User Manual: Modbus Slave / M-Bus Master - Converter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

User Manual Modbus Slave / M-Bus Master

Document code: MN67055_ENG Revision 1.011 Pagina 1 di 30


Industrial Electronic Devices

User Manual
Revision 1.011
English

Modbus Slave / M-Bus Master – Converter


( M-Bus Master port: RS232 or RS485,
Modbus Slave port: RS232 or RS485 )
(Order Code: HD67055)
HD67055
for Website information:
www.adfweb.com?Product=HD67055
For others M-Bus products:
for Price information: See also the following link:
www.adfweb.com?Price=HD67055 Adapter M-Bus to
www.adfweb.com?Product=HD67020 (RS232)
www.adfweb.com?Product=HD67021 (RS232)
www.adfweb.com?Product=HD67022 (RS485)
www.adfweb.com?Product=HD67024 (USB)
Similiar
www.adfweb.com?Product=HD67030 (Ethernet)
Benefits and Main Features: Products
M-Bus from/to Modbus RTU on RS232/RS485
See also the following link:
Very easy to configure www.adfweb.com?Product=HD67029M-232
www.adfweb.com?Product=HD67029M-485
Electrical isolation
M-Bus repeater
Industrial temperature range: www.adfweb.com?Product=HD67032M

-40°C / 85°C (-40°F / 185°F) Do you have an your customer protocol?


See the following link:
www.adfweb.com?Product=HD67003

Do you need to choose a device? do you want help?


Ask it to the following link:
www.adfweb.com?Cmd=helpme

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 2 di 30
Industrial Electronic Devices

INDEX: UPDATED DOCUMENTATION:

Dear customer, we thank you for your attention and we remind you that you
need to check that the following document is:
Page
Updated
INDEX 2 Related to the product you own
UPDATED DOCUMENTATION 2
REVISION LIST 2 To obtain the most recently updated document, note the “document code” that
WARNING 2 appears at the top right-hand corner of each page of this document.
TRADEMARKS 2
SECURITY ALERT 3 With this “Document Code” go to web page www.adfweb.com/download/ and
EXAMPLE OF CONNECTION 4 search for the corresponding code on the page. Click on the proper “Document
CONNECTION SCHEME 5 Code” and download the updates.
CHARACTERISTICS 6
CONFIGURATION 6 To obtain the updated documentation for the product that you own, note the
POWER SUPPLY 7 “Document Code” (Abbreviated written "Doc. Code" on the label on the product)
FUNCTION MODES 8 and download the updated from our web site www.adfweb.com/download/
LEDS 9
RS485 PORT (MODBUS) 10
RS485 PORT (M-BUS) 10 REVISION LIST:
RS232 PORT 11
USE OF COMPOSITOR SW67055 12 Revision Date Author Chapter Description
NEW PROJECT / OPEN PROJECT 12 1.000 30/10/2009 Fl All First release version
SET COMMUNICATION 13 1.001 06/07/2010 Ft All Revision
M-BUS 14 1.010 19/06/2012 Fl All Software changed (v1.100)
UPDATE DEVICE 26 1.011 18/02/2013 Nt All Added new chapters
MECHANICAL DIMENSIONS 28
ORDER CODES 28
ACCESSORIES 28 WARNING:
DISCLAIMER 29
OTHER REGULATIONS AND STANDARDS 29 ADFweb.com reserves the right to change information in this manual about our
WARRANTIES AND TECHNICAL SUPPORT 30 product without warning.
ADFweb.com is not responsible for any error this manual may contain.
RETURN POLICY 30
230
PRODUCTS AND RELATED DOCUMENTS 30
TRADEMARKS:

All trademarks mentioned in this document belong to their respective owners.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 3 di 30
Industrial Electronic Devices

SECURITY ALERT:

GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device are required for
each individual application, legal and safety regulation. The same applies also when using accessories.

INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e. independent limit
switches, mechanical interlocks, etc.).

QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and who
have appropriate qualifications for their job.

RESIDUAL RISKS
The device is state of the art and is safe. The instrument can represent a potential hazard if they are inappropriately installed and operated
by personnel untrained. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is danger for people to serious injury or death and / or the
possibility of damage.

CE CONFORMITY
The declaration is made by us. You can send an email to [email protected] or give us a call if you need it.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 4 di 30
Industrial Electronic Devices

EXAMPLE OF CONNECTION:

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 5 di 30
Industrial Electronic Devices

CONNECTION SCHEME:

Figure 1: Connection scheme for HD67055


ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 6 di 30
Industrial Electronic Devices

CHARACTERISTICS:

The HD67055 is Gateway that use M-Bus protocol over RS232/RS485 and Modbus RTU/ASCII ever RS232/RS485.
It allows the following characteristics:
Electrical isolation between RS232/RS485 and M-Bus on RS485;
Mountable on Rail DIN;
Temperature range -40°C to 85°C.

CONFIGURATION:

You need Compositor SW67055 software on your PC in order to perform the following:
Define the parameter of Modbus line;
Define the parameter of M-Bus line;
Define which Modbus register contain the M-Bus information;
Update the device.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 7 di 30
Industrial Electronic Devices

POWER SUPPLY:

The device can be powered between a wide range of tensions. For more details see the two tables below.

VAC VDC
Vmin Vmax Vmin Vmax
8V 19V 8V 35V

Consumption at 24V DC:

Device W/VA
HD67055 4

Caution: Not reverse the polarity power

HD67055

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 8 di 30
Industrial Electronic Devices

FUNCTION MODES:

The device has got two functions mode depending of the position of ‘Jumper3’:
The first, with ‘Jumper3’ not inserted (factory setting), is used for the normal working of the device.
The second, with ‘Jumper3’ inserted, is used for upload the Project/Firmware.

For the operations to follow for the updating (see ‘UPDATE DEVICE’ section).

According to the functioning mode, the LEDs will have specifics functions (see ‘LEDS’ section).

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 9 di 30
Industrial Electronic Devices

LEDS:

The device has got three LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.

LED Normal Mode Boot Mode

1: Device State (green) Blinks slowly (∼1Hz) Blinks quickly

2: M-Bus comm (green) Blinks quickly when receive a M-Bus response Off

3: Modbus comm (green) Change state when receive a correct Modbus request Off

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 10 di 30
Industrial Electronic Devices

RS485 PORT (MODBUS):

For terminate the RS485 line with a 220Ω resistor it is necessary that the
‘Jumper1’ is like the label over the device.

The maximum length of the cable should be 1200m (4000 feet).

Here some codes of cables:


Belden: p/n 8132 - 2x 28AWG stranded twisted pairs conductor +
foil shield + braid shield;
Belden p/n 82842 - 2x 24AWG stranded twisted pairs conductor +
foil shield + braid shield;
Tasker: p/n C521 - 1x 24AWG twisted pair conductor + foil shield + braid shield;
Tasker: p/n C522 - 2x 24AWG twisted pairs conductor + foil shield + braid shield.

RS485 PORT (M-BUS):

For terminate the RS485 line with a 220Ω resistor it is necessary that the
‘Jumper2’ is like the label over the device.

The maximum length of the cable should be 1200m (4000 feet).

Here some codes of cables:


Belden: p/n 8132 - 2x 28AWG stranded twisted pairs conductor + foil
shield + braid shield;
Belden p/n 82842 - 2x 24AWG stranded twisted pairs conductor + foil
shield + braid shield;
Tasker: p/n C521 - 1x 24AWG twisted pair conductor + foil shield +
braid shield;
Tasker: p/n C522 - 2x 24AWG twisted pairs conductor + foil shield + braid shield.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 11 di 30
Industrial Electronic Devices

RS232 PORT:

The connection from RS232 socket to a serial port (example one from a personal computer),
must be made with a Null Modem cable (a serial cable where the pins 2 and 3 are crossed).
It is recommended that the RS232C Cable not exceed 15 meters.

The serial port is used for programming the device or for Modbus communication.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 12 di 30
Industrial Electronic Devices

USE OF COMPOSITOR SW67055:

To configure the Gateway, use the available software that runs with
Windows, called SW67055. It is downloadable on the site
www.adfweb.com and its operation is described in this document.

When launching the SW67055 the right window appears (Fig. 2).

Figure 2: Main window for SW67055

NEW PROJECT / OPEN PROJECT:

The “New Project” button creates the folder which contains the entire device configuration.

A device configuration can also be imported or exported:


To clone the configurations of a Programmable M-Bus to Modbus Gateway in order to
configure another device in the same manner, it is necessary to maintain the folder and all
its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to
duplicate the project folder with another name and open the new folder with the button
“Open Project”.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 13 di 30
Industrial Electronic Devices

SET COMMUNICATION:

This section define the fundamental communication parameters of two Buses, Modbus and M-Bus.

By Pressing the “Set Communication” button from the main window for SW67055 (Fig. 2) the window
“Set Communication” appears (Fig. 3).
The window is divided in two sections, one for the Modbus RTU line (Serial) and the other for the M-Bus.

It is possible to configure the serials port between these options:


Modbus RTU (Serial) on RS232 & M-Bus on RS485;
Modbus RTU (Serial) on RS485 & M-Bus on RS485;
Modbus RTU (Serial) on RS485 & M-Bus on RS232.

The means of the fields for Serial are:


In the field “Baudrate” the baudrate of the serial line in use is defined;
In the field “Parity” the parity of the serial line is defined;
In the field “ID Dev.” the ID assigned to the Gateway, for the Modbus side, is defined.
In the subsection “Protocol” it is possible to select the protocol to use in Modbus line from the
following:
• Modbus RTU;
• Modbus ASCII;
• JBUS;
• Binary: simple protocol defined by Us, whose functions are described in the document “Simple
Protocol” downloadable at www.adfweb.com/download/filefold/Simple_Protocol_ENG.pdf ;
• ASCII: simple protocol defined by Us, whose functions are described in the document “Simple
Protocol” downloadable at www.adfweb.com/download/filefold/Simple_Protocol_ENG.pdf .

The means of the fields for M-Bus are:


In the field “Baudrate” the baudrate of the M-Bus line in use is defined;
In the field “Parity” the parity of the M-Bus line is defined;
If the field “M-Bus Poll on request” is checked, the Gateway makes the request only if a Modbus
register is requested; otherwise if “Cyclic request” is checked, the Gateway makes the request in
M-bus network each time the time defined under passes;
Figure 3: “Set Communication” window
In the field “Delay” insert a time expressed in seconds. This time is used for the “Cyclic
request”.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 14 di 30
Industrial Electronic Devices

M-BUS

By Pressing the “M-Bus” button from the main window for SW67029 (Fig. 2) the window “M-Bus Network” appears (Fig. 4).

SECTION NODES:
In the section “Nodes” it is possible to create the nodes of M-Bus
line. In order to create a new node it is necessary to select which
address use, selecting “Primary ID” or “Secondary ID”, to makes
the requests and then insert the “Primary Address” (from 1 to 250)
or the Secondary Address” (from 0 to 99999999) of M-Bus device in
the field “ID Node M-Bus”. In the field “Description” it is possible
to write a short description of the node.
In the field “Node State” it is possible to insert an address Modbus
that contain the Status of the M-Bus device. If you don’t need to
know this, put this register at 0.
In the field “Identification Number” it is possible to insert an
address Modbus that contain the Identification Number of the M-Bus
device. You have to read two consecutive registers for knowing the
value. If you don’t need to know this, put this register at 0.
If the field “Convert BCD in Integer Identification Num.” is
checked the gateway converts the Identification Number that is
normally expressed in BCD in a Integer.
In the field “Swap Identification Num.” it is possible to select the
swap mode of the Identification Number. If swap isn’t necessary you
have to select “None”; otherwise see the section “Swap
Identification” (page 21) of this document for select the swap mode.
If the field “Send SND_NKE” is checked, the Gateway send the
“SND_NKE” frame to start the communication.
In the field “Send Reset App.” Is checked the gateway send the
“Application Reset” command to the slave. In the field “Variables
List” it is possible to select which type of variables definition to use.
Figure 4: “M-Bus Network” window
If is selected “By Type” it is necessary to fill all fields, in the section
Variables, with the correct values; otherwise if “By Position” is selected you can insert the progressive number of the variable that you need
(page 15-16 for more information).
After that, pressing the “ADD NODE” button, a new node appears in the left side of the window. In order to modify a created node it is
necessary to select the desired node, change the wrong items and then press the “MODIFY NODE” button.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 15 di 30
Industrial Electronic Devices

