CompressiveStrength (ASTM-C39) Test Report

The document summarizes the results of compressive strength tests on concrete cylinder samples from a construction project. Three samples were tested at 10 and 14 days after casting to determine their compressive strength in accordance with ASTM C39 standards. At 10 days, the average compressive strength was 19.0 MPa (2760 psi). At 14 days, Sample 1 achieved a compressive strength of 20.0 MPa and failed via a combined shear and split fracture. The samples met or exceeded the intended design strength of 3500 psi.

Uploaded by

Nadira Pervin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views21 pages

CompressiveStrength (ASTM-C39) Test Report

The document summarizes the results of compressive strength tests on concrete cylinder samples from a construction project. Three samples were tested at 10 and 14 days after casting to determine their compressive strength in accordance with ASTM C39 standards. At 10 days, the average compressive strength was 19.0 MPa (2760 psi). At 14 days, Sample 1 achieved a compressive strength of 20.0 MPa and failed via a combined shear and split fracture. The samples met or exceeded the intended design strength of 3500 psi.

Uploaded by

Nadira Pervin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 21

CONCRETE LABORATORY

NSU Ref No : XXXX Date of Issue: XXXX

Sent By : Mr./Mrs. X

Ref. No. : XXXX Date of Receiving: XXXX

Project : XXXX

Sample : Cylinder [Mixing Proportion: X:X:X Aggregate Type: XXXX ]

Condition : Unsealed

Location : XXXX

Test : Compressive Strength [ASTM C39]

Date of Test : XXXX

TEST REPORT

Specimen
Date of casting Specimen Maximum Crushing Average Crushing Mode of
Sl No Designation/ Specimen Size Fracture Type
as per the letter Area Load Strength Strength Failure
Forg Mark

(sq.in) (lb) (psi)

1 8"X4" 12.57 0 XXXX psi *Combined Shear

2 ( 28 Days Test) 8"X4" 12.57 0 (XX Mpa) *Combined Split

3 8"X4" 12.57 0 (XXX kg/sq.cm) *Combined Shear & Split

Note: *Combined = Mortar and Aggregate failure

Test Supervised by: Countersigned by:

Assistant Professor Professor


Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes: Samples are supplied to us have been tested in our laboratory. NSU dose not have any responsibility as to the representative character
of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover/packet/container under signature of the
competent authority. In order to avoid fraudulent fabrication of test results, It is recommended that all test reports are collected by duly authorized person,
and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No : NSU/CEE/2016/11001 Date of Issue : June 23, 2016
Sent By : Engr. Debabrata Das, AGM (Construction), Date of Receiving : June 16, 2016
Jams Development Ltd.
Ref. No. : JAMSDL/BASUNDHARA R/A / 2016 / JUNE-16
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229

Test : Compressive Strength [ASTM C39] Mixing Proportion : Not mentioned

Sample : Concrete Cylinder Design Strength : 3500 psi


Condition : Sealed Cement Type : PCC

Location : Shore Pile (79 No.) Cement Brand : Holcim

Curing in days : 10 Days Aggregate Type : Shingles

Testing Date : June 23, 2016 Age in days : 14 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 P-79 (1) 7854.0 157.1 20.0 *Combined Split

2 9-Jun-16 P-79 (2) 8171.3 139.6 17.1 - - *Combined Shear

3 P-79 (3) 7854.0 185.8 23.7 *Combined Shear & Split

Note:
1. *Combined = Mortar and Aggregate failure

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Prof. Dr. Javed Bari, P.E.


Lab Officer Professor
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No : NSU/CEE/2016/11002 Date of Issue : June 27, 2016
Sent By : Engr. Debabrata Das, AGM (Construction), Date of Receiving : June 26, 2016
Jams Development Ltd.
Ref. No. : JAMSDL/BASUNDHARA R/A / 2016 / JUNE-26
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229

Test : Compressive Strength [ASTM C39] Mixing Proportion : Not mentioned

Sample : Concrete Cylinder Design Strength : 3500 psi

Condition : Sealed Cement Type : PCC


Location : Shore Pile (30 No.) Cement Brand : Akiz Cement

Curing in days : 07 Days Aggregate Type : Shingles

Testing Date : June 26, 2016 Age in days : 10 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 P-30 (1) 7854.0 147.3 18.8 *Combined Shear & Split

2 16-Jun-16 P-30 (2) 7854.0 151.1 19.2 19.0 2760 *Combined Split

3 P-30 (3) 8171.3 135.9 16.6 *Combined Shear & Split

Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-3 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Prof. Dr. Javed Bari, P.E.


