Digital Output #2 Active State


Low High N/A Low
Configuration
(7) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Relay Outputs

The Relay Output block is used in order to relay on/off information from the EMCP 3 for purposes such as operating
relays, solenoids and indicator lamps.

There are eight relay outputs on the EMCP 3.2 and EMCP 3.3. Six of the outputs have normally open contacts and two
of the outputs have normally open and normally closed contacts.

There are six normally open relay outputs on the EMCP 3.1. There are no normally closed outputs on the EMCP 3.1

Note: The "active" state for relay outputs is not configurable.

Table 36

Setpoints - Relay Outputs (29)

Setpoint Min Max Units Factory


Description
Name Value Value Default

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 50 de 54

Relay Output #1 is always


Relay Output #1 Active N/A
N/A N/A High configured as the "Starter Motor
State Configuration
Relay"

Relay Output #2 Active N/A Relay #2 is always configured as the


N/A N/A High
State Configuration "Fuel Control Relay"

Relay Output #3 Active N/A Relay Output #3 is controlled by


N/A N/A High
State Configuration Digital Selector #1

Relay Output #4 Active N/A Relay Output #4 is controlled by


N/A N/A High
State Configuration Digital Selector #2

Relay Output #5 Active N/A Relay Output #5 is controlled by


N/A N/A High
State Configuration Digital Selector #3

Relay Output #6 is controlled by


Relay Output #6 Active N/A Digital Selector #4
N/A N/A High
State Configuration The output can be set to "Active
High" or" Active Low"

Relay Output #7 Active N/A Relay Output #7 is controlled by


N/A N/A High
State Configuration Digital Selector #5

Relay Output #8 Active N/A Relay Output #8 is controlled by


N/A N/A High
State Configuration Digital Selector #6
( 29 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Spare Analog Input

The Spare Analog Input block converts a resistive sender value to engineering units, detects sender diagnostics, and
detects a high or low condition on the spare sender input.

Note: If you have selected a spare input to be a temperature, setpoints 6, 7, 10, and 11 will not appear since they are
associated with pressures and levels. If you have selected a spare input to be a pressure, setpoints 5, 7, 9, and 11 will not
appear since they are associated with temperatures and levels. If you have selected a spare input to be a level, setpoints 5,
6, 9, and 10 will not appear since they are associated with temperatures and pressures.

Table 37

Setpoints - Spare Analog Input (29)

Min
Setpoint Max Units Factory
Value Description
Name Value Default

Set to "Enabled" for MUI engines


Spare Analog Input Enable N/A
N/A N/A Enabled and set to "Disabled" for EUI
Status
engines

Spare Analog Input Type N/A Temperature Select "Temperature", "Pressure",


N/A N/A
Configuration or "Level".

Spare Analog Input Suspect N/A


N/A N/A 175 Oil temperature
Parameter Number (SPN)

Spare Analog Input High


Percentage Warning Event 0 100 % 0
Threshold

Spare Analog Input High -273 1,735


Temperature Warning Event Deg. 102 °C (216 °

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 51 de 54

Threshold C F)

Spare Analog Input High


10,000
Pressure Warning Event -250 kPa -250
Threshold

Spare Analog Input High


Warning Event Notification 0 60 sec. 2
Delay Time

Spare Analog Input High


Percentage Shutdown Event 0 100 % 0
Threshold

Spare Analog Input High


Deg.
Temperature Shutdown Event -273 1,735 107 °C (225 °
C
Threshold F)

Spare Analog Input High


10,000
Pressure Shutdown Event -250 kPa -250
Threshold

Spare Analog Input High


Shutdown Event Notification 0 60 sec. 10
Delay Time

Spare Analog Input Low


Percentage Warning Event 0 100 % 100
Threshold

Spare Analog Input Low


Deg.
Temperature Warning Event -273 1735 1735
C
Threshold

Spare Analog Input Low


-250 10000 kPa 10000
Warning Event Threshold

Spare Analog Input Low


Warning Event Notification 0 60 sec. 0
Delay Time

Spare Analog Input Low


Percentage Shutdown Event 0 100 % 100
Threshold

Spare Analog Input Low


Deg.
Temperature Shutdown Event -273 1735 1735
C
Threshold

Spare Analog Input Low


Pressure Shutdown Event -250 10000 kPa 10000
Threshold

Spare Analog Input Low


Shutdown Event Notification 0 60 sec. 0
Delay Time
( 29 ) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

NETWORK

Data Link - SCADA

The SCADA Data Link block is used in order to ()communicate with a System Control and Data Acquisition (SCADA)

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 52 de 54

and is used for support of a service tool connection. SCADA Data Link will use the Modbus protocol with an RS-485
half duplex hardware layer operation at a minimum 2400 bps.

