PLC5 - ControlNet
PLC5 - ControlNet
ControlNet
PLC-5
Quick Start
Programmable
Controllers
Phase 1.25
Cat. No. 1785-L20C,
-L40C, -L60C, -L80C
product icon
Important User Because of the variety of uses for the products described in this
Information publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
Preface
Read this preface to familiarize yourself with the rest of the manual.
This preface covers the following topics:
• who should use this manual
• the purpose of this manual
• conventions used in this manual
• Rockwell Automation support
Who Should Use this Use this manual if you are new to the ControlNet PLC-5 processor.
Manual
For more information, refer to the publications listed in the Related
Documentation section of this Preface, or contact your local
Rockwell Automation representative.
Purpose of this Manual This manual introduces you to installing and using a ControlNet
PLC-5 processor system. In addition, it shows you how to set up a
system using a typical configuration. Since this is a Quick Start
manual, we do not cover all of the ControlNet PLC-5 processor
features, but give you enough information to get you started.
Related Documentation
Conventions Used in This The following conventions are used throughout this manual:
Manual • Bulleted lists provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical
information.
• Italic type is used for emphasis.
• Text in this font indicates words or phrases you should type.
• Key names match the names shown and appear in bold, capital
letters (for example, ENTER).
" Tip: We use this convention to call attention to helpful information.
Rockwell Automation Support Rockwell Automation offers support services worldwide, with over
75 Sales/Support Offices, 512 authorized Distributors and 260
authorized Systems Integrators located throughout the United States
alone, plus Allen–Bradley representatives in every major country in
the world.
If you have any suggestions for how this manual could be made
more useful to you, please contact us at the address below:
Notes:
Check Your Components For this quick start, you need this hardware and software:
Hardware
ControlNet PLC-5 processor 1785-L20C, -L40C, L60C, -L80C
ControlNet network access cable 1786-CP
1771 I/O chassis 1771-A1B
power supply 1771-P4S
personal computer your choice
communication interface card 1784-KTCx
Software
RSLogix5 programming software
6200 programming software
RSLinx communication software
1771-P4S
power supply
PC with
Programming
Software
1786-CP
PLC-5/40C
processor
Compliance to If this product has the CE mark it is approved for installation within
European Union Directives the European Union and EEA regions. It has been designed and
tested to meet the following directives.
EMC Directive
Notes
PC with
Programming
Software
PLC-5/20C Internal
Processor Power Supply
ControlNet network
access cable (1786-CP)
Pressed in
at top ON (closed)
Pressed in Switch
at bottom OFF (open) Last State
1
Outputs of this I/O chassis remain in their last state when
on
a hardware failure occurs. ➀
Outputs of this I/O chassis are turned off when a
off
hardware failure occurs. ➀
Always
Off Switches
Addressing
4 5
off off 2 –slot
off on 1 –slot
on off 1/2 – slot
on on Not allowed
Switches
EEPROM Transfer
6 7
off off EEPROM memory transfer to processor memory at power-up. ➁ ➂
EEPROM memory transfers to processor memory if processor memory
on on
not valid.
on off EEPROM memory does not transfer to processor memory. ➃
Switch
Processor Memory Protection
8
off Processor memory protection disabled.
➀ Regardless of this switch setting, outputs are turned off when any of the following occurs:
• processor detects a runtime error
• an I/O chassis backplane fault occurs
• you select program or test mode
• you set a status file bit to reset a local rack
➁ If an EEPROM module is not installed and processor memory is valid, the processor’s PROC LED indicator blinks,
and the processor sets S:11/9, bit 9 in the major fault status word. To clear this fault, change the processor from
program mode to run mode and back to program mode.
➂ If the processor’s keyswitch is set in REMote, the processor enters remote RUN after it powers up and has its
memory updated by the EEPROM module.
➃ A processor fault (solid red PROC LED) occurs if processor memory is not valid.
➄ You cannot clear processor memory when this switch is on. 19309
Keying
Bands
between
• 40 & 42
• 54 & 56
20609–M
To Grounding
Electrode System
Ground Lug
Nut and
Captive Washer
Star
Washer
Ground Lug
I/O Chassis Wall
20626–M
locking bar
PLC-5/20
1 2 3 4 5 6 7
Processor
Battery Connector
side view
Battery Cover
down For series E and later processors:
57.6 Kbaud use this switch to select baud rate
For series D and earlier processors:
up this switch is always off
230 Kbaud
Card Guides
20610–M
2 Specify the serial port configuration for
channel 0.
Battery bottom view of PLC-5/20C processor
Front of
Processor
More For detailed information about handling and disposing of the battery
as well as other important guidelines, see publication AG-5.4.
1 2 3 4 5 6 7 8 9 10
For more information, see the ControlNet PLC-5 Programmable bottom view of PLC-5/40C and -5/80C processor
More Controllers User Manual, publication number 1785-6.5.14.
Front of
Processor
side view
1 2 3 4 5 6 7 8 9 10
OFF
Locking
Bar
Connect the Personal For more information, see the installation instructions or user manual
More
Computer to the for the particular module you are installing.
PLC-5 Processor
For more information, see:
More
• ControlNet PLC-5 Programmable Controllers User Manual,
publication number 1785-6.5.14
• the documentation provided with your communication card
• Data Highway/Data Highway Plus/Data Highway II/Data
Highway 485 Cable Installation Manual, publication 1770-6.2.2
Install the Software and Before you install your programming software, make certain you
Set Up the Programming meet the requirements for that software. Then, follow the procedures
System outlined in the online help and documentation to install the software
and configure communication.
