Topic 6 : Inspection, Testing and Certification
Topic 6 : Inspection, Testing and Certification
Topic 6 : Inspection, Testing and Certification
│ Topic 6 │
1
1. Work Completion Certificate
2. Periodic Inspection, Testing and Certification
3. Procedures of Inspection
4. Sequence of Test
2
1. Work Completion Certificate
A fixed electrical installation shall, after
completion (including any work completed after
repair, alteration or addition) and before it is
energized for use, be inspected, tested and
certified by a registered electrical worker to
confirm that the requirements of the Ordinance
have been met.
In the case of a repair, alteration or addition to a
fixed electrical installation, only the affected
parts of the installation need to be inspected,
tested and certified under this regulation.
3
1. Work Completion Certificate
4
2. Periodic Inspection, Testing and Certification
5
2. Periodic Inspection, Testing and Certification
6
2. Periodic Inspection, Testing and Certification
7
2. Periodic Inspection, Testing and Certification
8
3. Periodic Inspection
Inspection of low voltage installations (Code 21A)
A visual inspection should be made to verify that the
electrical installation is correctly selected and erected.
Examples of checking items:
Adequacy of working space, access and maintenance facilities
Labeling of circuits, protective devices, switches and etc.
Presence of danger and warning notices
Presence of diagrams and instructions
Protection against Basic (Direct Contact) and Fault (Indirect
Contact)
Identification of conductors, and so on.
9
4. Sequence of Test
Testing of low voltage installation (Code 21B)
Safety
Precaution should be taken during testing and the
method of tests should be such that no danger to
persons or property can occur even if the circuit
being tested is defective.
Sequence of Test
The following items, where relevant, are to be tested
preferably in the sequence indicated below:
1. Continuity of protective conductors, including
main and supplementary equipotential bonding
2. Continuity of ring final circuit conductors,
3. Insulation resistance
10
4. Sequence of Test
11
4. Sequence of Test
12
4. Sequence of Test
(1) Continuity of protective conductors
13
4. Sequence of Test
(1) Continuity of protective conductors(cont.)
The test current may be a.c. or d.c. but should be derived from a source
with an open circuit voltage of not less than 3 V and no greater than
20 V. The test current should be not less than 200mA.
Method 1 Method 2
Measurement at the
MCB DB with long
extended testing leads
14
4. Sequence of Test
15
4. Sequence of Test
0.25R1 = R2 - R3
where:
R1 = R of the phase, neutral and CPC measured in step 1
R2 = R of the phase, neutral and CPC measured in step 2
R3 = resistance of extension lead in step 3
16
4. Sequence of Test
(3) Insulation resistance
17
4. Sequence of Test
(3) Insulation resistance(cont.)
18
4. Sequence of Test
(3) Insulation resistance(cont.)
19
4. Sequence of Test
20
4. Sequence of Test
(3) Insulation resistance(cont.)
21
4. Sequence of Test
Insulation Resistance
Test
22
4. Sequence of Test
(3) Insulation resistance(cont.)
Log Sheet of Insulation test
23
4. Sequence of Test
(4) Polarity Test
24
4. Sequence of Test
(4) Polarity Test (cont.)
25
4. Sequence of Test
(5) Earth electrode resistance
Three electrodes
An a.c. at 50 Hz is passed
between T and T1.
Distance between T and T1
should not less than 20m
T2 is inserted half-way
between T and T1, and the
voltage drop between T and
T2, divided by current flowing
between T and T1 gives a
measured earth electrode
resistance of electrode T.
26
4. Sequence of Test
27
4. Sequence of Test
(6) Earth fault loop impedance
The earth fault loop impedance should be measured by a
phase-earth loop tester with a scale calibrated in ohms.
The measured value should not exceed the requirements of
Code 11
Test should be done under the condition that all relevant
earth connections are in place, and the bonding connection
to electricity supplier’s earthing facilities is disconnected.
28
4. Sequence of Test
(6) Earth fault loop impedance (cont.)
Measurement of Zs
29
4. Sequence of Test
(6) Earth fault loop impedance (cont.)
Measurement of Zs
Before the test begins, it is essential to establish,
by inspection, that the earthing conductor and all
relevant earth connections are in place, and that
the bonding connection to electricity supplier’s
earthing facilities is disconnected.
Measures should be taken, during the impedance
tests especially when the earth leakage protective
devices are effectively removed for the duration
of the tests, to ensure that the installation is not
being used other than by person(s) carrying out
the tests.
30
4. Sequence of Test
(6) Earth fault loop impedance (cont.)
Path for earth fault current
31
4. Sequence of Test
(6) Earth fault loop impedance (cont.)
32
4. Sequence of Test
(6) Earth fault loop impedance (cont.)
33
4. Sequence of Test
(6) Earth fault loop impedance (cont.)
Maximum Earth Loop Impedance – Fuse (5sec)
34
4. Sequence of Test
(6) Earth fault loop impedance (cont.)
Maximum Earth Loop Impedance – MCCB, RCD
35
4. Sequence of Test
(6) Earth fault loop impedance (cont.)
36
4. Sequence of Test
37
4. Sequence of Test
38
4. Sequence of Test
39