Lab Officer Professor & Chair
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/2016/11003 Date of Issue : July 25, 2016
Sent By : Engr. Debabrata Das, AGM (Construction), Date of Receiving : July 25, 2016
Jams Development Ltd.
Ref. No. :
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229

Test : Compressive Strength [ASTM C39] Mixing Proportion : 1:1.5:3

Sample : Concrete Cylinder Design Strength : 3500 psi

Condition : Sealed Cement Type : PCC


Location : Pile (102 No.) Cement Brand : Cemex

Curing in days : 28 Days Aggregate Type : Shingles

Testing Date : July 25, 2016 Age in days : 30 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 SP-01 7854.0 178.9 22.8 *Combined Split

2 25-Jun-16 SP-02 7854.0 162.5 20.7 21.4 3110 *Combined Shear & Split

3 SP-03 8011.8 166.2 20.8 *Combined Split

Note:
1. *Combined = Mortar and Aggregate failure

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Prof. Dr. Javed Bari, P.E.


Lab Officer Professor & Chair
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/2016/11004 Date of Issue : August 04, 2016
Sent By : Engr. Debabrata Das, AGM (Construction), Date of Receiving : August 02, 2016
Jams Development Ltd.
Ref. No. :
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229

Test : Compressive Strength [ASTM C39] Mixing Proportion : 1:1.5:3

Sample : Concrete Cylinder Design Strength : 3500 psi

Condition : Sealed Cement Type : PCC


Location : Pile (112 No.) Cement Brand : Crown

Curing in days : 06 Days Aggregate Type : Shingles

Testing Date : August 03, 2016 Age in days : 08 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 SP-01 7854.0 159.8 20.4 *Combined Shear

2 26-Jul-16 SP-02 7854.0 160.7 20.5 20.5 2970 *Combined Shear

3 SP-03 8011.8 135.7 16.9 *Combined Shear

Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-3 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Prof. Dr. Javed Bari, P.E.


Lab Officer Professor & Chair
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2016/11005 Date of Issue : August 24, 2016
Sent By : Md.Nazrul Islam, Asst. Project Engineer, Date of Receiving : August 16, 2016
JCX Enterprise Ltd.
Ref. No. : JDL/JCX/CY-05
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229

Test : Compressive Strength [ASTM C39] Mixing Proportion : 1:1.5:3

Sample : Concrete Cylinder Design Strength : 3500 psi

Condition : Sealed Cement Type : PCC


Location : Pile (159 No.) Cement Brand : Crown

Curing in days : 06 Days Aggregate Type : Stone Chips

Testing Date : August 23, 2016 Age in days : 17 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 SP-01 7854.0 162.5 20.7 *Combined Split

2 6-Aug-16 SP-02 7854.0 183.9 23.4 23.4 3390 *Combined Shear & Split

3 SP-03 8171.3 191.4 23.4 *Combined Shear

Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-1 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Prof. Dr. Javed Bari, P.E.


Lab Officer Professor & Chair
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2017/11006 Date of Issue : January 25, 2017
Sent By : Asaduzzaman, Asst. Project Engineer, Date of Receiving : January 16, 2017
Jams Development Ltd.
Ref. No. :
Project : Dhaka Creed Blessed Hill,

Test : Compressive Strength [ASTM C39] Mixing Proportion : 1:2:4

Sample : Concrete Cylinder Design Strength : 2800 psi

Condition : Sealed Cement Type : PCC


Location : Ground Floor Casting Cement Brand : Shah (Special)

Curing in days : 24 Days Aggregate Type : Brick Chips

Testing Date : January 19, 2017 Age in days : 28 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 SP-01 7854.0 102.6 13.1 *Combined Shear & Split

2 22-Dec-16 SP-02 7854.0 113.9 14.5 13.8 2000 *Combined Split

3 SP-03 7697.7 87.5 11.4 *Combined Shear & Split

Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-3 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Fokruddin Ahmed


Lab Officer Lecturer
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2017/11007 Date of Issue : January 26, 2017
Sent By : Md.Nazrul Islam, Asst. Project Engineer, Date of Receiving : January 23, 2017
Jams Development Ltd.
Ref. No. : JDL/JCX/CY-001
Project : Jams Sufia

Test : Compressive Strength [ASTM C39] Mixing Proportion : 1:1.5:3

Sample : Concrete Cylinder Design Strength : 3000 psi

Condition : Sealed Cement Type : PCC


Location : Pile- 1/F-(1) Cement Brand : Crown

Curing in days : 06 Days Aggregate Type : Shingles

Testing Date : January 25, 2017 Age in days : 09 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 SP-01 7854.0 108.1 13.8 *Combined Shear

2 16-Jan-17 SP-02 7854.0 109.4 13.9 13.8 2010 *Combined Split

3 SP-03 7854.0 108.8 13.9 *Combined Split

Note:
1. *Combined = Mortar and Aggregate failure

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Fokruddin Ahmed


Lab Officer Lecturer
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2017/11008 Date of Issue : August 07, 2017
Sent By : Sk. Mostafiz Billah, Sr. Project Engineer, Date of Receiving : August 02, 2017
Jams Developer Ltd.
Ref. No. : Not mentioned
Project : JCX Business Tower

Test : Compressive Strength [ASTM C39] Mixing Proportion : 1:1.5:3

Sample : Concrete Cylinder Design Strength : 21 MPa

Condition : Sealed Cement Type : PCC


Location : Support Pile Cement Brand : Supercrete

Curing in days : 64 Days Aggregate Type : Shingeles

Testing Date : August 03, 2017 Age in days : 66 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 SP-01 7854.0 83.1 10.6 *Combined Shear & Split

2 29-May-17 SP-02 8011.8 95.1 11.9 11.4 1660 *Combined Split

3 SP-03 7854.0 86.4 11.0 *Combined Shear & Split

Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-1 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Dr. Mohammad Nazmul Islam,


Lab Officer Professor,
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2017/11009 Date of Issue : August 07, 2017
Sent By : Sk. Mostafiz Billah, Sr. Project Engineer, Date of Receiving : August 02, 2017
Jams Developer Ltd.
Ref. No. : Not mentioned
Project : JCX Business Tower

Test : Compressive Strength [ASTM C39] Mixing Proportion : Not mentioned

Sample : Concrete Cylinder Design Strength : 4000 psi

Condition : Sealed Cement Type : OPC


Location : Slab (1st Basement) 2nd part Cement Brand : Bashundhara

Curing in days : 11 Days Aggregate Type : Stone Chips

Testing Date : August 06, 2017 Age in days : 16 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 SP-01 7854.0 180.5 23.0 *Combined Shear & Split

2 21-Jul-17 SP-02 8011.8 173.2 21.6 22.3 3240 *Combined Shear & Split

3 SP-03 8011.8 220.8 27.6 *Combined Shear

Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-3 is higher then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Dr. Mohammad Nazmul Islam,


Lab Officer Professor,
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2018/11010 Date of Issue : October 23, 2018
Sent By : Abul Kalam Azad, Project Manager Date of Receiving : October 11, 2018
Harbour Developments and Constructions Ltd.
Ref. No. : Not mentioned
Project : NSU Extension level 11

Test : Compressive Strength [ASTM C39] Mixing Proportion : 1:1.5:3

Sample : Concrete Cube Design Strength : Not mentioned

Condition : Unsealed Cement Type : PCC


Location : Beam Cement Brand : Premier Cement

Curing in days : 09 Days Aggregate Type : Stone Chips

Testing Date : October 14, 2018 Age in days : 10 Days


TEST REPORT

Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark

(sq.mm) (kN) (MPa) (MPa) (psi)

1 SP-01 22952.0 632.9 27.6 *Combined Shear & Split

2 3-Oct-18 SP-02 23408.0 688.3 29.4 28.0 4060 *Combined Shear & Split

3 SP-03 23562.0 638.3 27.1 *Combined Shear & Split

Note:
1. *Combined = Mortar and Aggregate failure

Test Supervised by: Countersigned by:

Md. Saidur Rahman Chowdhury Prof. Dr. Javed Bari, P.E.


Lab Officer Professor
Dept. of Civil & Environmental Engineering Dept. of Civil & Environmental Engineering
NSU, Dhaka-1229, Bangladesh NSU, Dhaka-1229, Bangladesh

Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.