Start the Programming Start the programming software by following the procedures
Software described in your programming software documentation.
If you have difficulty, verify that the power supply is turned on.
To monitor your system as you configure and run it, check the
processor LED display for the following indicators:
Power Up the System Power up the system if you have not done so already. Check the
LED display on the processor. If you are using NAP cable, then the
ControlNet LEDs will flash red. If you are using coaxial trunk cable,
with taps and terminators, then the ControlNet channels that are
connected will be steady green, and those that are unconnected will
flash red.
Notes:
Using the General The general status indicators inform you of the general operational
Status Indicators state of the processor.
Using the ControlNet The ControlNet status indicators inform you of the operational state
Status Indicators of the ControlNet network.
Alternating Incorrect node configuration Check network address and other ControlNet
Red/Off configuration parameters
Off
O Channel
annel disabled
i able No action required
or Configure for ControlNet communication
A B Steady Normal operation No action required
Green
Flashing
la in Temporary
e orar error
errors No action required
Green/Off
reen O Make sure that ControlNet is properly terminated
The processor’s ControlNet address Configure the ControlNet network so that UMAX is at
is above UMAX least as high as the processor’s ControlNet address.
Set the processor’s ControlNet address at or below
UMAX.
Flashing Media fault Check media for broken cables, loose connectors,
Red/Off
e O missing terminators, etc.
No other nodes present on network Add other nodes to the network
Flashing
la in Incorrect
ncorrect network
net or con
configuration
i uration Cycle power or reset unit
Red/Green
e reen If fault persists, contact your Allen-Bradley Company,
Inc. representative or distributor
À Definition of terms:
•alternating—the two indicators alternate between the two defined states at the same time (applies to both indicators viewed together);
the two indicators are always in opposite states, out of phase
•flashing—the indicator alternates between the two defined states (applies to each indicator viewed independent of the other); if both
indicators are flashing, they flash together, in phase
•steady—indicator is on continuously in the defined state
® The PLC-5/80C processor has a limit of 56K words per program file and 32 K words per data table file. The PLC-5/80C processor has 64K
words of total data table space.
CSA Hazardous Location Approval Approbation d’utilisation dans des emplacements dangereux par la
CSA
CSA certifies products for general use as well as for use in La CSA certifie les produits d’utilisation générale aussi bien que ceux qui
hazardous locations. Actual CSA certification is indicated by the s’utilisent dans des emplacements dangereux. La certification CSA en
product label as shown below, and not by statements in any user vigueur est indiquée par l’étiquette du produit et non par des
documentation. affirmations dans la documentation à l’usage des utilisateurs.
Example of the CSA certification product label Exemple d’étiquette de certification d’un produit par la CSA
To comply with CSA certification for use in hazardous locations, the Pour satisfaire à la certification de la CSA dans des endroits dangereux,
following information becomes a part of the product literature for les informations suivantes font partie intégrante de la documentation des
CSA-certified Allen-Bradley industrial control products. produits industriels de contrôle Allen-Bradley certifiés par la CSA.
• This equipment is suitable for use in Class I, Division 2, • Cet équipement convient à l’utilisation dans des emplacements de
Groups A, B, C, D, or non-hazardous locations only. Classe 1, Division 2, Groupes A, B, C, D, ou ne convient qu’à
• The products having the appropriate CSA markings (that is, Class l’utilisation dans des endroits non dangereux.
I Division 2, Groups A, B, C, D), are certified for use in other • Les produits portant le marquage approprié de la CSA (c’est à dire,
equipment where the suitability of combination (that is, application Classe 1, Division 2, Groupes A, B, C, D) sont certifiés à l’utilisation
or use) is determined by the CSA or the local inspection office pour d’autres équipements où la convenance de combinaison
having jurisdiction. (application ou utilisation) est déterminée par la CSA ou le bureau local
d’inspection qualifié.
Important: Due to the modular nature of a PLC control system, the Important: Par suite de la nature modulaire du système de contrôle PLC,
product with the highest temperature rating determines the overall le produit ayant le taux le plus élevé de température détermine le taux
temperature code rating of a PLC control system in a Class I, d’ensemble du code de température du système de contrôle d’un PLC
Division 2 location. The temperature code rating is marked on the dans un emplacement de Classe 1, Division 2. Le taux du code de
product label as shown. température est indiqué sur l’étiquette du produit.
The following warnings apply to products having CSA certification for Les avertissements suivants s’appliquent aux produits ayant la
use in hazardous locations. certification CSA pour leur utilisation dans des emplacements dangereux.
Notes
Pub. Name ControlNet PLC-5 Programmable Controllers Quick Start, Phase 1.25
Cat. No. 1785-L20C, -40C, -60C, -80C Pub. No. 1785-10.7 Pub. Date October 1997 Part No. 955129-12
Clarity
What is unclear?
Sequence
What is not in the right order?
Other Comments
Use back for more comments.
Return to: Technical Communication, Allen-Bradley Co., 1 Allen-Bradley Drive, Mayfield Hts., OH 44124 Phone: (216)646-3166
FAX: (216)646-4320
Other Comments
PLEASE REMOVE
PLEASE FOLD HERE
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
1 ALLEN BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve
productivity and quality for more than 90 years. We design, manufacture and support a broad
range of automation products worldwide. They include logic processors, power and motion
control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the
world’s leading technology companies.
Worldwide representation.
Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark •
Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy •
Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto
Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey •
United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444