SECTION VARIABLES (BY TYPE):

Selecting the desired node it is possible to add a variable. In order


to create a new variable it is necessary to fill these items:

To use the created variable the field “Enable Variable”


must be checked. If you have created a variable but for the
moment it is unused it is possible to uncheck the field
“Enable Variable” without delete it;
In the field “Description” it is possible to write a
description of the variable (it isn’t a necessary information,
it helps the readability of the tree of network);
The field “Type of Data” is used to select the unit of
measure;
In the field “VIF ASCII String” insert the string of VIF. It
is possible to use this field only if the “Type of Data” is “VIF
is in ASCII”;
In the field “Function Field” it is necessary to select the
type of data;
The field “Dimension” is used to select the dimension of
the variable (8, 16, 24, 32, 32 real, 48, 64 bit, Variable
Length);
In the field “Length(Variable Len)” insert the length of
the data in the case of the dimension is “Variable Length”;
In the field “Unit” if it is necessary it is possible to select
the unit of that variable. The Unit is used for indicates from
which device the data come;
In the field “Modbus Register” it is necessary to insert the
value of Modbus Register that contains the data of the M-Bus device. It is possible to insert from Modbus Register “1” to “60000”;
In the field “Modbus Re Scale” it is necessary to insert the value of Modbus Register that contains the value of measure scale. If the
scale is not necessary, you have to insert the number “0” in this field. It is possible to insert from Modbus Register “1” to “60000”;
In the field “Storage Number” if it is necessary it is possible to insert the value of storage counter of that variable. With this field
the slave can indicate and transmit various stored counter states or historical values, in the order in which they occur;
In the field “Tariff” if it is necessary it is possible to insert the value of the tariff of that variable. The Tariff is used for indicates from
which device the data come;
In the field “VIFE” it is possible to select a sub-type of “Type of Data”;

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 16 di 30
Industrial Electronic Devices

If the field “Use Five Modbus Register” and the “Type of Data” is “Time Point” it is possible to read the information of Year, Month,
Day, Hour, Minutes on five consecutive Modbus registers without decoding the data (if not selected the values are the same of the
reply of the slave device, so coded with a determinate structure). You have to insert the first Modbus Register.
If the field “From BCD to Integer” is checked the Gateway converts the BCD value of variable in Integer format. This happens only
if the variable is in BCD format; if it isn’t nothing changes.
If the field “Convert in Float” is checked the Gateway converts the data into Float type. Every variable occupies two consecutive
Modbus Registers and the first one is the one defined in “Modbus Register”. In this case the float value is multiplied by the “Modbus
Re Scale” automatically.

Having completed this fields, to add the variable the button “ADD VARIABLE” must be pressed.

In order to modify a created variable it is necessary to select the desired variable, change the wrong items and then press the “MODIFY
VARIABLE” button.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 17 di 30
Industrial Electronic Devices

SECTION VARIABLES (BY POSITION):

Selecting the desired node it is possible to add a variable. In order


to create a new variable it is necessary to fill these items:
To use the created variable the field “Enable Variable”
must be checked. If you have created a variable but for the
moment it is unused it is possible to uncheck the field
“Enable Variable” without delete it;
In the field “Description” it is possible to write a
description of the variable (it isn’t a necessary information,
it helps the readability of the tree of network);
The field “Dimension” is used to select the dimension of
the variable (8, 16, 24, 32, 32 real, 48, 64 bit, Variable
Length);
In the field “Length(Variable Len)” insert the length of
the data in the case of the dimension is “Variable Length”;
In the field “Modbus Register” it is necessary to insert the
value of Modbus Register that contains the data of the M-
Bus device. It is possible to insert from Modbus Register
“1” to “60000”;
In the field “Modbus Re Scale” it is necessary to insert the
value of Modbus Register that contains the value of
measure scale. If the scale is not necessary, you have to
insert the number “0” in this field. It is possible to insert
from Modbus Register “1” to “60000”;
If the field “Use Five Modbus Register” and the “Type of Data” is “Time Point” it is possible to read the information of Year, Month,
Day, Hour, Minutes on five consecutive Modbus registers without decoding the data (if not selected the values are the same of the
reply of the slave device, so coded with a determinate structure (page 22 for more information)). You have to insert the first Modbus
Register.
If the field “From BCD to Integer” is checked the Gateway converts the BCD value of variable in Integer format. This happens only
if the variable is in BCD format; if it isn’t nothing changes;
If the field “SWAP” is checked the byte of data of that variable are swapped. Example: from 0x01020304 to 0x04030201;
In the field “Position” insert the number of the variable that you want on Modbus.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 18 di 30
Industrial Electronic Devices

Example:

0x68 - Start Byte


0xBD - L Fied
0xBD - L Field
0x68 - Start Byte
0x08 - C Field
0x02 - A Field
0x72 - CI Field
Identification Number (or Secondary Address) putted in
0x71 - Identification Number (Byte 4of4)
0x65 - Identification Number (Byte 3of4) the selected register if “Identification Number” is
0x45 - Identification Number (Byte 2of4) checked
0x28 - Identification Number (Byte 1of4)
0x4D - Manufacturer (Byte 2of2)
0x6A - Manufacturer (Byte 1of2)
0x81 - Version
Fixed Data Header
0x04 - Medium
0x3E - Access Number
0x27 - Status
0x00 - Signature (Byte 2of2) Status of the meter putted in the selected register if
0x00 - Signature (Byte 1of2) “Node State” is checked
0x04 - DIF
0x79 - VIF Identification
0x00 - Data (Byte 4of4)
0x00 - Data (Byte 3of4)
First Variable ( 1 )
0x00 - Data (Byte 2of4)
0x00 - Data (Byte 1of4)

0x04 - DIF
0x06 - VIF Energy
0x00 - Data (Byte 4of4)
0x00 - Data (Byte 3of4)
Second Variable ( 2 ) To be use in the “Position” field
0x00 - Data (Byte 2of4)
0x00 - Data (Byte 1of4)

0x44 - DIF
0x06 - VIF Energy
0x00 - Data (Byte 4Of4)
0x00 - Data (Byte 3Of4)
Third Variable ( 3 )
0x00 - Data (Byte 2Of4)
0x00 - Data (Byte 1Of4)

… Other Variables

0x55 - Check Sum
0x16 - Stop Byte

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 19 di 30
Industrial Electronic Devices

SECTION DELETE ITEMS:

If it is necessary to delete a node or a variable, you have to select


the node or the variable and then press the “DELETE ITEM”
button.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 20 di 30
Industrial Electronic Devices

Possible choices for the fields used to create a variable:

