CompressiveStrength (ASTM-C39) Test Report
CompressiveStrength (ASTM-C39) Test Report
Sent By : Mr./Mrs. X
Project : XXXX
Condition : Unsealed
Location : XXXX
TEST REPORT
Specimen
Date of casting Specimen Maximum Crushing Average Crushing Mode of
Sl No Designation/ Specimen Size Fracture Type
as per the letter Area Load Strength Strength Failure
Forg Mark
Important Notes: Samples are supplied to us have been tested in our laboratory. NSU dose not have any responsibility as to the representative character
of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover/packet/container under signature of the
competent authority. In order to avoid fraudulent fabrication of test results, It is recommended that all test reports are collected by duly authorized person,
and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No : NSU/CEE/2016/11001 Date of Issue : June 23, 2016
Sent By : Engr. Debabrata Das, AGM (Construction), Date of Receiving : June 16, 2016
Jams Development Ltd.
Ref. No. : JAMSDL/BASUNDHARA R/A / 2016 / JUNE-16
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
Note:
1. *Combined = Mortar and Aggregate failure
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No : NSU/CEE/2016/11002 Date of Issue : June 27, 2016
Sent By : Engr. Debabrata Das, AGM (Construction), Date of Receiving : June 26, 2016
Jams Development Ltd.
Ref. No. : JAMSDL/BASUNDHARA R/A / 2016 / JUNE-26
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
2 16-Jun-16 P-30 (2) 7854.0 151.1 19.2 19.0 2760 *Combined Split
Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-3 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/2016/11003 Date of Issue : July 25, 2016
Sent By : Engr. Debabrata Das, AGM (Construction), Date of Receiving : July 25, 2016
Jams Development Ltd.
Ref. No. :
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
2 25-Jun-16 SP-02 7854.0 162.5 20.7 21.4 3110 *Combined Shear & Split
Note:
1. *Combined = Mortar and Aggregate failure
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/2016/11004 Date of Issue : August 04, 2016
Sent By : Engr. Debabrata Das, AGM (Construction), Date of Receiving : August 02, 2016
Jams Development Ltd.
Ref. No. :
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-3 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2016/11005 Date of Issue : August 24, 2016
Sent By : Md.Nazrul Islam, Asst. Project Engineer, Date of Receiving : August 16, 2016
JCX Enterprise Ltd.
Ref. No. : JDL/JCX/CY-05
Project : JCX Business Tower,
Plot# 1136/A, Block# I, Basundhara R/A, Dhaka-1229
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
2 6-Aug-16 SP-02 7854.0 183.9 23.4 23.4 3390 *Combined Shear & Split
Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-1 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2017/11006 Date of Issue : January 25, 2017
Sent By : Asaduzzaman, Asst. Project Engineer, Date of Receiving : January 16, 2017
Jams Development Ltd.
Ref. No. :
Project : Dhaka Creed Blessed Hill,
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-3 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2017/11007 Date of Issue : January 26, 2017
Sent By : Md.Nazrul Islam, Asst. Project Engineer, Date of Receiving : January 23, 2017
Jams Development Ltd.
Ref. No. : JDL/JCX/CY-001
Project : Jams Sufia
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
Note:
1. *Combined = Mortar and Aggregate failure
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2017/11008 Date of Issue : August 07, 2017
Sent By : Sk. Mostafiz Billah, Sr. Project Engineer, Date of Receiving : August 02, 2017
Jams Developer Ltd.
Ref. No. : Not mentioned
Project : JCX Business Tower
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-1 is lower then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2017/11009 Date of Issue : August 07, 2017
Sent By : Sk. Mostafiz Billah, Sr. Project Engineer, Date of Receiving : August 02, 2017
Jams Developer Ltd.
Ref. No. : Not mentioned
Project : JCX Business Tower
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
2 21-Jul-17 SP-02 8011.8 173.2 21.6 22.3 3240 *Combined Shear & Split
Note:
1. *Combined = Mortar and Aggregate failure
2. Strength of specimen-3 is higher then the permissible value, according to ASTM C39, compare to the average of the batch,
and thus, excluded from the average calculation.
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.
CONCRETE LABORATORY
NSU Ref No. : NSU/CEE/C39/2018/11010 Date of Issue : October 23, 2018
Sent By : Abul Kalam Azad, Project Manager Date of Receiving : October 11, 2018
Harbour Developments and Constructions Ltd.
Ref. No. : Not mentioned
Project : NSU Extension level 11
Date of Specimen
Sl Specimen Maximum Crushing Average Crushing Mode of
casting as Designation/ Fracture Type
No. Area Load Strength Strength Failure
per the letter Forg Mark
2 3-Oct-18 SP-02 23408.0 688.3 29.4 28.0 4060 *Combined Shear & Split
Note:
1. *Combined = Mortar and Aggregate failure
Important Notes:Samples are supplied to us have been tested in our laboratory.NSU does not have any responsibility as to the representative
character of the samples required to be tested. It is recommended that samples are sent in a secure and sealed cover / packet / container under
signature of the competent authority.In order to avoid fraudulent fabrication of test results, it is recommended that all test reports are collected
by duly authorized person, and not by the contractor/ supplier.