Table 38

Setpoints - Data Link - SCADA (4)

Setpoint Min Value Max Units Factory


Description
Name Value Default

SCADA Data Link Baud Rate 2400 57600 N/A 19200

Select "None", "Odd", or


SCADA Data Link Parity N/A N/A N/A None
"Even"

SCADA Data Link Slave Address


1 247 N/A 1

SCADA Data Link Access


0 0xfffff N/A 0
Password

SCADA Data Link Connection


0.1 3600.0 sec. 30
Timeout Interval

RS-485 Bias Resistor Enable


Disabled Enabled N/A Enabled
Status
(4) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

OTHER

Digital Selectors

The Digital Selector block determines what "EVENTS" or "STATUS" will cause each of the relays to activate.

Table 39

Setpoints - Digital Selectors (8)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Digital Selector #1 controls


Relay Output #3
Configuration Options are:
Disabled
Digital Selector #1 Source Use Input #1
Input #1
Configuration Use Input #2
Use Input #3
Use Input #4
Use Input #5
Use Data Link Input

Digital Selector #2 controls


Relay Output #4
Configuration Options are:
Digital Selector #2 Source Disabled
Input #4 Use Input #1
Configuration
Use Input #2
Use Input #3
Use Input #4
Use Input #5

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 53 de 54

Use Data Link Input

Digital Selector #3 controls


Relay Output #5
Configuration Options are:
Disabled
Digital Selector #3 Source Use Input #1
Input #6
Configuration Use Input #2
Use Input #3
Use Input #4
Use Input #5
Use Data Link Input

Digital Selector #4 controls


Relay Output #6
Configuration Options are:
Disabled
Digital Selector #4 Source Use Input #1
Input #6
Configuration Use Input #2
Use Input #3
Use Input #4
Use Input #5
Use Data Link Input

Digital Selector #5 controls


Relay Output #7
Configuration Options are:
Disabled
Digital Selector #5 Source Use Input #1
Disabled
Configuration Use Input #2
Use Input #3
Use Input #4
Use Input #5
Use Data Link Input

Digital Selector #6 controls


Relay Output #8
Configuration Options are:
Disabled
Digital Selector #6 Source Use Input #1
Disabled
Configuration Use Input #2
Use Input #3
Use Input #4
Use Input #5
Use Data Link Input

Digital Selector #7 controls


Digital Output #1
Configuration Options are:
Disabled
Digital Selector #7 Source Use Input #1
Input #1
Configuration Use Input #2
Use Input #3
Use Input #4
Use Input #5
Use Data Link Input

Digital Selector #8 controls


Digital Output #2
Configuration Options are:
Digital Selector #8 Source Disabled
Disabled
Configuration Use Input #1
Use Input #2
Use Input #3
Use Input #4

https://sisweb.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisw... 06/03/2009
3516B Generator Set ZAP00001-UP(SEBP4057 - 02) - Estructura del documento Página 54 de 54

Use Input #5
Use Data Link Input
(8) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.

Electronic Control Module Reduced Power Mode

The Electronic Control Module block Reduced Power Mode block minimizes drain on the battery when the engine is
stopped and the control is operating in a standby mode.

Note: Standard Caterpillar product does not utilize this group of setpoints.

Table 40

Setpoints - Electronic Control Module Reduced Power Mode (9)

Setpoint Min Max Units Factory


Description
Name Value Value Default

Electronic Control Module


Disabled N/A Allows control to go into
Reduced Power Mode Enable Enabled Disabled
reduced power mode
Status

Electronic Control Module


min.
Reduced Power Mode Delay Time 0 120 30

(9) The setpoints that are stored or the setpoints that are being programmed must match the specified setpoints of the particular
generator set.