Loop Check and Valve

This document is a loop check sheet used to verify the correct functioning of instrumentation loops. It includes checks of tag names, descriptions, units and ranges in the DCS. Alarm and trip setpoints are verified. The analog loop is tested by changing the input and verifying the local and DCS indicators respond properly. Control valve function is checked by changing the DCS output and observing valve position. Digital inputs and outputs are also verified to change states correctly locally and in the DCS. Remarks note any issues and sign off confirms the loop check is completed and verified.

Uploaded by

Mohd A Ishak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
564 views1 page

Loop Check and Valve

This document is a loop check sheet used to verify the correct functioning of instrumentation loops. It includes checks of tag names, descriptions, units and ranges in the DCS. Alarm and trip setpoints are verified. The analog loop is tested by changing the input and verifying the local and DCS indicators respond properly. Control valve function is checked by changing the DCS output and observing valve position. Digital inputs and outputs are also verified to change states correctly locally and in the DCS. Remarks note any issues and sign off confirms the loop check is completed and verified.

Uploaded by

Mohd A Ishak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

Instrument Loop Check Sheet

Job No: Loop Drawing No:


Area: P&ID No:
Loop No:
Inst. Tag No:

DCS/Local Indicator & Visual Check

Correct Tag in DCS ( Yes/No) Electrical Supply Check ( Yes/No)


Correct Description in DCS ( Yes/No) Instrument Air Supply Check ( Yes/No)
Correct Engineering Unit in DCS ( Yes/No)
Corrent Range ( Yes/No)

Alarm/Trip Function Check


Alarm Type Tag Setpoint Result
High High
High
Low
Low Low

Indicating Loop Test Control Control Valve Function Check


Analog Input Rising ( ) Falling ( ) DCS Manual Output Valve Position (%)
Amp Local DCS Local DCS % ( ) Rising ( ) Falling ( )
Measurement

Measurement

0
25
50
75
100

Ambient Temperature: Spring action at AIR failure :


Stroke time:

Digital Input/Output Test SDV/XV/On-Off Valve Function Check


Field Ints. PLC DCS Result Valve Action DCS/PLC
Digital Input Open/Close Alarm/Normal Alarm/Normal (FC/FO) Output Valve Position Result

Field Ints. PLC DCS Result


Digital Input De / Energise On/Off On/Off
Close/Open Position Remote
Positioner indicator Local Correct
Remark:

Done by:
Date:

Checked by:
Date: