c50 d6 Cummins 50kw

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Specification sheet

Diesel
generator set
50 kW - 60 kW
EPA emissions
stationary Standby

Description
®
Cummins generator sets are fully integrated Cooling system - Standard cooling package
power generation systems providing optimum provides reliable running at up to 50 °C (122 °F)
performance, reliability and versatility for ambient temperature.
stationary Standby applications.
Enclosures - The aesthetically appealing
Features enclosure incorporates special designs that
deliver one of the quietest generators of its kind.
Cummins heavy-duty engine - Rugged Aluminum material plus durable powder coat
4-cycle, liquid-cooled, industrial diesel engine paint provides the best anti-corrosion
delivers reliable power, low emissions and fast performance. The generator set enclosure has
response to load changes. been evaluated to withstand 180 MPH wind
Alternator - Several alternator sizes offer loads in accordance with ASCE7-10. The
intelligent design has removable panels and
selectable motor starting capability with low
service doors to provide easy access for service
reactance 2/3 pitch windings, low waveform
and maintenance.
distortion with non-linear loads and fault clearing
short-circuit capability. Fuel tanks - Two dual wall sub-base fuel tank
Control system - The PowerCommand 1.1
® series are offered as optional features, providing
economical and flexible solutions to meet
electronic control is standard equipment and
extensive code requirements on diesel fuel
provides total generator set system integration
tanks.
including automatic remote starting/stopping,
precise frequency and voltage regulation, alarm NFPA - The generator set accepts full rated load
and status message display, output metering, in a single step in accordance with NFPA 110 for
auto-shutdown at fault detection and NFPA 110 Level 1 systems.
Level 1 compliance.
Warranty and service - Backed by a
comprehensive warranty and worldwide
distributor network.

Standby rating Prime rating Data sheets


60 Hz 60 Hz 60 Hz
Model kW kVA kW kVA
C50 D6 50.0 62.5 45.0 56.25 NAD-5863
C60 D6 60.0 75.0 54.0 67.50 NAD-5864

power.cummins.com
©2017 Cummins Inc. | NAS-5873-EN (10/17)
Generator set specifications
Governor regulation class TBC
Voltage regulation, no load to full load ± 1.0%
Random voltage variation ± 1.0%
Frequency regulation Isochronous
Random frequency variation TBD
Radio frequency emissions compliance FCC code Title 47 Part 15 Class B

Engine specifications
Design Turbocharged and charge air-cooled
Bore 95.0 mm (3.74 in.)
Stroke 115.0 mm (4.53 in.)
Displacement 3.26 litres (199 in3)
Cylinder block Cast iron, in-line, 4 cylinder
Battery capacity 550 amps at ambient temperature of 0 °F to 32 °F (-18 °C to 0 °C)
Battery charging alternator 50 amps
Starting voltage 12 volt, negative ground
Fuel system Direct injection, number 2 diesel fuel, fuel filter, electric fuel shut off
Fuel filter Single element, 10 micron filtration, spin-on fuel filter with water
separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Spin-on, full flow
Standard cooling system 50 °C (122 °F) ambient cooling system
Rated speed 1800 rpm

Alternator specifications
Design Brushless, 4 pole, drip proof, revolving field
Stator 2/3 pitch
Rotor Direct coupled, flexible disc
Insulation system Class H per NEMA MG1-1.65
Standard temperature rise 120 ºC (248 °F) Standby
Exciter type Torque match (shunt) with PMG as option
Alternator cooling Direct drive centrifugal blower
AC waveform Total Harmonic Distortion (THDV) < 5% no load to full linear load, < 3% for any single harmonic
Telephone Influence Factor (TIF) < 50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) 3%

Available voltages
Single phase 3 phase
 120/240  120/208  120/240 delta  277/480  347/600
Note: Consult factory for other voltages.

Generator set options


Fuel system Control Cooling system
 Basic fuel tanks  AC output analog meters (bargraph)  Shutdown – low coolant level
 Regional fuel tanks  Stop switch – emergency  Warning – low coolant level
Engine  Auxiliary output relays (2)  Extension – coolant drain
 Engine air cleaner – normal or  Auxiliary configurable signal  Coolant heater – 120 V, 1 Ph
heavy duty inputs (8) and relay outputs (8) Exhaust system
 Shut down – low oil pressure Electrical  Exhaust connector - NPT
 Extension – oil drain  Single circuit breaker Generator set application
 120 V 1000 W coolant heater  Dual circuit breakers  Battery rack
Alternator Enclosure  Battery rack, heavy duty
 One size up alternator  Aluminum enclosure sound level 1
 PMG or level 2, with muffler installed,
 Alternator heater, 120 V sandstone or green color
 Open set

power.cummins.com
©2017 Cummins Inc. | NAS-5873-EN (10/17)
Generator set options (continued)
Warranty  Standby, 5 year, 2500 hour, parts
 Base warranty – 2 year, 1000 hour, and labor
Standby  Standby, 3 year, 1500 hour, parts,
 Standby, 3 year, 1500 hour, parts labor and travel
 Standby, 5 year, 2500 hour, parts  Standby, 5 year, 2500 hour, parts,
labor and travel
 Standby, 3 year, 1500 hour, parts
and labor

Note: Some options may not be available on all models - consult factory for availability.

Generator set accessories


 Coolant heater  Battery charger – stand-alone, 12 V
 Extreme cold weather components  Circuit breakers
 HMI211RS in-home display,  Enclosure Sound Level 1 to Sound Level 2
including pre-configured 12” harness upgrade kit
 HMI211 remote display, including  Enclosure paint touch up kit
pre-configured 12” harness  Mufflers – industrial, residential or critical
 HMI220 remote display  Alternator PMG
 Auxiliary output relays (2)  Alternator heater
 Auxiliary configurable signal  Maintenance and service kit
inputs (8) and relay outputs (8)  Engine lift kit
 Annunciator – RS485  Various fuel tanks and accessories
 Remote monitoring device –
PowerCommand 500

Control system PowerCommand 1.1


AC protection
 Over current warning and shutdown
 Over and under voltage shutdown
 Over and under frequency shutdown
 Over excitation (loss of sensing) fault
 Field overload
Engine protection
 Overspeed shutdown
PowerCommand control is an integrated generator set  Low oil pressure warning and shutdown
control system providing voltage regulation, engine protection,
 High coolant temperature warning and shutdown
operator interface and isochronous governing (optional). Major
features include:  Low coolant level warning or shutdown
 Battery monitoring and testing features and smart starting  Low coolant temperature warning
control system.  High, low and weak battery voltage warning
 Standard PCCNet interface to devices such as remote  Fail to start (overcrank) shutdown
annunciator for NFPA 110 applications.  Fail to crank shutdown
 Control boards potted for environmental protection.  Redundant start disconnect
 Control suitable for operation in ambient temperatures from -  Cranking lockout
40 °C to +70 °C (-40 °F to +158 °F) and altitudes to 5000
 Sensor failure indication
meters (13,000 feet).
 Low fuel level warning or shutdown
 Prototype tested; UL, CSA, and CE compliant.
Alternator data
 InPower™ PC-based service tool available for detailed
diagnostics.  Line-to-Line and Line-to-Neutral AC volts
Operator/display panel  3-phase AC current
 Manual off switch  Frequency
 Alpha-numeric display with pushbutton access for viewing  Total kVa
engine and alternator data and providing setup, controls and Engine data
adjustments (English or international symbols)  DC voltage
 LED lamps indicating generator set running, not in auto,  Lube oil pressure
common warning, common shutdown, manual run mode and
 Coolant temperature
remote start
 Engine speed
 Suitable for operation in ambient temperatures from
-40 °C to +70 °C
 Bargraph display (optional)

power.cummins.com
©2017 Cummins Inc. | NAS-5873-EN (10/17)
Other data Options
 Generator set model data  Auxiliary output relays (2)
 Start attempts, starts, running hours  Remote annunciator with (3) configurable inputs and
 Fault history (4) configurable outputs
 RS485 Modbus interface
®  PMG alternator excitation
 Data logging and fault simulation (requires InPower  PowerCommand 500/550 for remote monitoring and alarm
service tool) notification (accessory)
Digital governing (optional)  Auxiliary, configurable signal inputs (8) and configurable
relay outputs (8)
 Integrated digital electronic isochronous governor
 Digital governing
 Temperature dynamic governing
Digital voltage regulation  AC output analog meters (bargraph)
- Color-coded graphical display of:
 Integrated digital electronic voltage regulator
- 3-phase AC voltage
 2-phase Line-to-Line sensing
- 3-phase current
 Configurable torque matching
- Frequency
Control functions
- kVa
 Time delay start and cooldown
 Remote operator panel
 Cycle cranking
 PCCNet interface
 (2) Configurable inputs
 (2) Configurable outputs
 Remote emergency stop
 Automatic Transfer Switch (ATS) control
 Generator set exercise, field adjustable

Ratings definitions
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical load
for the duration of power interruption of a reliable utility
source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel Stop power in
accordance with ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited-Time Running Power
(LTP) is in accordance with ISO 8528.
Prime Power (PRP):
Applicable for supplying power to varying electrical load
for unlimited hours. Prime Power (PRP) is in accordance
with ISO 8528. Ten percent overload capability is
available in accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a constant This outline drawing is for reference only. See respective
electrical load for unlimited hours. Continuous Power model data sheet for specific model outline drawing
(COP) in accordance with ISO 8528, ISO 3046, AS 2789, number.
DIN 6271 and BS 5514.
Do not use for installation design

power.cummins.com
©2017 Cummins Inc. | NAS-5873-EN (10/17)
Dim “A” Dim “B” Dim “C” Set weight* Set weight*
Model mm (in.) mm (in.) mm (in.) dry kg (lbs) wet kg (lbs)
Open set
C50 D6 2224 (87.5) 864 (34) 1121 (44.13) 648 (1434) 669 (1480)
C60 D6 2224 (87.5) 864 (34) 1121 (44.13) 701 (1550) 721 (1596)
Sound attenuated enclosure Level 1
C50 D6 2384 (93.8) 864 (34) 1156 (45.5) 695 (1538) 716 (1584)
C60 D6 2384 (93.8) 864 (34) 1156 (45.5) 748 (1654) 768 (1700)
Sound attenuated enclosure Level 2
C50 D6 2629 (103.5) 864 (34) 1156 (45.5) 714 (1580) 735 (1626)
C60 D6 2629 (103.5) 864 (34) 1156 (45.5) 767 (1696) 787 (1742)

* Weights represent a set with standard features. See outline drawings for weights of other configurations.

Codes and standards


Codes or standards compliance may not be available with all model configurations – consult factory for availability.
This generator set is designed
in facilities certified to ISO 9001 The generator set is available
and manufactured in facilities Listed to UL 2200, Stationary
certified to ISO 9001 or Engine Generator Assemblies.
ISO 9002.
The Prototype Test Support
(PTS) program verifies the
performance integrity of the
Engine certified to U.S. EPA SI
generator set design. Cummins
products bearing the PTS U.S. EPA Stationary Emission Regulation
40 CFR, Part 60.
symbol meet the prototype test
requirements of NFPA 110 for
Level 1 systems.
International The generator set is certified for
All low voltage models are CSA
seismic application in
certified to product class Building accordance with International
4215-01. Code Building Code (IBC) 2012.

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s
electrical system except through an approved device or after building main switch is open.

For more information contact your local Cummins distributor


or visit power.cummins.com

©2017 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
NAS-5873-EN (10/17)

You might also like