Type of Data: Function Field:


|_Energy (Wh) |_Instantaneous Value
|_Energy (J) |_Minimum Value
|_Volume (m3) |_Maximum Value
|_Mass (Kg) |_Value During Error State
|_On Time
|_Operating Time
|_Power (W) Dimension (bit):
|_Power (J/h) |_8
|_Volume Flow (m3/h) |_16
|_Volume Flow Ext. (m3/min) |_24
|_Volume Flow Ext. (m3/s) |_32
|_Mass Flow (Kg/h) |_32 real
|_Flow Temperature (°C) |_48
|_Return Temperature (°C) |_64
|_Temperature Difference (K) |_Variable Length
|_External Temperature (°C)
|_Pressure (bar)
|_Averaging Duration
|_Actuality Duration
|_Type of data in VIFE
|_Time Point
|_VIF is in ASCII
|_Unit for H.C.A.
|_Fabrication No
|_(Enhaced) Identification
|_Bus Address

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 21 di 30
Industrial Electronic Devices

VIFE:
|_ Not Selected |_ Period of tariff months(s)
|_ Credit of the nominal local legal currency units |_ Period of tariff year(s)
|_ Debit of the nominal local legal currency units |_ dimensionless/ no VIF
|_ Access Number (transmission count) |_ Volts
|_ Medium (as in fixed header) |_ Ampere
|_ Manufacturer (as in fixed header) |_ Reset counter
|_ Parameter set identification |_ Comulation counter
|_ Model/Version |_ Control signal
|_ Hardware Version # |_ Day of week
|_ Firmware Version # |_ Week number
|_ Software Version # |_ Time point of day change
|_ Customer Location |_ State of parameter activation
|_ Customer |_ Special supplier information
|_ Access Code User |_ Duration since last comulation [hour(s)..year(s)]
|_ Access Code Operator |_ Operation time battery [hour(s)..year(s)]
|_ Access Code System Operator |_ Date and time of battery change
|_ Access Code Developer |_ Energy MWh
|_ Password |_ Energy GJ
|_ Error flags (binary) |_ Volume
|_ Error mask |_ Mass
|_ Digital Output (binary) |_ Volume 0,1 feet^3
|_ Digital Input (binary) |_ Volume 0,1 american gallon
|_ Baudrate [Baud] |_ Volume 1 american gallon
|_ response delay time [bittimes] |_ Volume flow 0,001 american gallon/min
|_ Retry |_ Volume flow 1 american gallon/min
|_ First storage # for cyclic storage |_ Volume flow 1 american gallon/h
|_ Last storage # for cyclic storage |_ Power MW
|_ Size of storage block |_ Power GJ/h
|_ Storage interval [sec(s)..day(s)] |_ Flow Temperature
|_ Storage interval month(s) |_ Return Temperature
|_ Storage interval year(s) |_ Temperature Difference
|_ Duration since last readout[sec(s)..day(s)] |_ External Temperature
|_ Start (date/time) of tariff |_ Cold/Warm Temperature Limit °F
|_ Duration of tariff (nn=01..11:min to day) |_ Cold/Worm Temperature Limit °C
|_ Period of tariff [sec(s) to day(s)] |_ Cumul. count max power

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 22 di 30
Industrial Electronic Devices

|_ per second |_ Duration of limit exceed


|_ per minute |_ Duration of first/last
|_ per hour |_ Date(/time) of first/last begin/end
|_ per day |_ Multiplicative currection factor
|_ per week |_ Additive correction constant * unit of VIF (offset)
|_ per month |_ Moltiplicative correction factor: 10^3
|_ per year |_ future value
|_ per revolution/measurement |_ next VIFE's and data of this block are manufacturer specific
|_ increment per input pulse on input channel |_ None
|_ increment per output pulse on output channel |_ Too many DIFE's
|_ per liter |_ Storage number not implemented
|_ per m^3 |_ Unit number not implemented
|_ per kg |_ Tariff number not implemented
|_ per K (Kelvin) |_ Function not implemented
|_ per kWh |_ Data class not implemented
|_ per GJ |_ Data size not implemented
|_ per kW |_ Too many VIFE's
|_ per (K*l)(Kelvin*liter) |_ Illegal VIF-Group
|_ per V (Volt) |_ Illegal VIF-Exponent
|_ per A (Ampere) |_ VIF/DIF mismatch
|_ multiplied by sek |_ Unimplemented action
|_ multiplied by sek/V |_ No data available (undefined value)
|_ multiplied by sek/A |_ Data overflow
|_ start date(/time) of |_ Data underflow
|_ VIF contains uncorrected unit instead of corrected unit |_ Data error
|_ Accumulation only if positive contributions |_ Premature end of record
|_ Accumulation of abs value only if negative contributions
|_ upper/lower limit value
|_ # of exceeds of lower/upper limit
|_ Date(/time) of begin/end of first/last lower/upper limit exceed

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 23 di 30
Industrial Electronic Devices

Swap Identification:

This field is used for select the Swap mode of Identification Number.

At the moment there are these possibilities:


None;
Type 1.

Examples:

- Identification Number (Secondary Address): 12345678; Address Register 1000; Convert BCD in Integer Identification Num. not checked.

None Type 1
1000: 0x1234 1000: 0x5678
1001: 0x5678 1001: 0x1234

- Identification Number (Secondary Address): 12345678; Address Register 1000; Convert BCD in Integer Identification Num. checked.

None Type 1
1000: 0x00BC 1000: 0x614E
1001: 0x614E 1001: 0x00BC

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 24 di 30
Industrial Electronic Devices

To know the meaning of value read in the “Modbus Re Scale” field, you must follow this table (x = Value read in Modbus Re Scale):

Description Range Coding Range


Energy 10 (x – 3) Wh 0.001 Wh to 10000 Wh
Energy 10 (x) J 0.001 kJ to 10000 kJ
(x – 6)
Volume 10 m3 0.001 l to 10000 l
(x – 3)
Mass 10 kg 0.001 kg to 10000 kg
x=0 Seconds
x=1 Minutes
On Time
x=2 Hours
x=3 Days
Operating Time coded like On Time
Power 10 (x – 3) W 0.001 W to 10000 W
Power 10 (x) J/h 0.001 kJ/h to 10000 kJ/h
Volume Flow 10 (x – 6) m3/h 0.001 l/h to 10000 l/h
(x – 7) 3
Volume Flow Ext. 10 m /min 0.0001 l/min to 1000 l/min
(x – 9)
Volume Flow Ext. 10 m3/s 0.001 ml/s to 10000 ml/s
(x – 3)
Mass Flow 10 kg/h 0.001 kg/h to 10000 kg/h
Flow Temperature 10 (x – 3) °C 0.001 °C to 1 °C
(x – 3)
Return Temperature 10 °C 0.001 °C to 1 °C
Temperature Difference 10 (x – 3) K 1 mK to 1000 mK
(x – 3)
External Temperature 10 °C 0.001 °C to 1 °C
Pressure 10 (x – 3) bar 1 mbar to 1000 mbar
Averaging Duration coded like On Time
Actuality Duration coded like On Time
x=0 Date Data type G
Time Point
x=1 Time&Date Data type F
Unit for H.C.A. dimensionless

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 25 di 30
Industrial Electronic Devices

Data type F:
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
15 14 13 12 11 0 9 8
2 2 2 2 2 21 2 2
23 22 21 0 19 18 17 16
2 2 2 22 2 2 2 2
31 30 29 28 27 26 25 24
2 2 2 2 2 2 2 2

Min (0 … 59);
Hour (0 … 23);
Day (1 … 31);
Month (1 … 12);
Year (0 … 99);
Time Invalid (0=Valid, 1=Invalid);
Summer Time (0=Standard Time, 1=Summer Time);
Reserved (0).

Data type G:
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
15 14 13 12 11 0 9 8
2 2 2 2 2 21 2 2

Day (1 … 31);
Month (1 … 12);
Year (0 … 99).

For example, if you have defined:


Type of Data= Energy (J);
Function Field=Instantaneous Value;
Dimension= 32 bit;
Modbus Register=150 (Register 151 declared implicitly because the dimension is 32 bit);
Modbus Re Scale=152.
After the request, in Modbus register 150 you read 0x0004, in 151 you read 0x5678 and in register 152 is write 0x0006. The value obtained
is: 284280 x10(6) J.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 26 di 30
Industrial Electronic Devices

UPDATE DEVICE:

By pressing the “Update Device” button it is possible to load the created Configuration into the device; and also the Firmware, if is
necessary.

In order to load the parameters or update the firmware in the device, follow these instructions:
Turn off the Device;
Connect the RS232 Null Modem Cable from your PC to the Gateway;
Insert the Boot Jumper (see “FUNCTION MODES” section);
Select the “COM port” and press the “Connect” button;
Turn on the device;
Check the BOOT Led. It must blink quickly (see “LEDS” section);
Press the “Next” button;
Select which operations you want to do.
Press the “Execute update firmware” button to start the upload;
When all the operations are “OK” turn off the device;
Disconnect the Boot jumper;
Disconnect the RS232 Cable;
Turn on the device.

At this point the configuration/firmware on the device is correctly update.

Figure 5: “Update Device” windows

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 27 di 30
Industrial Electronic Devices

Note:
When you install a new version of the software it is better if the first time you do the update of the Firmware in the HD67055 device.

Warning:
If the Fig. 6 appears when you try to do the Update before require assistance try
these points:
Check if the serial COM port selected is the correct one;
Check if the serial cable is connected between the PC and the device;
Try to repeat the operations for the updating;
If you are using a USBRS232 converter try with a native COM port or change the
converter;
Try with another PC;
Try to restart the PC;
Figure 6: “Protection” window
If you are using the program inside a Virtual Machine, try to use in the main
Operating System;
If you are using Windows Seven or Vista, make sure that you have the administrator privileges.

In the case of HD67055 you have to use the software “SW67055”: www.adfweb.com\download\filefold\SW67055.zip.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 28 di 30
Industrial Electronic Devices

MECHANICAL DIMENSIONS:

Figure 7: Mechanical dimensions scheme for HD67055


ORDER CODES:

Order Code: HD67055 - Modbus Slave / M-Bus Master - Converter

ACCESSORIES:

Order Code: AC34107 - Null Modem Cable Fem/Fem DSub 9 Pin 1,5 m

Order Code: AC34114 - Null Modem Cable Fem/Fem DSub 9 Pin 5 m

Order Code: AC34001 - Rail DIN - Power Supply 220/240V AC 50/60Hz – 12 V AC

Order Code: AC34002 - Rail DIN - Power Supply 110V AC 50/60Hz – 12 V AC

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 29 di 30
Industrial Electronic Devices

DISCLAIMER

All technical content within this document can be modified without notice. The content of the document content is a recurring audit.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS

WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and human health, which could otherwise be caused by
inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about recycling this
product, please contact your local city office, your household waste disposal service or the shop where you purchased the product.

RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE


The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical
and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE MARKING
The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual Modbus Slave / M-Bus Master
Document code: MN67055_ENG Revision 1.011 Pagina 30 di 30
Industrial Electronic Devices

WARRANTIES AND TECHNICAL SUPPORT:

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]

RETURN POLICY:

If while using your product you have any problem and you wish to exchange or repair it, please do the following:
1) Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to provide detailed information
about the problem.
2) Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be accepted).
If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no longer under warranty,
you will receive a repair estimate.

PRODUCTS AND RELATED DOCUMENTS:

Part Description URL


HD67120 Converter Ethernet to RS232/RS485 www.adfweb.com?product=HD67120
HD67119 Converter USB 2.0 to RS485 Isolated www.adfweb.com?product=HD67119
HD67507 Gateway Modbus TCP Server to RTU Master www.adfweb.com?product=HD67507
HD67510 Gateway Modbus TCP Client to RTU Slave www.adfweb.com?product=HD67510

ADFweb.com Srl – IT31010 – Mareno – Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31